WE RESERVE THE RIGHT TO MAKE TECHNICAL CHANGES. 1/3
ST M3200 ENG STA R2 03/17
M3200: PRESSURE SUSTAINING / RELIEF VALVE
Pressure sustaining/relief control valves maintain a constant upstream pressure (valve inlet) by relieving ex-
cess pressure.
SUSTAINING APPLICATION - The valve is installed on a distribution line between two pressure zones. If de-
mand on the lower zone causes a drop in upper zone pressure, the pressure is sustained at a preset mini-
mum. When this occurs the pressure available to the downstream zone is reduced.
RELIEF APPLICATION - The valve is installed to relieve excess pressure from a source. In a typical installa-
tion the valve diverts excess flow/pressure to atmosphere, a storage tank, or back to a pump intake.
ADDITIONAL FEATURES AVAILABLE:
solenoid on-off control function - a remote controller switches the valve on-off;
check function - if outlet pressure rises higher than inlet pressure, backflow is prevented;
reverse flow - the main valve opens fully if outlet pressure is higher than inlet pressure;
low pressure shut-off with manual reset;
two adjustable pressure outlet values - switching can be by manual override, or remote electrical sole-
noid control;
flow rate control;
on-off float device level control;
constant level float control valve;
booster pump control valve with check.
OPERATING PRINCIPLE
WE RESERVE THE RIGHT TO MAKE TECHNICAL CHANGES. 2/3
ST M3200 ENG STA R2 03/17
M3200 CIRCUIT LAYOUT
ITEM DESCRIPTION MATERIAL
1 Main valve GJS400-15 EN1563
2 (a,b) Isolating ball valve Ni-plated Brass
3 Y - Strainer with calibrated orifice 1.4401 EN10088-3 + Brass
4 Monodirectional needle valve 1.4401 EN10088-3 + Brass
5 Pressure relief / sustaining pilot CM200 1.4401 EN10088-3 + Brass
6 Isolating ball valve Ni-plated Brass
7 Position indicator with manual venting cock Brass + Hardened glass
8 Gauge holder with drainage Ni-plated Brass
9 Pressure gauge 1.4301 EN10088-3 + Glycerine
-- Pipe 1.4401 EN10088-3
-- Fittings 1.4401 EN10088-3
-- Pressure unions 1.4401 EN10088-3 + Brass
9
8
7
6
5
4
3
2b
1
2a
WE RESERVE THE RIGHT TO MAKE TECHNICAL CHANGES. 3/3
ST M3200 ENG STA R2 03/17
Critical user
Pressure relief valve to protect upstream hydraulic network.
Pressure sustaining valve suit-able for maintaining a minimum
pressure for a critical user.