52
ABB M101-P/M102-P User’s Guide

M101 PM102 P+Users+Guide

Embed Size (px)

DESCRIPTION

M101 PM102 P+Users+Guide

Citation preview

Page 1: M101 PM102 P+Users+Guide

ABB     M101-P/M102-P User’s Guide

Page 2: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

1

1TNC911115D0202 Edition June 2005

ABB

Table of Contents

1 INTRODUCTION........................................................................................................................... 3

1.1 Objective ...................................................................................................................................... 3

1.2 Related Documentation .............................................................................................................. 3

2 PRODUCT OVERVIEW ................................................................................................................ 3

2.1 Introduction ................................................................................................................................. 3

2.2 M101-P/M102-P’s Structure ........................................................................................................ 3

3 MOUNTING................................................................................................................................... 4

3.1 Mounting of M101-P/M102-P....................................................................................................... 4

4 M101-P/M102-P INTERFACES .................................................................................................... 4

4.1 Terminal Designations ................................................................................................................ 5

4.2 Typical diagram ........................................................................................................................... 9

5 FUNCTIONALITY ....................................................................................................................... 11

5.1 Starter Types.............................................................................................................................. 11

5.2 Protection Function .................................................................................................................. 21

5.3 M101-P/M102-P Function and Supervision ............................................................................. 32

6 M101-P/M102-P COMMUNICATION INTERFACE..................................................................... 38

6.1 Overview .................................................................................................................................... 38

6.2 Profibus Interface wiring .......................................................................................................... 40

6.3 Profibus DP description ........................................................................................................... 40

7 PARAMETERIZATION................................................................................................................ 41

7.1 Overview .................................................................................................................................... 41

7.2 Parameterization via MD2/MD3 ................................................................................................ 41

7.3 Parameterization via PROFIBUS.............................................................................................. 41

7.4 M101-P/M102-P Parameters...................................................................................................... 41

Page 3: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

2

1TNC911115D0202 Edition June 2005

ABB

8 ACCESSORIES .......................................................................................................................... 41

8.1 MD2/MD3 Operator Panel .........................................................................................................41

8.2 Parameterization Software: Mcusetup_P................................................................................ 45

9 APPENDIX A TECHNICAL DATA.......................................................................................... 47

10 APPENDIX B TYPE DESIGNATION...................................................................................... 49

Page 4: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

3

1TNC911115D0202 Edition June 2005

ABB

1 Introduction 1.1 Objective The objective of this users manual is to provide the technical information of M101-P/M102-P. This manual should be studied carefully before installing, parameterizing or operating the motor control unit. It is expected that the user has a basic knowledge of physical and electrical fundamentals, electrical wiring practices and electrical components. This document should be used along with M101-P/M102-P Parameter Description, which provides detailed information about parameters and their applications. 1.2 Related Documentation 1TNC 9111106M0202 M101-P/M102-P Parameter Description M101-P/M102-P 1TNC 9111507M0202 PROFIBUS Protocol Implementation for M101-P/M102-P

2 Product Overview 2.1 Introduction M101-P/M102-P is a motor protection and control device with a fieldbus interface.

M101-P/M102-P is a microprocessor-based device. All motor protection and control functions are implemented with the microprocessor, as well as interlocking functions, the calculation of operating, diagnosis and statistical data and communication.

Standard features simplify maintenance and plant expansion. One M101-P/M102-P is required for every starter unit in the MCC. Motor protection is included for the most common causes of failure to prevent costly shutdowns and rewinds. These include overload, stalled rotor, ground fault and phase failure etc. M101-P/M102-P with Profibus interface makes it possible to network upward with automation level in a high speed and reliable way. The M101-P/M102-P implements a subset of the Profibus-DP communication standard. Any M101-P/M102-P may be interrogated on demand to determine both actual and operating parameters. Fast response time for alarm or trip status makes real time control of a complete process possible. Statistical recording of running hours and number of operations assists with predictive maintenance scheduling. Picture 1 M101-P/M102-P

For AC motor and the operated installation this means:

• Reliable protection • Maximum utilization • Continuous supervision • Flexibility

2.2 M101-P/M102-P’s Structure M101-P/M102-P consists of two parts: Main unit (with current converter unit) Operator Panel MD2/MD3

Notes: This user’s guide isfor M102-P V2.0 only.

Page 5: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

4

1TNC911115D0202 Edition June 2005

ABB

M102-P

MD3

Main unit The Main unit is a unit contains the electronics of the motor control unit. Main unit is fixed to a mounting rail. Current converter unit here is the internal CT fixed onto the Main unit. 6 types of M102-P are designed basing on the 6 different types of CT range. Operator panel MD2/MD3 The Operator panel is the user interface mounted on the front door or drawer. With control buttons, LED, LCD module (MD2 only), MD2/MD3 provides the functions as motor control, supervision and parameterizing. One operator panel is provided for each main unit at request. M101-P/M102-P enclosure material The enclosure of the M101-P/M102-P is made of polycarbonate. Flammability rating of the material is UL 94 V-0 and material is halogen free. Colour of the enclosure is RAL 7012. Note: The details of MD2/MD3 please see the chapter 8 accessories.

3 Mounting 3.1 Mounting of M101-P/M102-P Basic dimension of M101-P/M102-P:

WXHXD=110mmX140mmX75mm Typical Installation of M101-P/M102-P:

DIN rail or installation to horizontal plane Basic dimension of MD2:

WXHXD=88mmX72mmX40mm Mounting dimension of MD2:

WXH=85mmX69mm Basic dimension of MD3:

WXHXD=88mmX50mmX28mm Mounting dimension of MD3:

WXH=84mmX46mm Note: The installation details of M101-P/M102-P and MD2/MD3 please see the related documentation installation manual. Picture 2 M101-P/M102-P in 8E/4 module

4 M101-P/M102-P interfaces M101-P/M102-P has 4 I/O terminal blocks. I/O terminals located at the top of the main unit as shown in the following.

Notes:

Page 6: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

5

1TNC911115D0202 Edition June 2005

ABB

The information of each port is described later. Picture 3 Terminals viewed from top

L

Switch inputs for various functions Thermistor input

Interface for MD2/3

CT inputs (Lead-through)

Profibus ports

Ground CT input

Relay output Ground safety and surge

Voltage input

T

Power supply

4.1 Terminal Designations Table 1 Device terminals

Terminal Block Terminal Number Designation…

Plug/Contacts Remark

X1:1…X1:14 Digital Input X1

X1:15…X1:16 PTC input Cross section 1.5mm2

X2 X2:1…6 Interface for MD2/3 Cable with RJ11 is provided as standard

X3:1…5 Fieldbus for external communication

X3:6,7 RCT input X3

X3:8…13 Voltage Input

Cross section 2.5mm2

X4:1…9 Relay output

X4:10,11 24VDC Supply X4

X4:12 Ground

Cross section 2.5mm2

L1-T1;L2-T2;L3-T3 Let-through Current Measurement Φ10mm hole

Notes:

Page 7: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

6

1TNC911115D0202 Edition June 2005

ABB

4.1.1 Power supply The standard power supply is 24V DC preferably from a UPS. Table 2 Power supply input terminals Terminal No. Name Description X4:11 24VDC Power supply 24VDC + X4:10 GND Power supply 24VDC - 4.1.2 Digital input M101-P has 6 and M102-P has 13 digital inputs of the type 5mA/24VDC. Digital inputs are cyclically read. The contact is detected as closed if the input current is over 2.5mA and open if current is under 0.8mA. There are three programmable inputs included, which can be assigned to a defined function. Table 3 Digital input terminals and pins of M101-P. Terminal No. Name Description X1:1 DI0 Digital Input 0 X1:2 DI1 Digital Input 1 X1:3 DI2 Digital Input 2 X1:4 DI3 Digital Input 3 X1:5 DI4 Digital Input 4 X1:6 DI5 Digital Input 5 X1:7 DI6 Digital Input 6 X1:8 DI7 Digital Input 7 X1:9 DI8 Digital Input 8 X1:10 DI9 Digital Input 9 X1:11 DI10 Digital Input 10 X1:12 DI11 Digital Input 11 X1:13 DI12 Digital Input 12 X1:14 DI_COM Digital Input common terminal (DC24V-) Table 4 Digital input terminals and pins of M102-P. Terminal No. Name Description X1:1 DI0 Digital Input 0 X1:2 DI1 Digital Input 1 X1:3 DI2 Digital Input 2 X1:4 DI3 Digital Input 3 X1:5 DI4 Digital Input 4 X1:6 DI5 Digital Input 5 X1:7 DI6 Digital Input 6 X1:8 DI7 Digital Input 7 X1:9 DI8 Digital Input 8 X1:10 DI9 Digital Input 9 X1:11 DI10 Digital Input 10 X1:12 DI11 Digital Input 11 X1:13 DI12 Digital Input 12 X1:14 DI_COM Digital Input common terminal (DC24V-) Note: 1) If the DIs come from field control, which are far away from the motor control unit, the 24V

system power supply should be isolated from the power supply for DIs to reduce the possibility of system power failure.

Notes:

Page 8: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

7

1TNC911115D0202 Edition June 2005

ABB

Picture 4 Schematic wiring for two power supplies (24VDC)

M101-P/M102-P

2) If all of the DIs are not far away from the motor control unit, the source of power supply for

M101/M102-P and DIs can be the same. Picture 5 Schematic wiring for one power supply (24VDC)

M101-P/M102-P

4.1.3 PTC input (only for M102-P) M102-P can utilize PTC sensor to follow the temperature of motor winding. The measuring principle is to use two identical current generators over a 3-wire Pt transmitter. PTC connector is located on the top of M102-P unit, terminal X1. Note: The M102-P has PTC input only. Table 5 PTC input terminals. Terminal No. Name Description X1:14 PTCA PTC measurement input A X1:15 PTCB PTC measurement input B X1:16 PTCG PTC measurement input G 4.1.4 Fieldbus interface There is a profibus communication interface integrated in M101-P/M102-P. Only RS485 interface is supported.

Notes:

Page 9: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

8

1TNC911115D0202 Edition June 2005

ABB

Table 6 Fieldbus interface terminal . Terminal No. Name Description X3:1 5V Power supply 5V+ for bus terminator X3:2 B RS485 B X3:3 A RS485 A X3:4 GND Power supply 5V-(GND) for bus terminator X3:5 SHIELD Shield For more detail information of wiring, please refer to the relative docs. 4.1.5 Residual current transformer M101-P/M102-P supports earth fault measurement through Residual Current Transformer (RCT). Table 7 Residual current transformer terminals Terminal No. Name Description X3:6 Ioa Residual current transformer input A X3:7 Iob Residual current transformer input B Note: 1. The details of RCT please see the documentation of M101/M102 Ordering Guide.

2. If not used, terminals X3:6 and X3:7 should be shorted to avoid of potential external disturbance.

4.1.6 Voltage measurement (only for M102-P) M102-P continuously measures three phase voltages. The voltage data is used for protection functions and power calculation. Note: The M102-P has voltage input only. Table 8 Voltage input terminals of M102-P only. Terminal No. Name Description X3:9 Vc Phase C voltage input X3:11 Vb Phase B voltage input X3:13 Va Phase A voltage input X3:8 N Neutral line input 4.1.7 Current measurement terminal M101-P/M102-P measures continuously three motor phase currents. The phase current data will be used by the protection functions and is reported to the fieldbus. Phase currents are reported as relative value. Relative value is proportional to the motor nominal current In. Current wires are lead through current sensors from either side of the terminal. Direction can be either L->T or T->L considering that all currents must have the same direction. Motor nominal currents above 63A are not measured directly, but instead intermediate current transformer’s secondary side is connected through M101-P/M102-P current measurement terminal. Note: when one phase system is selected, current is measured only from phase A. 4.1.8 Contactor control output M101-P/M102-P supports several motor starter types. The control of the contactor is performed with internal relays (Output CCA, CCB, CCC) by the microprocessor. Internal relays CCA and CCB are hardwire-interlocked to prevent both contactors being closed at the same time. Note: M101-P has the relays CCA and CCB only. Table 9 Contactor control terminals Terminal No. Name Description M101-P

M102-P

X4:6 CCLI Contactor control voltage input √ √

X4:7 CCA Contactor control A √ √ X4:8 CCB Contactor control B √ √ X4:9 CCC Contactor control C √

Notes: Notes:

Page 10: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

9

1TNC911115D0202 Edition June 2005

ABB

4.1.9 Programmable output M101-P/M102-P has two auxiliary programmable output relays. These two outputs can be assigned any of the functions defined in Clause 5.3.6. Table 10 Programmable output terminals Terminal No. Name Description M101-P M102-P X4:1 GR1_A X4:2 GR1_B X4:3 GR1_C

Programmable relay output 1 (NO+NC) √ √

X4:4 GR2_A X4:5 GR2_B

Programmable relay output 2 (NO) √

Caution: When M102-P is power on, the output status of the programmable relay may be different, it depends on the function definition of the output, refer to 5.3.6 for more detail.

4.1.10 Interface for MD2/MD3 M101-P/M102-P has a RJ11 interface for operator panel MD2/MD3. Table 11 Operator panel interface terminals Terminal No. Name Description X2:1 RS485 B X2:2 RS485 A

Communication ports with operator panel

X2:3 SHIELD X2:4 SHIELD

Shield

X2:5 Vcc X2:6 GND

Power supply for operator panel

4.1.11 Ground terminal Table 12 Ground terminal Terminal No. Name Description X4:12 GROUND Ground safety and surge This is an additional ground terminal provided for dissipating transient signals and surges. This must be connected by a thick wire or braid to the system ground for reliable operation. 4.2 Typical diagram A typical wiring diagram is show below:

Notes:

Page 11: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

10

1TNC911115D0202 Edition June 2005

ABB

Picture 6 Typical wiring diagram for M101-P

MOTOR

X3:13X3:11X3:9X3:8

Internal Connector

X3:6 X3:7

M101-P CT Module

X1:1

X1:2

X1:3

X1:4

X1:5

X1:6

X1:7

X1:8

X1:9

X1:10

X1:11

X1:12

X1:13

X1:14

X1:15

X1:16

X3:1

X3:2

X3:3

X3:4

X3:5

X4:10

X4:11

X4:6

X4:7

X4:8

X4:9

X4:1

X4:2

X4:3

X4:4

X4:5

DC24V

DI2

DI4

DI_COM

NC

NC

5VB

AGNDSHIELD

DC24VGND

CCLICCACCB

NC

GR1_A

NC

Phone jack RJ11 KMN

L1

MCB KML1

L2

L3

PE

to MD2/MD3

Residual CT

RS485

-

+

DI3

DI6

DI10

DI12

DI8

DI11

DI9

DI7

DI5

DI1DI0

NC

GR1_BGR1_C

NC NC NCNC I0A I0B

GROUND X4:12

DC24V+ EXT*

24VGND EXT*

Note: ---------- Internal Connection Line: the shield terminal X3: 5 is connected with the ground terminal

X4: 12 via internal circuit.

Notes:

Page 12: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

11

1TNC911115D0202 Edition June 2005

ABB

Picture 5 Typical wiring diagram for M102-P

MOTOR

X3:13X3:11X3:9X3:8

Internal Connector

X3:6X3:7

M102-P CT Module

X1:1

X1:2

X1:3

X1:4

X1:5

X1:6

X1:7

X1:8

X1:9

X1:10

X1:11

X1:12

X1:13

X1:14

X1:15

X1:16

X3:1

X3:2

X3:3

X3:4

X3:5

X4:10

X4:11

X4:6

X4:7

X4:8

X4:9

X4:1

X4:2

X4:3

X4:4

X4:5

DC24V

DI0DI1

DI2DI3

DI4

DI5

DI6

DI9

DI12

DI_COM

PTCA

PTCB

5VB

A

GNDSHIELD

DC24VGND

CCLICCA

CCB

CCC

GR2_A

Phone jack RJ11

DC24V+ EXT*

KMN

L1

MCB KML1

L2

L3

N

PTC

PE

to MD2/MD3

Residual CT

RS485

-

+

DI7

DI8

DI10

DI11

GR2_B

GR1_AGR1_B

GR1_C

VA VB VCN I0AI0B

GROUND X4:12

24VGND EXT*

Note: ---------- Internal Connection Line: the shield terminal X3: 5 is connected with the ground terminal

X4: 12 via internal circuit.

5 Functionality 5.1 Starter Types The module offers several kinds of motor starting control modes via the control of relay output. It supervises the operating state of the contactor according to the feedback of auxiliary contact. The following starting control modes are offered: Table 13 Starter types supported by M101-P/M102-P

Starter type M101-P M102-P NR-DOL √ √ REV-DOL √ √ NR-DOL/RCU √ √ REV-DOL/RCU √ √ Actuator √ NR-S/D √

Notes: Notes:

Page 13: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

12

1TNC911115D0202 Edition June 2005

ABB

NR-2N √ Autotransformer √ NR_softstater √ REV_softstater √ Feeder √ √ NR_DOL: Non Reversing Direct Online REV_DOL: Reversing Direct Online NR_DOL/RCU: Non Reversing Direct Online with RCU REV_DOL/RCU: Reversing Direct Online with RCU Actuator: Actuator with limit switch input NR_S/D: Non Reversing Star-Delta NR_2N: Two speed driver for Non Reversing starter Autotransformer: Autotransformer starter NR_Softstarter: Non Reversing softstarter control REV_Softstarter: Reversing softstarter control Feeder: Feeder is regarded as a specific starter mode in M101/M102

Starter type is selected with a dedicated parameter to match the wiring for contactor and motor control circuits. 5.1.1 NR-DOL STARTER NR_DOL starter is the basic starter type for driving motor to one direction. When start command has been received from field or local I/O, the contactor control output will be energized and remains this condition until stop command has been received or any protection function activated. Table 14 NR-DOL starter contactor control interface(for M101-P/M102-P)

Name Pin Description

CCLI X4:6 Contactor control voltage input

CCA X4:7 Contactor control A

DI6 (F_Ca) X1:7 Contactor control A feedback *

Note: 1) The necessary Digital Inputs is listed in the description table. 2) *: The definition of the terminal X1 in the above list is only an example.

Picture 8 Control circuit for NR-DOL starter (for M101-P/M102-P)

M101-P/M102-P

5.1.2 NR-DOL STARTER(RCU) RCU (Remote Control Unit) is a starter type where contactors are directly controlled by a special RCU-switch located near the motor. This allows control to the motor even without the M101-P/M102-P.

Notes:

Page 14: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

13

1TNC911115D0202 Edition June 2005

ABB

Table 15 NR-DOL starter contactor control interface (for M101-P/M102-P)

Name Pin Description Remark

CCLI X4:6 Contactor control voltage input

CCA X4:7 Contactor control A

GR1_C X4:3 Programmable relay output Only for M101-P

CCC X4:9 Contactor control C

DI6(F_Ca) X1:7 Contactor control A feedback *

Note: 1) The necessary Digital Inputs is listed in the description table. 2) *: The definition of the terminal X1 in the above list is only an example.

Picture 9 Control circuit for NR-DOL/RCU starter(for M101-P)

M101-P

Picture 10 Control circuit for NR-DOL/RCU starter(for M102-P)

M102-P

Notes: Notes: Notes: Notes: Notes: Notes: Notes: Notes:

Page 15: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

14

1TNC911115D0202 Edition June 2005

ABB

5.1.3 REV-DOL STARTER REV-DOL uses contactor control output A for controlling the contactor which drives motor to direction CW and correspondingly contactor control output B is used for direction CCW. When starting motor to either direction contactor will be energized and is stopped (not energized) by command (fieldbus or local I/O) or active protection function. Table 16 REV-DOL starter contactor control interface (for M101-P/M102-P)

Name Pin Description

CCLI X4:6 Contactor control voltage input

CCA X4:7 Contactor control A

CCB X4:8 Contactor control B

DI6(F_Ca) X1:7 Contactor control A feedback*

DI7(F_Cb) X1:8 Contactor control B feedback*

Note: 1) The necessary Digital Inputs is listed in the description table. 2) *: The definition of the terminal X1 in the above list is only an example.

Picture 11 Control circuit for REV-DOL starter (for M101-P/M102-P)

M101-P/M102-P

5.1.4 REV-DOL/RCU STARTER The functionality of this starter type is according to NR-DOL/RCU starter with support for reversing use of motor. Table 17 REV-DOL starter contactor control interface (for M101-P/M102-P)

Name Pin Description Remark

CCLI X4:6 Contactor control voltage input

CCA X4:7 Contactor control A

CCB X4:8 Contactor control B

GR1_C X4:3 Programmable relay output1 Only for M101-P

CCC X4:9 Contactor control C Only for M102-P

DI6(F_Ca) X1:7 Contactor control A feedback *

DI7(F_Cb) X1:8 Contactor control B feedback *

Note: 1) The necessary Digital Inputs is listed in the description table.

2) *: The definition of the terminal X1 in the above list is only an example.

Notes:

Page 16: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

15

1TNC911115D0202 Edition June 2005

ABB

Picture 12 Control circuit for REV-DOL/RCU starter (for M101-P)

M101-P

Picture 13 Control circuit for REV-DOL/RCU starter (for M102-P)

M102-P

5.1.5 Actuator STARTER (for M102-P only) This starter type is for controlling valves and actuators by using limit switches. Table 18 Actuator starter contactor control interface

Name Pin Description

CCLI X4:6 Contactor control voltage input

CCA X4:7 Contactor control A

CCB X4:8 Contactor control B

Notes:

Page 17: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

16

1TNC911115D0202 Edition June 2005

ABB

DI0 (LIMIT1) X1:1 Limit position switch 1 input *

DI1 (LIMIT2) X1:2 Limit position switch 2 input *

DI9 (Torque) X1:10 Torque switch input *

DI6 (F_Ca) X1:7 Contactor control A feedback *

DI7 (F_Cb) X1:8 Contactor control B feedback *

Note: 1) The necessary Digital Inputs is listed in the description table.

2) *: The definition of the terminal X1 in the above list is only an example. Picture 14 Control circuit for Actuator starter

M102-P

Limit switch causes the motor to be stopped when activated. Event message is sent to the fieldbus according to activated limit switch and additionally start command is allowed only to reverse direction. Torque switch is selectable by parameterization. 5.1.6 NR-SD STARTER (for M102-P only) Motor start current is reduced in star connection to 1/3rd of the current in delta connection, with lower torque during the same time. Start to delta starting sequence is based on the presented control logic picture. The changeover condition is time. The following guideline applied for selecting parameter values Changeover time < Motor startup time Table 19 NR_SD starter contactor control interface

Name Pin Description

CCLI X4:6 Contactor control voltage input

CCA X4:7 Contactor control A

CCB X4:8 Contactor control B

CCC X4:9 Contactor control C

DI6 (F_Ca) X1:7 Contactor control A feedback *

Notes:

Page 18: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

17

1TNC911115D0202 Edition June 2005

ABB

DI7 (F_Cb) X1:8 Contactor control B feedback *

DI8 (F_Cc) X1:9 Contactor control C feedback *

Note: 1) The necessary Digital Inputs is listed in the description table. 2) *: The definition of the terminal X1 in the above list is only an example.

Picture 15 Control circuit for NR-SD starter

M102-P

5.1.7 NR-2N STARTER (for M102-P only) NR-2N/Dahlander uses three contactors control motor rotation speed, The motor contains a three phase winding. Rotation speed can be changed “on the fly” without stop command in between. Current measurement for NR-2N utilizes two external current transformers measuring current from motor main supply. External current transformers can be selected separately for both speeds. Table 20 NR-2N starter contactor control interface

Name Pin Description

CCLI X4:6 Contactor control voltage input

CCA X4:7 Contactor control A

CCB X4:8 Contactor control B

CCC X4:9 Contactor control C

DI6 (F_Ca) X1:7 Contactor control A feedback *

DI7 (F_Cb) X1:8 Contactor control B feedback *

DI8 (F_Cc) X1:9 Contactor control C feedback *

Note: 1) The necessary Digital Inputs is listed in the description table. 2) *: The definition of the terminal X1 in the above list is only an example.

Notes:

Page 19: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

18

1TNC911115D0202 Edition June 2005

ABB

Picture 16 Control circuit for NR_2N starter, Danlander

M102-P

CT for N1CT for N2

Picture 17 Control circuit for NR_2N starter, separate windings

M102-P

CT1 for N1 CT2 for N2

Note: For this starter type, although there is not a contactor controlled by CCC, a feedback of CCC

output is necessary for the internal control sequence, so a DI for F_Cc is needed. 5.1.8 AUTOTRANSFORMER STARTER (for M102-P only) This starter type is used to control autotransformer unit in order to minimize the voltage drop during motor startup. Autotransformer starter with three contactors supports motor starting with reduced voltage thus providing reduced motor startup current. The starting torque will be reduced accordingly. The following guideline applied for selecting parameter values Changeover time < Motor startup time

Notes:

Page 20: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

19

1TNC911115D0202 Edition June 2005

ABB

Table 21 Autotransformer starter contactor control interface

Name Pin Description

CCLI X4:6 Contactor control voltage input

CCA X4:7 Contactor control A

CCB X4:8 Contactor control B

CCC X4:9 Contactor control C

DI6 (F_Ca) X1:7 Contactor control A feedback *

DI7 (F_Cb) X1:8 Contactor control B feedback *

DI8 (F_Cc) X1:9 Contactor control C feedback *

Note: 1) The necessary Digital Inputs is listed in the description table. 2) *: The definition of the terminal X1 in the above list is only an example.

Picture 18 Control circuit for Autotransformer starter

M102-P

5.1.9 NR-SOFTSTARTER (for M102-P only) Softstarter applications are for controlling motor accessory softstarter device. M101-P/M102-P gives start and stop commands to the softstarter unit. The softstarter is set for adjusting motor voltage with it’s own parameters. More information about softstarter can be found from softstarter’s manual. This starter type supports all protection functions during normal “Running” situation. For motor start and stop period some of the protection functions are disabled by these parameters. Table 22 NR_Softstarter starter contactor control interface

Name Pin Description

CCLI X4:6 Contactor control voltage input

CCA X4:7 Contactor control A

DI6 (F_Ca) X1:7 Contactor control A feedback *

Note: 1) The necessary Digital Inputs is listed in the description table. 2) *: The definition of the terminal X1 in the above list is only a example.

Notes:

Page 21: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

20

1TNC911115D0202 Edition June 2005

ABB

Picture 19 Control circuit for NR-softstarter

M102-P

softstarterKA

5.1.10 REV-SOFTSTARTER (for M102-P only) Functionality of this starter type is according to NR-softstarter starter with support for reversing use of motor. Table 23 REV-softstarter starter contactor control interface

Name Pin Description

CCLI X4:6 Contactor control voltage input

CCA X4:7 Contactor control A

CCB X4:8 Contactor control B

CCC X4:9 Contactor control C

DI6 (F_Ca) X1:7 Contactor control A feedback *

DI7 (F_Cb) X1:8 Contactor control B feedback *

Note: 1) The necessary Digital Inputs is listed in the description table. 2) *: The definition of the terminal X1 in the above list is only a example.

Picture 20 Control circuit for REV-Softstarter

softstarter

M102-P

Notes:

Page 22: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

21

1TNC911115D0202 Edition June 2005

ABB

5.1.11 Feeder ‘Feeder’ mode is regarded in M101/M102 as a specific starter type to provide measurement and control functionality. The protection of feeder is not covered in M101/M102 and is normally done by main circuit breaker. The ‘feeder’ mode in M101/M102 is designed to provide a complete intelligent solution in MCC plant where the feeder circuits are usually small but important parts from the whole MCC plant management point of view. Table 24 Feeder control interface Name Pin Description CCLI X4:6 Contactor control voltage input CCA X4:7 Control YC /motor drive in MCCB (2 seconds holding) CCB X4:8 Control YO/motor drive in MCCB (2 seconds holding) DI6 (F_Ca) X1:7 Circuit breaker position aux. feedback *

DI10 (MCCB Trip Input)

X1:11 Circuit breaker trip aux. feedback *

Note: 1) The necessary Digital Inputs is listed in the description table. 2) *: The definition of the terminal X1 in the above list is only a example.

Picture 21 Control circuit for Feeder

M101/102-P

5.2 Protection Function The module provides full protection for motor by supervising three phases voltage, three phases current, earth fault current, PTC sensor, the state of contactors and the state of main switch. Functionality of protection functions is based on the parameters given by user. The operation of separate functions is independent thus protection functions can be active at the same time but the one which indicates the situation first will give a trip for motor. According to the application, all kinds of protection can be enabled, disabled by the upper level system or MCU setup tool, also the protection characteristics can be adjusted. Protection module offers the following protection and supervisory function. Table 25 Protection supported by M101-P/M102-P

Protection type M101-P M102-P Overload protection √ √ Stall protection √ √ Phase failure protection √ √ Unbalance protection √ √ Underload protection √ √ Noload protection √ √ Earth fault protection √ √ PTC protection √ Undervoltage protection √ Start limitation protection √ √

Notes:

Notes:

Page 23: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

22

1TNC911115D0202 Edition June 2005

ABB

5.2.1 Overload protection Thermal overload protection (TOL) protects the motor against overheating. The motor thermal condition is simulated by a calculation. The result of the calculation is stored in a thermal register and can be reported via operator panel or fieldbus interface. Calculation is accomplished in a different motor operation conditions, principle presented below, thermal increase and decrease are simulated by TOL protection function for running and stopped motor. Picture 22 Principle picture of motor thermal simulation

M101-P/M102-P simulates thermal conditions in the motor for all operating modes ( Running or Stopped) . This permits maximum utilization of an installation and assures safe protection of the motor. Thermal overload protection simulation accounts for the temperature rise of both the stator winding and the iron mass of the motor, it gives thorough consideration on the effect of motor overheating due to three phase unbalance during the simulation calculation of motor thermal overload. There are two thermal models supported by M101-P/M102-P: Standard or EEx e. The standard model makes use of parameters Trip class, t6 in thermal overload calculation. The protection of explosion proof three-phase motors with type of protection ‘increased safety’ EEx e is done with two special parameters, the Ia/In ratio ( stall/nominal current ratio ) and Te time. The following diagram offers the characteristic curve of overload protection, in which the character is adjusted by changing t6( trip time for current ILmax=6×In from the cold state). Picture 23 Trip curve from cold condition

The Maximum thermal capacity level is 100%. Maximum level is reached when motor as been running with a current 6xIn at the time t6 starting from the cold state in ambient temp. 40°C.

Notes: Notes:

Page 24: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

23

1TNC911115D0202 Edition June 2005

ABB

Table 26 IEC 60947-4-1 trip class when ambient temp. 40°C, balanced motor current Trip class T6

10A 3-7

10 7-12 20 10-25 30 15-38 In some applications it is beneficial to be able to bypass the TOL protection momentarily because of the process reasons. The lifetime of the motor will be shortened but it will be more costly to stop the process. TOL-bypass is a special command given through the fieldbus. There is a dedicated parameter to enable the execution of this command. TOL-bypass function is available only for TOL standard model, thus it can not be enabled if TOL EEx e model is in use. When thermal level is above parameterised alarm level there is a possibility to send a bypass command to M101-P/M102-P. When bypass function is activated, the thermal image is allowed to rise to 200% level before a trip will occur. If motor is in overload condition, i.e. ILmax > 1,14 x TFLC (Thermal full load current multiplier reduced by motor ambient temperature), the Overload alarm is active to indicate overload, but time to trip is not updated if the thermal capacity level (θ) is not going to rise above 200% (ITOL < √2). If motor is stopped before trip and the thermal capacity decreases below TOL alarm level the bypass functionality is disabled. Bypass command is ignored when running under alarm level. Table 27 TOL protection parameters Function Enable/Disable Setting range 0=Disabled 1=Enabled Default value Enabled Step value 1 Thermal model Setting range 0=Standard model 1=EEX e Default value 0 Step value 1 T6 Setting range 3-40s Default value 6s Step value 1 Ia/In Setting range 1.2-8.0 Default value 5.0 Step value 0.1 Te Setting range 1-250s Default value 5s Step value 1s Cool coe. Setting range 1-10 Default value 4 Step value 1 TOL Alarm Level Setting range 6 0-100% Default value 90% Step value 1% TOL Trip Level Setting range 70-100% Default value 100% Step value 1% TOL Reset Level Setting range 10-60% Default value 50% Step value 1% Trip Reset Mode Setting range 1=.Auto 2=Local 3=Remote 4=Remote&Local Default value 4

Notes:

Page 25: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

24

1TNC911115D0202 Edition June 2005

ABB

Step value 1 TOL bypass Setting range 0=Disabled 1=Enabled Default value Disabled

When Standard thermal model is selected When EEX e thermal model is selected

5.2.2 Stall Protection Stall protection is used to protect the driven mechanical system from jams and excessive overload. Stall protection function uses Imax as the criterion. There are other parameters to be determined as followed. Table 28 Stall protection parameters Function Enable/Disable Setting range 0=Disabled 1=Enabled Default value Disabled Step value 1 Trip Level Setting range 120-800% Default value 400% Step value 1% Trip Delay Setting range 0.0-25.0s Default value 0.5s Step value 0.1s Trip Reset Mode Setting range 2=Local 3=Remote 4=Remote&Local Default value 4 Step value 1 Picture 24 Stall protection

I N

t

I Lmax

Trip Delay

Trip

Startup current Trip Level

Startup Function activated

Stall function activates after motor nominal startup time elapsed. The highest measured phase current (ILmax) is compared against the Trip level. When ILmax remains over the trip level at a time longer than Trip delay, a “Stall trip” alarm is issued and the contactor tripped. 5.2.3 Phase failure protection M101-P/M102-P protects the motor against phase current loss condition. Phase failure protection function uses ILmin/ILmax (the ratio of lowest ILmin and highest measured phase value ILmax ) as the criterion. Function is suppressed by parameters Motor startup time, Number of phases and Softstart ramp time. Table 29 Phase failure parameters Function Enable/Disable Setting range 0=Disabled 1=Enabled 3=Alarm only Default value Disabled Step value 1 Alarm Level

Notes:

Page 26: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

25

1TNC911115D0202 Edition June 2005

ABB

Setting range 10-90% Default value 80% Step value 1% Trip Level Setting range 5-90% Default value 70% Step value 1% Trip Delay Setting range 0-60s Default value 10s Step value 1s Trip Reset Mode Setting range 2=Local 3=Remote 4=Remote&Local Default value 4 Step value 1 Picture 25 Phase failure protection

1. alarm2. start trip delay3. clear trip delay4. start trip delay

5. trip6. trip reset

Alarm level

Trip level

1.

(I LMIN / I LMAX )

t

Trip delay

2. 3. 4. 5. 6.

ILmin/ILmax is compared against the phase failure Alarm level . When ILmin/ILmax decreases below the Alarm level, a “Phase failure alarm” alarm is issued. ILmin/ILmax is compared against the phase failure Trip level. When ILmin/ILmax remains below the Trip level at a time longer the Trip delay, an “Phase failure trip” alarm is issued and the contactor tripped. 5.2.4 Unbalance protection M101-P/M102-P protects the motor against unbalance condition. Unbalance protection function also uses ILmin/ILmax as the criterion. Function is suppressed by parameters Motor startup time, Number of phases and softstart ramp time. Table 30 Unbalance protection parameters Function Enable/Disable Setting range 0=Disabled 1=Enabled 3=Alarm only Default value Disabled Step value 1 Alarm Level Setting range 50-90% Default value 90% Step value 1% Trip Level Setting range 50-90% Default value 85% Step value 1% Trip Delay Setting range 0-60s Default value 10s Step value 1s

Notes:

Page 27: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

26

1TNC911115D0202 Edition June 2005

ABB

Trip Reset Mode Setting range 2=Local 3=Remote 4=Remote&Local Default value 4 Step value 1 Picture 26 Unbalance protection

1. alarm2. start trip delay3. clear trip delay4. start trip delay

5. trip6. trip reset

Alarm level

Trip level

1.

(I LMIN / I LMAX )

t

Trip delay

2. 3. 4. 5. 6.

ILmin/ILmax is compared against the unbalance Alarm level . When ILmin/ILmax decreases below the Alarm level, a “Unbalance alarm” alarm is issued. ILmin/ILmax is compared against the unbalance Trip level. When ILmin/ILmax remain below the Trip level at a time longer the Trip delay, an “Unbalance Trip” alarm is issued and the contactor tripped. 5.2.5 Underload protection M101-P/M102-P protects the motor against underload condition. Underload protection function uses ILmax/In ( the ratio of highest measured phase value ILmax and the rated current of the motor In ) as the criterion. There are other parameters to be determined, such as alarm level, trip level and trip delay. The protection characteristic is as follows: Table 31 Underload protection parameters Function Enable/Disable Setting range 0=Disabled 1=Enabled 3=Alarm only Default value Disabled Step value 1 Alarm Level Setting range 20-90% Default value 30% Step value 1% Trip Level Setting range 5-90% Default value 20% Step value 1% Trip Delay Setting range 0-1800s Default value 10s Step value 1s Trip Reset Mode Setting range 2=Local 3=Remote 4=Remote&Local Default value 4 Step value 1

Notes:

Page 28: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

27

1TNC911115D0202 Edition June 2005

ABB

Picture 27 Underload protection

Alarm level

1. warning2. start trip delay3. clear trip delay4. start trip delay

5. trip6. trip reset

Trip level

1 .

(I Lmax / I n )

t

Trip delay

2 .

3 .

4 .

5 .

6 .

The ILmax/In is compared against the Underload Alarm level. When ILmax/In decreases below the Alarm level an “Underload alarm” alarm is issued. The ILmax/In is compared against the Underload trip level. When ILmax/In remains below the Trip level at a time longer than underload Trip delay, a “ Underload trip” alarm is issued and the contactor tripped. 5.2.6 Noload protection M101-P/M102-P protects the motor against noload condition. Practically noload protection is the same function as underload protection. The function also uses ILmax/In as the criterion. Table 32 Noload protection parameters Function Enable/Disable Setting range 0=Disabled 1=Enabled 3=Alarm only Default value Disabled Step value 1 Alarm Level Setting range 5-50% Default value 20% Step value 1% Trip Level Setting range 5-50% Default value 15% Step value 1% Trip Delay Setting range 0-1800s Default value 5s Step value 1s Trip Reset Mode Setting range 2=Local 3=Remote 4=Remote&Local Default value 4 Step value 1

Notes:

Page 29: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

28

1TNC911115D0202 Edition June 2005

ABB

Picture 28 Noload protection

A larm level

1. w arning2. s tart trip de lay3. c lear trip de lay4. s tart trip de lay

5. trip6. trip reset

Trip level

1 .

(I Lmax / I n )

t

Trip delay

2 .

3 .

4 .

5 .

6 .

The ILmax/In is compared against the Noload Alarm level. When ILmax/In decreases below the Alarm level an “Noload alarm” alarm is issued. The ILmax/In is compared against the Noload trip level. When ILmax/In remains below the Trip level at a time longer than Noload Trip delay, a “ Noload trip” alarm is issued and the contactor tripped. 5.2.7 Earth fault protection M101-P/M102-P protects the motor against the earth fault condition with an additional residual current transforme. The function is suppressed by parameters Motor startup time and Softstart ramp time. Earth fault protection uses parameters as in the following table. Table 33 Earth fault protection parameters Function Enable/Disable Setting range 0=Disabled 1=Enabled 3=Alarm only Default value Disabled Step value 1 Alarm Level

Setting range 100-3000mA (Earth Fault Primary = 1A) 500-15000mA (Earth Fault Primary = 5A)

Default value 500mA Step value 100mA Trip Level

Setting range 100-3000mA (Earth Fault Primary = 1A) 500-15000mA (Earth Fault Primary = 5A)

Default value 800mA Step value 100mA Trip Delay Setting range 0.2-60.0s Default value 10.0s Step value 0.1s Trip Reset Mode Setting range 2=Local 3=Remote 4=Remote&Local Default value 4 Step value 1

Notes:

Page 30: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

29

1TNC911115D0202 Edition June 2005

ABB

Picture 29 Earth fault protection

Trip Delay

Trip Delay

Alarm Level

t

Trip Level

(I0)

Earth Fault Current Alarm

Earth Fault Current TripAlarm

I0 is compared against the earth fault current fault Alarm level. When I0 exceeds above the Alarm level, an “Earth fault alarm” alarm is issued. I0 is compared against the earth fault current Trip level. When I0 remains above the earth fault current Trip level at a time longer than Trip delay, an “Earth fault trip” alarm is issued and the contactor tripped. 5.2.8 PTC protection (only for M102-P) PTC protection protects the motor against too high temperature by using PTC-sensor embedded in the stator winding or the bearings. The measuring principle is the current measurement according the transmitters are supposed to be of the 3-wire type. Thus the circuit is independent of the cable-length limitations and the voltage drop in the cable. Table 34 PTC protection parameters Function Enable/Disable Setting range 0=Disabled 1=Enabled 3=Alarm only Default value Disabled Step value 1 Alarm Level Setting range 1000-10000Ω Default value 1600Ω Step value 1Ω Trip Level Setting range 1000-10000Ω Default value 3600Ω Step value 1Ω Trip Delay Setting range 1-1800s Default value 1s Step value 1s Reset Level Setting range 100-10000Ω Default value 1600Ω Step value 1Ω Trip Reset Mode Setting range 1=Auto 2=Local 3=Remote 4=Remote&Local Default value 4 Step value 1

Notes:

Page 31: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

30

1TNC911115D0202 Edition June 2005

ABB

Picture 30 PTC protection

t

Alarm Level

(Η )

PTC Temperaturealarm

PTC trip

Trip delay

Alarmclear

Trip Level

Reset Level

Trip reset

The resistance of PTC input is compared against the Alarm level. When resistance of PTC input exceeds above the Alarm level, a “PTC alarm” message is issued. The resistance of the PTC input is compared against the Trip level. When resistance of PTC input is above the Trip level “PTC trip” alarm is issued and the contactor tripped. After PTC trip is executed the resistance of PTC input is compared against the PTC reset level. When resistance of PTC input decreases below the reset level, the PTC protection function executes the function parametrised by “PTC Reset Mode”. 5.2.9 Undervoltage protection (only for M102-P) M102-P protects the motor against undervoltage condition as “voltage dip”. The undervoltage protection function uses ULmin as the criterion. There are other parameters to be determined, such as alarm level, trip level and trip delay, reset voltage level. The protection characteristic is as follows: Picture 31 Undervoltage protection

3

The lowest measured main voltage (Ulmin) is compared against the undervoltage alarm level. When Ulmin decreases below the undervoltage alarm level, an “Undervoltage alarm” alarm is issued. The lowest measured main voltage (Ulmin) is compared against the undervoltage Trip level and voltage restore level. When ULmin recovers above undervoltage Restore level before Trip delay expires and motor continues running. If ULmin remains below the restore level at a time longer than Trip delay, “ Undervoltage trip “ is issued and contactor will be opened. Note! If Autorestart function is active, the autoreclose time is treated as the trip delay. The undervoltage trip delay is suppressed. Table 35 Undervoltage protection parameters Function Enable/Disable Setting range 0=Disabled 1=Enabled 3=Alarm only Default value Disabled Step value 1 Alarm Level Setting range 50-100% Default value 80%

Notes:

Page 32: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

31

1TNC911115D0202 Edition June 2005

ABB

Step value 1% Trip Level Setting range 50-100% Default value 65% Step value 1% Trip Delay Setting range 0.2-5.0s Default value 1.0s Step value 0.1s Reset Level Setting range 50-100% Default value 90% Step value 1% Trip Reset Mode Setting range 1=Auto 2=Local 3=Remote 4=Remote&Local Default value 4 Step value 1 5.2.10 Start limitation Start limitation helps to protect the motor and also the process against excess number of starts in a given interval. When the number of starts is reached and the motor is switched off, a new start is prevented. The time interval starts from the first start. After the elapse of the time interval the counter is reset to the pre-set value. The permissible motor starts per hour can be obtained from the manufacturers motor and apparatus data sheet. However, the minimum waiting time between two starts shall be complied. The parameterisation of the protection function can be the number of starts per time interval or the time between two consecutive starts. In the first case the user must wait after the trip for the reset to take place before making a start. The time to reset after start limitation trip is provided to the fieldbus. Independent of this function, the motor is protected by TOL function and a start is possible only if the thermal capacity is below the startup inhibit level. If motor data specifies the number of starts during a certain time span the advantage of this protection function can be taken of supervising the number of starts. On some other cases process may put requirements for the motor start number thus this protection can be employed. Functionality is presented in the following example. The next picture, presents the start limitation protection with 3 starts allowed. 1. Normal situation, after stop command motor can be started normally, “Start 2”. Every start activates an internal timer for the time defined by time interval parameter. The number of active timers are reviewed after every stop command and compared to value of number of starts parameter. Stop command can thus exist during active or elapsed timer. 2. Two timers are still active, thus stop command generates alarm message "Start limitation alarm" and one more start is allowed, “Start 3”. 3. The 3rd start has been executed. A contactor trip and trip message "Start Limitation Trip" alarm will follow when motor is stopped while there are two active timers, here starting from “Start 1”. When start limitation trip is active the time to reset is provided to the fieldbus. 4. Trip can be reset when the first timer from “Start 1” is finished. Motor start is possible when all pending trips are reset. Supervision continues with a new timer from “Start 4”.

Notes:

Page 33: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

32

1TNC911115D0202 Edition June 2005

ABB

Picture 32 Start limitation protection

Table 36 Start limitation parameters Function Enable/Disable Setting range 0=Disable 1=Enable Default value Disabled Step value 1 Time interval Setting range 1-600min Default value 1min Step value 1 Number of starts Setting range 2-10 Default value 2 Step value 1 Trip reset mode Setting range 1=Auto 2=Local 3=Remote 4=Remote&Local Default value 4 Step value 1 5.3 M101-P/M102-P Function and Supervision 5.3.1 Autorestart (only for M102-P) The voltage (Ua) is supervised continuously. It is possible to automatically restart the motor after momentary power loss. Two alternative models of auto restart function are provided in M101-P/M102-P: Standard and enhanced. Note: M101-P has not autorestart function Table 37 Autorestart function parameters Function Enable/Disable Setting range 0=Disabled 1=Enabled Default value Disabled Step value 1 Function mode Setting range 0=standard 1=enhanced Default value 0 Step value 1 Max. autoreclose time Setting range 100-1000ms Default value 200ms Step value 100ms Max. power down time

Notes:

Page 34: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

33

1TNC911115D0202 Edition June 2005

ABB

Setting range 0-1200s Default value 5s Step value 1s Staggered start delay Setting range 0-1200s Default value 5s Step value 1s Auto restart function (standard) In standard mode, the reaction of the auto restart function depends on the length of the voltage dip. The following cases show the different reactions of M101-P/M102-P in different voltage dip situations. Case 1: Voltage dip< autoreclose time Picture 33 Autorestart (Voltage dip< autoreclose time)

If voltage is restored within the autoreclose time, the motor will be restarted immediately. Case 2: autoreclose time<voltage dip< Max. power down time Picture 34 Autorestart (autoreclose time<voltage dip< Max. power down time)

If the supply is restored after the autoreclose time but before the Max power down time, the motor will be restarted after the Staggered start time.

Notes:

Page 35: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

34

1TNC911115D0202 Edition June 2005

ABB

Case 3: Voltage dip> Max. power down time Picture 35 Restart (Voltage dip> Max. power down time)

If the supply remain below the restore level after max power down time, no automatic restart is triggered ,even voltage restores later. Auto restart function (enhanced) If the voltage dip is taken more serious, the enhanced autorestart function can be applied. In the enhanced mode, the reaction of the auto restart function not only depends on the length of the voltage dip, but also the number of voltage dips within a certain time. The following cases show the different reactions of M101-P/M102-P in different voltage dip situations. Case1: Voltage dip< autoreclose time Identical to 6.3.1.1 Case1 Case2: Autoreclose time<voltage dip< Max. power down time Identical to 6.3.1.1 Case2 Csae3: Voltage dip> Max. power down time Identical to 6.3.1.1 Case3 Case4: 2xdip<200ms within 1s Picture 36 Restart (2xdip<200ms within 1s)

If the interval between two voltage dipping (which length less than 200ms) is less than 1 second. Automatic delay restart is triggered after second voltage restore.

Notes:

Page 36: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

35

1TNC911115D0202 Edition June 2005

ABB

5.3.2 Number of Starts M101-P/M102-P counts number of start. For each operation cycle M101-P/M102-P updates the number of operating cycle in memory map. When start number alarm level is exceeded, M101-P/M102-P issues an alarm. 5.3.3 Motor running time M101-P/M102-P counts motors running hours. When the limit of running hours is reached, M101-P/M102-P will issue a “ running time” alarm. 5.3.4 M101-P/M102-P control authority 5.3.4.1 Terminology Motor control in this context means entering the normal motor control commands, such as motor start and stop, to the M101-P/M102-P. Functions such as internal or external tripping are not considered as normal motor control commands and are therefore left outside this definition. Motor can control by the digital inputs of the M101-P/M102-P (The function of DIs should be set as PLC control, Start1, Start2, Stop etc.). Control command comes from digital inputs (X1 terminals) called local control. Motor control can also be performed by other fieldbus network devices (DCS), which transit motor control commands to the M101-P/M102-P via fieldbus network. Control performed by other network devices via fieldbus can be called remote control. Operator panel (MD) or HMI(reserved) can be a option for motor control. 5.3.4.2 Local/Remote control switching Switching the motor control from remote to local and vice versa can be done by using the binary-I/O connected remote/local switch in the local control panel/switchgear control panel. This switch has the highest priority in the remote/local switching. If a digital input is assigned for the function of Loc/R, that means the Local/Remote function is enabled. The status of the Loc/R input will manipulate the control authority. 5.3.4.3 Control authority The control commands can be authorized by the Loc/R input and parameterization. When the function of Loc/R is assigned to a digital input in the parameters. The default control mode as follows.

Control Authority Loc/R input

Local Remote(Fieldbus) Operator panel MD HMI 0 (open input) Disabled Enabled Enabled Disabled(reserved)

1 (close input) Enabled Disabled Enabled Disabled(reserved)

When none of digital inputs is defined as Loc/R input, the function of Local/Remote is disabled, control commands can only be authorized via parameterisation. The default control mode as follows.

Control Authority Loc/R input

Local Remote(Fieldbus) Operator panel MD HMI

No Definition Disabled Disabled Enabled Disabled

Note: The blue-shaded fields can be set to either Enabled or Diabled via parameterisation, but for Profibus DPV0, it is only change the control authority via parameterisation kit. 5.3.5 Digital inputs There are thirteen separate programmable digital inputs( DIs) in M101-P/M102-P. These digital inputs can be assigned any of the functions listed below.

• NOP Not special operation for the digital input, only for the check of digital input status. • Start1 The input is used to control motor to start via hardwire. Motor can be running CW/N1 via Start1. • Start2 The input is used to control motor to start via hardwire. Motor can be running CCW/N2 via Start2. • Stop The input is used to control motor to stop via hardwire.

Notes: Notes:

Page 37: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

36

1TNC911115D0202 Edition June 2005

ABB

• Limit1 That is limit position switch1 input. • Limit2 That is limit position switch2 input. • Process interlock1 The process interlock1 function is used to provide time dependent trip/alarm/stop features based on a switch input. This function is used together with OPERATION DELAY and OPERATION parameters. The parameter of OPERATION DELAY sets the amount of time that the Process interlock1 switch can remain close on the occurrence of a motor start. If the switch remains unhealthy for longer than this time, a trip/stop will occur. If the parameter of OPERATION DELAY is set to 0, that the process interlock1 switch must be healthy for M101-P/M102-P to start the motor. OPERATION: this parameter determines whether process interlock1 feature is a trip( reset required in order to restart the motor), a stop (no reset required) or an alarm. Picture 37 Process Interlock1

Note: 1) When t1>t2, motor can run normally; when t1<t2, a trip or stop will be performed

according to the predefined operation. 2) When the operation delay is set to 0, if the process interlock1 is inactive, motor start will

not be allowed. 3) When Trip occurs, it can be reset only via MD2 or fieldbus.

• Process interlock2 The process interlock2 function is used to provide time dependent trip/alarm/stop features based on a switch input. This function is used together with OPERATION DELAY and OPERATION parameters. The parameter of OPERATION DELAY sets the amount of time that the process interlock2 switch can be remain open on the occurrence of a motor start. If the switch remains healthy for longer than this time, a trip/stop will occur. . If the parameter of OPERATION DELAY is set to 0, that the process interlock2 switch must be unhealthy for M101-P/M102-P to start the motor. OPERATION: this parameter determines whether process interlock feature is a trip( reset required in order to restart the motor), a stop (no reset required) or an alarm.

Notes:

Page 38: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

37

1TNC911115D0202 Edition June 2005

ABB

Picture 38 Process Interlock2

Note: 1) When t1>t2, motor can run normally; when t1<t2, a trip or stop will be performed

according to the predefined operation. 2) When the operation delay is set to 0, if the process interlock2 is active, motor start will

not be allowed. 3) When Trip occurs, it can be reset only via MD2 or fieldbus.

• Test switch input The input is used to indicate whether the main switch is in the test –position. While in test position, M101-P/M102-P monitors the I/O statuses and phase voltages/currents. Contactor operations by M101-P/M102-P are allowed but all protection functions based on the current and voltage measurement are disabled and the test of control circuit is allowed. • Emergency stop The input is used for the emergency stop device. When the input is active, the motor will be stopped and cannot restarted until the input is inactive. • PLC contact The input is used for the PLC contact input. When the PLC contact closes, the motor runs. When the contact opens, the motor stops. This input is only suitable for no-reversing starter. • Trip reset The input is used to reset a trip. • Reserved That is null. • Torque switch The input is used to check the status of torque switch used for Actuator Starter. When the input is different from normal state, M101-P/M102-P will release all contactor control relays to stop the motor. • F_CA That is contactor control A feedback. • F_CB That is contactor control B feedback. • F_CC That is contactor control C feedback. • Loc/R

Notes: Notes:

Page 39: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

38

1TNC911115D0202 Edition June 2005

ABB

That is Local/Remote control switch input. • Main switch status That is auxiliary contact from main switch. It’s used to indicate the status of main switch. • MCCB Trip Input That is feedback contact when the circuit breaker tripped. Only use for the starter type ‘ Feeder’.

5.3.6 Programmable output M101-P has one and M102-P has tow programmable relays output. These outputs can be assigned any of the functions listed below.

• Energize on motor start delay: Provides a delayed energization of relay when motor is started.

• De-energize on motor stop delay: Provides a delayed de-energization of relay when motor is stopped.

• Fieldbus control: The relay can be energized or de-energized via the fieldbus. • DI9 Status: The relay will be energized while the DI9 switch is closed • DI10 Status: The relay will be energized while the DI10 switch is closed • DI11 Status: The relay will be energized while the DI11 switch is closed • Trips: The relay is energized immediately after power on. and keep energized when no

trip. When a trip occurs, it will be de-energized. Then energized after trip reset. • Ground fault trip: The relay is energized immediately after power on when no ground

fault trip occurs. When ground fault trip occurs, it will be de-energized. Then energized after trip reset.

• Overload: The relay is energized immediately after power on when no overload trip occurs. When overload trip occurs, the relay will be de-energized. Resetting M101-P/M102-P will energize the relay.

• Watchdog output: M101-P/M102-P has an internal hardware watchdog supervising the behavior of the microprocessor software. Programmable output can be used as signaling output relay for indicating the status of the unit’s internal watchdog. In case of fault the watchdog activates and the relay is energized.

• Communication failure: The relay is energized immediately after power on when no communication failure occurs. When the failure occurs, the relay will be de-energized.

• RCU Mode (only for M101-P): This definition is assigned to the programmable out when ‘NR DOL/RCU ‘ or REV DOL/RCU is selected as motor starter mode. The relay output serves the same function of ‘ de-energized the contactor coil’ as ‘CCC’ output in M102.

• Local/ remote output (only for M102-P): The relay is energized when the control authority is Remote only .The relay will be de-energized when the control authority is Local and Remote or Local only.

5.3.7 Metering The M101-P/M102-P meters and displays:

• RMS current • RMS voltage (only for M102-P) • Ground fault current • Frequency (only for M102-P) • Power factor (only for M102-P) • Power (only for M102-P) • Energy (only for M102-P)

6 M101-P/M102-P communication interface 6.1 Overview The M101-P/M102-P implements a subset of the PROFIBUS -DP serial communication standard. PROFIBUS is multiple master/multiple slave type of protocol suitable for a multi drop configuration as provided by RS485 hardware. The M101-P/M102-P is always a PROFIBUS-DP slave. They could not be programmed as PROFIBUS-DP masters. Commonly computers or PLCs are acted as masters.

Notes:

Page 40: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

39

1TNC911115D0202 Edition June 2005

ABB

The physical interface used from the M101-P/M102-P is RS485. Via RS485 interfaces all functions are supported, e.g. parameterization, control, supervisions, etc. Both bus network and tree network are supported by M101/M102 profibus installation. Two network types are illustrated as follows,

Illustration A: Bus (line) Network

Notes:

Page 41: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

40

1TNC911115D0202 Edition June 2005

ABB

Illustration B: Tree Network 6.2 Profibus Interface wiring All devices are connected in bus structure or tree structure. In one segment up to 32 nodes can be connected. At the beginning and the end of one segment, the cable is terminated with resistor. The maximum length depends on cable type and baud-rate. Note: For more detail information, please consult with Profibus organization or the manufacturer. 6.3 Profibus DP description PROFIBUS-DP is a distributed I/O system, which enables the master to use a large number of peripheral modules and field devices. The data transfer is mainly cyclic: the master reads the input information from the slaves and sends the output information back to the slaves. The services of the PROFIBUS Data Link Layer (Layer 2) are used by PROFIBUS-DP through Service Access Points (SAPs). Precisely defined functions are assigned to individual SAPs. For further information on Service Access Points, refer to the manual of the PROFIBUS master. The following SAPs are supported by the M101-P/M102-P:

SAP54 - Master-Master function SAP55 - Set or change address SAP56 - Read Input SAP57 - Read output SAP58 - Global Control Command SAP59 - Read Configuration data SAP60 - Read Diagnosis data SAP61 - Initial Parameters SAP62 - Check the configuration data SAP128 - User Data exchange

Note: More details on M101/M102 profibus pls refer to ‘ M101/M102 Profibus Implementation’.

Notes: Notes:

Page 42: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

41

1TNC911115D0202 Edition June 2005

ABB

7 Parameterization 7.1 Overview Parameterization means entering values to M101-P/M102-P parameters. Before integrated in a system, the parameters of communication should be set correctly only via the parameterization interface on operator panel. M101-P/M102-P parameters can be uploaded by and downloaded via the parametering device. 7.2 Parameterization via MD2/MD3 There is a USB-Pin physical interface on MD2 or MD3, which is for parameterization via a laptop. 7.3 Parameterization via PROFIBUS M101-P/M102-P parameters are listed in the PROFIBUS memory map. The user can parameterize M101-P/M102-P by using related SAPs. For detail information, refer to the PROFIBUS Protocol Implementation for M101-P/M102-P document. 7.4 M101-P/M102-P Parameters M101-P/M102-P Parameters are listed together with explanations, possible ranges and default values in the M101-P/M102-P Parameter Description document.

8 Accessories 8.1 MD2/MD3 Operator Panel 8.1.1 Overview You can use the MD2/MD3 operator panel to control a motor from the control-cubicle door or from a drawer. You can use additional pushbutton functions and LED displays as alternatives. There are also more message available on a LCD display unit (MD2 only). The operator panel can be connected to the M101-P/M102-P basic unit via a RS485 communication port ( which physical interface is RJ11 ) . It is supplied with power from the basic unit also via RJ11 interface. The faceplate of operator panel are shown below Picture 39 MD2

Parameterization port

LED

LCD screen

Select START1 START2 STOP

Notes:

Page 43: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

42

1TNC911115D0202 Edition June 2005

ABB

Picture 40 MD3

8.1.2 LED indicator Table 39 LED indicator

LED Indicator LED State Description

light Unit is ready for operation READY

Wink Unit is yet not initialized

START1 light Motor is running CW/N1

START2 light Motor is running CCW/N2

light Fault trip FAULT

Wink Alarm

8.1.3 Buttons Table 40 MD2/3 Buttons

Button Function Remark

To select the message

To Start motor CW/N1

To start motor CCW/N2

To stop motor Also used to reset fault trip

Parameterization Port

LED INDICATOR

START1 START 2 STOP

Notes:

Page 44: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

43

1TNC911115D0202 Edition June 2005

ABB

8.1.4 Actual value display

Ia 1.78A Ib 1.79A Ic 1.77A

This message displays the actual RMS current in eachphase in amps Format: 1.00 at CT primary≤1A 10.0 at CT primary≤50A 100 at CT primary>50A

Ia/In 25% Ib/In 25% Ic/In 25%

This message displays the current as a percentage ofmotor nominal current.

Ua 219V Ub 220V Uc 221V

This message displays L-N voltage. Note: Not available for M101-P

Uab 379V Ubc 380V Uca 381V

This message displays L-L voltage. Note: Not available for M101-P

S 145KVA P 141KW COSØ 0.97

This message displays apparent power, active power andpower factor. Note: Not available for M101-P

Energy used 12345 kWhr

This message displays the total accumulated energy usedsince last cleared. Note: Not available for M101-P

Therm Capacity : 53%

This message displays the thermal memory of the motor.The max thermal capacity is 100%. A thermal capacityvalue equal to Trip level will cause overload trip.

Ground current 0mA

This message displays ground fault current.

Frequency 49.98Hz

This message displays the frequency of power supply.

Notes: Notes:

Page 45: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

44

1TNC911115D0202 Edition June 2005

ABB

8.1.5 Parameterization port The parameterzation port is a USB-pin interface. After communication plug is inserted, the communication between the M101-P/M102-P and operator panel is terminated. The message on LCD shows the parameterization state, and the functions of buttons are invalid.

M101-P/M102-P parameters can be upload and downloaded from the parametering device via the interface. 8.1.6 Connection Operator panel is connected to the X2 terminal on M101-P/M102-P via RJ11 interface. The connection shown below includes power supply and communication.

Parameter setting

Cause of Trip: Overload

This message displays the cause of the current trip. The causeof trip message will override the currently selected defaultmessage. The possible causes of trip are as follows, but cannotbe showed via MD2. Overload Stalled rotor Phase failure Unbalance Underload Noload Earth fault Thermistor Undervoltage Feedback COMM. Failure DI

Cause of Alarm: Overload

Any alarm conditions that are currently active will be display.The cause of alarm message will override the currentlyselected default message. The possible causes of alarm areas follows, but cannot be showed via MD2. OverloadThermal capacity Phase failure Unbalance Underload Noload Earth fault Welded Feedback Fail to stop Fail to start Serial COM Start limitation Start number Running time DIThermistor(only for M102-P) Undervoltage(only for M102-P) Autoreclose (only for M102-P)

Addr. 3 M102-P v2.0 MD v2.0

This message displays network ID, Firmware version of theM101/M102-P and MD2 after pressing the select key for 5seconds.

Notes:

Page 46: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

45

1TNC911115D0202 Edition June 2005

ABB

Picture 41 Connection between M101-P/M102-P and MD2/3

If MD2 can’t get information from M101-P/M102 an alarm message displayed on LCD. 8.2 Parameterization Software: Mcusetup_P Mcusetup_P software is used to set parameter. It exchanges data with M101-P/M102-P via RS485. Picture 42 Parameterization interface

No message

Notes: Notes:

Page 47: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

46

1TNC911115D0202 Edition June 2005

ABB

Picture 43 Mcusetup_P interface

The parameterization software available with following function: Edit parameters Export parameter to a file Import parameter from a file Update M101-P/M102-P’s parameters Download M101-P/M102-P’s parameters Read M101-P/M102-P’s parameters User management The parameterization software can run on all of the following PC operation system: Windows 98, Windows 2000, Windows NT For more information refer to Mcusetup manual.

Notes:

Page 48: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

47

1TNC911115D0202 Edition June 2005

ABB

9 Appendix A Technical Data Technical data Main circuit Rated operation voltage (Ue) 230/400V or 400/690V Rated insulation voltage (Ui) 400V or 690V Rated impulse withstand voltage (Uimp) 4kV or 6kV

Rated operation current (Ie) 0.5-1A 1-2.5A 2.5-5A 5-12.5A 12.5-30A 30-63A

Rated frequency 50/60Hz Control circuit Rated operational voltage (Ue) 24V DC or 230 VAC Rated insulation voltage (Ui) 250V Rate impulse withstand voltage (Uimp) 4 kV Rated operational current (Ie)

2A (DC-13) Contactor Control relay output 2A (AC-15) 2A (DC-13) Programmable relay output 2A (AC-15)

Rated frequency 50/60 Hz DC Power supply Rated operational voltage (Ue) 24VDC Voltage operation range 85%-110% Ue DC Power consumption Typical 4.5W Maxium 8W Digital input Number of digital input 6(M101-P) / 13(M102-P) Close contact current (peak) 2.5…5mA Open contactor current (peak) 0…0.8mA Filedbus interface Protocol PROFIBUS-DP Baud-rate 9.6kbps/19.2kbps/45.45kbps/93.75Kbps/

187.5Kbps/500Kbps/1.5Mbps Fieldbus capacity 32 nodes each segment Environmental conditions Ambient temperature range Storage -25-+85oC Normal operation -5-+60oC Metering accuracy

Range: 0.1-8 ×phase CT primary amps Phase current Accuracy: ±2% Full scale: 1.2 × RCT nominal current Earth fault current Accuracy: ±2% RCT primary Voltage input rating: 110V-250V Full scale: 1.2 ×VT Primary Phase voltage (only for M102-P) Accuracy: ± 2% of VT primary or ± 2% of reading, which is greater

Power (only for M102-P) Accuracy: ± 5% nominal or ± 5% reading, whichever is greater Sensor type: positive temperature coefficient PTC RHOT=100-10,000 Ω

Thermistor Input (only for M102-P)

Accuracy: ±5% or 100Ω which is greater

Notes:

Notes:

Page 49: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

48

1TNC911115D0202 Edition June 2005

ABB

Standards Low voltage switchgears IEC60947-1 Low voltage switchgear and controlgear” Part1:

General rules IEC60947-4-1 Low voltage switchgear and controlgear” Part4:

Contactors and motor-starters, Section one-Electromechanical contactors and motor-starters

EMC Electrostatic discharge IEC61000-4-2, Level 3 Electromagnetic field immunity IEC61000-4-3, Level 3 Fast transient/burst immunity IEC61000-4-4, Level 4 Surge immunity IEC61000-4-5, Level 3 Conducted disturbance immunity IEC61000-4-6, Level 2 Radiated disturbance EN55011, Class A

Notes:

Page 50: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

49

1TNC911115D0202 Edition June 2005

ABB

10 Appendix B Type Designation

Type designation Functionality In Order number

M101-P 0.5-1.0 Motor control unit 0.5-1.0A 1TNA911004R0831

M101-P 1.0-2.5 Motor control unit 1.0-2.5A 1TNA911004R0832

M101-P 2.5-5.0 Motor control unit 2.5-5.0A 1TNA911004R0833

M101-P 5.0-12.5 Motor control unit 5.0-12.5A 1TNA911004R0834

M101-P 12.5-30.0 Motor control unit 12.5-30.0A 1TNA911004R0835

M101-P 30.0-63.0 Motor control unit 30.0-63.0A 1TNA911004R0836

M102-P 0.5-1.0 Motor control unit 0.5-1.0A 1TNA911004R0911

M102-P 1.0-2.5 Motor control unit 1.0-2.5A 1TNA911004R0912

M102-P 2.5-5.0 Motor control unit 2.5-5.0A 1TNA911004R0913

M102-P 5.0-12.5 Motor control unit 5.0-12.5A 1TNA911004R0914

M102-P 12.5-30.0 Motor control unit 12.5-30.0A 1TNA911004R0915

M102-P 30.0-63.0 Motor control unit 30.0-63.0A 1TNA911004R0916

M101-P 0.5-1.0 with MD2

Including: M101-P 0.5-1.0 (1TNA911004R0831) MD2 (1TNA911004R0802) Cable set internal (1TNA911005R2101)

0.5-1.0A 1TNA911004R2831

M101-P 1.0-2.5 with MD2

Including: M101-P 1.0-2.5 (1TNA911004R0832) MD2 (1TNA911004R0802) Cable set internal (1TNA911005R2101)

1.0-2.5A 1TNA911004R2832

M101-P 2.5-5.0 with MD2

Including: M101-P 2.5-5.0 (1TNA911004R0833) MD2 (1TNA911004R0802) Cable set internal (1TNA911005R2101)

2.5-5.0A 1TNA911004R2833

M101-P 5.0-12.5 with MD2

Including: M101-P 5.0-12.5 (1TNA911004R0834) MD2 (1TNA911004R0802) Cable set internal (1TNA911005R2101)

5.0-12.5A 1TNA911004R2834

M101-P 12.5-30.0 with MD2

Including: M101-P 12.5-30.0 (1TNA911004R0835) MD2 (1TNA911004R0802) Cable set internal (1TNA911005R2101)

12.5-30.0A 1TNA911004R2835

M101-P 30.0-63.0 with MD2

Including: M101-P 30.0-63.0 (1TNA911004R0836) MD2 (1TNA911004R0802) Cable set internal (1TNA911005R2101)

30.0-63.0A 1TNA911004R2836

Notes:

Page 51: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

50

1TNC911115D0202 Edition June 2005

ABB

M102-P 0.5-1.0 with MD2

Including: M102-P 0.5-1.0 (1TNA911004R0911) MD2 (1TNA911004R0802) Cable set internal (1TNA911005R2101)

0.5-1.0A 1TNA911004R2911

M102-P 1.0-2.5 with MD2

Including: M102-P 1.0-2.5 (1TNA911004R0912) MD2 (1TNA911004R0802) Cable set internal (1TNA911005R2101)

1.0-2.5A 1TNA911004R2912

M102-P 2.5-5.0 with MD2

Including: M102-P 2.5-5.0 (1TNA911004R0913) MD2 (1TNA911004R0802) Cable set internal (1TNA911005R2101)

2.5-5.0A 1TNA911004R2913

M102-P 5.0-12.5 with MD2

Including: M102-P 5.0-12.5 (1TNA911004R0914) MD2 (1TNA911004R0802) Cable set internal (1TNA911005R2101)

5.0-12.5A 1TNA911004R2914

M102-P 12.5-30.0 with MD2

Including: M102-P 12.5-30.0 (1TNA911004R0915) MD2 (1TNA911004R0802) Cable set internal (1TNA911005R2101)

12.5-30.0A 1TNA911004R2915

M102-P 30.0-63.0 with MD2

Including: M102-P 30.0-63.0 (1TNA911004R0916) MD2 (1TNA911004R0802) Cable set internal (1TNA911005R2101)

30.0-63.0A 1TNA911004R2916

M101-P 0.5-1.0 with MD3

Including: M101-P 0.5-1.0 (1TNA911004R0831) MD3 (1TNA911004R0803) Cable set internal (1TNA911005R2101)

0.5-1.0A 1TNA911004R3831

M101-P 1.0-2.5 with MD3

Including: M101-P 1.0-2.5 (1TNA911004R0832) MD3 (1TNA911004R0803) Cable set internal (1TNA911005R2101)

1.0-2.5A 1TNA911004R3832

M101-P 2.5-5.0 with MD3

Including: M101-P 2.5-5.0 (1TNA911004R0833) MD3 (1TNA911004R0803) Cable set internal (1TNA911005R2101)

2.5-5.0A 1TNA911004R3833

M101-P 5.0-12.5 with MD3

Including: M101-P 5.0-12.5 (1TNA911004R0834) MD3 (1TNA911004R0803) Cable set internal (1TNA911005R2101)

5.0-12.5A 1TNA911004R3834

M101-P 12.5-30.0 with MD3

Including: M101-P 12.5-30.0 (1TNA911004R0835) MD3 (1TNA911004R0803) Cable set internal (1TNA911005R2101)

12.5-30.0A 1TNA911004R3835

M101-P 30.0-63.0 with MD3

Including: M101-P 30.0-63.0 (1TNA911004R0836) MD3 (1TNA911004R0803) Cable set internal (1TNA911005R2101)

30.0-63.0A 1TNA911004R3836

M102-P 0.5-1.0 with MD3

Including: M102-P 0.5-1.0 (1TNA911004R0911) MD3 (1TNA911004R0803) Cable set internal (1TNA911005R2101)

0.5-1.0A 1TNA911004R3911

Notes:

Page 52: M101 PM102 P+Users+Guide

M101-P/M102-P User’s Guide

51

1TNC911115D0202 Edition June 2005

ABB

M102-P 1.0-2.5 with MD3

Including: M102-P 1.0-2.5 (1TNA911004R0912) MD3 (1TNA911004R0803) Cable set internal (1TNA911005R2101)

1.0-2.5A 1TNA911004R3912

M102-P 2.5-5.0 with MD3

Including: M102-P 2.5-5.0 (1TNA911004R0913) MD3 (1TNA911004R0803) Cable set internal (1TNA911005R2101)

2.5-5.0A 1TNA911004R3913

M102-P 5.0-12.5 with MD3

Including: M102-P 5.0-12.5 (1TNA911004R0914) MD3 (1TNA911004R0803) Cable set internal (1TNA911005R2101)

5.0-12.5A 1TNA911004R3914

M102-P 12.5-30.0 with MD3

Including: M102-P 12.5-30.0 (1TNA911004R0915) MD3 (1TNA911004R0803) Cable set internal (1TNA911005R2101)

12.5-30.0A 1TNA911004R3915

M102-P 30.0-63.0 with MD3

Including: M102-P 30.0-63.0 (1TNA911004R0916) MD3 (1TNA911004R0803) Cable set internal (1TNA911005R2101)

30.0-63.0A 1TNA911004R3916

MD2 Operator panel - 1TNA911004R0802

MD3 Operator panel - 1TNA911004R0803

Mcusetup-P Software 1TNA911001R0801

Cable set internal 1TNA911005R2101

Cable set parametering 1TNA911005R2102

Notes: