SERVING Industry SINCE 1923 And Our Partnership Team providing Inspection , Testing , & Repair of Generators, Turbines, & Stators

Luse Coils Generator & Turbine Repair Serices

Embed Size (px)

Citation preview

Page 1: Luse Coils Generator & Turbine Repair Serices

SERVING Industry SINCE 1923

And Our Partnership Team providing Inspection ,

Testing , & Repair of Generators, Turbines, & Stators

Page 2: Luse Coils Generator & Turbine Repair Serices

Generator Testing & Inspection

Page 3: Luse Coils Generator & Turbine Repair Serices

Generator Services

• Field Services

• Stator Services

• Testing & Inspections

• Hydraulic Integrity Test (HIT)

• Liquid-Cooled Clip Repairs

• High Voltage Bushings

• Reverse Engineering

Page 4: Luse Coils Generator & Turbine Repair Serices

Generator Field Services

Turnkey Rewinds

Technical Direction

Retaining Ring Change Outs Using Induction

Heating

Retaining Ring Machining & Insulation

Repairs of Elongation, Foreshortening & Top

Turn Isolation

Main Lead Manufacturing

Containment Facilities & Asbestos Abatement

Copper Dust Inspections

Bore Copper Inspection & Replacement

NDE of Wedges, Forging & Rings

Hydrogen Seal Inspection

Turnkey Collector Ring Services

Painting of Forgings

Application of Tagging Compounds

Turnkey Transportation

Page 5: Luse Coils Generator & Turbine Repair Serices

Generator Stator Services

Conventional and Liquid-Cooled Rewinds

Turnkey Disassembly & Assembly

New Stator Bars, Including Liquid-Cooled

Project Management & Technical Direction

Bar Insulation Repair

Repair of core iron

End Winding Redesign & Installation

Re-Wedging & Upgrades, Including TIL-

1197

Tagging Compounds for Core Monitoring

Installation of Flux Probes, Buss & Slot

Couplers

Installation of New RTDs

Page 6: Luse Coils Generator & Turbine Repair Serices

Electrical Testing & Inspection Services

AC & DC Hi Potential Test

AC Impedance Tests

Digital ELCID

Meggar

Boroscopic Inspections

Pole Balance Drop

Calculation of Polarity Indexes

DC Leakage

Wedge Surveys and Mapping

Resistance Testing of RTDs

Visual Inspections

Capacitance Mapping

Retaining Ring Inspections

Page 7: Luse Coils Generator & Turbine Repair Serices

H.I.T. Skids / Flush & Bake Skids

For Liquid Cooled Generators

Five Skids

Tools to Address TIL 1098

Fast Dry Out of Cooling System for

Elec. Testing

Prep For Vacuum & Pressure Decay

Tests

Flush & Bake Skids:

Flush Stator Cooling System & Bars

After Rewind

Cures Epoxies & Conforming

Materials

Reduces Bake Cycle Significantly

Page 8: Luse Coils Generator & Turbine Repair Serices

High Voltage Bushing Refurbishment

New or Refurbished High Voltage

Bushings :

Re-manufacture & rebuild nearly all

models

Refurbishment cost much less than new

bushings

Provides an opportunity to upgrade

bushing components

Faster turn-around than waiting for new

bushings

We maintain a finished inventory of

common bushings

Porcelain or composite insulators

Complete electrical testing

Turnkey installation

Page 9: Luse Coils Generator & Turbine Repair Serices

Rotor Testing & Inspection

Page 10: Luse Coils Generator & Turbine Repair Serices

Components of a Field

Collector Rings

Journal

Fan Ring

Retaining Ring

Body

Slot

Blocking

Coils

Coupling

Page 11: Luse Coils Generator & Turbine Repair Serices

Components of a Field Slot

Wedge

Creepage

Turns

Turn Insulation

Slot Armor

Sub Slot Armor

Page 12: Luse Coils Generator & Turbine Repair Serices

Typical Electrical Field Test on a Generator Rotor

Megohm Test (megger)

Winding Resistance Test

AC Impedance Test

Pole Balance Test

Visual Inspections

Page 13: Luse Coils Generator & Turbine Repair Serices

Field Testing

Megohm Test (megger)

Checks Ground Wall Insulation

Slot Liners

Creepage Blocks and Slot Bottom Covers

Retaining Ring Insulation

Terminal Stud Insulation

Bore Copper Tube

Collector Ring Sleeves

Page 14: Luse Coils Generator & Turbine Repair Serices

Field Winding Resistance Test

Measurement is converted to standard temperature specific to the

manufacturer

Page 15: Luse Coils Generator & Turbine Repair Serices

Field Winding Resistance Test

Typical Issues to Identify

Lower than Normal Resistance Means

Turn

to Turn Shorting is Present

Higher than Normal Resistance Could

Mean

a Few Different Things:

Cracked Conductor

Elongated Conductors

Bad Connection

Page 16: Luse Coils Generator & Turbine Repair Serices

Field Testing

AC Impedance Test

Checks for Turn to Turn Shorting

Rotor Acts as an Inductor when

Passing AC

Current Through the Windings

The Current Flow is “Choked” or

Restricted by

the Number of Turns Around the Iron

Core

(Rotor Body)

Page 17: Luse Coils Generator & Turbine Repair Serices

AC Impedance Test Set

Voltage is raised in 10V steps and current is measured at

each step.

Also, Impedance (Ohms) is calculated

Page 18: Luse Coils Generator & Turbine Repair Serices

Pole Balance Test

Only Performed if Access is Available to

the Pole to Pole Connector (or Very Close

By)

Usually Performed with AC

Voltage Applied as High as Practical--

Usually 100V

Voltage is Measured from Inboard Collector

Ring to the Pole Jumper and then from the

Field Testing

Page 19: Luse Coils Generator & Turbine Repair Serices

Field During Rewind

Page 20: Luse Coils Generator & Turbine Repair Serices

Bore Copper Assembly

Page 21: Luse Coils Generator & Turbine Repair Serices

Stator Testing

Page 22: Luse Coils Generator & Turbine Repair Serices

Stator (Armature) Testing

Winding Resistance Test

Megohm Test (megger)

DC Leakage Test

DC Hipot

RTD Resistance Test

RTD Megger Test

Page 23: Luse Coils Generator & Turbine Repair Serices

Winding Resistance Test

oMeasured with a Digital Low Resistance

Ohm

Meter (DLRO)

• Also Known as a “Bridge”, “Ductor”,

“Micro Ohm Meter”

Regardless of Name, All are a 4 Wire Kelvin

Bridge Device

Stator Field Testing

Page 24: Luse Coils Generator & Turbine Repair Serices

Stator Field Testing

Megohm Test (megger)

Checks Ground Wall Insulation

Taped Insulation on Bars/Coils

Porcelain or Epoxy Insulation on

Terminal and Stand-off Bushings

Hoses on Water or Oil Cooled

Machines

Page 25: Luse Coils Generator & Turbine Repair Serices

Stator Field Testing

Megohm Test (megger)

Usually Performed at 2500 V or 5000 V

for 10 Minutes

All Megger Tests are DC

Achieve a Final Megohm Reading and

Polarization Index (PI)

PI = R10 / R1

Page 26: Luse Coils Generator & Turbine Repair Serices

Stator Field Testing

Megohm Test (megger)

Reduced Creepage Paths (Distance to

Ground) Can Lead to Low Megohm

Readings

Dirty or Contaminated

Bushings/Terminals

Insulation Migration (Big Problem in

Certain Asphalt-Mica Machines)

Page 27: Luse Coils Generator & Turbine Repair Serices

Stator Field Testing

AEMC Electronic

Megohm Meter

Page 28: Luse Coils Generator & Turbine Repair Serices

Stator Field Testing

DC Leakage Test

A High Voltage Test of the Stator

Windings Used to Gain Quantitative

and Historical Data as to the

Condition of the Insulation

DC Tests in General are Sensitive

Indicators of the Presence of

Cracks, Fissures, Reduced

Creepage Paths, Moisture and Dirt

Page 29: Luse Coils Generator & Turbine Repair Serices

Stator Field Testing

DC Leakage Test

Consists of a Series of Insulation

Resistance Measurements Taken at

Increasing Voltage Steps on a

Scheduled Time Basis

A 10 Minute Preliminary Di-electric

Absorption Test Determines the

Absorption Ratio of the Insulation

(N number)

Page 30: Luse Coils Generator & Turbine Repair Serices

Stator Field Testing

DC Leakage

Test Underway

Page 31: Luse Coils Generator & Turbine Repair Serices

Stator Field Testing

DC Leakage Test

Sphere-Gap Voltmeter Is Used to

Verify Voltmeter and for Overvoltage

Protection

Sphere-Gap Voltmeter (Spheres) Are

Set to Arc Over at 10 to 15% Higher

Than Max Test Voltage

Set High Enough So That It Does Not

Add Significant Leakage Current

Page 32: Luse Coils Generator & Turbine Repair Serices

Stator Field Testing

80 KV DC Hipot, Isolation

Transformer and Sphere-Gap

Voltmeter

Page 33: Luse Coils Generator & Turbine Repair Serices

Stator Field Testing

DC High Potential Test (Hipot)

Final Suitability for Service Test

Substitute for AC Test, Which

Requires a Large and Expensive Piece

of Equipment

May or May Not Be Required by

Insurance Company

Page 34: Luse Coils Generator & Turbine Repair Serices

Stator Field Testing

DC High Potential Test (Hipot)

Often Times Is Performed as the

Last Step of a DC Leakage Test

Leakage Value Is Not Important

Since Extraneous Leakage Currents

Can Be Very High

Surface Tracking

Ionization of Air Near Terminals

Page 35: Luse Coils Generator & Turbine Repair Serices

Stator Field Testing

RTD Testing

Resistance Test

Resistance Is Measured

Between Each Leg (wire)

Excel Spread Sheets Calculates

Temperature

Checked to Insure That All

RTDs are Functional

Page 36: Luse Coils Generator & Turbine Repair Serices

Stator Field Testing

RTD Testing

Megger Test (Slot RTDs Only)

Resistance to Ground Is

Measured at 500 Volts

Checked to Insure That

RTDs are Not Capable of

Creating Circulating

Currents Which Could

Result In Localized Heating

and Back Feeds into the

Meters

Page 37: Luse Coils Generator & Turbine Repair Serices

Stator Photos

End Windings

and Core on

Large Water

Cooled

Generator

Page 38: Luse Coils Generator & Turbine Repair Serices

Stator Photos

Stand-Off

Insulator

Page 39: Luse Coils Generator & Turbine Repair Serices

Stator Photos

PTFE Hoses

on Water

Cooled Stator

Page 40: Luse Coils Generator & Turbine Repair Serices

Stator Photos

Tape

Separation on

Asphalt-Mica

Bar

Page 41: Luse Coils Generator & Turbine Repair Serices

Stator Photos

Typical GE RTD

Panel

Page 42: Luse Coils Generator & Turbine Repair Serices

Turbine-Generator Repair Facility

• 170, 000 Square Feet

• 90 Ton Crane Capacity

• Dedicated Blast Cleaning

• High Speed Balance Facility

(late 2013)

Page 43: Luse Coils Generator & Turbine Repair Serices

Reverse Engineering: Addressing Critical Needs

Page 44: Luse Coils Generator & Turbine Repair Serices

Reverse Engineering: Addressing Critical Needs

Focused on Stator Components (Free)

We Come to You

Experienced Staff

State-of-the-Art Equipment

Supported by In-house CAD & Engineering

Digital Material Composition Analysis

Quick Turn Around

Page 45: Luse Coils Generator & Turbine Repair Serices

THANK YOU FOR YOUR TIME !

Page 46: Luse Coils Generator & Turbine Repair Serices

QUESTIONS ?

Page 47: Luse Coils Generator & Turbine Repair Serices

YOUR INFORMATION REQUESTS RECEIVE OUR HIGHEST PRIORITY

Jim Ford

630.240.6381

[email protected]

John Provencher

708.363.3838

[email protected]