3

Click here to load reader

Luna 36,000 Single Wall Mount Submittal Data Sheet

Embed Size (px)

DESCRIPTION

Luna 36,000 BTUH

Citation preview

Page 1: Luna 36,000 Single Wall Mount Submittal Data Sheet

Submittal Data Sheet

Luna MSC-36HRDN1-MN5W / MOJ-36HDN1-MN5W 36,000 Btu High Wall Mounted Heat Pump System

Project Name Location Date

Location Approval Date

Engineer Unit Designation

Submitted To Drawing Number

Submitted By

Reference Approval Construction (Circle One)

Performance SpecificationIndoor Unit Model MSC-36HRDN1-MN5W Air Circulation (Low, Medium, High) 942/750/680

Outdoor Unit Model MOJ-36HDN1-MN5WNoise Level Cooling Indoor(High) (Dba) 50

Cooling Capacity (BTUH) 36,000Noise Level Heating Indoor (High) (Dba) 50

Sensible Capacity (BTUH) 36,000Noise Level Cooling Outdoor (High) (Dba) 55

SEER 15.5Noise Level Heating Outdoor (High) (Dba) 56

EER Cooling 10.0 Connection (Tubing) Flare

EER Heating 10.0 Connection Pipe size Supply/Return 5/8”/3/8”

HSPF (BTUH/H/W) 10.0 Maximum Tube Length (Feet) 82.02

Moisture Removal (Pints) 6.3 Maximum Height Difference (Feet) 32.80

Energy Star Yes

Operating Range Cooling 5F to 122F PhysicalOperating Range Heating 5F to 86F Net Weight (Indoor/Outdoor) (LBS) 53/181

Height Condensing Unit (Inches) 38.0

Electrical Depth Condensing Unit (Inches) 13.56

Voltage/Phase/Cycle 230/1/60 Length Condensing Unit (Inches) 39.0

Cable Indoor to outdoor14AWG/4 conductor

Shielded Height Indoor Unit (Inches) 13.38

Minimum Circuit Ampacity 20.0 Depth Indoor Unit (Inches) 10.88

Recommended Fuse Size 30.0 Length Indoor Unit (Inches) 56.88

Current Rating Cooling 16.0 Refrigerant R-410a

Current Rating Heating  16.0

W

Page 2: Luna 36,000 Single Wall Mount Submittal Data Sheet

Model W D HMSV1-24HRDN1-

MQ0W56.8

810.8

813.3

8

Model W D H W1 A B

MOG-24HDN1-MQ0W35.2

5 13.033.7

8

NOTE: Test conditions based on ARI 210/240.Rating conditions: Indoor: 80º db / 67º wb; Outdoor 95º db / 75º wb

H