CLAUSE NO.
TECHNICAL REQUIREMENTS
39.03.00 Motor Module Selection table
Sl. No.
Motor rating
kW
Max. Motor Amp.
Switch rating Amp.
Fuse rating Amp.
Contactor rating Amp.
Cable size
Sq.mm
1. 1.1-1.5 3.5 16 6/16 16 3Cx2.5 2. 1.6-3.0 7 32 20 16 3Cx2.5 3. 3.1-5.5 11 32 32 16 3Cx6 4. 5.6-7.0 14.4 63 50 32 3Cx6 5. 7.1-13.0 27.3 63 63 32 3Cx16 6. 13.1-24.0 45 125 80/100 63 3Cx35 7. 24.1-37.0 70 125 125 70
(upto 30 kW) 100
(above 30 kW)
3cx70
8. 37.1-55.0 100 250 160 100 (upto 40
kW) 160
(upto 55 kW)
3Cx120
9. 55.1-80.0 150 250 250 200 3Cx150 10. 80.1-110 200 400 315 250 3Cx150
(upto 90 kW)
3Cx240 (above 90
kW) 11. 110.1-125 230 400 350 300 3Cx240 12. 125.1-160 400 400 400 3-1Cx300 13. above
160 Circuit
Breaker 3-1Cx300
Note i) The cables of size below 150 sq. mm shall be PVC insulated
and those of size 150 sq. mm and above shall be XLPE insulated.
ii) All cables shall be of aluminum conductor except for 2.5 sq.
mm size which shall be copper conductor.