Low Voltage Selectivity QT1_EN

Embed Size (px)

Citation preview

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    1/56

    1SDC007100G0204

    Technical Application PapersMay 2008

    1

    Low voltage selectivitywith ABB circuit-breakers

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    2/56

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    3/56

    1

    IndexA theoretical outline o

    selectivity

    Introduction ............................................................. 2

    Main denitionsSelectivity ................................................................ 3

    Total selectivity - Partial selectivity .......................... 3

    Overload zone Short-circuit zone ......................... 4

    Real currents circulating in the circuit-breakers ...... 5

    Selectivity techniquesTime-current selectivity ........................................... 7

    Current selectivity .................................................... 8

    Time selectivity ........................................................ 9

    Energy selectivity ................................................... 10

    Zone selectivity ..................................................... 11

    How to obtain selectivity with

    ABB circuit-breakers

    Types o ABB circuit-breakers ............................... 12

    MCB Miniature Circuit-BreakersSupply-side S200 / Load-side S200 ..................... 13

    Supply-side S290D-S800D / Load-side S200 ...... 13

    MCCB-MCB SelectivitySupply-side T1-T2-T3-T4 / Load-side MCB ......... 14

    Supply-side T5-T6-T7 / Load-side MCB ............... 15

    Low voltage selectivity with ABB circuit-breakers

    Technical Application Papers

    MCCB-MCCB SelectivityCurrent selectivity .................................................. 16

    Time selectivity ...................................................... 17

    Energy selectivity ................................................... 18

    Zone selectivity (T4L-T5L-T6L) .............................. 19

    ACB-MCCB SelectivityTraditional solution ................................................ 25

    Zone selectivity between Emax and Tmax ............ 26

    ACB-ACB SelectivityTime selectivity ...................................................... 28

    Zone selectivity between Emax ............................. 29

    Directional time selectivity ..................................... 32

    Directional zone selectivity .................................... 34

    Appendix A:

    MV/LV selectivity ................................................... 40

    Appendix B:

    General considerations regarding residual currentselectivity ............................................................... 43

    Appendix C:

    Example o LV/LV selectivity study ........................ 45

    Appendix D:

    Further considerations regarding the real currents

    circulating in the circuit-breakers .......................... 48

    Glossary ............................................................... 52

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    4/56

    2 Low voltage selectivity with ABB circuit-breakers

    Technical Application Papers

    A theoretical outline o selectivity

    Problems and requirements or thecoordination o the protections

    Selection o the protection system o the electrical instal-

    lation is undamental both to guarantee correct economi-

    cal and unctional service o the whole installation and

    to reduce the problems caused by abnormal service

    conditions or actual aults to a minimum.

    Within the sphere o this analysis, the coordination be-

    tween the various devices dedicated to protection o

    sections o installation or specic components is studied

    in order to:

    guarantee saety o the installation and o people in allcases;

    rapidly identiy and exclude just the area involved in

    the problem, without indiscriminate trips which reduce

    the availability o energy in areas not involved in the

    ault;

    reduce the eects o the ault on other integral parts

    o the installation (reduction in the voltage value, and

    loss o stability in rotating machines); reduce the stress on components and damage to the

    area involved;

    guarantee service continuity with good quality power

    supply voltage;

    guarantee adequate support in the case o malunction

    o the protection delegated to opening;

    provide the personnel in charge o maintenance andthe management system with the inormation needed

    to restore service to the rest o the network as rapidly

    as possible and with the least intererence;

    achieve a good compromise between reliability, sim-

    plicity and cost-eectiveness.

    In detail, a good protection system must be able to: perceive what has happened and where, discriminating

    between abnormal but tolerable situations and ault

    situations within its zone o competence, avoiding

    unwanted trips which cause unjustied stoppage o a

    sound part o the installation; act as rapidly as possible to limit the damage (destruc-

    tion, accelerated ageing, etc.), saeguarding powersupply continuity and stability.

    The solutions come rom a compromise between these

    two antithetic requirements precise identication o the

    ault and rapid tripping - and are dened according to

    which requirement is privileged.

    For example, in the case where it is more important toprevent unwanted trips, an indirect protection system is

    generally preerred, based on interlocks and data trans-

    mission between dierent devices which locally measure

    the electrical values, whereas speeds and limitation o

    the destructive eects o the short-circuit require direct

    action systems with with protection releases integrateddirectly in the devices. In low voltage systems or primary

    and secondary distribution, the latter solution is normally

    preerred.

    With regard to the Italian Standard CEI 64-8 Electrical

    user installations with rated voltage below 1000 V in alter-

    nating current and 1500 V in direct current regarding lowvoltage installations, under Part 5 Selection and installa-

    tion o the electrical components this states that:

    Selectivity between protection devices against

    overcurrents (536.1)

    When several protection devices are placed in series and

    when the service needs justiy it, their operating charac-teristics must be selected so as to disconnect only the

    part o the installation where the ault is.

    Moreover, in the comments, the ollowing is added:

    The operating situations which require selectivity are

    dened by the customer or by the designer o the in-

    stallation.

    The Standard thereore states that the operating charac-

    teristics must be selected so as to have selectivity, when

    the service needs justiy this.

    In general, designing a selective installation not only

    means realising a state-o-the-art project, but also

    designing a good installation which does, in act, respondto the customers requirements, not simply to the aspects

    o the Standards.

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    5/56

    3Low voltage selectivity with ABB circuit-breakers

    Atheoreticaloutlineof

    selectivity

    Main denitions

    SelectivityThe denition o selectivity is given by the IEC 60947-1

    Standard Low voltage equipment - Part 1: General rules

    or low voltage equipmentTrip selectivity (or overcurrent) (441-17-15)

    Coordination between the operating characteristics o

    two or more overcurrent protection devices, so that when

    an overcurrent within established limits occurs, the device

    destined to operate within those limits trips whereas the

    others do not trip

    where by overcurrent a current o a higher value than therated current is intended, due to any cause (overload,

    short-circuit, etc.).

    There is thereore selectivity between two circuit-break-

    ers in series when, or an overcurrent which passes

    through both, the load-side circuit-breaker opens thereby

    protecting the circuit, whereas the supply-side one re-mains closed guaranteeing power supply to the rest o

    the installation.

    The denitions o total selectivity and partial selectiv-

    ity are, on the other hand, given in Part 2 o the same

    Standard IEC 60947-2 Low voltage Equipment - Part2: Circuit-breakers

    Total selectivity (2.17.2)Overcurrent selectivity where, in the presence o two

    protection devices against overcurrent in series, the load-

    side protection device carries out the protection without

    making the other device trip.Partial selectivity (2.17.3)

    Overcurrent selectivity where, in the presence o two

    protection devices against overcurrent in series, theload-side protection device carries out the protection

    up to a given level o overcurrent, without making the

    other device trip.

    One can speak o total selectivity when there is selectiv-

    ity or any overcurrent value possible in the installation.

    Between a pair o circuit-breakers, one speaks o totalselectivity when there is selectivity up to the lesser o the

    Icu values o the two circuit-breakers, since the maximum

    prospective short-circuit current o the installation will inany case be less or equal to the smallest o the Icu values

    o the two circuit-breakers.

    One talks about partial selectivity when there is onlyselectivity up to a certain Is current value (ultimate

    selectivity value). I the current exceeds this value, se-

    lectivity between the two circuit-breakers will no longer

    be guaranteed.

    Between a pair o circuit-breakers, one speaks about

    partial selectivity when there is selectivity up to a certain

    Is value below the Icu values o the two circuit-break-

    ers. I the maximum prospective short-circuit current othe installation is lower than or equal to the Is selectivity

    value, one can still speak o total selectivity.

    ExampleThe ollowing two circuit-breakers are considered:

    On the supply side T4N250 PR221 In250 (Icu=36kA)

    On the load side S294 C 100 (Icu=15kA)

    From the Coordination Tables publication it can be seen that there

    is total selectivity (T) between the two circuit-breakers.

    This means that there is selectivity up to 15kA, i.e. the

    lower o the two Icu values.

    Obviously, the maximum possible short-circuit current at the pointo installation o the S294 C 100 circuit-breaker will be less than

    or equal to 15kA.

    Now the ollowing two circuit-breakers are considered:

    On the supply side T4N250 PR221 In160 (Icu=36kA)

    On the load side S294 C 100 (Icu=15kA)

    ELTM, M

    Supplyside

    Version

    Release

    Iu [A]

    In [A]

    80

    100

    125

    80100

    5

    5*

    5

    250

    160 200 250 320

    320 250 320

    160 250 320

    11

    8

    8*

    118

    T

    T

    12

    T

    T

    T

    T

    TT

    T

    12

    T12

    T

    T

    T

    TT

    T

    T

    T

    TT

    T

    N,S H,L,V

    T4

    Icu [kA]

    15

    Charact.

    C-K

    C

    D

    Load-side

    S290

    * Value valid with magnetic only circuit-breaker on the suppy side

    T4N 250 PR221DS-LS/I

    S 294 C 100

    Tmax T4 - S290 @ 400/415 V

    From the Coordination Tables publication it can be seen that the

    selectivity value is Is=12kA between the two circuit-breakers.

    This means that, i the maximum prospective short-circuit currenton the load-side o the S294 C 100 circuit-breaker is less than 12kA,

    there will be total selectivity, whereas i the short-circuit current has

    a higher value, there will be partial selectivity, i.e. only or the aults

    with a current below 12kA, whereas or aults between 12 and 15 kAnon-tripping o the supply-side circuit-breaker is not guaranteed.

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    6/56

    4 Low voltage selectivity with ABB circuit-breakers

    Technical Application Papers

    Atheoreticaloutlineof

    selectivity

    Overload zone Short-circuit zone By short-circuit zone one means the ranges o currentvalues, and thereore the relative part o the trip curveso the circuit-breaker, which are 8-10 times higher than

    the rated current o the circuit-breaker.

    This is the zone in which the magnetic protection or

    thermomagnetic releases or protections S, D and I or

    electronic releases are normally called on to intervene.

    These current values usually correspond to a ault on the

    supply circuit. This event is most unlikely than a simpleoverload.

    For the purposes o the selectivity analysis made in this

    publication, the concepts o overload zone and short-

    circuit zone are introduced.

    By overload zone one means the ranges o current

    values, and thereore the relative part o the circuit-

    breaker trip curves coming between the rated current o

    the circuit-breaker itsel and 8-10 times this value.

    This is the zone in which the thermal protection or

    thermomagnetic releases and protection L or electronic

    releases are normally called on to intervene.

    These currents usually correspond to a circuit where a

    load results to be overloaded. This event is likely to occur

    more requently than a real ault.

    0.1kA 1kA 10kA

    104s

    103s

    102s

    10s

    1s

    10-1s

    10-2s

    0.1kA 1kA 10kA

    104s

    103s

    102s

    10s

    1s

    10-1s

    10-2s

    Overload Zone = In 8-10In Short-circuit Zone => 8-10In

    Main denitions

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    7/56

    5Low voltage selectivity with ABB circuit-breakers

    tA

    tB

    IA IB

    IB IA

    tA

    tB

    IA=IB

    tA

    tB

    IA=IB+Iloads

    IA=(IB+Iloads)/n

    IA=IB

    A

    B

    A

    B

    A

    B

    Atheoreticaloutlineof

    selectivity

    Real currents circulating in the circuit-breakers

    When the time-current curves o two circuit-breakers are

    compared, one is oten led to assess the trip times o

    the two devices as i they were passed through by the

    same current.This consideration is only true when, between the two

    circuit-breakers placed in series, there are no other shun-

    ts, i.e. there is a single incoming and a single outgoing

    eeder which insist on the same node.

    When, on the other hand, there are several supply-side

    circuit-breakers which insist on the same busbar or

    several outgoing eeders on the load side, the currents

    which pass through the apparatus can be even consi-derably dierent.

    With regard to the real currents circulating in the circuit-breakers, the three main cases which can be consideredare as ollows:- a single circuit-breaker on the supply side o a single

    circuit-breaker on the load side (passed through by thesame current)

    - a single circuit-breaker on the supply side o severalcircuit-breakers on the load side (supply-side circuit-breaker passed through by a current higher than thato the load-side circuit-breaker)

    - two or more circuit-breakers on the supply side and

    several circuit-breakers on the load side.

    Where:IB

    is the overcurrent which passes through circuit-breaker B

    IA

    is the overcurrent which passes through circuit-breaker A

    Iloads

    is the sum o the currents which, during normal operation, is consumed by the loads (excluding B) supplied by the supply-side

    circuit-breaker A. This sum can, i necessary, be corrected with suitable contemporaneity and use actorsn is the number o circuit-breakers placed in parallel on the power supply side.

    * These ormulas do not take into account the dierent phase displacement o the currents or any asymmetry o the circuit; the rst two ormulas are

    however conservative and the third one is acceptable when the two supply circuits are equal.

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    8/56

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    9/56

    7Low voltage selectivity with ABB circuit-breakers

    Time-current selectivityIn general, the protections against overload have a

    denite time characteristic, whether they are made by

    means o a thermal release or by means o unction L o

    an electronic release.

    A denite time characteristic is intended as a trip cha-

    racteristic where, as the current increases, the trip time

    o the circuit-breaker decreases.When there are protections with characteristics o this

    type, the selectivity technique used is time-current se-lectivity.Time-current selectivity makes trip selectivity by adjusting

    the protections so that the load-side protection, or all

    possible overcurrent values, trips more rapidly than the

    supply-side circuit-breaker.

    When the trip times o the two circuit-breakers are analy-

    sed, it is necessary to consider:

    - the tolerances over the thresholds and trip times- the real currents circulating in the circuit-breakers.

    Operatively speakingWith regard to the tolerances, ABB SACE makes the trip curves o their releases available in the technical catalogues and in the DOCWin

    sotware. In particular, in the curve module o the DOCWin sotware, the curves o both the electronic and thermomagnetic releases include

    the tolerances. A release trip is thereore shown by two curves, one which indicates the highest trip times (top curve), and the other whichindicates the most rapid trip times (bottom curve).For a correct analysis o selectivity, the worst conditions must be considered, i.e.:

    - the supply-side circuit-breaker trips according to its own bottom curve

    - the load-side circuit-breaker trips according to its own top curveWith regard to the real currents circulating in the circuit-breakers:

    - i the two circuit-breakers are passed through by the same current, it is sucient or there to be no overlapping between the curve o

    the supply-side circuit-breaker and the curve o the load-side circuit-breaker;

    - i the two circuit-breakers are passed through by dierent currents, it is necessary to select a series o signicant points on the timecurrent curves and check that the trip times o the supply-side protection are always higher than the corresponding times o the load

    side protection.

    1.05 x I1 o the supply-side circuit-breaker

    Assuming IA

    =1.05xI1,with reerence to what has been said aboutthe realcurrents which circulatein the circuit-breakers, the I

    Bcurrent

    is obtained on the load side.

    The trip times o the two devices are obtained rom the time-current

    curves.

    1.20XI3 (or I2)

    o the load-side circuit-breaker

    Assuming IB

    = 1.20XI3 (or I2), the IA

    current is obtained in the same

    way on the supply side and, rom the time-current curves, the trip

    times o the two devices are obtained.

    I the ollowing is true or both the points considered:

    tA>t

    B

    then selectivity in the overload zone is guaranteed.

    1 1.05 is the value or minimum defnite non-intervention dictated by the Standard (IEC60947-2). For some types o circuit-breakers this value could vary

    (see the technical catalogue or urther inormation).

    2 1.2 is the value or maximum defnite intervention or protection against short-circuit dictated by the Standard (IEC60947-2). For some types o circuit-

    breakers this value could be lower (see the technical catalogue or urther inormation).

    A

    B

    In particular, in the case o circuit-breakers equipped with electronic releases, since the trend o the curves is at I2t=const, to carry out

    the check correctly, it is sucient to examine two current values:1.05 x I11 o the supply-side circuit-breaker (value below which the supply-side protection never intervenes)

    1.20XI3 (or I2)2 o the load-side circuit-breaker (value above which the load-side protection certainly trips with the protections against

    short-circuit)Time-current Selectivity

    0.1kA 1kA 10kA 100kA

    A

    B

    103s

    102s

    10s

    1s

    10-1s

    0.1kA 1kA 10kA 100kA

    0.1s

    1s

    10s

    100s

    1E3sA

    B

    Time-current Selectivity

    Atheoreticaloutlineof

    selectivity

    In the gure at the side an absorption o current rom other loads has been

    assumed

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    10/56

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    11/56

    9Low voltage selectivity with ABB circuit-breakers

    Time selectivity

    This type o selectivity is an evolution o the previous one.In this type o coordination, apart rom the trip thresholdin terms o current, a trip time is also dened: a certaincurrent value will make the protections trip ater a denedtime delay, suitable or allowing any protections placedcloser to the ault to trip, excluding the area which is theseat o the ault.The setting strategy is thereore to progressively increasethe current thresholds and the trip delays as one getscloser to the power supply sources (level o setting di-rectly correlated to the hierarchical level).The delayed trip thresholds must take into account the

    tolerances o the two protection devices and the eectivecurrents which circulate in them.The dierence between the delays set or the protectionsin series must take into account the ault detection andelimination times o the device on the load side and othe inertia time (overshoot) o the device on the supplyside (time interval during which the protection can trip

    even when the phenomenon is over).As in the case o current selectivity, the study is made bycomparing the time-current trip curves o the protectiondevices.Generally this type o coordination:

    - is easy to study and realise;- is not very costly with regard to the protection sy-

    stem;- allows even high selectivity limit values to be obtai-

    ned (i Icw is high);- allows redundancy o the protection unctions.

    However:- the trip times and energy levels let through by the

    protections, especially by those close to the sources,are high.

    It is a type o selectivity which can also be made

    between circuit-breakers o the same size, equippedwith electronic releases with delayed protection againstshort-circuit.

    Operatively speaking

    The protections against short-circuit o the two circuit-breakers will be set:

    - with the I2 trip thresholds against delayed short-circuit adjusted so as not to create trip overlapping,

    taking into consideration the tolerances and the real currents circulating in the circuit-breakers.

    - with t2 trip times adjusted so that the load-side circuit-breaker B extinguishes the ault whereas thesupply-side circuit-breakerA, still in the timing phase, manages to see the extinction o the current

    and thereore remains closed.

    The ultimate selectivity limit which is obtained is equal:

    to the instantaneous trip threshold o the supply-side protection,

    i this unction is enabled, less any tolerance:

    Is = I3minA

    to the value o Icw or supply-side air circuit-breakers when the

    instantaneous protection unction is set to OFF.

    Note

    These selectivity limits are exceeded in all the cases where energy type

    selectivity is realised.

    I the settings indicated or energy selectivity are respected or the com-

    binations o circuit-breakers with an energy selectivity value given in the

    coordination tables published by ABB, the selectivity limit to be taken into

    consideration is the one given in the tables and not the one which can be

    obtained rom the considerations made in this paragraph. 0.1kA 1kA 10kA 100kA

    Time Selectivity

    A

    B

    Is103s

    102s

    10s

    1s

    10-1s

    10-2s

    104s

    A

    B

    Atheoreticaloutlineof

    selectivity

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    12/56

    10 Low voltage selectivity with ABB circuit-breakers

    Technical Application Papers

    Energy selectivityCoordination o energy type is a particular type o selec-tivity which exploits the current-limiting characteristicso moulded-case circuit-breakers. It is pointed out that acurrent-limiting circuit-breaker is a circuit-breaker witha suciently short trip time to prevent the short-circuitcurrent rom reaching the peak value which would othe-rwise be reached (IEC 60947-2).In practice, all the ABB SACE moulded-case circuit-breakers o the Tmax series, the modular circuit-breakersand the E2L E3L air current-limiting circuit-breakers havemore or less marked current-limiting characteristics.Under short-circuit conditions, these circuit-breakers

    are extremely ast (trip times in the region o a ew milli-seconds) and open when there is a strong asymmetricalcomponent. It is thereore not possible to use the time-

    current trip curves o the circuit-breakers, obtained withsymmetrical sinusoidal types o wave orms, or thecoordination study.The phenomena are mainly dynamic (thereore propor-tional to the square o the instantaneous current value)and are heavily dependent on the interaction betweenthe two pieces o apparatus in series. Thereore theenergy selectivity values cannot be determined by theend user.The manuacturers make tables, slide-rules and calcu-lation programmes available where the ultimate currentselectivity values o Is under short-circuit between di-erent combinations o circuit-breakers are given. Thesevalues are dened by theoretically integrating the results

    o tests carried out in compliance with what is indicatedin Annex A o the IEC 60947-2 Standard.

    Operatively speaking

    The Is ultimate selectivity limit obtained is the one given in the tables which ABB SACE makes available to the customer.

    The protections against short-circuit o the two circuit-breakers must respect the conditions given below.

    - Supply-side release o thermomagnetic type

    the magnetic trip thresholds must be such so as not to create trip overlapping, taking into consideration the tolerances

    and the real currents circulating in the circuit-breakers;the magnetic threshold o the supply-side circuit-breaker must be equal to or higher than10xIn or set to the maximum

    value when it is adjustable.

    - Supply-side release o electronic type

    any protections against delayed short-circuit S must be adjusted ollowing the same indications as time selectivity;the instantaneous protection unction I o the supply-side circuit-breakers must be set to o

    I3=OFF

    B

    Supplyside

    T5

    N,S,H,L,W

    Release

    In [A] 400 630 400 630

    TM LL

    Version

    Load side

    T3

    N

    S

    TM 160

    In [A]

    63

    80

    100

    125160

    200

    250

    63

    80

    100

    125

    160

    200

    250

    25

    25

    25

    20

    25

    25

    25

    20

    25

    25

    25

    20

    25

    25

    25

    20

    25

    25

    25

    2020

    25

    25

    25

    20

    20

    25

    25

    25

    2020

    20

    20

    25

    25

    25

    20

    20

    20

    20

    25

    25

    25

    2020

    20

    20

    25

    25

    25

    20

    20

    20

    25

    25

    25

    2020

    20

    20

    25

    25

    25

    20

    20

    20

    20

    25

    25

    25

    2020

    20

    20

    25

    25

    25

    20

    20

    20

    20

    A

    Energy Selectivity

    0.1kA 1kA 10kA

    A

    B

    Is

    103s

    102s

    10s

    1s

    10-1s

    10-2s

    A

    B

    Atheoreticaloutlineof

    selectivity

    Selectivity techniques

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    13/56

    11Low voltage selectivity with ABB circuit-breakers

    Zone selectivity

    This type o coordination is an evolution o time coor-

    dination.

    In general, zone selectivity is made by means o dialogue

    between the current measuring devices which, once

    the setting threshold has been detected as having been

    exceeded, allows just the ault zone to be identied cor-

    rectly and the power supply to it to be cut o.It can be realised in two ways:

    the measuring devices send the inormation linked

    to the current setting threshold having been exceeded

    to a supervision system and the latter identies which

    protection has to intervene; when there are current values higher than their setting,

    each protection sends a lock signal by means o a direct

    connection or a bus to the hierarchically higher level pro-tection (on the supply side in relation to the power fow

    direction) and, beore intervening, checks that a similar

    lock signal has not arrived rom the load-side protection.

    In this way only the protection immediately to the supply

    side o the ault intervenes.

    The second case allows denitely shorter trip times.

    Compared with coordination o the time type, the needto increase the intentional delay as one moves towards

    the power supply source is no longer necessary. The

    delay can be reduced to the time needed to excludethe presence o a possible lock signal coming rom the

    load-side protection.

    This is a type o selectivity suitable or radial networks

    and, when associated with the directional protection,

    also suitable or meshed networks.Compared with coordination o time type, zone selec-

    tivity allows:

    - reduction o the trip times (these can be lower than

    hundred milliseconds);

    - reduction both o the damage caused by the ault and

    o intererences to the power supply system;

    - reduction o the thermal and dynamic stresses on the

    components o the installation;- a very high number o selectivity levels to be obtai-

    ned.

    However:

    - it is more burdensome both in terms o cost and o

    complexity o the installation

    - it requires an auxiliary supply.

    This solution is thereore mainly used in systems with

    high rated current and short-circuit current values, with

    saety and service continuity requirements which are both

    binding: in particular, there are oten examples o logical

    A remains closed

    B opens

    A opens

    B remains closed

    A

    B

    Fault current

    Lock signal

    A

    B

    Fault current

    Lock signal

    Operatively speakingThis is a type o selectivity which can be realised:

    - between Emax air circuit-breakers equipped with PR122 and PR123 releases.The ultimate selectivity limit which can be obtained is equal to the Icw Is = Icw

    - between Tmax T4L,T5L and T6L moulded-case circuit-breakers equipped with PR223 EF releases.

    The ultimate selectivity limit which can be obtained is 100kA Is = 100kA

    Then, by means o the S51/P1 contact module, it is possible to make a chain o zone selectivity between Tmax and Emax. It is also

    possible to realise a selectivity chain including ABB MV protections.

    The operating principle o zone selectivity betweenABB circuit-breakers is as ollows:

    When there are current values higher than their setting, each protection sends a lock signal by means o a direct connection or a bus to

    the hierarchically higher level protection (on the supply side in relation to the power fow direction) and, beore intervening, checks that

    a similar lock signal has not arrived rom the load-side protection. In this way only the protection immediately to the supply side o the

    ault intervenes.

    Atheoreticaloutlineof

    selectivity

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    14/56

    12 Low voltage selectivity with ABB circuit-breakers

    Technical Application Papers

    How to obtain selectivity with ABB circuit-breakers

    MCB

    Miniature Circuit-Breakers

    These are the System Pro-M series o circuit-breakers.

    They are equipped with thermomagnetic releases whose

    trip characteristics conorm to the IEC60898 Standard

    and to the DIN VDE 0660 Standard.

    These circuit-breakers have the breaking capacity (Icu)

    complying with the Standard IEC 60947-2 and the energy

    selectivity limits reer to this Standard.

    ACB

    Air Circuit-Breakers

    These are the Emax series o circuit-breakers.

    They can be equipped with electronic releases.

    The most advanced electronic releases o the Emax

    series are the PR122/P, which allows zone selectivity to

    be realised, and the PR123/P which, apart rom zone

    selectivity, also allows directional zone selectivity to berealised.

    MCCB

    Moulded-Case Circuit-Breakers

    These are the Tmax series o circuit-breakers.They can be equipped with thermomagnetic or electronic

    releases.

    The most advanced electronic release o the Tmax series

    is the PR223EF which allows zone selectivity to be reali-

    sed between moulded-case circuit-breakers.

    Types o ABB circuit-breakers

    How to obtain selectivity with the dierent types o ABBcircuit-breakers will be analysed in details in the next

    chapters.

    Each chapter is dedicated to a particular combination

    o circuit-breakers and to the methods to realise selec-

    tivity between them.This pubblication gives indicationsor rapid selection o the circuit-breaker adjustments in

    order to obtain selectivity.

    These indications about adjustments o the releases

    are generally valid and are used or rapid selection o

    the settings.

    For specic combinations o circuit-breakers and orspecic installation conditions, ABB SACE may provideindications which do not respect the rules given in this

    document.

    Here is a short description o the dierent types o ABB

    circuit-breakers taken into consideration in this publi-

    cation.

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    15/56

    13Low voltage selectivity with ABB circuit-breakers

    Supply-side S200 / Load-side S200Only current type selectivity can be looked or between two circuit-breakers o the S200 series.

    In particular, the ollowing prescriptions are valid:

    - In the overload zone, the load-side circuit-breaker must trip more rapidly than the supply-side circuit-breaker, taking into considerationthe tolerances and the eective currents circulating in the circuit-breakers.

    In the short-circuit zone given that the ollowing are:

    I3minA

    the lowest magnetic threshold o the supply-side circuit-breakerA

    I3MaxB

    the highest magnetic threshold o the load-side circuit-breaker BIk

    Bthe maximum prospective short-circuit current on the load side o B

    These are circuit-breakers with a thermomagnetic relea-se and thereore neither time selectivity let alone zone

    selectivity is possible.

    The two selectivity techniques which can be used are

    This is assuming that the magnetic trip thre-

    sholds o the supply-side circuit-breaker and othe load-side circuit-breaker do not create trip

    overlapping, taking into consideration the realcurrents circulating in the circuit-breakers.

    I the ollowing relationships are veried:

    I3minA

    > IkB

    I3MaxB

    < IkB

    one can talk about total selectivity.

    Otherwise there will be partial selectivity and

    the ultimate selectivity limit will be:

    Is = I3minA

    Supply-side S290D-S800D / Load-side S200Between the S800 curve D or S290 curve D circuit-breakers on thesupply side and the circuit-breakers o the S200 series on the load

    side, ABB SACE provides selectivity tables which give the values

    o energy selectivity.In particular, or the values o the tables to be considered valid, the

    ollowing prescriptions are valid:

    - in the overload zone, the load-side circuit-breaker must tripmore rapidly than the supply-side circuit-breaker, taking into

    consideration the tolerances and the real currents circulating in

    the circuit-breakers.

    - in the short-circuit zone, the lower magnetic trip threshold

    o the supply-side circuit-breaker and the upper magnetic trip

    threshold o the load-side circuit-breaker must be such so as

    not to create trip overlapping, taking into consideration the realcurrents circulating in the circuit-breakers.

    current selectivity and energy selectivity. Depending onthe type o MCB on the supply side, either one or the

    other can be realised.

    A

    B

    Cable

    IkB

    Energy selectivity between S200 D40 and S200 C10

    0.1kA 1kA 10kA0.1kA

    Is

    A

    B

    103s

    102s

    10s

    1s

    10-1s

    10-2s

    Energy selectivity between S290 D100 and S200L C25

    0.1kA 1kA 10kA0.1kA

    Is

    B

    A

    103s

    102s

    10s

    1s

    10-1s

    10-2s

    S800N-S

    D

    32

    S200L C 5

    In [A]

    6-8

    10

    1316

    20

    25

    32

    40

    Icu [kA]

    D

    40 50 63

    36-5015

    80 100

    S290

    T

    5

    4.54.5

    3.5

    3.5

    T

    T

    TT

    5

    5

    4.5

    0.6

    0.6

    0.60.6

    0.8

    0.8

    0.80.8

    0.8

    0.8

    1.1

    1.1

    1.11.1

    1.1

    1.1

    0.9

    1.4

    1.4

    1.41.4

    1.3

    1.3

    1.1

    1.1

    B

    A

    Supplyside

    Characteristic

    Load side

    MCB-MCB Selectivity

    A

    B

    HowtoobtainselectivitywithABBcircuit-breakers

    The Is ultimate selectivity limit which is obtained is the one given inthe tables which ABB SACE makes available to the customer

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    16/56

    14 Low voltage selectivity with ABB circuit-breakers

    Technical Application Papers

    B

    Supply side

    Release

    Iu [A]

    Version

    Load side In [A]Icu [kA]Charact.

    TM,M

    N,S,H,L

    T2

    EL

    160

    C

    B-C

    S200P

    25

    15

    12.5 16 20 25 32 40 50 63 80 100 125 160 10 25 63 100 160

    2

    3

    4

    6

    8

    10

    13

    16

    20

    25

    32

    40

    50

    63

    T

    15

    15

    5.5*

    T

    15

    15

    5.5

    T

    15

    15

    5.5

    5.5

    3*

    3*

    T

    15

    15

    5.5

    5.5

    3

    T

    15

    15

    5.5

    5.5

    3

    3

    3*

    3*

    T

    15

    15

    5.5

    5.5

    3

    3

    3

    T

    15

    15

    5.5

    5.5

    4.5

    4.5

    4.5

    3

    3*

    3*

    T

    15

    15

    10.5

    10.5

    7.5

    7.5

    5

    5

    5

    T

    15

    15

    15

    15

    8.5

    7.5

    7.5

    6

    6

    6

    5.5*

    3*

    T

    17

    17

    17

    17

    17

    12

    12

    10

    10

    7.5

    7.5

    5*

    5*

    T

    T

    T

    T

    T

    T

    20

    20

    15

    15

    12

    12

    7.5

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    10.5

    10.5

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    10.5

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    10.5

    10.5

    A

    Supply-side T1-T2-T3-T4 / Load-side MCBIn the Coordination Tables publication, there are tables with circuit-breakers o the Tmax T1, T2, T3and T4 series on the supply side o the modular circuit-breakers o the S200, S290 and S800 series.

    The energy selectivity values given are valid once the conditions described below are veried.

    The case where selectivity is looked or between a moul-ded-case circuit-breaker on the supply side and a modu-

    lar circuit-breaker on the load side is now analysed.

    The Is ultimate selectivity limit which is obtained is the one given in the Coordination Tables publication

    Overload zone

    In the overload zone,the load-side circuit-breaker must trip more

    rapidly than the supply-side circuit-breaker, taking into considera-

    tion the tolerances and the real currents circulating in the circuit-breakers.

    Short-circuit zoneSupply-side circuit-breaker o thermomagnetic type

    The magnetic trip threshold must be:

    - higher than or equal to 10xIn when the magnetic threshold is

    xed (TMD)- set to the maximum value when the magnetic threshold is

    adjustable (TMA)

    - such so as not to create trip overlapping with the load-side

    circuit-breaker, taking into consideration the tolerances andthe real currents circulating in the circuit-breakers.

    Supply-side circuit-breaker o electronic type

    The instantaneous protection unction I must be set to OFF

    I3=OFF

    The I2 current threshold o unction S, less any tolerance, must be

    adjusted so as not to create trip overlapping with the upper ma-gnetic threshold o the load-side circuit-breaker I3

    MaxB, taking into

    consideration the real currents circulating in the circuit-breakers.

    With regard to the t2 trip time o unction S:

    t2A 100ms both with I2t=const as well with t=const

    HowtoobtainselectivitywithABBcircuit-breakers

    Selectivity between T2160 PR221 In100 and S280 C50

    0.1kA 1kA 10kA

    103s

    102s

    10s

    1s

    10-1s

    10-2s

    104s

    Is

    B

    A

    MCCB-MCB Selectivity

    In this case, thanks to the dierent size o the twocircuit-breakers, it is always possible to obtain energy

    selectivity.

    A

    B

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    17/56

    15Low voltage selectivity with ABB circuit-breakers

    Supply-side T5-T6-T7 / Load-side MCBWith the Tmax T5, T6 and T7 moulded-case circuit-breakers and the modular circuit-breakers on the loadside, there is always total selectivity i the conditions described below are veried.

    HowtoobtainselectivitywithABBcircuit-breakers

    Selectivity between T5N400 PR221In320 and S284 D63

    0.1kA 1kA 10kA

    B

    A

    103s

    102s

    10s

    1s

    10-1s

    10-2s

    104s

    Is

    Overload zone

    In the overload zone, the load-side circuit-breaker must trip morerapidly than the supply-side circuit-breaker, taking into considera-

    tion the tolerances and the real currents circulating in the circuit-

    breakers.

    Short-circuit zone

    Supply-side circuit-breaker o thermomagnetic type

    The magnetic trip threshold must be:- higher than or equal to 10xIn when the magnetic threshold is

    xed (TMD)

    - set to the maximum value when the magnetic threshold is

    adjustable (TMA)- such so as not to create trip overlapping with the load-side

    circuit-breaker, taking into consideration the tolerances and

    the real currents circulating in the circuit-breakers.

    Supply-side circuit-breaker o electronic type

    The instantaneous protection unction I must be set to OFF

    I3=OFF

    The Is ultimate selectivity limit is the lesser between the breaking capacity o the supply-side circuit-breaker and the breaking capacityo the load-side circuit-breaker.

    With reerence to the example given in the gure above

    S284D63 Icu = 15kA

    T5N400 Icu = 36kA

    there is thereore Is = 15kA

    The I2 current threshold o unction S, less any tolerance, must be

    adjusted so as not to create trip overlapping with the upper ma-gnetic threshold o the load-side circuit-breaker I3

    MaxB, taking into

    consideration the real currents circulating in the circuit-breakers.

    With regard to trip time t2 o unction S:

    t2A 100ms both with I2t=const as well with t=const

    A

    B

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    18/56

    16 Low voltage selectivity with ABB circuit-breakers

    Technical Application Papers

    Current selectivityLooking or current selectivity between moulded-case circuit-breakers may be necessary when there are circuit-breakers o the same

    size which do not have energy selectivity values in the tables.

    In any case, only low selectivity values in the order o a maximum o 10 times the In rated current o the release on the supply side can

    be obtained.To obtain the current type o selectivity, the ollowing prescriptions must be respected:

    In the overload zone, the load-side circuit-breaker must trip more rapidly than the supply-side circuit-breaker, taking into considerationthe tolerances and the eective currents circulating in the circuit-breakers.

    The case where selectivity is looked or between twomoulded-case circuit-breakers is now analysed. In this

    case, dierent techniques can be used to obtain selec-tivity between the circuit-breakers:

    current selectivity

    or combinations o circuit-breakers which do not have

    an energy selectivity value when an element with high

    impedance is placed between the two

    time selectivity

    or combinations o circuit-breakers which do not have

    an energy selectivity value and the supply-side circuit-breaker is equipped with an electronic release

    energy selectivity

    or the combinations given in the Coordination Tables

    publication

    zone selectivity

    or Tmax circuit-breakers equipped with PR223EF re-

    leases

    I the ollowing relationships are true:

    I3minA

    > IkB

    I3MaxB

    < IkB

    one can speak o total selectivity.

    Otherwise there will be partial selectivity and the

    ultimate selectivity limit will be:Is = I3

    minA

    This is assuming that the magnetic trip thresholds o

    the supply-side circuit-breaker and o the load-sidecircuit-breaker do not create trip overlapping, taking

    into consideration the real currents circulating in the

    circuit-breakers.

    In the short-circuit zone given that the ollowing are:I3

    minAthe lower magnetic threshold of the supply-side circuit-breakerA

    I3MaxB

    the upper magnetic threshold of the load-side circuit-breaker B

    IkB

    the maximum prospective short-circuit current on the load side of B

    A

    B

    Cable

    IkB

    A

    Current selectivity between T4N250 TMA250 and T4N250 TMA80

    0.1kA 1kA 10kA

    B

    103s

    102s

    10s

    1s

    10-1s

    10-2s

    104s

    Is

    MCCB-MCCB Selectivity

    HowtoobtainselectivitywithABBcircuit-breakers

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    19/56

    17Low voltage selectivity with ABB circuit-breakers

    Time selectivityLooking or current selectivity between moulded-case circuit-breakers may be necessary when there are

    circuit-breakers o the same size which do not have energy selectivity values in the tables and the supply-

    side circuit-breaker is equipped with an electronic release with unction S (T2-T4-T5-T6-T7).In any case, only low selectivity values in the order o a maximum o 10-12 times the rated uninterrupted

    current Iu o the supply-side circuit-breaker can be obtained.

    To obtain the time type o selectivity, the ollowing prescriptions must be respected:

    In the overload zone, the load-side circuit-breaker must trip more rapidly than the supply-side cir-

    cuit-breaker, taking into consideration the tolerances and the real currents circulating in the circuit-breakers.

    t2 times set

    MCCB on the supply side t2A=250 t2

    A=250 t2

    A=500

    MCCB on the load side t2B=50 t2B=100 t2B =250

    Note

    The indications about the adjustments o the releases are valid in general and useul or a rapid choice o setting guaranteing selectivity. For specifc

    combinations o circuit-breakers and or specifc installation conditions, ABB SACE may provide indications which do not respect the rules given in

    this document, but however able to ensure selectivity.

    The ultimate selectivity limit is equal to the istantaneus trip threshold I3 o the upstream circuit-breaker minus the tollerance

    Is = I3minA

    In the short-circuit zone

    - the I2A

    current threshold o unction S o the supply-side

    circuit-breaker must be adjusted so as not to create trip over-lapping with the current threshold o the protection against

    short-circuit (I3 or I2) o the load-side circuit-breaker, takinginto consideration the tolerances and the real currents circu-

    lating in the circuit-breakers

    - with regard to trip time t2 o unction S, the settings o theMCCBs on the supply side are indicated below according to

    the setting/type o MCCB on the load side:

    when the I2A

    threshold o the supply-side circuit-breaker ishigher than an instantaneous protection o the load-side cir-

    cuit-breaker (magnetic, I3=ON or sel-protection) the ollowing

    is valid:

    t2A 150ms i I2t =const

    t2A 100ms i t =const

    when the I2A

    threshold o the supply-side circuit-breaker is only

    higher than the I2B

    threshold o the load-side circuit-breaker,

    by using curves with the same characteristics, the ollowing

    is valid:

    t2A

    - tolerance t2B+ tolerance + 50ms

    A

    Time selectivity between two T4

    0.1kA 1kA 10kA

    B

    Is103s

    102s

    10s

    1s

    10-1s

    10-2s

    104s

    This relationship must be respected when, through the dialogue or the PR010T unit, electronic settings are used. In the more requent

    case - use o the available settings through dip-switches - the values given in the ollowing tables must be complied with:

    A

    B

    HowtoobtainselectivitywithABBcircuit-breakers

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    20/56

    18 Low voltage selectivity with ABB circuit-breakers

    Technical Application Papers

    Energy selectivityABB SACE makes selectivity tables available to the customer which providethe energy selectivity valuesat 415V between the possible combinations o moulded-case circuit-breakers.Since the moulded-case circuit-breakers can be equipped with thermomagnetic and electronic releaseswhich are both adjustable, it is necessary or the user to carry out some checks in order to obtain selec-tivity up to the short-circuit current value given in the tables.In the overload zone, the load-side circuit-breaker must trip more rapidly than the supply-side circuit-breaker, taking into consideration the tolerances and the real currents circulating in the circuit-breakers.

    In the short-circuit zone

    Note: The indications about the adjustments o the releases are valid in general and useul or a rapid choice o setting guaranteing selectivity. For

    specifc combinations o circuit-breakers and or specifc installation conditions, ABB SACE may provide indications which do not respect the rules

    given in this document, but however able to ensure sectivity.

    The Is ultimate selectivity limit obtained is the one given in the

    Coordination Tables publication.

    Iu [A]

    N,S,H,L

    T6

    MCCB - Tmax T5 @ 400/415 V

    T7

    S,H,L,V(1)

    TM, M EL EL

    630 1600

    400630

    400

    630

    TM

    EL

    N,S,H,L,V

    T5

    In [A]

    320400500320400630

    30

    3030

    630 800(2) 1000(2) 1250 1600

    TTTTTT

    TTTTTT

    TTTTTT

    TTTTTT

    800

    3030

    3030

    800

    630

    30

    3030

    630

    800

    3030303030

    800

    1000

    303030303030

    1000

    800 1000 1250

    Supply side

    Versions

    Release

    Load side

    t2 times set

    MCCB on the supply side t2A=250 t2

    A=250 t2

    A=500

    MCCB on the load side t2B=50 t2

    B=100 t2

    B=250

    This relationships must be respected when, through the dialogue or the PR010T unit, electronic settings are used. In the more re-quent case - use o the available settings through dip-switches - the values given in the ollowing tables must be complied with:

    Supply-side circuit-breaker o thermomagnetic type(T1-T2-T3-T4-T5-T6)The magnetic trip threshold must be:- higher than or equal to 10xIn when the magnetic threshold is

    xed (TMD)- set to the maximum value when the magnetic threshold is

    adjustable (TMA).- such so as not to create trip overlapping with the load-side

    circuit-breaker, taking into consideration the tolerances and

    the eective currents circulating in the circuit-breakers.

    Supply-side circuit-breaker o electronic type(T2-T4-T5-T6-T7)- the instantaneous protection unction I must be set to OFF

    I3=OFF

    - trip threshold I2A

    o the supply-side circuit-breaker must beadjusted so as not to create trip overlapping with the tripthreshold o the protection against short-circuit (I3 or I2) o theload-side circuit-breaker, taking into consideration the toleran-ces and the real currents circulating in the circuit-breakers

    - with regard to trip time t2 o unction S, the settings o theMCCBs on the supply side are indicated below according tothe setting/type o MCCB on the load side:when the I2

    Athreshold o the supply-side circuit-breaker is

    higher than an instantaneous protection o the load-side cir-cuit-breaker (magnetic, I3=ON or sel-protection) the ollowing

    is valid:

    t2A 150ms i I2t =const

    t2A 100ms i t =const

    when the I2A

    threshold o the supply-side circuit-breaker isonly higher than threshold I2

    Bo the load-side circuit-breaker,

    by using curves with the same characteristics, the ollowing

    is valid:

    t2A

    - tolerance t2B+ tolerance + 50ms

    Energy selectivity between thermomagnetic MCCB

    A

    0.1kA 1kA 10kA

    B

    Is

    103s

    102s

    10s

    1s

    10-1s

    10-2s

    A

    Energy selectivity between electronic MCCB

    0.1kA 1kA 10kA

    B

    Is

    103s

    102s

    10s

    1s

    10-1s

    10-2s

    A

    B

    MCCB-MCCB Selectivity

    HowtoobtainselectivitywithABBcircuit-breakers

    (1) Available only with Iu 1250 A(2) Value valid only or PR232/P,

    PR331/P and PR332/P trip units

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    21/56

    19Low voltage selectivity with ABB circuit-breakers

    Zone selectivity (T4L-T5L-T6L)By means o the new PR223EF electronic release, it is possible to

    realise zone selectivity between moulded-case circuit-breakers o

    the Tmax T4L, T5L and T6L series.

    The PR223EF implements the new EF protection unction, ca-pable o detecting the short-circuit at its onset. This is thanks to

    predicting the ault, based on analysis o the trend o the current

    derivative in relation to the time, di(t)/dt vs i(t).

    I the EF protection is enabled, it intervenes or aults o considera-ble size, replacing the I protection unction against instantaneous

    short-circuit when there is an auxiliary power supply.

    Between PR223EF releases, zone selectivity is implemented simul-taneously on unctions S, G and EF. It is carried out by means o an

    interlocking protocol (Interlocking, IL), guaranteed by a coupleo

    shielded twisted pair cables or modbus RS485 which connect the

    circuit-breakers equipped with the PR223EF (ask ABB or urtherinormation about cable type).

    In the case o a short-circuit, the circuit-breaker immediately to the

    supply side sends a lock signal to the hierarchically higher level

    protection by means o the bus and, beore trippping, checks thata similar lock signal has not come rom the load-side protection.

    System integrity is controlled by a monitoring unction: in the case

    o a short-circuit, i a ault is ound in the interlocking system, the

    EF protection unction trips (with trip times in the order o tens oms), but zone selectivity is not guaranteed.

    Furthermore, i the load-side circuit-breaker does not manage to

    trip, it asks the supply-side circuit-breaker or help and the latter

    opens even i it does not detect the ault (SOS unction).A 24Vdc auxiliary power supply is required or operation o the EF

    protection and zone selectivity.

    The ultimate selectivity limit which can be obtained is 100kA

    Is=100kA

    All the protection unctions can be programmed remotely, exploi-ting the dialogue unction on the release, or locally by means o

    the PR010/T, which can be connected to a serial port on the ront

    o the PR223EF.One o the main advantages in using zone selectivity between

    MCCBs is the reduction in size o the circuit-breakers it makes

    possible.

    In act, in looking or selectivity between moulded-case circuit-

    breakers with the classic techniques, it is oten necessary to increa-se the size o the supply-side circuit-breakers to obtain selectivity

    limits congruous with the short-circuit current o the installation.

    By means o suitably cabled PR223EF releases, it is possible toobtain 100kA o selectivity even between two circuit-breakers o

    the same size.

    An example is given below (see pages 22 and 23) o how, by means

    o zone selectivity between moulded-case circuit-breakers, a re-duction in sizes and a considerable reduction in the peak current

    and specic energy let through by the circuit-breakers is possible,

    whilst still maintaining total selectivity.

    Interlock confgurationEach release is characterised by:

    - an input destined or connection with the release on the supplyside Uplink

    - an output destined or connection with the release on the load

    side Downlink

    Each o the two can be congured in two ways: PP (point-point)

    or MP (multi-point) according to the installation condition the

    releases are in.

    The main congurations are given below:

    Uplink: PP/MP

    Downlink: PP/MP

    PR223EF

    MP PP

    MPMPMP

    PR223EFPR223EFPR223EF

    PR223EFMP

    MPMPMP

    PR223EFPR223EFPR223EF

    PR223EFPP

    PP

    PR223EF

    PR223EF

    HowtoobtainselectivitywithABBcircuit-breakers

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    22/56

    20 Low voltage selectivity with ABB circuit-breakers

    Technical Application Papers

    The main parameters, characteristic of the release, are:

    Trip delayed Enabling this parameter introduces a trip delay in the case when, on the load side o a release, smaller sized

    Tmax or modular circuit-breakers are installed. The aim o this parameter is to obtain selectivity with the

    other devices on the load side not equipped with PR223EF.

    This parameter is only enabled in the circuit-breakers which have the device outside the zone selectivity

    chain on the load side.

    EF enable/disable Enabling/disabling protection EF.I protection EF is enabled:

    the presence o Vaux leads to automatic exclusion o unction I and enabling o protection EF,

    the lack o Vaux leads to exclusion o protection EF and to the return o unction I (i enabled).

    100 kA Ultimate selectivity limit which can be obtained with the PR223EF suitably cabled and supplied with power.

    16 Maximum number o releases which can be connected to the BUS o a level.

    1000 meters Maximum overall length o the connection cable. Cabling the dierent releases is carried out as in the classicBus topology (see fgure).

    UPUPUP

    PR223EFPR223EFPR223EF

    PR223EF

    Down

    = max 1000 mCable RS485

    MCCB-MCCB Selectivity

    HowtoobtainselectivitywithABBcircuit-breakers

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    23/56

    21Low voltage selectivity with ABB circuit-breakers

    Zone selectivity between Tmax

    0.1kA 1kA 10kA

    B AC

    103s

    102s

    10s

    1s

    10-1s

    10-2s

    104s

    A

    B

    C

    Trip delayed ON

    PR221DS

    PR223EF

    PR223EF

    Indications about the settingsTo obtain total selectivity, both in the case o overload and short-circuit, using the PR223EF releases suitably cabled and supplied withpower, making the ollowing selections and the ollowing settings between the various circuit-breakers is recommended:

    - Trip delayed

    By enabling this parameter on the releases which have a circuit-

    breaker directly on the load side not equipped with PR223EF,

    selectivity is obtained with the Tmax o a smaller size or theMCBs placed on the load side.

    Overload

    - Check there is no trip overlapping o protection unctions L(against overload), taking into consideration the tolerances and

    the real currents circulating in the circuit-breakers.

    Short-circuit

    - No trip overlapping o the I2 current thresholds o unction S,

    taking into consideration the tolerances and the real currents

    circulating in the circuit-breakers.

    - Trip time t2

    Adjusted so as to realise time selectivity with any load-sidecircuit-breaker placed outside the zone selectivity chain.Between the circuit-breakers equipped with PR223EF and inter-

    locked with each other, i A is the supply-side circuit-breaker and

    B the load-side circuit-breaker, the ollowing must be valid:

    t2A t2B.

    When possible, it is advisable to look or time type selectivity as

    well between the interlocked circuit-breakers so as to guarantee

    partial selectivity in case the auxiliary power supply is lost.

    - Instantaneous protection unction I

    This protection unction is automatically disabled when unction

    EF is enabled and there is an auxiliary power supply. Its settings

    are thereore only o importance in the case o losing Vaux.

    HowtoobtainselectivitywithABBcircuit-breakers

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    24/56

    22 Low voltage selectivity with ABB circuit-breakers

    Technical Application Papers

    V = 400 VIk = 95 kAU

    L

    LLL

    Switchboard A

    Switchboard B

    QF1E3H800 PR122/P-LSI In800

    WC16x(1x400)+2x(1x240)+1G400Ib = 740 AIz = 1050 A

    L = 17mPVC

    QF1E3S/ S1000

    QF2T6L630 PR222DS-LSI In630

    QS2T6D630

    IkA=74 kA

    QF3T4L250 PR222DS-LSI In250

    L1In = 200 A

    QF4T4H250 PR222DS-LSI In250

    QF5T4H250 PR222DS-LSI In250

    QF6T4H250 PR222DS-LSI In250

    L2In = 200 A

    L3In = 170 A

    L4In = 170 A

    IkA=54.5 kA

    WC26x(1x300)+2x(1x150)+1G300Ib = 540 AIz

    = 682 AL = 25 mPVC

    WC33x(1x150)+1x(1x95)+1G95Ib = 200 AIz = 275 AL = 10mPVC

    WC43x(1x95)+1x(1x50)+1G50Ib = 200 AIz = 207 A

    L = 40mPVC

    WC53x(1x95)+1x(1x50)+1G50Ib = 170 AIz = 207 A

    L = 60mPVC

    WC63x(1x95)+1x(1x50)+1G50Ib = 170 AIz = 207 A

    L = 30mPVC

    Example o applicationIn the ollowing example a comparison between an installation where selectivity is implemented with traditional techniques and the sameinstallation with selectivity ensured by EFDP system is given.

    Traditional installation

    The choice o the protection devices shall be carried out above all making reerence to the rated currents o the loads and to the short-circuit current o the busbars. Besides, this choice is infuenced by the search or selectivity realized through traditional techniques, whosevalues can be ound in the Coordination Tables publication.The short-circuit current at the busbars o switchboard B (Ik

    B=54.5kA) infuences the choice o the protection devices and imposes the

    use T4H 250 circuit-breakers on the outgoing eeders.In order to guarantee selectivity, the circuit-breaker (QF2) on the supply side o switchboard B and installed in switchboard A must beT6L 630 type.The busbar o switchboard A is characterized by a short-circuit current value Ik

    A=74kA: this aects deeply the choice o the upstream

    protection device which, independent o the rated current, shall be an Emax circuit-breaker and precisely an Emax E3H, thereore able

    to guarantee selectivity towards the apparatus on the load side.Each switchboard has got as main device a switch-disconnector, which shall be protected against short-circuit and overload by thecircuit-breaker on the supply side. Generally speaking, in order to guarantee protection, it is necessary to use a switch-disconnector inthe version derived rom the circuit-breaker on the supply side.Thereore it is evident that the selectivity requirements condition deeply the choice o the protection devices and direct it towards die-rentiated sizes according to the location o the circuit-breakers in the installation.

    MCCB-MCCB Selectivity

    HowtoobtainselectivitywithABBcircuit-breakers

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    25/56

    23Low voltage selectivity with ABB circuit-breakers

    Installation with PR223EF

    Since the rated current and the short-circuit values o the network under consideration remain unchanged, the use o the new protectionrelease PR223EF allows selectivity to be obtained without increasing the size o the apparatus to be used.

    In particular, a T5L630 equipped with PR223EF can be used as circuit-breaker on the supply side o switchboard B (QF2). As a conse-

    quence, the switch-disconnector on the incoming eeder o switchboard B can be reduced in size.

    The most evident reduction in size which can be obtained regards the main device o the installation: thanks to the use o PR223EFrelease, a moulded-case circuit-breaker can be chosen instead o an air circuit-breaker. In this specic case, a T6L800 circuit-breaker

    with a downstream switch-disconnector o the same size can be used.

    V = 400 VIk = 95 kAU

    L

    LLL

    Switchboard A

    Switchboard B

    QF1T6L800 PR223EF In800

    WC16x(1x400)+2x(1x240)+1G400Ib = 740 AIz = 1050 A

    L = 17mPVC

    QF1T6D800

    QF2T5L630 PR223EF In630

    WC26x(1x300)+2x(1x150)+1G300Ib = 540 AIz

    = 682 AL = 25 mPVC

    QS2T5D630

    IkA=74 kA

    QF3T4L250 PR223EF In250

    WC33x(1x150)+1x(1x95)+1G95Ib = 200 AIz = 275 AL = 10mPVC

    L1In = 200 A

    QF4T4L250 PR223EF In250

    QF5T4L250 PR223EF In250

    QF6T4L250 PR223EF In250

    WC43x(1x95)+1x(1x50)+1G50Ib = 200 AIz = 207 A

    L = 40mPVC

    L2In = 200 A

    L3In = 170 A

    L4In = 170 A

    WC53x(1x95)+1x(1x50)+1G50Ib = 170 AIz = 207 A

    L = 60mPVC

    WC63x(1x95)+1x(1x50)+1G50Ib = 170 AIz = 207 A

    L = 30mPVC

    IkA=54.5 kA

    HowtoobtainselectivitywithABBcircuit-breakers

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    26/56

    24 Low voltage selectivity with ABB circuit-breakers

    Technical Application Papers

    MCCB-MCCB Selectivity

    HowtoobtainselectivitywithABBcircuit-breakers

    The ollowing table summarizes the advantages deriving rom the use o the new electronic release.In details, it has been possible:

    toreplacealarge-sizedmoulded-casecircuit-breakerwithasmalleroneT5L630PR223EFinsteadofT6L630PR221-LS; toreplacealarge-sizedaircircuit-breakerwithamuchsmallermoulded-caseoneT6L800PR223EFinsteadofE3H800PR122/P-

    LSIG;

    toreplacealarge-sizedswitch-disconnectorwithasmaller-sizedoneT5D630insteadofT6D630; toreplaceanairswitch-disconnectorwithaswitch-disconnectorderivedfromamuchsmaller-sizedmoulded-casecircuit-breaker

    T6D 800 instead o E3S/MS1000.

    Besides a remarkable reduction in the applicable sizes, with the consequent advantages rom a dimensional and economical point oview, the installation equipped with PR223EF releases is subject to more limited electrodynamical and thermal stresses than those o the

    traditional solution. Hereunder the let-through energy and peak curves relevant to the considered circuit-breakers are shown.

    From the curves above, it should be noticed that at a short-circuit current value corresponding to 55kA, the specic let-through energyallowed by T6H630 is equal to 13 MA2s, whereas that o T5L630 is 3.5 MA2s. Also the peak values decrease drastically rom 54kA o T6Hto about 35kA o T5L630.Similarly, at 74kA short-circuit current, the specic let-through energy and the peak current limited by T6L800 circuit-breaker reduce verymuch the thermal and dynamical stresses i compared with E3H circuit-breaker.In particular, in this case, it is possible to use the current limiting capacities o the moulded-case circuit-breaker to optimize the dimen-sioning o the busbar system o switchboard A. In act, with an air circuit-breaker on the supply side, it is necessary to adopt a busbarsystem dimensioned or a rated short-time withstand current (Icw) equal to 75kA and consequently with a current carrying capacity muchmore higher than the total current required by the installation. On the contrary, by using a T6L800 circuit-breaker on the supply side othe switchboard, it is possible to adopt a busbar system with Icw equal to 35kA, which results more consistent rom a dimensional pointo view with 800A current, which is the current carrying capacity required to this busbar system.In details, the ollowing values correspond to 35kA rated short-time withstand current o the busbar system:- peak current Ip = (35x2.1) = 73.5kA, which results to be higher than the peak o 66kA allowed by T6L800 circuit-breaker at 75kA short-

    circuit current;- let-through energy I2t = 352 x 1 =1225 MA2s, which results to be higher than the let-through energy equal to 20MA2s o T6L800 circuit-

    breaker with a short-circuit value corresponding to 75kA.

    10 kA

    1 MA2s

    103 kA

    Irms [kA]

    10 MA2s

    102 MA2s

    I2[MA2s]

    E3H 800

    T5L 630

    T6L 800T6H 630

    102 kA

    103 MA2s

    10 kA 103 kA

    Irms [kA]

    Ip[kA]

    E3H 800

    T5L 630

    T6L 800T6H 630

    102 kA

    10 kA

    103 kA

    102 kA

    Let-through energy curve Peak curve

    Traditional solution Solution with EFDP

    Busbars o

    switchboard AIcw = 75kA Icw = 35kA

    Traditional solution Solution with EFDP

    E3H800 PR122/P

    E3S/MS1000

    T6L630 PR221DS

    T6D630

    T6L800 PR223EF

    T6D800

    T5L630 PR223EF

    T5D630

    QF1

    QS1

    QF2

    QS2

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    27/56

    25Low voltage selectivity with ABB circuit-breakers

    ACB-MCCB Selectivity

    The case where selectivity is looked or between an aircircuit-breaker on the supply side and a moulded-case

    circuit-breaker on the load side is now analysed.

    In this case, two paths can be ollowed:

    - traditional solution with time/energy selectivity;

    - zone selectivity, when the load-side circuit-breakeris a Tmax equipped with a PR223EF release and theEmax on the supply side is equipped with a PR122/P

    or PR123/P release.

    Traditional solutionIn this case, ABB SACE makes a table available in which the selectivity values between air circuit-breakers on the supply side and moul-ded-case circuit-breakers on the load side are given.The need to set the releases appropriately to obtain the selectivity value given in the table is obvious.The ollowing must be true:In the overload zone, the load-side circuit-breaker must trip more rapidly than the supply-side circuit-breaker, taking into considerationthe tolerances and the real currents circulating in the circuit-breakers.

    In the short-circuit zone

    - instantaneous protection unction I must be set to OFFI3=OFF

    - the I2A

    trip threshold o the supply-side circuit-breaker mustbe adjusted so as not to create trip overlapping with the tripthreshold o the protection against short-circuit (I3 or I2) othe load-side circuit-breaker, taking into consideration thetolerances and the eective currents circulating in the circuit-breakers

    - with regard to the t2 trip time o unction S, the settings o theEmax on the supply side are indicated hereunder, accordingto the setting/type o MCCB on the load side:

    when the I2Athreshold o the supply-side circuit-breaker is

    higher than an instantaneous protection o the load-side cir-cuit-breaker (magnetic, I3=ON or sel-protection) the ollowing

    is valid: t2

    A100ms both i I2t =cost as well as i t =cost

    when the I2A

    threshold o the supply-side circuit-breaker is only higher than the I2B

    threshold o the load-side circuit-breaker, by

    using curves with the same characteristics, the ollowing is valid:

    t2A

    - tolerance t2B+ tolerance + 50ms

    The Is ultimate selectivity limit obtained is the one given in the Coordination Tables publication.

    Note

    The indications about the adjustments o the releases are valid in general and useul or a rapid choice o settings guaranteeing selectivity. For speci-

    fc combinations o circuit-breakers and or specifc installation conditions, ABB SACE may provide indications which do not respect the rules given

    in this document, but however able to ensure selectivity.

    B A

    Emax-MCCB selectivity

    0.1kA 1kA 10kA

    103s

    102s

    10s

    1s

    10-1s

    10-2s

    104

    s

    Version

    Release

    Iu [A]Load side

    ACB - MCCB @ 400/415 V

    Supplyside

    T1

    T2

    B

    C

    N

    N

    S

    H

    TM

    TM,EL

    E1 E2 E3

    B N B N S L* N S H V L* S

    EL EL EL

    800100012501600

    800100012501600

    16002000

    1000125016002000

    8001000125016002000

    12501600

    25003200

    100012501600200025003200

    800100012501600200025003200

    800100012501600200025003200

    20002500

    4000

    160

    160

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    55

    T

    T

    T

    T

    T

    65

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    T

    HowtoobtainselectivitywithABBcircuit-breakers

    t2 times set

    ACB on the supply side t2A=200 t2

    A=200 t2

    A=400 t2

    A=700

    MCCB on the load side t2B=50 t2

    B=100 t2

    B=250 t2

    A=500

    This relationship must be respected when, through the dialogue or the PR010T unit, electronic settings are used. In the more requent

    case - use o the available settings through dip-switches - the values given in the ollowing tables must be complied with:

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    28/56

    26 Low voltage selectivity with ABB circuit-breakers

    Technical Application Papers

    The S51/P1 contact is a clean and normally open contact, requiring

    an auxiliary power supply at 24V to supply the locking signal to the

    supply side relays in the selectivity chain.The contact is located inside the release and is made available

    by means of connector X3. By programming it appropriately, it is

    possible to send the locking signal to the SZin input of the supplyside release. Contact programming can be carried out by means ofSDTestBus2, PR010/T and all the programming instruments which

    can communicate via ModBus.

    S51/P1

    PR122EFPR122EFPR1223EF

    PR122EFSZin

    = max 1000 mCable RS485

    S51/P1 S51/P1

    Zone selectivity between Emax and TmaxBy means of the programmable contact S51/P1 on the Tmax circuit-breakers, it is possible to extend zone selectivity from the PR223EF

    releases to the PR122/P, PR332/P, PR123/P or PR333/P releases on the supply side.

    In practice, the contact makes interfacing between IL protocol of PR223EF and ZS zone selectivity of the releases for Emax and Tmaxpossible.

    By making this selectivity chain between Emax and Tmax the limit selectivity value shall be the lesser value between:

    - the short-time withstand current of the supply-side circuit-breaker (Icw of the Emax)

    - the breaking capacity of the circuit-breaker on the load side (Icu of the Tmax in version L 100kA)

    ACB-MCCB Selectivity

    HowtoobtainselectivitywithABBcircuit-breakers

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    29/56

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    30/56

    28 Low voltage selectivity with ABB circuit-breakers

    Technical Application Papers

    0.1kA 1kA 10kA 100kA

    103s

    102s

    10s

    1s

    10-1s

    10-2s

    104s

    ACB-ACB Selectivity

    The case where selectivity is looked or between two air circuit-breakers is now analysed. In this case variousmethods can be used to obtain selectivity between the circuit-breakers:

    time selectivity or combinations o Emax with any type o release

    zone selectivity or combinations o Emax with PR122 and PR123 releases

    directional time selectivity or combinations o Emax with PR123 releasesdirectional zone selectivity or combinations o Emax with PR123 releases.

    Time selectivityTo obtain the maximum level o selectivity compatible with the chosen strategy, both in the case o overload and short-circuit, the ollowing

    selections and the ollowing settings between the various circuit-breakers are recommended:

    Minimum dierence between the t2 times o two Emax circuit-breakers equipped with PR121, PR122, and PR123

    t=const t2A > t2B+ 100ms* *70ms i in aux supply or in sel-supply under steady conditions

    I2t=const t2A > t2B+ 100ms t2A < 400ms

    I2t=const t2A > t2B + 200ms t2A 400ms

    Note

    The indications about the adjustments o the releases are valid in general and useul or a rapid choice o settings guaranteeing selectivity. For specifc

    combinations o circuit-breakers and or specifc installation conditions, ABB SACE may provide indications which do not respect the rules given in this

    document, but however able to ensure selectivity.

    With regard to the ultimate selectivity limit

    - I instantaneous unction I is set to ON (I3=ON), the ultimate selectivity limit will be the value o the I3 instantaneous trip threshold othe supply-side circuit-breaker less its tolerance:

    Is = I3minA

    - I instantaneous unction I is set to OFF (I3=OFF), the ultimate selectivity limit is equal to the Icw value o the supply-side circuit-breaker:

    Is = Icw.

    Overload

    - Check that there is no trip overlapping o protection unctions L

    (against overload), taking into consideration the tolerances andthe real currents circulating in the circuit-breakers.

    Short-circuit

    - The instantaneous protection unction I o the supply-side circuit-

    breaker must be set to OFF

    I3A=OFF

    - the I2A

    trip threshold o the supply-side circuit-breaker must be

    adjusted so as not to create trip overlapping with the trip threshold

    o the protection against short-circuit (I3 or I2) o the load-side

    circuit-breaker, taking into consideration the tolerances and thereal currents circulating in the circuit-breakers

    - with regard to the t2 trip times o unction S, no overlapping o

    the curves and the ollowing relationships must be respected:

    HowtoobtainselectivitywithABBcircuit-breakers

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    31/56

    29Low voltage selectivity with ABB circuit-breakers

    Fault current

    Connection with lock signal

    Connection without lock signal

    A

    B

    CPR122/P

    PR122/P

    PR122/P

    PR122/P

    PR122/P

    PR122/PPR122/P

    PR122/P PR122/P

    PR122/PPR122/P

    PR122/P

    t2A

    t2B

    t2A

    does nottrip

    selectivity

    timeA

    selectivitytimeB

    selectivitytimeC

    does nottrip

    does nottrip

    Zone selectivity between EmaxBy means o zone selectivity, it is possible to obtain selectivity between Emax circuit-breakers, notably reducing the trip times by obtaininglower curves which can acilitate the search or selectivity towards the medium voltage circuit-breakers.

    By reducing the trip times, the thermal stresses on all the components o the installation during the ault are also reduced.

    Zone selectivity between Emax circuit-breakers, applicable to protection unctions S and G, can be enabled in the case where:

    - the xed time curve is selected or these protections;- there is a 24V auxiliary power supply source;

    - the Emax circuit-breakers are equipped with PR122 or PR123 releases.

    The ultimate selectivity limit obtained is equal to the Icw o the supply-side circuit-breaker i the I3 is set to OFF

    The operating principle o zone selectivity between Emax is described below.

    By zone the part o the installation included between two circuit-breakers in series is intended. The ault zone is the one immediately to

    the load side o the circuit-breaker which detects the ault. By means o a simple connection wire, each circuit-breaker which detects a

    ault communicates this to the one on the supply side.The circuit-breaker which does not receive any communication rom those on the load side will launch the opening command in the

    selectivity time set, adjustable rom 40 to 200ms.

    The aim o the selectivity time is to realise time selectivity towards pieces o apparatus connected on the load side which are outsidethe zone selectivity chain (apparatus not cabled).On the other hand, the circuit-breakers which receive a lock signal rom another release, will trip according to the t2 time seto protection S.

    As can be seen, i the settings indicated below have been respected, in the case o a short-circuit no circuit-breaker trips in the t2 time,

    but all o them trip within the selectivity time set.

    A

    B

    Lock signal

    Fault current

    A

    B

    Lock signal

    Fault current

    A t2A

    B selectivity timeA selectivity timeB closed

    HowtoobtainselectivitywithABBcircuit-breakers

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    32/56

    30 Low voltage selectivity with ABB circuit-breakers

    Technical Application Papers

    0.1kA 1kA 10kA 100kA

    Zone selectivity between Emax

    t2A

    time o selectivityA

    103s

    102s

    10s

    1s

    10-1s

    10-2s

    104sOverload

    - Check that there is no trip overlapping o protection unctions L

    (against overload), taking into consideration the tolerances and

    the real currents circulating in the circuit-breakers.

    Short-circuit

    - No trip overlapping o the I2 current thresholds o unction S,taking into consideration the tolerances and the real currents

    circulating in the circuit-breakers.

    - Trip times t2 and selectivity time adjusted in the ollowing

    way:

    selectivity time adjusted so as to realise time-current selecti-vity with any device connected directly on the load side placed

    outside the zone selectivity chain

    t2 (time o unction S) adjusted so as to guarantee no trip o theprotection which receives the lock signal, i.e. according to the

    relationship:

    t2A

    > selectivity timeB

    +70ms*

    *t minumum between the trip times o two CBs in series, with auxiliary

    power supply, and with constant time curves, to guarantee no trip o the

    CB on the supply side.

    Indications about the settingsTo obtain total selectivity, both in the case o overload, short-circuit and earth ault, using the zone selectivity unction, making theollowing selections and the ollowing settings between the various circuit-breakers is recommended:

    A

    B

    With regard to the ultimate selectivity limit

    - I the instantaneous unction I is set to ON (I3=ON), the ultimate selectivity limit will be the value o the I3 instantaneous trip thresholdo the supply-side circuit-breaker less its tolerance, i this unction is enabled:

    Is = I3minA

    - I the instantaneous unction I is set to OFF (I3=OFF), the ultimate selectivity limit is equal to the Icw value o the supply-side circuit-

    breaker:

    Is = Icw.

    ACB-ACB Selectivity

    HowtoobtainselectivitywithABBcircuit-breakers

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    33/56

    31Low voltage selectivity with ABB circuit-breakers

    Indications about cablingTo carry out the cabling, a two-wire shielded corded cable can be used (Vn50V; AWG 22; nominal conductor DC resistance@20C 15Ohm/1000t; nominal outer shield DC resistance@20C 3 Ohm/1000 t). The shield must only be connected to earth on the release o

    the supply-side circuit-breaker.The maximum cabling length or zone selectivity between two units is 300 metres. This limit can be increased with special mechani-

    sms.

    The maximum number o circuit-breakers which can be connected to the outputs (Z out) o a release is 20.

    Thelock signal o the release is a +24V signal.

    Repetition o the signal

    As shown in the table, in the case where one release receives the lock signal on the load side, even i it has not entered the threshold o

    unction S, it will repeat the lock signal on the supply side.

    This to avoid any setting errors, i.e. a release on the load side not having entered the threshold, but a release on the supply side having

    entered the threshold, leading to lack o selectivity:

    Zone Selectivity I > I2 ZSI signal ZSO signal T trip time

    Excluded NO 0 0 no trip

    Excluded NO 1 0 no trip

    Excluded YES 0 0 t2 programmed

    Excluded YES 1 0 t2 programmed

    Inserted NO 0 0 no trip

    Inserted NO 1 1 no trip

    Inserted YES 0 1 selectivity time

    Inserted YES 1 1 t2 programmed

    ZSA MODULE

    In the case where several load-side circuit-breakers have to lock several supply-side circuit-breakers, but in a dierent way, it is necessary

    to use the ZSA module supplied byABB.

    A B

    C D

    A B

    C D

    ZSA

    HowtoobtainselectivitywithABBcircuit-breakers

    With reerence to the gures at the side, let us suppose, or exam-

    ple, that:

    C must lockA and B

    D must only lock B.

    With the cabling made as in the gure at the side, it would not be

    possible to obtain the desired solution.

    In act, the lock signal coming rom D would also be transmitted to

    A by means o the electrical continuity which is created between

    the dierent B-C and C-A interlocking connections.

    By means o suitable cabling o the ZSA module, the lock signal

    is made one-way so that a signal coming rom D towards B is not

    transmitted toA as well.The gure at the side shows use o the ZSA module.

  • 8/14/2019 Low Voltage Selectivity QT1_EN

    34/56

    32 Low voltage selectivity with ABB circuit-breakers

    Technical Application Papers

    Directional time selectivityBy means o the directional protection D present on the Emax circuit-breakers equipped with PR123 releases, it is possible to realise

    time selectivity o directional type.

    This type o selectivity has all the advantages and limits o time selectivity realised by means o unction S,but is also able to trip within

    dierent times according to the direction o the ault.

    Using this type o selectivity is particularly recommended in all those cases where there is more than one power supply source.

    In act, in the case o a ault near a source, service continuity o the remaining power supply can be guaranteed by means o

    directional protection.

    Directional protectionDirectional protection is based on the possibility o correlating the circuit-breaker behaviour with the direction o the ault current whichpasses through it in relation to the reerence direction which can be set on the release.According to the direction o the current, it is possible to set two dierent trip times on the PR123 release:a time (t7Fw) in a direction concordant (Fw) with the reerence direction set;

    a time (t7Bw) in a dire