LOGSTOR FlexPipe
Flexible pre-insulated pipe systems for heating installations
Energy efficiency and flexibility
2187
Med
iegr
uppe
n 09
/13_
UK
• The protective casing pipe is made of low density polyethylene (PE-LD)
• LOGSTOR FlexPipes are available with service pipes of PEX, PEX/aluminium/PE, copper or steel, making it suitable for transportation of all kinds of liquids
• The insulation material is flexible polyurethane foam (PUR) with guaranteed insulation properties of lambda 0.022 W/mK
• Between the casing pipe and the PUR insulation LOGSTOR FlexPipes are fitted with a diffusion barrier to prevent diffusion of cell gases. Thus the pipes retain the same high insulation properties throughout their entire service life
Flexible pipe systems for many purposes
• PexFlex (with PEX service pipes)• AluFlex (with service pipes of PEX/
aluminium/PE)• CuFlex (with copper service pipes)• SteelFlex (with steel service pipes)
The choice of service pipe depends on the temperature and pressure of the individual pipe system.
PexFlex is also available for hot and cold domestic water supplies.
Easy to install and economical in operationMany years of experience from developing pre-insulated pipe systems enable us to produce the most energy efficient flexiblepipe systems that can remain buried for the next 30 years without unforeseen maintenance costs.
The pipes are avail able in coils of 50 or 100 meters, what minimizes the number of joints required.
LOGSTOR’s flexible pipe systems are avail able both as single and twin pipe solu-tions. LOGSTOR TwinPipes are particular-ly energy and cost-effective as heat loss is reduced to an absolute minimum – typical-ly by up to 48 percent, depending on the dimension. In addition, installation of Twin-Pipes require less space and less joints, reducing installation costs considerably.
Flexible, pre-insulated pipe systems are used for branch pipes in district heating pipelines. But they are also advantageous for smaller district heating systems with their own heat source, such as in summerhouses, pools, garages, greenhouses, market gardens, farms and residential areas. LOGSTOR’s product range includes four flexible systems:
FlexPipes are supplied in coils of 50 or 100 meters.
As an option PexFlex can be supplied in fixed lengths of between 10 and 90 meters.
Outer casing (PE-LD)
Diffusion barrier (aluminium foil or polymer foil)
Polyurethane foam (PUR) insulation
Service pipe (steel, copper, PEX or PEX/aluminium/PE)
Example:Savings achieved with LOGSTOR FlexPipe
Insulation type Heat loss in MWh Mineral wool 118.0Cellular plastic 107.1PexFlex, single pipe 64.4PexFlex, TwinPipe 33.8
Parameters:Energy price: 0.05 €/kWhPipe length: 40 mPipe type: PexFlex TwinPipe, Ø32 mm. Insulation Series 1
Savings using PexFlex TwinPipe compared to pipe with cellular plastic insulation amount to € 2,700 over 10 years.
Agriculture
Market
gardening
New residential areas
The LOGSTOR FlexPipe systems include the couplings, fittings and joints necessary for establishing any pipe network.
Schools
Types of pipes
SteelFlex
CuFlex
CuFlex, TwinPipe
AluFlex
AluFlex, TwinPipe
PexFlex
PexFlex DW, domestic water
PexFlex, TwinPipe
Optimum insulation properties and durability in a flexible packingDue to the flexibility of the service pipes in the LOGSTOR FlexPipe systems, they absorb the effects of temperature fluctuations and eliminate any need for expansion measures.
Casing pipes and insulation material are also flexible and the FlexPipes can be bent on site to fit into any trench.
FlexPipes are laid in traditional trenches or by means of tunnelling techniques, dependent on the surroundings and the soil.
With the programs LOGSTOR Calculator and StaTech, available on www.logstor.com, you can determine vital parameters such as pipe dimension, heat loss and statics.
Technical data
SteelFlex CuFlex AluFlexPexFlex DH
District heatingPexFlex DW
Domestic water
Coils of50 or 100 m
Coils of 50 or 100 m
Coils of50 or 100 m
Coils of50 or 100 m*
Coils of50 or 100 m
Dimensions mmService pipe/Outer casing
Dimensions mmService pipe/Outer casing
Dimensions mmService pipe/Outer casing
Dimensions mmService pipe/Outer casing
Dimensions mmService pipe/Outer casing
Single pipe Single pipe TwinPipe Single pipe TwinPipe Single pipe TwinPipe Single pipe
Double pipe
Series 1
Series 2
Series 1
Series 2
Series 1
Series 2
Series 1
Series 2
Series 1
Series 2
Series 1
Series 2
Series 1
Series 2
Series 1
Series 1
20/77 20/90 15/77 15/90 2x15/90 2x15/110 16/77 16/90 2x16/90 2x16/110 20/77 20/90 2x16/90 2x16/110 22/77 28-22/90
25/77 25/90 18/77 18/90 2x18/90 2x18/110 20/77 20/90 2x20/90 2x20/110 25/77 25/90 2x20/90 2x20/110 28/77 32-22/110
28/77 28/90 22/77 22/90 2x22/90 2x22/110 26/77 26/90 2x26/110 2x26/125 32/77 32/90 2x25/110 2x25/125 32/77 40-28/125
28/77 28/90 2x28/110 32/90 2x32/110 2x32/125 40/90 40/110 2x32/110 2x32/125 40/90 50-32/125
35/90 35/110 50/110 50/125 2x40/125 2x40/140 50/110
63/125 63/140 2x50/160 63/125
75/140 75/160
90/160
110/160
* Fixed lengths can be ordered to measure. Minimum 10 meters and maximum 90 meters.
Service pipe Steel, copper, PEX or PEX/Aluminium/PE
Insulation Polyurethane foam (PUR) using cyclopentane as blowing agent
Insulation value Thermal conductivity (50°C): </= 0.022 W/mK
Diffusion barrier Aluminium foil. PexFlex with polymer foil
Outer casing Polyethylene (PE-LD)
Alarm wires Copper. The Nordic system
LOGSTOR A/SDanmarksvej 11 · DK-9670 LøgstørTel. +45 9966 1000 · Fax +45 9966 [email protected] · www.logstor.com
2187
Med
iegr
uppe
n 09
/13_
UK