24
7/1 ABB | Catalog Electronic Products and Relays 2013/2014 | 2CDC 110 004 C0209 7 Logic relays Product group picture

Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

  • Upload
    lehanh

  • View
    227

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

7/1 ABB | Catalog Electronic Products and Relays 2013/2014 | 2CDC 110 004 C0209

7

Logic relaysProduct group picture

Page 2: Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

2CDC 110 004 C0209 | Catalog Electronic Products and Relays 2013/2014 | ABB 7/2

7

Logic relaysTable of contents

Logic relays

Product group picture 7/1

Table of contents 7/2

System overview 7/3

Approvals and marks 7/5

Ordering details - Stand alone logic relays 7/6

Ordering details - Expandable logic relays 7/7

Ordering details 7/8

Ordering details - Display systems 7/9

Technical data 7/10

Dimensional drawings 7/24

Page 3: Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

7/3 ABB | Catalog Electronic Products and Relays 2013/2014 | 2CDC 110 004 C0209

7

Logic relaysSystem overview

1SV

C 1

10 0

00 F

055

4

S1 K1 S4

S5

K1 K2 T1

T1

T1

S6

Documentation (download from the internet)

Logic relay manual 1SVC 440 795 M0100Remote display manual 1SVC 440 795 M2100Display system manual 1SVC 440 795 M1100

Concept

CL range logic relays are suitable for small and medium-sized control tasks and are able to substitute logic wiring in a quick and sim-ple manner.They can be used for applications in control as well as for timing func-tions, e. g. � in buildings, lighting systems, air-conditioning systems,

general control functions, � in small machines and systems or � as stand-alone control module for small applications.

Steps to the application of CL range

� CL range can be used easily, rapidly and comfortably without any time-consuming planning and programming.

� The user can discover the advantages and the benefit of these logic relays in no time at all.

� CL range provides for the control statements according to a simple circuit diagram.

� Setup, storage, simulation and documentation are performed using the compact and user-friendly CL-SOFT software (CL-LAS.PS002).

Software characteristics (CL-SOFT)

� display on a PC monitor according to IEC, ANSI � different languages to choose from � easy installation on all Microsoft WindowsTM operating systems

Logic links instead of wiring

Technical Data overviewLogic relays

� 8 or 12 digital inputs � 4 or 6 digital relay outputs � optionally with 4 or 8 transistor outputs � 128 rungs � 3 contacts as n/o or n/c contacts in series plus 1 coil per rung � optionally with 2 or 4 analog inputs (not 100-240 V AC version) � power flow display for checking the circuit diagram (devices with

display) � expansions for local or remote level � enclosure color RAL 7035 � DIN rail mounting

Display system

� useable as compact HMI logic relay � fully graphic, backlit display module � 12 digital inputs � 4 digital relay outputs � optionally with 4 transistor outputs � 256 rungs � 4 contacts as n/o or n/c contacts in series plus 1 coil per rung � optionally with 4 analog inputs (not 100-240 V AC version) � networking-compatible via CL-NET � front panel mounting � expansion for local

Remote display

� Remote display up to a distance of 5 m � Illustration of text and status displays � Remote adjustment via keypad � Front panel mounting

Software

� 16 timing relays 0.01-99:59 h � 16 counting relays for up-, down counting � 8 weekly timer, 8 annual timers � 16 analog value comparators � 16 freely editable display texts � 32 markers or auxiliary relays

Page 4: Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

2CDC 110 004 C0209 | Catalog Electronic Products and Relays 2013/2014 | ABB 7/4

7

Logic relaysSystem overview

Power

98a

8b

3

4

6, 8b

5

71b1a

2 2

6, 8b

5

98a

8b

Power

2CD

C 3

12 0

01 F

0b08

1a Logic relay CL-LS..1b Expandable logic relay CL-LM..2 Power supply CP-D...3 I/O expansion CL-LER.., CL-LET.. for logic relays CL-LM..4 Coupler unit CL-LEC.. for remote expansion of logic relays CL-LM..5 Memory module CL-LAS.MD003 for logic relays CL-LS.., CL-LM..6 Connecting cable CL-LAS.TK001, CL-LAS.TK002 to connect PC7 CL-LINK plug CL-LAS.TK011 to connect expansion to logic relays CL-LM..8a Remote display connection module CL-LDC.S..8b Connecting cable CL-LAD.TK007 to connect a remote displays to a logic relay9 Display module CL-LDD..

Logic relays

Stand alone Expandable

2b

1

3

2a

5

4

2CD

C 3

12 0

37 F

0b07

Expansion of logic relays*

1 Logic relay CL-LM..2 I/O expansion CL-LER.., CL-LET.. 2a local expansion 2b remote expansion3 Coupler unit CL-LEC.. for remote expansion of logic relays CL-LM..4 CL-LINK plug CL-LAS.TK011 for expansion of logic relays CL-LM..5 up to 30 m

* max. 1 expansion per logic relay

79

8

6

5

32

13

21

...4

4

CL-NET

10

2CD

C 3

12 0

25 F

0b06

1

2

3

2CD

C 3

12 0

27 F

0b06

32

1

32

1

4

...5 5

CL-NET

2CD

C 3

12 0

26 F

0b06

Stand alone with I/O module

Communication via CL-NET

1 Display CL-LDD..2 Remote display connection module CL-LDC.S.. incl. connecting cable3 Display base module CL-LDC.L..

1 Display module CL-LDD..2 Display base module CL-LDC.LN..3 Display I/O module CL-LDR.., CL-LDT..4 Termination resistor CL-LAD.TK0095 I/O expansion CL-LER.., CL-LET..6 Coupler unit CL-LEC.. for remote expansion7 Memory module CL-LAD.MD004 for display base module8 Connecting cable CL-LAD.TK002, CL-LAD.TK003, CL-LAD.TK0049 Connecting cable CL-LAD.TK001, CL-LAD.TK011 to connect PC10 CL-LINK plug CL-LAS.TK011 for expansion of logic relays CL-LM..K e.g. door of switchgear cabinet

Display system R Compact HMI logic relay

1 Display CL-LDD..2 Display base module CL-LDC.LN.. for CL-NET3 Display I/O module CL-LDR.., CL-LDT..4 Connecting cable CL-LAD.TK002, CL-LAD.TK003, CL-LAD.TK0045 Termination resistor CL-LAD.TK009

Page 5: Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

7/5 ABB | Catalog Electronic Products and Relays 2013/2014 | 2CDC 110 004 C0209

7

Logic relaysApprovals and marks

� existing j pending Logic relays Expansions Display system Accessories

Approvals CL-

LSR

CL-

LST

CL-

LMR

CL-

LMT

CL-

LER

CL-

LET

CL-

LEC

CL-

LDD

CL-

LDC

CL-

LDR

CL-

LDT

CL-

LAS

CL-

LAD

B UL � � � � � � � � � � � � 1) � 2)

F CAN/CSA C22.2 No.14 � � � � � � � � � � � � 1) � 2)

F CAN/CSA C22.2 No.213 (hazardous locations)

� � � � � � � � � � � � 1) � 2)

C GL � � � � � � 3) � 4) �

D GOST � 5) � 5) � 5) � 5) � 5) � 5) � 5) � 5) � 5) � 5) � 5) � 5) � 5)

P Lloyds Register � � � � � � 3) � 4) �

Marks

a CE � � � � � � � � � � � � �

b C-Tick k k k k k k k k k k k k k

1) not for: CL-LAS-PS002, CL-LAS.TD001, CL-LAS.FD001, CL-LAS.TK002, CL-LAS.TK011 2) not for: CL-LAD.TK006, CL-LAD.TK011, CL-LAD.FD0023) not for: CL-LDC.SDC2, CL-LDC.SAC2, CL-LDC.LAC2, CL-LDC.LNAC24) not for: CL-LDR.16AC25) May have been replaced by EAC during the availability of this catalog edition

Page 6: Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

2CDC 110 004 C0209 | Catalog Electronic Products and Relays 2013/2014 | ABB 7/6

7

Logic relaysOrdering details - Stand alone logic relays

Ordering details - Logic relays stand alone

Rated opera-tional voltage

Display+Keypad

Timer Input /Output

Type Order code Price

1 pce

Weight(1 pce)kg (lb)

24 V AC� �

8 inputs / 4 relay outputs

CL-LSR.C12AC1 1SVR440712R0300

0.20 (0.44)

� CL-LSR.CX12AC1 1SVR440712R0200

100-240 V AC

� CL-LSR.12AC2 1SVR440713R0100

� � CL-LSR.C12AC2 1SVR440713R0300

� CL-LSR.CX12AC2 1SVR440713R0200

12 V DC� � CL-LSR.C12DC1 1SVR440710R0300

� CL-LSR.CX12DC1 1SVR440710R0200

24 V DC

� CL-LSR.12DC2 1SVR440711R0100

� CL-LSR.C12DC2 1SVR440711R0300

� CL-LSR.CX12DC2 1SVR440711R0200

24 V DC� � 8 inputs /

4 transistor outputs

CL-LST.C12DC2 1SVR440711R1300

� CL-LST.CX12DC2 1SVR440711R1200

Ordering details - Display modules

Rated opera-tional voltage

Description Type Order code Price

1 pce

Weight(1 pce)kg (lb)

- Graphic display 132 x 64 pixel CL-LDD.XK 1SVR440839R4500 0.14 (0.30)

-Graphic display 132 x 64 pixel, with keypad

CL-LDD.K 1SVR440839R4400 0.13 (0.29)

24 V DC Module to displace the display from the logic relay, incl. connecting cable CL-LAD.TK007, 5m, lenght adaptable

CL-LDC.SDC2 1SVR440841R0000 0.16 (0.36)

100-240 V DC CL-LDC.SAC2 1SVR440843R0000 0.16 (0.36)

CL-LSR

CL-LST

CL-LDD.K

CL-LDC.S..

2CD

C 2

81 0

34 F

0006

2CD

C 2

81 0

33 F

0006

2CD

C 2

81 0

28 F

0006

2CD

C 2

81 0

17 F

0007

Page 7: Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

7/7 ABB | Catalog Electronic Products and Relays 2013/2014 | 2CDC 110 004 C0209

7

Logic relaysOrdering details - Expandable logic relays

Ordering details - Logic relays expandable

Rated opera-tional voltage

Display+Keypad

Timer Input /Output

Type Order code Price

1 pce

Weight(1 pce)kg (lb)

24 V AC� �

12 inputs / 6 relay outputs

CL-LMR.C18AC1 1SVR440722R0300

0.36 (0.79)

� CL-LMR.CX18AC1 1SVR440722R0200

100-240 V AC

� � CL-LMR.C18AC2 1SVR440723R0300

� CL-LMR.CX18AC2 1SVR440723R0200

12 V DC� � CL-LMR.C18DC1 1SVR440720R0300

� CL-LMR.CX18DC1 1SVR440720R0200

24 V DC� � CL-LMR.C18DC2 1SVR440721R0300

� CL-LMR.CX18DC2 1SVR440721R0200

24 V DC� � 12 inputs,

8 transistor outputs

CL-LMT.C20DC2 1SVR440721R13000.36 (0.79)

� CL-LMT.CX20DC2 1SVR440721R1200

Ordering details - Expansions

Rated opera-tional voltage

Description Type Order code Price

1 pce

Weight(1 pce)kg (lb)

- 2 relay outputs CL-LER.2O 1SVR440709R5000 0.07 (0.15)

100-240 V AC

12 inputs, 6 relay outputsCL-LER.18AC2 1SVR440723R0000 0.26 (0.57)

24 V DC CL-LER.18DC2 1SVR440721R0000 0.22 (0.49)

24 V DC 12 inputs, 8 transistor outputs CL-LET.20DC2 1SVR440721R1000 0.21 (0.46)

-Coupler unit for remote expansion with a distanceof up to 30 m

CL-LEC.CI000 1SVR440709R0000 0.07 (0.15)

CL-LER

CL-LEC

CL-LMR

2CD

C 3

11 0

36 F

0006

2CD

C 3

11 0

37 F

0007

2CD

C 3

11 0

38 F

0006

Page 8: Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

2CDC 110 004 C0209 | Catalog Electronic Products and Relays 2013/2014 | ABB 7/8

7

Logic relaysOrdering details

Ordering details - CL-LA...

Description Type Order code Price

1 pce

Weight(1 pce)kg (lb)

Software for programming and control of CL range devices. Installation CD-ROM for Microsoft WindowsTM.

CL-LAS.PS002 1SVR440799R8000 0.10 (0.21)

Memory module for logic relaysMemory size: 32 kB CL-LAS.MD003 1SVR440799R7000 0.02 (0.04

Cable with serial interface to connect PC and logic relay. Length: 2 m CL-LAS.TK001 1SVR440799R6000 0.10 (0.22)

Cable with USB interface to connect PC and logic relay. Length: 2 m CL-LAS.TK002 1SVR440799R6100 0.06 (0.13)

Cable for point-to-point connection of remote-display connection module and logic relay, length: 5m, adaptable

CL-LAD.TK007 1SVR440899R6600 0.20 (0.44)

Fixing brackets for screw mounting of logic relay, expansion, display base module CL-LAS.FD001 1SVR440799R5000 0.01 (0.01)

Spare plug (CL-LINK) for connection of logic relay to expansion CL-LAS.TK011 1SVR440799R5100 0.10 (0.22)

Primary switch mode power supplies, Rated input voltage: 100-240 V ACRated output voltage/current: 24 V DC / 0.42 A

CP-D 24/0.421) 1SVR427041R0000 0.06 (0.13)

Primary switch mode power supplies, Rated input voltage: 100-240 V ACRated output voltage/current: 24 V DC / 1.3 A

CP-D 24/1.32) 1SVR427043R0100 0.19 (0.41)

1) replaces CL-LAS.SD001, technical data see chapter “Primary switch mode power supplies”2) replaces CL-LAS.SD002, technical data see chapter “Primary switch mode power supplies”

CL-LAS.PS002

CL-LAS.MD003

CL-LAS.TK001

2CD

C 3

11 0

12 F

0007

2CD

C 3

11 0

13 F

0007

2CD

C 3

11 0

14 F

0007

Page 9: Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

7/9 ABB | Catalog Electronic Products and Relays 2013/2014 | 2CDC 110 004 C0209

7

Ordering details - Display systems

Rated opera-tional voltage

Description Type Order code Price

1 pce

Weight(1 pce)kg (lb)

-Display module Graphic display 132 x 64 pixel

CL-LDD.XK 1SVR440839R4500 0.14 (0.30)

-Display module Graphic display 132 x 64 pixel, with keypad

CL-LDD.K 1SVR440839R4400 0.13 (0.29)

24 V DC Display base module CPU / power supply

CL-LDC.LDC2 1SVR440821R00000.16 (0.36)

100-240 V AC CL-LDC.LAC2 1SVR440823R0000

24 V DC Display base module CPU / power supply, networ-king-compatible (CL-NET)

CL-LDC.LNDC2 1SVR440821R10000.17 (0.38)

100-240 V AC CL-LDC.LNAC2 1SVR440823R1000

100-240 V AC Display I/O module12 inputs, 4 relay outputs

CL-LDR.16AC2 1SVR440853R00000.17 (0.38)

24 V DC CL-LDR.16DC2 1SVR440851R0000

24 V DCDisplay I/O module 12 inputs, 4 relay outputs, 1 analog output

CL-LDR.17DC2 1SVR440851R2000 0.17 (0.38)

24 V DCDisplay I/O module 12 inputs, 4 transistor outputs

CL-LDT.16DC2 1SVR440851R1000 0.14 (0.30)

24 V DCDisplay I/O module 12 inputs, 4 transistor out-puts, 1 analog output

CL-LDT.17DC2 1SVR440851R3000 0.14 (0.30)

Logic relaysOrdering details - Display systems

CL-LDD.K

CL-LDC.LN..

2CD

C 3

11 0

28 F

0006

2CD

C 3

11 0

31 F

0006

Ordering details - CL-LAD...

Description Type Order code Price

1 pce

Weight(1 pce)kg (lb)

Memory module for display base modules Memory size: 256 kB CL-LAD.MD004 1SVR440899R7000 0.02 (0.03)

Cable with serial interface to connect PC and display base module CL-LAD.TK001 1SVR440899R6000 0.11 (0.23)

Cable with USB interface to connect PC and display base module CL-LAD.TK011 1SVR440899R6700

Network cable (CL-NET) to connect 2 display base modules Length: 0.3 m CL-LAD.TK002 1SVR440899R6100 0.05 (0.12)

Network cable (CL-NET) to connect 2 display base modules Length: 0.8 m CL-LAD.TK003 1SVR440899R6200 0.07 (0.14)

Network cable (CL-NET) to connect 2 display base modules Length: 1.5 m CL-LAD.TK004 1SVR440899R6300 0.08 (0.18)

Cable for point-to-point connection of remote display connection modules and display base module, length adaptable, Length: 5 m

CL-LAD.TK005 1SVR440899R6400 0.20 (0.44)

Cable for point-to-point connection of 2 display base modules, length adaptable. Length: 5 m

CL-LAD.TK006 1SVR440899R6500 0.12 (0.26)

Termination resistor, content: 2 pieces CL-LAD.TK009 1SVR440899R6900 0.01 (0.02)

Protective cover, transparent, for harsh envi-ronmental conditions and application in the food industry

CL-LAD.FD001 1SVR440899R1000 0.03 (0.07)

Protective cover, transparent and sealable CL-LAD.FD011 1SVR440899R2000 0.03 (0.07)

Assembly tool for mounting of display mo-dules CL-LAD.FD002 1SVR440899R3000

CL-LAD.MD004

CL-LAD.TK001

CL-LAD.TK002

2CD

C 3

11 0

18 F

0007

2CD

C 3

11 0

19 F

0007

2CD

C 3

11 0

20 F

0006

Page 10: Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

2CDC 110 004 C0209 | Catalog Electronic Products and Relays 2013/2014 | ABB 7/10

7

Logic relaysTechnical data

Data at Ta = 25 °C and rated values, if nothing else indicated.

Type CL-LSR.C...12DC1 CL-LSR....12DC2 CL-LST.C...12DC2 CL-LSR.C...12AC1 CL-LSR...12AC2

Input circuit - supply circuitRated operational voltage Ue 12 V DC 24 V DC 24 V AC 100-240 V ACRated operational voltage tolerance -15...+30 % -15...+20 % -15...+10 %Operational voltage range 10.2-15.6 V DC 20.4-28.8 V DC 20.4-26.4 V AC 85-264 V ACRated frequency 0 Hz 50/60 HzRated frequency tolerance - ±5 %Residual ripple m 5 % -Input current at 12 V DC typ. 140 mA - - -

at 24 V DC - typ. 80 mA - -at 24 V AC - - typ. 200 mA -

at 115/120 V AC (60 Hz) - - - typ. 40 mAat 230/240 V AC (50 Hz) - - - typ. 20 mA

Power failure buffering (IEC/EN 61131-2) 10 ms 20 msPower dissipation at 12 V DC typ. 2 W - - -

at 24 V DC - typ. 2 W - -at 24 V AC - - typ 5 VA -

at 115/120 V AC - - - typ. 5 VAat 230/240 V AC - - - typ. 5 VA

Type CL-LMR.C...18DC1 CL-LMR.C...18DC2 CL-LMT.C...20DC2 CL-LMR.C...18AC1 CL-LMR.C...18AC2

Input circuit - supply circuitRated operational voltage Ue 12 V DC 24 V DC 24 V AC 100-240 V ACRated operational voltage tolerance -15...+30 % -15...+20 % -15...+10 %Operational voltage range 10.2-15.6 V DC 20.4-28.8 V DC 20.4-26.4 V AC 85-264 V ACRated frequency 0 Hz 50/60 HzRated frequency tolerance - ±5 %Residual ripple m 5 % -Input current at 12 V DC typ. 200 mA - - -

at 24 V DC - typ. 140 mA - -at 24 V AC - - typ. 300 mA -

at 115/120 V AC (60 Hz) - - - typ. 70 mAat 230/240 V AC (50 Hz) - - - typ. 35 mA

Power failure buffering (IEC/EN 61131-2) 10 ms 20 msPower dissipation at 12 V DC typ. 3.5 W - - -

at 24 V DC - typ. 3.5 W - -at 24 V AC - - typ. 7 VA -

at 115/120 V AC - - - typ. 10 VAat 230/240 V AC - - - typ. 10 VA

Type CL-LER.18DC2 CL-LET.20DC2 CL-LER.18AC2

Input circuit - supply circuitRated operational voltage Ue 24 V DC 100-240 V ACRated operational voltage tolerance -15...+20 % -15...+10 %Operational voltage range 20.4-28.8 V DC 85-264 V ACRated frequency 0 Hz 50/60 HzRated frequency tolerance - ±5 %Residual ripple m 5 % -Input current at 24 V DC typ. 140 mA -

at 115/120 V AC (60 Hz) - typ. 70 mAat 230/240 V AC (50 Hz) - typ. 35 mA

Power failure buffering (IEC/EN 61131-2) 10 ms 20 msPower dissipation at 24 V DC typ. 3.4 W -

at 115/120 V AC - typ. 10 VAat 230/240 V AC - typ. 10 VA

Page 11: Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

7/11 ABB | Catalog Electronic Products and Relays 2013/2014 | 2CDC 110 004 C0209

7

Logic relaysTechnical data

Data at Ta = 25 °C and rated values, if nothing else indicated.

Type CL-LSR.C...12DC1 CL-LSR....12DC2 CL-LST.C...12DC2 CL-LSR.C...12AC1 CL-LSR.C...12AC2

Input circuit - Digital inputs 12 V DC 24 V DC 24 V AC 115 / 230 V AC

Number 8

Inputs can be used as analog inputs 2 (I7, I8) -

Indication of operational states LCD-Display (if existing)

Electrical isolation from voltage supply no

between digital inputs no

from the outputs yes

Rated operational voltage Ue

12 V DC 24 V DC 24 V AC

Ue on „0“ signal 4 V DC (I1-I8) < 5 V DC (I1-I8) 0-6 V AC (sinusoidal) 0-40 V AC (sinusoidal)

Ue on „1“ signal8 V DC (I1-I8)

> 15 V DC (I1-I6), > 8 V DC (I7, I8)

> 9,5 V DC, 14-26,4 V AC (sinusoidal) (I1-I6), > 7 V AC (sinusoidal) (I7,I8)

79-264 V AC (sinusoidal)

Rated frequency - 50-60 Hz

Input current on „1“ signal

3.3 mA (at 12 V DC, I1-I6), 1.1 mA (at 12 V DC, I7, I8)

3.3 mA (at 24 V DC, I6-I7), 2.2 mA (at 24 V DC, I7, I8)

4 mA (at 24 V AC, 50 Hz, I1-I6),2 mA (at 24 V AC, 50 Hz, I7,I8),2 mA (at 24 V DC, I7, I8)

6x0.25 mA (at 115 V AC, 60 Hz, I1-I6), 6x0.5 mA (at 230 V AC, 50 Hz, I1-I6)2x4 mA (at 115 V AC, 60 Hz, I7, I8), 2x6 mA (at 230 V AC, 50 Hz, I7, I8)

Time delay from „0“ to „1“

debounce ON 20 ms 80 ms (at 50 Hz), 66 2/3 ms (at 60 Hz)

debounce OFF typ. 0.3 ms (I1-I6), typ. 0.35 ms (I7, I8)

typ. 0,25 ms (I1-I8) 20 ms (at 50 Hz), 16 2/3 ms (at 60 Hz)

Time delay from „1“ to „0“

debounce ON

20 ms80 ms (at 50 Hz, 66 2/3 ms (at 60 Hz)

80 ms (at 50 Hz, I1-I6), 66 2/3 ms (at 60 Hz, I1-I6)160 ms (at 50 Hz, I7, I8), 150 ms (at 60 Hz, I7, I8)

debounce OFFtyp. 0.3 ms (I1-I6),typ. 0.15 ms (I7, I8)

-20 ms (at 50 Hz), 16 2/3 ms (at 60 Hz)

20 ms (at 50 Hz, I1-I6), 16 2/3 ms (at 60 Hz, I1-I6)100 ms (at 50 Hz, I7. I8), 100 ms (at 60 Hz, I7, I8)

Cable length (unshielded) 100 m - -

Maximum cable length per input - 40 m 40 m (I1-I6), 100 m (I7, I8)

Frequency counter Number 2 (I3, I4) - -

counting frequency < 1 kHz - -

pulse shape square-wave - -

pulse / pause ratio 1:1 - -

Rapid counter inputs Number 2 (I1, I2) - -

counting frequency < 1 kHz - -

pulse shape square-wave - -

pulse / pause ratio 1:1 - -

Cable length (shielded) < 20 m - -

Input circuit - Analog inputs

Number 2 (I7, I8) -

Electrical isolation from voltage supply no -

from the digital inputs no -

from the outputs yes -

from PC interface, memory module, CL-NET, CL-LINK no -

Input type DC voltage -

Signal range 0-10 V DC -

Resolution analog 0.01 V -

digital 0.01 V; 10 Bit (value 1-1023) -

Input impedance 11.2 kq -

Accuracy of the actual value

two CL devices ±3 % -

within one device ±2 %, ±0.12 V -

Conversion time analog/digital

Input delay ON 20 ms -

Input delay OFF each cycle -

Input current < 1 mA -

Cable length (shielded) < 30 m -

Page 12: Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

2CDC 110 004 C0209 | Catalog Electronic Products and Relays 2013/2014 | ABB 7/12

7

Logic relaysTechnical data

Data at Ta = 25 °C and rated values, if nothing else indicated.

Type CL-LMR.C...18DC1 CL-LMR.C...18DC2 CL-LMT.C...20DC2 CL-LMR.C...18AC1 CL-LMR.C...18AC2

Input circuit - Digital inputs 12 V DC 24 V DC 24 V AC 115 / 230 V ACNumber 12

Inputs can be used as analog inputs 4 (I7, I8, I11, I12) -

Indication of operational states LCD-Display (if existing)

Electrical isolation from voltage supply no

between digital inputs no

from the outputs yes

from PC interface, memory module, CL-NET, CL-LINK no yes

Rated operational voltage Ue

12 V DC 24 V DC 24 V AC

Ue on „0“ signal 4 V DC (I1-I12) < 5 V DC (I1-I12, R1-R12) 0-6 V AC (sinusoidal) 0-40 V AC (sinusoidal)

Ue on „1“ signal

8 V DC (I1-I12)> 15 V DC (I1-I6, I9, I10) > 8 V DC (I7, I8, I11, I12)

> 9.5 V DC, 14-26.4 V AC (sinusoidal) (I1-I6, I9, I10) > 7 V AC (sinusoidal) (I7,I8; I11, I12)

79-264 V AC (sinusoidal)

Rated frequency - 50-60 Hz

Input current on „1“ signal

3.3 mA (at 12 V DC, I1-I6, I9-I12),1.1 mA (at 12 V DC, I7, I8)

3.3 mA (at 24 V DC, I1-I6, I9, I10), 2.2 mA (at 24 V DC, I7, I8, I11, I12)

4 mA (at 24 V AC, 50 Hz, I1-I6, I9, I10), 2 mA (at 24 V AC, 50 Hz, I7, I8, I11, I12), 2 mA (at 24 V DC, I7, I8, I11, I12)

6x0.25 mA (at 115 V AC, 60 Hz, I1-I6), 6x0.5 mA (at 230 V AC, 50 Hz, I1-I6) 2x4 mA (at 115 V AC, 60 Hz, I7, I8), 2x6 mA (at 230 V AC, 50 Hz, I7, I8), 4x0.25 mA (at 115 V AC, 60 Hz, I9-I12), 4x0.5 mA (at 230 V AC, 50 Hz, I9-I12)

Time delay from „0“ to „1“

debounce ON 20 ms 80 ms (at 50 Hz), 66 2/3 ms (at 60 Hz)

debounce OFF typ. 0.3 ms (I1-I6, I9, I10), typ. 0.35 ms (I7, I8, I11, I12)

typ. 0.25 ms 20 ms (at 50 Hz), 16 2/3 ms (at 60 Hz)

Time delay from „1“ to „0“

debounce ON 20 ms 80 ms (at 50 Hz), 66 2/3 ms (at 60 Hz)

debounce OFF typ. 0.4 ms (I1-I6, I9, I10), typ. 0.35 ms (I7, I8, I11, I12)

- 20 ms (at 50 Hz), 16 2/3 ms (at 60 Hz)

Cable length (unshielded) 100 m

Maximum cable length per input max. 40 m, typ. 40 m (I9, I10)

typ. 40 m (I1-I6, I9-I12), typ. 100 m (I7, I8)

Frequency counter number 2 (I3, I4) - -

counting frequency < 1 kHz - -

pulse shape square-wave - -

pulse / pause ratio 1:1 - -

Rapid counter inputs number 2 (I1, I2) - -

counting frequency < 1 kHz - -

pulse shape square-wave - -

pulse / pause ratio 1:1 - -

Cable length (shielded) < 20 m - -

Input circuit - Analog inputsNumber 4 (I7, I8, I11, I12) -

Electrical isolation from voltage supply no -

from the digital inputs no -

from the outputs yes -

from PC interface, memory module, CL-NET, CL-LINK no -

Input type DC voltage -

Signal range 0-10 V DC -

Resolution analog 0.01 V -

digital 0.01 V; 10 Bit (value 1-1023) -

Input impedance 11.2 kq -

Accuracy of the actual value

two CL devices ±3 % -

within one device ±2 %, ±0.12 V -

Conversion time analog/digital

Input delay ON 20 ms -

Input delay OFF each cycle -

Input current < 1 mA -

Cable length (shielded) < 30 m -

Page 13: Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

7/13 ABB | Catalog Electronic Products and Relays 2013/2014 | 2CDC 110 004 C0209

7

Logic relaysTechnical data

Data at Ta = 25 °C and rated values, if nothing else indicated.

Type CL-LER.18DC2 CL-LET.20DC2 CL-LER.18AC2

Input circuit - Digital inputs 24 V DC 115 / 230 V ACNumber 12

Inputs can be used as analog inputs -

Indication of operational states -

Electrical isolation from voltage supply no

between digital inputs no

from the outputs yes

from PC interface, memory module, CL-NET, CL-LINK no

Rated operational voltage Ue

24 V DC

Ue on „0“ signal < 5 V DC (I1-I12, R1-R12) 0-40 V AC (sinusoidal)

Ue on „1“ signal - 79-264 V AC (sinusoidal)

Rated frequency - 50-60 Hz

Input current on „1“ signal

3.3 mA (at 24 V DC, R1-R12)

12x0.25 mA

(at 115 V AC, 60 Hz, R1-R12),

12x0.5 mA

(at 230 V AC, 50 Hz, R1-R12)

Time delay from „0“ to „1“

debounce ON20 ms

80 ms (at 50 Hz, I1-I12, R1-R12),

66 2/3 ms (at 60 Hz, I1-I12, R1-R12)

debounce OFFtyp. 0.25 ms (R1-R12)

20 ms (at 50 Hz, I1-I12, R1-R12),

16 2/3 ms (at 60 Hz, I1-I12, R1-R12)

Time delay from „1“ to „0“

debounce ON20 ms

80 ms (at 50 Hz, I1-I12, R1-R12),

66 2/3 ms (at 60 Hz, I1-I12, R1-R12)

debounce OFF-

20 ms (at 50 Hz, I1-I12, R1-R12),

16 2/3 ms (at 60 Hz, I1-I12, R1-R12)

Cable length (unshielded) 100 m -

Maximum cable length per input-

typ. 40 m (I1-I6, I9-I12, R1-R12),

typ. 100 m (I7, I8)

Page 14: Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

2CDC 110 004 C0209 | Catalog Electronic Products and Relays 2013/2014 | ABB 7/14

7

Logic relaysTechnical data

Data at Ta = 25 °C and rated values, if nothing else indicated.

Type CL-LSR... CL-LMR... CL-LER... CL-LER.2O

Output circuit - Relay outputs

Number 4 6 2

Outputs in groups of 1 2

Parallel switching of outputs to increase capacity not permissible

Fusing of the output relay circuit-breaker B16 or fuse 8 A (slow-acting)

Electrical isolation from voltage supply yes

from the inputs yes

from PC interface, memory module, CL-NET, CL-LINK no

protective separation 300 V AC

basic isolation 600 V AC

Mechanical lifetime 10x106 switching cycles

Rung conventional thermal current (10 A UL) 8 A

recommended for load 12 V AC/DC > 500 mA

short-circuit proof cos j = 1; characteristic B16 at 600 A

16 A

short-circuit proof cos j = 0,5 up to 0,7; characteristic B16 at 900 A

16 A

Rated impulse withstand voltage Uimp contact-coil 6 kV

Rated operational voltage Ue 250 V AC

Rated insulation voltage Ui 250 V AC

Protective separation (EN 50178) between coil and contact 300 V AC

between two contacts 300V AC

Making capacity AC15, 250 V AC, 3 A (600 ops./h) 300.000 switching cycles

DC13, L/R m 150 ms, 24 V DC, 1 A (500 ops./h) 200.000 switching cycles

Breaking capacity AC15, 250 V AC, 3 A (600 ops./h) 300.000 switching cycles

DC13, L/R m 150 ms, 24 V DC, 1 A (500 ops./h) 200.000 switching cycles

Incandesent lamp load 1000 W at 230/240 V AC 25.000 switching cycles

500 W at 115/120 V AC 25.000 switching cycles

Fluorescent lamp load 10 x 58 W at 230/240 V AC with electrical control gear

25.000 switching cycles

10 x 58 W at 230/240 V AC uncompensated

25.000 switching cycles

1 x 58 W at 230/240 V AC conventional compensated

25.000 switching cycles

Switching frequency mechanical operations 10x106

switching frequency 10 Hz

resistive load / lamp load 2 Hz

inductive load 0.5 Hz

UL/CSA

Continuous current at 240 V 10 A AC

Continuous current at 24 V 8 A DC

AC Utilization catagory (Control Circuit Rating Codes) B 300 Light Pilot Duty

max. rated operational voltage 300 V AC

max. continuous thermal current cos j = 1 at B 300

5 A

max. making / breaking apparent power (Make/Break) cos j ≠ 1 at B 300

3600/360 VA

DC Utilization catagory (Control Circuit Rating Codes) R 300 Light Pilot Duty

max. rated operational voltage 300 V DC

max. continuous thermal current at R 300 1 A

max. making / breaking apparent power (Make/Break) at R 300

28/28 VA

Page 15: Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

7/15 ABB | Catalog Electronic Products and Relays 2013/2014 | 2CDC 110 004 C0209

7

Logic relaysTechnical data

Data at Ta = 25 °C and rated values, if nothing else indicated.

Type CL-LST... CL-LMT... CL-LET...

Output circuit - Transistor outputs

Number 4 8

Rated operational voltage Ue 24 V DC

Operational voltage range 20.4-28.8 V DC

Residual ripple m 5 %

Supply current on „0“ signal typ. 9 mA / max. 16 mA

typ. 18 mA / max. 32 mA

on „1“ signal typ. 12 mA / max. 22 mA

typ. 24 mA / max. 44 mA

Reverse voltage protection yes (Attention: If supply voltage is reversed, applying voltage at the outputs, causes a short circuit.)

Electrical isolation from voltage supply yes

from the inputs yes

from PC interface, memory module, CL-NET, CL-LINK

-

Rated operational current Ie on„1“ signal DC max. 0.5 A

Lamp load without Rv 5 W

Residual current on „0“ signal per channel < 0.1 mA

Max. output voltage on „0“ signal at external load < 10 Mq 2.5 V

on „1“ signal at Ie = 0.5 A U = Ue - 1 V

Short-circuit protection yes, thermal (analysis results from diagnosis input I16, I15; R15, R16)

Short-circuit tripping current for Ra m 10 mq 0.7 A m Ie m 2 A per output

Total short-circuit current 8 A 16 A

Peak short-circuit current 16 A 32 A

Thermal tripping yes

Max. switching frequency with constant resistive load RL < 100 kq (depending on active channels and their load)

40.000 switching cycles/h

Parallel connection of outputs with resistive load, inductive load with external suppressor, combination within one group

group 1: Q1-Q4group 1: Q1-Q4, group 2: Q5-Q8

group 1: S1-S4, group 2: S5-S8

number of outputs max. 4

max. total current 2 A (Attention! Outputs must be actuated simultaneously and for the same length of time.)

Indication of operational states of the outputs LCD-Display (if existing)

Inductive load1) without external suppressor

T0.95 = 1 ms, R = 48 q, L = 16 mH

utilization factor 0.25 g

duty time 100 %

max. switching frequency f = 0,5 Hz (max. duty time = 50 %)

1500 switching cycles

DC13, T0.95 = 72 ms, R = 48 q, L = 1.15 H

utilization factor 0.25 g

duty time 100 %

max. switching frequency f = 0,5 Hz (max. duty time = 50 %)

1500 switching cycles

T0.95 = 15 ms, R = 48 q, L = 0.24 H

utilization factor 0.25 g

duty time 100 %

max. switching frequency f = 0,5 Hz (max. duty time = 50 %)

1500 switching cycles

Inductive load1) with external suppressor

demand factor 1 g

duty time 100 %

max. switching frequency max. duty time

depends on suppressor

1) For inductive loading, without external suppression of the transistor outputs, the following applies: T0.95 = time in ms, until 95 % of the steady-state current is achieved. T0.95 3 × T0.65 = 3 × L/R.

Data transfer rate in the CL-NET network: bus lengths of 40 m and over only attainable with cables with additional cross-section and connection adapter.

Page 16: Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

2CDC 110 004 C0209 | Catalog Electronic Products and Relays 2013/2014 | ABB 7/16

7

Logic relaysTechnical data

Data at Ta = 25 °C and rated values, if nothing else indicated.

Type CL-LSR..., CL-LST... CL-LMR... CL-LMT.. CL-LET.., CL-LER.18..

CL-LER.2O CL-LEC.CI000

General dataDimensions (W x H x D) 71.5 mm x 90 mm x 58 mm

(2.81 inch x 3.54 inch x 2.28 inch)107.5 mm x 90 mm x 58 mm (4.23 inch x 3.54 inch x 2.28 inch)

35.5 mm x 90 mm x 58 mm (1.40 inch x 3.54 inch x 2.28 inch)

Weight 0.2 kg (0.44 lb) 0.3 kg (0.66 lb) 0.07 kg (0.15 lb)Mounting DIN rail (IEC/EN 60715),

35 mm or screw mounting with fixing brackets CL-LAS.FD001 (accessories)Mounting position horizontal / vertical

Electrical connectionWire size rigid 0.2-4 mm2 (22–12 AWG)

fine-strand with wire end ferrule 0.2-2.5 mm2 (22–12 AWG)Max. tightening torque 0.6 Nm

Environmental dataAmbient temperature range operation -25...+55 °C, cold acc. to IEC 60068-2-1, heat acc. to IEC 60068-2-2

storage -40...+70 °CLCD-Display (clearly legible) 0...+55 °CCondensation avoid condensation with suitable methodsHumidity, no condensation (IEC/EN 60068-2-30) 5-95 %Air pressure (operation) 795-1080 hPaDegree of protection (IEC/EN 60529) IP20Vibration (IEC/EN 60068-2-6) 10-57 Hz (constant amplitude 0.15 mm), 57-150 Hz (constant acceleration 2 g)Shock resistance (half-sine 15 g / 11 ms) (IEC/EN 60068-2-27) 18 ShocksDrop (IEC/EN 60068-2-31) height of fall 50 mmFree fall, packaged (IEC/EN 60068-2-32) 1 m

Insulation dataOvervoltage category IIPollution degree (DIN EN 60947) 2Rating of air and creepage distances EN 50178, UL 508, CSA C22.2, No. 142Insulation resistance EN 50178

StandardsStandards and directives EN 55011, EN 55022, IEC/EN 61000-4, IEC 60068-2-6, IEC 60068-2-27

Electromagnetic compatibilityInterference immunity

electrostatic discharge (ESD) IEC/EN 61000-4-2 Level 3 (air discharge 8 kV, contact discharge 6 kV)electromag. field (HF radiation resistance) IEC/EN 61000-4-3 10 V/mfast transients (Burst) IEC/EN 61000-4-4 Level 3 (supply cable 2 kV, signal lines 2 kV)powerful impulses (Surge) IEC/EN 61000-4-5 supply cable symmetrical (AC) 2 kV,

Level 2 (supply cable symmetrical (DC) 0.5 kV)HF line emission IEC/EN 61000-4-6 10 V

Interference suppression (EN 55011, EN 55022) class B

Real time clockBack-up time see diagram -Accuracy typ. ±5 (±0.5 h/year) -

Repeat accuracy of the time relayAccuracy (from value) ±1 -Resolution range „S“ 10 ms -

range „M:S“ 1 s -range „H:M“ 1 min -

Retention behaviourWrite cycles of retention memory (minimum) 1.000.000 (106) -

180200

160140120100806040200

55 ˚C

25 ˚C

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Buf

fer

time

(hou

rs)

2CD

C 3

12 0

23 F

0206

Operating time (years)

Technical diagram

Back-up time of the real time clock

Page 17: Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

7/17 ABB | Catalog Electronic Products and Relays 2013/2014 | 2CDC 110 004 C0209

7

Logic relaysTechnical data

Data at Ta = 25 °C and rated values, if nothing else indicated.

Type CL-LDD...

Input circuit - Supply circuit

Power failure buffering (IEC/EN 61131-2) 10 ms

General data

Dimensions (W x H x D) with keypad: 86.5 x 86.5 x 21.5 mm (3.41 x 3.41 x 0.85 inch)without keypad: 86.5 x 86.5 x 20 mm (3.41 x 3.41 x 0.79 inch)

Weight 0.13 kg (0.29 lb)

Mounting 2 x 22.5 mm, with 2 retainers screwed

Mounting position horizontal / vertical

Environmental data

Ambient temperature range operation -25...+55 °C (cold acc. to IEC 60068-2-1, heat acc. to IEC 60068-2-2)

storage -40...+70 °C

LCD-Display (clearly legible) -5...+50 °C,-10...0 °C (with backlit / continuous operation)

Condensation avoid condensation with suitable methods

Humidity, no condensation (IEC/EN 60068-2-30) 5-95 %

Air pressure (operation) 795-1080 hPa

Degree of protection (IEC/EN 60529) IP65

Vibration (IEC/EN 60068-2-6) 10-57 Hz (constant amplitude 0.15 mm), 57-150 Hz (constant acceleration 2 g)

Shock resistance (half-sine 15 g / 11 ms) (IEC/EN 60068-2-27) 18 Shocks

Drop (IEC/EN 60068-2-31) height of fall 50 mm

Free fall, packaged (IEC/EN 60068-2-32) 1 m

Insulation data

Pollution degree (DIN EN 60947) 3

Rating of air and creepage distances EN 50178, UL 508, CSA 22.2, No 142

Insulation resistance EN 50178

Standards

Standards and directives EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, IEC 60068-2-6, IEC 60068-2-27

Electromagnetic compatibility

Interference immunity

electrostatic discharge (ESD) IEC/EN 61000-4-2 Level 3 (air discharge 8 kV, contact discharge 6 kV)

electromag. field (HF radiation resistance) IEC/EN 61000-4-3 10 V/m

fast transients (Burst) IEC/EN 61000-4-4 Level 3 (supply cable 2 kV, signal lines 2 kV)

powerful impulses (Surge) IEC/EN 61000-4-5 Level 3 (supply cable symmetrical 2 kV, CL-LDC.L...AC2)

Level 2 (0.5 kV supply cable symmetrical, CL-LDC.L...AC2)

HF line emission IEC/EN 61000-4-6 10 V

Interference suppression (EN 55011, EN 55022) class B

Page 18: Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

2CDC 110 004 C0209 | Catalog Electronic Products and Relays 2013/2014 | ABB 7/18

7

Logic relaysTechnical data

Data at Ta = 25 °C and rated values, if nothing else indicated.

Type CL-LDC.SDC2 CL-LDC.SAC2 CL-LDC.LDC2 CL-LCD.LAC2 CL-LDC.LNDC2 CL-LDC.LNAC2

Input circuit - Supply circuitRated operational voltage Ue 24 V DC 100-240 V AC 24 V DC 100-240 V AC 24 V DC 100-240 V AC

Rated operational voltage tolerance -15...+20 % -15...+10 % -15...+20 % -15...+10 % -15...+20 % -15...+10 %

Operational voltage range 20.4-28.8 V DC 85-264 V AC 20.4-28.8 V DC 85-264 V AC 20.4-28.8 V DC 85-264 V AC

Frequency 0 Hz 50/60 Hz 0 Hz 50/60 Hz 0 Hz 50/60 Hz

Frequency tolerance - ± 5 % - ± 5 % - ± 5 %

Residual ripple m 5 % - m 5 % - m 5 % -

Input current at 24 V DC typ. 185 mA - typ. 200 mA - typ. 200 mA -

at 115/120 V AC (60 Hz) - typ. 90 mA - typ. 90 mA - typ. 90 mA

at 230/240 V AC (50 Hz) - typ. 60 mA - typ. 60 mA - typ. 60 mA

Power failure buffering (IEC/EN 61131-2) 10 ms

Power dissipation at 24 V DC 1.5 W - 3.4 W - 3.4 W -

at 115/120 V AC - typ. 11 VA - typ. 11 VA - typ. 11 VA

at 230/240 V AC - typ. 15 VA - typ. 15 VA - typ. 15 VA

Network - point-to-point connectionNumber of stations 1 -

Data transfer rate CL-LS..., CL-LM... 9,6 kBaud -

CL-LDD 19,2 kBaud -

Distance max. 5 m -

Electrical isolation to voltage supply yes -

to connected device yes -

Termination system spring-type terminal -

Network - CL-NETNumber of stations max. 1 - max. 8

Data transfer rate 6 m - 1000 kBit/s

25 m - 500 kBit/s

40 m - 250 kBit/s

125 m - 125 kBit/s

300 m - 50 kBit/s

700 m - 20 kBit/s

1000 m - 10 kBit/s

Electrical isolation to voltage supply - yes

to inputs - yes

to outputs - yes

to PC interface, memory module, CL-NET, CL-LINK - yes

Bus terminator (first and last station) - yes

Termination system - RJ45, 8 pole

General dataDimensions (W x H x D) 75 x 58 x 36.2 mm

(2.95 x 2.28 x 1.43 inch)107.5 x 90 x 30 mm (4.23 x 3.54 x 1.18 inch)

Weight 0.164 kg (0.36 lb) 0.145 kg (0.32 lb)

Mountingplugged onto CL-LDD

plugged onto CL-LDD or on DIN rail (IEC/EN 60715)

Mounting position

Electrical connection - Supply circuitWire size fine-strand with wire end ferrule 0.2 mm2 / 2.5 mm2 (24-12 AWG)

rigid 0.2 mm2 / 4 mm2 (24-12 AWG)

Electrical connection - Data cable

Wire size fine-strand with wire end ferrule 0.08 mm2 / 1.5 mm2 (28-12 AWG) - 0.2 mm2 / 2.5 mm2 (24-12 AWG)

rigid 0.08 mm2 / 2.5 mm2 (28-12 AWG) - 0.2 mm2 / 4 mm2 (24-12 AWG)

Environmental dataAmbient temperature range operation -25...+55 °C (cold acc. to IEC 60068-2-1, heat acc. to IEC 60068-2-2)

storage -40...+70 °C

Condensation avoid condensation with suitable methods

Humidity, no condensation (IEC/EN 60068-2-30) 5-95 %

Air pressure (operation) 795-1080 hPa

Degree of protection (IEC/EN 60529) IP20

Vibration (IEC/EN 60068-2-6) 10-57 Hz (constant amplitude 0.15 mm), 57-150 Hz (constant acceleration 2 g)

Page 19: Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

7/19 ABB | Catalog Electronic Products and Relays 2013/2014 | 2CDC 110 004 C0209

7

Logic relaysTechnical data

Data at Ta = 25 °C and rated values, if nothing else indicated.

Type CL-LDC.SDC2 CL-LDC.SAC2 CL-LDC.LDC2 CL-LCD.LAC2 CL-LDC.LNDC2 CL-LDC.LNAC2

Shock (half-sine 15 g / 11 ms) (IEC/EN 60068-2-27) 18 Shocks

Drop (IEC/EN 60068-2-31) height of fall 50 mm

Free fall, packaged (IEC/EN 60068-2-32) 1 m

Insulation data

Degree of protection (DIN EN 60947) 2

Rating of air and creepage distances EN 50178, UL 508, CSA 22.2, No 142

Isolation resistance EN 50178

Standards

Standards and directives EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, IEC 60068-2-6, IEC 60068-2-27

Electromagnetical compatibility

Interference immunity

electrostatic discharge (ESD) IEC/EN 61000-4-2 Level 3 (air discharge 8 kV, contact discharge 6 kV)

electromag. field (HF radiation resistance) IEC/EN 61000-4-3 10 V/m

fast transients (Burst) IEC/EN 61000-4-4 Level 3 (supply cable 2 kV, signal lines 2 kV)

powerful impulses (Surge) IEC/EN 61000-4-5 Level 3 (supply cable symmetrical 2 kV, CL-LDC.L...AC2)

Level 2 (1 kV supply cable symmetrical)

Level 2 (0.5 kV supply cable symmetrical, CL-LDC.L...AC2)

HF line emission IEC/EN 61000-4-6 10 V

Interference suppression (EN 55011, EN 55022) class B

Real time clock

Back-up time - see diagram

Accuracy - typ. ± 5 s/day (± 0,5 h/year)

Repeat accuracy of the time relay

Accuracy (from value) - ± 0.02 %

Resolution range „S“ - 5 ms

range „M:S“ - 1 s

range „H:M“ - 1 min

Retention behaviour

Write cycles of retention memory (minimum) - 1010 (read/ write cycles)

180200

160140120100806040200

55 ˚C

25 ˚C

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Buf

fer

time

(hou

rs)

2CD

C 3

12 0

23 F

0206

Operating time (years)

Technical diagram

Back-up time of the real time clock

Page 20: Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

2CDC 110 004 C0209 | Catalog Electronic Products and Relays 2013/2014 | ABB 7/20

7

Logic relaysTechnical data

Data at Ta = 25 °C and rated values, if nothing else indicated.

Type CL-LD...16DC2 CL-LD...17DC2 CL-LDR.16AC2

Input circuit - Digital inputs 24 V DC 115/230 V

Number 12

Inputs can be used as analog inputs 4 (I7, I8, I11, I12) -

Indication of operational states - LCD-Display (if existing)

Electrical isolation from supply voltage no

from digital inputs no

from the outputs yes

from PC interface, memory module, CL-NET, CL-LINK yes

Rated operational voltage Ue 24 V DC -

Ue on „0“ signal < 5 V DC (I1-I6, I9, I10), < 8 V DC (I7, I8, I11, I12) 0-40 V AC (sinusoidal)

Ue on „1“ signal > 15 V DC (I1-I6, I9, I10), > 8 V DC (I7, I8, I11, I12) 79-264 V AC (sinusoidal)

Rated frequency 0 Hz 50-60 Hz

Input current on „1“ signal 3.3 mA (at 24 V DC, I1-I6, I9, I10),

2.2 mA (at 24 V DC, I7, I8, I11, I12)

12x0.2 mA (at 115 V AC, 60 Hz, I1-I12),12x0.5 mA (at 230 V AC, 50 Hz, I1-I12)

Time delay from „0“ to „1“

debounce ON20 ms

10 ms (at 50 Hz), 100 ms (at 60 Hz)

debounce OFFtyp. 0.1 ms (I1-I4), typ. 0.25 ms (I5-I12)

10 ms (at 50 Hz), 100 ms (at 60 Hz)

Time delay from „1“ to „0“

debounce ON20 ms

10 ms (at 50 Hz), 100 ms (at 60 Hz)

debounce OFF typ. 0.1 ms (I1-I4), typ. 0.4 ms (I5, I6, I9, I10), typ. 0.2 ms (I7, I8, I11, I12)

10 ms (at 50 Hz), 100 ms (at 60 Hz)

Cable length (unshielded) 100 m -

Maximum cable length per input - typ. 60 m

Frequency counter number 4 (I1, I2, I3, I4) -

counting frequency < 3 kHz -

pulse shape square-wave -

pulse / pause ratio 1:1 -

Incremental counter number 2 (I1 + I2, I3 + I4) -

counting frequency < 3 kHz -

pulse shape square-wave -

signal offset 90° -

pulse / pause ratio 1:1 -

Rapid counter inputs number 4 (I1, I2, I3, I4) -

counting frequency < 3 kHz -

pulse shape square-wave -

pulse / pause ratio 1:1 -

Cable length (shielded) < 20 m -

Input circuit - Analog inputs

Number 4 (I7, I8, I11, I12) -

Electrical isolation to voltage supply no -

to digital inputs no -

to outputs yes -

to PC interface, memory modul, CL-NET, CL-LINK yes -

Input type DC voltage -

Signal range 0-10 V DC -

Resolution analog 0.01 V -

digital 0.01 V; 10 Bit (value 0-1023) -

Input impedance 11.2 kq -

Accuracy of the actual value two CL-LD... devices ± 3 % -

within one device ± 2 % -

Conversion time analog/digital each cycle -

Input current < 1 mA -

Cable length (shielded) < 30 m -

Page 21: Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

7/21 ABB | Catalog Electronic Products and Relays 2013/2014 | 2CDC 110 004 C0209

7

Logic relaysTechnical data

Data at Ta = 25 °C and rated values, if nothing else indicated.

Type CL-LD...16DC2 CL-LD...17DC2 CL-LDR.16AC2

Output circuit - Analog outputs

Number - 1 -

Electrical separation from voltage supply - no -

from the digital inputs - no -

from the digital outputs - yes -

from PC interface, memory module, CL-NET, CL-LINK - yes -

Output type - DC voltage -

Signal range - 0-10 V DC -

Max. output current - 0.01 A -

Burden resistance - 1 kq -

Overload and short-circuit protection - yes -

Resolution analog - 0.01 V DC -

digital - 10 Bit, (value: 0-1023) -

Setting time - 100 ms -

Accuracy -25...+55 °C - 2 % -

25 °C - 1 % -

Conversion time - each CPU cycle -

General data

Dimensions (W x H x D) CL-LDR: 89 x 90 x 44 mm (3.5 x 3.54 x 1.73 inch)

CL-LDT (build-in): 89 x 90 x 25 mm (3.5 x 3.54 x 0.98 inch)

89 x 90 x 44 mm

(3.5 x 3.54 x 1.73 inch)

Weight CL-LDR: 0.15 kg (0.33 lb) / CL-LDT: 014 kg (0.31 lb) 0.15 kg (0.33 lb)

Mounting snap-on power supply unit

Mounting position horizontal / vertical

Electrical connection

Wire size fine-strand with wire end ferrule 0.2 mm2 / 2.5 mm2 (24-12 AWG)

rigid 0.2 mm2 / 4 mm2 (24-12 AWG)

Electrical connection - Data cable

Wire size fine-strand with wire end ferrule 0.08 mm2 / 1.5 mm2 (28-12 AWG)

rigid 0.08 mm2 / 2.5 mm2 (28-12 AWG)

Environmental data

Ambient temperature range operation -25...+55 °C (cold acc. to IEC 60068-2-1, heat acc. to IEC 60068-2-2)

storage -40...+70 °C

Condensation avoid condensation with suitable methods

Humidity, no condensation (IEC/EN 60068-2-30) 5-95 %

Atmospheric pressure (operation) 795-1080 hPa

Degree of protection (IEC/EN 60529) IP20

Vibration (IEC/EN 60068-2-6) 10-57 Hz (constant amplitude 0.15 mm), 57-150 Hz (constant acceleration 2 g)

Shock (half-sine 15 g / 11 ms) (IEC/EN 60068-2-27) 18 Shocks

Drop (IEC/EN 60068-2-31) height of fall 50 mm

Free fall, packaged (IEC/EN 60068-2-32) 1 m

Insulation data

Pollution degree 2

Rating of air and creepage distances EN 50178, UL 508, CSA C22.2, No. 142

Isolation resistance EN 50178

Standards

Standards and directives EN 61000-6-1/-2/-3/-4, IEC/EN 61000-4, IEC 60068-2-6, IEC 60068-2-27

Electromagnetic compatibility

electrostatic discharge (ESD) IEC/EN 61000-4-2 Level 3 (air discharge 8 kV, contact discharge 6 kV)

electromag. field (HF radiation res.) IEC/EN 61000-4-3 10 V/m

fast transients (Burst) IEC/EN 61000-4-4 Level 3 (supply cable 2 kV, signal cable 2 kV)

powerful impulses (Surge) IEC/EN 61000-4-5 2 kV (supply cable symmetrical),

Level 2 (0.5 kV supply cable symmetrical)

HF line emission IEC/EN 61000-4-6 10 V

Interference suppression (EN 55011, EN 55022) class B

Page 22: Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

2CDC 110 004 C0209 | Catalog Electronic Products and Relays 2013/2014 | ABB 7/22

7

Logic relaysTechnical data

Data at Ta = 25 °C and rated values, if nothing else indicated.

Type CL-LDR...

Output circuit - Relay outputs

Number 4

Outputs in groups of -

Parallel switching of outputs to increase capacity not permissible

Fusing of the output relay circuit-breaker B16 or fuse 8 A (slow-acting)

Electrical isolation from voltage supply yes

from the inputs yes

from PC interface, memory module, CL-NET, CL-LINK yes

protective separation 300 V AC

Basic isolation 600 V AC

Mechanical lifetime 10x106 switching cycles

Rung conventional thermal current (10 A UL) 8 A

recommended load 12 V AC/DC > 500 mA

short-circuit proof cos j = 1; characteristic B16 at 600 A 16 A

short-circuit proof cos j = 0.5 up to 0.7; characteristic B16 at 900 A 16 A

Rated impulse withstand voltage Uimp contact-coil 6 kV

Rated operational voltage Ue 250 V AC

Rated insulation voltage Ui 250 V AC

Protective separation (EN 50178) between coil and contact 300 V AC

between two contacts 300V AC

Making capacity AC15, 250 V AC, 3 A (600 ops./h) 300.000 switching cycles

DC13, L/R m 150 ms, 24 V DC, 1 A (500 ops./h) 200.000 switching cycles

Breaking capacity AC15, 250 V AC, 3 A (600 ops./h) 300.000 switching cycles

DC13, L/R m 150 ms, 24 V DC, 1 A (500 ops/h) 200.000 switching cycles

Incandesent lamp load 1000 W at 230/240 V AC 25.000 switching cycles

500 W at 115/120 V AC 25.000 switching cycles

Fluorescent lamp load 10 x 58 W at 230/240 V AC with electrical control gear 25.000 switching cycles

10 x 58 W at 230/240 V AC uncompensated 25.000 switching cycles

1 x 58 W at 230/240 V AC conventional compensated 25.000 switching cycles

Switching frequency mechanical operations 10x106

switching frequency 10 Hz

resistive load / lamp load 2 Hz

inductive load 0.5 Hz

UL/CSA

Continuous current at 240 V 10 A AC

Continuous current at 24 V 8 A DC

AC Utilization category (Control Circuit Rating Codes) B 300 Light Pilot Duty

max. rated operational voltage 300 V AC

max. continuous thermal current cos j = 1 at B 300 5 A

max. making / breaking apparent power (Make/Break) cos j ≠ 1 at B 300 3600/360 VA

DC Utilization category (Control Circuit Rating Codes) R 300 Light Pilot Duty

max. rated operational voltage 300 V DC

max. continuous thermal current at R 300 1 A

max. making / breaking apparent power (Make/Break) at R 300 28/28 VA

Page 23: Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

7/23 ABB | Catalog Electronic Products and Relays 2013/2014 | 2CDC 110 004 C0209

7

Logic relaysTechnical data

Data at Ta = 25 °C and rated values, if nothing else indicated.

Type CL-LDT...

Output circuit - Transistor outputs

Number 4

Rated operational voltage Ue 24 V DC

Operational voltage range 20.4-28.8 V DC

Residual ripple -

Supply current on „0“ signal typ. 18 mA / max. 32 mA

on „1“ signal typ. 24 mA / max. 44 mA

Reverse voltage protection yes (Attention: If supply voltage is reversed, applying voltage at the outputs, causes a short circuit.)

Electrical isolation from voltage supply yes

from the inputs yes

from PC interface, memory module, CL-NET, CL-LINK yes

Rated operational current Ie on„1“ signal DC max. 0.5 A

Lamp load without Rv 5 W (Q1-Q4)

Residual current on „0“ signal per channel < 0.1 mA

Max. output voltage on „0“ signal at external load < 10 Mq 2.5 V

on „1“ signal at Ie = 0.5 A U = Ue - 1 V

Short-circuit protection thermal (Q1-Q4), (analysis results from diagnosis input I16)

Short-circuit tripping current for Ra m 10 mq 0.7 A m Ie m 2 A per output

Total short-circuit current 8 A

Peak short-circuit current 16 A

Thermal tripping yes

Max. switching frequency with constant resistive load RL < 100 kq (depending on active channels and their load) 40.000 switching cycles/h

Parallel connection of outputs with resistive load, inductive load with external suppressor, combination within one group group 1: Q1-Q4

number of outputs max. 4

max. total current 2 A (Attention! Outputs must be actuated simultaneously and for the same length of time.)

Indication of operational states of the outputs LCD-Display (if existing)

Inductive load1) without external suppressor

T0.95 = 1 ms, R = 48 q, L = 16 mH

utilization factor 0.25 g

duty time 100 %

max. switching frequency f = 0,5 Hz (max. duty time = 50 %) 1500 switching cycles

DC13, T0.95 = 72 ms, R = 48 q, L = 1.15 H

utilization factor 0.25 g

duty time 100 %

max. switching frequency f = 0,5 Hz (max. duty time = 50 %) 1500 switching cycles

T0.95 = 15 ms, R = 48 q, L = 0.24 H

utilization factor 0.25 g

duty time 100 %

max. switching frequency f = 0,5 Hz (max. duty time = 50 %) 1500 switching cycles

Inductive load1) with external suppressor

demand factor 1 g

duty time 100 %

max. switching frequency max. duty time depends on suppressor

1) For inductive loading, without external suppression of the transistor outputs, the following applies: T0.95 = time in ms, until 95 % of the steady-state current is achieved. T0.95 3 × T0.65 = 3 × L/R.

Data transfer rate in the CL-NET network: bus lengths of 40 m and over only attainable with cables with additional cross-section and connection adapter.

Page 24: Logic relays Product group picture - ABB · PDF fileLogic relays Product group picture. ... Documentation (download from the internet) ... CL-LAS-PS002, CL-LAS.TD001,

2CDC 110 004 C0209 | Catalog Electronic Products and Relays 2013/2014 | ABB 7/24

7

Logic relaysDimensional drawings

90 102

110

71.5

M4

10.75 50

35.75

45

58

56.5

47.5

4.5

2CD

C 3

12 0

11 F

0b06

90 102

110

M4

107.5

75 16.2516.25

45

58

56.5

47.5

4.5

2CD

C 3

12 0

12 F

0b06

CL-LSR, CL-LST CL-LMR, CL-LMT

CL-LDD

3217

20 13.7

86.5

30

62

86.5

28.25 28.25

22.3

30

2CD

C 3

12 0

18 F

0b06

90 102

110

45

58

56.5

47.5

4.5

7.5

35.5

7.5

M4

2CD

C 3

12 0

13 F

0b06

CL-LER.2O

90

88.2

107.5

20 43.2

33.7

2CD

C 3

12 0

14 F

0b06

65.5

29.3 36.2

86.5

75

86.5

58

2CD

C 3

12 0

15 F

0b06

90

88.1 19 25

2CD

C 3

12 0

16 F

0b06

CL-LDC.S..

CL-LDR, CL-LDT

CL-LDD.K + CL-LDC.L.. + (CL-LDR or CL-LDT)

Dimensional drawings dimensions in mm