112
Manual Local control unit DLP-VSE-... DLP-VSE-...-DP DLP-VSE-...-ASI Manual 396 535 en 0206a

Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

  • Upload
    others

  • View
    60

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

Manual

Local control unitDLP-VSE-...DLP-VSE-...-DPDLP-VSE-...-ASI

Manual396 535en 0206a

Page 2: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa
Page 3: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

Contents and general instructions

IFesto P.BE-DLP-VSE-... en 0206a

Authors Uwe Reimann, Timo Engelfried. . . . . . . . . . . . . . . .

Editors H.-J. Drung, M.Holder. . . . . . . . . . . . . . . . . . . . . . . .

Original de. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Translation transline Deutschland GmbH. . . . . . . . . . . . . . .

Layout Festo AG & Co., Dept. KG-GD. . . . . . . . . . . . . . . . . . .

Typesetting DUCOM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Edition en 0206a. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Title MANUAL-EN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Designation P.BE-DLP-VSE-.... . . . . . . . . . . . . . . . . . . . . . . .

Order no. 396 535. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E (Festo AG & Co., D-73726 Esslingen, Federal Republic ofGermany, 2000)Internet: http://www.festo.come-mail: [email protected]

The copying, distribution and utilization of this document aswell as the communication of its contents to others withoutexpressed authorization is prohibited. Offenderswill beheldliable for the payment of damages. All rights reserved, inpar-ticular the right to carry out patent, utility model or orna-mental design registration.

Page 4: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

Contents and general instructions

II Festo P.BE-DLP-VSE-... en 0206a

Page 5: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

Contents and general instructions

IIIFesto P.BE-DLP-VSE-... en 0206a

Contents

Intended use VI. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Target group VI. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Notes on these operating instructions VI. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Important user instructions VII. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1. Description of the product 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.1 Method of operation 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2 Summary of variants 1-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2.1 Operating and display field 1-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.2.2 Electrical connections and bus connection 1-6. . . . . . . . . . . . . . . . . . . . . . . . . . .1.2.3 Housing block with integrated air supply 1-7. . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2.4 Integrated pneumatic valve 1-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2. Fitting 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.1 Fitting onto a wall 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.2 Tubing and fastening on the DLP cylinder 2-3. . . . . . . . . . . . . . . . . . . . . . . . . . .

3. Installation 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1 Connecting the pneumatic components 3-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1.1 Tubing variants 3-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.1.2 Assigning the pneumatic connections 3-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.2 Connecting the electric components 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.2.1 Electrical connections on the housing 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.2.2 Connecting the limit switches 3-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.2.3 Connecting the power supply 3-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.2.4 Connecting a PLC or an external controller (not with DLP-...-DP and ...-ASI) 3-103.3 Connection with PROFIBUS-DP (on DLP-VSE-...DP) 3-11. . . . . . . . . . . . . . . . . . . .3.3.1 Fitting and dismantling the switch module 3-11. . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.2 Setting the Local control unit 3-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.3.3 Connecting the field bus 3-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.3.4 Bus termination with terminating resistors 3-22. . . . . . . . . . . . . . . . . . . . . . . . . .

Page 6: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

Contents and general instructions

IV Festo P.BE-DLP-VSE-... en 0206a

3.3.5 Fibre-optical waveguide 3-24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.4 Connection with AS-interface (on DLP-VSE-...-ASi) 3-25. . . . . . . . . . . . . . . . . . . .3.4.1 Assigning the AS-i address 3-25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4.2 Connecting the limit switch (PNP inputs) 3-26. . . . . . . . . . . . . . . . . . . . . . . . . . . .3.4.3 Festo installation accessories 3-26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.4.4 Connecting the AS-i bus and the load voltage 3-28. . . . . . . . . . . . . . . . . . . . . . . .3.4.5 Example of connections Local control unit with EMERGENCY STOP 3-29. . . . . .

4. Commissioning 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.1 Commissioning the pneumatic components 4-1. . . . . . . . . . . . . . . . . . . . . . . . . .

4.1.1 Switching on the operating voltage 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.1.2 Switching on the compressed air 4-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.1.3 Positioning the limit switches 4-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.2 Commissioning on the PROFIBUS-DP 4-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.2.1 Assigning the inputs and outputs 4-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.2.2 Preparing the Local control unit for commissioning 4-6. . . . . . . . . . . . . . . . . . .4.2.3 Configuration with a Siemens master 4-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.2.4 Operation with general DP master 4-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.2.5 Device data base (GSD) 4-28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.3 Commissioning on the AS-interface 4-29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.3.1 Assigning the data bits 4-29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.4 Commissioning test for PROFIBUS-DP and AS-interface 4-30. . . . . . . . . . . . . . . .

5. Diagnosis 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.1 Eliminating faults 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.1.1 Pneumatic components 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.1.2 Electric components 5-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.1.3 Replacing the indicator lights 5-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.1.4 Status displays (LED) of the in- and outputs (only with DLP-...-DP and ...-ASI) 5-35.2 Diagnosis when connected to PROFIBUS-DP 5-4. . . . . . . . . . . . . . . . . . . . . . . . .

5.2.1 Diagnosis with the LEDs POWER and BUS 5-4. . . . . . . . . . . . . . . . . . . . . . . .5.2.2 Diagnosis with PROFIBUS-DP 5-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.2.3 Diagnostic words 5-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.2.4 Diagnostic information 5-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 7: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

Contents and general instructions

VFesto P.BE-DLP-VSE-... en 0206a

5.3 Error treatment with PROFIBUS-DP 5-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.3.1 General DP master 5-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.3.2 Siemens SIMATIC S5/S7 5-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3.3 STEP 7 V4.x - Online diagnosis via diagnostic buffer 5-17. . . . . . . . . . . . . . . . . . .5.4 Diagnosis with AS-interface 5-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A. Technical appendix A-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.1 Technical specifications of the Festo Local control unit A-1. . . . . . . . . . . . . . . . .A.2 Index A-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 8: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

Contents and general instructions

VI Festo P.BE-DLP-VSE-... en 0206a

Page 9: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

Contents and general instructions

VIIFesto P.BE-DLP-VSE-... en 0206a

Intended use

The Local control unit described in this documentation is in-tended exclusively for use in process control. In conjunctionwith additional commercially available components, such assensors and actuators, the specified limits for pressures, tem-peratures, electrical data, torques etc. must be observed.

Please comply with national and local safety laws and regula-tions.

Target group

These operating instructions are intended exclusively forqualified personnel who have experience in installing andcommissioning automation and control devices. For the vari-ants DLP-VSE-...-DP and ...-ASI, knowledge of programmingand diagnosing PROFIBUS-DP or AS-Interface slaves is alsorequired.

The Local control unit is intended for use in controlling servodrives on valves and flap valves of the process controller,referred to in the following as fittings.

Notes on these operating instructions

These operating instructions contain specific information onfitting, installing and commissioning the Festo Local controlunit, as well as on programming and diagnosing the Localcontrol unit as a slave on the PROFIBUS-DP or AS-Interface.AS-Interface® is an internationally protected trade mark.

Page 10: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

Contents and general instructions

VIII Festo P.BE-DLP-VSE-... en 0206a

Important user instructions

Danger categories

This manual contains instructions on the dangers which mayoccur if the product is not used correctly. These instructionsare marked with a heading (Warning, Caution, etc.), printedon a shaded background and accompanied by a pictogram. Adistinction is made between the following danger categories:

WarningThis means that there is a danger of serious injury tohuman beings and damage to property if these instruc-tions are not observed.

CautionThis means that there is a danger of human injury anddamage to property if these instructions are not observed.

Please noteThis means that there is a danger of damage to property ifthese instructions are not observed.

In addition, the following pictogram marks passages in thetext which describe activities involving electrostatically sensi-tive components:

Electrostatically sensitive components: Incorrect handlingmay result in damage to the components.

Page 11: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

Contents and general instructions

IXFesto P.BE-DLP-VSE-... en 0206a

Marking special information

The following pictograms mark passages in the text contain-ing special information.

Pictograms

Information:recommendations, tips and references to other sources ofinformation.

Accessories:information on necessary or useful accessories for the Festoproduct.

Environment:information on the environmentally-friendly use of Festoproducts.

Text markings

S The bullet denotes activities which can be carried out inany sequence.

1. Figures denote activities which must be carried out in theorder specified.

Hyphens denote general activities.

Page 12: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

Contents and general instructions

X Festo P.BE-DLP-VSE-... en 0206a

The following product-specific terms and abbreviations areused in these operating instructions.

Term/abbreviation Meaning

AS-i AS-Interface®

DLP-VSE Local control unit

Fittings Servo drives on valves and flap valves of the process control

I digital input

I/Os digital inputs and outputs

Limit switch Proximity switch on the cylinder

O digital output

SPS, IPC Programmable logic controller, industrial PC

Word width Number of address words assigned by the Local control unit

Page 13: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

1. Summary of components

1-1Festo P.BE-DLP-VSE-... en 0206a

1. Description of the product

1.1 Method of operation

The Local control unit has the following features:

modular structure

it can process electric input signals by means of process-monitoring elements

it can be operated manually

Output variables for Local control unit are:

switches for the compressed air to the fittings

electric signals for externally-actuated valves

optical displays for the operating personnel

Page 14: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

1. Summary of components

1-2 Festo P.BE-DLP-VSE-... en 0206a

1 Operating anddisplay field(2 variants)

2 Pressure-compensatingelement

3 Electrical connec-tions

4 Bus connection(only with ...-DPor ...-ASI)

5 Housing blockwith integratedair supply

6 Integrated pneu-matic valve (notshown)

1

2

3

4

5

6

Fig. 1/1: Components of the Local control unit (example DLP-VSE-...-DP)

Page 15: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

1. Summary of components

1-3Festo P.BE-DLP-VSE-... en 0206a

1.2 Summary of variants

There are several variants of the Local control unit. Pleasenote the type plate. This indicates the variant:

Type designation Operating variant

DLP-VSE-2-5/2-C with integrated 5/2-way valve,closes in the basic position

DLP-VSE-2-5/2-O with integrated 5/2-way valve,opens in the basic position

DLP-VSE-3-5/3-G with integrated 5/3-way valve,stops in the basic position

DLP-VSE-3-5/3-G-DP with integrated 5/3-way valve,stops in the basic positionfield bus connection PROFIBUS-DP

DLP-VSE-3-5/3-G-ASI with integrated 5/3-way valve,stops in the basic positionconnection to AS-Interface®

Page 16: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

1. Summary of components

1-4 Festo P.BE-DLP-VSE-... en 0206a

1.2.1 Operating and display field

The following elements can be found on the operating anddisplay field:

1

2 3 4 5

6

7

8

HAND AUTO AUF ZULOC A L REMOTE OPEN C LOSE

0

ERROR

POWER

AUF ZUOPEN C LOSE

AUF ZUOPEN C LOSE

HA LTSTOP

1 Key switch for operating mode

2 Knob-operated switch for opening orclosing (DLP-VSE-2-...)

3 Knob-operated switch for opening,stopping or closing (DLP-VSE-3-...)

4 Indicator light for displaying positionOPEN (position reached)

5 Indicator light for displaying positionCLOSE (position reached)

6 LED red (ERROR) error display on fieldbus (only DLP-VSE-...-DP or ...-ASI)

7 LED green (POWER) for operating volt-age display

8 Switch module (only with DLP-VSE-...-DP)

Fig. 1/2: Operating and display field

Page 17: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

1. Summary of components

1-5Festo P.BE-DLP-VSE-... en 0206a

Key switch You can set the operating mode of the Local control unit withthe key switch.

HAND/LOCAL: Manual operation In this position, you canopen or close the fittings with the knob-operated switch.

0: Off

AUTO/REMOTE: Remotely monitored. The fittings areswitched by a higher-order controller.

Knob-operated switch If the key switch is in the position HAND/LOCAL you canswitch the valve with the knob-operated switch. There are 2or 3 switch positions, depending on the variant.

AUF/OPEN The fittings are opened.

HALT/STOP Hold intermediate position (only with DLP-VSE-3-...)

ZU/CLOSE The fittings are closed.

Page 18: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

1. Summary of components

1-6 Festo P.BE-DLP-VSE-... en 0206a

1.2.2 Electrical connections and bus connection

The Local control unit has the following electrical connections,depending on the type:

1 PROFIBUS-DP(only withDLP-VSE-...-DP)

2 AS-Interface(only withDLP-VSE-...-ASI)

3 reserved (onlywith DLP-VSE-...-DP)

4 Earth connection

5 Operating voltageconnection(not with DLP-VSE-...-ASI)

6 Connection forPLC or externalcontroller (notwith DLP-VSE-...-ASI and ...-DP)

7 Limit switch in-puts

1 2 3

4 5 6 7

Fig. 1/3: Electrical connections

Page 19: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

1. Summary of components

1-7Festo P.BE-DLP-VSE-... en 0206a

1.2.3 Housing block with integrated air supply

The housing block is formed of a two-part profiled sectionwhich is screwed together with two covers. The lower partcontains a base which has fastening devices and air channelsfor supplying the valves.

1 Supply/exhaustside

2 Grooves for thefastening blocks

3 Work air side

1

2

3

Fig. 1/4: Housing block with integrated air supply

1.2.4 Integrated pneumatic valve

Local control units with integrated pneumatic valves can con-tain valves of the following designs:

Type 5/2-way valve 5/3-way valve

Type MEH-5/2-5,0-B MEH-5/2-5,0-B MEH-5/3-5,0-G

Basic positionof Local controlunit

closing(with DLP-VSE-2-...-C)

opening(with DLP-VSE-2-...-C)

stopped(with DLP-VSE-3-...-G)

Design with spring return blocked in mid-position

Function moving to a defined safety position holding a variable intermediateposition

Page 20: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

1. Summary of components

1-8 Festo P.BE-DLP-VSE-... en 0206a

Page 21: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

2. Fitting

2-1Festo P.BE-DLP-VSE-... en 0206a

2. Fitting

CautionCompare the maximum values specified with those of yourapplication. The permitted maximum values, e.g. for pres-sures, forces, torques, masses, speeds and temperaturesmust not be exceeded. Make sure that the cables betweenthe Local control unit and the fittings are kept as short aspossible.

Please noteBefore fitting the Local control unit, you must order thefollowing parts separately:

a suitable sub-base type DLP-VSE-AP or DLP-VSE-NA.(further information see chapter 2.2)

if fitted onto a wall, the fastening kit DLP-VSE-BP (seechapter 2.1)

2.1 Fitting onto a wall

CautionMake sure that the fastening surface can support theweight of the Local control unit.

S Prepare the Local control unit for fitting with slidingblocks as follows (Fig. 2/5):

1. Remove the protective foil from the air channels.

2. Insert the sliding blocks

3. Fit the end cover. Tighten the cover screws with 1.5 Nm(± 20%).

Page 22: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

2. Fitting

2-2 Festo P.BE-DLP-VSE-... en 0206a

Please noteMake sure that the seal in the cross-section profile is notdamaged.

1 2 3

4

1 Protective foil

2 Sliding block

3 End cover

4 Integrated seal

Fig. 2/5: Preparations for fastening with sliding blocks (view of supply/exhaust side ofLocal control unit)

S Fitting the Local control unit onto the wall (Fig. 2/6)

1. Screw the fastening kit (DLP-VSE-BP, must be orderedseparately) to the sliding blocks. Screw 4 screws intoeach of the fastening plates. The tightening torque is 1.5Nm (± 20%).

2. Fasten the Local control unit to the wall.

Page 23: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

2. Fitting

2-3Festo P.BE-DLP-VSE-... en 0206a

1

1 Fastening plate (fastening kit DLP-VSE-BP)

Fig. 2/6: Fitting onto a wall with sliding blocks and fastening kit DLP-VSE-BP

2.2 Tubing and fastening on the DLP cylinder

Before fitting the Local control unit, you must order a suitablesub-base. There are two ways of fastening the Local controlunit to the cylinder:

Separate from the DLP cylinder (e.g. wall fitting): use sub-base DLP-VSE-AP (must be ordered separately) (seeFig. 2/7).

Fit onto the cylinder using extended sub-base DLP-VSE-NA (must be ordered separately) (see Fig. 2/8).

Connect the tubing of the DLP cylinder after fitting the Localcontrol unit.

Page 24: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

2. Fitting

2-4 Festo P.BE-DLP-VSE-... en 0206a

1 DLP cylinder(Copac) or DERcylinder (Copar)

2 Tubing

3 Sub-base DLP-VSE-AP (must beordered separ-ately)

4 Local control unit

1 2 3 4

Fig. 2/7: Fitting and tubing for the DLP cylinder (view of work air side of Local controlunit)

1 Sub-base DLP-VSE-NA(must be orderedseparately)

1

Fig. 2/8: Fitting on the DLP cylinder and tubing (view of work air side of Local controlunit)

Page 25: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-1Festo P.BE-DLP-VSE-... en 0206a

3. Installation

WarningSwitch off the following before undertaking installationand/or maintenance work:

S the compressed air supply

S the operating voltage supply

You can thereby avoid:

sudden uncontrolled movements of loose tubing

unexpected movements of the connected actuators

non-defined switching states of the electronic compo-nents.

Please noteHandle all components of the Local control unit with theutmost care. Pay particular attention to the following:

S Make sure that screws are not distorted and not sub-jected to mechanical stress.

S Make sure that screws are correctly aligned (otherwisetheir threads may be damaged).

S Make sure that the specified torques are not exceeded.

S Avoid misalignment between the modules (IP 65).

S Make sure that connecting surfaces are clean (avoidleakage and contact faults).

Page 26: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-2 Festo P.BE-DLP-VSE-... en 0206a

3.1 Connecting the pneumatic components

Please notePlace a suitable seal under each screw connector or si-lencer in order to avoid leakage. By greasing the sealsslightly you can increase the sealing effect. If elbow screwconnectors or multiple distributors are used, the airflowwill be reduced slightly.

3.1.1 Tubing variants

Connecting 1. Push the tubing as far as possible over or into the tubeconnection of the screw connector.

2. Tighten locking screw 2 or, where applicable, pull lockingring 4 over the tube connection.

3. For reasons of clarity, group the tubing together with tube straps or multiple hose holders

1 Quick connectors

2 Locking screw

3 Quickstar con-nection

4 Locking ring

1 2

3 4

Fig. 3/9: Connecting the tubing

Page 27: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-3Festo P.BE-DLP-VSE-... en 0206a

Removing 1. Loosen the locking screw or locking ring of the screwconnector.

2. Pull out the tubing.

3. If applicable, replace screw connector with plug 4.

1 Quick connectors

2 Locking screw

3 Quickstar con-nection

4 Plug

1 2

3 4

Fig. 3/10: Removing the tubing

3.1.2 Assigning the pneumatic connections

Connect the tubing for the pneumatic connections as shownin Fig. 3/11.

CautionConnect the tubing of the Local control unit with the cylin-der, so that the fittings open or are open when the knob-operated switch is in the position AUF/OPEN. The sameapplies to ZU/CLOSE and Closed.

Page 28: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-4 Festo P.BE-DLP-VSE-... en 0206a

Please noteSome of the connections are covered with adhesive foil toprotect them from dirt. Remove all adhesive foil from theconnections. If connections are not used, they should besealed with plugs.

1 2

1 Compressed air connections on thesupply/exhaust side

2 Compressed air connections on thework air side (shown with sub-baseDLP-VSE-AP)

Fig. 3/11: Assigning the pneumatic connections

Page 29: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-5Festo P.BE-DLP-VSE-... en 0206a

3.2 Connecting the electric components

CautionThe components of the Local control unit contain electro-statically sensitive elements.

S Do not therefore touch any contact surfaces of the plugconnectors on the components.

S Please observe the regulations for handling electrostati-cally sensitive components.

In this way, you will avoid damaging the individual compo-nents.

3.2.1 Electrical connections on the housing

1 Earth connection

2 Operating voltageconnection

3 Socket for PLC orexternal con-troller (not withDLP-VSE-...-DPand ...-ASI)

4 Limit switch in-puts

1 2 3 4

Fig. 3/12: Electrical connections (summary)

Page 30: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-6 Festo P.BE-DLP-VSE-... en 0206a

3.2.2 Connecting the limit switches

Please notePlease note that the length of the limit switch cables mustnot exceed 30 m.

S Connect the limit switches to the socket for the limitswitch inputs.

Use the plugs included in delivery for this connection.

Pin assignment of the limit switch inputs

1 2 3 4 5 6

1 2

1 Inputs of the limit switch for signalClosedPin 1: signal ClosedPin 2 0 VPin 3: 24V

2 Inputs of the limit switch for signalOpenPin 4: signal OpenPin 5 0 VPin 6: 24V

Fig. 3/13: Pin assignment of socket for limit switch inputs (view of Local control unit)

Page 31: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-7Festo P.BE-DLP-VSE-... en 0206a

3.2.3 Connecting the power supply

Selecting the power unit

WarningUse only power units which guarantee reliable isolation inaccordance with IEC 742/EN 60742/VDE 0551 with at least4kV isolation resistance (Protected Extra-Low Voltage,PELV). Switch power packs are permitted providing theyguarantee reliable isolation in accordance withEN 60950/VDE 0805.

Remark:By using PELV power units, you can ensure protection againstelectric shock (protection against direct and indirect contact)in accordance with EN 60204-1/IEC 204. For supplying powerto PELV networks, you should use safety transformers withthe symbol shown here. The Local control unit must beearthed in order to guarantee the operation of certain func-tions (e.g. EMC).

S When selecting a power unit, make sure that it has suffi-cient power output.

Operating voltage cable

Please notePlease note that the length of the operating voltage cablemust not exceed 10 m.

S Use an operating voltage cable with sufficient cross-sec-tional area (stiff or flexible cable with cross-sectional area1.5 mm2 ,outer diameter: 3...8 mm).

Page 32: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-8 Festo P.BE-DLP-VSE-... en 0206a

Connecting the operating voltage

Please noteCheck within the framework of your EMERGENCY STOPcircuit, to ascertain the measures which are required forputting your machine/system in a safe state in the event ofan EMERGENCY STOP (e.g. switching off the load voltagefor the valves and output modules, switching off the pres-sure).

The operating voltage connection is in the form of a 5-pinsocket (pin assignment see Fig. 3/14). On the DLP-VSE-... and...-DP, the Local control unit is supplied with operating andload voltages via this socket. On the DLP-VSE-...-ASI, the loadvoltage is supplied via the black flat cable.

Use the plug included in delivery for the operating voltageconnection.

Pin assignment of the operating voltage connection

1 2 3 4 5

1

1 Operating voltage connectionPin 1: 24 V DC operating voltagePin 2: 0 V operating voltagePin 3: Earth connectionPin 4: 0 V load voltagePin 5: 24 V DC operating voltage

Fig. 3/14: Pin assignment of the operating voltage connection(view of Local control unit)

Page 33: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-9Festo P.BE-DLP-VSE-... en 0206a

Please note the following when connecting the 24 V load volt-age (pin 5):

S Observe the tolerance (20.4 V ... 28.8 V DC). Check the24 V load voltage of the valve while your system is oper-ating.

Potential equalization

The Local control unit has two earth connections for potentialequalization: on the operating voltage connection (pin 3) on the housing plate (see Fig. 3/12)

Please noteS Always connect the earth potential to pin 3 of the oper-ating voltage connection.

S Connect the earth connection on the housing to theearth potential with low impedance (short cable withlarge cross-sectional area).

S By means of low-impedance connections, you can besure that the housing of the Local control unit and theearth connection at pin 3 have the same potential andthat there are no equalizing currents.

You thereby avoid faults caused by electromagnetic in-fluences.

Page 34: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-10 Festo P.BE-DLP-VSE-... en 0206a

3.2.4 Connecting a PLC or an external controller (not with DLP-VSE-...-DPand ...-ASI)

You can connect a PLC or an external controller to this socket.

Fig. 3/15: Socket for PLC connection (view of Local controlunit, pin assignment see table)

Pin Designation Pin Designation

1 Closed 9 Limit switch Open

2 0 V 10 not connected

3 0 V 11 24 V stepper

4 Open 12 0 V stepper

5 Hand*) 13 0 V

6 Auto*) 14 Indicator light ZU/CLOSE

7 0*) 15 Indicator light AUF/OPEN

8 Limit switchClose

*)Switching status of key switch

Fig. 3/16: Pin assignment of PLC connection (only with DLP-VSE-...)

Page 35: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-11Festo P.BE-DLP-VSE-... en 0206a

3.3 Connection with PROFIBUS-DP (on DLP-VSE-...DP)

3.3.1 Fitting and dismantling the switch module

WarningThe switch module contains electrostatically sensitiveelements.

S Do not therefore touch any contacts.

S Please observe the regulations for handling electrostati-cally sensitive components.

In order to set the Local control unit, you must first dismantlethe switch module.

Fig. 3/17: Fitting/dismantling the switch module

Page 36: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-12 Festo P.BE-DLP-VSE-... en 0206a

Dismantling

1. Switch off the operating voltage.

2. Unscrew the two fastening screws of the switch module.

3. Lift up the switch module and remove it.

Fitting

1. Insert the switch module carefully in the groove.

2. Tighten both fastening screws alternately to the samedegree (tightening torque is 0.6 Nm ± 30%).

Please noteS Do not tilt the switch module when inserting it. The fit-ting position is clearly marked by a groove in the hous-ing.

S Make sure that the seal ring is seated correctly.

3.3.2 Setting the Local control unit

When the switch module has been dismantled, you will seetwo DIL switches for setting the following parameters(Fig. 3/18):

the configuration of the Local control unit (with/withoutmeasurement bus)

the station number

the diagnostic mode

Page 37: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-13Festo P.BE-DLP-VSE-... en 0206a

Proceed as follows:

1. Switch off the operating voltage.

2. Dismantle the switch module (see chapter 3.3.1)

3. Set the configuration of the Local control unit (4-elementDIL switch, element 1).

4. Assign an unused station number to the Local controlunit. Set the desired station number (8-element DILswitch,elements 1-7).

5. Set the diagnostic mode (8-element DIL switch,element 8).

6. Fit the switch module (see chapter 3.3.1)

1 Configurationwith/withoutmeasurementbus

2 not assigned

3 Address selectorswitch for stationnumber

4 Setting the diag-nostic mode

1 2 3 4

O N

1 2 3 4 5 6 7 8

O N

1 2 3 4

Fig. 3/18: DIL switch in the switch module

Page 38: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-14 Festo P.BE-DLP-VSE-... en 0206a

Setting the configuration

The Local control unit can be operated in the configurationswith measurement bus or without measurement bus. Inthe configuration with measurement bus an analoguemeasured value can be provided for the controller.

Set your desired configuration according to the followingdiagram:

without measurement bus with measurement bus

Fig. 3/19: Setting the configuration (4-element DIL switch)

Setting the station number

You can set the field bus station number with the 8-elementDIL switch.

Please noteStation numbers may only be assigned once per field busline.

Recommendation:Assign the station numbers in ascending order. Assign thestation numbers, if necessary, to suit the machine structure ofyour system.The following station numbers are permitted:

Protocol Address designation Permitted station numbers

PROFIBUS-DP PROFIBUS address 0; ...; 125

Page 39: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-15Festo P.BE-DLP-VSE-... en 0206a

1 Switch elements1...7

1

20=1

21=2

22=4

23=8

24=16

25=32

26=64

Fig. 3/20: Setting the station number

The station number is entered coded via the 8-element DILswitch.

Set station numbers:05 (= 1 + 4)

Set station numbers:38 (= 2 + 4 + 32)

Fig. 3/21: Example of set station numbers

Page 40: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-16 Festo P.BE-DLP-VSE-... en 0206a

Setting the diagnostic mode

The following diagnosis can be activated/deactivated withswitch element 8 of the 8-element DIL switch:

S PROFIBUS-DP device-related diagnosis active/inactive

Diagnosis ON

Diagnosis OFF

Fig. 3/22: Setting the diagnostic mode

If the device-related diagnosis is masked out with switch el-ement 8, no diagnostic information about the Local controlunit will be sent to the master system, e.g. short circuit atoutputs or undervoltage at the valves (see chapter 5.2).

Page 41: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-17Festo P.BE-DLP-VSE-... en 0206a

3.3.3 Connecting the field bus

Field bus cable

Use a twisted screened 2-core cable for the field bus.

Please notePlease observe the cable specifications.During the exchange of data, transmission errors, signalreflections and signal attenuation occur, especially withhigh baud rates. Both can lead to transmission faults. Thecauses of reflections may be:

missing or incorrect terminating resistor

branches

The causes of signal attenuation may be:

transmission over long distances

unsuitable cables

Please refer to the manual for your controller for informa-tion on the cable type to be used.

If you use the Festo IP65 plug, the cable must have adiameter of 7-10 mm.

Please noteConnect the screening of the field bus cable with a shortcable to the earth potential (PE) (length of cable max.20 cm, cross-sectional area at least 1.5 mm2)

Page 42: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-18 Festo P.BE-DLP-VSE-... en 0206a

Field bus baud rate and field bus length for PROFI-BUS-DP

The maximum permitted field bus length depends on thebaud rate used. The table in Fig. 3/23 shows the baud rateswhich can be used.

Please noteThe Local control unit sets itself automatically to one of thebaud rates listed in Fig. 3/23.

Length of branch lines

Please noteS Please note the maximum permitted length of the fieldbus cable if you connect the Local control unit via abranch line.

S When calculating the maximum permitted length of thefield bus cable, also take into consideration the sum ofthe branch line lengths.

Page 43: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-19Festo P.BE-DLP-VSE-... en 0206a

The maximum permitted length of a branch line depends onthe cable type and on the baud rate.

Baud rate(in kBaud)

Field bus length(max.)

Maximum per-mitted branchline length

9.6 1200 m 500 m

19.2 1200 m 500 m

93.75 1200 m 100 m

187.5 1000 m 33.3 m

500 400 m 20 m

1500 200 m 6.6 m

3000-12000 100 m

Fig. 3/23: Maximum permitted field bus and branch linelengths for PROFIBUS-DP depending on the baudrate

Recommendation:Use a cable with a capacitance per unit length of < 30 nF/kmas specified below.Otherwise the permitted cable length will have to be reduced.

Cable specification as per EN 50170 (cable type A):Surge impedance 135-165 Ohm (3-20 MHz)Capacitance per unit length < 30 nF/kmLoop impedance < 110 Ohm/kmCore diameter > 0.64 mmCore cross sectional area > 0.34 mm2

Page 44: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-20 Festo P.BE-DLP-VSE-... en 0206a

Connecting the field bus

Please notePlease note that only the Festo plug complies with protec-tion class IP 65.

Use plastic conduit-thread connectors for fitting the fieldbus plug. This creates better resistance to environmentalinfluences.

There is a 9-pin sub-D socket on the Local control unit forconnecting it to the field bus. This connection serves for thesupply cable as well as for the continuing field bus cable. Youcan connect the Local control unit with the sub-D plug fromFesto (part no. 18529).

Pin Festo sub-D plug (IP65) PROFIBUS-DP Designation

123456789Housing

B

A

Cable clip

n.c.n.c.RxD/TxD-PCNTR-P 1)

DGNDVPn.c.RxD/TxD-Nn.c.Screening

not connectednot connectedReceive/send data PRepeater control signalData reference potential (M5V)Supply voltage positive (P5V)not connectedReceive/send data Nnot connectedConnection to housing

1)The repeater control signal CNTR-P is in the form of a TTL signal.

Fig. 3/24: Pin assignment of the field bus interface (view of socket)

Page 45: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-21Festo P.BE-DLP-VSE-... en 0206a

Please noteConnecting sub-D plugs of other manufacturers

S Before connecting sub-D plugs of other manufacturesreplace the two flat screws by bolts(Festo part no. 340 960).

Connecting the screening

A floating screening connection is provided by the Festosub-D plug.

S Clamp the screening of the field bus cable under the cableclip of the Festo sub-D plug (Fig. 3/25).

1 Screening con-nection, cableclip

2 Only connectedcapacitively

A B --A B --

ON

1

2

Fig. 3/25: Connecting the screening

Please noteThe cable clip in the Festo sub-D plug is connected inter-nally only capacitively with the metallic housing of thesub-D plug. This is to prevent equalizing currents fromflowing through the screening of the field bus cable(Fig. 3/25).

Page 46: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-22 Festo P.BE-DLP-VSE-... en 0206a

3.3.4 Bus termination with terminating resistors

Please noteUse a bus termination at both ends of a bus segment. Thisalso applies when the bus module or bus interface is at thebeginning of the bus cable.

If the Local control unit is at the end of the field bus system, abus termination is necessary.

Recommendation:Use here the sub-D plug from Festo (part no. 18529). A suit-able resistor network is provided in the housing of the sub-Dplug. The bus termination must be switched manually withslide switches.

1 Sealing plug

Bus termination

switched onnotswitched on

1

Fig. 3/26: Switch for bus termination in the Festo sub-D plug

Page 47: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-23Festo P.BE-DLP-VSE-... en 0206a

1 Switch in theFesto plug

Pin 6Power supply

Pin 3RxD/TxD-P

Pin 8RxD/TxD-NRxD/TxD-N

Pin 5DGNDDGND

390 Ω

220 Ω

390 Ω

1

Fig. 3/27: Circuit diagram for bus termination network for cable type A as per EN 50 170

Page 48: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-24 Festo P.BE-DLP-VSE-... en 0206a

3.3.5 Fibre-optical waveguide

We recommend fibre-optical waveguide technology for trans-mission in areas which are subjected to heavy interference,as well as for extending the range of transmission with highbaud rates.

This offers the following extra advantages:

high degree of EMC compatibility, ESD protection due tothe optical transmission of the signals

protection against lightning

potential isolation of the individual DP slaves

The PROFIBUS-DP interface of the Local control unit has beendesigned in accordance with specification EN 50170 volume 2and therefore supports the control of network componentsfor fibre-optical waveguides.Examples of fibre-optical waveguide network components:

Siemens optical link module (OLM) for PROFIBUS plus

Siemens optical link plug (OLP) for PROFIBUS

Page 49: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-25Festo P.BE-DLP-VSE-... en 0206a

3.4 Connection with AS-Interface (on DLP-VSE-...-ASi)

3.4.1 Assigning the AS-i address

Recommendation: Use the Festo addressing device ASI-PRG-ADR part no. 18959 with adapter cable part no. 18960 (orSiemens PSG).

Before connecting an AS-i slave to the bus:assign an unused AS-i address to each AS-i slave. Set thedesired address with the AS-i addressing device. Permittedaddress range 1 ... 31.

Please noteThe AS-i address of the Local control unit with connectionto the AS-Interface is saved electronically after everymodification (no battery) and can be modified as often asdesired.

Remark:

Factory setting of the Local control unit address 00

ID code = FH; IO code = 7H (see type plate)

It is not necessary to parametrize the AS-i slave.

Page 50: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-26 Festo P.BE-DLP-VSE-... en 0206a

3.4.2 Connecting the limit switch (PNP inputs)

Information on the pin assignment and on connecting theinputs can be found in chapter 3.2.2.

Please noteThe inputs are resistant to short circuits. In the event of ashort circuit, the slave will be switched off. The AS-i masterregards this slave as missing. When the short circuit hasbeen eliminated, the slave indicates immediately that it isfunctioning again.

3.4.3 Festo installation accessories

Recommendation:Use the Festo cable sockets ASI-SD-FK, part no. 18785 forconnecting the Local control unit. You will then comply withprotection class IP65.

Proceed as follows:

1. Connect the cable sockets as described in the separatebrief description.

2. Lay the AS-i cable free of tension.

3. Mount the cable socket and screw it tight.

Page 51: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-27Festo P.BE-DLP-VSE-... en 0206a

1 Yellow flat cable

2 Black flat cable

3 Cable socket

4 Cable cap

1

2

3

4

Fig. 3/28: Connecting the AS-i flat cable

Please note with branch lines:

the maximum total length on the AS-i bus: 100 m.

the length of the load voltage cable (depends on the cur-rent consumption of the Local control unit and the fluctu-ations in the load voltage).

Fit Festo cable caps ASI-KK-FK or cable sleeves ASI-KT-FKto open ends of cables. In this way you can avoid leakagecurrents and comply with protection class IP65.

Page 52: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-28 Festo P.BE-DLP-VSE-... en 0206a

3.4.4 Connecting the AS-i bus and the load voltage

Please noteThe power supply for the inputs is provided via the AS-ibus.The Local control unit must always be provided with 24 Vseparately via the load voltage connection(black flatcable).

The AS-Interface has an integrated watchdog functionwhich resets the outputs in the event of failure of the buscommunication.

1 0 V

2 +24 V

3 AS-i (light blue)

4 AS-i + (brown) 24V DC BUS

1 2 3 4

Fig. 3/29: Assignment of the AS-Interface connections

Page 53: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-29Festo P.BE-DLP-VSE-... en 0206a

3.4.5 Example of connections Local control unit with EMERGENCY STOP

The diagram below shows an example of connection of theLocal control unit with an EMERGENCY STOP function.

1 Festo combipower unit

2 AS-i master

3 Yellow flat cable

4 DLP-VSE-...-ASI

5 Black flat cable

6 EMERGENCYSTOP relay

6 5

4

32

1

Fig. 3/30: Example of connection

Festo accessories

Designation Type

AS-i combi power unit ASI-CNT-115/230-VAC-B

AS-i bus cable (yellow) KASI-1.5-Y-100

Additional supply cable (black) KASI-1.5-Z-100

AS-i cable cap ASI-KK-FK

AS-i cable sleeve ASI-KT-FK

Identification signs IBS6x10

Page 54: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

3. Installation

3-30 Festo P.BE-DLP-VSE-... en 0206a

Page 55: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-1Festo P.BE-DLP-VSE-... en 0206a

4. Commissioning

Please noteIf your Local control unit has a bus module with PROFIBUS-DP or AS-Interface, please read first chapter 4.2 resp. 4.3and 4.4.

4.1 Commissioning the pneumatic components

4.1.1 Switching on the operating voltage

WarningMake sure that the connected pneumatic fittings are notunder pressure. Bring the Local control unit into the follow-ing basic position:

key-operated switch to position 0 with DLP-VSE-3-...: knob-operated switch to positionHALT/STOP

Fig. 4/1: Basic position on the DLP-VSE-2-...

Page 56: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-2 Festo P.BE-DLP-VSE-... en 0206a

Fig. 4/2: Basic position on the DLP-VSE-3-...

S Apply current to the Local control unit at the socket forthe power supply. The green LED POWER will light up.

4.1.2 Switching on the compressed air

1. Only with DLP-VSE-3-...: turn the knob-operated switch toHALT/STOP.

2. Turn the key-operated switch to HAND/LOCAL. The fittingscan now be set with the knob-operated switch of the Localcontrol unit.

3. Switch on the compressed air.

4. Turn the knob-operated switch to AUF/OPEN or ZU/CLOSE.

WarningMake sure that the movement of the fittings correspondsto the labelling on the knob-operated switch.

Page 57: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-3Festo P.BE-DLP-VSE-... en 0206a

5. If the movement does not correspond to the labelling:modify the tubing (see below).

6. Repeat steps 4 and 5 for the other position.

7. Position the limit switch (see below).

8. Local control unit with bus module: commission the Localcontrol unit in accordance with chapter 4.2 or 4.3 .

9. Use the key-operated switch to select the desired operat-ing mode.

10. Remove the key from the switch and keep it in a safeplace.

Please noteRemove the key from the switch when the Local controlunit is operating. The lock barrel will then be better pro-tected against environmental influences.

Modifying the tubing

If the movement of the fittings does not correspond to thelabelling on the knob-operated switch, modify the tubing asfollows:

1. Turn the key-operated switch to 0.

2. Only with DLP-VSE-3-...: turn the knob-operated switch toHALT/STOP.

3. Switch off the compressed air.

4. Swap the tubing.

5. Repeat the steps in section 4.1.2.

Page 58: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-4 Festo P.BE-DLP-VSE-... en 0206a

Please noteIn cases of extreme fluctuations in temperature, check theseating of the conduit-thread screw connectors on theplugs. If necessary, tighten them.

4.1.3 Positioning the limit switches

In order that the Local control unit can function faultlessly, thelimit switches must be positioned as follows:

1. Move the fittings into a defined end position (key-oper-ated switch to HAND/LOCAL, knob-operated switch toAUF/OPEN or ZU/CLOSE).

2. Position the appropriate limit switch.

3. Repeat steps 1 and 2 for the other end position.

4. Compare the end positions with the signals from the indi-cator lights in accordance with the table below.

Position ofknob-operatedswitch

Position offittings

Indicator light

ZU/CLOSE Closed ZU/CLOSE lightsup

AUF/OPEN Open AUF/OPEN lightsup

Page 59: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-5Festo P.BE-DLP-VSE-... en 0206a

4.2 Commissioning on the PROFIBUS-DP

4.2.1 Assigning the inputs and outputs

The following tables show the assignment of the inputs andoutputs.

Input Meaning

Input 0 Key-operated switch to HAND/LOCAL

Input 1 Key-operated switch to AUTO/REMOTE

Input 2 Limit switch signal Open

Input 3 Limit switch signal Closed

Fig. 4/3: Bit assignment of the inputs

Output Meaning

Output 0 Open fittings

Output 1 Close fittings

Output 2 Indicator light AUF/OPEN

Output 3 Indicator light ZU/CLOSE

Fig. 4/4: Bit assignment of the outputs

Page 60: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-6 Festo P.BE-DLP-VSE-... en 0206a

4.2.2 Preparing the Local control unit for commissioning

Switching on the operating voltage

Please notePlease observe also the switching-on instructions in themanual for your PLC controller.

When the controller is switched on, it automatically carriesout a comparison between the NOMINAL and the ACTUALconfigurations. For this configuration run it is important that:

the specifications for the field bus configuration are com-plete and correct.

the power supplies for the PLC and the field bus slavesare switched on either simultaneously or in the sequencespecified below.

Please note the following points when switching on the powersupply:

Commonsupply

If there is a common power supply for the control systemand all the field bus slaves, the power should be switchedon via a central power unit or switch.

Page 61: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-7Festo P.BE-DLP-VSE-... en 0206a

Separatesupply

If the control system and the field bus slaves have separatepower supplies, the power should be switched on in thefollowing sequence:

1. the power supply for all the field bus slaves

2. the power supply for the controller.

FREEZE and SYNC

The operating modes FREEZE and SYNC are supported by theFesto Local control unit in accordance with EN 50170 (DIN19245). The use of the FREEZE or SYNC command dependson your master controller. Please refer to the documentationfor your field bus module for further information.

CautionIn the following cases, the FREEZE or SYNC mode will beautomatically reset:

when the Local control unit is switched on/off

when the field bus module has stopped

The FREEZE mode will also be automatically reset in thefollowing case:

when the bus connection to the Local control unit is in-terrupted (response monitoring active).

FREEZE With this function all the inputs of the Local control unit canbe frozen. The Local control unit then sends a constantinput image of all the inputs to the master. The followingFREEZE command causes the input image to be updated.The updated input image is then sent constantly to themaster.Return to normal operation with the UNFREEZE command.

Page 62: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-8 Festo P.BE-DLP-VSE-... en 0206a

SYNC With this function all the outputs of the Local control unitcan be frozen. As a consequence, the Local control unit nolonger reacts to modifications of the output image in themaster. The following SYNC command causes the outputimage of the master to be updated.Return to normal operation with the UNSYNC command.

Module consistency

The Local control unit supports the following variants of mod-ule consistency:

via the selected format (word)

The configuration

The position of the DIL switch for the configuration is relevantfor the required DP identifier of the Local control unit (seechapter 3.2.1)

DP identifier Comment

1 8DX 8 digital inputs and outputs(4 used)

Example 1: Local control unit in the configuration withoutmeasurement bus

DP identifier Comment

1 8DX 8 digital inputs and outputs(4 used)

2 1AE analogue measured value

Example 2: Local control unit in the configuration withmeasurement bus

Page 63: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-9Festo P.BE-DLP-VSE-... en 0206a

4.2.3 Configuration with a Siemens master

Please noteVarious configuration programs are available in conjunc-tion with a Siemens master. Note the relevant procedurewith your configuration program.

COM PROFIBUS 3.x

Preparations

1. Copy the Device data base of the Local control unit tothe directory \COMPB3x\GSD of your PC or programmer.You can also find the Device data bases in the GSD li-brary in Internet underhttp://www.profibus.comor on the accompanying CD ROM.File: VSE-045B.GSD

Further information (directories, etc.) can be found inthe file readme in the main directory of the CD ROMpreparations.

Please noteUpdate the slave catalogue when you copy the Device database while working with COM PROFIBUS.Menu File - Load GSD file.

Page 64: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-10 Festo P.BE-DLP-VSE-... en 0206a

2. There are Bitmap files with symbols on the CD ROM tofacilitate configuration.Copy the files LP-VSEN.BMP and DLP-VSES.BMPinto directory \COMPB3x\BITMAPS\ on your PC/pro-grammer.

3. Process the fields- Bus profile- Baud ratein the menu Configure in the mask Bus parameter

Further information (directories, etc.) can be found in thefile readme in the main directory of the CD ROM.

Page 65: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-11Festo P.BE-DLP-VSE-... en 0206a

Selecting the station

12 5 3

4

Fig. 4/5: Station selection with COM PROFIBUS (explanations see text)

1. With the left-hand mouse key mark the slave typeVALVES1 in the slave catalogue. The slave typeVALVES will appear if you have copied the Device database correctly (see step 1 of the preparations).

2. Move the mouse to the left and click below graphic 2.

3. The entry mask PROFIBUS address3 will appear. Se-lect the slave address identical to the selected setting ofthe DIL switch in the switch module (see page 3-14) andconfirm this.

Page 66: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-12 Festo P.BE-DLP-VSE-... en 0206a

4. The entry mask Slave parameters4 will appear. Selectthe station type FESTO VORORT / LOCAL and confirmthis with OK.

The icon of the Festo Local control unit5 will appear underthe graphic of the master. The icon will appear if you havecopied the Bitmap file correctly (see step 3 of the prepara-tions).

Station selection is then completed.

COM PROFIBUS configuration

Prerequirements:

the Device data base must be in the directory of your PC/programmer.

the mask Bus parameter must be processed (bus pro-file, baud rate)

the PROFIBUS address must be assigned (see above)

the station type FESTO VORORT / LOCAL must be se-lected (see above)

Page 67: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-13Festo P.BE-DLP-VSE-... en 0206a

Access the mask Configure:

1. Double-click with the left-hand mouse key or once withthe right-hand key on the icon of the Festo Local controlunit.

2. Select Configure from the menu which appears.

The mask Configure appears (Fig. 4/6).

The program has already entered the DP identifier for the 4inputs and outputs of the Local control unit automatically inthis mask.

If you work in the configuration with measurement bus (seechapter 3.3.2),

S enter the identifiers for the angle measurement. 1AE(50hex)

S Confirm with OK.

Fig. 4/6: Configuration with COM PROFIBUS (example: configuration with measurementbus)

Page 68: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-14 Festo P.BE-DLP-VSE-... en 0206a

Input and output address

Enter the starting addresses of the inputs and outputs underI-address or O-address.

Example(Addresses used as from input/output word 42)

DP identifier Order number Comment Inputaddress

Outputaddress

1 8DX P042 P042

2 1AE analogue: 1AE P044

Please noteWith a marked I/O address range, the function Auto ad-dress carries out an automatic assignment of the freeaddresses of the system, depending on the system limits.

Configuration/address assignment with COM PROFIBUS isthen completed.

Page 69: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-15Festo P.BE-DLP-VSE-... en 0206a

STEP 7 V4.x Hardware configurator

Preparations

1. Copy the Device data base of the Local Control Unit intothe directory \STEP7\S7DATA\GSD of your PC or pro-grammer.You will find the Device data bases on the accompanyingCD ROM or in the GSD library in Internet underhttp://www.profibus.comFile: VSE-045B.GSD

You can either:

S copy the Device data base manually into the above-men-tioned directory or

S load it via menu item Extras Install new GSD in themask Hardware config.

Further information (directories, etc.) can be found in the filereadme in the main directory of the CD ROM.

Please noteUpdate the hardware catalogue when you copy the Devicedata base while working with STEP7. Menu in Hardwareconfig: Extras Update catalogue.

Page 70: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-16 Festo P.BE-DLP-VSE-... en 0206a

Please noteAs from STEP7 version V4.02, Device data bases are savedin the STEP7 project (station Device data bases). This cancause the updating/loading of new Device data bases tobe carried out incorrectly. Please inform yourself abouthandling the station Device data bases in the STEP7 help.

2. There are Bitmap files with icons of the Local control uniton the CD ROM or in Internet to facilitate configuration.Copy the files DLP-VSEN.BMP and DLP-VSES.BMPinto directory \STEP7\S7DATA\NSBMP on your PC/pro-grammer.

The Bitmaps can either:S be copied manually into the above mentioned

directory orS loaded via menu item Extras Install new device

master files- file type Bitmap in Hardware config.

3. Process the mask Properties of the DP master Bus profile Baud rate

4. Activate the DP master in the rack.

Page 71: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-17Festo P.BE-DLP-VSE-... en 0206a

Station selection and configuration

1 23

Fig. 4/7: Station selection with STEP7 V4.x Hardware config (the masks shown are notall visible at the same time, see text)

1. Click catalogue icon1. This will then open the hardwarecatalogue.

2. Use the left-hand mouse key2 to mark station typeFESTO VORORT / LOCAL (\PROFIBUS-DP\further FIELDDEVICES\VALVES) in the hardware catalogue.The slave type VALVES will only appear underfolderAdditional FIELD DEVICES, if you have copied the

Page 72: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-18 Festo P.BE-DLP-VSE-... en 0206a

Device data base correctly (see step 1 of the prepara-tions).

3. Hold the left-hand mouse key pressed down and pull thecursor onto the graphic PROFIBUS line on the DP master(drag and drop)3.

4. The entry mask Properties PROFIBUS node will thenappear.Select the slave (PROFIBUS) address identical to the se-lected setting of the DIL switch in the switch module (seechapter 3.3.2) and confirm with OK.The icon of the Local control unit appears in the PROFI-BUS line (see Fig. 4/6).

5. Mark the icon of the Local control unit4 to be configuredon the graphic user level of the Hardware config. The con-figuration data with the columns DP ID, Ordernumber, Input address, Output address, Commentappear in the table in the lower half of the monitor screen.

Page 73: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-19Festo P.BE-DLP-VSE-... en 0206a

4 5

6

Fig. 4/8: Configuration with STEP7 Hardware catalogue

6. Open the directory FESTO VORORT / LOCAL in the hard-ware catalogue and mark module5 corresponding to theconfiguration of your Local control unit.

7. With the mouse key pressed down, pull the marked mod-ule out of the hardware catalogue and onto the next freeline of the configuration table6.

Page 74: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-20 Festo P.BE-DLP-VSE-... en 0206a

Modifying the address

The input addresses and output addresses are assignedautomatically by STEP7. Proceed as follows, if you wish tomodify this address assignment:

Open the mask Features of DP slave by double-clickingthe appropriate line in the configuration table of the DP slaveand modify the starting address of the inputs/outputs.

Fig. 4/9: Modifying the address

Please noteIn S7-400 controllers 4 bytes of addresses are always re-served per DP identifier.

Station selection is then completed.

Recommendation:Providing the safety concept of your machine/system per-mits, commission the Local control unit with both operatingvoltages (pins 1 and 5) but without compressed air.You therefore have a suitable test function which does nottrigger undesired reactions.

Page 75: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-21Festo P.BE-DLP-VSE-... en 0206a

4.2.4 Operation with general DP master

The Festo Local control unit can be controlled from any PLC,PC or industrial PC with a PROFIBUS-DP module in accord-ance with EN 50170 (DIN 19245). Information on the func-tions FREEZE, SYNC and the DP identifiers can be found insection 4.2.1.

Bus run-up

Before the Local control unit can be commissioned properly,the DP master must perform the following functions in thesequence specified.

1. send parametrizing telegrams

2. send configuration telegrams

3. request diagnostic information

4. start cyclic data transmission

The structure and contents of the individual telegrams aredescribed in the following chapters.

Page 76: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-22 Festo P.BE-DLP-VSE-... en 0206a

Sending parametrizing data

The parametrizing data are transmitted from the DP master tothe Local control unit with the function Set_Prm .

Octet 1 Station status

Bit Meaning Explanation

0 - Reserved

1 -

2 -

3 WD_On Response monitoring (watchdog) of the Local control unit on/off:log. 0: Offlog. 1: On

4 Freeze_Req log. 0: Freeze mode not requested by masterlog. 1: Freeze mode set by master

5 Sync_Req log. 0: Sync mode not requested by masterlog. 1: Sync mode set by master

6 Unlock_Req Bit 7 Bit 6 Explanation

7 Lock_Req 0 0 min TSDR + slave parameter may be overwritten

0 1 Local control unit for other mastersenabled

1 0 Local control unit for other mastersblocked

1 1 Local control unit for other mastersenabled

Page 77: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-23Festo P.BE-DLP-VSE-... en 0206a

Further octets

Octet Designation Explanation

2 and 3 WD_Fact_1WD_Fact_2

Range 1-255: the response monitoring time of theLocal control unit is transmitted with these twooctets:TWD [s] = 10ms * WD_Fact_1 * WD_Fact_2

4 Minimum station delay re-sponder (min TSDR)

The minimum time the Local control unit must waitbefore the reply telegram may be sent to the DPmaster.

5 and 6 Ident_Number Transmitting the Ident number (= 045B) of the Localcontrol unit;Parametrizing telegrams to the Local control unit areonly accepted if the transferred Ident number and theprogrammed Ident number are the same.

7 Group_Ident Not supported by the Local control unit

8 ... 32 User_Prm_Data Not supported by the Local control unit

Sending configuration data

The configuration data are transmitted from the DP master tothe Local control unit with the function Chk_Cfg .

Summary of parameters (Chk_Cfg):

Octet 1-n DP identifierPermitted identifiers for Festo CP systemsin compact mode.

Number of inputs/outputs

DP identifierdecimal hex

Comment

4 Octet 1 8DX Octet 1 30 4 digital inputs and outputs

1 analogue Octet 2 1AE Octet 2 50 analogue measured value

Page 78: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-24 Festo P.BE-DLP-VSE-... en 0206a

Request diagnostic information

The diagnostic data are requested by the Local control unitwith the function Slave_Diag. A description of this functioncan be found in chapter 5.2, Diagnosis with PROFIBUS-DP.

Cyclic exchange of data

The cyclic exchange of data is carried out with functionData_Exchange. With this function, the output data for theLocal control unit are transferred as an octet string of lengthx. The length of the octet string depends on the number ofidentifier bytes.

Please noteWith the function Data_Exchange the Local control unitexpects the output information for the valve and electricoutputs. The input information is sent as a reply telegramto the master.

Summary of parameters (Data_Exchange):

Octet 1 I/O data byte_1Bit 0 Input/output x*)Bit 1 Input/output x*+1)Bit 2 Input/output x*+2)Bit 3 Input/output x*+3)Bit 4 Input/output x*+4)Bit 5 Input/output x*+5)Bit 6 Input/output x*+6)Bit 7 Input/output x*+7)

Octet 2 I-data byte_2Bit 0 Input x+8Bit 1 Input x+9

...Bit 7 Input x+15

Page 79: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-25Festo P.BE-DLP-VSE-... en 0206a

Octet 3 I-data byte_3Bit 0 Input y *)Bit 1 Input x+1

...Bit 7 Input x+7

*) x, y = address offset of master module

Page 80: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-26 Festo P.BE-DLP-VSE-... en 0206a

Summary of implemented functions and service ac-cess points (SAP)

Function Available Destination SAP(DSAP)

Data_Exchange Yes NIL

RD_Inp Yes 56

RD_Outp Yes 57

Slave_Diag Yes 60

Set_Prm Yes 61

Chk_Cfg Yes 62

Get_Cfg Yes 59

Global_Control Yes 58

Set_Slave_Add No 55

Bus parameter/reaction times

Baud rate(kBaud)

max TSDR (TBit) max TSDR (TBit)

...187.5 60

500 100

1500 150 11

3000 250

11

6000 450

12000 800

Page 81: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-27Festo P.BE-DLP-VSE-... en 0206a

Baud rates on the PROFIBUS-DP

Please noteS Note here the cycle time of your PLC and the update timeof the PROFIBUS-DP.

The delay time in the Local control unit depends on theamount of data. It amounts to: < 2 ms.

Please refer to the manual for your controller for calculatingthe total transmission time.

4.2.5 Device data base (GSD)

CD ROM The accompanying CD ROM contains the Device data base(GSD) with the specific standardized Device data bases forthe Local control unit. Further information can be found inthe file Readme on the CD ROM.

You can also find the Device data base in the GSD library inInternet under http://www.profibus.com

The Device data base contains a selection of identifiers inaddition to the slave-typical entries (Ident number, revision,etc.).

Page 82: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-28 Festo P.BE-DLP-VSE-... en 0206a

4.3 Commissioning on the AS-Interface

4.3.1 Assigning the data bits

The following tables show the assignment of the data bitswhich can be sent or received.

Data bit Input Meaning

D0 Input 0 Key-operated switch to HAND/LOCAL

D1 Input 1 Key-operated switch to AUTO/RE-MOTE

D2 Input 2 Limit switch signal Open

D3 Input 3 Limit switch signal Closed

Fig. 4/10: Bit assignment for AS-Interface (inputs)

Data bit Output Meaning

D0 Output 0 Open fittings

D1 Output 1 Close fittings

D2 Output 2 Indicator light AUF/OPEN

D3 Output 3 Indicator light ZU/CLOSE

Fig. 4/11: Bit assignment for AS-Interface (outputs)

Page 83: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-29Festo P.BE-DLP-VSE-... en 0206a

4.4 Commissioning test for PROFIBUS-DP and AS-Interface

WarningCheck the configuration of your system before commis-sioning the Local control unit with your bus system.

1. Turn the key-operated switch to the position AUTO/RE-MOTE. The Local control unit will now be controlled byyour bus system.

2. Test the controller and the movement of the fittings withyour bus system.

Information on error treatment can be found in the chapterDiagnosis and error treatment.

Page 84: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

4. Commissioning

4-30 Festo P.BE-DLP-VSE-... en 0206a

Page 85: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

5. Diagnosis

5-1Festo P.BE-DLP-VSE-... en 0206a

5. Diagnosis

5.1 Eliminating faults

5.1.1 Pneumatic components

When you switch on the compressed air supply or subse-quently check the individual valves, you can learn the follow-ing about the operating status of the pneumatic system.

Faults Setting of the fittings Error treatment

Air comes out of the com-mon tubing connections

basic position undefined position

1. Switch off the compressed air supply2. Check the sealing ring or the tubing

fitting (slightly grease the plugscrews)

The fittings do not react asexpected

unexpected 1. Switch off the compressed air supply2. Check the tubing3. After switching on again check the

operating pressure If faults still exist: return for servicing

Indicator light does notlight up

Cable connection to limit switch inter-rupted

Incorrect tubing connection LED in indicator light defective

Fig. 5/1: Eliminating faults

Page 86: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

5. Diagnosis

5-2 Festo P.BE-DLP-VSE-... en 0206a

5.1.2 Electric components

Error messages of the electric components

Indicator light Setting of the fittings Meaning

Indicator light does not lightup, although the fitting is in theappropriate position.

switch position Incorrect connection for limitswitch

Limit switch does not supply asignal

Compressed air supply not cor-rect.

Fault in bus module(only DLP-...-DP or -ASI)

Indicator light defective

Both indicator lights light up basic position or switch position

Incorrect connection for limitswitch

Fault in bus module(only DLP-...-DP or -ASI)

Servicing required

Fig. 5/2: Indicator light displays showing the position of the fittings

5.1.3 Replacing the indicator lights

If the indicator lights for AUF/OPEN or ZU/CLOSE are defec-tive, you can replace these yourself.

1. Unscrew the transparent part of the cap.

2. Replace the LED. Use a bulb remover here for bulb typeBA9S.

3. Screw the cap into place again.

Page 87: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

5. Diagnosis

5-3Festo P.BE-DLP-VSE-... en 0206a

5.1.4 Status displays (LED) of the inputs and outputs (only with DLP-...-DPand ...-ASI)

You can read the status of the inputs and outputs on the LEDdisplays.

1 Status display(LEDs) of the in-puts

2 Status display(LEDs) of theoutputs

0123 0123

1 2

Fig. 5/3: LED displays for the inputs and outputs

LEDOutput

Meaning LEDInput

Meaning

0 Open fittings 0 Key-operatedswitch to HAND/LOCAL

1 Close fittings 1 Key-operatedswitch to AUTO/RE-MOTE

2 Indicator lightAUF/OPEN

2 Limit switch signalOpen

3 Indicator lightZU/CLOSE

3 Limit switch signalClosed

Fig. 5/4: Meaning of the LED display

Page 88: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

5. Diagnosis

5-4 Festo P.BE-DLP-VSE-... en 0206a

5.2 Diagnosis when connected to PROFIBUS-DP

5.2.1 Diagnosis with the LEDs POWER and BUS

On the user interface there are two LEDs (POWER and BUS)by means of which you can read diagnostic messages fromthe Local control unit.

DisplayPOWER-LED

Operating status Error treatment

out Operating voltage for the electronicsis not applied

S Check the operating voltage con-nection (pin 1)

flashes fast Load voltage < 20.4 V (Vtol) S Check the operating voltage supply(pin 5)

flashes slowly Load voltage < 10 V (Vval) S Check the operating voltage supply(pin 5)

Fig. 5/5: Error diagnosis with the green POWER-LED

Load voltage faults are always shown with the green LED,irrespective of the diagnostic mode set.

If the device-related diagnosis is activated, the faults will alsobe communicated to the master PLC via the field bus connec-tion.

Page 89: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

5. Diagnosis

5-5Festo P.BE-DLP-VSE-... en 0206a

DisplayBUS-LED

Operating status Error treatment

out normal, no fault

lights up red Hardware fault S servicing required

flashes slowly(1 second inter-vals)

Field bus connection not correct.Possible causes Station number not correct (e.g. ad-

dress assigned twice) switched-off or defective field bus

module interrupted, short-circuited or

faulty field bus connection Configuration faulty. Master con-

figuration setting in the switchmodule

Check the ...

S address setting

S field bus module

S field bus connection

S configuration of the master and thesetting in the switch module

flashes (outbriefly)

Switch module missingSwitch module defective

S Insert switch moduleS Replace switch module

Fig. 5/6: Error diagnosis with the red BUS-LED

5.2.2 Diagnosis with PROFIBUS-DP

The Local control unit supports diagnostic possibilities via thePROFIBUS in accordance with EN 50170 (DIN 19245). (Thedevice-specific diagnosis is supported).

Please noteThe identifier-related or channel-related diagnosis listed inEN 50170 (DIN 19245) is not supported.

Page 90: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

5. Diagnosis

5-6 Festo P.BE-DLP-VSE-... en 0206a

5.2.3 Diagnostic words

The following error states of the Local control unit aregrouped into diagnostic words and passed on to the DPmaster:

Failure of the load voltage supply to the valve (pin 5 of thesocket for the power supply)

Short circuit in power supply to the sensors

Failure of the load voltage supply at the outputs

Short circuit/overload at the outputs

Drop below lower tolerance in voltage supply to proces-sing valves (< 20.4 V)

Diagnostic measurement bus

Diagnostic possibilities

As a slave on the PROFIBUS DP the Local control unit offersextensive diagnostic possibilities via the PROFIBUS-DP. Thediagram below shows the steps which are necessary for diag-nosing the Local control unit.

123 04567

123 04567

123 04567

1

Bit

Station status 1

Device-related diagnosis 1

Bit

Bit

Device-related diagnosis 2

Device-relateddiagnosis exists

see chapter 5.2.4

see chapter 5.2.4

Fig. 5/7: Diagnostic steps

Page 91: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

5. Diagnosis

5-7Festo P.BE-DLP-VSE-... en 0206a

Please noteThe diagnostic information is only sent to the master sys-tem when device-related diagnosis is activated in theswitch module. To do this, set switch element 8 of the8-element DIL switch to ON.

When you are commissioning your system, it can in somecases be useful if you switch off the device-related diagnosis.If your controller does not start, try the setting Device-re-lated diagnosis inactive on the 8-element DIL switch(see chapter 3.3.2).

Summary of diagnostic bytes

Diagnostic words Several diagnostic words are provided for each bus slave.The diagnostic words and their meanings in conjunctionwith the Festo Local control unit are as follows:

Byte* Octet** Diagnostic address Diagnostic address+ 1

Octet** Byte*

0 1 Station status 1 Station status 2 2 1

2 3 Station status 3 Master address(Diag.master_Add)

4 3

4 5 Manufacturer identifica-tion(Ident_numberHigh byte 04)

Manufacturer identifica-tion(Ident_numberLow byte 5B)

6 5

6 7 Header Device-related diag-nosis 1

8 7

8 9 Device-related diag-nosis 2

always log. 0 10 9

Heavy print = Content will be modified by the Local control unit* = Siemens* = Siemens** = EN50170

Fig. 5/8: Diagnostic words

Page 92: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

5. Diagnosis

5-8 Festo P.BE-DLP-VSE-... en 0206a

5.2.4 Diagnostic information

The following diagnostic information can be requested by theDP master from the Local control unit via the functionSlave_Diag. The Local control unit replies with an octet stringof length 10.The procedure for reading this diagnostic information with aSIMATIC S5/S7 system is described in chapter 5.3.2.

Page 93: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

5. Diagnosis

5-9Festo P.BE-DLP-VSE-... en 0206a

Structure of station status 1

Bit Meaning Explanation for log. 1

0 Diag.Station_Non_Existent

Local control unit is no longer/not yet addressable.Possible causes Operating voltage not applied Data cable interrupted Fault in data cable

1 Diag.Station_Not_Ready Local control unit for data exchange not yet ready

2 Diag.Cfg_Fault The configuration data received from the master do not corre-spond to those ascertained by the Local control unit.

3 Diag.Ext_Diag Device-related diagnosis existsPossible causes Cable fracture at input/output Short circuit/overload at electric outputs Vvalves < 20.4 V Voutputs < 10 V Vsensor < 10 V

4 Diag.Not_Supported log. 1: The Local control unit does not support the functionrequested

5 Diag.Invalid_Slave_Response

always log. 0 (set by the Local control unit)log. 1: The DP master cannot interpret the reply

6 Diag.Prm_Fault Last parametrizing telegram faultylog. 1: Planned type is not correct

7 Diag.Master_Lock always log. 0 (set by the Local control unit)log. 1: Access by a different master

Fig. 5/9: Octet 1 Station status_1 (diagnostic byte 0)

Page 94: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

5. Diagnosis

5-10 Festo P.BE-DLP-VSE-... en 0206a

Structure of station status 2

Bit Meaning Explanation for log. 1

0 Diag.Prm_Req The master must configure the Local control unit again

1 reserved

2 reserved

3 Diag.WD_On Response monitoring (watchdog) is active

4 Diag.Freeze_Mode FREEZE activated

5 Diag.Sync_Mode SYNC activated

6 reserved

7 Diag.Deactivated always log. 0 (set by the Local control unit)

Fig. 5/10: Octet 2 Station status_2 (diagnostic byte 1)

Structure of station status 3

Bit Meaning Explanation for log. 1

0 ... 6 reserved

7 Diag.Ext_Diag_Overflow

always log. 0 (set by the Local control unit)

Fig. 5/11: Octet 3 Station status_3

Page 95: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

5. Diagnosis

5-11Festo P.BE-DLP-VSE-... en 0206a

Further octets

Octet Designation Explanation

4 Diag.Master_Add Master address:The address of the master, which parametrized theLocal control unit, is entered in this octet.

5 ... 6 Ident_Number Manufacturer identification:These octets contain the manufacturer identifier. Forthe Festo Local control unit: 045B

7 Ext_Diag_Data Device-related diagnosis:This octet represents the header for the device diag-nosis. The Local control unit enters the value 2 in thisoctet, i.e. 2 octets Device-related diagnosis, incl.the header octet, are made available.

Fig. 5/12: Summary of the octets 4 ... 7

Structure of device-related diagnosis 1

Device-related diagnosis 1 will only be sent to the master PLCwhen the device-related diagnosis in the switch module of theLocal control unit is activated.

Bit Meaning Explanation for log. 1

0 Short circuit/overload Short circuit/overload at electric output 0for processing valve position CLOSED

1 Short circuit/overload Short circuit/overload at electric output 1for processing valve position OPEN

2 Short circuit/overload Short circuit/overload at electric output 2for indicator light CLOSED

3 Short circuit/overload Short circuit/overload at electric output 3for indicator light OPEN

4 Vsen Short circuit/overload in sensor supply voltage < 10 V

5 Vval Supply voltage for valve solenoid coils < 20.4 V

Page 96: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

5. Diagnosis

5-12 Festo P.BE-DLP-VSE-... en 0206a

Bit Explanation for log. 1Meaning

6 Vload Supply voltage for valve solenoid coils < 10 V

7 always log. 0

Fig. 5/13: Octet 8 Device-related diagnosis 1 (diagnostic byte 7)

Structure of device-related diagnosis 2

Bit Meaning Explanation for log. 1

0 Bus-OFF Measurement bus in Bus-OFF status

1 No reply No communication with measuring point

2 Reserved

3 Reserved

4 Error 1 Measuring point cable fracture

5 Error 2 Measuring point

6 Error 3 Measuring point

7 Error 4 Measuring point

Fig. 5/14: Octet 9 Device-related diagnosis 2 (diagnostic byte 8)

Page 97: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

5. Diagnosis

5-13Festo P.BE-DLP-VSE-... en 0206a

5.3 Error treatment with PROFIBUS-DP

With the following faults, the reaction of the Local control unitdepends on the configured reaction of the master module.

Telegram failure

Master has stopped

Interruption in bus cable

If setting or configuration is successful, all the outputs (valvesor outputs) will be switched off or maintain their status.

WarningS Make sure that valves and outputs are reset when thefaults mentioned occur.

A dangerous situation can arise if the valves and outputsare not reset.

Page 98: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

5. Diagnosis

5-14 Festo P.BE-DLP-VSE-... en 0206a

5.3.1 General DP master

With the function Set_Prm you have the possibility of deter-mining the watchdog time (WD_Fact_1, Octet 2, WD_Fact_2,Octet 3). In the event of a fault, e.g. a bus failure, the Localcontrol unit will switch off all the valves and electric outputsafter the parametrized time.

5.3.2 Siemens SIMATIC S5/S7

With these controllers you can determine the reaction of theLocal control unit to the faults mentioned (details see con-troller manual).

Almost all configuration programs contain the function Re-sponse monitoring. For the operating modes mentioned, thetime specified corresponds to the drop-off time of the valvesand electric outputs.Further details on response monitoring can be found in theappropriate manuals.

You can set two types of error reactions of the control system.

S when a fault occurs the controller switches to the operat-ing mode STOP (hard error reaction) or

S when a fault occurs the controller remains in the operat-ing mode RUN (soft error reaction)

Page 99: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

5. Diagnosis

5-15Festo P.BE-DLP-VSE-... en 0206a

Control system Module Meaning STOP RUN

SIMATIC S5 withIM 308C

OB23 Reaction to QVZ withdirect periphery access

default OB is programmed

OB24 Reaction to QVZ withperiphery access viaprocess image

default OB is programmed

OB35 Reaction to PEU default OB is programmed

SIMATIC S7/M7 OB82 Reaction to a device-related diagnosis

default OB is programmed

OB86 Reaction to failure of aDP slave

default OB is programmed

QVZ: Acknowledgement delayOB: Organisation modulePEU: Periphery not clear

Fig. 5/15: Error reactions of the control system

Further details can be found in the appropriate manuals forthe control systems.

Possibility of reading diagnosis for S5/S7

The diagnosis for the PROFIBUS-DP is supported by functionmodules in the various control systems. These function mod-ules read out the slave diagnoses and write them in a datarange in the user program.

Page 100: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

5. Diagnosis

5-16 Festo P.BE-DLP-VSE-... en 0206a

Control system Functionmodule

See... Manufacturer

SIMATIC S5 withIM 308C

FB 192IM 308C

Manual ET 200 decentral periph-ery system

Siemens

SIMATIC S5 withS5-95U/DP master

FB 230S_DIAG

Manual ET 200 decentral periph-ery system

Siemens

SIMATIC S5 withS50/DP master

FB 230S_DIAG

Manual Programmable valve ter-minal with SB/SF 50

Festo

SIMATIC S7/M7 SFC 13DP NRM_DG

Reference manual System andstandard functions

Siemens

Fig. 5/16: Possibility of reading diagnosis for S5/S7

Example of a STEP 7 user program:

AWL ExplanationCALL SFC 13 Request readREQ:=TRUELADDR:=W#16#03FE Pointer to diagnostic address, e.g. 1022D = 03FEH

(see mask Features of DP slave in Hardware config)RET_VAL:=MW100 when faults occur, output error codeRECORD:=P#M110.0 WORD 4 Pointer to start of data range for diagnosis

and length of diagnostic dataBUSY:=M10.0 Reading finished

Fig. 5/17: Program example for Step 7

Page 101: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

5. Diagnosis

5-17Festo P.BE-DLP-VSE-... en 0206a

5.3.3 STEP 7 V4.x - Online diagnosis via diagnostic buffer

The diagnostic buffer of STEP7 offers the possibility of dis-playing diagnostic events of the S7 system in the order inwhich they occur.

1 2 3 4

56

Fig. 5/18: Online diagnosis via diagnostic buffer (explanation see text)

Page 102: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

5. Diagnosis

5-18 Festo P.BE-DLP-VSE-... en 0206a

Direct diagnostic events in conjunction with the Local controlunit can be:

decentral periphery: station failure- communication between slave and master interrupted

faulty module- see Device-related diagnosis

Transition from operating status START to RUN (nominal/actual difference)- Configuration data of the Local control unit do not corre-spondto the periphery- Local control unit has incorrect DIL setting

Prerequirements

Hardware config has been accessed

Proceed as follows (Fig. 5/18):

1. Switch from Offline to Online1

2. Use the right-hand mouse key to mark the CPU2 in therack. Now click Component status in the menu whichappears.

3. The window Component status appears3.

4. Select the rider Diagnostic buffer4.

5. Mark the event5 and read the details on the event.These will give you more detailed information on how toproceed further and depend on the S7 controller used.

Page 103: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

5. Diagnosis

5-19Festo P.BE-DLP-VSE-... en 0206a

Component status of the Local control unit

6. Mark the icon for the Local control unit6 instead of theCPU. By means of the window Component status youcan now read further information on the status of theLocal control unit.

5.4 Diagnosis with AS-Interface

On the user interface there are two LEDs (POWER and BUS)by means of which you can read diagnostic messages fromthe Local control unit.

POWER-LED(green)

ERROR-LED(red)

Meaning

on out AS-i voltage applied, no fault

out out No AS-i voltage on bus

flashes on AS-i address not set(= 0 )

on flashes Short circuit/overload at the in-puts

on on Failure of bus communication(Watchdog expired)

Fig. 5/19: Diagnostic displays with the LEDs POWER and BUSon AS-Interface

Page 104: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

5. Diagnosis

5-20 Festo P.BE-DLP-VSE-... en 0206a

Page 105: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

A. Technical specifications and index

A-1Festo P.BE-DLP-VSE-... en 0206a

A. Appendix

A.1 Technical specifications of the Festo Local control unit

General

Temperature range, operationas per EN 60654-1

-5 °C +50 °Cfollowing closely EN 60654-1,Class C1, weather-protected ap-plication sites

Temperature range, storage -40 °C +80 °C

Relative humidity 5 ... 95% condensing

Protection class(as per EN 60529)

IP 65 (fitted completely)

Medium Compressed air, filtered (40 ìm),lubricated (oil: VG 32) or non-lu-bricated

Pressure range 2 ... 8 bar

Compressed air connections G 1/8

Mounting position as desired

Vibration(as per IEC68, DIN/EN 60068) transport

operation

3.5 mm path at 2-9 Hz1g acceleration at 9-200Hz0.35 mm path at 10-60 Hz5g acceleration at 60-150Hz

Page 106: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

A. Technical specifications and index

A-2 Festo P.BE-DLP-VSE-... en 0206a

Electric components

Operating voltage connection*)

(pin 1 of supply socket)(not with DLP-VSE-...-ASI)

24 V DC (protected against in-correct polarity)-15%/+20% (DC 20.4 ... 28.8 V)

Load voltage connection*)

(pin 5 of supply socket)(not with DLP-VSE-...-ASI)

24 V DC (protected against in-correct polarity)-15%/+20% (DC 20.4 ... 28.8 V)

Protection against electricshock (protection against directand indirect contact as perEN 60204-1/IEC 204)

By connection to a PELV powerunit (Protected Extra-Low Volt-age)

Indicator light LED bulb type BA9S

*) the length of the operating voltage cable must not exceed 10 m.

Electromagnetic compatibility

Interference emission tested as per EN 55011 tested as per EN 50081-2Immunity to interference tested as per

EN 61000-4-2...6 tested as per EN 50082-2

Limit value class A

passed

Page 107: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

A. Technical specifications and index

A-3Festo P.BE-DLP-VSE-... en 0206a

PROFIBUS-DP (only DLP-VSE-...-DP)

Field bus RS 485, as per EN 50170

Inputs Number Minimum voltage Maximum voltage Log. 1 Log. 0 Current consumption Output current (sum of all

sensor supply outputs)

40 V30 V≥ 10 V≤ 5 Vtyp. 12 mAmax. 1 A (short-circuit resistant,protected against incorrect po-larity)

Outputs Number Current Voltage

4max. 500 mA per outputmax. 30 V

AS-Interface (only DLP-VSE-...-ASI)

Bus connection Voltage range

Residual ripple

26.5 V ... 31.6 V DCprotected against incorrect po-larity≤ 20 mVpp

Load voltage connection Rated value

Residual ripple Current consumption (at 24 V)

24 V DC ...-15%/+20% (20.4 ... 28.8 V DC)4 Vpp140 mA

AS-Interface profile ID code = FH; IO code = 7HS-7.F

Page 108: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

A. Technical specifications and index

A-4 Festo P.BE-DLP-VSE-... en 0206a

Page 109: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

A. Technical specifications and index

A-5Festo P.BE-DLP-VSE-... en 0206a

A.2 Index

A

Abbreviations X. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Air supply 1-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

AS-InterfaceCommissioning 4-28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Commissioning test 4-29. . . . . . . . . . . . . . . . . . . . . . . . . . .Data bits 4-28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Diagnosis 5-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Example of connections 3-29. . . . . . . . . . . . . . . . . . . . . . . .Status displays (LED) of the inputs and outputs 5-3. . . . . .

B

Basic position 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Bus connection 1-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

C

ConnectionsAS-Interface 3-25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Electrical 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Pneumatic 3-3, 3-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PROFIBUS-DP 3-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

D

DLP cylinder 2-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E

Electrical connections 1-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 110: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

A. Technical specifications and index

A-6 Festo P.BE-DLP-VSE-... en 0206a

F

Fitting 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Fitting onto a wall 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

I

Indicator lights, replacing 5-2. . . . . . . . . . . . . . . . . . . . . . . . . .

Intended use VII. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

K

Key switch 1-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Knob-operated switch 1-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

L

Limit switches 4-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Connecting 3-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Pin assignment 3-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

M

Method of operation 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

N

Notes on these instructions VII. . . . . . . . . . . . . . . . . . . . . . . . .

O

Operating and display field 1-4. . . . . . . . . . . . . . . . . . . . . . . .

Operating voltage, connecting 3-7. . . . . . . . . . . . . . . . . . . . . .

Page 111: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

A. Technical specifications and index

A-7Festo P.BE-DLP-VSE-... en 0206a

P

Pin assignmentAS-Interface 3-28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Field bus interface (PROFIBUS) 3-20. . . . . . . . . . . . . . . . . .Operating voltage connection 3-8. . . . . . . . . . . . . . . . . . . . .PLC connection 3-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Potential equalization 3-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Power unit 3-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

PROFIBUS-DPAssigning the inputs and outputs 4-5. . . . . . . . . . . . . . . . .Baud rate 3-18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bus termination 3-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .COM PROFIBUS 4-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Commissioning 4-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Connecting the field bus 3-17. . . . . . . . . . . . . . . . . . . . . . .Connection 3-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Device data base 4-9, 4-15, 4-27. . . . . . . . . . . . . . . . . . . . .Diagnosis 5-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Diagnostic words 5-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Error treatment 5-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Fibre-optical waveguide 3-24. . . . . . . . . . . . . . . . . . . . . . . .Field bus length 3-18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .FREEZE 4-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .General DP master 4-21. . . . . . . . . . . . . . . . . . . . . . . . . . . .GSD 4-9, 4-15, 4-27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Module consistency 4-8. . . . . . . . . . . . . . . . . . . . . . . . . . . .Online diagnosis via diagnostic buffer 5-17. . . . . . . . . . . .Preparing 4-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Screening 3-21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Setting the diagnostic mode 3-16. . . . . . . . . . . . . . . . . . . .Setting the station number 3-14. . . . . . . . . . . . . . . . . . . . .Siemens master 4-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Status displays (LED) of the inputs and outputs 5-3. . . . . .STEP 7 4-15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SYNC 4-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Proximity switch X. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

S

Switch module 3-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 112: Local control unit DLP-VSE- DLP-VSE--DP DLP-VSE--ASI · 2020-03-31 · Festo P.BE-DLP-VSE-... en0206a 1-7 1.2.3 Housingblockwith integrated air supply The housing block isformed ofa

A. Technical specifications and index

A-8 Festo P.BE-DLP-VSE-... en 0206a

T

Target group VII. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Technical specifications A-1. . . . . . . . . . . . . . . . . . . . . . . . . . .

TubingDLP cylinder 2-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Modifying 4-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Tubing variants 3-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

U

User instructions VIII. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

V

Variants 1-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .