Lindab Coverline | Technical Information Sandwich Panels Lindab Sandwich Panels Technical Information Lindab Coverline TM

Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

Embed Size (px)

Citation preview

Page 1: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

Lindab Coverl ine | Technical Information Sandwich Panels

Lindab Sandwich PanelsTechnical Information

Lindab CoverlineTM

Page 2: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation
Page 3: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

3

Lindab Coverl ine | Sandwich Panels

Technical information

Thermal insulation

Lindab's range of sandwich panels includes two types of core, foam (PIR, PUR, IPN) and mineral wool. A panel with a foam core is easy to handle and can cope with large spans, and even a relatively thin core produces high insulation values. The panel has a closed cell structure that produces a very high insulation value and ensures very low water vapour permeability. The closed cell structure also prevents the core from absorbing water. Below is a comparison showing the core thickness required for a variety of panel types to achieve similar U-values.

PUR, 100 mm = 0.22 W/m2 KEPS (expanded polystyrene), 150 mm = 0.24 W/m2 KMineral wool (high-density), 200 mm = 0.21 W/m2 K

A panel with a core of mineral wool is preferable if there are stringent requirements regarding fire performance. Lindab's PUR panels are free from CFCs/HCFCs, which means they do not have any negative impact on the Earth's ozone layer. Reported U-values in this brochure have been revised with regard to ageing of the foam in accordance with EN 13165.

Sandwich panels and fire

Lindab's sandwich panels are fire-tested and rated with reference to their reaction to fire as well as their fire resistance. Testing and rating are performed in accordance with standards EN 13501-1 and EN 13501-2. The majority of Lindab's sandwich panels have also undergone full-scale testing.

Reaction to fireThis method of testing shows how a building product reacts when exposed to high heat in the form of a direct flame, radiant heat or high temperatures. Reaction to fire tests can be performed using a variety of test methods, including the SBI method (Single Burning Item). Parameters such as smoke formation, heat release and any flame spread are measured to determine the product's fire characteristics. The following classifications for combustibility are assigned based on the limit values achieved by the tested product:

A1 or A2 for a non-combustible material

B, C, D, E for a combustible material, where B is lowest combustibility.

A1 is the highest class and is not combined with any additional class. The other classes are always combined with the following additional classes which indicate the product's ability to produce smoke and flaming droplets and particles.

s1 – the structural element may produce a very limited amount of combustion gasess2 – the structural element may produce a limited amount of combustion gasess3 – no requirement for limited production of smoked0 – flaming droplets and particles may not be produced by the structural elementd1 – a limited amount of flaming droplets and particles may be produced by the structural element

d2 – no requirement for limited amount of flaming droplets and particles Swedish standards use the following classifications for internal building surfaces:

Class I = B-s1, d0

Class II = C-s2, d0

Class III = D-s2, d0

Page 4: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

4

Lindab Coverl ine | Sandwich Panels

Resistance to fireThis classification concerns a building product's ability to withstand a flashover. The panels are tested and assigned a specific class based on their function:

R Load-bearing capacity

RE Load-bearing capacity and Integrity (containment)

REI Load-bearing capacity, Integrity and Insulation

E Integrity

EI Integrity and Insulation

EW Integrity and limited radiation Tests on fire cell partitions (wall panels) are performed in a test furnace on a 3x3 m wall, with the temperature inside the furnace normally reaching around 1000 °C. The temperature on the unexposed side is measured at a number of points

and the requirement is for the average temperature not to exceed 140 °C generally or 180 °C at one specific point. The integrity requirement means no flames must penetrate the joints. The time for which the panel satisfies the criteria is measured and the panel is rated for integrity and insulation followed by a time requirement in minutes, e.g. EI60. Tests on load-bearing structures (roof panels) are performed in a test furnace measuring 3x6 m, where the panel is exposed to a load for the duration of the fire. The panels are rated with reference to their load-bearing capacity, integrity and insulation, followed by a time requirement in minutes, e.g. REI60. A number of Lindab's sandwich panels have been subjected to full-scale testing in accordance with FM-Global and LPCB.

Fire engineering classesA building can be constructed to one of three different classes: Br1, Br2 or Br3. Classification takes into account factors such as possibilities for escape and the risk of personal injury in the event of the building collapsing. Assessments are made based on, for instance, the height and volume of the building, the activities conducted in the building, and the number of people calculated to be present inside. Class Br1 means that a fire in the building poses a high risk of personal injury. This normally applies to buildings of three or more storeys, two-storey buildings such as hospitals and hotels, and two-storey buildings with public areas on the top floor, e.g. two-storey shopping centres. Interior ceiling surfaces should comply with B-s1,d0 (class I) and wall surfaces C-s2,d0 (class II). In public areas, e.g. shopping centres, walls must also comply with the highest requirement

B-s1,d0 (class I). Fire cell partitions must be of class EI60 to EI240, depending on the fire load. Br2 buildings are buildings where fire poses a moderate risk of personal injury. This normally means two-storey buildings with a building area of more than 200 m2 or single-storey buildings containing public areas. Interior ceiling surfaces should comply with C-s2,d0 (class II) and wall surfaces D-s2,d0 (class III). In public areas, e.g. shopping centres, walls and ceilings must both comply with the highest requirement B-s1,d0 (class I). Fire cell partitions are normally of class EI30, irrespective of the fire load. Br3 buildings are other buildings. For example, single-storey industrial or storage facilities. Interior ceiling and wall surfaces should comply with D-s2,d0 (class III). Any fire cell partitions are normally of class EI30, irrespective of the fire load.

Fire can not only cause personal injury but also substantial material damage. This can lead to a business having to halt production and losing customers, documentation and stock. This may in turn result in considerable financial losses and can put the survival of the business at serious risk. Factory Mutual (FM Global) and Loss Prevention Certification Board (LPCB) are insurance and certification companies with their own resources for testing. These organisations promote proactive qualitative building design through a number of written documents and certification testing of materials and services.

In order for a product to receive FM Global Approval it must undergo a series of tests looking at a number of physical properties, including fire characteristics. For instance, there is a '50 ft wall test', where a 15 m high panel wall is exposed to fire of approx. 1 megawatt and temperatures of around 1000 °C. For the product to be approved, flames must not spread and there must be no fire propagation at the panel's extremi-ties. Lindab's sandwich panels with IPN core are approved by FM Global and LPCB and should not result in any increased insurance premiums with regard to fire.

FM Global, LPCB Certification – Products certified for protection against damage to property

Technical information

Page 5: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

5

Lindab Coverl ine | Sandwich Panels

Technical information

Core types for Lindab sandwich panels

Mineral wool Normally classed as A2-s1, d0. Panels with a hard core of high-density mineral wool fibre. A mineral wool panel generally achieves a very high fire performance and normally produces less smoke and heat than a panel with a polymer core. However, even a mineral wool panel is not classed as wholly non-combustible (class A1), as the fibre core contains binders and the core is glued to the sheets, usually with a polyurethane adhesive. For this reason, it is classed as A2. For structures serving as fire cell partitions, where a high fire resistance is required (greater than EI30), requirements are currently only satisfied by panels with a mineral wool core. IPN – Isophenic Normally classed as B-s1, d0.IPN is a refined PIR foam. It emits less smoke and contributes relatively little heat to the fire. As with a PIR core, the core chars on the exposed side; this stable, protective charred layer then protects the rest of the core from the fire. Lindab's sandwich panels with IPN core achieve the highest rating for internal surfaces (B-s1,d0) and are classed as EI30 with fire-resistant joints. The panel's good fire performance has also been demonstrated in full-scale tests. Lindab's IPN panel has lasted the full test period in full-scale testing in accordan-ce with ISO 13784-1. Testing was carried out by SP (Techni-cal Research Institute of Sweden) at the request of the Swedish National Board of Housing, Building and Planning.

PIR – Polyisocyanurate Normally classed as B-s2, d0.A PIR core is a type of polyurethane that has undergone significant material modification. In the event of a fire the core chars on the exposed side; this charred layer then protects the rest of the core from the fire. This means that a panel with a PIR core is more resistant to fire than a PUR B2 core. It also emits less heat and smoke.

PUR B2 – Polyurethane B2 Normally classed as B-s3, d0.Panels with a rigid polyurethane core also char in the event of a fire. However, the charred layer is not as strong as that in a PIR or IPN core and it has a relatively low resistance to fire. A PUR B2 core produces no flaming droplets during a fire but does emit quite a lot of smoke. However, it usually emits less than a corresponding EPS panel. Full-scale tests have also shown that there is no hidden flame spread inside the panel. Studies using real fires and full-scale tests have shown that PUR panels are only partly involved in the early stages of the fire and are not affected until the fire has developed fully. The core is self-extinguishing, which means that the core stops

burning when the heat source disappears. Studies have also shown that a PUR panel that is fixed to the framework with a continuous mechanical fastener does not fail until the structural framework fails. Other core types on the market

PUR B3 – Polyurethane B3 Normally classed as C or D-s3, d0. A PUR B3 foam performs less well in a fire than type B2. It emits more smoke and produces more heat during a fire. Unlike a B2 foam, B3 foam is not self-extinguishing.

Fibreglass Normally classed as A2-s1, d0.Fibreglass is, like mineral wool, a mineral fibre, although its fire characteristics are not as good as those of mineral wool. Fibreglass shrinks at high temperatures. A fibreglass panel normally achieves a maximum rating of EI90. Polystyrene (EPS) melts at temperatures as low as 180 °C and produces a lot of flaming droplets during a fire. Even flame/fire-resistant EPS can produce a lot of black smoke and emit a lot of heat during a fire. Once the core melts the fire can also spread unchecked inside the panel. If the panel wall is not securely fixed, it can collapse and accelerate the fire's progress. Despite this, EPS can be classed as d0, because only droplets and particles that fall outside the so-called 'burn zone' of approx. 300x350 mm are counted during testing. A major UK study has shown that some of the greatest industrial damage of modern times in the UK has involved polystyrene panels installed internally in buildings.

Delivery information Max. length roof panel: 13.6 m Longer panels available on request; these require special transport arrangements. Min. standard length roof and wall panel = 2 m.

All wall panels are supplied with an integrated seal along the long joint.

All roof panels are supplied with an integrated seal along the long joint and overlap (however, not the overlap on RT panels).

See standard cross-sections and colours for each panel on the following pages.

Page 6: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

6

Lindab Coverl ine | Sandwich Panels

Technical information

Wall panel cross-sections

Box (Inside/Outside) Micro (Outside) Euro (Outside)

Wave (Outside) B/B (Inside/Outside) Flat* (Outside)

* Smoothness tolerance = +/-2 mm/m2

Page 7: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

7

Lindab Coverl ine | Sandwich Panels

Sin 20 (Outside) Segment (Outside) Plank (Outside)

Technical information

Wall panel cross-sections

Minibox (Inside/Outside) Perforated (Inside)

Page 8: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

8

Lindab Coverl ine | Sandwich Panels

Technical information

Roof panel cross-sections

3 Wave Trapeze (Outside) 4 Wave Trapeze (Outside) Tile effect (Outside)

Minibox (Inside) B/B (Inside)

Page 9: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

9

Lindab Coverl ine | Sandwich Panels

Technical information

TF1150Profiles, External: Box, Micro, Euro, Flat**Minibox, Wave

(Minibox only as IPN panel)

Std colours ext.: Ral 1015, 3000, 5010, 7035, 9002, 9006*, 9007*, 9010, 8004, HBP60***

Steel ext. (mm): 0.6/0.5

Profiles, Internal: Box, Minibox

Std colours int.: Ral 9002

Steel int. (mm): 0.5

*Metallic colours

** Smooth outside only available as IPN panel option. Smoothness tolerance = +/-2 mm/m2

*** Colour HBP60 available as option, see page 25

Wall panels

Thick-ness of insulat-ing core (d)

U-value W/m2K

Airborne sound insulation (dB) PUR B2 IPN

Dead load kg/m2

40 0.56 25 B-s3,d0 B-s1,d0 10.2

50 0.45 25 B-s3,d0 B-s1,d0 10.6

60 0.37 25 B-s3,d0 B-s1,d0 11.0

80 0.28 25 B-s3,d0 B-s1,d0 11.8

100 0.22 25 B-s3,d0B-s1,d0 EI30*

12.6

120 0.19 25 B-s3,d0B-s1,d0 EI30*

13.4

150 0.15 25 B-s3,d0B-s1,d0 EI30

13.7

170 0.13 25 – B-s1,d0 14.4

200 0.11 25 – B-s1,d0 15.5

*Panels with an IPN core are class EI30 with fire-resistant joint. Panels >150 mm thick only with IPN foam, and only profiles Minibox and Flat. Only Minibox and Flat profiles for 150 mm panel with EI30 joint.

TW1000Profiles, External: B/B, Micro, Flat**

Std colours ext.: Ral 1015, 7035, 7016, 9002, 9006*, 9007*, 9010, 7037, 3000, 3009, 5010, 8004

Steel ext. (mm): 0.6

Profiles, Internal: B/B

Std colours int.: Ral 9002

Steel int. (mm): 0.5

*Metallic colours ** Smooth outside is optional. Smoothness tolerance = +/-2 mm/m2

*** min 500 m2

Thick-ness of insulat-ing core (d)

U-value W/m2K

Airborne sound insula-tion (dB) PUR B2 PIR

Dead load kg/m2

80 0.30 25 B-s3,d0 B-s2,d0 12.4

100 0.24 25 B-s3,d0 B-s2,d0 13.2

120 0.20 25 B-s3,d0 B-s2,d0 14.0

150 0.16 25 B-s3,d0 B-s2,d0 15.3

Fire ratingCore type

Fire ratingCore type

Page 10: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

10

Lindab Coverl ine | Sandwich Panels

Technical information

Wall panels

SF1000Profiles, External: Box, Micro, Euro, Wave

Std colours ext.: Ral 1015, 3000, 5010, 7035, 9002, 9006*, 9007*, 9010, 8004, HBP60**

Steel ext. (mm): 0.6

Profiles, Internal: Box, Minibox

Std colours int.: Ral 9002

Steel int. (mm): 0.5

*Metallic colours

** Colour HBP60 available as option, see page 25

Thick-ness of insulat-ing core (d)

U-value W/m2K

Airborne sound insulation (dB)

PUR B2 IPN Dead load kg/m2

50 0.45 25 B-s3,d0 B-s1,d0 10.8

60 0.38 25 B-s3,d0 B-s1,d0 11.2

80 0.29 25 B-s3,d0 B-s1,d0 12.0

100 0.23 25 B-s3,d0 B-s1,d0 12.8

120 0.19 25 B-s3,d0 B-s1,d0 13.6

Sin20 1000Profiles, External: Sin 20

Std colours ext.: Ral 1015, 7035, 7016, 9002, 9006*, 9007*, 9010, 7037, 3000, 3009, 5010, 8004

Steel ext. (mm): 0.6

Profiles, Internal: B/B

Std colours int.: Ral 9002

Steel int. (mm): 0.5

*Metallic colours

Thick-ness of insulat-ing core d/D

U-value W/m2K

Airborne sound insula-tion (dB)

PUR B2 PIR Dead load kg/m2

50/70 0.40 25 B-s3,d0 B-s2,d0 12.2

80/100 0.27 25 B-s3,d0 B-s2,d0 13.4

100/120 0.22 25 B-s3,d0 B-s2,d0 15.2

Concealed fixing

Concealed fixing

Page 11: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

11

Lindab Coverl ine | Sandwich Panels

Technical information

Wall panels

FR1000Profiles, External: Box, Minibox, Micro, Euro, Segment, Flat**

Std colours ext.: Ral 1015, 3000, 5010, 7035, 9002, 9006*, 9007*, 9010, 8004, HBP60***

Steel ext. (mm): 0.6/0.5

Profiles, Internal: Box, Minibox

Std colours int.: Ral 9002

Steel int. (mm): 0.5

*Metallic colours ** Smooth outside is optional, tolerance +/-2 mm/m2

*** Colour HBP60 available as option, see page 25

Thick-ness of insulat-ing core (d)

U-value W/m2K

Airborne sound insulation (dB)

*Mineral wool

Fire rat-ing

Dead load kg/m2

60 0.68 31 A2-s1,d0 EI30 17.3

80 0.52 31 A2-s1,d0 EI30 19.9

100 0.42 32 A2-s1,d0 EI90 22.5

120 0.35 32 A2-s1,d0 EI90 25.1

150 0.28 32 A2-s1,d0 EI180 29.0

200 0.21 33 A2-s1,d0 EI180 34.4

*Density mineral wool ≥100 kg/m3

FR1150Profiles, External: Box, Minibox, Micro, Euro, Flat**

Std colours ext.: Ral 1015, 3000, 5010, 7035, 9002, 9006*, 9007*, 9010, 8004, HBP60***

Steel ext. (mm): 0.6/0.5

Profiles, Internal: Box, Minibox

Std colours int.: Ral 9002

Steel int. (mm): 0.5

*Metallic colours ** Smooth outside is optional, tolerance +/-2 mm/m2

*** Colour HBP60 available as option, see page 25

Thick-ness of insulat-ing core (d)

U-value W/m2K

Airborne sound insulation (dB)

*Mineral wool

Fire rat-ing

Dead load kg/m2

60 0.68 31 A2-s1,d0 EI30 17.3

80 0.52 31 A2-s1,d0 EI30 19.9

100 0.42 32 A2-s1,d0 EI90 22.5

120 0.35 32 A2-s1,d0 EI90 25.1

150 0.28 32 A2-s1,d0 EI180 29.0

200 0.21 33 A2-s1,d0 EI180 31.9

*Density mineral wool ≥100 kg/m3

Page 12: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

12

Lindab Coverl ine | Sandwich Panels

Technical information

Wall panels

FR1200

Profiles, External: Box, Minibox, Micro, Euro, Plank, Flat**

Std colours ext.: Ral 1015, 7035, 9002, 9006*, 9007*, 9010, 3000, 5010, HBP60***

Steel ext. (mm): 0.6/0.5

Profiles, Internal: Box, Minibox

Std colours int.: Ral 9002

Steel int. (mm): 0.5

*Metallic colours

**Smooth outside is optional. Smoothness tolerance = +/-2 mm/m2

*** Colour HBP60 available as option, see page 25

Thick-ness of insulat-ing core (d)

U-value W/m2K

Airborne sound insulation (dB)

*Mineral wool

Fire rat-ing

Dead load kg/m2

60 0.68 31 A2-s1,d0 EI30 17.3

80 0.52 31 A2-s1,d0 EI30 19.9

100 0.42 32 A2-s1,d0 EI90 22.5

120 0.35 32 A2-s1,d0 EI90 25.1

150 0.28 32 A2-s1,d0 EI180 29.0

200 0.21 33 A2-s1,d0 EI180 31.9

*Density mineral wool ≥100 kg/m3

FH1000Profiles, External: Box, Minibox, Micro, Euro

Std colours ext.: Ral 1015, 3000, 5010, 7035, 9002, 9006*, 9007*, 9010, HBP60**

Steel ext. (mm): 0.6

Profiles, Internal: Box, Minibox

Std colours int.: Ral 9002

Steel int. (mm): 0.5

*Metallic colours

** Colour HBP60 available as option, see page 25

Thick-ness of insulat-ing core (d)

U-value W/m2K

Airborne sound insulation (dB)

*Mineral wool

Fire rat-ing

Dead load kg/m2

60 0.70 31 A2-s1,d0 untested 17.6

80 0.53 31 A2-s1,d0 untested 20.2

100 0.42 31 A2-s1,d0 EI60 22.8

120 0.36 31 A2-s1,d0 EI60 25.4

150 0.29 31 A2-s1,d0 EI60 29.3

200 0.22 31 A2-s1,d0 EI60 32.5

Concealed fixing

Page 13: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

13

Lindab Coverl ine | Sandwich Panels

Technical information

Wall panels

HW 1000/HW-S 1000 Acoustic panel

Thickness of insulating core (d)

U-value W/m2K

Airborne sound insula-tion (dB)HW/HW-S

*Mineral wool

Fire ratingonlyHW

Dead loadkg/m2

HW HW-S

60 0.66 30/31 A2-s1,d0 El30** 17.1 15.4

80 0.51 30/32 A2-s1,d0 El30** 19.1 17.4

100 0.42 30/33 A2-s1,d0 El120** 21.1 19.4

120 0.35 30/untested A2-s1,d0 El120** 23.1 21.4

150 0.28 30/- A2-s1,d0 El120/El180** 26.1 -

200 0.22 30/- A2-s1,d0 El120/El180** 32.4 -

*Density mineral wool ≥100 kg/m3

**Resistance classification applies with fire-resistant joint

Profiles, External: HW: B/B, Micro, Flat**,

HW-S: B/B, PERFORATED

Std colours ext.: Ral 1015, 3000, 3009, 5010, 8004, 7016, 7035, 7037, 9002, 9006*, 9007*, 9010

Steel ext. (mm): 0.6

Profiles, Internal: HW: B/B, HW-S: PERFORATED

Std colours int.: Ral 9002

Steel int. (mm): 0.6

*Metallic colours

**Smooth outside is optional. Smoothness tolerance = +/-2 mm/m2

HW-SOUND is an acoustic panel for interior walls. Perforation: ø 3 mm holes, 5 mm hole spacing.

Dead loadkg/m2

Page 14: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

14

Lindab Coverl ine | Sandwich Panels

Technical information

Roof panels

RW1000Profiles, External: 3 Wave Trapeze profile

Std colours ext.: Ral 3000, 3009, 5010, 7016, 7035, 8004, 9002, 9006*, 9007*, 9010, 1015, HBP60**

Steel ext. (mm): 0.5

Profiles, Internal: Minibox

Std colours int.: Ral 9002

Steel int. (mm): 0.4

*Metallic colours

** Colour HBP60 available as option, see page 25

Bare section without filling: 100 mm standard, 250 mm max., min. length for bare section without filling = 2.7 m

Thick-ness of insulat-ing core d/D

U-value W/m2K

Airborne sound insulation (dB)

PUR B2 IPN Dead load kg/m2

25 (60) 0.77 25 B-s3,d0 B-s1,d0 9.3

40 (75) 0.50 25 B-s3,d0 B-s1,d0 9.9

50 (85) 0.41 25 B-s3,d0 B-s1,d0 10.3

60 (95) 0.35 25 B-s3,d0 B-s1,d0 10.7

70 (105) 0.30 25 B-s3,d0 B-s1,d0 11.1

80 (115) 0.26 25 B-s3,d0 B-s1,d0 11.5

100 (135) 0.21 25 B-s3,d0 B-s1,d0 12.3

120 (155) 0.18 25 B-s3,d0 B-s1,d0 13.1

Min. roof pitch 5 degrees without transverse joint

Min. roof pitch 6 degrees at transverse joint

G41000Profiles, External: 3 Wave Trapeze profile

Std colours ext.: Ral 3000, 3009, 5010, 7016, 7035, 7037, 8004, 9002, 9006*, 9007*, 9010, 1015

Steel ext. (mm): 0.6

Profiles, Internal: B/B

Std colours int.: Ral 9002

Steel int. (mm): 0.5

*Metallic colours

Bare section without filling: 100 mm standard, 300 mm max., min. length for bare section without filling = 5.5 m

Thick-ness of insulat-ing core d/D

U-value W/m2K

Airborne sound insulation (dB)

PUR B2 PIR Dead load kg/m2

30 (68) 0.71 25 B-s3,d0 B-s2,d0 11.1

40 (78) 0.55 25 B-s3,d0 B-s2,d0 11.5

50 (88) 0.45 25 B-s3,d0 B-s2,d0 12.0

60 (98) 0.38 25 B-s3,d0 B-s2,d0 12.4

80 (118) 0.29 25 B-s3,d0 B-s2,d0 13.2

100 (138) 0.23 25 B-s3,d0 B-s2,d0 14.1

120 (150) 0.20 25 B-s3,d0 B-s2,d0 14.8

Min. roof pitch 5 degrees without transverse joint

Min. roof pitch 6 degrees at transverse joint

Page 15: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

15

Lindab Coverl ine | Sandwich Panels

Technical information

Roof panels

RT1000Profiles, External: Tile effect

Std colours ext.: Anthracite grey, Terracotta red, 50 my HBP

Steel ext. (mm): 0.5

Profiles, Internal: Minibox

Std colours int.: RAL 9010

Steel int. (mm): 0.4

Bare section without filling: 160 mm standard

Only seal in long joint integrated. Seal in overlap applied on site. Bare section without filling always implemented for installation from left to right.

The panel length is a multiple of the tile spacing of 325 mm. Max. standard length = 13475 mm. Longer lengths require special transport arrangements.

Thickness of insulating core d/D

U-value W/m2K

Airborne sound insula-tion (dB)

PIR** Dead load kg/m2

45 (85) 0.48 25 B-s2,d0 12.6

60 (100) 0.38 25 B-s2,d0 13.2

80 (120) 0.29 25 B-s2,d0 14.1

100 (140) 0.24 25 B-s2,d0 15.0

Min. roof pitch 12 degrees

Number of tiles

Panel length

Number of tiles

Panel length

Number of tiles

Panel length

6 2100 21 6975 36 11850

7 2425 22 7300 37 12175

8 2750 23 7625 38 12500

9 3075 24 7950 39 12825

10 3400 25 8275 40 13150

11 3725 26 8600 41 13475

12 4050 27 8925

13 4375 28 9250

14 4700 29 9575

15 5025 30 9900

16 5350 31 10225

17 5675 32 10550

18 6000 33 10875

19 6325 34 11200

20 6650 35 11525

Panel lengths (mm) with 160 mm bare section without filling

Page 16: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

16

Lindab Coverl ine | Sandwich Panels

Technical information

Roof panels

FF1000Profiles, External: 4 Wave Trapeze profile

Std colours ext.: Ral 1015, 3000, 3009, 5010, 7016, 7035, 9002, 9006*, 9007*, 9010, 8004, HBP60**

Steel ext. (mm): 0.6

Profiles, Internal: Minibox

Std colours int.: Ral 9002

Steel int. (mm): 0.5

*Metallic colours

** Colour HBP60 available as option, see page 25

Bare section without filling, not possible

Thick-ness of insulat-ing core d/D

U-value W/m2K

Airborne sound insulation (dB)

*Mineral wool

Fire rat-ing

Dead load kg/m2

60 (94) 0.67 31 A2-s1,d0 untested 18.6

80 (114) 0.51 31 A2-s1,d0 REI90 21.2

100 (134) 0.42 32 A2-s1,d0 REI90 23.8

120 (154) 0.35 32 A2-s1,d0 REI120 26.4

150 (184) 0.29 32 A2-s1,d0 REI120 30.3

200 (234) 0.20 33 A2-s1,d0 REI120 32.5

*Density mineral wool ≥100 kg/m3

Min. roof pitch 5 degrees without transverse joint

Min. roof pitch 8 degrees at transverse joint

HD1000

Thick-ness of insulat-ing core d/D

U-value W/m2K

Airborne sound insulation (dB)

*Mineral wool

Dead load kg/m2

60 (98) 0.65 29 A2-s1,d0 16.6

80 (118) 0.51 29 A2-s1,d0 18.8

100 (138) 0.41 30 A2-s1,d0 21.0

120 (158) 0.35 30 A2-s1,d0 23.2

150 (188) 0.28 30 A2-s1,d0 26.4

*Density mineral wool ≥100 kg/m3

Min. roof pitch 5 degrees without transverse joint

Min. roof pitch 7 degrees at transverse joint

Profiles, External: 3 Wave Trapeze profile

Covering width: 1000 mm

Std colours ext.: Ral 3000, 3009, 5010, 7016, 7035, 7037 8004, 9002, 9006*, 9007*, 9010, 1015

Steel ext. (mm): 0.6

Profiles, Internal: B/B, Perforated**

Std colours int.: Ral 9002

Steel int. (mm): 0.5

*Metallic colours

Bare section without filling: 100 mm standard, 300 mm max.,

min. length for bare section without filling = 5.5 m

** HD1000 is also available with the inside perforated for use as an internal non-load-bearing acoustic panel.

Page 17: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

17

Lindab Coverl ine | Sandwich Panels

Planning, installation guides and tools

Tools and technical aids for mounting panelsWe have developed mounting clamps to make lifting wall and roof panels easier and installation work more efficient. The clamps are easy to use and fit almost any lifting device.

The clamp shoes are easy to change, meaning the clamps can be used to mount most types of Lindab sandwich panel.

For additional information and advice, please contact Lindab.

Fasteners

Everything you needFasteners are a very important part of any construction project involving sandwich panels. At Lindab you will find a complete range of fasteners for use with different materials in any environ-ment.

Our stainless steel screws for mounting panels on purlins and steel profiles have been type-approved for use up to and including corrosion class C4. Approval denotes an estimated technical life of as much as 50 years.

The range also includes products such as external flashing fastenings and panel washers.

For more information, see our brochure Lindab Fasteners.

Roof safety

Roof safety and sandwich panelsWe also have a type-approved roof safety system for use with sandwich panels. The range includes snow fences, ridge guards, walkways, and roof and vertical ladders. For more information, see our brochure Lindab Roof Safety Systems.

Page 18: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

18

Lindab Coverl ine | Sandwich Panels

From left to right: gable flashing (SGB) as bargeboard with angled gable flashing (SVGB) underneath, and at the point where the wall and roof panels meet sill flashing (SUBG) mounted externally and sill flashing (TFBI) mounted internally.

Corner flashing (SHBY) and a gable flashing (SGB).

Lindab's extensive range of profiles and flashings means that the final result will be both functional and attractive. The easy-to-mount profiles are manufactured from durable painted sheet metal. In our range you will find standard and custom-made flashings suitable for any project.

Technical information

Sandwich panels and flashings

Page 19: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

19

Lindab Coverl ine | Sandwich Panels

Wall panels mounted on steel framework with compriband sealing tape. A fill-in insulation

strip between the panels and sealing tape on the outside.

A pilaster (SPIL) is mounted on the panels with compriband sealing tape.

Below: an exterior base cover flashing (SUSB). A 10 mm thick seal in the sill runner (S20) with a 10 mm sill seal underneath. On the inside an interior base cover flashing (SISB).

Behind the KFK fascia bracket are a front flashing (SFB) and a z-shaped eaves profile (STFP), and a sill flashing (SUBL) up against the wall panel on the outside.

A ridge capping (NP170) is mounted on a seal profile. A fill-in insulation strip between the two panels and an interior ridge plate (NPI200) under the panels.

Panel joint, bare section without filling 300 mm with compriband sealing tape.

Page 20: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

20

Lindab Coverl ine | Sandwich Panels

Technical information

Flashings

NPI200 Interior ridge plate

STFP Eaves profile

SFB Front flashing

NP170 Ridge capping

(1.2 mm galv)

Page 21: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

21

Lindab Coverl ine | Sandwich Panels

Technical information

Flashings

SGB Gable flashing

SVGB Angled gable flashing

SHBY Corner flashing

SUBL Sill flashing long side

Page 22: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

22

Lindab Coverl ine | Sandwich Panels

SUSB Base cover flashing exterior

SISB Base cover flashing interior

TFBI Sill flashing interior

SPIL Pilaster

Technical information

Flashings

Page 23: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

23

Lindab Coverl ine | Sandwich Panels

SFOB Case flashing

SOB Drip flashing

SUBG Sill flashing gable

Technical information

Flashings

Page 24: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

24

Lindab Coverl ine | Sandwich Panels

S20 Sill runner

SUB Sill ledge

Technical information

Flashings

Dim. Amm mm

60 40

80 60

100 80

120 100

150 130

170 150

200 180

(1.2 mm galv)

US U-profile, slotted

(1.5 mm galv)

Page 25: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

25

Lindab Coverl ine | Sandwich Panels

Colour RAL Nearest NCS

5010 S 5040-Y90R

9006* S 2502-B

7037 S 5500-N

9007* S 6000-N

7016 S 8005-B20G

* Metallic colours

Colour chart

Colour system for exte-rior coating

25 µm PolyesterZinc, 275 g/m2

Environmental class C3 (standard)

Colour system for interior coating

15 µm PolyesterEnvironmental class C2

Other information

The colours of Lindab's sandwich panels follow the RAL standard.

The NCS which is stated after the RAL number is the nearest NCS.

Colours may differ from those shown due to printing limitations.Paints and properties

ProductNom. thick-ness µm

Gloss units

Minimum bend radius

Example of environ-ment

Corrosion class

Environ-mental cor-rosiveness

Ral num-ber

UV cat-egory

HBP 60 301T (Dark) 2T (Light)

Industrial areas with high air humidity and an aggressive atmosphere. Coastal areas.

RC 5 Very high

9002, 9010, 9006, 9007, 7016, 5010, 3009

Ruv4

Polyester 25 my

25 302T (Dark) 4T (Light)

Atmospheres with some salt or moderate pollutant volumes.

RC3 Moderate Std colours Ruv2

Optional coating Special Pe colours – when a project requires RAL or NCS Pe colours available on the market but not included in the standard colour range.

PVDF 25 µm – a coating offering extraordinary UV resistance and good corrosion resistance.

HBP60 – a coating with UV resistance and corrosion resistance similar to PVF, but which is cheaper than PVF colours. This coating is also very flexible and highly resistant to mechanical damage. Standard colours HBP60 Granite: RAL 9002, 9006, 9007, 7016, 3009, 7035.

Foodsafe – a 150 µm polymer coating that is free from toxins and resistant to mould. It is durable, easy to clean, chemically inert and approved for use in the same premises as unpacka-ged foodstuffs. Standard colour is white RAL 9010.

25 µm Pe interior – 25 my Pe on the interior side of the panel, for indoor environments corresponding to environmen-tal class C3.

INOX – outer or inner stainless steel sheet of EN 1.4301 grade.

Contact your Lindab representative to find out more about which options are available for each panel.

Colour RAL Nearest NCS

9010 S 0603-G40Y

9002 S 1502-Y

7035 S 2005-G30Y

1015 S 1510-Y20R

3000 S 2070-Y90R

8004 S 4550-Y60R

3009 S 5040-Y90R

Page 26: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

26

Lindab Coverl ine | Sandwich Panels

Page 27: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

27

Lindab Coverl ine | Sandwich Panels

Page 28: Lindab Sandwich Panels Technical Information Components Global/sandwich... · Lindab Sandwich Panels Technical Information ... A panel with a foam ... and there must be no fire propagation

Lindab Coverl ine | Technical Information Sandwich PanelsA

rt. n

o. 1

5328

2 0

8-06

-201

0

Lindab is an international group that develops,

manufactures, markets and distributes products

and system solutions of thin sheet metal and steel

that simplify construction and improve the indoor

climate.

Our range includes everything from complete

construction systems to individual components

for homes, commercial properties and industrial

premises.

The Lindab Group has approximately 4,500 em-

ployees in 31 countries. Its head office is located in

Grevie near Båstad in north-west Skåne.