Linac Coherent Light Source (LCLS)

at SLAC

Hamid Shoaee

forSLAC Controls Department

Page 2: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

Outline

• LCLS-I– Facility Overview– Commissioning Success– Controls System Architecture

• Towards the Future– Overwhelming demand for LCLS-II– LCLS-II Proposal– R&D– Further into the future

ICALEPCS 2011Page 2

Page 3: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

X-ray FEL uses last 1-km of existing 3-km linacX-ray FEL uses last 1-km of existing 3-km linacLinac Coherent Light Source at SLACLinac Coherent Light Source at SLAC

Page 4: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

X-ray FEL uses last 1-km of existing 3-km linacX-ray FEL uses last 1-km of existing 3-km linac

Injector (35º)at 2-km point

Existing 1/3 Linac (1 km)(with modifications)

New e− Transfer Line (340 m)

Undulator (130 m)

Electron Beam Dump

Linac Coherent Light Source at SLACLinac Coherent Light Source at SLAC

Page 5: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

ICALEPCS 2011Page 5

World’s First Hard X-ray FEL

• A billion times brighter than previous sources

• < 2 Å & 50 femtoseconds– Study of ultra-fast and

ultra-small phenomena– Can capture images of

atoms and molecules in motion

Page 6: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

ICALEPCS 2011Page 6

Photosystems I complex(R. Fromme, ASU)

Single Mimivirus particle(T. Ekeberg, Uppsala U.)

Fully-ionized Ne 10+

(Bozek , Bostedt)

Page 7: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

γεx,y ≈ 0.4 μm (slice)Ipk ≈ 3.0 kAσE/E ≈ 0.01% (slice)

April 2009(25 of 33 undulators)

Lg ≈ 3.3 m

Saturation at 60 m (design was 90 m)

LCLS Achieves FEL Saturation at 1.5A

Slide 7

P. Emma

Page 8: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

Beam saturates in 60m rather than 90m(25 of 33 undulators)

Gun brightness exceeds LCLS GoalsFEL is fully tunable: rep rate, pulse length, photon energy, peak power

Page 9: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

LCLS Machine PerformanceBaseline performance Current performance

Photon energy range 830 to 8300 eV 480 to 10,000 eV

FEL pulse length 230 fs 5 - 500 fs

FEL pulse energy up to 2 mJ up to 4 mJ

• Beam availability to users > 95%

•Controls uptime > 98% (goal = 98.8%)

•120 fs pump probe synchronization has been achieved

Page 10: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

Commissioning Successes & Challenges

• Challenging combination of Legacy & EPICS• EPICS-based Injector & drive laser 2007• Legacy & EPICS Linac 2008• BPMs & Magnets in EPICS 2009-2010• Linac Upgrade to full EPICS 2010-2011

• Transition critical functionality from VMS to Linux • Data bridge from CAMAC to VME IOCs

– LCLS fully EPICS-based Early 2012

ICALEPCS 2011Page 10

Page 11: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

AIDA – Accelerator Integrated Data Access

• A system for uniform access to controls infrastructure data• Integrated data from Legacy & EPICS systems• Complex Data in addition to individual controls points• Data from remote machines made available to MATLAB &

Java apps, in control room, or off site• Data sources include machine, model, history,

configuration, RDB, etc.• Allows rapid physics applications development regardless

of underlying legacy or EPICS controls• Applications mostly unaffected by controls system

upgrades

ICALEPCS 2011Page 11

Page 12: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

AIDA Cloud

EPICS ControlsEPICS

Archiver

DIMAD Model

BPM Orbit dataArbitrary Oracle

DB queries

Client

Scientist's own laptop / desktop

SLC Controls

Synchronized Magnet and RF Control

XAL ModelINTEGRATES DIFFERENT CONTROL SYSTEMS

ABSTRACTS CONTROL VIEW TO

PHYSICS VIEW

SINGLE, TRIVIAL USER INTERFACE TO ALL DATA

*ALL* KINDS OF DATA,

NOT JUST CONTROLS

Control Room Physics Applications / Matlab

AIDA - Accelerator Integrated Data Access http://www.slac.stanford.edu/grp/cd/soft/aida/

Authors: Greg White, Bob Hall, Bob Sass, George MacIntyre, Ron MacKenzie

AIDA is a Service Oriented Architecture for LCLS and

other SLAC machines

Page 13: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

LCLS 4-Layer Network Architecture

ICALEPCS 2011Page 13

Page 14: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include
Page 15: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

485 IOCs171 VME220 Embedded94 Soft

1.3 Million PVs120,000 Archived 17,523 in alarm system

Page 16: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

LCLS Timing Event System

ICALEPCS 2011Page 16

DEV

~ Linac main drive line

Sync/Div

VMTG

119 MHz360 Hz

IRQ & Timeslot

LCLSevents

EVR

CPU

TTL-NIMconvert.

DigitizerLLRFBPMsToroidsCamerasWire ScannerKlystrons

TTL

FAN

CPU

EPICS Network

Fiber distribution

*

*

EVG

LCLS MasterOscillator

476MHz

Linac Master Osc

FIDO PDURaw 360 Hz LCLS Timeslot Trigger

TRD Tx

TRD Rx

TRD Rx

119Mhz + FID

Sq Wave on Coax 119Mhz + FIDSq Wave on Coax

Fiber Cable

TO:- Cav BPM- MPS BLM- MPS PIC- BCS

60Hz Timeslot 1

From LCLS-IIMPS

Star Network: EVG (many) EVRsBased on MicroResearch Event SystemProgrammable delay/width/polarity8.4ns delay step10ps(rms) jitterEPICS timestamp sent over timing link

Dusatko, Krejcik

Page 17: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

ICALEPCS 2011Page 17

LCLS 120 Hz Feedback System

Dedicated network uplinks and connections to 2nd NIC on ~150 IOCs

LI21 LI24 BSY LTU

Core switch & router

IN20

Li22 LI23 Li25 LI26 LI27 Li28 LI29 LI30 UND DMP

bp01 bp02 rf01

bp01 bp02

3750 switch

bp01

fb01

BPMS VME IOC

Controller VME IOC

swh-in20-nw02

bl01

Controller IOCs

swh-in20-nw01

fb02fb01

mg01

mg01 MGNT VME IOC

rf01 RF VME IOC bl01 BLEN VME IOC

rf01 bl01bp02

DMPbp01

UNDbp03

UNDbp04

UNDbpo1

UNDbp02

LTU1bp04

LTU1bp03

LTU1bp02

LTU1bp01

LTU0bp01

BSYbp01

BSYbp02

Channel Access

D. Fairley

Page 18: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

ICALEPCS 2011Page 18

LCLS 120 Hz Feedback System

Dedicated network uplinks and connections to 2nd NIC on ~150 IOCs

LI21 LI24 BSY LTU

Core switch & router

IN20

Li22 LI23 Li25 LI26 LI27 Li28 LI29 LI30 UND DMP

bp01 bp02 rf01

bp01 bp02

3750 switch

bp01

fb01

BPMS VME IOC

Controller VME IOC

swh-in20-nw02

bl01

Controller IOCs

swh-in20-nw01

fb02fb01

mg01

mg01 MGNT VME IOC

rf01 RF VME IOC bl01 BLEN VME IOC

rf01 bl01bp02

DMPbp01

UNDbp03

UNDbp04

UNDbpo1

UNDbp02

LTU1bp04

LTU1bp03

LTU1bp02

LTU1bp01

LTU0bp01

BSYbp01

BSYbp02

Channel Access

Add dedicated Feedback Network D. Fairley

Page 19: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

ICALEPCS 2011Page 19

Runtime Feedback Display

Page 20: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

Timing data

LCLS Machine Protection Architecture

MPS Link Processor

GbE Switches

MPS Link Node

Mitigation Device (Gun Permit)

MPS Link Node MPS Link Node MPS Link Node MPS Link NodeMPS Link Node

Mitigation Device (Mech. Shutter)

Mitigation Device (Lsr Htr Shutter) Mitigation

Device (BYKIK)

Device Device Device Device Device Device Device Device DeviceDevice

LCLS CA

Network

LCLS CA

Network

MPS History Server

Interim MPS

Soft InputSoft InputSoft Input

Analog & digital I/O

Dedicated GbEover Cat5

GbE over Cat 5

Dedicated GbEover Fiber

100BASE-TX

100BASE-TX

EVR

MPS Configuration

Editor

MPSConfiguration RDB and files

Compile time & runtime files

MPS Logic Editor

MPS Logic RDB and files

APEX*, on linux server APEX*, on linux server

Java, on linux server

MPS History

GUI

Java, on linux server

Compile time files

GTM

MPS History RDB

Page 21: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

Timing data

LCLS Machine Protection Architecture

MPS Link Processor

GbE Switches

MPS Link Node

Mitigation Device (Gun Permit)

MPS Link Node MPS Link Node MPS Link Node MPS Link NodeMPS Link Node

Mitigation Device (Mech. Shutter)

Mitigation Device (Lsr Htr Shutter) Mitigation

Device (BYKIK)

Device Device Device Device Device Device Device Device DeviceDevice

LCLS CA

Network

LCLS CA

Network

MPS History Server

Interim MPS

Soft InputSoft InputSoft Input

Analog & digital I/O

Dedicated GbEover Cat5

GbE over Cat 5

Dedicated GbEover Fiber

100BASE-TX

100BASE-TX

EVR

MPS Configuration

Editor

MPSConfiguration RDB and files

Compile time & runtime files

MPS Logic Editor

MPS Logic RDB and files

APEX*, on linux server APEX*, on linux server

Java, on linux server

MPS History

GUI

Java, on linux server

Compile time files

GTM

MPS History RDB

Page 22: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

Personnel Protection System (PPS)

• Two redundant safety PLC (PILZ) independently programmed and validated

• Supervisor: Allen-Bradley

• EPICS interface IEC61508, ISO9001

Page 23: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

Centralized RDB for Configuration Control

• LCLS Infrastructure includes a multi-function database of LCLS devices and related data– It is derived from the machine design model– includes beamline components, device

information, polynomials, cabling data– laser device parameters– Field installed modules inventory– Links to QA documents and drawings– web interface for IRMIS and AIDA

Page 24: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

RDB Applications

• Feedback Configuration parameters• Save/Restore application• Java and MATLAB physics applications

parameters• MPS faults history• E-Log App• CATER for Software Requests

ICALEPCS 2011Page 24

Page 25: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

High Level Application Software

Two-tiered approach• Java-based utility applications

– XAL machine modeling and tuning• MATLAB / EPICS/AIDA infrastructure

– Enabling physicists and operations staff to rapidly prototype required applications

– Soft IOC framework for physicists• User-configurable PV records for physics data

Page 26: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

Controls Model Based Apps– Model Manager

P. Chu

Page 27: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

MATLAB High Level Physics Apps …

Page 28: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

Slide 28

LCLS-I Automation SoftwareRF Phase ScansRF Phase Scans

Automatically scan all RF phasesAutomatically scan all RF phases

Align laser heater beam to e-beamAlign laser heater beam to e-beam

Set dispersion free 100 m long undulator beam lineSet dispersion free 100 m long undulator beam line

Laser Heater AlignLaser Heater Align

Undulator Beam-based AlignmentUndulator Beam-based Alignment

H. Loos

Page 29: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

LCLS-I Automation Software

Slide 29

TCAV Bunch LengthTCAV Bunch Length

Calibrate TCAV/measure bunch lengthCalibrate TCAV/measure bunch length

Multi screen/quad scan/slice emittanceMulti screen/quad scan/slice emittance

EmittanceEmittance

Correlation PlotsCorrelation Plots

Combine measurements for parameter scansInjector tuning/bunch length monitor calibrationCombine measurements for parameter scansInjector tuning/bunch length monitor calibration

0

20

40E = 13.634 GeVQ = 0.249± 0.01 nCγεx = 1.14± 0.01 μmξx = 1.04± 0.00B

eam

Siz

e (μ

m)

-1

0

1

Nor

m. A

ngle

-40 -20 0 20 40 60 800

20

40γεy = 1.05± 0.01 μmξy = 1.00± 0.00

Bea

m S

ize

(μm

)

Position (m)-1 0 1

-1

0

1

Nor

m. A

ngle

Norm. Position

0

20

40E = 13.634 GeVQ = 0.249± 0.01 nCγεx = 1.14± 0.01 μmξx = 1.04± 0.00B

eam

Siz

e (μ

m)

-1

0

1

Nor

m. A

ngle

-40 -20 0 20 40 60 800

20

40γεy = 1.05± 0.01 μmξy = 1.00± 0.00

Bea

m S

ize

(μm

)

Position (m)-1 0 1

-1

0

1

Nor

m. A

ngle

Norm. Position

H. Loos

Page 30: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

• Only 28% of users have received beam time• Key Desired Capabilities Driving LCLS-II

– More capacity & capability – One to four stations operating simultaneously– two injectors offering independent pulses– Extension to full intensity hard x-rays – study of thick 3D materials with increased x-ray

penetration and spatial resolution– Extended soft x-ray spectral range

J. Stohr

Page 31: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

LCLS-II Machine Layout

• Use same injector design at sector-10 (1 km upstream)• Two new bunch compressors and 4-14 GeV linac (~1 km)• 1200-m long bypass goes around LCLS-I• Two new undulators (HXR & SXR) in new tunnel• Baseline is 60 Hz in each undulator (multi-bunch later)

Slide 31

LCLS-IXX

L1L1 L2L2 L3L3BC1BC1 BC2BC2

RFgun-1

RFgun-1

L0L0

3-15 GeV3-15 GeV

existingexisting und-hall-1und-hall-1

LCLS-I

Page 32: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

LCLS-II Machine Layout

• Use same injector design at sector-10 (1 km upstream)• Two new bunch compressors and 4-14 GeV linac (~1 km)• 1200-m long bypass goes around LCLS-I• Two new undulators (HXR & SXR) in new tunnel• Baseline is 60 Hz in each undulator (multi-bunch later)

Slide 32

LCLS-IXX

L1L1 L2L2 L3L3BC1BC1 BC2BC2

RFgun-1

RFgun-1

L0L0

3-15 GeV3-15 GeV

existingexisting und-hall-1und-hall-1

LCLS-I

L3′

RFgun-2

L1′ L2′BC1′ BC2′

L0′

one more km of linac

HXR4-14 GeV bypass line

SXR

und-hall-2und-hall-2

X

LCLS-II

Page 33: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include
Page 34: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

LCLS-II is part of a long term strategy

• 2 injectors, 2 linac sections (14 GeV each)• 1 hard x-ray undulator 5-10keV in tunnel 1• 1 hard x-ray SASE undulator in tunnel 2; (variable gap)• 1 soft x-ray SASE undulator in tunnel 2; (variable gap)• 6 experimental stations, up to 4 operating simultaneously• Room for 4 more experimental stations

LCLS-II components in color, LCLS 2025 in grey

hard x-raysoft x-ray

J. Stohr

Page 35: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

Advancing Controls to Meet Future Needs

• Migrating from CAMAC to new platforms– m-TCA platform research currently underway– Low Level RF field test of new system in 6 months– BPM m-TCA field tests April 2012

• Large-scale data archiving management– Scale to 1-2 millions PV’s– Fast data retrieval

• Days worth of 1Hz data for a PV in less than 500ms

• More automation of routine control room tasks

ICALEPCS 2011Page 35

Page 36: Linac Coherent Light Source (LCLS) at SLAC · Linac Coherent Light Source (LCLS) at SLAC Hamid Shoaee for SLAC Controls Department. Outline •LCLS-I ... • Data sources include

Conclusion

• LCLS has been an unqualified success exceeding performance goals

• Major challenge has been managing hybrid legacy-EPICS controls system

• LCLS-II and beyond will provide rich opportunities for advancing the state of controls and instrumentation

• Collaboration with Physics and Operations groups has been essential for success.