7
G-171-0-C8641-A HQ-1009 Printed in Japan (MDOC) New publication, effective Sep. 2010 Specifications are subject to change without notice. Power System Stabilizer (PSS) Improper use of the products can cause severe injury or death, and may result in damage to the products and other property. Please read the instruction manual before installing or using the products. Mitsubishi Electric Power System Stabilizer (PSS) Generator power PSS OFF PSS ON PSS OFF PSS ON Time (sec) Time (sec) 0.85 0.9 0.95 Generator power 0.85 0.9 0.95 0 1 2 0 1 2 Step response Grid one line open HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

Limit parameter setting PSS2A-NOTY.pdf

Embed Size (px)

Citation preview

  • G-171-0-C8641-A HQ-1009 Printed in Japan (MDOC)New publication, effective Sep. 2010

    Specifications are subject to change without notice.

    Power System Stabilizer (PSS)

    Improper use of the products can cause severe injury or death,and may result in damage to the products and other property.Please read the instruction manual before installing or using the products.

    Mitsubishi Electric Power System Stabilizer (PSS)

    Gen

    erat

    or p

    ower PSS OFF PSS ON

    PSS OFF PSS ON

    Time (sec)

    Time (sec)

    0.85

    0.9

    0.95

    Gen

    erat

    or p

    ower

    0.85

    0.9

    0.95

    0 1 2

    0 1 2

    Step response

    Grid one line open

    HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

  • AVR

    AVR+

    PSS

    K1

    K1+K1A

    K1A+DA

    K1+D

    K1+D

    K1+K1A+K1P

    Tm

    Tm

    Tm

    01Ms

    1Ms

    1Ms

    S

    0S

    0S

    D 0

    0

    0

    D+DA

    D+DA+DP

    G

    Power

    Mitsubishi Power System Stabilizer (PSS)The power system stabilizer (PSS) is a device that measures improvements in system stability when added to a generators automatic voltage regulator (AVR). Therefore, compared to system reconstruction or enhancement, it offers overwhelmingly superior cost performance. With an abundant system line-up including analogue, digital and P//f input type models, Mitsubishi Electric is ready to respond to the diversified needs of its customers.

    Summary of Power System Stability

    Theory of PSS

    Summary

    Explanation of torque vector

    Though generator output power is decided by a turbines mechanical torque, it can be changed by transiently changing the excitation value (Fig.1). A PSS detects the change in generator output power, controls the excitation value, and reduces the rapid power fluctuation (Fig.2).

    Generator output power

    Excitation value

    Generator output power

    Excitation value

    Fault (3-phase fault, several cycles open)

    Unstable (less dynamic stability)

    StableStep out (less transient stability)

    Fault

    occu

    rrenc

    eFa

    ult cl

    eare

    d

    Transient area

    Dynamic area

    Constant excitation

    Block diagram Torque characteristics

    K1 : Synchronizing torqueD : Damping torqueM : Inertia

    K1A : Synchronizing torque by AVRDA : Damping torque by AVR

    K1P : Synchronizing torque by PSSDP : Damping torque by PSS

    (Damping torque)

    (Synchronizing torque)

    Resultant torque

    Resultant torque

    (Unstable at DDA0)

    (Stable at DDADP0)

    1 2

    Time

    Power

    By changing the excitation value, generator output power can be changed transiently

    (Fig.1) (Fig.2)

    A PSS detects the change ingenerator output power, controls the excitation value, and reduces the rapid power fluctuation

  • Vref

    Vref

    Vref

    PT

    PT

    PT

    CT

    EXC

    EXC

    EXC

    AVR

    AVR

    AVR

    PSS

    f PSS

    P PSS

    PSS

    f PSS

    P PSS

    3 4

    Mitsubishi Power System Stabilizer (PSS)

    As previously mentioned, the PSS detects fluctuations in generator output power and controls the excitation. The type of PSS is distinguished by its detection signal. The simplest and most typical type is the P input type unit; however, and f input typeunits have been introduced to improve the stability of the intra-system oscillation mode (i.e., long-term or interface mode) in view of thelarge increase in power systems and power re-routing in recent years. Each of the features is outlined below.

    Multi-input PSS

    P signal

    orf signal

    Gain and phasecompensation

    Gain and phasecompensation

    Limiter

    AVR

    Local Mode Power Oscillation

    Inter-area(Long-cycle) Mode Power Oscillation

    Complex Power Oscillation

    Individual generator oscillates against the systemFrequency is approx. 1Hz

    The whole system oscillates as a resultof long-distance, large-capacity power transmissionFrequency is 0.2 to 0.5Hz

    Complex power oscillation mode, such as local mode inter-area mode

    Single-frequency PSS, such as P, or fP type PSS is more effective

    Single-frequency PSS, such as P, or f or f type PSS is more effective

    Multi-input PSS is more effectiveP type or Pf type

    Types of PSS

  • Kpss Trs1+Trs1+Tlead1s1+Tlag1s

    1+Tlead2s1+Tlag2s

    1+Tlead3s1+Tlag3s 1+Tlags

    1

    Kpss Trs1+Trs1+Tlead1s1+Tlag1s

    1+Tlead2s1+Tlag2s

    1+Tlead3s1+Tlag3s

    P1P2

    T

    Hardware Configuration

    DevicePower/VoltageconverterPSS main card(SPMT)

    PSS auxiliary card(SPST)

    PSS protection card(SPPT)

    FunctionDetects generator power and voltage from PT, CT signalAmplifier (Gain) [Kpss]Reset filter [Tr]Lag [Tlag]Limiter

    Lead/Lag1 [Tlead1,Tlag1]Lead/Lag2 [Tlead2,Tlag2]Deadband, absolute

    Low-power detection

    Generator over-and under-voltagedetectionFault detection

    PSS ON/OFF switching circuit

    SpecificationPower converter: 0-1kW/0-30mV, response time: less than 10msec,voltage converter: 0-150VAC/0-5VDCKpss=0.13.0pu/pu (typical range)Tr=120secTlag=0.011secSetting range 0.1pu based on generator voltageStandard setting 0.05puTlead 1=0.082.2sec, Tlag 1=0.072.2secTlead 2=0.0080.22sec, Tlag 2=0.0070.22secSetting range 0-1pu based on generator outputStandard setting 0.3puSetting range 0-1pu based on generator outputStandard setting 0.3puSetting range 0-1.3pu based on generator voltageStandard setting over voltage: 1.1pu, under-voltage: 0.9puDetects PSS output that is over a set value/timeSetting range pick up: 0.1pu based on generator voltagetimer: 0-30secStandard setting0.045pu, 10secAutomatic lock (OFF) and automatic reset (ON) by low power detection,Generator over- and under-voltage detectionAutomatic lock (OFF) and manual reset (ON) by fault detection

    Transfer function

    Gain Reset filterDeadband Lead/Lag(1) Lead/Lag(2) Lead/Lag(3) Lag Limiter

    Remarks) If Lead/Lag (3) is necessary, two PSS auxiliary cards (SPST) are used.

    Transfer function

    Gain Reset filterDeadband Lead/Lag(1) Lead/Lag(2) Lead/Lag(3) Limiter

    Inductor Electromagnetic pick-up

    Speed detection card

    Speed detection Torsional oscillation filtersto PSS functions

    4 steps

    Design of PSS Parameters

    Site Commissioning test of PSS

    Calculation of damping torque :

    M : inertia

    Ms2+Ns+WKs2+Ds+W

    5 6

    Mitsubishi Power System Stabilizer (PSS)

    AnalogueAnalogueAnalogue

    DigitalDigital

    Speed Detectionin Input Type

    2MT

    P2P1

    nD =

    The dimensions of the analogue PSS are 250 x 680 x 480mm (LxWxD). Each unit is equipped with thefollowing devices:

    The functions of the digital PSS are realized through the software. Generally, computations are performedin the same CPU as the digital AVR. The basic functions are the same as for analogue. Minor differencesare as follows:(1) Fault detection: for analogue, excessive PSS output is detected. However, in the case of the digital unit,

    a fault occurring in individual parts (e.g., reset filter) is not realistic. Therefore, rather than basing faultdetection on computation results, a self-diagnostics function is built into the hardware and software todetect faults.

    (2) Lag: analogue units have a lag circuit at the final stage that suppresses the noise signal. Generally,this is not incorporated in digital units since noise suppression is carried out at the point of input-signaldetection.

    The generator speed is detected by the input type PSS. It is necessary for the PSS speed detectorto be able to detect very small fluctuations with high accuracy. Mitsubishi Electric developed a highlyaccurate, high-performance speed detector (16-bit resolution, 0.05% accuracy) and a filter to eliminatetorsional oscillation in the spinning component.

    An appropriate parameter design is very important in order for a PSS to operate effectively. In general, theseparameters are set with the single machine infinite bus model; however, on request, analysis using amulti-system model is also available.

    During site examination, to confirm the effectiveness of the PSS, power fluctuations are generated when thePSS is in use and when it is not in use, and damping measurements are compared. As a common method forgenerating power fluctuations, a generator voltage transient response test, is applied. In order to quantify theeffectiveness of the PSS, the damping torque is calculated from the test results. Generally, in the case ofapplying a local mode, the PSS is judged to be sufficiently effective if the damping torque is tenfold higher as aresult of using the PSS.

    Filter :

  • Integral of Accelerating Power Type PSS (Power System Stabilizer)

    time (sec)

    Pow

    er

    AVR without PSS

    Step respnse of voltage reference

    AVR with PSS

    time (sec)

    Pow

    er

    AVR without PSS

    AVR with PSS

    Power system fault(1 line open after 3 phases grounding)

  • A POWER SYSTEM STABILIZER (PSS), which is installed in the Automatic Voltage Regulator of a Generator, can improve power system stability. The PSS has excellent cost performance compared to other power system modifications or additions. MITSUBISHI "Integral of Accelerating Power Type PSS" conforms to Type PSS2A in "IEEE Std. 421.5-1992".

    Integral of Accelerating Power Type PSS

    The relation of change among mechanical power, electrical power, accelerating power and rotor speed can be illustrated as Fig.1 from the swing equation where the integral of accelerating power is equal to rotor speed.

    Thus, Integral of mechanical power is derived as the following equation from measured electrical power and rotor speed (or frequency).The resultant block diagram of sensing input signal can be illustrated as Fig.2. Thus, the input signal of "Integral of Accelerating Power Type PSS" is equivalent to rotor speed.

    Where, F(s) is transfer function of the filter for attenuating the torsional oscillation.

    Mechanical Power

    Electrical Power

    Accelerating PowerRotor Speed

    M=2H:Inertia constant Fig.1

    Fig.2Ms

    M

    1

    1

    M1

    F(s) Equivalent rotor speed signal

    Pmdt

    Pedt

    Ms1

    *Kinds of Speed signal

    Configuration of PSS Function

    Mitsubishi Integral of Accelerating Power Type PSS (Power System Stabilizer)

    (1) Frequency of terminal voltage.....only terminal voltage(2) Frequency of internal voltage calculated from terminal voltage and current (Vi=Vg+xd lg).....(option)(3) Actual rotor speed.....required speed detector, toothed wheel mounted on generator shaft and pickup (option)

    Parameters

    Parameter DescriptionWash-out Time constant-1Wash-out Time constant-2Wash-out Time constant-3Wash-out Time constant-4Lead Time constant-1Lag Time constant-1Lead Time constant-2Lag Time constant-2Lag Time constantIntegral Time constantRamp-tracking time constantFilter time constantLead Time constant-3Lag Time constant-3Lag Time constant-4PSS GainGainGainInteger filter constantInteger filter constantPSS output limiter "max"PSS output limiter "min"

    UnitsSec.Sec.Sec.Sec.Sec.Sec.Sec.Sec.Sec.Sec.Sec.Sec.Sec.Sec.Sec.pu/pupu/pupu/pu

    IntegerInteger

    pupu

    Typical range1 to 10.1 to 10.1 to 10.1 to 10.

    0. & 0.02 to 2.0. & 0.02 to 2.0. & 0.02 to 2.0. & 0.02 to 2.0. & 0.02 to 2.

    0.5 to 10.0. & 0.02 to 2.0. & 0.02 to 2.0. & 0.02 to 2.0. & 0.02 to 2.0. & 0.02 to 2.

    0.2 to 20.0.1 to 5.0.5 to 2.1 to 51 to 5

    0. to 0.20. to -0.1

    Remarks

    Integral of Pe

    Normally = T7/2H(Inertia)Normally = 1

    Tw1Tw2Tw3Tw4T1T2T3T4T6T7T8T9T10T11T12Ks1Ks2Ks3MN

    VSTMAXVSTMIN

    Transfer Function of PSS

    To AVR

    Pe

    Vg

    1 : Added to PSS2A model2 : If generator voltage is continuosly kept higher than 105% or lower than 95% of rated voltage, generator voltage is automatically reduced within 95 to 105% by changing limit value after time delay.

    sTw11+sTw1

    sTw21+sTw2

    11+sT6

    (1+sT8)(1+sT9)M

    N

    Ks21+sT7

    sTw41+sTw4

    1+sT11+sT2

    1+sT31+sT4

    1+sT10 11+sT11 1+sT12

    Limiter

    Ks1

    Ks3

    VSTMIN

    VSTMAX

    sTw31+sTw3

    (option)

    Pmdt = Pedt +M

    Electrical Power(Pe)

    Terminal Voltage(Vg)

    Wash-out

    Wash-out Integral

    Lead/Lag

    Filter

    LimiterTo AVR

    Gain

    Frequency

    Step-up Transformer

    Rotor Speed

    TransducerPick Up

    Vg,Ig

    PTCTG

    or

    (option)

  • New Publication, effective Sep. 2001.Specifications subject to change without notice.

    HEAD OFFICE: MITSUBISHI DENKI BLDG., MARUNOUCHI, TOKYO 100-8310. TELEX: J24532 CABLE: MELCO TOKYO

    Improper use of products can cause severe injury or death,and may result in damage to product and other property.Please read instruction manual before installing or using product.

    SE-D779-A(0109-0.5)MDOC

    Mitsubishi Integral of Accelerating Power Type PSS (Power System Stabilizer)

    AVR

    AVR+

    PSS

    K1

    K1+K1A

    K1A+DA

    K1+D

    K1+D

    K1+K1A+K1P

    1Ms

    1Ms

    1Ms

    S

    S

    S

    D 0

    0

    0

    D+DA

    D+DA+DP

    Theory of PSS

    Though a generator output power is decided by the turbine mechanical torque, a generator output power also can be changed by changing excitation value transiently. (Fig.3) A PSS detects the changing of generator output power, controls the excitation value, and reduces the power swing rapidly. (Fig.4)

    Generator output power

    Excitation value

    Generator output power

    Excitation value

    Constant Excitation

    Block Diagram Torque Characteristics

    K1 : Synchronizing TorqueD : Damping TorqueM : Inertia

    K1A : Synchronizing Torque by AVRDA : Damping Torque by AVR

    K1P : Synchroning Torque by PSSDP : Damping Torque by PSS

    (Damping Torque)

    (Synchronizing Torque)

    Resultant Torque

    Resultant Torque

    By changing of excitation value,generator output power can be changed transiently

    (Fig.3) (Fig.4)

    A PSS detects the changing of generator output power, controls the excitation value, and reduces the power swing rapidly.

    Summary

    Explanation on torque vector

    (Stable at D+DA+DP 0)

    (Unstable at D+DA 0)

    C8641-A_Power_System_Stabilizer(1).pdfD779-A_Power_System_Stabilizer(2).pdf