    CHAPTER 1

    INTRODUCTION

    With increasingly complex and sophisticated buildings and equipment, a single

    lightning stroke can result in physical damage and catastrophic failure. It can initiate fire,

    cause major failures to electrical, telephone and computer services and simultaneously

    cause substantial loss of revenue through down-time.

    There are no devices or methods capable of modifying the natural weather

    phenomena to the extent that they can prevent lightning discharges. Lightning flashes to,

    or nearby, structures (or lines connected to the structures) are hazardous to people, to the

    structures themselves, their contents and installations as well as to lines. This is why the

    application of lightning protection measures is essential.

    The lightning protection system is generally considered in two parts. The external

    lightning protection system intercepts, conducts and dissipates the lightning flash to

    earth. The internal lightning protection system prevents dangerous sparking within the

    structure (using equipotential bonding or separation distance) [6].

    The design of a lightning protection system needs to:

    Intercept lightning flash (i.e. create a preferred point of strike)

    Conduct the lightning current to earth

    Dissipate current into the earth

    Create an equipotential bond to prevent hazardous potential differences between LPS,

    structure and internal elements/circuits

    In achieving this, the lightning protection system must:

    Not cause thermal or mechanical damage to the structure

    Not cause sparking which may cause fire or explosion

    Limit step and touch voltages to control the risk of injury to occupants

    Limit damage to internal electrical and electronic systems

    Dept. of EEE TEC, Vellarakkad1

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    2/27

    Lightning protection systems typically follow two approaches,

    Non-isolated system where

    potentially damaging voltage differentials

    are limited by bonding the lightning

    protection system to the structure

    Isolated system where the

    lightning protection system is isolated from

    the structure by a specified separation

    distance. This distance should be sufficient

    that energy is contained on the LPS and

    does not spark to the structure [6].

    1.1 Step and touch voltages

    Touch voltage is the voltage acting upon a person between his position on the earth

    and the position of down conductor, when touching the down conductor. The current

    path leads from the hand via the body to the feet.

    Step voltage is a part of the earthing potential which can be bridged by a person

    taking a step over 1m. The current path runs via the human body from one foot to the

    other [7].

    Fig. 1.1) Isolated and Non-Isolated protection

    Fig. 1.2) Step and Touch voltage gradients

    Dept. of EEE TEC, Vellarakkad2

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    3/27

    1.2 Separation (isolation) distance requirements

    A separation distance,

    between the external LPS and

    the structural metal parts is

    essentially required. This will

    minimize any chance of partial

    lightening current being

    introduced internally in the

    structure. This can be achieved

    by placing lightening conductors sufficiently far away from any conductive parts that

    have routes leading into the structure. So, if the lightening discharge strikes the

    lightening conductor, it cannot bridge the gap and flash over to the adjacent metal

    work.

    The separation distance between the item to be considered and the LPS (to ensure

    that the dangerous sparking between them does not occur) is determined by the

    following equation,

    Fig. 1.3) Concept of separation distance

    Fig. 1.4) Bonding & separation distance

    Dept. of EEE TEC, Vellarakkad3

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    4/27

    Where,

    kiis a factor that depends upon the chosen lightning protection level.

    kcis a factor that depends upon the number of down-conductors (note that a range is

    given for 2 or more down-conductors, and depends on the current-sharing between

    down-conductors).

    kmis a factor that depends upon the electrical insulation material (1.0 for air, 0.5 for

    concrete and bricks).

    Lis the length in meter, along the air-termination or down conductor, from the point

    being considered to the closest equipotential bonding point [1].

    The values of ki, and kcare given in Tables 1.1 and 1.2.

    Table 1.1) Values of ki

    Table 1.2) Values of kc

    1.3 Conclusion

    At present, photo voltaic cells have a growing demand as a renewable energysource. For the roof-top installation, PV panels are integrated to the new buildings and

    new constructions. This integration raise challenges in designing the building and also

    the PV system. A major issue arises in this case is the lightning protection of the

    building and PV system [1]. A single lightning stroke can damage the panels and cause

    substantial loss of money. Hence, available protection techniques for safeguarding the

    buildings against direct strikes are necessary to be evaluated to provide a safe location

    to install the PV system.

    Dept. of EEE TEC, Vellarakkad4

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    5/27

    CHAPTER 2

    EXTERNAL LPS

    2.1 Introduction

    External protection system of a building intercepts the direct lightning strikes by

    air termination system, conducts the lightning current through a low impedance path to

    the earth termination system, and disperses this high current to a low resistance earth.

    In following the challenges in designing these three components are discussed [1].

    2.2 Air termination system

    The role of an air termination system is to capture the lightning discharge current

    and dissipate it harmlessly to earth via the down conductor and earth termination

    system. Therefore it is vitally important to use a correctly designed air termination

    system [4]. The type of air termination system installed on the roof depends on the

    shape and materials of the roof and usage of the building. Also, the type of protection

    and the area which is critical to be protected influence the selection of air termination

    system. Considering these factors, the following in any combination can be used for the

    design of air termination,

    Air rods (or finials) whether they are free standing masts or linked with conductors to

    form a mesh on the roof.

    Catenary (or suspended) conductors, whether they are supported by free standing masts

    or linked with conductors to form a mesh on the roof.

    Meshed conductor network that may lie in direct contact with the roof or be suspended

    above it, so that the roof is not exposed to a direct lightening discharge.

    Positioning of the air termination system is of paramount importance. The air

    termination components should be installed on corners, exposed points and edges of the

    structure [4]. Three basic methods recommended for determining the optimum location

    of the air termination systems are,

    The rolling sphere method (RSM)

    The protection angle method (PAM)

    The mesh method (MM)

    Dept. of EEE TEC, Vellarakkad5

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    6/27

    2.2.1 The Rolling Sphere Method

    The rolling sphere method is a simple means of identifying areas of a structure that

    need protection, taking into account the possibility of side strikes to the structure. In

    this method, an imaginary sphere is rolled over the surface of the structure. Where the

    sphere touches the structure, this point is vulnerable to a lightning flash and air-

    termination(s) are required. The air-termination system is placed such that the sphere

    only touches the air-terminations, and not the structure [4][6].

    Corresponding to the class of LPS, radius of the rolling sphere is different.

    For structures less than 60 m high the risk of flashes to the sides of the building is

    low, and therefore protection is not required for the vertical sides directly below

    protected areas.

    Fig. 2.1) Rolling sphere method

    Table 2.1) Rolling sphere radius and class of LPS

    Fig. 2.2) RSM for buildings less than 60 m high

    Dept. of EEE TEC, Vellarakkad6

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    7/27

    In the IEC standards, for buildings above 60 m, protection is required to the sides of the

    upper 20% of height.

    This method is suitable for defining zones of protection for all types of structures

    especially those of complex geometry [6].

    Fig. 2.3) RSM for buildings greater than 60 m & less than 120m high.

    Fig. 2.4) RSM for buildings greater than 120 m high

    Dept. of EEE TEC, Vellarakkad7

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    8/27

    2.2.2 The Protective Angle Method

    The protective angle method is a mathematical simplification of the rolling sphere

    method. The protective angle (a) is the angle created between the tip (A) of the vertical

    rod and a line projected down to the surface on which the rod sits.

    Air-terminations (rods/masts and catenary wires) are located so the volume defined

    by the protection angle covers the structure to be protected. The height of the air-

    termination is measured from the top of the air-termination to the surface to be

    protected. The protective angle varies with the height of the air termination and the

    class of the LPS. The protection angle method is limited in application to heights that

    are equal to or less than the corresponding

    rolling sphere radius [4][6].

    The protection angle method can be used

    on inclined surfaces, where the height of the

    rod is the vertical height, but the protection

    angle is referenced from a perpendicular line

    from the surface to the tip of the rod [6].

    Dept. of EEE TEC, Vellarakkad

    Fig. 2.5) PAM for a single air rod

    Fig. 2.6) Effect of height of the reference plane

    on protection angle

    Fig. 2.7) PAM applied to an inclined surface.

    8

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    9/27

    Where the protection angle method alone is employed, multiple rods are generally

    required for most structures. However the protection angle method is most commonly

    used to supplement the mesh method, providing protection to items protruding from the

    plane surface.

    2.2.3 The Mesh Method

    For protection of a plane (flat) surface, the mesh method is considered to protect

    the whole bound surface if meshed conductors are:

    Positioned on the edges (perimeter) of the surface

    The mesh size is in accordance with Table 2.2

    No metallic structures protrude outside the volume (consider air-terminals and

    RSM/PAM method to protect these)

    Fig. 2.8) Combination protection

    Table 2.2) Mesh size for mesh method

    Dept. of EEE TEC, Vellarakkad9

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    10/27

    From each point, at least two separate paths exist to ground (i.e. no dead ends), and

    these paths follow the most direct routes

    The mesh method should not be used on curved surfaces, but can be used on non-

    horizontal plane surfaces and compound surfaces [6]. For example on the vertical sides

    of tall buildings, for protection against flashes to the side, or on compound surfaces

    such as industrial roofs. For compound surfaces, conductors should be placed on the

    roof ridge lines if the slope exceeds 1/10.

    Fig. 2.9) Protection via mesh method

    Fig. 2.10) Mesh method for compound shapes

    Dept. of EEE TEC, Vellarakkad10

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    11/27

    The protective area provided by the mesh method is the area bounded by the mesh.

    The protection to areas adjacent to the mesh (e.g. building sides and lower structural

    points) is determined by the protection angle method or rolling sphere method.

    The protection provided by meshed conductors not placed in full accordance with

    the mesh method, e.g., those raised above the building surface, should be determined

    with an alternative design method, i.e., PAM or RSM, applied to the individual

    conductors.

    2.3 Down conductor system

    The down conductor system is the electrically conductive connection between the

    air termination system and the earth termination system. The function of down

    conductor systems is to conduct the intercepted lightening current to the earth

    termination system without intolerable temperature rises to damage the structure.It can

    be implemented by separate conducting tapes/wires or natural components of the

    building such as reinforcing rods of walls or concrete columns and steel structured

    frames.

    Fig. 2.11) Volume protected by meshed conductors according to PAM & RSM method

    Dept. of EEE TEC, Vellarakkad11

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    12/27

    To avoid damage caused during the lightening current discharge to the earth

    termination system, the down conductor systems must be mounted to ensure that from

    the point of strike to the earth,

    Provide multiple paths for lightning current.

    Be a direct continuation of the air-termination system.

    The length of the current paths is kept as short as possible (straight, vertical, no loops).

    Not be installed in gutters or down-spouts (even if PVC covered).

    The connections to conductive components of the structure are made wherever required

    (distance < s; s= separation distance).

    Connect via a test joint to the earth termination network.

    The general requirements for down-conductors on non- isolated LPS are:

    At least two down-conductors should be used.

    Down-conductors should be equally distributed around the perimeter of the structure

    (within practical and aesthetic reasons).

    Down-conductor should be located at exposed (external) corners of the structure where

    possible (within 300 mm).

    Attempt to locate down-conductors (using separation distance requirements) away from

    doors, window frames, railings etc. that would be subjected to human touch during

    thunderstorms periods.

    The typical values of the distance between down conductors are shown in Table

    2.3. In case of tall structures bonding all down conductors at regular vertical intervals

    (say 20 m) may keep the system at equipotential [7].

    Table 2.3) Typical spacing of down-conductors & equipotential bonding rings

    Dept. of EEE TEC, Vellarakkad12

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    13/27

    The general requirements for down-conductors in an isolated LPS are:

    For rod air-terminations, one down-conductor is required per mast. If the mast is

    metallic or interconnected reinforcing steel, then no additional down-conductor is

    required.

    For catenary air-terminations (one or more wires), at least one down-conductor is

    required per support.

    It should be noted that, down conductors must be installed straight and vertical,

    and they should not be installed in loops or as over hangs. If loops cannot be avoided,

    the separation distance across the gap must be greater than minimum separation, s.

    2.4 Earth termination system

    The surge current flowsthrough the down conductors will be dispersed to the soil

    by the earth termination system. Since the reliable performance of the entire lightning

    protection system is dependent upon an effective earthing system, it should possess the

    following characteristics,

    Low electrical resistance between the electrode and the earth. The lower the earth

    electrode resistance the more likely the lightening current will choose to flow down that

    path in preference to any other, allowing the current to be conducted safely to and

    dissipated in the earth.The general requirement is that the lightning protection earthing

    system must have a resistance of less than 10 ohms

    Good corrosion resistance. The choice of material for the earth electrode and its

    connections is of vital importance. It will be buried in soil for many years so has to be

    totally dependable.

    Design details are given on two methods:

    Type A Vertical and/or horizontal electrodes installed outside the structure footprint.

    Type B Ring electrode, installed outside the structure footprint (at a distance of about

    1 meter from the structure walls. In a given ring conductor 80% of its length should be

    in contact with soil) or natural earth electrode within footprint (e.g. footing

    reinforcing).

    Dept. of EEE TEC, Vellarakkad13

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    14/27

    In type A system, there must be earth electrodes installed at the base of each down-

    conductor. A minimum of two electrodes must be used.Depending on the class of the

    LPS, the minimum total length of electrode at each down-conductor is, (l1) for

    horizontal electrodes and (0.5l1) for vertical electrodes.

    In type B system, a ring electrode around the perimeter of the structure, or natural

    elements within the foundation is used.A ring conductor should have a mean radius of

    distance re l1.

    Fig. 2.13) Minimum length of electrodes, l1, for type A & B earthing systems

    Dept. of EEE TEC, Vellarakkad

    Fig. 2.12) Type A & B earthing systems

    14

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    15/27

    Where the distance rewould require the ring to be installed at a distance greater

    than 1 m from the structure, then it is recommended that the ring be installed at 1 m and

    additional supplemental horizontal or vertical electrodes are added per the following

    requirements. At least two equidistant supplemental electrodes should be installed and

    ideally connected at the each point where the down-conductors connect to the ring

    electrode.

    Additional horizontal electrode lengthat each down-conductor = - re

    Additional vertical electrode lengthat each down-conductor = ( - re) / 2

    Type B is recommended for bare solid rock and for structures with extensive

    electronic systems or great risk of fire. Type B is preferential from the point of view of

    providing equipotential bonding between the down-conductors (assuming no ground

    level equipotential ring is used) and providing better potential control in the vicinity of

    conductive building walls. For structures with non-conducting walls (brickwork, wood,

    etc.), and no interconnection to foundation reinforcing, a type B system or earth

    equipotential bonding ring is highly recommended.

    2.5 Conclusion

    An external LPS consists of Air termination system, Down conductor system and

    Earth termination system. These individual elements of an LPS should be connected

    together using appropriate lightning protection components satisfying the lightning

    protection standards. This will ensure that in the event of a lightning current discharge

    to the structure, the correct design and choice of components will minimize any

    potential damage.

    Fig. 2.14) Type B earthing system with additional elements

    Dept. of EEE TEC, Vellarakkad15

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    16/27

    CHAPTER 3

    INTERNAL LPS

    3.1 Introduction

    In the event of lightning, the danger of direct strikes to the protected building is

    reduced by external lightning protection system, which facilitates the high inrush

    current to flow through multiple down conductor system and then disperse to the soil

    through the earth termination system. Apart from the direct strikes nearby strikes of

    lightning can also affect the electrical systems inside the building. This is due to surges

    that are generated by inductive coupling (rarely capacitive coupling as well).

    3.2 Lightning protection zones

    The protection of electrical and electronic systems in buildings and structures

    against surges resulting from the lightening electromagnetic pulse (LEMP) is based on

    the principle of Lightening Protection Zones. According to this principle, the building

    or structure to be protected must be divided into internal Lightening Protection Zones

    according to the level of threat posed by LEMP. The zones may not necessarily be

    physical boundaries (e.g. structure walls). The zones are areas characterized according

    to threat of direct or indirect lightning flashes and full or partial electromagnetic field.

    The occurrence of lightning flashes, the lightning current or induced current and the

    electromagnetic field are varied in these different LPZs [2][6][7].

    LPZ 0 (Zero) is considered the lowest zone, LPZ 1, 2n being respectively

    higher. In general the higher the number of zone the lower the electromagnetic

    effects expected. It is the design and placement of the LPS that ensures the structureand internal contents are within an LPZ 0B zone.

    Table 3.1) Lightning protection zones

    Dept. of EEE TEC, Vellarakkad16

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    17/27

    Internal systems are required be located within an LPZ 1 (or higher) zone. As seen

    from Figure 3.1, electrical/electronic equipment located in LPZ 1 (or higher) and

    connecting to external services such as power lines, data lines and water and gas pipes

    (located in LPZ 0B or LPZ 0A) require transient protection devices (TPD) or Surge

    Protective Device (SPD) and spatial shielding or shielding cables, to limit energy being

    conducted from zones exposed to direct lightning or full/partial electromagnetic fields

    or surge current. Non electrical services (e.g. water, gas, etc.) meet this requirement by

    equipotential bonding [7].

    At the boundary of each internal zone, the equipotential bonding must be carried

    out for all metal components and utility lines entering the building or structure. This is

    done directly or with suitable SPDs.

    Fig. 3.1) Lightning protection zone concept

    Dept. of EEE TEC, Vellarakkad17

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    18/27

    3.3 Equipotential bonding

    Equipotential bonding is simply the electrical interconnection of all appropriate

    metallic installations/parts, such that in the event of lightening currents flowing, no

    metallic part is at a different voltage potential with respect to one another. If the

    metallic parts are essentially at the same potential then the risk of sparking or flashover

    is nullified.

    This electrical interconnection can be achieved by natural bonding or by using

    specific bonding conductors. Bonding can also be accomplished by the use of Surge

    Protective Devices (SPDs) where the direct connection with bonding conductors is not

    suitable.

    Figure 3.2 shows a typical example of an equipotential bonding arrangement. The

    gas, water and central heating system are all bonded directly to the equipotential

    bonding bar located inside but close to an outer wall near ground level. The power

    cable is bonded via a suitable SPD, upstream from the electric meter, to the

    equipotential bonding bar. This bonding bar should be located close to the Main

    Distribution Board (MDB) and also closely connected to the earth termination system

    with short length conductors [4][5].

    Fig. 3.2) Example of main equipotential bonding

    Dept. of EEE TEC, Vellarakkad18

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    19/27

    In larger or extended structures several bonding bars may be required but they

    should all be interconnected with each other. The screen of any antenna cable along

    with any shielded power supply to electronic appliances being routed into the structure

    should also be bonded at the equipotential bar [4].

    3.4 Conclusion

    The fundamental role of the internal LPS is to ensure the avoidance of dangerous

    sparking occurring within the structure to be protected. This could be due to following

    a lightning discharge, to lightning current flowing in the external LPS or indeed other

    conductive parts of the structure and attempting to flash or spark over to internal

    metallic installations. Carrying out appropriate equipotential bonding measures or

    ensuring there is a sufficient electrical insulation distance between the metallic parts

    can avoid dangerous sparking between different metallic parts.

    Dept. of EEE TEC, Vellarakkad19

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    20/27

    CHAPTER 4

    LIGHTNING PROTECTION FOR ROOF-TOP PV SYSTEMS

    4.1 Introduction

    Building Integrated Photo Voltaic (BIPV) system as a type of implementation of solar

    energy has a high demand at present. The assessment of risk of damage due to lightning for these

    systems is necessary as the systems are installed at significantly large heights and extended

    surface at such heights make these systems vulnerable to be intercepted with lightning stepped

    leaders. Therefore, the external LPS ofBIPV systems must be designed by considering the PV

    panel on the roof top as well.

    4.2 Design of Lightning Protection System

    To design suitable air termination system which is capable of protecting PV panels from

    direct strikes and induced effects several extra precautions should be taken by the designer. The

    roof should be protected considering the PV panel as an isolated system from the LPS. In this

    case extra care should be taken regarding the shape, height, and total configuration of panels. In

    addition, the separation distance of panels to the LPS is another specified issue. In designing the

    air termination system which consists of rods on the flat surface roofs by the protection angle

    method can be seen in Figure 4.1, the angle of the PV panels or the maximum angle of the

    moving panels should be taken into consideration; the protected area by the rod must cover the

    panel when the panel surface is rotated. In Figure 4.1, it can be observed that by the rolling

    sphere method the distance between each two rods in a row, also the distance between the rods in

    one row to the other row can be obtained. Further, in designing LPS, care should be taken to

    minimize the shadow effect of finials on panels which may reduce the efficiency of system [1].

    Fig. 4.1) Protection of PV panels applying RSM and PAM

    Dept. of EEE TEC, Vellarakkad20

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    21/27

    As shown in Figure 4.2, at least the minimum separation s should be kept between

    LPS and the panels frame (isolated LPS). Separation s should also be kept between the

    bonding conductor and PV panels mounting structure unless the LPS is bonded to the

    frames (non-isolated LPS) to be protected. The requirement of an isolated or non-

    isolated LPS depends on the sensitivity of the PV system for the stray lightning

    currents that will be diverted into the metal framework of the panel. Depending on the

    requirement of isolation or non-isolation of external LPS, other necessary components

    of the LPS (such as SPD) may be determined.

    An important aspect of external LPS in the presence of roof top PV system that has

    not been properly addressed in the LP standards is the mechanical stability of the

    vertical air-terminations. In the event of a mechanical failure of vertical air-termination

    (such as the whole rod being enrooted from the base or part of the upper segment

    detached from the main rod), the cost of damage may be highly enhanced if the fallen

    part lands on the PV system [1]. Damage may be even worse in the case of mechanical

    failure of early streamer emission (ESE) type air terminations (recommended in French

    Standards NF C 17-102 and Spanish Standards UNE-21186) where a heavy metal part

    is most often connected at the pinnacle of the rod. Authors have observed such damage

    to the roof of buildings in several countries including India and Malaysia.

    Fig. 4.2) Applying protection angle method for PV panels

    Dept. of EEE TEC, Vellarakkad21

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    22/27

    Hence, more stringent conditions should be introduced into the standards (or

    guidelines) on the mechanical strength of vertical air-terminations of LPS for buildings

    with roof top PV systems. These recommendations should cover the fixing strength of

    the base plate, material strength, weight of the rod etc. On the other hand, mesh type

    (horizontal tapes or wires) air-termination systems can strongly be recommended for

    such structures instead of vertical metal rods. Such design will also reduce the shadow-

    effect problem as well.

    The selection of SPDs for roof-top PV systems depends on the class of LPS for

    building and the isolation of PV panels frames from LPS, unless bonding the panel

    frames to the LPS makes the system non-isolated which changes the SPD type

    applicable for that PV system and sizes of earthing conductors that carry the lightning

    induced currents. DC wires are used to connect the output of PV panels to the inverter

    inside. Protection of DC wires in the LPZ1 is performed by SPDs that are connected

    before the inverter in DC side. If the separation distance between panels on the roof and

    inverter is more than 10 m, two sets of SPDs are required, one close to the PV modules

    and another one close to the inverter. Furthermore, one set of SPD is essential in the

    AC side. Also, if the distance between the inverter and load center is more than 10 m,

    one SPD is needed in the load center as well [1]. Figure 4.3 shows a roof top PVsystem with all components, the internal and external LPS.

    Fig. 4.3) SPD connection for roof top PV system

    Dept. of EEE TEC, Vellarakkad22

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    23/27

    The types of SPDs applicable for the PV system can be selected according to the

    situation between the panels and LPS. For a roof-top PV system in a building without

    the external LPS, two sets of SPD type 2 are needed in the DC side and two sets of

    SPD type 2 in the AC side and load center (distance more than 10 m).

    In the roof-top PV system with external LPS, if the distances between air

    terminations and bonding conductors on the roof to the panels frame and mounting

    system are more than the separation distance S, the PV system can be kept isolated, in

    this case, two sets of SPD type 2 are required in the DC side and one SPD type 2 in the

    AC side close to the inverter, but the SPD in the AC load center should be selected

    from type 1.

    For the non-isolated PV system where the LPS is connected to the panels frames

    with a distance less than the separation distance S, two sets of SPDs type 2 are required

    in the DC side, but in the AC side of inverter one SPD type 1 must be installed close to

    the inverter and one SPD type 1 is also needed in the AC load center [1].

    In order to reduce the dangerous sparking between the PV system components and

    to make the PV system equipotentialized, all SPDs and inverter equipment grounding

    must be bonded to the Equipotential bonding bar. This bonding bar should beconnected to the main earthing bar close to the earth termination system. Also the

    panels frame must be connected directly to both the equipotential bonding bar and the

    main earth bonding bar. The sizes of earthing conductors which connect the

    components to the bonding bar are different depending on the volume of the induced

    current that may be carried through the conductor. Also, different dimensions of

    conductors are employed when the LPS is connected to the panel [1][7].

    4.3 Conclusion

    BIPV system is becoming an emerging trend in India. The PV panels are usually

    placed in the roofs of tall buildings so the chance of lightning strikes is large. To

    protect the panels, available protection techniques for safeguarding the buildings

    against direct strikes are to be evaluated to provide a safe location to install the PV

    system.

    Dept. of EEE TEC, Vellarakkad23

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    24/27

    CHAPTER 5

    BIPV CASE STUDIES IN INDIA

    5.1 Introduction

    The solar PV technology involves direct conversion of available solar energy into

    some useful electrical energy. It can realistically contribute to greater global

    sustainability in the medium to long term. PV is becoming more and more accessible

    both in urban and rural areas due to declining costs. Recently, there has been a world-

    wide focus on the architectural integration of PV modules in the building envelope.

    Such type of modules can effectively replace conventional building materials like roof

    tiles, shingles, facades, and normal glazing. PV building materials can be manufactured

    in a manner that they are quite similar to the conventional building products, blending

    well with the surrounding environment.

    5.2 BIPV systems in India

    India with a tropical climate with sunny weather condition is a suitable area for

    installing PV systems. Rabi Rashmi Abasan (meaning a solar housing complex) is

    Indias first solar complex. This complex conceived by WBREDA (West Bengal

    Renewable Energy Development Agency) is located at New Town Kolkata and is

    spread over an area of 1.76 acres. There are 25 independent apartments in the complex,

    each of which has been provided with a rooftop solar PV system of 2 KWP capacity.

    Sixteen single crystal silicon modules of 125 WP have been put up in each case. Each

    house owner within the complex willproduce his own power for domestic use and feed

    any surplus power into the local grid. He can also draw power from the grid as and

    when needed. The utility will pay the house owner and vice-versa on net monthly

    metering.

    Also great numbers of bungalows constructed in the country side provide

    opportunities to install the rooftop PV systems. The preference of bungalows instead of

    tall buildings normally with flat surface roofs are the lower height of the building and

    slopped roof. By installing PV panels on the bungalows roofs, the danger of lightningstrikes shall be much less than tall apartments.

    Dept. of EEE TEC, Vellarakkad24

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    25/27

    Also the shading effects in most cases can be reduced because the panels are

    mounted above a height that is taller than trees or any other equipment on the ground.

    Furthermore, in the rooftop PV systems most of the wirings and all other equipments

    except panels can be imbedded inside the building with the separation distance to the

    LPS which can be protected against lightning [1].

    Figure 5.1 and 5.2 show two BIPV projects in India, the slopped roof and the flat roof

    respectively.

    5.3 Conclusion

    Two types of BIPV projects in India are slopped roof and flat roof projects. The

    panels on the slopped roof are mounted directly on the roof without any mounting

    structure while in flat surfaced roofs the panels are mounted on bars with certain height

    fixed to structure; therefore, the height of the structure to be protected in the flat surface

    is higher. Hence, in suchcases vertical type air-terminations become a must.

    Fig. 5.1) Slopped roof BIPV system

    Fig. 5.2) Flat roof BIPV system

    Dept. of EEE TEC, Vellarakkad25

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    26/27

    CHAPTER 6

    CONCLUSION

    An efficient design of the LPS with a well-located PV panel provides high

    efficiency of power generation with minimized lightning risk. To design the external

    LPS, the type of PV system and the configuration of PV panel should be taken into

    account. The shape of the roof and location of the panel are also important factors in

    optimizing the LPS. It is recommended to design the required LPS for the PV system

    during the construction or pre-construction stage of the building, so that the efficiency

    of the protection system could be maximized. Wherever it is possible, mesh type air

    terminations are preferred over vertical rods to minimize mechanical damage in the

    case of air-termination failure and also to avoid shadow effect.

    Dept. of EEE TEC, Vellarakkad26

  • 8/13/2019 Lightning ProtectionTechniques For Roof-Top PV Systems

    27/27

    CHAPTER 7

    REFERENCES

    [1]Narjes Fallah, Chandima Gomes, Mohd Zainal Abidin Ab Kadir, Ghasem Nourirad,Mina Baojahmadi, and Rebaz j.Ahmed Lightning Protection Techniques for Roof-

    Top PV Systems IEEE 7th International Power Engineering and Optimization

    Conference (PEOCO2013), Langkawi, Malaysia June 2013.

    [2]IEC 62305-1: Protection against lightning Part 1: General principles, 2010.[3]IEC 62305-2: Protection against lightning Part 2: Risk management, 2010.[4]IEC 62305-3: Protection against Lightning Part 3: Physical damage to structures

    and life hazard, 2010.

    [5]IEC 62305-4: Protection against lightning Part 4: Electrical and electronicsystems within structures, 2010.

    [6] Erico international corporationERITECH-Lightning Protection Handbook Designingto the IEC 62305 Series of Lightning Protection Standards. , 2010

    [7]DEHN Lightning protection guide revised 2nd edition., 2007