Lightning Air Terminals - Is Shape Important

Embed Size (px)

Citation preview

  • 7/23/2019 Lightning Air Terminals - Is Shape Important

    1/6

    Lightning Air Terminals s Shape Important?

    William Rison Senior Member, IEEE),

    Charles

    B.

    Moore,

    and Graydon

    D.

    ulich

    Langmuir Laboratory for Atmospheric Research

    New Mexico Institute of Mining and Technology

    Socorro, New Mexico USA

    [email protected]

    Abstrad-Benjamin Frank lin originally proposed th e use of

    sharp pointed lightning rods

    as

    a way to prevent lightning strikes.

    It

    was

    soon

    found that such rods did not prevent lightning

    strikes, hut that they worked to prevent damage to a strncture

    when it

    as

    struck by lightning. Conventional lightning protection

    systems evolved from this finding. Conventional lightning

    protection systems consist of air terminals (lightning rods) used

    to intercept a lightning discharge, downcondnctors used to carr y

    the current, and a grounding system used to dissipate the curre nt

    away from the protected structure. However, it has long been

    recognized by the scientific community that lightning protection

    systems do not prevent lightning, and that the sharp points

    on

    lightning rods traditionally used in North America are not

    needed for that purpose. To be effective air term inal s should be

    designed so tbat they are much more likely to be struck by

    lightning than objects

    on

    the structure they are protecting.

    Recent field studies indicate that

    a

    lightning rod with a blunt tip

    is

    more effective than a lightning rod with a sh arp tip.

    Two nonsonventiona l lightning protection systems are heavily

    marketed in North America Early Streamer Emission @SE) ai r

    terminals and Charge Transfe r Systems (CTS). Proponents of

    ESE air terminals claim that such devices have a much larger

    zone of protection than do conventional air terminals. Proponents

    of

    CTSs claim tbat corona current emilted from their arrays

    of

    sharp points can prevent lightning strikes to protected

    structures.

    Field studies of ESE a ir terminals show that their performance is

    similar to that of conventional sharp-pointed air terminals, and

    that they do

    not

    have the greatly enhanced zone of protection

    claimed for them. Field studies of Charge Transfer Systems show

    that they do not prevent lightning strikes

    Kqwords-air lerminals, Charge Transfer Systems, Early

    Streamer Emission air terminals, lightning,

    ligltlning prorec l ion,

    lightning rods

    I. INTRODUCTlON

    Conventional lightning protection systems (LPSs) have

    developed from the pioneering work of Benjamin Franklin in

    the late

    1700s

    [I]. Franklin was the first to conclusively

    demonstrate that lightning is a n electrical discharge, similar in

    phenomenology (though not magnitude)

    to

    the small sparks

    Franklin generated in his laboratory experiments. Franklin

    found that if be approached a charged object with a grounded

    blunt conductor, a spark would develop between the two.

    However, if be approached the cha rged object with

    a

    grounded

    sharp conductor, a spark did not develop; rather, the charged

    object was silently discharged. This led Franklin to the

    hypothesis that it might be possible to p revent lightning strikes

    to a structure by erecting sharp grounded conductors on the

    structure the sharp conductors might be able to silently

    discharge the thundercloud, preventing a lightning discharge:

    houses, churches and ships [should be provided] on

    the highest parts o f those edifices, upright rods of iron

    made sharp as a needle, and gilt

    to

    prevent rusting, and

    from the foot of those rods

    a

    wire down the outside o f the

    building into the ground,

    or

    down round one of the

    shrouds of a ship, and down her side till it reaches the

    water.

    Franklin and others installed lightning rods on structures

    to try

    to protect them by preventing lightning. While there is

    no evidence th t lightning strikes were prevented, it

    soon

    became evident that, when lightning did strike a structure

    equipped with lightning rods, the lightning would attach

    to

    one

    of the elevated rods, the lightning current was carried to ground

    through the down conductors, and the structure was protected.

    This led Franklin to modify his claim for lightning

    rods

    to

    include the ability to provide a safe path

    to

    ground for the

    lightning current:

    I have mentioned in several of my

    letters,

    and except

    once, always in the olternutive viz, that pointed rods

    erected on buildings, and communicating with the moist

    earth, would either prevent a stroke, or, if not prevented,

    could conduct it,

    so as

    hat the building should suffer no

    damage.

    Since Franklins invention of the lightning rod it has been

    convincingly demonstrated that conventional lightning

    protection systems are extremely effective in preventing

    damage

    to

    protected structures from direct lightning strikes [2,

    31.

    During the 1800s most improvements in conventional

    LPSs came about through trial and error analysesof system

    failures

    led

    to improvements

    in

    the placement of air terminals

    and down conductors, and in grounding system installation.

    With the development of modem inshumentation over the past

    eighty years, our scientific understanding of lightning has

    greatly improved, which has led to a better understanding of

    and improvements

    to

    LPSs.

    0-7803-8443-1/04/ 20.00

    IEEE.

    300

    mailto:[email protected]:[email protected]
  • 7/23/2019 Lightning Air Terminals - Is Shape Important

    2/6

    Some aspects of LPSs are historical canyovers from

    Franklins original work, and do not necessarily follow from

    current scientific understanding of lightning. One

    of

    these is

    the use in North America of traditional sharp pointed lightning

    rods.

    In 1878 several British.societies organized a conference on

    lightning protection. In

    1882,

    they issued their report,

    Report

    of the Lighining Rod Conference, which laid out a code of

    rules

    for

    those who installed lightning protection systems in

    Britain [4]. This document (and its American successor, the

    National Fire Protection Associations

    Specijcations for

    Proiecfion of Buildings

    against

    Lighfning

    [ 5 ] , contained the

    following statement:

    A lightning conductor fulfills two functions; it

    facilitates the progress of the electricity to the earth,

    carrying it

    off

    harmlessly, and tends to prevent

    disruptive discharge by neutralizing the conditions

    which d etermine such discharge in the vicinity of the

    conductor. _.. he second object is accomplished by

    the conductor being surmounted by a point or

    points.

    Over the next few decades, however, it

    was

    realized that

    lightning rods could not neutralize the conditions which lead to

    lightning strikes. In 1933, M. G Lloyd

    of

    he National Bureau

    of Standards w o te [6]:

    Most of those who have given considerable study to

    this problem [lightning protection] recognize that the

    discharges from the points of lightning rods have little,

    if any, value in preventing a stroke of lightning, and that

    it is not important that the points should be sharp.

    While it is now well known that lightning rods neither

    eliminale nor reduce the probability of a lightning strike, the

    authors have long been interested in the question of whether

    the shape of

    a

    lightning rod might influence its effectiveness.

    This paper discusses that question.

    11.

    THE

    LIGHTNING TTACHME NT

    ROCESS

    In order to discuss the effectiveness of lightning air

    terminals, it is necessq to have a hasic understanding of the

    phenomenology of the lightning attachment process. More

    detailed discussion can be found in standard references on

    lightning (e.g., [7]). Physical processes in a thundercloud

    separate electrical charge inside the cloud. In a typical

    thundercloud, there is a mid-level negative charge at ahout

    6

    km

    altitude and an upper positive charge at about

    IO

    km

    altitude. (Thunderstorm charging

    is

    a complicated process,

    depending on many environmental conditions, and many

    storms have charge structures different than the typical

    thunderstorm I describe here.) The negative charge in the mid

    level of the thundercloud induces a positive charge on the

    ground beneath it. The electric fields on the ground under a

    thunderstorm are typically 5 to 20 kV/m. The fields at the

    ground are intensified at the extremities of an exposed object

    to such an extent that the fields at the ex tremities can reach the

    value needed to break down air

    (3

    MV/m at sea level). When

    this happens, the object emits corona current, which produces

    a positive space charge above it. The corona current continues

    to flow until the space charge reduces the field at the

    extremities

    of

    the object to helow the air breakdown threshold.

    All exposed pointed objects emit corona current ree leaves,

    grass blades, antennas, power lines, etc. The space charge

    produced by objects on the ground limits the fields at the

    ground to the

    5

    to 20 kV/m value mentioned above. Without

    this space charge, the fields at the ground under a

    thunderstorm would often exceed 100kV/m.

    As the charge separation continues in the thundercloud,

    electric fields intensify inside the cloud. When the fields

    become strong enough an electrical breakdown (lightning)

    occurs, which discharges the thundercloud and reduces its

    electric field. The majority of lightning is intracloud

    discharges between the mid-level negative charge and the

    upper positive charge. A significant fraction of lightning is

    cloud-to-ground

    (CG)

    between the mid-level negative

    charge in the thundercloud and the induced positive charge on

    the ground below. (There are also positive cloud-to-ground

    discharges, not discussed in this paper, between a positive

    charge region in a thundercloud and an induced negative

    charge on the ground.)

    A negative CG discharge begins in the lower part of the

    mid-level negative charge region of the thundercloud. The

    breakdown propagates downward in a process known

    as

    a

    stepped leader. It develops in steps

    of

    about

    50 m

    in length,

    with an interval of about 50

    ps

    between the steps, and an

    average velocity of about 1.5 x

    IOs

    d s . This gives lightning

    its characteristic jagged app earance. The stepped leader

    carries negative charge towards the ground. A charge

    of

    about

    1

    mC/m

    is deposited on the leader channel, and a current of

    about 100 A flows as he channel develops.

    As the leader nears the ground, the electric fields on the

    ground intensify to such a level that the field near the tips of

    objects becomes strong enough to produce positive sparks

    (called streamers,

    or

    counter-leaders) which race upward

    towards the descending negative leader. If the stepped leader

    is too

    iir

    away from the ground, the electric fields between the

    leader and the streamer are not large enough to sustain the

    propagation of the streamer, and the streamer dies out.

    Eventually the leader gets close enough to the ground so that

    the intervening fields are strong enough to sustain a streamer,

    and a streamer will propagate to attach to the descending

    leader. When the streamer and leader meet, a conductive path

    to ground is established, and the charge on the leader channel

    flows to ground. This is the high current return stroke of a

    lightning discharge. Typical return stroke currents are 5

    kA

    and currents can he as large as 200 kA.

    The object which emits the streamer which wins the race

    the one which reaches the stepped leader fust s the object

    which gets struck by the lightning discharge. The distance

    0-7803-8443-1/04/ 20.00

    EEE.

    301

  • 7/23/2019 Lightning Air Terminals - Is Shape Important

    3/6

    from the grounded object to the tip o f the descending leader at

    the time the successful streamer is initially emitted from the

    object is called the striking distance. The striking distance for

    a typical lightning strike is about

    100m.

    111.

    EFFECTIVE

    LIGHTNING RODS

    An

    effective lightning rod is one w hich is much m ore likely

    to generate a successful propagating streamer than is a part of

    the structure it is protecting. It has long been known that

    tall,

    exposed objects are more likely to get struck

    th n

    are shorter,

    shielded objects. There are two reasons for this:

    1) If a taller object and

    a

    shorter object generate streamers

    at the same time, the streamer from the taller object will be

    more likely to attach to the approaching leader because that

    streamer has

    a

    shorter distance

    to

    travel. This is the basis of the

    electrogeometric method for the placement of

    air

    terminals in

    an LPS [PI If one assumes a 50 meter striking distance, then

    air

    terminals should be placed such that a streamer

    om

    an air

    terminal will have a shorter distance to travel to meet an

    approaching leader than will a streamer from any point on the

    protected structure, regardless of the direction from which the

    leader is approaching. A practical way to place lightning rods

    using this method is the Rolling Ball method [9]

    2)

    A tall, exposed object will provide electrical shielding

    for

    a nearby lower object. The e lectric fields at the shielded

    object will be lower than they would be if the taller object were

    not present. Consequ ently the shielded object

    will

    generate a

    streamer later than it would have if the taller object had not

    been there. This is why an LPS made of a grid of overhead

    wires

    is so

    effective.

    The electrogeometric method is based on the assumption

    that all objects are equally likely to generate streamers under

    the same conditions. However, if an object of one shape were

    more effective at generating a successful streamer th n

    an

    object of a different shape, then the electrogeometric method

    will not hold

    for

    all placem ents of air terminals an object on

    the protected structure with a more optimal shape for

    generating streamers might produce a streamer earlier th n a

    less optimally shaped lightning rod closer to the approaching

    leader. Moore

    [lo]

    suggested that lightning rods with blunt

    tips might be more effective at generating successful streamers

    than rods with sharp tips. We recen tly conducted a twelve year

    field study to

    try to

    determine if the shape

    of

    an air terminal

    affects its ability to succ essh lly generate a streamer. Results

    of the field studies are discussed in [I I] and are summarized

    below.

    A. Competition benveen Air Terminals of Different Shapes

    In

    order to determine if the shape of an air terminal affects

    its ability to generate a successful streamer, we arranged

    a

    compe tition between air terminals of different shapes. We

    conducted the experiment in an area with a high lightning strike

    den sity on a ridge near the 3288-111 high sum mit of South

    Baldy Peak in the Magdalena Mountains of central New

    Mexic o. We used a number of setups, each of which had

    two

    rods of different shapes. The two rods were mounted on

    6 meter tall poles, separated by a distance of 6 meters. The

    Figure 1. Blunt-tippcdlightning ods which were struck by lightning

    6meter separation insured that the Perturbation in the field

    strengths at one of the tips produced by an adjacent rod was

    about

    1

    of the ambient field strength. Each rod

    was

    equipped

    with a fuse

    or

    a lightning counter

    to

    determine if it were struck

    by lightning. The rods were

    made

    of aluminum, a

    metal

    which

    is much more likely to melt at the attachment point, and hence

    show physical evidence when struck by lightning than

    materials such as nickel-plated steel

    or

    copper

    are.

    A typical

    setup bad

    a

    traditional sharp-pointed air terminal and a blunt

    air

    terminal in compe tition. The diam eters of the blunt rods varied

    from 9.5 mm to

    51 nun.

    Over the twelve years of the

    study

    none of the sharp rods

    were struck by lightning, whereas 13 of the blunt rods were. A

    photograph

    of

    six blunt rods which were struck is shown in

    Figure 1. None of the blunt rods with diameters of

    9.5

    nun or

    51

    mm were struck. Most of the strikes have been to 19

    mm

    diameter rods. These results indicate

    that a

    moderately blunt

    tipped object is more likely to generate a successful streamer

    than is a

    sharp

    tipped object

    or

    an object with an extremely

    blunt tip. Reasons for this are discussed in detail in [12,13].

    B Streamers fr om Lighfning Rods

    In

    an

    attempt to learn more about the generation of

    streamers from lightning rods, we measured the streamer

    currents generated from several rods of different shapes in

    response

    to

    approaching leaders. We used

    three

    air terminals

    installed on

    6

    m tall masts separated by 6 m, in the

    form

    on an

    equilateral triangle. We measured the currents from the masts

    using 12-bit 5 MHz digitizers. We also measured the electric

    field change induced by an approaching stepped leader.

    Figure 2shows the results for on e lightning strike. The black

    trace in Figure

    2

    shows the increase in the electric field

    as

    a

    stepped leader approaches. Note that the ambie nt electric field

    increased from about 30 kV/m to about

    60

    kV/m. While the

    electric field tends to increase with time, there are instances

    0-7803-8443-1/04/$20.00

    EEE.

    302

  • 7/23/2019 Lightning Air Terminals - Is Shape Important

    4/6

    where the field decreases for a short period of time. These

    decreases are due to the shielding effect of space charge

    produced by objects in the vicinity. As a negatively charged

    leader approaches, the fields at the tips of nearby objects

    become strong enough to induce the objects to emit positive

    corona current. That positive charge provided some shielding

    from the approaching negative charge, and temp orarily reduced

    the field at the ground.

    The colored traces in Figure 2 show the currents emitted

    from three air terminals. The blue trace is the current 6 om a

    19 nun diameter blunt rod, the green trace is the current f7om a

    traditional

    sha rp

    pointed rod, and the red trace is the current

    6om a so-called Early Streamer Emission air terminal

    (discussed more fully in Section IV. The figure shows the

    responses from about 500 ps to about

    50

    p before the high

    current return stroke of the lightning strike. Starting at about

    370 p before the return stroke, all three rods s m e d emitting

    attempted streamers streame n which died out because the

    fields between the tip of the air terminal and the approaching

    leader were

    too

    small to

    sustain

    the streamer's propagation.

    The currents in the early attempted streamers were about 1 A.

    s the fields increased with the approaching leader, the

    attempted streamer currents became larger. At about

    150 ps

    before the return stroke, the blunt rod (blue trace) generated a

    streamer which did not die out. M e r he current initially rose

    to about 4 A, it fell to about A, but the streamer continued to

    propagate. At about 100 ps before the return stroke, the current

    began to increase rapidly as the streamer developed in

    intensity. When the current reached a value of 8 A it saturated

    the instrumentation; a short while later, a fuse used to protect

    the instrumentation blew. A subsequent inspection of the blunt

    rod showed fused spots where the lightning had attached to

    the

    rod.

    E L E C ~ C r l E L D C H * N O E A N D C U R R E N T T O L I G ~ N C i R O O S . W ~ 1 7 .l f f l . r n 1 7 u T

    Black DBlm

    E

    ( lor kVlm multiply by

    10 :

    Blue: 14mm

    I

    Red.

    RBdimcCv~

    ESP

    devi-:

    Green:

    FranWin md

    L s

    U0 a3

    250 2m ~1 5 0

    -,m 50

    TIME RELA TIVE TO TRIGGER SIGNAL

    microremnds)

    Figure 2. Lightning

    rod responses

    (colored t r a c e s

    to increasing

    electric field

    (black

    trace from an approaching lightning stepped

    leader.

    0-7803-8443-1/04/ 20.00

    0

    IEEE.

    303

    The data indicate that all three rods generated attempted

    streamers in response to an approaching leader. However, only

    the blunt rod generated a successful streamer a streamer

    which propagated to meet the approaching leader.

    Our esults show that a blunt tipped object is more likely to

    generate a successful streamer than is a sharp tipped one. If a

    lightning protection system using sharp tipped lightning rods

    protects a stlucture, then a blunt object on the structure may

    generate a propagating streamer earlier than one of the

    lightning rods.

    A

    more effective LPS would be one w hich used

    blunt tipped lightning rods, so that an object on the protected

    building is less likely to generate a propagating streamer earlier

    than i s one of the ligh tning rods.

    N N O N C O T I 0 N A L LIGHTNINGROTECTION

    SYSTEMS

    Currently there are two widely promoted non-conventional

    lightning systems which are claimed to have a scientific basis.

    These are the so-called Early Streamer Emission @SE) air

    terminals, and Charge Transfer Systems

    (CrS's) .

    A

    Early Streamer Emission Air Terminals

    ESE air terminals have either a unique shape or active

    elements at the air terminal tip. Proponents of ESE air

    terminals claimed that these features cause the terminals to

    generate streamers significantly earlier than conventional air

    terminals [14]. The earlier streamer generation is claimed to

    effectively increase the height of the air terminal by AL =

    v

    AT,

    where v is the velocity of the streamer and

    AT

    is the time

    advantage of the ESE air terminal. Manufacturers of ESE air

    terminals measure AT in laboratory studies. Typical reported

    values of AT are 50 to 300

    p

    and the value

    used

    for v is

    lO m/s. This purportedly gives an ESE air terminal an

    advantage

    AL

    of about

    100

    m over a conventional air terminal.

    There are

    three

    significant problems with

    this

    claim:

    1)

    Proponents of ESE d evices claim a streamer propagation

    speed of about IO6

    s .

    However both laboratory and field

    measurements of streamer speeds show that the speeds are on

    the order

    of

    IO4

    m/s

    tn

    10' d s ,

    one

    to

    two orders of magnitude

    lower than claimed [I5 ,161. Using the actual speed of leaders,

    the adv antage of ESE rods is decreased by one to two orders of

    magnitude.

    2) Even if

    an

    ESE device were to emit a streamer

    significantly earlier than a conventional air terminal did, it

    would be e ffective only if the streamer were able to propagate

    from the ESE device to the approaching leader. The

    propagation of a streamer does not depend on the conditions at

    the tip of the air terminal, but on the conditions between the tip

    and the approaching leader, which are not affected by ESE

    devices. In an an alysis of ESE d evices, Mackerras et al. [17]

    conclude that it is not possible to

    gain

    a significant

    improvement in lightning interception performance by causing

    the early emission of a streamer kom an

    air

    terminal.

    3)

    Our field studies

    [ I l l

    (e.g., Figure

    2)

    show that ESE

    devices do not generate streamers any earlier th nconventional

    air terminals do. We tested the two most popular ESE air

    terminals marketed in North America, and found that their

  • 7/23/2019 Lightning Air Terminals - Is Shape Important

    5/6

    responses to approaching leaders were similar to that of a

    conventio nal sharp painted lightning rod. During ow twelve

    year field study we found no evidence that any of the ESE

    device were struck by lightning, although we have many

    documented cases in which lightning struck with the claimed

    zones of protection of the ESE devices.

    B.

    Charge Transfer Systems

    A

    Charge Transfer System typically consists of an array of

    many sharp conducting points erected over a facility to be

    protected. Corona current 6om the points on the array

    supposedly transfers a significant amount of charge 60m the

    array into a region above the array. Condu ctors betwee n the

    array of points and a grounding system provide a path for the

    current 6om ground to the points in the array. The primary

    claim made for Charge Transfer Systems is that this space

    charge above the array prevents lightning discharges to the

    protected facility. When originally introduced , the claim was

    similar to the original hypothesis

    of Franklin:

    that the charge

    generated by the

    CTS

    would silently discharge a thundercloud

    and prevent lightning [18]. When it becam e obvious that the

    additional charge from a few thousand paints would not add

    significantly to the charge generated 6 0m the large number of

    natural points (tree leaves, grass blades, etc.), the proponents

    changed their arguments to say that a CTS would inject

    sufficient charge (about 5 C ) above it to neutralize an

    approaching leader [19]. It is easy to demonstrate that it is

    impossible to inject the necessary charge into a small volume

    above such an array [16]. The current claim is that a small

    amount of space charge above the array will inhibit the

    formation of steamers from the array. causing the lightning to

    strike a nearby object rather than the array and the protected

    structure below [20]. Howe ver, all of these mech anisms

    require that an array of closely spaced points generate

    significantly more corona current than a single point. Field

    studies of arrays of

    paints

    show that this is not the case

    [21,22,23].

    Because the mechanism by which

    a

    Charge Transfer

    System is supposed to work in not clear, the

    best

    way to

    investigate the effectiveness of

    a

    CT S is to determine whether

    or

    not such systems get struck by lightning. Anec dotal

    accounts of arrays being struck do not necessarily invalidate

    the systems an array could have been imprope rly installed or

    maintained, which could reduce its effectiveness. The best way

    to assess the effectiveness of CTS s is to compare two similar

    structures, one of which is equipped with a CTS and

    a

    similar

    control structure without a CTS. There have been several such

    studies done [22,24,25,26]. All of the studies have shown that

    the Charge Transfer Systems were struck by lightnihg (as were

    the control structures), and that there was no significant

    reduction in the frequency of lightning strikes to a structure

    equipped with a CTS.

    The main selling point used by manufacturers of

    CTSs

    is

    that their customers report significant decreases in lightning

    damage after a structure has been equipped with a

    C T S .

    It is

    important to note that a decre ase in (or eliminationo f lightning

    damage does not necessarily indicate the elimination of

    lightning strikes. In fact, a well designed convention al LPS

    will greatly reduce

    or

    eliminate damage 6o m a direct lightning

    ~

    0-7803-8443-1/04/ 20.00 0

    IEEE.

    304

    strike without preventing strikes.

    A

    CTS has all the elements

    of a conventional LPS, and probably reduces lightning damage

    for the same reasons a conventional

    LPS

    does. A C T S contains

    a grid of overhead wires, which functions both

    as

    a preferred

    strike point for a lightning discharge, and

    to

    reduce the fields at

    the protected structure below, reducing the probability of a

    streamer from the structure itself A CTS has a low impedance

    path to a good grounding system, which gives

    a

    path to ground

    for the large lightning currents when the CTS is struck.

    V. CONCLUSIONS

    A conventional lightning protection system consist of air

    terminals which act

    as

    preferential receptors of lightning

    strikes, downconductors to cany the large lightning currents,

    and

    a

    grounding system to dissipate the lightning current away

    6 0 m

    the protected structure. The r terminals in

    an

    LPS

    should be higher than objects on the protected structure, and

    should be designed to be more effective at the generation of

    successfully propagating streamers. A twelve year field study

    has shown that lightning rods with moderately blunt tips

    (19 mm diameter) are more effective

    th n

    rods with sharp tips

    or extremely blunt tips

    (>

    50m m) . Lightning protection

    systems using sharp rods have a long history of effectiveness,

    but systems which use blunt rods should be even more

    effective.

    Field studies of two non-conventional lightning protection

    systems (Early Streamer Emission air terminals and Charge

    Transfer Systems) show that these systems do not function as

    claimed by their proponents. ESE air terminals have been

    shown to be no more effective th n sharp pointed lightning

    rods.

    While Charge Transfer Systems may reduce damage

    60m

    lightning strikes, they do

    so

    in the same way that much

    less expensive conventional lightning protection systems do.

    They do not eliminate lightning strikes

    as

    claimed.

    REFERENCES

    [I] I .

    B. Cohen, Benjamin Franklins Experiments, A New Edition of

    Franklins Experiments and Observations on Electricity, b a r d

    University

    Press,

    Cambridge, MA 1941

    [2] Comm inee on Atmospheric and Spac e Electricity

    of

    the American

    Geophysical Union, The scientific basis

    for

    mditional lightning

    protection systems,

    h n o : l l a s e . a r m . o r ~ ~ ~ o ~ ~ . v d f ,

    001

    131 Federal Interagency Lightn ing Protection Users Group, The basis of

    conventional lightning protection technology M I

    - ~ . l i ~ h m i n e s a f e t . ~ ~ ~ l ~ ihmiwnventionalLPT.odf.2001..

    [4] G. I Symons,,

    editor,

    R e p R of the Lighming Rod Conference, E. B F.

    N. Spohn, 16 Charing Cross Road, London, 1882..

    [SI W.

    Lemmon,

    B.

    H.

    Loomis and R. P. Barbour, Specifications for

    Protection

    of

    Buildings against Lightning, National Fire Pmtection

    Association. Quincy.

    MA

    1904.

    161 M. G . Lloyd, iigh tning protection for Irees Science,

    vol. 70,

    p. 603,

    1933.

    [q

    M.

    A

    U-. The Lightning Discharge, Aca dem ic

    Fress,

    Orlando, 1987.

    [SI Mousa, A.M . and R D . Srivastava, A Revised Elecbogeom ehic Model

    for

    the Termination of Lightning Smkes on Ground Objects, Proc.

    Inter. Aerospace omi Ground Conference

    on

    Lightning and S t d c

    Elecwicip,

    Oklahoma

    City, OK, 342-352, 1988.

    [9] R. H.

    Lee.

    Protect your plant against lightning, IEEE

    Trans.

    On

    Industry Applications.vol. L4-15, pp. 236-240, 1978.

    [IO] C.

    B.

    Moore, Improved configurations of lightning rads and ir

    t m n i ~ l s ,. Franklin

    Inst.,

    vol. 315, pp. 61-85, 1983.

  • 7/23/2019 Lightning Air Terminals - Is Shape Important

    6/6

    [I 11 C. B. Moore. G. D. Aulich and W. Rison,

    Measuremcntr

    of lighm ing rod

    rerpanses

    to

    nearby strikes, Oeophys. Res. Len ., vol. 21, pp. 1487-1490,

    2000.

    [I21

    C. B. Moore, W. Rison, I. Mathis and G. D. Aulich, Lightning rod

    improvement studies, J. Appl. Meteor., vol. 39, pp. 593-609.2000.

    [I31 C. B. Moore, G. D. Aulich and W. Risan, The

    case

    for blunt-tipped

    lightning rods as sbike receptors, 1. Appl. Meteor.,

    vol.

    42, pp . 984-993,

    2003.

    1141

    G.

    Berger,

    The

    early

    Sfreamer

    lightning

    rod

    conductor, Proc.

    15

    Int.

    Conf. of L ightning and Static Electricity, Atlantic City, NI. U.S. ept. of

    Transportstion, pp. 38-1 - 8-9, 1992.

    [IS]

    S Yokoama, K Miyake and T.

    Su&,

    Winter lightning on Iapaa

    Sea

    coast - Development of

    measuring

    systems on progressive feature of

    lightning discharge, IEEE Trans. Power Delivery,

    vol.

    5 , pp. 1418.1425,

    1990.

    1161 M. A. Uman and V.

    A

    Rakov, A critical reviow of nonconvcntional

    approaches to lightning protection, Bull. Amer. Meteor. Soc.,

    vol.

    83,

    (171 D. Mackerras. M. Darvcniza and A. C . Licw, Review of claimed

    e n h a n d lightning protection of buildings by early sheaner emission

    air

    terminals, IEEE proc. Sci. Meas. Technol., vol.

    144,

    pp. 1-10. 1997.

    [18]

    E. H.Wileox, Lightning pmtection

    by

    prevention of oil field tanks and

    reservoin,Oil Field Engine er, pp. 21-31, Sepl., 1927.

    1191 D. W. ipse, Lightning protection methods An update

    and

    a discndacd

    system vindicated, IEEE Trans. ndustry Applications,

    vol.

    37, pp. 407-

    414,2001

    pp. 1809-l820,2002.

    1201

    E. M. Bazelyan and M. M. Drabkin, Scientific

    and

    technical basis for

    preventing lightning strikes

    to

    earthbound objects, FTac. 2003 IEEE

    Power Eag. Soc. General Meeting. T oronto, a t . . CA, 6 pp., 2003.

    [21] Chalmen. 1.A.. Almospheric Electr ic i@, Pergamon FTess, Oxford, 1961.

    1221 Bent, R.B. and S.K. Llewellyn, n Investigation of the Lighming

    Elimination and Sbike Reduction Properties of Dissipation

    Arrays. in

    Re v im

    of Lightning roleclion Technologv for Tall

    Slrucrures,

    Publication No. AD-AO57. O E c e of Naval Research.

    Arlington,

    VA,

    1975.

    1231 W. Rison, Experimental validation o f conv entional and non-

    conventional lightning protection systems,

    Proc.

    2003 IEEE Power Eng.

    Soc.General Meeting, Toronto, Oat.,

    CA,

    6 pp., 2003.

    1241 Fedc ral Aviation A dministration , 1989 Lightnrng Pro l ea i on

    Abbrpdnt

    Discharge

    S w e m s

    Tests. Or lmdo . Sorosolo T a m p .

    Florida, Final

    Repan, FAATC T I6 Power Systems Program, ACN-210,1990.

    1251 N. Kuwabara, T Tominaga, M. Kanazam and S. Kuramoto,

    Probability Occurrence of Estimated Lighming Surge Current at

    Lighming Rod Before

    and

    a Installing Dissipation An ay System

    @AS), Proceeding* of Ihe 1998

    IEEE-EMC

    S w p s i u m , pp.1072-107.

    1998.

    1261 W. Rison, W.,

    Evaluation of the Lighming Dissipation Array

    an

    the

    WSMR

    ightning test

    bcd,

    Final Repon for the US. my Research

    Lab,Connact D AAw7-89-KdO3 I WS MR NM 994.

    0-7803-8443-1/04/ 20.00

    Q IEEE.

    305