Upload
rodriguez-juan
View
215
Download
0
Embed Size (px)
Citation preview
8/18/2019 Light Maintanence
1/14
Get out the inspection mirror and fash light. The ollowing is hopeully a useul
guide to a service call in general. Much o it has already been covered in other
parts o the orum, this is the details otherwise. Long winded but in ollowing
what to look or and watch or does not in servicing the equipment does not take
long. rint it up, then print up a poster si!e type o sheet with what basic
principals you are looking or. "emember that you are looking or problemsbeore they ail as the goal in a good service call. #leaning and prepping a $%ture
is one thing, do a real service call or inspection such as the rest o the world in
theory is doing yearly and it&s a by ar di'erent thing.
(irst the simple ) what is easy to notice without much work or the good service
call. Look at the $%ture, it&s cord and plug and note anything that stands out.
*hake the plug, do you hear it&s terminals loose within it+ oes it work+
-Look at the plug/s strain relie, has it ailed to keep the $berglass or cord/s
sleeving in the strain relie+ Look or suspicious stu' about the plug and the wire
coming out o it. Look at the pins and general condition o the plug. 0 stage pin,
are the slots in the pins parallel, with any plug ) did someone over spray the pins
with paint, are they arched+ 1ll would need repair than. 2ou can service a plug
but that&s a di'erent discussion.
3 4pen up a sampling o the plugs o given lot numbers and ensure that screws
are tight 5-67 turn past $nger tight or the speci$ed torque o the plug and
conductors are not warn or breaking away at both the strain relie and terminal.
0 you don/t have a way o knowing when a $%ture was wired, or it would be
di8cult, error on the side o opening up all plugs when possible during a good
inspection.
9a Make sure that those installing the conductor into the terminal knew what
they were doing in the proper amount o wire stripped and inside the terminal.
2ou would not believe how many wires have the insulator also inside the terminal
in now making good tension to the insulation o the plug but not so good tension
on the conductors. Much less loose terminals, or over)stripped :acket removed
rom the conducts and thus rats nest o wire within a plug. 4n a -;amp plug you
should see -67< between outer :acket o cable and the plug&s ace, on a 3=amp
up to >< but no more. id they get all strands o wire into the terminal or most
with a ew hapha!ardly finging about inside the plug+ 5it happens.
9b ?hat do the crimps or errules look like i stage pin plug+ id someone use
the wrong crimp tool or a pair o pliers to smash down on a crimp that later will
let the wire pull loose+ 0s the wire even correct in 1?G or the errule or terminal
in use+ @mm, double up a -Aga wire and it equals three si!es smaller in number
or three si!es bigger in dia. 0n other words, two -Aga wires equal -91?G. @eat
wire don&t old as neatly as copper thus you might in olding it to $t within a -3)
-=ga terminal or -3ga errule old it and it&s now $ne. 4n the other hand, a -Aga
wire stuck into a -3ga or -3)-=ga opening is about useless. More oten than not,
even when using a -3ga errule, the screw will still cut into the conductor and not
support all strands equally. 0 you $nd un)sae crimps or errules in use, and theconductors are damaged it might be worth your tugging e'ort in replacing them
8/18/2019 Light Maintanence
2/14
should they ail. Most stage pin plugs use a BC)93 screw. 1s long as you get a
ring terminal with a BC stud, there is a variety o ring terminal i not fag terminal
si!es based upon the wire not only what comes with the plug. 1 -7)-Aga ring
terminal will than $t the conductors properly as opposed to a wire that&s the
wrong si!e in the wrong hole. 4n a errule, use say a -Aga insulated errule, and
sleeve the normal -3ga errule over it. 2ou than get twice as much tin over thewire and much less chance the screw will simply cut thru the errule. ?ere your
plugs even installed with the proper crimp or errule hardware, or were
conductors :ust shoved into holes or wrapped around terminals+ Tinned wire can
be ok at times, but other than that, that&s why you are inspecting. on&t accept
crap wiring.
7 Look at the strain relie. ?as it too tight in damaging the insulation around the
conductors+ @as time and wear at this fe% point damaged the insulation or
conductors in this area+ ?as too much wire stripped and the strain relie is now
bearing down directly onto conductors as opposed to the sleeving or outer :acket+ ?as it too loose in causing problems with conductors breaking or pulling
loose o terminals+ Look at how much e'ect clamping pressure o the strain relie
has had on the outer :acket and or conductors. o they have the happy medium
or one e%treme o no tension or another o too much pressure and insulation
squee!ed dangerously out o the way+
; Look at the cord. ?hat kind o condition is it in+ 1re there little snags to it&s
$berglass that might e%pand with usage that you can glue back down in
preventing raying+ lyobond and other multi)surace adhesives work well in
preventing a small nick in the $berglass rom opening up urther. Deyond this,
are there large holes in the sleeving necessitating replacement o the conductor
protection+ (iberglass sleeving is cheap, replace it when it can&t be glued tight.
1nything larger or similar in si!e to a -67< hole needs replacement or cutting the
whip down in length. E%amine the conductors themselves at such holes. 0 *()3
with a $berglass braid over it, it might be rayed some but sae, on the other
hand it can also hide a scratch that e%poses conductors under the silicone
insulation. 0 other than $berglass braided conductors under a $berglass outer
sleeve, e%amine them also or what condition they are in. 4n the cord oten non)
braided heat wire will last longer, in the $%ture and near heat source, the
$berglass braided heat wire will oten be superior in heat refection. Dalance your
usage o a heat wire by what&s provided verses what you $nd most easy to use. 2ou are not allowed to have a splice within a whip. 1ny $%tures having splices
within the whip need replacement. @igh Temperature (iberglass Electrical tape
can at times work wonders or quick repairs to whips or work well in strain relies,
but should only be used i absolutely necessary to do a repair to conductors as a
temporary $%. Electrical tape is not rated or high temperature use nor advised
or use on a $%ture either conductor or sleeve to it. 0n most cases the *i!e B=
sleeve is the proper one to be using. 0s the sleeving in place too big, or plastic+
0 other than $berglass sleeved cord, you have some that are heat rated and
some that are not. 0n the good stu' ) at least FE that&s somewhat heat rated 0think to -;=c, or better stu' that will have a 3== or 3;=c rating to it stamped on
8/18/2019 Light Maintanence
3/14
the cable, have a look at it&s :acket and condition o the cable in general. 1t the
moment 0&m having some suppliers con$rm that their heat wire such as Tempfe%
or "ockbestos is water, oil 5og fuid and F rated or e%terior use. 4ten you will
$nd that heat wire cables ) in a rubber6silicone sleeve especially Euro FE types
will break down due to oil. amage to the outer sleeved cable than should be
e%amined or cuts and punctures as above and replaced as above. @eat in thecord touching a $%ture and other water, oil, and F can break down a cable in
making it unsae. F, oil and water can also break down a $berglass outer
sleeve.
Thermoplastic *HT wire is especially bad where oil rom og gets concerned.
1ma!ing how a little ();= fuid will break down a *HT cable. Much less, even i
I=c instead o J;c, it does not like to touch a hot lighting $%ture without serious
danger rom now e%posed conductors now touching the $%ture. *tage and *tudio
much less movie lights don&t use such cable ) probably not in the L listing or
application ) it&s :ust the cheap H club lights and 1" cans used or rock showsthat use the wire. #hecking with your local building authority on the KE# use o
such $%tures when powered by such cords might be a good idea. Even i a
actory aluminum 1" can, you might not be able to use the normal cord eeding
it on stage i they put any thought into the code. *o as with other ma:or or minor
pro:ects you might need to replace all $%ture cords o one type or another. 0 0
touch a $%ture, it&s really rare 0 will re)install a *HT cable on it unless really low
wattage thus heat.
Kot all brands o heat $%ture cable 5having inner conductors and outer :acket as
one assembly is created equal. 1ll will work to replace $berglass sleeved
conductors as long as you can attach them within the $%ture. ?hile Euro cable )
Tempfe% and ro #able amongst others might be rated or 3==# also, but it&s
insulation is poured around the conductors. 4ten a cut or nick in the outer :acket
than once fe%ed will go all the way down to the conductor. This as opposed to a
more *H seeming 1merican type o cable such as "ockbestos that has a separate
outer :acket with $ller material surrounding the inner conductors. "ockbestos or
heat wire cables is by ar superior. 1ltman and electrical suppliers can get it.
General distributors or gear more sell the Euro cable heat wire 0 less recommend
or use even i cheap and rated or the same temperature.
There is 3;=c wire, -;=c wire and 3==c wire. -;=c wire or other than use as aground is not recommended in line other than 1" $%tures :ust as a I=c *H or *HT
cable oten won&t be o much use. De cautious about $%tures wired by way o
e%tension cords, oten they are going to need a lot o work. (or the most part,
stick to the 3==c rated conductors, be it *()3 silicone $berglass sleeved or not,
or a 3==c rated three conductor cable. 3;=c #able while rated or a higher
temperature also most oten has less fe%ibility to it&s conductors and individual
strands o wire. 0n other words, while you can stick it in an oven and it won&t
melt down, day to day use and fe%ing on the other hand might break down the
conductors. 0nside a $%ture ) especially a Mole Light or 1udience Dlinder type
$%ture and other $%tures o very high temperature, you can&t do better, but as a$%ture whip you can. 3;=c wire is most oten Tefon instead o silicone and when
8/18/2019 Light Maintanence
4/14
available as a cable it will have a sort o varnished $berglass sleeving over the
cable. Good stu' or permanent install, :ust don&t bend it with constant use.
o not be overly concerned i your heat wire seems less in 1?G rating than that
o a normal e%tension cord. ?hat are these 3,===w (resnels doing using -769
wire on them+ @eat wire by it&s nature will be a little less e'ected by heat inamperage rating due to it&s higher working temperature. 0 that&s what the
manuacturer speci$es to use, it&s use is correct. 4n the other hand, some
lighting $%tures such as the ;J;w version o the ET# $%ture came with -Cga
wire. 4nce they came out with the J;=w version, the -Cga wire was insu8cient
or the wattage. 2ou must in using a ET# $%ture at J;=w be using the proper
conductor si!e. ?hile or all other intensive purposes the $%ture is one in the
same and on the really old versions you can get rid o the alignment nubs
speci$c to the ;J; $%ture in installing a J;= cap on it, you must change the
conductors. *ome heat wire you can use or over it&s thought to be e%pected
amperage, others you don&t want to be using. "ead and ollow the $%tureinstruction manual and guides on them.
@ave 0 mentioned the use o an e%ploded pictorial o each $%ture you are to work
on in being useul+ Go to the website and pull up the assembly drawings. This
will both save time should you have to pull a $%ture apart in re)assembly, and
help you to know when someone did a other than actory improvement to it.
2ou should have a three ring binder in the service area o the instruction manual
and e%ploded pictorial on all $%tures in use.
A @ave a look at where the cord now enters the lighting $%ture. That&s another
fe% point that oten will wear out both or outer :acket6sleeve and inner
conductors. Deyond that what type o strain relie is in use+ 0s it a two screw
strain relie that oten cuts into the conductors, a nylon strain relie that becomes
brittle and has too small o a cross section in rubber water tight strain relie to
take heat well without becoming brittle or a metal one that&s more substantial in
taking heat better but can still slip or allow the cable to slide ree. 1 @eyco nylon
strain relie oten will need to be replaced. 1 two screw strain relie i cutting into
the conductors or sleeving might require you to replace the whip. (iberglass heat
tape will be a good abrasion and fe% resistant $% to such strain relies. 4therwiseproperly si!ed nylon tubing while it&s hot will oten last well in a $%ture in limiting
the fe% and clamping pressure. 4n a nylon strain relie you will oten $nd that i
the nylon shrunk, became brittle and cut or moved, the little nylon $ngers than
clamp directly onto the cable and it than is dangerous. The tape will also help in
this area.
J The strain relie itsel, is it loose+ Especially with plastic strain relies, they
come loose. 1 loose strain relie than will allow conductors to twist, move and
pull ree. That&s a bad thing, the conductors should not move about within the
$%ture other than where needed while ocusing the lamp. Get the strain relie
tight by hook or by crook 5rivet or other method, and when e%posed, add hightemperature Thread Locker to it to keep it there.
8/18/2019 Light Maintanence
5/14
C (ollow the wire rom strain relie to lamp base within the $%ture. ?here
e%posed such as in a lamp cap, have a good look at it to ensure the conductors
don&t stretch or overly touch anything such as screws or anything else that can
cause bad cooling around it or pull tighter as the $%ture gets ad:usted. 0t&s
common conductors will pull some with use, make sure that you both have slack,
yet they don&t touch what they should not in having too much slack. 0 you can&tget e%posed wire in direct sight, use the fash light and mirror as necessary.
0nspect every inch o the wire. This especially near the lamp base as it&s the
most concentrated source o heat and oten where the wire will start to ail. 4ten
in a $%ture you will see $berglass sleeving called spaghetti tubing over the
conductors. That&s a good thing both to protect rom wear on things it might rub
up against, and shield some against the heat. 0 nothing else, where cord enters
lamp base, a sleeved wire should it ail than has the e%tra layer o protection.
That&s also the general concept o $berglass outer sleeved silicone wire as
$%ture whip. *hould you be replacing whips or doing work in them, sleeving the
conductors i not the high temperature tape is oten useul.
I *ome $%tures such as a 1" can will oten have a splice inside the lamp cap
that goes rom heat wire o' the lamp base, to what ever type o cord is used.
4ther stage and studio cans will :ust use longer leads in a $berglass sleeve ) a
better idea. 4ther $%tures will have au%iliary gutters mounted to the $%ture that
are slightly cooler to house things like switches, circuit breakers or uses, i not
:ust patch the wires.
4ten the splice will be $ne, other times it can use improvement to it ) even i
actory. Hust opened up a 1ltman #M outdoor par today. 0t had 3==c wire coming
o' the lamp base, 3;=c cord o' the $%ture, and I=c household grade wire nuts
binding the conductors. The $%ture itsel in only being -;=w arc source can get
hot still in it being an arc source, but the wiring cavity where the wire nuts were
in use were separated rom the heat both by way o refector and secondary
plate covering this cavity. 0 was less concerned about heat ) though questioning
the use o vinyl wire nuts, and more worried about the wire nut coming loose as
oten wire nuts will due to vibration or :ust use.
o not allow standard wire nuts even in such a $%ture. Kylon, Finyl and F# all
have the same sae operating temperature so don&t be ooled by nylon splices
either in being better. rimary di'erence is the other two melt in e%posing theconductor, nylon :ust becomes brittle and as a secondary thing needs to break
away beore it also e%poses conductors. My choice in this instance where heat is
less a actor will have been to use something nylon.
*peci$cally 0 will have used nylon cap splices that are like a wire nut, but you use
a crimp tool to crimp the thing into place so it won&t come loose in e%posing the
conductors or letting them pull ree. 4therwise there is lots o high temperature
wire nut solutions that either can be hi)temp tapped so they can&t pull loose, or
have internal set screws over high temperature plastic outer coverings. epends
upon the application.
8/18/2019 Light Maintanence
6/14
?hile a splice within a $%ture is preerable to within the cord, it short o having it
&s own area is oten dangerous. Look at rock and roll par cans. There is a good
reason why the spin the bottle hole is oten capped o' or there is a knob to do so
now. Most o it comes rom the splice method and cable. 0n the past this was
made especially hard since oten you needed the same 1" can to run 1#L in
series, "ay Light with wire leads eeding it, and 1" #an lamp with it&s MogulE%tended End rong base. M4E or GN)-Ad. Given you had to switch, easy to
remove methods rom spade terminals to using the wire nuts has been done in
the past. Kow 0 high temperature splice and high temperature water proo heat
shrink tubing over the crimp terminal i not replace the whip. Ensure that
especially i *HT cable or lower rated cable, that the $%ture whip is not touching
the lamp or metal components within the $%ture. 1ir is the key.
0 you have a splice within the $%ture, note the conductors going into it to see i
e%posed conductors are alling out o the splice or i it all looks neat and trim
with the insulation stopping shortly beore the crimp or turned area but de$antlynot e%posed. 1re conductors able to pull out o the splice, are there strands o
wire not quite going all the way in, is the $berglass sleeving becoming loose+
Lots o other details you will note up to and including a strand o wire melting
thru the wire nut. o not use vinyl wire nuts within $%tures )replace them i you
see them or they will work loose and allow a short. Ko matter the conductors,
don&t use something that can come loose. 1nother type o splice is the push in
terminator6tap splice. *uch things work well with solid wire, but it&s oot grip
otherwise will cut thru stranded wire. 0 you have stranded wire going into a push
in to grip type o $tting such as used on some stereo equipment speakers,
replace it as it&s not dependable. ?here possible cable tie in a par can wherethere is a lot o cooling vents, or use $berglass E)tape to band the wire together.
This will take up most o the strain relie rom the splice, make or a neat splice
and prevent the conductors rom moving where they need to be spliced. Oeep
the tape6cable tie away rom the splice so you can see into the splice. 4therwise
when you hide the splice by way o tape, it makes those later seeing it suspicious
as to what shotty work you are trying to cover up such as too much stripped
insulation o' conductors e%posed.
1nother type o splice would be the butt splice. @igh temperature butt splices as
long as covered in at least three layers o high temperature tape, or in the case
o a par can ) high temperature heat shrink that&s water resistant is an option.1lways use the correct splicing tools and give a good tug on your wires ater
splicing them to ensure you have a good splice.
-= #heck the ground. Ground conductors can be using lower temperature wire
in that they don&t touch the heat source directly, and one would preer to note a
melted ground as a warning sign or the rest o the $%ture, than have something
else ail in melt down. They oten will also be a lower gauge o wire in some
belie that the current fow temporally in overload thru them will be su8ciently
8/18/2019 Light Maintanence
7/14
able. That&s a actory consideration. ?hen replacing a ground wire, use the same
gauge o wire as the conductors.
1 melted ground wire, or e%posed crimp to it is not a bad thing in all cases. 2ou
don&t want such a thing where it can touch terminals, but the idea o a ground is
that a hot will touch it or the rame $rst anyway so why insulate it+ 1rchitecturallighting $%tures oten won&t use a insulated ground wire. 0nsulate where possible
but don&t be overly interested in over insulation o it as opposed to a conductor.
#heck it&s crimp terminal. 0 it&s all burned up, use a high temperature crimp
terminal instead. 0n general, use high temperature crimps and splices anywhere
inside the lamp base area. "eplace where o%idi!ed and corroded ) you want a
good ground path.
-- #heck the mounting o the ground. That wire should not be able to move
about or twist because this also means a less than sae connection. 4n a 1"
can, that riveted ground will oten work it&s way loose. *ame story on a real$%ture. The ground will oten come loose no matter i rivited or screwed. 2ou
cannot use Lock Tight or Thread Locker on conducting screws thus it won&t work
here ) it needs to be all mechanical. 0n the same respect you also should not be
using nylock nuts. Think about nylon verses heat ) a nylock nut inside a lighting
$%ture oten won&t hold tight in the long run. 0 necessary you can re)pound a
rivet back to tight as a temporary $%, but otherwise need to replace it or better
yet go with a screw.
1lways a lock washer. Dut instead o the spring lock washer types, use a internal
or e%ternal lock washer or better gripping o the conductor. 2ou can use lockwashers with rivets. This especially i what you are grounding to is painted. aint
don&t conduct well thus some orm o displacement o material lock washer
between crimp terminal and paint surace can be useul in it both preventing the
terminal rom moving about and in digging into bare metal.
1 good lock washer and nut will work at times better than a nylock nut. Try to
avoid washers where your ring termials are concerned. They :ust act as a pivot
easing surace in urther loosening up the :oint. 1 e%ternal tooth lock washer will
both unction as a washer and prevent it rom coming loose. Deyond this, a
toplock nut will both take the heat in mechanically being hard to loosen and add
to the resistance o the nut coming loose.
-3 Look at the lamp base where the wire goes into it. 0s the wire showing heat
damage+ 1re the screws i used to mount wire to lamp base loose+ o they have
a lock washer+ 1re lock washer and screw brass or bron!e+ 1 belleville or cone
washer will otherwise be acceptable as long as the same metal. *teel tends to
corrode and stainless has at times problems with touching other metals such as
brass and bron!e in otherwise causing corrosion problems. Pinc plated steel once
in a lamp base will corrode very easily ) avoid it&s use. 4n a lamp base, a
brass6bron!e and perhaps only as one o the two in nickel plating will su8ce. 1re
the crimp terminals showing heat problems such as corroding+ "eplace in thatcase with high temperature terminals and insulate them as needed with high
8/18/2019 Light Maintanence
8/14
temp. tape and tubing. Kothing other than the ring should be esposed. 0 (resnel
or Medium re)ocus 5)3Cs base, there should be an insulator between lamp
base and it&s mount. 0s it in good condition or all brittle and burned up+ @ave the
conductors ailed in getting too hot+ E%posed corroded conductors coming o' the
lamp base+ This can be because o loose screws or other arching sources, or :ust
heat in general. #ut and replace as needed. se spaghetti tubing and a smallamount o tape as necessary.
-9 Look at the lamp base mounts. 1re they tight+ 1s above in using lock
washers and i needed high temperature Thread Locker will also help. Most
important is the metal type. 1gain brass and bron!e in taking heat well,
otherwise stainless steel in also taking heat well i not better ) :ust not
conducting as well. Even on a 1" can lamp base, how about that screw holding
the plates together in it&s being tight+ *hould your wire eed into a hole in the
base mounting plate, what kind o condition is it in and is that hole a sharp edge+
Tape, a silicone panel washer or something to make it work better+ 4n otherlamp bases such as mogul screw or medium pre)ocus internally, be it rivet or
screw are they tight+ *ome are designed to have a bit o movement, study the
type o lamp base or what&s best but don&t accept loose where not appropriate.
-7 "emove the lamp and inspect its& contacts. 1re they actory or arched and
corroded+ 1re they nickel plated as per new or or the most part clean but
blue6black+ ?hat the lamp when it&s taken out as need be with a pry bar says
about itsel, it also says about the lamp base in contact with it. Gold plating is
great, but also melts down. 4therwise nickel plating is normal. E%amine any
center point contact plates also. ?hile a screw base to a 1)lamp6household lamp
might be nice and neat, oten that center contact ) that should be the hot will get
really unky. 0s it a smooth surace without bumps and divots rom welding+
Especially bad will be "*# 5")Js lamp base types that have a sort o cone
contact on each end o the lamp. They :ust don&t conduct well in tension and
surace area to conduct with. *urace area ) clean surace area is the key to
conduction. Dlackened and arched lamps in base will have less path o least
resistance to conduct with meaning lots o heat and e%tra heat at those points
that conduct better. 2ou can clean lamp base contacts but that&s a separate
discussion.
"e)install i in good shape the lamp. 4n a 1", can you physically lit the lamp byit&s base, or does it :ust all out+ 4ther lamps and bases will have similar
relationships rom bi)pin to "*#. 0 that lamp easily gets removed, one bounce
while installing or transporting it will also allow the lamp to become disengaged
rom the base. *uch loose contact will also be a source or e%tra heat as the
current tries to fow but has less than optimum tension. Take the lamp back out.
-; look at the lamp in general. *ome types will have porcelain around the pinch
area. *ome will even have a layer o silica sand between pinch and porcelain.
That silica sand with a crack allowing it to run right out o the lamp base than is a
bad thing. 0n other lamps, perhaps i the two part porcelain is loose such as in a
8/18/2019 Light Maintanence
9/14
;Ow 2 or larger lamp, perhaps more support such as a stainless steel hose
clamp will be necessary to keep the two piece lamp base together.
Look at the lamp itsel. *ee any white $nger prints or buldges+ Much less look at
the lamp $lament and it&s supports. Lamps are another discussion as to what
you in inspection can live with or need to note in replacing. #lean the lamp withde)natured alcohol and a lint ree cloth ater looking at it. *uch alcohol will also
let you e%amine the $lament o a outside rost lamp such as in the case o a (#M
cyc light double ended "*# lamp. 1s long as you are able to look thru the
rosting to the glass, you might as well look at the $lament.
-A ?hile the pins o the lamp, and the lamp in the base tension is important to
note, during a real inspection you need to pull out the fashlight and inspection
mirror. 2ou are e%amining the $%ture, so why stop when it&s something you can&t
easily see+ Granted a G)7 up thru G)I.; base such as a (LO6(EL will use will be
hard to see the sockets, but give it a shot. *ome types o base are servicable
5again as a separate discussion others once they show wear such as blackening.
Lack o tension and pitting need replacement. 1lso throw out the lamp unless it
can be saved with work. *ome older versions o (resnel lamp bases allowed the
center contact to un)screw some. *hould it not provide correct tension, you could
screw out a little more to some e%tent in making it a tighter $t within the socket.
Most modern bases won&t do this. 1 edison lamp base on the other hand has a
center contact that i not providing su8cient contact can be bent outbound to
provide more spring to the contact point. @ave a look or arching or discoloring at
a speci$c place on the lamp base ) this will tell you where the lamp to base
either makes it&s only contact or no contact. ?here possible to service you lamp
bases it can be done, otherwise at very least a cleaning with perhaps a thinned
out cue tip and some carburetor cleaner will work wonders in removing carbon
build up and o%idation. 0mportant to note is that once you have a bu'ed and
serviced surace, or at least one that&s chemically clean, you need to coat the
now bare metal or it will o%idi!e worse than i you had not touched it. There is
various de)o%idants and coatings on the market discussed elsewhere also.
-J Electrically now your $%ture should be in sae condition. There are potential
other notes 0 orget in general or that the manuacturer might state. *peci$c
$%tures also have certain details about them. Mark your $%ture in some way with
the date and your name. erhaps grease pencil or marker inside the lamp cap orsomething. That&s a good tracking and quality control type o thing.
-C (i%ture itsel. (ollow the manuacturers instructions or how to clean the lens
and refector much less bench ocus it. There will be di'erences in style
dependant upon the brand and type. *uch things also have already been
discussed.
-I Dlow air into and all around your $%ture with the lamp removed beore you
clean refector6lens. #lean the $%ture with ?inde% or other non)residue
chemicals. 4therwise give it a second alcohol cleaning to remove the residue.
Kote that resh rags are a good thing. Look or rust. "eplacement o bolts,tapping and oiling with a oil rated or the temperature i not tightening them and
8/18/2019 Light Maintanence
10/14
using thread locker will be needed now. aint as needed the $%ture now that it&s
disassembled or the most part. De careul with some o the screws that are
stuck. (or many o them they will break or strip beore coming loose. 0n cases like
that, you have to replace them to the best e%tent possible. (rom gel rame clip
that comes loose or un)welded to lamp base knob that does not screw in easily,
now is the time to check each part and $% them.
3= @ave a look at other pivot and working parts such as the yoke mount. 1re it
&s screws6rivets tight or loose+ 0s the locking dog or clutch in good shape and not
broken or loose+ "eplace especially the yoke mounts now as opposed to later.
Most will use ;6-A< grade 3 screws. These oten rust with heat and moisture.
Detter ones are availiable. The area o the yoke is oten what needs replacement.
2our $%ture should not slip out o it&s ocus even when locked into position
without dogging down. 0 it slips, there is a cause. #an be as simple as turning
the carriage bolt on the clutch mechanism I= degrees or it could be something
stripped, broken or loose. @ave a look at the non)clutch side o the $%ture. 0s itstripped+ 0 all such as on a par can that side is attached to is a aluminum plate,
it&s easy to strip this out. erhaps a longer screw with side lock nut to prevent it
rom coming loose ) but not so tight it gets in the way might be o value. *uch a
nut might also be o use on the knob side o the yoke. "emember the alling
ollow spot issue. 0 you can&t remove the screw, it won&t all. 4ten on a 1"
can, the screw will come with a nut on the inside o the can. 4ten given this a
nylon locking nylock nut. Great idea in preventing the screw rom coming loose,
bad idea on the nut type, much less given you can&t see the nylon not ailing
how do you know it&s still there+ 4n a 1" can, what i you were to eed the
screw rom the inside o the $%ture and put the nut ) even i nylock now that it&sless in the path o the light, on the outside o the $%ture+ 1t that point a missing
nut hopeully is noted.
3- @ave a look at the lens train or ocus operation. oes it&s rails or slot need
tefon oil, white lithium grease or spray on graphite ater removing any rust+ @ow
does the lens train move about+ 0s it easy and smooth, or do you have to kick it
to get moving+ (irst sand the lens train with say -== up to A== grit paper, than
as needed add the spray on graphite coating and wipe o' the e%tra. 2ou will be
surprised as to how well it works than.
33 #heck to ensure your lenses are clean and not chipped in any way that wille'ect the output. 1re they green or blue+ 1re they the same type o lens as the
other $%tures, much less in the correct mounting holes+ #lean the lenses say in a
dish washer amongst other debated solutions. 1lso make sure that the proper
lenses are both in the proper order in the lens train as there can be more than
one si!e in one lens train. Much less at times lenses while or the same $%ture
can have been upgraded to a wider but thinner lens. Make sure that i you are
buying new lenses that you state how old your equipment is.
39 2ou have drawings, look or the missing parts rom a cone washer replaced
by a lock washer to a $ber washer not used at all. #heck the condition o the
parts on the $%ture. Look also hard or loose and missing asteners i not cracks
8/18/2019 Light Maintanence
11/14
in the rame. 1 crack in the gel rame casting can be a bad thing. 1 crack
elsewhere might be acceptable.
37 *hould this $%ture have an iris, what kind o shape is it in+ erhaps crocus
cloth and graphite will help it, or do some o its leas need replacement+ There
are only a ew di'erent types o iris leas and they are interchangeable or themost part other than i one o the three. 1 Lycian M3 ollow spot lea is the same
lea as used on a 1ltman 9.;Q; $%ture. 4k, such a iris base $%ture does not e%ist
but 0 own one. *o i you have a bunch o burning up iris units, perhaps you can
buy one and change out what leas are needed, than clean the rest. 1 iris
burning up in one area more than another means a badly centered lamp but it&s
too late now.
3; *ame with the shutters, as long as they are not bending inward, you can to
some e%tent sand with very $ne sand paper, i not even grind a new smooth
edge on them that&s :ust slightly shorter in re)using them as long as they are fat
and smooth. This is a very speci$c technique 0 will inrequently use but or the
most part replacement shutters are not that e%pensive. 1s with the iris, what is
most important is a smooth fat edge to the surace. 0 it has even a ding in that
edge, that&s where heat will concentrate in making that shutter ail. *hould be a
given that i you have to have a shutter in more than say 7=R rom one side,
that perhaps you should re)ocus the instrument, but what ever the case, look or
heat damage because not everyone thinks. *ome you can save and graphite,
others you need to replace. Each brand has a di'erent means o getting at the
gate6shutter assembly. Much less or instance on the 1ltman 9A=q series, it&s one
o three types o round washer like handle and a speci$c rivet. se the wrong
rivet and you might wreck that washer.
3A #heck the refector, gate and other parts o the refector assembly or rust in
mounting or plate or rust on screws. *hould the $%ture get wet, that rust will
seep onto suraces and destroy them urther. These ater the lamp base and wire
will be ne%t to get hottest. 0 you blow out your $%ture and get a shower o
micron si!ed silver conetti, you know that you have a dichroic coating on the
refector that&s peeled up. 1s said, ollow directions in cleaning refector and
lenses. se the wrong cleaning method even on a 1l!ak aluminum refector and
you can destroy it. 4n a ; or -= degree Leko&s plastic lens, that glass cleaner
might :ust scratch it worse than :ust using alcohol on it to wipe o' the dust. 4nthe other hand or say the inside o a scoop, perhaps a resh coat o high)heat
refective or white paint will do it wonders when not so nice in $nish.
3J (i%ture or the most part is done in a thorough inspection. 2ou don&t have to
$eld strip the $%ture, but checking as much as possible even with one&s $ngers
to veriy tension is o use. 4bserve everything, than re)assemble, turn it on and
bench ocus. "emember that hot patching is a bad thing. 0nstall a in)line switch
instead when protected by a G(#0 outlet. i'erent methods or the bench ocus
and another debate.
3C #heck the saety cable. There should be no rust, much less that snap hookneeds to snap shut. 0 it does not perhaps a bit o oil will make it do so, but don&t
8/18/2019 Light Maintanence
12/14
spend too much time in making it snap. #ut up and replace saety cables that
don&t snap closed. "eplace snap hooks also that don&t close properly or that
have broken teeth to them. There is a debate urther in i it&s permissible to bend
a saety cable&s loop to $t thru a >< hole in the $%ture. *uch a bend than
becomes a weak point in the wire rope, but given the distance o all, it&s
probably not un)sae enough. Hudge or yoursel and look or broken strands orseriously damaged bends or wire rope in general.
3I The clamp is oten neglected. ?hy do actory send a >)-9 grade 3 screw
that&s only 967< long with the $%ture+ @mm, loose -6C< worth o lock washer, and
another -6C< worth o yoke and that&s only >< worth o thread within the #)
#lamp. Kot enough nor a strong enough screw in my opinion. Even i J6C< or -
8/18/2019 Light Maintanence
13/14
clamp to the pipe, they will deorm the tip o the bolt. ?hen you try to remove it
rom the clamp, the bolt oten is harder than the cast iron o the clamp and it&s
removal will destroy the threads o the clamp. That&s unsae. *hould you have a
damaged tip, re)tap, or cut it&s tip o' than re)tap. Then e%tract it. *hould it be a
bent bolt, cut it o' at the bend and remove what you can near where it e%its the
clamp. 1ttempting to remove a bent screw rom the clamp otherwise will alsostrip out the clamp. "eplace with the same brand o set screw.
0n assuming a #)#lamp, the technology o the casting has improved much over
past years. They still are not perect. 0 your clamp no matter i bent steel, cast
iron or stamped or cast aluminum shows any sign o bending, replace the clamp.
o not allow in service a bent clamp. ?hile more requent that it will bend
instead o break, you still don&t want to continue using it or it potentially will
break.
De watchul o stock looking cast #)#lamps that have a sort o pint6varnish
coating on them. They do not come rom any manuacturer and instead rom
china. *uch clamps that have this seeming varnish coating are using much
cheaper metal in the casting and need that e%tra coating to prevent the rust.
*uch clamps with the cheaper metal will break and strip -=% aster than anything
a name brand even 7= years ago was making. 0t&s also something that should it
get hit might ail instantly at any point. @ave a look at the clamp or hair line
cracks, but with these cheap #)clamps you might never see the hair line clamp.
o not use some o' shore other than name brand clamp. Ko name on the clamp,
varnish like coating to it, toss it in the trash.
*uch clamps came on the market say -= or -; years ago and only lasted a ewyears by way o the theater supply market looking or a cheap alternative. 0
doubt they are still available, but thousands have been sold over the years. De
watchul o such things.
9= #E verses L $%tures. De mindul o the world economy. 1t one point we had
a delivery o a hundred or more *)7 1" $%tures come in on a rush order. They
were all metric we ound out later. 4ver -,7== *)7 1" $%tures in stock, and
other than some sold o' and replaced over the years, the metric *)7 1" still
shows up in the inventory at a constant basis. *ubstitute a M )7 or a -=)93 screw
and you have serious problems. Take the clamp o' and try to install it on another$%ture and you now have a standard >< screw $tting into a metric clamp. "ock
and roll aluminum 1" cans and their clamps are phenomenal in having any
number o three ) yes three types o hardware in them. Metric, *tandard and old
English *tandard. Think back to the history o #hina and the orient. 0 industry
was set up during the turn o the century, they in being backwards but catching
up might still be using some say antiquated >< but -3 instead o -9 threads per
inch screws. Think about the possibilities o such hardware getting into your own
inventory. ?hile you can or the most part i you know your asteners tell the
di'erence oten between a metric and standard piece o hardware ) or instance
the black o%ide type asteners when metric will have a sort o gloss coating to
them, once you get something that is imperial but the wrong thread in being
8/18/2019 Light Maintanence
14/14
very close into your system you are screwed. 4r or us the shop manager that
made the choice to not instantly toss out all that hardware screwed us. 1 bolt
might be a bolt in saving money, but once it&s mi%ed in with other bolts you are
screwed. Many metric asteners will be very close in threading to that o a
standard thread. Hust a wee bit loose or tighter than normal. De very careul
these days and get your theater to purchase screw thread plates to test themwith.
Deyond this, should you get a $%ture that is metric, take a engraving tool and
write metric across it&s body so those looking to SBC33=$%SBC33- it don&t
make it worse. De very careul about the hardware that is on the clamp or
$%ture. Fery easy to screw up and ruin your world.
1 simple, thirty step process anyone can do in his6her own theatre.