Upload
others
View
3
Download
0
Embed Size (px)
Citation preview
LIFE SAFETY CODE ESSENTIALS
PRESENTED BY: LARRY VIGIL, RISK CONSULTANT
INTRODUCTION 2007-11 5,690 Structure fires
75 Civilian Deaths
$83 Million Direct Property Damage
71% in Nursery, Elementary, Middle or High Schools
Peak times week days, 8:00 am to 4:00 pm
49% Intentionally Set
LEADING CAUSES Cooking Equipment
Intentional Acts
Inappropriate Use of Heat Sources
ITEM 1ST IGNITED Cooking Materials
Trash or Rubbish
Magazine, Newspaper or Writing Paper
Most of These Confined to Room of Origin
NFPA 101 LIFE SAFETY CODE
Most Widely Used For Fire Protection Strategies
Requirements for: Egress Fire Protection Emergency Lighting Smoke Barriers Special Hazard Protections
LIFE SAFETY CODE PURPOSE Provide Minimum Requirements Regarding:
Design
Maintenance
Operation
Group E - Educational Group B - Business Group A-3 – Assembly
Community or Exhibition Halls Gymnasiums (without seating) Indoor Swimming Pools (without seating) Indoor Tennis Courts (without seating) Lecture Halls Libraries
K-12 Facilities
OCCUPANCY- K-12 FACILITIES
Group A-4 – Assembly – Arenas (with seating) – Swimming Pool (with seating) – Tennis Courts (with seating)
Group A-5 – Assembly – Bleachers – Grandstands – Stadiums
Assembly with seats Shall be determined by number
of seats
Assembly without seats Concentrated - chairs not fixed–
7 net Unconcentrated - tables and
chairs– 15 net
Educational Classroom – 20 net Shops/ Vocational room – 50 net
Means of Egress
OCCUPANCY- MEANS OF EGRESS
Rooms greater than 1000sf have two exits.
Travel distance exceed 150 feet non-sprinkled, exceed 200 feet sprinkled building.
Exist corridors minimum of 6 feet wide.
Spaces serving 100 or more have panic exit hardware.
Checklist
EGRESS- CHECKLIST
Among the requirements of NFPA 101: lighting of means of egress under normal conditions must be maintained at a
minimum of one foot-candle along the entire path;
emergency illumination must be provided for a period of 1.5 hours in the event of the interruption or failure of normal lighting;
emergency lighting must provide at least an average of one foot-candle and a minimum of 0.1 foot-candle measured along the path of egress at floor level;
a functional test must be done on every battery-powered emergency lighting system every 30 days for a minimum of 30 seconds, and once a year for 1.5 hours’ duration;
means of egress must be clearly marked, with directional exit signs along the paths of egress and exit doors, doors into stairway enclosures, etc. clearly marked; and
exit signs must be illuminated, either internally or externally.
Exit Lights
EGRESS- EXIT LIGHTS
EGRESS- RELIABILITY Width – 36 to 44 inch minimum
Exit corridors minimum of 6 feet wide
Dead End Corridors no more than 20 feet in length.
Free of Obstructions or Impediments
No Furnishings or Decorations in Means of Egress
Do Not Prop Open Fire Doors
FIRE DOORS Openings And Surrounding Areas Kept Clear
Blocking or Wedging of Doors Prohibited
Maintenance Of Closing Mechanisms Annual Testing Written Records
DECORATIONS ON FIRE DOORS Signage- Informational Not To Exceed 5%
Use Adhesive
Not on Glazing
Do Not Impair or Interfere with Operation
CLASSROOM DECORATIONS Not To Exceed 20% Non-sprinklered, 50%
Sprinklered
Curtains, Draperies Flame Retardant Treated
Clothing Personal Effects Should Not be Stored in Hallways
No Combustibles from Ceiling
COMMUNICATING TO STAFF
COMMUNICATING TO STAFF Fire Drills
Daily Inspections of Exits
Awareness Of Location Of Fire Protection, Alarm Pulls
Emergency Evacuation Maps in ALL Rooms
Everyone Participates in Drills
COMMUNICATING TO STAFF Emphasis on Order During Drills
Identify Individuals with Special Needs
Rosters to Ensure Accounting
Drills During Expected and Unexpected Times and Varying Conditions
Drills are a Model for Students
18