Special featureS
LIFESPAN INSTALLATION WEIGHT
EcO-FrIENdLy
INSTALLATION SPAcE
OPErATING TEMPErATUrE
Lead Acid LIB
3~7years guarantee
15years guarantee
Lead Acid LIB Lead Acid LIB
Temp. / Impedanceprimary sensing capability
Analysis / Forecast Protection Capability
No hazardous materials used
Lead Acid LIBLead Acid LIB
No additional cooling need
20~25°C -20~65°C
100%
50%
-50% 40%-60%100%
LI-ION BATTEry UPS SOLUTION
Air conditioning systems account for approximately 40% of a data center’s total energy consumption and the broad oper-ating temperature of Samsung SDI Li-ion battery technology helps reduce operating costs by curbing the use of air condi-tioning in battery rooms.
Furthermore, lithium ion batteries offer significant advantages in weight and energy density over lead acid batteries which translates to lower real estate needs and higher white space. Along with Battery Management System, Samsung SDI offers real-time monitoring and control of the system’s functions such as state of charge and health.
Mission critical UPS solutions for green data centers, buildings, and plants
BMS(Battery Management System)
Standard rack Specification
* SDI's LIB system can be easily expanded by adding racks in parallel series* The rack is subject to structural change depending on the UPS specification
Battery ManageMent SySteM
• System voltage, current, SOC, SOH• Cell voltage, current, temperature• Warning / Fault report
• Easy maintenance • Operation cost reduction
rEAL-TIME BATTEry INFOrMATION dIrEcTLy AccESSIBLE By THE USEr
SySteM configuration
cell Module rack System
Prismatic 40Ah / 60Ah 8 cells in series (29.6V) N modules in series N racks in parallel
148Wh / 222Wh 1.2kWh / 1.8kWh ~ 30.8kWh / ~ 46.2kWh > 21.3kWh
SaMSung Sdi co., ltd. 150-20 Gongse-ro, Giheung-gu,Yongin-si, Gyeonggi-do, 446-577, South Korea www.samsungsdi.co.kr
eMail contact
Dealer Information Box
Shelf Type ('15.04 release)
“Lower initial cost”“Less installation space”
capacity kWh 23.1 32.0 35.5
N modules in Series ea 13 18 20
capacity kWh 23.1 32.0 35.5
W mm 600 600 600
L mm 730 730 750
H mm 1,600 2,000 2,350
Weight kg 460 560 650
certificate UL1642 (Cell), UL1973 (Module), UN38.3 (Module), Seismic (Rack), IEC 61000-6-2 / 4 (Rack)