LG Multi V VRF for Middle East Market

Embed Size (px)

Citation preview

  • 8/10/2019 LG Multi V VRF for Middle East Market

    1/86

    LG ElectronicsAE Company, Commercial Air ConditioningTwo IFC, 10 Gukjegeumyung-ro, Yeongdeungpo-gu, Seoul150-945

    www.lg.com www.lgeaircon.com

    Copyright 2014 LG Electronics. All rights reserved.

    Distributed by

    LG HVAC SOLUTION

    Tropical

  • 8/10/2019 LG Multi V VRF for Middle East Market

    2/86

    Vitalizing every environment is the ultimate goal of LG Air

    Conditioning and Energy Solution company. It is a vision to

    provide great vitality to everyone, everywhere on the globe

    from consumers private residences to commercial buildingsand shared communal spaces. Under this unied goal, the

    company is committed to providing highly innovative heating,

    ventilation and air conditioning (HVAC) solutions, offering

    building users completely pleasant environments while using

    less energy.

    In the last few years, LG has focused on the development

    of variable refrigerant ow (VRF) technologies, the latest

    series of advanced air conditioning solutions. Standing at

    the forefront of realizing LGs aspirational philosophy is the

    development of the MULTI V IV: A product which extends

    the VRF model, ensuring startling operational efciency

    in cooling as well as heating for high-rise buildings, while

    defying comparison to any conventional HVACs.

    As many manufacturers have now incorporated VRF

    technologies into their products, the likelihood of further

    innovating on this platform has been perceived as being

    fairly low. However, thanks to LGs high level of expertise

    and dedication, the company has been able to achieve atechnological breakthrough on its latest VRF system the

    MULTI V IV, namely the drastic reduction in the cause of

    hidden energy loss, which is a big factor in the ineffective

    performance of HVAC.

    In the development process of the MULTI V IV, LG has

    undertaken close observation, testing, analysis and extensive

    R&D, in order to create an industry-rst technology aimed at

    improving operational efciency. It is the latest innovation in

    LGs long experience in air conditioning which dates back to

    1968 and another success for the companys dedicated R&D

    capacity. With HVAC innovation at the core of the product,

    the MULTI V IV represents a symbol of LGs unprecedented

    achievement, driven by the Vitalizing every environment

    development philosophy.

    MULTI V IV Development Philosophy

    The True Leader of 4, MULTI V IV

    In order for the MULTI V IV to achieve unbeatable

    seasonal efciency, LG has made ceaseless efforts, driving

    breakthrough VRF technological advancements that make

    the MULTI V IV differentiated from its predecessor, the

    MULTI V III. Finally, LG has helped to raise the standard of

    VRF technologies by developing the true fourth generation

    VRF system, rather than merely upgrading several numerical

    indicators or offering generic functions.

    Thus, LG is dedicated to the four key elements that

    determine operational efciency, which includes compressor,heat exchanger, oil and refrigerant technology. These four

    elements play key roles to maximize the energy efciency

    of its VRF solutions. However, they also generated some of

    hidden loss in conventional models.

    As the result of heavy investment and extensive R&D to

    remove all forms of hidden loss, companys own technologies,

    including High Pressure Oil Return (HiPORTM), Active

    Refrigerant Control, Smart Oil Return and the Variable Heat

    Exchanger Circuit have been developed for the MULTI V IV,

    contributing to raise seasonal efciency.

    LG is proud to introduce customers worldwide to its latest air

    conditioning solution, MULTI V IV. This groundbreaking productrepresents the embodiment of the companys consistent

    commitment to excellence and technological innovation.

  • 8/10/2019 LG Multi V VRF for Middle East Market

    3/86

    050 ARTCOOL

    051 Wall Mounted

    053 Console

    054 Ceiling Cassette

    056 Ceiling Concealed Duct

    058 Ceiling & Floor / Ceiling Suspended

    059 Floor Standing

    010

    028

    032

    OUTDOOR UNITS

    086

    094

    INDOOR UNITS

    100 Air conditioner Control System

    144 Mechanical Accessories

    156 Piping Accessories

    ACCESSORIES

    INDEXLG HVAC SOLUTION

  • 8/10/2019 LG Multi V VRF for Middle East Market

    4/86

    OUTDOOR UNITLINE UP

    HEAT PUMP HEAT PUMP

    8, 10HP 12, 14, 16HP 18, 20HP

    22, 24, 26HP 28, 30, 32HP 34HP

    36, 38HP 40, 42, 44, 46, 48HP

    4, 5, 6HP

    3, 380V

    8, 10, 12, 14, 16, 20HP 22, 24, 26, 28, 30, 32, 34, 36, 38, 40HP

    40, 42, 44, 46, 48, 50, 52, 54, 56, 58, 60HP

    HEAT PUMP

  • 8/10/2019 LG Multi V VRF for Middle East Market

    5/86

    kW 1.5 2.2 2.8 3.6 4.5 5.6 6.2 7.1 8.2 10.6 12.3 14.1 15.8 22.4 28.0

    Btu / h 5k 7k 9k 12k 15k 18k 21k 24k 28k 36k 42k 48k 54k 76k 96k

    SeriesMirror

    Wall Mounted

    Console

    CeilingCassettes

    4 Way Cassette

    (570x570)

    4 Way Cassette

    (840x840)

    2 Way Cassette

    1 Way Cassette

    CeilingConcealedDucts

    Low Static

    Built-in

    High Static

    FreshAir Intake Units

    Ceiling & Floor

    Ceiling Suspended

    FloorStanding

    With Case

    Without Case

    INDOOR UNITLINE UP

  • 8/10/2019 LG Multi V VRF for Middle East Market

    6/86

    MULTI V series offers outstanding energy savings, easy installation and

    connection to many different types of indoor units, making it easy to design.

    OUTDOOR UNITS010

    028

    032

  • 8/10/2019 LG Multi V VRF for Middle East Market

    7/86

    1110

    OUTDOORUNITS

    HEATPUMP

    The new High-Side Shell (HSS) scroll inverter compressor and BLDC concentration motor coil optimizes part load efciency,

    with the 50% reduction in weight and increase in high-frequency operation of 120Hz to 150Hz.

    LGs 4thGeneration Inverter Compressor

    Vapor Injection- Maximize heating capacity via two-stage compression

    - Provide powerful heating in low temperature conditions

    - Improve energy efciency and heating performance

    Extended Compressor Speed 150Hz- Rapid operation response

    - Capable of reaching required temperature quickly

    - Increase part load efciency

    Constant LG 3rdGeneration

    LG 4thGeneration

    Operationrange(Hz)

    15

    20

    60

    120

    150

    Worlds First Class, Rated and Part Load Efciency

    Rated Efciency Integrated Part Load Efciency

    * Comparison Between 10HP

    Efciency(COP)

    4.78

    3.94

    MULTI V IV TropicalConventional

    20% 6%Cycle Control Tech enhancement

    3% VI+HiPORTM1% HEX size up

    4% Active Refrigerant Control

    6% All Inverter Control

    * Comparison Between 14HP, Part Load Efciency Based On Internal Test Data

    Efciency(COP)

    7.65

    5.89

    MULTI V IV TropicalConventional

    30%1% Cycle Control Tech enhancement

    8% VI+HiPORTM1% HEX size up

    5% Active Refrigerant Control

    15% All Inverter Control

    Active Refrigerant Control

    Active Refrigerant Control automatically controls the level of refrigerant amount to maximize efciency.

    Conventional

    Regardless of operation mode, xed amount of refrigerant is provided

    to the compressor, which limits optimal efciency of each modes

    MULTI V IV

    Active Refrigerant Control automatically monitors and adjusts the

    volume of circulating refrigerant during each cycle. This precise,

    ve-step control leads to an improvement in energy ef ciency

    Maximizing efciency

    for all operations

    Accumulator

    Receiver

    Coolingefciency

    Ef

    ciency

    Refrigerantquantity (kg)

    ActiveRefrigerant

    Control

    Part loadefciency 10%

    Coolingefciency

    Efciency

    Fixed Refrigerantquantity (kg)

    Part loadefciency

    Compromising efciency

    for each operation

    Accumulator

    9 10

    Flexible Capacity Control

    It is possible for the user to control heating & cooling performance and save energy through outdoor capacity control.- 5 Basic steps capacity control

    - 10 steps control is possible with IO(Input & Output) module (option)

    - Up to 40% input power reduction through energy saving operation

    Demand control with IO module (In cooling mode)

    * Reduction rate varies upon site conditions** It will be available at the end of 2013*** IO module also provides silent operation during night time, IDU/ODU alarm operation, error alarm and low ambient control

    Dischargeair temperature

    Signal input step0 1

    2 3 4 5 6 7 8

    Powerconsumption

    Efciency

    EXCEPTIONAL EFFICIENCY

    Worlds rst class, rated and part load efciency

  • 8/10/2019 LG Multi V VRF for Middle East Market

    8/861312

    OUTDOORUNITS

    HEATPUMP

    Fast Heating and Cooling via Advanced Inverter

    Continuous Heating Operation in Defrost

    Conventional

    Heating stops during defrosting operation.

    MULTI V IV uses the split-defrost technology for continuous heating operation, which provides consistent heating for the

    indoor environment to improve both heating capacity and indoor comfort.

    MULTI V IV

    Continuous heating during part load defrosting operation.

    * Continuous heating operation can be switched to existing defrost

    mode depending on environmental conditions.

    Operation time

    H

    eatingperformance

    OFFON ON ONOFF OFF

    Operation time

    Heatingperformance

    ONON ON ON ONON

    Paused

    Heating

    Heating Defrosting

    Heating Continuous

    Heating

    Part load

    Defrosting

    In conventional models, inverter compressor and on/off compressor operate one by one, which taking far longer to reach

    maximum capacity. Thanks to LGs all inverter compressor system and high performance cycle design, MULTI V IV delivers

    fast cooling or heating by operating two compressors simultaneously.

    Conventional

    1stStageA : StartB : Start

    2ndStageA: SpeedB: Speed

    3rdStageA : Full SpeedB : Full Speed

    1stStageA : StartB : Off

    2ndStageA : SpeedB : Off

    3rdStageA : SpeedB : On

    4thStageA : SpeedB : On

    5thStageA : Full SpeedB : On

    MULTI V IV

    * Condition : Standard heating mode (Ambient air temp. 7C, Indoor temp. 20C)

    TimeIndoorunitdischargeairtemp.(

    CDB)

    40C

    20C

    11min.

    TimeIndoorunitdischargeairtemp.(

    CDB)

    40C

    20C

    4min.

    OUTSTANDING PERFORMANCEAlways ahead of the competition and on the leading edge of innovation

    with powerful heating and unsurpassed cooling performance

    HiPORTMtechnology enables oil to return directly into the compressor, instead of returning through the refrigerant suction

    pipe, to minimize energy losses.

    HiPORTM (High Pressure Oil Return)

    Conventional

    Loss of low pressure refrigerant to

    the extent of the oil volume returned by

    the refrigerant pipe

    MULTI V IV

    Maximizing reliability and efciency of

    the compressor by reducing high pressure

    refrigerant loss

    No loss in suction gas

    OilSeparator

    OilSeparator

    Compressor Compressor HiPORTM

    Efciency Comparison

    MULTI V IVConventional (Hz)

    * Rating condition (Tc=54.4C,Te=7.2C)

    15

    33%

    20

    23%

    30

    15%

    60

    6%

    90

    6%

    120

    6%

    150

    6%

    Efciency

  • 8/10/2019 LG Multi V VRF for Middle East Market

    9/861514

    OUTDOORUNITS

    HEATPUMP

    Light Weight Outdoor Units

    Expanded Piping Capabilities

    MULTI V IV inverter technology and subcooling control circuit technology allows greater piping length and outstanding

    elevation differences. A cooling system can be implemented more exibly in a high-rise building or complex facilities,reducing the designers work time and providing more efcient design.

    225m*

    Longest

    piping length

    1,000m

    Total piping length

    110m

    Height between

    ODU~IDU

    40m

    Height

    between

    IDU~IDU

    90m**

    Longest

    piping length

    after 1st branch

    Total piping length 1,000m

    Actual longest piping length**(Equivalent*)

    200m**(225m*)

    Longest piping length after 1stbranch(Conditional application)

    40m (90m**)

    Height between ODU~IDU 110m

    Height between IDU~IDU 40m

    Height between ODU~ODU 5m

    ODU : Outdoor unit

    IDU : Indoor unit

    * Equivalent

    ** Conditional application

    Fan with Less Noise and Higher Air Volume

    Cannon fan is applied with optimized shape of shroud, increasing air volume by 50CMM and decreasing

    noise level down to 4dB(A) compared to the previous value.

    Auto Dust Removal

    MULTI V IV Tropical can remove dust on heat exchanger of outdoor unit.

    8, 10HP 12, 14, 16HP

    Cannon Fan

    Minimized vortex and exfoliation provides

    high air volume, low noise level and high efciency

    1

    Sinusoidal leading edge

    Low noise level with sinusoidal chord

    distribution (4dB(A) decreased)

    1

    2

    Grooved suction surface

    Exfoliation of surface

    2

    2 3 Tip vortex suppressor

    Winglet technology applied for

    efciency

    3

    25% lighter weight than major competitors

    - Less pressure on the roof

    - Easier installation

    * 16HP Continuous heating model comparison

    280kgMULTI V IV

    374kgCompany B

    OUTSTANDING PERFORMANCEAlways ahead of the competition and on the leading edge of innovation

    with powerful heating and unsurpassed cooling performance

    DESIGN WITHOUT LIMITS

    Easy design with the most convenient features

    Outdoor unit stopfor a long time

    Normal operationAuto Dust Removal

    - Dust remove on heat exchanger of outdoor unit

    - Outdoor unit fan is backlashing

    - Operating hours : in 5 minutes

  • 8/10/2019 LG Multi V VRF for Middle East Market

    10/861716

    OUTDOORUNITS

    HEATPUMP

    * Connection type : Bluetooth

    To use Mobile LGMV application, exclusive Bluetooth module is required.

    LG SAC (System Air-conditioning) Control App.Central Controller (ACP (Advanced Control Platform) /

    AC Smart Premium) provides smartphone monitoring and control

    function for users. Group control is available via smartphone.

    Mobile LGMV (LG Monitoring View)Mobile LGMV helps users to monitor and control the MULTI V IV

    system cycle using Bluetooth module. Technicians can check LGMV

    data 10m away from MULTI V IV outdoor wi th smartphone.

    Smartphone Monitoring & Control

    Smartphone specication Effective communication distance ofBluetooth

    Basic specication Recommended specication Exception

    - Android OS 2.2- CPU 1 GHz- RAM 1 GB

    - Android OS 4.0(ICS) or higher- CPU 1 GHz Dual Core or higher- RAM 1GB or higher- 1280 x 720, 800 x 480 resolution (Optimized)

    - Android OS 3.x (Honeycomb)- iPhone not supported

    - Effective distance : 10m(Open Space)

    - Effective distance can beshortened based on thecommunication environment.

    Auto Compressor Oil Management

    Compressor reliability is improved with a oil level sensor th at allows for oil balancing and oil return.

    Upgraded FDD (Fault Detection & Diagnosis)

    Newly upgraded FDD elements provide the optimal solution for user reliability and easy maintenance.

    New Refrigerant Quantity Decision Feature

    LG MULTI V IV is the rst VRF that has a Cooling mode start up function which

    permits whole year start up as well as refrigerant quantity evaluation

    - Start up time reduction (60min 45min)

    - Available to use LGMV (LG Monitoring View)

    through a smartphone

    - Piping & wiring error check-up

    - Auto start-up mode / report

    - Black box function

    - Simultaneous diagnosis

    - Auto refrigerant quantity evaluation and charge

    - Cooling refrigerant quantity decision

    Auto Oil Balancing Smart Oil ReturnPump down Pump out

    Indoorairtemp.(

    CDB)

    Outdoor temp.(C)

    18

    27

    33

    10

    -10 -5 24 54

    Cooling mode

    FDDMICOM

    Auto Refrigerant Collection

    In case of an indoor or outdoor unit replacement for service, refrigerant from the malfunctioning unit is transferred to the

    outdoor unit by pumping down or to an indoor unit by pumping out for easy service.

    Refrigerant Flow Refrigerant Flow

    Fail Fail

    Mobile LGMVMULTI V IV

    Bluetooth

    ACP/ACSmart

    PremiumInternet

    LG SAC Control App.

    Group Control

    Manager

    * Available from Oct 2013

    Bluetoothmodulecanbeinstalledonthemainboardof theoutdoorunit.

    * Refrigerant quantity evaluation during cooling Operation

    CYCLE & SERVICE OPTIMIZATION

    Self-diagnostic maintenance solution, offering smart and reliable functionality

  • 8/10/2019 LG Multi V VRF for Middle East Market

    11/861918

    OUTDOORUNITS

    HEATPUMP

    ARUN080LTH4 ARUN100LTH4 ARUN120LTH4 ARUN140LTH4 ARUN160LTH4

    HP 8 10

    Model Name Combination unit ARUN080LTH4 ARUN100LTH4

    Independent unit ARUN080LTH4 ARUN100LTH4

    Capacity (Rated) 1)

    *Cooling

    RT 6.4 8.0

    kW 22.4 28.0

    Btu/h 76,400 95,900

    **Cooling

    RT 5.4 7.1

    kW 19.0 25.0

    Btu/h 64,900 85,300

    Heating

    RT 7.2 9.0

    kW 25.2 31.5

    Btu/h 85,300 107,500

    Input (Rated) 1)*Cooling kW 4.75 5.86

    **Cooling kW 5.40 7.98

    Heating kW 4.98 5.97

    COP 1)*Cooling kW / kW 4.72 4.78

    **Cooling kW / kW 3.52 3.13

    Heating kW / kW 5.06 5.28

    Power Factor Rated - 0.92 0.92

    C as in g Co lo r Wa rm G ray / M or ni ng G ray W ar m Gr ay / M or ni ng G ra y

    Heat Exchanger Gold n Gold n

    Compressor

    Type Hermetically Sealed Scroll Hermetically Sealed Scroll

    Piston Displacement cm3/rev 43.8 62.1

    Number of Revolution rev/min 3,600 3,600

    Motor Output x Number W x No. 4,200 1 5,300 1

    Starting Method Inverter Inverter

    Oil Type FVC68D(PVE) FVC68D(PVE)

    Fan

    Type Propeller fan Propeller fan

    Motor Output x Number W 750 1 750 1

    Air Flow Ratem3/min 210 210

    ft3/min 7,400 7,400

    Drive DC INVERTER DC INVERTER

    Discharge Side / Top TOP TOP

    PipingC onnectionsLiquid mm (inch) 9.52(3/8) 9.52(3/8)

    Gas mm (inch) 19.05(3/4) 22.2(7/8)

    Dimensions(W xHx D)

    mm (9201,680760) (9201,680760)

    i nc h ( 36 -7 /3 2 66 -5 /3 2 29 -2 9/ 32 ) ( 36 -7 /3 2 66 -5 /3 2 29 -2 9/ 32 )

    Net Weightkg 195 201

    lbs 430 433

    Sound PressLevelCooling dB(A) 58.5 59.0

    Heating dB(A) 59.0 59.5

    Sound Power Level dB(A) 78.0 79.0

    Protection Devices

    Hig h pressure protection -High pressuresensor,

    High pressureswitch

    High pressuresensor,

    High pressureswitch

    Comperssor/Fan -Over-heat protection/

    Fan driver overload protector

    Over-heat protection/

    Fan driver overload protector

    Inverter -Over-heat protection,

    Over-current protection

    Over-heat protection,

    Over-current protection

    Communication Cable No. x mm2 (VCTF-SB) 2C 1.0 ~ 1.5 2C 1.0 ~ 1.5

    Refrigerant

    Refrigerant name R410A R410A

    Precharged Amount kg 6.5 6.5

    lbs 14.3 14.3

    C on tr ol E le ct ro ni c Ex pa ns io n V al ve E le ct ro ni c Ex pa ns io n V al ve

    Power SupplyV, , Hz 380-415, 3, 50 380-415, 3, 50

    V, , Hz 400, 3, 60 400, 3, 60

    Number ofmaxmumconnectable indoor units 2) 13 16

    HP 12 14 16

    Model Name Combination unit ARUN120LTH4 ARUN140LTH4 ARUN160LTH4

    Independent unit ARUN120LTH4 ARUN140LTH4 ARUN160LTH4

    Capacity (Rated) 1)

    *Cooling

    RT 9.6 11.1 12.7

    kW 33.6 39.2 44.8

    Btu/h 114,700 133,800 152,900

    **Cooling

    RT 8.1 10.0 11.5

    kW 28.5 35.3 40.3

    Btu/h 97,200 120,400 137,600

    Heating

    RT 10.7 12.5 14.2

    kW 37.8 43.9 50.0

    Btu/h 128,000 149,800 170,600

    Input (Rated) 1)*Cooling kW 7.91 8.79 10.38

    **Cooling kW 9.41 11.36 13.45

    Heating kW 7.96 9.35 10.92

    COP 1)*Cooling kW / kW 4.25 4.46 4.32

    **Cooling kW / kW 3.03 3.11 3.00

    Heating kW / kW 4.75 4.70 4.58

    Power Factor Rated - 0.92 0.92 0.92

    C as in g C ol or W ar m G ra y / M o rn in g G ra y W ar m G ra y / M o rn in g G ra y W ar m G ra y / M o rn in g G ra y

    Heat Exchanger Gold n Gold n Gold n

    Compressor

    Type Hermetically Sealed Scroll Hermetically Sealed Scroll Hermetically Sealed Scroll

    Piston Displacement cm3/rev 62.1 43.8 2 43.8 2

    Number of Revolution rev/min 3,600 3,600 2 3,600 2

    Motor Output x Number W x No. 5,300 1 4,200 2 4,200 2

    Starting Method Inverter Inverter Inverter

    Oil Type FVC68D(PVE) FVC68D(PVE) FVC68D(PVE)

    Fan

    Type Propeller fan Propeller fan Propeller fan

    Motor Output x Number W 600 2 600 2 600 2

    Air Flow Ratem3/min 290 290 290

    ft3/min 10,200 10,200 10,200

    Drive DC INVERTER DC INVERTER DC INVERTER

    Discharge Side / Top TOP TOP TOP

    PipingConnectionsLiquid mm (inch) 12.7(1/2) 12.7(1/2) 12.7(1/2)

    Gas mm (inch) 28.58(1-1/8) 28.58(1-1/8) 28.58(1-1/8)

    Dimensions(W xHx D)

    mm (1,240 x1,680 x760) (1,240 x1,680 x760) (1,240 x1,680 x 760)

    inch(48-13/16 66-5/32

    29-29/32)

    (48-13/1666-5/32

    29-29/32)

    (48-13/1666-5/32

    29-29/32)

    Net Weightkg 235 270 280

    lbs 518 595 617

    Sound PressLevelCooling dB(A) 59.0 59.5 59.5

    Heating dB(A) 59.5 60.0 60.0

    Sound Power Level dB(A) 79.0 79.5 79.5

    Protection Devices

    Hi gh p ressure protection -High pressuresensor,

    High pressureswitch

    High pressuresensor,

    High pressureswitch

    High pressuresensor,

    High pressureswitch

    Comperssor/Fan -Over-heat protection/

    Fan driver overload protector

    Over-heat protection/

    Fan driver overload protector

    Over-heat protection/

    Fan driver overload protector

    Inverter -Over-heat protection,

    Over-current protection

    Over-heat protection,

    Over-current protection

    Over-heat protection,

    Over-current protection

    Communication Cable No. x mm2(VCTF-SB) 2C 1.0 ~ 1.5 2C 1.0 ~ 1.5 2C 1.0 ~ 1.5

    Refrigerant

    Refrigerant name R410A R410A R410A

    Precharged Amount kg 8.5 8.5 10.0

    lbs 18.7 18.7 22.0

    Co nt rol Elect ro n icEx pan s io n Valve Elect ro n icEx pan s io n Va lve Elect ro n icEx pan s io n Va lve

    Power SupplyV, , Hz 380-415, 3, 50 380-415, 3, 50 380-415, 3, 50

    V, , Hz 400, 3, 60 400, 3, 60 400, 3, 60

    Number ofmaxmumconnectable indoor units 2) 20 23 26

    2. TheMaximum combination ratio is130%.

    3. Wiringcable sizemust comply with theapplicable local and national codes.

    And Electriccharacteristicschapter should be considered for electrical work and design.

    Especially thepower cable and circuit breaker should beselected in accordancewith that.

    4. Dueto our policy ofinnovation somespecications may bechanged without notication.

    5. Sound Level Valuesare measured at Anechoicchamber. Therefore,these values

    can beincreased owingto ambient conditionsduring operation

    6. Power factor could vary lessthan 1% accordingto theoperatingconditions.

    Notes:1. Capacitiesarebased on thefollowingconditions:

    -*Cooling : -Indoor Temperature27C(80.6F) DB/19C(66.2F)WB

    -Outdoor Temperature35C(95F) DB/24C(75.2F)WB

    **Cooling: -Indoor Temperature27C(80.6F) DB/19C(66.2F)WB

    -Outdoor Temperature46C(114.8F)DB/ 24C(75.2F)WB

    -Heating Temperature: Indoor 20C(68F)DB/15C(59F) WB

    Outdoor 7C(44.6F)DB/6C(42.8F) WB

    -Piping Length : Interconnected PipeLength = 7.5m

    -Difference Limit ofElevation (Outdoor ~ Indoor Unit)is Zero.

    2. TheMaximumcombination ratio is130%.

    3. Wiringcable sizemust comply with theapplicable local and national codes.

    And Electriccharacteristics chapter should beconsidered for electrical work and design.

    Especially thepower cable and circuit breaker should beselected in accordancewith that.

    4. Dueto our policy ofinnovation somespecications may bechanged without notication.

    5. Sound Level Valuesare measured at Anechoicchamber. Therefore,these values

    can beincreased owingto ambient conditionsduring operation

    6. Power factor could vary lessthan 1% according to theoperating conditions.

    Notes:1. Capacitiesareb ased on thefollowing conditions:

    -*Cooling : -Indoor Temperature27C(80.6F) DB/19C(66.2F)WB

    -Ou tdoor Temperature35C(95F) DB/24C(75.2F)WB

    **Cooling: -Indoor Temperature27C(80.6F) DB/19C(66.2F)WB

    -Outdoor Temperature46C(114.8F) DB/24C(75.2F)WB

    -Heating Temperature: Indoor 20C(68F)DB/15C(59F) WB

    Outdoor 7C(44.6F)DB/6C(42.8F) WB

    -Piping Length : Interconnected PipeLength =7.5m

    -Difference Limit ofElevation (Outdoor ~ Indoor Unit)isZero.

  • 8/10/2019 LG Multi V VRF for Middle East Market

    12/862120

    OUTDOORUNITS

    HEATPUMP

    ARUN180LTH4 ARUN200LTH4 ARUN220LTH4 ARUN240LTH4 ARUN260LTH4

    HP 18 20

    Model Name Combination unit ARUN180LTH4 ARUN200LTH4

    Independent unit ARUN100LTH4 ARUN100LTH4

    ARUN080LTH4 ARUN100LTH4

    Capacity (Rated) 1)

    *Cooling

    RT 14.4 16.0

    kW 50.4 56.0

    Btu/h 172,300 191,800

    **Cooling

    RT 12.5 14.2

    kW 44.0 50.0

    Btu/h 150,200 170,600

    Heating

    RT 16.2 18.0

    kW 56.7 63.0

    Btu/h 192,800 215,000

    Input (Rated) 1)*Cooling kW 10.61 11.72

    **Cooling kW 13.38 15.96

    Heating kW 10.95 11.94

    COP 1)*Cooling kW / kW 4.75 4.78

    **Cooling kW / kW 3.29 3.13

    Heating kW / kW 5.18 5.28

    Power Factor Rated - 0.92 0.92

    C as in g Co lo r Wa rm G ray / M or ni ng G ray W ar m Gr ay / M or ni ng G ra y

    Heat Exchanger Gold n Gold n

    Compressor

    Type Hermetically Sealed Scroll Hermetically Sealed Scroll

    Piston Displacement cm3/rev (62.1) + (43.8) (62.1) x 2

    Number of Revolution rev/min (3,600) + (3,600) (3,600) x 2Motor Output x Number W x No. (5,300 x 1) + (4,200 x 1) (5,300 x 1) x 2

    Starting Method Inverter Inverter

    Oil Type FVC68D(PVE) FVC68D(PVE)

    Fan

    Type Propeller fan Propeller fan

    Motor Output x Number W (750 x 1) x 2 (750 x 1) x 2

    Air Flow Ratem3/min (210) x 2 (210) x 2

    ft3/min (7,400) x 2 (7,400) x 2

    Drive DC INVERTER DC INVERTER

    Discharge Side / Top TOP TOP

    PipingC onnectionsLiquid mm (inch) 15.88(5/8) 15.88(5/8)

    Gas mm (inch) 28.58(1-1/8) 28.58(1-1/8)

    Dimensions(W xHx D)

    mm (9201,680760) x 2 (9201,680760) x 2

    i nc h ( 3 6- 7/ 32 6 6- 5/ 32 2 9- 29 /3 2) x 2 ( 36 -7 /3 2 66 -5 /3 2 29 -2 9/ 32 ) x 2

    Net Weightkg (201) + (195) (201) x 2

    lbs (433) + (430) (433) x 2

    Sound PressLevelCooling dB(A) 61.8 62.0

    Heating dB(A) 62.3 62.5

    Sound Power Level dB(A) 81.5 82.0

    Protection Devices

    Hig h pressure protection -High pressuresensor,

    High pressureswitch

    High pressuresensor,

    High pressureswitch

    Comperssor/Fan -Over-heat protection/

    Fan driver overload protector

    Over-heat protection/

    Fan driver overload protector

    Inverter -Over-heat protection,

    Over-current protection

    Over-heat protection,

    Over-current protection

    Communication Cable No. x mm2 (VCTF-SB) 2C 1.0 ~ 1.5 2C 1.0 ~ 1.5

    Refrigerant

    Refrigerant name R410A R410A

    Precharged Amount kg (6.5) x 2 (6.5) x 2

    lbs (14.3) x 2 (14.3) x 2

    C on tr ol E le ct ro ni c Ex pa ns io n V al ve E le ct ro ni c Ex pa ns io n V al ve

    Power SupplyV, , Hz 380-415, 3, 50 380-415, 3, 50

    V, , Hz 400, 3, 60 400, 3, 60

    Number ofmaxmumconnectable indoor units 2) 29 32

    HP 22 24 26

    Model Name Combination unit ARUN220LTH4 ARUN240LTH4 ARUN260LTH4

    Independent unit ARUN120LTH4 ARUN140LTH4 ARUN160LTH4

    ARUN100LTH4 ARUN100LTH4 ARUN100LTH4

    Capacity (Rated) 1)

    *Cooling

    RT 17.6 19.1 20.7

    kW 61.6 67.2 72.8

    Btu/h 210,600 229,700 248,800

    **Cooling

    RT 15.2 17.1 18.6

    kW 53.5 60.3 65.3

    Btu/h 182,500 205,700 222,900

    Heating

    RT 19.7 21.5 23.2

    kW 69.3 75.4 81.5

    Btu/h 235,500 257,300 278,100

    Input (Rated) 1)*Cooling kW 13.77 14.65 16.24

    **Cooling kW 17.39 19.34 21.43

    Heating kW 13.93 15.32 16.89

    COP 1)*Cooling kW / kW 4.47 4.59 4.48

    **Cooling kW / kW 3.08 3.12 3.05

    Heating kW / kW 4.97 4.92 4.83

    Power Factor Rated - 0.92 0.92 0.92

    C as in g C ol or W ar m G ra y / M o rn in g G ra y W ar m G ra y / M o rn in g G ra y W ar m G ra y / M o rn in g G ra y

    Heat Exchanger Gold n Gold n Gold n

    Compressor

    Type Hermetically Sealed Scroll Hermetically Sealed Scroll Hermetically Sealed Scroll

    Piston Displacement cm3/rev (62.1) x 2 (43.8 x 2) + (62.1) (43.8 x 2) + (62.1)

    N um be r o fR ev ol ut io n r ev/ mi n ( 3,6 00 )x 2 ( 3,6 00 x 2) + (3 ,6 00 ) ( 3, 60 0x 2) + (3 ,6 00 )Motor Output x Number W x No. (5,300 x1) x 2 (4,200 x2) + (5,300 x 1) (4,200 x2) + (5,300 x 1)

    Starting Method Inverter Inverter Inverter

    Oil Type FVC68D(PVE) FVC68D(PVE) FVC68D(PVE)

    Fan

    Type Propeller fan Propeller fan Propeller fan

    Mo to r O utp ut x N um be r W ( 75 0x 1) + (6 00 x 2) ( 75 0x 1) + (6 00 x 2) ( 75 0x 1) + (6 00 x 2)

    Air Flow Ratem3/min (210) + (290) (210) + (290) (210) + (290)

    ft3/min (7,400) +(10,200) (7,400) +(10,200) (7,400) +(10,200)

    Drive DC INVERTER DC INVERTER DC INVERTER

    Discharge Side / Top TOP TOP TOP

    PipingConnectionsLiquid mm (inch) 15.88(5/8) 15.88(5/8) 19.05(3/4)

    Gas mm (inch) 28.58(1-1/8) 34.9(1-3/8) 34.9(1-3/8)

    Dimensions(W xHx D)

    mm(1,240x1,680x 760)

    +(9201,680760)

    (1,240x1,680x 760)

    + (9201,680760)

    (1,240x1,680x 760)

    + (9201,680760)

    inch(48-13/1666-5/3229-29/32)+

    (36-7/3266-5/3229-29/32)(48-13/1666-5/3229-29/32)

    +(36-7/3266-5/3229-29/32)(48-13/1666-5/3229-29/32) +(36-7/3266-5/3229-29/32)

    Net Weightkg (235) + (201) (270) + (201) (280) + (201)

    lbs (518) + (433) (595) + (433) (617) + (433)

    Sound PressLevelCooling dB(A) 62.0 62.3 62.3

    Heating dB(A) 62.5 62.8 62.8

    Sound Power Level dB(A) 82.0 82.3 82.3

    Protection Devices

    Hi gh p ressure protection -High pressuresensor,

    High pressureswitch

    High pressuresensor,

    High pressureswitch

    High pressuresensor,

    High pressureswitch

    Comperssor/Fan -Over-heat protection/

    Fan driver overload protector

    Over-heat protection/

    Fan driver overload protector

    Over-heat protection/

    Fan driver overload protector

    Inverter -Over-heat protection,

    Over-current protection

    Over-heat protection,

    Over-current protection

    Over-heat protection,

    Over-current protection

    Communication Cable No. x mm2(VCTF-SB) 2C 1.0 ~ 1.5 2C 1.0 ~ 1.5 2C 1.0 ~ 1.5

    Refrigerant

    Refrigerant name R410A R410A R410A

    Precharged Amount kg (8.5) + (6.5) (8.5) + (6.5) (10.0) + (6.5)

    lbs (18.7) + (14.3) (18.7) + (14.3) (22.0) + (14.3)

    Co nt rol Elect ro n icEx pan s io n Valve Elect ro n icEx pan s io n Va lve Elect ro n icEx pan s io n Va lve

    Power SupplyV, , Hz 380-415, 3, 50 380-415, 3, 50 380-415, 3, 50

    V, , Hz 400, 3, 60 400, 3, 60 400, 3, 60

    Number ofmaxmumconnectable indoor units 2) 35 39 42

    2. TheMaximum combination ratio is130%.

    3. Wiringcable sizemust comply with theapplicable local and national codes.

    And Electriccharacteristicschapter should be considered for electrical work and design.

    Especially thepower cable and circuit breaker should beselected in accordancewith that.

    4. Dueto our policy ofinnovation somespecications may bechanged without notication.

    5. Sound Level Valuesare measured at Anechoicchamber. Therefore,these values

    can beincreased owingto ambient conditionsduring operation

    6. Power factor could vary lessthan 1% accordingto theoperatingconditions.

    Notes:1. Capacitiesarebased on thefollowingconditions:

    -*Cooling : -Indoor Temperature27C(80.6F) DB/19C(66.2F)WB

    -Outdoor Temperature35C(95F) DB/24C(75.2F)WB

    **Cooling: -Indoor Temperature27C(80.6F) DB/19C(66.2F)WB

    -Outdoor Temperature46C(114.8F)DB/ 24C(75.2F)WB

    -Heating Temperature: Indoor 20C(68F)DB/15C(59F) WB

    Outdoor 7C(44.6F)DB/6C(42.8F) WB

    -Piping Length : Interconnected PipeLength = 7.5m

    -Difference Limit ofElevation (Outdoor ~ Indoor Unit)is Zero.

    2. TheMaximumcombination ratio is130%.

    3. Wiringcable sizemust comply with theapplicable local and national codes.

    And Electriccharacteristics chapter should beconsidered for electrical work and design.

    Especially thepower cable and circuit breaker should beselected in accordancewith that.

    4. Dueto our policy ofinnovation somespecications may bechanged without notication.

    5. Sound Level Valuesare measured at Anechoicchamber. Therefore,these values

    can beincreased owingto ambient conditionsduring operation

    6. Power factor could vary lessthan 1% according to theoperating conditions.

    Notes:1. Capacitiesareb ased on thefollowing conditions:

    -*Cooling : -Indoor Temperature27C(80.6F) DB/19C(66.2F)WB

    -Ou tdoor Temperature35C(95F) DB/24C(75.2F)WB

    **Cooling: -Indoor Temperature27C(80.6F) DB/19C(66.2F)WB

    -Outdoor Temperature46C(114.8F) DB/24C(75.2F)WB

    -Heating Temperature: Indoor 20C(68F)DB/15C(59F) WB

    Outdoor 7C(44.6F)DB/6C(42.8F) WB

    -Piping Length : Interconnected PipeLength =7.5m

    -Difference Limit ofElevation (Outdoor ~ Indoor Unit)isZero.

  • 8/10/2019 LG Multi V VRF for Middle East Market

    13/862322

    OUTDOORUNITS

    HEATPUMP

    ARUN280LTH4 ARUN300LTH4 ARUN320LTH4 ARUN340LTH4

    HP 28 30 32

    Model Name Combination unit ARUN280LTH4 ARUN300LTH4 ARUN320LTH4

    Independent unit ARUN160LTH4 ARUN160LTH4 ARUN160LTH4

    ARUN120LTH4 ARUN140LTH4 ARUN160LTH4

    Capacity (Rated) 1)

    *Cooling

    RT 22.3 23.8 25.4

    kW 78.4 84.0 89.6

    Btu/h 267,600 286,700 305,800

    **Cooling

    RT 19.6 21.5 23.0

    kW 68.8 75.6 80.6

    Btu/h 234,800 258,000 275,200

    Heating

    RT 24.9 26.7 28.4

    kW 87.8 93.9 100.0

    Btu/h 298,600 320,400 341,200

    Input (Rated) 1)*Cooling kW 18.29 19.17 20.76

    **Cooling kW 22.86 24.81 26.90

    Heating kW 18.88 20.27 21.84

    COP 1)*Cooling kW / kW 4.29 4.38 4.32

    **Cooling kW / kW 3.01 3.05 3.00

    Heating kW / kW 4.65 4.63 4.58

    Power Factor Rated - 0.92 0.92 0.92

    C as in g C ol or W ar m G ra y / M o rn in g G ra y W ar m G ra y / M o rn in g G ra y W ar m G ra y / M o rn in g G ra y

    Heat Exchanger Gold n Gold n Gold n

    Compressor

    Type Hermetically Sealed Scroll Hermetically Sealed Scroll Hermetically Sealed Scroll

    Piston Displacement cm3/rev (43.8 x 2) + (62.1) (43.8 x 2) x 2 (43.8 x 2) x 2

    Nu mb er of Revolution rev/min (3,600 x 2) + (3,600) (3,600 x 2) x 2 (3,600 x 2) x 2

    Motor Output x Number W x No. (4,200 x2) +(5,300 x1) (4,200 x2) x2 (4,200 x2) x2

    Starting Method Inverter Inverter Inverter

    Oil Type FVC68D(PVE) FVC68D(PVE) FVC68D(PVE)

    Fan

    Type Propeller fan Propeller fan Propeller fan

    Motor Output x Number W (600 x2) x 2 (600 x2) x 2 (600 x 2) x2

    Air Flow Ratem3/min (290) x 2 (290) x 2 (290) x 2

    ft3/min (10,200) x 2 (10,200) x 2 (10,200) x 2

    Drive DC INVERTER DC INVERTER DC INVERTER

    Discharge Side / Top TOP TOP TOP

    PipingConnectionsLiquid mm (inch) 19.05(3/4) 19.05(3/4) 19.05(3/4)

    Gas mm (inch) 34.9(1-3/8) 34.9(1-3/8) 34.9(1-3/8)

    Dimensions(W xHx D)

    mm (1,240 x1,680 x760) x2 (1,240 x1,680 x760) x2 (1,240 x1,680 x760) x2

    inch(48-13/1666-5/32

    29-29/32)x2

    (48-13/1666-5/32

    29-29/32)x2

    (48-13/1666-5/32

    29-29/32)x2

    Net Weightkg (280) + (235) (280) + (270) (280) x 2

    lbs (617) + (518) (617) + (595) (617) x 2

    Sound PressLevelCooling dB(A) 62.3 62.5 62.5

    Heating dB(A) 62.8 63.0 63.0

    Sound Power Level dB(A) 82.3 82.5 82.5

    Protection Devices

    High p ressu re protecti on -High pressuresensor,

    High pressureswitch

    High pressuresensor,

    High pressureswitch

    High pressuresensor,

    High pressureswitch

    Comperssor/Fan -Over-heat protection/

    Fan driver overload protector

    Over-heat protection/

    Fan driver overload protector

    Over-heat protection/

    Fan driver overload protector

    Inverter -Over-heat protection,

    Over-current protection

    Over-heat protection,

    Over-current protection

    Over-heat protection,

    Over-current protection

    Communication Cable No. x mm2(VCTF-SB) 2C 1.0 ~ 1.5 2C 1.0 ~ 1.5 2C 1.0 ~ 1.5

    Refrigerant

    Refrigerant name R410A R410A R410A

    Precharged Amount kg (10.0) + (8.5) (10.0) + (8.5) (10.0) x 2

    lbs (22.0) + (18.7) (22.0) + (18.7) (22.0) x 2

    Co nt rol Elect ron icExpans ion Va lve Elect ro n icEx pan s io n Va lve Elect ro n icEx pan s io n Valve

    Power SupplyV, , Hz 380-415, 3, 50 380-415, 3, 50 380-415, 3, 50

    V, , Hz 400, 3, 60 400, 3, 60 400, 3, 60

    Number ofmaxmumconnectable indoor units 2) 45 49 52

    HP 34

    Model Name Combination unit ARUN340LTH4

    Independent unit ARUN140LTH4

    ARUN100LTH4

    ARUN100LTH4

    Capacity (Rated) 1)

    *Cooling

    RT 27.1

    kW 95.2

    Btu/h 325,600

    **Cooling

    RT 24.2

    kW 85.3

    Btu/h 291,000

    Heating

    RT 30.5

    kW 106.9

    Btu/h 364,800

    Input (Rated) 1)*Cooling kW 20.51

    **Cooling kW 27.32

    Heating kW 21.29

    COP 1)*Cooling kW / kW 4.64

    **Cooling kW / kW 3.12

    Heating kW / kW 5.02

    Power Factor Rated - 0.92

    CasingColor WarmGray / MorningGray

    Heat Exchanger Gold n

    Compressor

    Type Hermetically Sealed Scroll

    Piston Displacement cm3

    /rev (43.8x 2)+(62.1)x 2Number ofRevolution rev/min (3,600x 2)+ (3,600)x2

    Motor Output xNumber W xNo. (4 ,200x 2)+(5 ,300x 1)x 2

    StartingMethod Inverter

    Oil Type FVC68D(PVE)

    Fan

    Type Propeller fan

    Motor Output xNumber W (750x 1)x 2+(600x 2)

    Air Flow Ratem3/min (210)x2 +(290)

    ft3/min (7,400)x2 +(10,200)

    Drive DCINVERTER

    Discharge Side / Top TOP

    PipingConnectionsLiquid mm (inch) 19.05(3/4)

    Gas mm (inch) 34.9(1-3/8)

    Dimensions(W xHx D)

    mm (1,240x1,680x 760)+(9201,680760)x2

    inch (48-13/1666-5/32 29-29/32)+(36-7/3266-5/32 29-29/32)x2

    Net Weightkg (270)+(201)x2

    lbs (595)+(433)x2

    Sound PressLevelCooling dB(A) 63.9

    Heating dB(A) 64.4

    Sound Power Level dB(A) 83.9

    Protection Devices

    High p ressure protection - Highpressure sensor,Highpressureswitch

    Comperssor/Fan - Over-heatprotection/Fan driveroverloadprotector

    Inverter - Over-heatprotection,Over-currentprotection

    Communication Cable No. x mm2 (VCTF-SB) 2C 1.0~ 1.5

    Refrigerant

    Refrigerant name R410A

    Precharged Amount kg (8.5)+(6.5)x2

    lbs (18.7)+(14.3)x2

    Control ElectronicExpansion Valve

    Power SupplyV,,Hz 380-415,3,50

    V,,Hz 400,3,60

    Number ofmaxmumconnectable indoor units 2) 55

    2. TheMaximum combination ratio is130%.

    3. Wiringcable sizemust comply with theapplicable local and national codes.

    And Electriccharacteristicschapter should be considered for electrical work and design.

    Especially thepower cable and circuit breaker should beselected in accordancewith that.

    4. Dueto our policy ofinnovation somespecications may bechanged without notication.

    5. Sound Level Valuesare measured at Anechoicchamber. Therefore,these values

    can beincreased owingto ambient conditionsduring operation

    6. Power factor could vary lessthan 1% accordingto theoperatingconditions.

    Notes:1. Capacitiesarebased on thefollowingconditions:

    -*Cooling : -Indoor Temperature27C(80.6F) DB/19C(66.2F)WB

    -Outdoor Temperature35C(95F) DB/24C(75.2F)WB

    **Cooling: -Indoor Temperature27C(80.6F) DB/19C(66.2F)WB

    -Outdoor Temperature46C(114.8F)DB/ 24C(75.2F)WB

    -Heating Temperature: Indoor 20C(68F)DB/15C(59F) WB

    Outdoor 7C(44.6F)DB/6C(42.8F) WB

    -Piping Length : Interconnected PipeLength = 7.5m

    -Difference Limit ofElevation (Outdoor ~ Indoor Unit)is Zero.

    2. TheMaximumcombination ratio is130%.

    3. Wiringcable sizemust comply with theapplicable local and national codes.

    And Electriccharacteristics chapter should beconsidered for electrical work and design.

    Especially thepower cable and circuit breaker should beselected in accordancewith that.

    4. Dueto our policy ofinnovation somespecications may bechanged without notication.

    5. Sound Level Valuesare measured at Anechoicchamber. Therefore,these values

    can beincreased owingto ambient conditionsduring operation

    6. Power factor could vary lessthan 1% according to theoperating conditions.

    Notes:1. Capacitiesareb ased on thefollowing conditions:

    -*Cooling : -Indoor Temperature27C(80.6F) DB/19C(66.2F)WB

    -Ou tdoor Temperature35C(95F) DB/24C(75.2F)WB

    **Cooling: -Indoor Temperature27C(80.6F) DB/19C(66.2F)WB

    -Outdoor Temperature46C(114.8F) DB/24C(75.2F)WB

    -Heating Temperature: Indoor 20C(68F)DB/15C(59F) WB

    Outdoor 7C(44.6F)DB/6C(42.8F) WB

    -Piping Length : Interconnected PipeLength =7.5m

    -Difference Limit ofElevation (Outdoor ~ Indoor Unit)isZero.

  • 8/10/2019 LG Multi V VRF for Middle East Market

    14/862524

    OUTDOORUNITS

    HEATPUMP

    ARUN360LTH4 ARUN380LTH4 ARUN400LTH4 ARUN420LTH4

    HP 36 38

    Model Name Combination unit ARUN360LTH4 ARUN380LTH4

    Independent unit ARUN140LTH4 ARUN160LTH4

    ARUN120LTH4 ARUN120LTH4

    ARUN100LTH4 ARUN100LTH4

    Capacity (Rated) 1)

    *Cooling

    RT 28.7 30.3

    kW 100.8 106.4

    Btu/h 344,400 363,500

    **Cooling

    RT 25.2 26.7

    kW 88.8 93.8

    Btu/h 302,900 320,100

    Heating

    RT 32.2 33.9

    kW 113.2 119.3

    Btu/h 385,300 406,100

    Input (Rated) 1)*Cooling kW 22.56 24.15

    **Cooling kW 28.75 30.84

    Heating kW 23.28 24.85

    COP 1)*Cooling kW / kW 4.47 4.41

    **Cooling kW / kW 3.09 3.04

    Heating kW / kW 4.86 4.80

    Power Factor Rated - 0.92 0.92

    C as in g Co lo r W ar mG ra y / M or ni ng G ray Wa rm G ray / M or ni ng G ray

    Heat Exchanger Gold n Gold n

    Compressor

    Type Hermetically Sealed Scroll Hermetically Sealed Scroll

    Piston Displacement cm3

    /rev (43.8 x 2) + (62.1) x 2 (43.8 x 2) + (62.1) x 2N um be r of R ev ol uti on re v/ mi n (3 ,6 00 x 2) + (3 ,6 00 )x 2 ( 3,6 00 x 2) + (3 ,6 00 ) x2

    Motor Output x Number W x No. (4,200 x2) +(5,300 x1) x2 (4,200 x2) +(5,300 x1) x2

    Starting Method Inverter Inverter

    Oil Type FVC68D(PVE) FVC68D(PVE)

    Fan

    Type Propeller fan Propeller fan

    Motor O utpu t x Nu mber W (750 x 1) + (600 x 2) x 2 (750 x 1) + (600 x 2) x 2

    Air Flow Ratem3/min (210) + (290) x 2 (210) + (290) x 2

    ft3/min (7,400) + (10,200) x 2 (7,400) + (10,200) x 2

    Drive DC INVERTER DC INVERTER

    Discharge Side / Top TOP TOP

    PipingC onnectionsLiquid mm (inch) 19.05(3/4) 19.05(3/4)

    Gas mm (inch) 41.3(1-5/8) 41.3(1-5/8)

    Dimensions(W xHx D)

    mm(1,240x1,680x760)x2

    +(9201,680760)

    (1,240x1,680x760)x2

    +(9201,680760)

    inch(48-13/1666-5/32 29-29/32)x2

    +(36-7/32 66-5/3229-29/32)

    (48-13/1666-5/32 29-29/32)x2

    +(36-7/32 66-5/3229-29/32)

    Net Weightkg (270) + (235) + (201) (280) + (235) + (201)

    lbs (595) + (518) + (433) (617) + (518) + (433)

    Sound PressLevelCooling dB(A) 63.9 63.9

    Heating dB(A) 64.4 64.4

    Sound Power Level dB(A) 83.9 83.9

    Protection Devices

    Hig h pressu re protection -High pressuresensor,

    High pressureswitch

    High pressuresensor,

    High pressureswitch

    Comperssor/Fan -Over-heat protection/

    Fan driver overload protector

    Over-heat protection/

    Fan driver overload protector

    Inverter -Over-heat protection,

    Over-current protection

    Over-heat protection,

    Over-current protection

    Communication Cable No. x mm2 (VCTF-SB) 2C 1.0 ~ 1.5 2C 1.0 ~ 1.5

    Refrigerant

    Refrigerant name R410A R410A

    Precharged Amount kg (8.5) x 2 + (6.5) (10.0) + (8.5) + (6.5)

    lbs (18.7) x 2 + (14.3) (22.0) + (18.7) + (14.3)

    C on tr ol E le ct ro ni c Ex pa ns io n V al ve E le ct ro ni c Ex pa ns io n V al ve

    Power SupplyV, , Hz 380-415, 3, 50 380-415, 3, 50

    V, , Hz 400, 3, 60 400, 3, 60

    Number ofmaxmumconnectable indoor units 2) 58 61

    HP 40 42

    Model Name Combination unit ARUN400LTH4 ARUN420LTH4

    Independent unit ARUN160LTH4 ARUN160LTH4

    ARUN120LTH4 ARUN140LTH4

    ARUN120LTH4 ARUN120LTH4

    Capacity (Rated) 1)

    *Cooling

    RT 31.9 33.4

    kW 112.0 117.6

    Btu/h 382,300 401,400

    **Cooling

    RT 27.7 29.6

    kW 97.3 104.1

    Btu/h 332,000 355,200

    Heating

    RT 35.6 37.4

    kW 125.6 131.7

    Btu/h 426,600 448,400

    Input (Rated) 1)*Cooling kW 26.20 27.08

    **Cooling kW 32.26 34.22

    Heating kW 26.84 28.23

    COP 1)*Cooling kW / kW 4.27 4.34

    **Cooling kW / kW 3.02 3.04

    Heating kW / kW 4.68 4.67

    Power Factor Rated - 0.92 0.92

    C as ing C ol or W ar m Gr ay / M or ni ng G ra y W ar mG ray / M or ni ng G ray

    Heat Exchanger Gold n Gold n

    Compressor

    Type Hermetically Sealed Scroll Hermetically Sealed Scroll

    Piston Displacement cm3

    /rev (43.8 x 2) + (62.1) x 2 (43.8 x 2) x 2 + (62.1)N um be r of Re vo lu ti on re v/ mi n ( 3, 60 0 x2 )+ ( 3, 60 0) x 2 (3 ,6 00 x 2) x 2 + (3, 60 0)

    Motor Output x Number W x No. (4,200 x2) +(5,300 x1) x2 (4,200 x2) x2 +(5,300 x1)

    Starting Method Inverter Inverter

    Oil Type FVC68D(PVE) FVC68D(PVE)

    Fan

    Type Propeller fan Propeller fan

    Motor Output x Number W (600 x 2) x 3 (600 x 2) x 3

    Air Flow Ratem3/min (290) x 3 (290) x 3

    ft3/min (10,200) x 3 (10,200) x 3

    Drive DC INVERTER DC INVERTER

    Discharge Side / Top TOP TOP

    PipingConnectionsLiquid mm (inch) 19.05(3/4) 19.05(3/4)

    Gas mm (inch) 41.3(1-5/8) 41.3(1-5/8)

    Dimensions(W xHx D)

    mm ( 1,240 x 1,680 x 760) x 3 ( 1,240 x 1,680 x 760) x 3

    i nc h ( 4 8- 13 /1 6 66 -5 /3 2 29 -2 9/ 32 ) x 3 ( 4 8- 13 /1 6 66 -5 /3 2 29 -2 9/ 32 ) x 3

    Net Weightkg (280) + (235) x 2 (280) + (270) + (235)

    lbs (617) + (518) x 2 (617) + (595) + (518)

    Sound PressLevelCooling dB(A) 63.9 64.1

    Heating dB(A) 64.4 64.6

    Sound Power Level dB(A) 83.9 84.1

    Protection Devices

    High p ressure protection -High pressuresensor,

    High pressureswitch

    High pressuresensor,

    High pressureswitch

    Comperssor/Fan -Over-heat protection/

    Fan driver overload protector

    Over-heat protection/

    Fan driver overload protector

    Inverter -Over-heat protection,

    Over-current protection

    Over-heat protection,

    Over-current protection

    Communication Cable No. x mm2(VCTF-SB) 2C 1.0 ~ 1.5 2C 1.0 ~ 1.5

    Refrigerant

    Refrigerant name R410A R410A

    Precharged Amount kg (10.0) + (8.5) x 2 (10.0) + (8.5) x 2

    lbs (22.0) + (18.7) x 2 (22.0) + (18.7) x 2

    C on tr ol E le ct ro ni c Ex pa ns io n V al ve E le ct ro ni c Ex pa ns io n V al ve

    Power SupplyV, , Hz 380-415, 3, 50 380-415, 3, 50

    V, , Hz 400, 3, 60 400, 3, 60

    Number ofmaxmumconnectable indoor units 2) 64 64

    2. TheMaximum combination ratio is130%.

    3. Wiringcable sizemust comply with theapplicable local and national codes.

    And Electriccharacteristicschapter should be considered for electrical work and design.

    Especially thepower cable and circuit breaker should beselected in accordancewith that.

    4. Dueto our policy ofinnovation somespecications may bechanged without notication.

    5. Sound Level Valuesare measured at Anechoicchamber. Therefore,these values

    can beincreased owingto ambient conditionsduring operation

    6. Power factor could vary lessthan 1% accordingto theoperatingconditions.

    Notes:1. Capacitiesarebased on thefollowingconditions:

    -*Cooling : -Indoor Temperature27C(80.6F) DB/19C(66.2F)WB

    -Outdoor Temperature35C(95F) DB/24C(75.2F)WB

    **Cooling: -Indoor Temperature27C(80.6F) DB/19C(66.2F)WB

    -Outdoor Temperature46C(114.8F)DB/ 24C(75.2F)WB

    -Heating Temperature: Indoor 20C(68F)DB/15C(59F) WB

    Outdoor 7C(44.6F)DB/6C(42.8F) WB

    -Piping Length : Interconnected PipeLength = 7.5m

    -Difference Limit ofElevation (Outdoor ~ Indoor Unit)is Zero.

    2. TheMaximumcombination ratio is130%.

    3. Wiringcable sizemust comply with theapplicable local and national codes.

    And Electriccharacteristics chapter should beconsidered for electrical work and design.

    Especially thepower cable and circuit breaker should beselected in accordancewith that.

    4. Dueto our policy ofinnovation somespecications may bechanged without notication.

    5. Sound Level Valuesare measured at Anechoicchamber. Therefore,these values

    can beincreased owingto ambient conditionsduring operation

    6. Power factor could vary lessthan 1% according to theoperating conditions.

    Notes:1. Capacitiesareb ased on thefollowing conditions:

    -*Cooling : -Indoor Temperature27C(80.6F) DB/19C(66.2F)WB

    -Ou tdoor Temperature35C(95F) DB/24C(75.2F)WB

    **Cooling: -Indoor Temperature27C(80.6F) DB/19C(66.2F)WB

    -Outdoor Temperature46C(114.8F) DB/24C(75.2F)WB

    -Heating Temperature: Indoor 20C(68F)DB/15C(59F) WB

    Outdoor 7C(44.6F)DB/6C(42.8F) WB

    -Piping Length : Interconnected PipeLength =7.5m

    -Difference Limit ofElevation (Outdoor ~ Indoor Unit)isZero.

  • 8/10/2019 LG Multi V VRF for Middle East Market

    15/862726

    OUTDOORUNITS

    HEATPUMP

    ARUN440LTH4 ARUN460LTH4

    HP 44 46

    Model Name Combination unit ARUN440LTH4 ARUN460LTH4

    Independent unit ARUN160LTH4 ARUN160LTH4

    ARUN160LTH4 ARUN160LTH4

    ARUN120LTH4 ARUN140LTH4

    Capacity (Rated) 1)

    *Cooling

    RT 35.0 36.5

    kW 123.2 128.8

    Btu/h 420,500 439,600

    **Cooling

    RT 31.1 33.0

    kW 109.1 115.9

    Btu/h 372,400 395,600

    Heating

    RT 39.1 40.9

    kW 137.8 143.9

    Btu/h 469,200 491,000

    Input (Rated) 1)*Cooling kW 28.67 29.55

    **Cooling kW 36.31 38.26

    Heating kW 29.80 31.19

    COP 1)*Cooling kW / kW 4.30 4.36

    **Cooling kW / kW 3.01 3.03

    Heating kW / kW 4.62 4.61

    Power Factor Rated - 0.92 0.92

    C as in g Co lo r Wa rm G ray / M or ni ng G ray W ar m Gr ay / M or ni ng G ra y

    Heat Exchanger Gold n Gold n

    Compressor

    Type Hermetically Sealed Scroll Hermetically Sealed Scroll

    Piston Displacement cm3

    /rev (43.8 x 2) x 2 + (62.1) (43.8 x 2) x 3N umber of Revolu tion rev/ mi n (3,600 x 2) x 2 +(3,600) (3,600 x 2) x 3

    Motor Output x Number W x No. (4,200 x 2) x 2 + (5,300 x 1) (4,200 x 2) x 3

    Starting Method Inverter Inverter

    Oil Type FVC68D(PVE) FVC68D(PVE)

    Fan

    Type Propeller fan Propeller fan

    Motor Output x Number W (600 x 2) x 3 (600 x 2) x 3

    Air Flow Ratem3/min (290) x 3 (290) x 3

    ft3/min (10,200) x 3 (10,200) x 3

    Drive DC INVERTER DC INVERTER

    Discharge Side / Top TOP TOP

    PipingC onnectionsLiquid mm (inch) 19.05(3/4) 19.05(3/4)

    Gas mm (inch) 41.3(1-5/8) 41.3(1-5/8)

    Dimensions(W xHx D)

    mm (1,240 x 1,680 x 760) x 3 (1,240 x 1,680 x 760) x 3

    i nc h ( 48 -1 3/ 16 6 6- 5/ 32 2 9- 29 /3 2) x 3 ( 48 -1 3/ 16 6 6- 5/ 32 2 9- 29 /3 2) x 3

    Net Weightkg (280) x 2 + (235) (280) x 2 + (270)

    lbs (617) x 2 + (518) (617) x 2 + (595)

    Sound PressLevelCooling dB(A) 64.1 64.3

    Heating dB(A) 64.6 64.8

    Sound Power Level dB(A) 84.1 84.3

    Protection Devices

    Hig h pressure protection -High pressuresensor,

    High pressureswitch

    High pressuresensor,

    High pressureswitch

    Comperssor/Fan -Over-heat protection/

    Fan driver overload protector

    Over-heat protection/

    Fan driver overload protector

    Inverter -Over-heat protection,

    Over-current protection

    Over-heat protection,

    Over-current protection

    Communication Cable No. x mm2 (VCTF-SB) 2C 1.0 ~ 1.5 2C 1.0 ~ 1.5

    Refrigerant

    Refrigerant name R410A R410A

    Precharged Amount kg (10.0) x 2 + (8.5) (10.0) x 2 + (8.5)

    lbs (22.0) x 2 + (18.7) (22.0) x 2 + (18.7)

    C on tr ol E le ct ro ni c Ex pa ns io n V al ve E le ct ro ni c Ex pa ns io n V al ve

    Power SupplyV, , Hz 380-415, 3, 50 380-415, 3, 50

    V, , Hz 400, 3, 60 400, 3, 60

    Number ofmaxmumconnectable indoor units 2) 64 64

    HP 48

    Model Name Combination unit ARUN480LTH4

    Independent unit ARUN160LTH4

    ARUN160LTH4

    ARUN160LTH4

    Capacity (Rated) 1)

    *Cooling

    RT 38.1

    kW 134.4

    Btu/h 458,700

    **Cooling

    RT 34.5

    kW 120.9

    Btu/h 412,800

    Heating

    RT 42.6

    kW 150.0

    Btu/h 511,800

    Input (Rated) 1)*Cooling kW 31.14

    **Cooling kW 40.35

    Heating kW 32.76

    COP 1)*Cooling kW / kW 4.32

    **Cooling kW / kW 3.00

    Heating kW / kW 4.58

    Power Factor Rated - 0.92

    CasingColor WarmGray /MorningGray

    Heat Exchanger Gold n

    Compressor

    Type Hermetically Sealed Scroll

    Piston Displacement cm3

    /rev (43.8 x 2) x 3Number ofRevolution rev/min (3,600x 2)x3

    Motor Output x Number W x No. (4,200 x 2) x 3

    StartingMethod Inverter

    Oil Type FVC68D(PVE)

    Fan

    Type Propeller fan

    Motor Output xNumber W (600x2)x 3

    Air Flow Ratem3/min (290) x 3

    ft3/min (10,200) x 3

    Drive DC INVERTER

    Discharge Side / Top TOP

    PipingConnectionsLiquid mm (inch) 19.05(3/4)

    Gas mm (inch) 41.3(1-5/8)

    Dimensions(W xHx D)

    mm (1,240 x 1,680 x 760) x 3

    inch (48-13/1666-5/32 29-29/32)x3

    Net Weightkg (280) x 3

    lbs (617) x 3

    Sound PressLevelCooling dB(A) 64.3

    Heating dB(A) 64.8

    Sound Power Level dB(A) 84.3

    Protection Devices

    High pressure protection - High pressure sensor, High pressure switch

    Comperssor/ Fan - Over-heat protection / Fan driver overload protector

    Inverter - Over-heat protection, Over-current protection

    Communication Cable No. x mm2 (VCTF-SB) 2C 1.0 ~ 1.5

    Refrigerant

    Refrigerant name R410A

    Precharged Amount kg (10.0) x 3

    lbs (22.0) x 3

    Control ElectronicExpansion Valve

    Power SupplyV,,Hz 380-415,3,50

    V,,Hz 400,3,60

    Number ofmaxmumconnectable indoor units 2) 64

    ARUN480LTH4

    2. TheMaximum combination ratio is130%.

    3. Wiringcable sizemust comply with theapplicable local and national codes.

    And Electriccharacteristicschapter should be considered for electrical work and design.

    Especially thepower cable and circuit breaker should beselected in accordancewith that.

    4. Dueto our policy ofinnovation somespecications may bechanged without notication.

    5. Sound Level Valuesare measured at Anechoicchamber. Therefore,these values

    can beincreased owingto ambient conditionsduring operation

    6. Power factor could vary lessthan 1% accordingto theoperatingconditions.

    Notes:1. Capacitiesarebased on thefollowingconditions:

    -*Cooling : -Indoor Temperature27C(80.6F) DB/19C(66.2F)WB

    -Outdoor Temperature35C(95F) DB/24C(75.2F)WB

    **Cooling: -Indoor Temperature27C(80.6F) DB/19C(66.2F)WB

    -Outdoor Temperature46C(114.8F)DB/ 24C(75.2F)WB

    -Heating Temperature: Indoor 20C(68F)DB/15C(59F) WB

    Outdoor 7C(44.6F)DB/6C(42.8F) WB

    -Piping Length : Interconnected PipeLength = 7.5m

    -Difference Limit ofElevation (Outdoor ~ Indoor Unit)is Zero.

    2. TheMaximumcombination ratio is130%.

    3. Wiringcable sizemust comply with theapplicable local and national codes.

    And Electriccharacteristics chapter should beconsidered for electrical work and design.

    Especially thepower cable and circuit breaker should beselected in accordancewith that.

    4. Dueto our policy ofinnovation somespecications may bechanged without notication.

    5. Sound Level Valuesare measured at Anechoicchamber. Therefore,these values

    can beincreased owingto ambient conditionsduring operation

    6. Power factor could vary lessthan 1% according to theoperating conditions.

    Notes:1. Capacitiesareb ased on thefollowing conditions:

    -*Cooling : -Indoor Temperature27C(80.6F) DB/19C(66.2F)WB

    -Ou tdoor Temperature35C(95F) DB/24C(75.2F)WB

    **Cooling: -Indoor Temperature27C(80.6F) DB/19C(66.2F)WB

    -Outdoor Temperature46C(114.8F) DB/24C(75.2F)WB

    -Heating Temperature: Indoor 20C(68F)DB/15C(59F) WB

    Outdoor 7C(44.6F)DB/6C(42.8F) WB

    -Piping Length : Interconnected PipeLength =7.5m

    -Difference Limit ofElevation (Outdoor ~ Indoor Unit)isZero.

  • 8/10/2019 LG Multi V VRF for Middle East Market

    16/862928

    OUTDOORUNITS

    MINI

    Appropriate for mid-sized ofces, shops, and high-end residential spaces

    High BLDC inverter compressor is used for optimal load and operation.

    Inverter control technology provides various types of system.

    High Cooling and Heating Efciency

    Long Piping Length

    Easy Service

    COP

    3, 380V

    HP Cooling Heating

    4 4.3 4.3

    5 4.0 4.1

    6 3.7 3.9

    300m

    Total piping length

    50m (40m*)

    Heightdifference

    between

    ODU~IDU

    15mHeight

    difference

    between

    IDU~IDU

    Longest piping length

    40m (90m**)Longest

    piping lenth

    after

    1st branch

    Total piping length 300m

    Longest piping length (Equivalent)150m**(175m*)

    Longest piping length after 1st branch 40m (90m**)

    Height difference between ODU~IDU 50m (40m*)

    Height di ffer ence between ID U~IDU 15m

    * Equivalent** Conditional application

    2

    3

    Quick and efcient installation of MULTI V MINI can provide the best solution for small ofces and shops.

    Compact design and easy to service

    - Remove 3 screws for service

    - Front panel removal system

    2

    Easy service

    3 pieces of screw

    1 Way

    Inner service valve

    - 4 Way piping is possible(Front, Rear, Right, Down)

    - Excellent exterior

    3

    4 Way

    Convenient Handles1

    Axial fan provides high efciency for heat exchange through a high air ow.

    High Efciency Outdoor Axial Fan

    Applying High efc iency Axia l Fan Mo re powerful Heat exchange efciency

    28.026.625.223.822.421.0

    19.618.216.815.414.012.6

    11.29.88.47.05.64.2

    2.81.40.0

    460 520

    MULTI V MINI provides the optimal solution for small ofces and shops.

    Compact Size

    Foot print area

    Conventional MULTI V MINI

    46%Reduction

    806mm

    730mm

    330mm

    950mm

    5, 6 HP

    4, 5, 6 HP

    1

  • 8/10/2019 LG Multi V VRF for Middle East Market

    17/86

    3130

    ARUN40LH2A ARUN50LH2A ARUN60LH2A

    OUTDOORUNITS

    MINI

    HP 4

    Model ARUN40LH2A

    Capacity

    *Cooling

    RT 3.2

    kW 11.2

    kcal/h 9,632

    Btu/h 38,200

    **Cooling(46)

    RT 2.6

    kW 9.2

    kcal/h 7,910

    Btu/h 31,400

    Heating

    RT 3.6

    kW 12.5

    kcal/h 10,750

    Btu/h 42,700

    Power Supply , V, Hz3 / 380~415 / 50

    3 / 380 / 60

    Dimensions (WxHxD) mm 950x1380x330inch 37.4x54.3x13.0

    Net Weight kg 107

    Casing color Warm Gray

    Max. Number of Connectable Indoor Units 1

    Ratio of the Connectable Indoor Units 100%

    Compressor (#1)

    Type DC INV Rotary

    Piston Displacement m3/h 42.5

    Number of Revolutions r.p.m 3,600x1

    Oil charge volume cc 1,300

    Oil Type FVC68D

    Refrigerant

    Type R410A

    Charge kg 3.0

    Control EEV

    Heat Exchanger Gold Fin

    Fan

    Drive BLDC Inverter

    Discharge Direction(Side/Top) Side

    Air Flow Rate x No. of Fan m3/min 110

    Motor output kW 0.124x2

    Sound level Sound Pressure dB(A)3 50/52

    Pipe ConnectionsLiquid mm(inch) 9.52(3/8)

    Gas mm(inch) 15.88(5/8)

    HP 5 6

    Model ARUN50LH2A ARUN60LH2A

    Capacity

    *Cooling

    RT 4.0 4.4

    kW 14.0 15.5

    kcal/h 12,040 13,330

    Btu/h 47,800 52,900

    **Cooling(46)

    RT 2.9 3.3

    kW 10.3 11.5

    kcal/h 8,860 9,890

    Btu/h 35,100 39,200

    Heating

    RT 4.5 5.1

    kW 16.0 18.0

    kcal/h 13,760 15,480

    Btu/h 54,600 61,400

    Power Supply , V, Hz3 / 380~415 / 50

    3 / 380 / 603 / 380~415 / 50

    3 / 380 / 60

    Dimensions (WxHxD) mm 950x1380x330 950x1380x330inch 37.4x54.3x13.0 37.4x54.3x13.0

    Net Weight kg 107 107

    Casing color Warm Gray Warm Gray

    Max. Number of Connectable Indoor Units 1 1

    Ratio of the Connectable Indoor Units 100% 100%

    Compressor (#1)

    Type DC INV Rotary DC INV Rotary

    Piston Displacement m3/h 42.5 42.5

    Number of Revolutions r.p.m 3,600x1 3,600x1

    Oil charge volume cc 1,300 1,300

    Oil Type FVC68D FVC68D

    Refrigerant

    Type R410A R410A

    Charge kg 3.0 3.0

    Control EEV EEV

    Heat Exchanger Gold Fin Gold Fin

    Fan

    Drive BLDC Inverter BLDC Inverter

    Discharge Direction(Side/Top) Side Side

    Air Flow Rate x No. of Fan m3/min 110 110

    Motor output kW 0.124x2 0.124x2

    Sound level Sound Pressure dB(A)3 51/53 52/54

    Pipe ConnectionsLiquid mm(inch) 9.52(3/8) 9.52(3/8)

    Gas mm(inch) 15.88(5/8) 19.05(3/4)

    Note :

    1. Capacities are based on the following conditions

    Cooling - Indoor temp. 27C(80.6F) DB/19C(66.2F) WB Cooling - Indoor temp. 27C(80.6F) DB/19C(66.2F) WB

    Outdoor temp. 35C(95F) DB/24C(75.2F) WB Outdoor temp. 46C(114.8F) DB/24C(75.2F) WB

    Interconnecting piping length 7.5m

    Level difference of zero

    Heating -Indoor Temperature 20C(68F) DB/15C(59F) WB

    - Outdoot Temperature 7C(44.6F) DB/6C(42.8F) WB

    2. Capacities are net capacities

    3. EEV : Electronic Expansion Valve

    4. Wiring cable size must comply with the applicable local and national code.

    5. Due to our policy of innovation some specication may be cha nged without prior notication

    * ( ) : equivalent length

    ** Conditional Application

    Note :

    1. Capacities are based on the following conditions

    Cooling - Indoor temp. 27C(80.6F) DB/19C(66.2F) WB Cooling - Indoor temp. 27C(80.6F) DB/19C(66.2F) WB

    Outdoor temp. 35C(95F) DB/24C(75.2F) WB Outdoor temp. 46C(114.8F) DB/24C(75.2F) WB

    Interconnecting piping length 7.5m

    Level difference of zero

    Heating -Indoor Temperature 20C(68F) DB/15C(59F) WB

    - Outdoot Temperature 7C(44.6F) DB/6C(42.8F) WB

    2. Capacities are net capacities

    3. EEV : Electronic Expansion Valve

    4. Wiring cable size must comply with the applicable local and national code.

    5. Due to our policy of innovation some specication may be changed without prior notication

    * ( ) : equivalent length

    ** Conditional Application

  • 8/10/2019 LG Multi V VRF for Middle East Market

    18/86

    3332

    OUTDOORUNITS

    HEATPUMP

    SUPERIOR EFFICIENCY VIA

    THE INTEGRATION OF SMART

    TECHNOLOGIESTodays businesses demand highly efcient temperature

    control solutions, capable of providing optimal energy savings

    without sacricing performance. When it comes to cooling

    and heating a multi-storey or high-rise building, water cooled

    HVAC systems have become the solution of choice.

    Offering several performance enhancements and greater

    installation versatility, LGs MULTI V WATER IV combines

    intelligent functions with advanced inverter technology;

    boosting both energy efciency and operational range.

    This superior water cooled system signicantly improves

    return on investment (ROI) with a stellar 5.9 coefcient of

    performance (COP) and an equally impressive independent

    part load value (IPLV) of 6.73.

    Along with outstanding energy efciency, the new solution

    comes with a range of truly smart features, including

    optimized cycle composition and smart control. For ease of

    installation and better economy of space, MULTI V WATER IV

    is both lighter in weight and smaller in overall size.

    LG, a leading innovator in HVAC technologies, will continue to

    develop and manufacture high performance, energy efcient

    solutions for the benet of its growing global customer-base.

    Adopting a water-based cooling method, this unit optimizes

    performance in comparison to compressor capacity. It also

    ensures heat exchange performance for high-rise buildings,

    thus allowing electrical-savings.

    Regardless of outdoor temperature and other environmental

    conditions, MULTI V WATER IV is the optimal solution for

    high-rise buildings.

    Economical,Highly EfcientSystem

    High EfciencySystem Regardless ofExternal Conditions

    12%

    WATER

    WindOutside Temp.

    1400

    1600

    1800

    2000

    1000

    1200

    600

    800

    200

    400

    MULTI V WATER IVPrevious Model

    Source : LG Energy Estimate Program (LEEP)

    simulation data-5th oor building in Paris, France

    Powerinput(kWh)

    12%AverageSaving

  • 8/10/2019 LG Multi V VRF for Middle East Market

    19/86

    3534

    OUTDOORUNITS

    WATERHEATPUMP

    With a fourth generation inverter compressor, the MULTI V WATER IV boasts top-class energy efciency.

    LGs 4th Generation Inverter Compressor

    Extended Compressor

    Speed 20Hz ~ 140Hz

    - Rapid operation response

    - Capable of reaching required

    temperature quickly

    - Increase part load efciency

    HiPORTM(High Pressure Oil Return)

    - Eliminating loss in suction gas by

    returning oil directly to compressor

    - Resolve compressor efciency

    loss caused by oil return

    Smart Oil Return

    - Oil recovery occurs only when required

    - Enhanced compressor reliability &

    user comfort

    10 HP 4EA Per Each

    20 HP 2EA Per Each

    Easier to transport and install thanks to 13% reduction in unit size and 15% reduction in overall weight.

    ATER

    ATER

    ATER

    ATER

    WATER

    ATER

    WATER

    ATER

    The optimal design of the compact, lightweight outdoor unit enables double stacking, which results in 50% savings on

    installation space.

    Compact Size

    Light Weight

    MULTI V WATER IVCompany B

    1,560 550 750 500

    * Double stacking oor area** 40HP Capacity Installation scene

    * 40HP Capacity Installation scene

    15%Reduced

    ATER

    ATER

    ATER

    ATER

    ATER

    ATER

    ATER

    WATER

    The world's rst variable water ow control system for water cooled VRF system. LG applied variable water ow control

    system to reduce circulation pump energy consumption, by controlling embedded kit.

    Variable Water Flow Control Kit (Option)

    WATER

    InverterPump

    Variable WaterFlow Control Valve

    Cooling Tower DC 0~10V

    River / Sea

    Geothermal

    Note

    1. Location: France

    2. Total operationn time: 1,344hr

    3. Indoor temperature: normal ofce environment

    4. Outdoor temperature: average summer temperature

    5. Inlet ow temperature: approximately 30oC

    - Adjust water ow by pressure control after connecting

    PCB in the existing MULTI V WATER Outdoor unit

    Efciency(EER)

    TotalWaterFlow(m3)

    5.5

    5.0

    MULTI V WATER IV

    VariableWater Flow

    Previous Model

    ConstantWater Flow

    10%

    4,439

    15,456

    71%

    * Comparison between 10HP in cooling mode

    5% HEX Optimization

    1% Cycle CompositionImprovement

    1% Inverter Control

    1% Active Oil Control

    1% HIPOR

    WORLD'S SMALLEST SIZEIts reduced size and lighter weight allow increased freedom in choosing a

    location for external unit as well as enhanced utilization of indoor space

    EXCEPTIONAL EFFICIENCY

    Worlds rst class, rated and part load efciency

    127kgMULTI V WATER IV

    154kgPrevious Model

    * Based on 10HP

  • 8/10/2019 LG Multi V VRF for Middle East Market

    20/86

  • 8/10/2019 LG Multi V VRF for Middle East Market

    21/86

    3938

    OUTDOORUNITS

    HEATPUMP

    Reference Site

    Bouygues Construction

    Co. HQ building

    New Water-Cooled VRF System

    Combines Two Great HVAC Systems

    This innovative variable water ow technology looks great in

    the lab, but how does it work in actual practice? As a matter

    of fact, it turns out working extremely well. LGs water-cooled

    VRF system, MULTI V WATER II, was used in the remodeling of

    Bouygues Construction Ofce in Paris. The French industrial

    group. The ambitious remodeling project became the worlds

    rst site using LGs water-cooled VRF. It utilized 162 outdoor

    units which is 2,000 horsepower.

    Keeping Bouygues

    Construction Cool

    From the start, the Bouygues Construction ofce was designed

    environment-friendly.

    It has a glass atrium in the center with a green roof and solar

    blinds. The building acquired the NF Btiments tertiares

    Demarch HQE label, which certies high performance level in

    three different environmental areas at least.

    The water-cooled VRF system was the best option for who

    wants high energy saving ofce building.

    Bouygues Construction (France) is a global player of building, civil works, energy and

    services markets and operate its business in more than 80 countries.

    LocationParis, France

    Product MULTI V WATER II

    Paris

  • 8/10/2019 LG Multi V VRF for Middle East Market

    22/86

    4140

    HP 8 10 12

    Model Combination unit ARWN080LAS4 ARWN100LAS4 ARWN120LAS4

    Independent unit A RW N08 0L AS 4 A RW N1 00L AS 4 A RW N1 20 LAS 4

    CapacityCooling Nom kW 22.4 28 33.6

    Heating Nom kW 25.2 31.5 37.8

    Power InputCooling Nom kW 3.86 5.09 6.46

    Heating Nom kW 4.20 5.34 6.75

    EER 5.80 5.50 5.20

    COP 6.00 5.90 5.60

    Operation RangeCooling Min~Max C DB 10C ~ 45C 10C ~ 45C 10C ~ 45C

    Heating Min~Max C DB -5C ~ 45C -5C ~ 45C -5C ~ 45C

    CompressorType Hermetically Sealed Scroll Hermetically Sealed Scroll Hermetically Sealed Scroll

    Number of Compressor 1 1 1

    Sound Pressure (Cooling) Nom dBA 47 50 56

    Sound Pressure (Heating) Nom dBA 51 53 56

    Sound Power (Cooling) Nom dBA 59 62 68

    Sound Power (Heating) Nom dBA 63 65 68

    Dimensions WxHxD mm (755 997 500) 1 (755 997 500) 1 (755 997 500) 1

    Net Weight kg 127 x 1 127 x 1 127 x 1

    Refrigerant

    Type R410A R410A R410A

    Charge kg 5.8 5.8 5.8

    Control EEV EEV EEV

    Refrigerant OilType FVC68D(PVE) FVC68D(PVE) FVC68D(PVE)

    Control cc 1,200 1,200 1,200

    Power Supply /V/Hz 3 / 380 - 415 / 50 3 / 380 - 415 / 50 3 / 380 - 415 / 50

    Transmission Cable (VCTF-SB) No.xmm 1.0 ~1.5 x 2C 1.0 ~1.5 x 2C 1.0 ~1.5 x 2C

    Piping Length

    Total Max m 300(500)* 300(500)* 300(500)*

    Actual Longest Piping Length Max m 150(200)* 150(200)* 150(200)*

    After 1st Y branch Max m 40(90)* 40(90)* 40(90)*

    Piping Level DifferenceIDU-ODU Max m 50 50 50

    IDU-IDU Max m 40 40 40

    Piping ConnectionLiquid mm(inch) 9.52(3/8) 9.52(3/8) 12.7(1/2)

    Gas mm(inch) 22.2(7/8) 22.2(7/8) 25.4(1)

    Number of Outdoor Units 1 1 1

    Number of Connectable Indoor Units Max 13(20) 16(25) 20(30)

    Ratio of the Connectable Indoor Units Min-Max 50 ~ 200% 50 ~ 200% 50 ~ 200%

    Heat Exchanger

    Type Stainless Steel Plate Stainless Steel Plate Stainless Steel Plate

    Pressure Resistance Max kgf/cm 45 45 45

    Head Loss kPa 10.7 15.8 21.8

    Rated Water Flow LPM 77 96 116

    Water Connection pipe

    Inlet mm(inch) PT 40 PT 40 PT 40

    Outlet mm(inch) PT 40 PT 40 PT 40

    Drain Outlet mm 20 20 20

    HP 14 16 18 20

    Model Combination unit ARWN140LAS4 ARWN160LAS4 ARWN180LAS4 ARWN200LAS4

    Independent unit ARWN140LAS4 ARWN160LAS4 ARWN180LAS4 ARWN200LAS4

    CapacityCooling Nom kW 39.2 44.8 50.4 56

    Heating Nom kW 44.1 50.4 56.7 63

    Power InputCooling Nom kW 7.84 8.15 9.69 11.2

    Heating Nom kW 8.17 8.54 10.13 11.67

    EER 5.00 5.50 5.20 5.00

    COP 5.40 5.90 5.60 5.40

    Operation RangeCooling Min~Max C DB 10C ~ 45C 10C ~ 45C 10C ~ 45C 10C ~ 45C

    Heating Min~Max C DB -5C ~ 45C -5C ~ 45C -5C ~ 45C -5C ~ 45C

    CompressorType HermeticallySealedScroll HermeticallySealedScroll HermeticallySealedScroll HermeticallySealedScroll

    Number of Compressor 1 1 1 1

    Sound Pressure (Cooling) Nom dBA 58 53 55 54

    Sound Pressure (Heating) Nom dBA 57 57 56 60

    Sound Power (Cooling) Nom dBA 70 65 67 66

    Sound Power (Heating) Nom dBA 69 69 68 72

    Dimensions WxHxD mm (755997500)1 (755997500)1 (755997500)1 (755997500)1

    Net Weight kg 127 x 1 140 x 1 140 x 1 140 x 1

    Refrigerant

    Type R410A R410A R410A R410A

    Charge kg 5.8 3.0 3.0 3.0

    Control EEV EEV EEV EEV

    Refrigerant OilType FVC68D(PVE) FVC68D(PVE) FVC68D(PVE) FVC68D(PVE)

    Control cc 1,200 1,400 1,400 1,400

    Power Supply /V/Hz 3 / 380 - 415 / 50 3 / 380 - 415 / 50 3 / 380 - 415 / 50 3 / 380 - 415 / 50

    Transmission Cable (VCTF-SB) No.xmm 1 .0 ~ 1. 5 x 2 C 1 .0 ~ 1. 5 x 2 C 1. 0 ~1 .5 x 2 C 1 .0 ~ 1. 5 x 2 C

    Piping Length

    Total Max m 300(500)* 300(500)* 300(500)* 300(500)*

    Actual Longest Piping Length Max m 150(200)* 150(200)* 150(200)* 150(200)*

    After 1st Y branch Max m 40(90)* 40(90)* 40(90)* 40(90)*

    Piping Level DifferenceIDU-ODU Max m 50 50 50 50

    IDU-IDU Max m 40 40 40 40

    Piping ConnectionLiquid mm(inch) 12.7(1/2) 12.7(1/2) 12.7(1/2) 12.7(1/2)

    Gas mm(inch) 25. 4(1) 28.58(1- 1/8) 28.58(1-1/8) 28.58(1-1/8)

    Number of Outdoor Units 1 1 1 1

    Number of Connectable Indoor Units Max 23(35) 26(40) 29(45) 32(44)

    Ratio of the Connectable Indoor Units Min-Max 50 ~ 200% 50 ~ 200% 50 ~ 200% 50 ~ 200%

    Heat Exchanger

    Type Stainless Steel Plate Stainless Steel Plate Stainless Steel Plate Stainless Steel Plate

    Pressure Resistance Max kgf/cm 45 45 45 45

    Head Loss kPa 28.6 19.4 24.0 30.1

    Rated Water Flow LPM 135 154 173 192

    Water Connection pipe

    Inlet mm(inch) PT 40 PT 40 PT 40 PT 40

    Outlet mm(inch) PT 40 PT 40 PT 40 PT 40

    Drain Outlet mm 20 20 20 20

    Note :

    1. Capacities and Inputs are based on the following conditions

    Cooling : Indoor temp. 27C (80.6F) DB/19C(66.2F) WB, Water inlet temp. 30C(86F), Interconnecting piping length 7.5m, Level difference of zero

    Heating : Indoor temp. 20C(68F) DB - Water inlet temp. 20C(68F)

    2. Capacities are net capacities

    3. Due to our policy of innovation some specications may be changed without notication

    4. EEV : Electronic Expansion Valve

    5. Add an anti freeze to circulation water when outside units is operating undet 10C (50F), and change the DIP switch on main PCB.(For more information oninstallation section.)

    * ( ) : Conditional application

    Note :

    1. Capacities and Inputs are based on the following conditions

    Cooling : Indoor temp. 27C (80.6F) DB/19C(66.2F) WB, Water inlet temp. 30C(86F), Interconnecting piping length 7.5m, Level difference of zero

    Heating : Indoor temp. 20C(68F) DB - Water inlet temp. 20C(68F)

    2. Capacities are net capacities

    3. Due to our policy of innovation some specications may be changed without notication

    4. EEV : Electronic Expansion Valve

    5. Add an anti freeze to circulation water when outside units is operating undet 10C (50F), and change the DIP switch on main PCB.(For more information oninstallation section.)

    * ( ) : Conditional application

    ARWN080LAS4 ARWN100LAS4 ARWN120LAS4

    ARWN140LAS4 ARWN160LAS4

    ARWN180LAS4 ARWN200LAS4

    OUTDOORUNITS

    WATERHEATPUMP

  • 8/10/2019 LG Multi V VRF for Middle East Market

    23/86

    4342

    HP 26 28

    Model Combination unit ARWN260LAS4 ARWN280LAS4

    Independent unit ARWN140LAS4 ARWN140LAS4

    ARWN120LAS4 ARWN140LAS4

    CapacityCooling Nom k W 72.8 78.4

    Heating Nom k W 81.9 88.2

    Power InputCooling Nom kW 14.3 15.68

    Heating Nom kW 14.92 16.34

    EER 5.09 5.00

    COP 5.49 5.40

    Operation RangeCooling Min~Max C DB 10C ~ 45C 10C ~ 45C

    Heating Min~Max C DB -5C ~ 45C -5C ~ 45C

    CompressorType Hermetically Sealed Scroll Hermetically Sealed Scroll

    Number of Compressor 2 2

    Sound Pressure (Cooling) Nom dBA 59 59

    Sound Pressure (Heating) Nom dBA 58 58

    Sound Power (Cooling) Nom dBA 72 72

    Sound Power (Heating) Nom dBA 71 71

    Dimensions WxHxD mm (755 997 500) x 2 (755 997 500) x 2Net Weight kg 127 x 3 127 x 2

    Refrigerant

    Type R410A R410A

    Charge kg 5.8 + 5.8 5.8 + 5.8

    Control EEV EEV

    Refrigerant OilType FVC68D(PVE) FVC68D(PVE)

    Control cc 1,200 + 1,200 1,200 + 1,200

    Power Supply /V/Hz 3 / 380 - 415 / 50 3 / 380 - 415 / 50

    Transmission Cable (VCTF-SB) No.xmm 1.0 ~1.5 x 2C 1.0 ~1.5 x 2C

    Piping Length

    Total Max m 300(500)* 300(500)*

    Actual Longest Piping Length Max m 150(200)* 150(200)*

    After 1st Y branch Max m 40(90)* 40(90)*

    Piping Level DifferenceIDU-ODU Max m 50 50

    IDU-IDU Max m 40 40

    Piping ConnectionLiquid mm(inch) 19.05(3/4) 19.05(3/4)

    Gas mm(inch) 34.9(1-3/8) 34.9(1-3/8)

    Number of Outdoor Units 2 2

    Number of Connectable Indoor Units Max 42(52) 45(56)

    Ratio of the Connectable Indoor Units Min-Max 50 ~ 160% 50 ~ 160%

    Heat Exchanger

    Type Stainless Steel Plate Stainless Steel Plate

    Pressure Resistance Max kgf/cm 45 45

    Head Loss kPa 28.6 + 21.8 28.6 + 28.6Rated Water Flow LPM 135 + 116 135 + 135

    Water Connection pipe

    Inlet mm(inch) PT 40 + PT 40 PT 40 + PT 40

    Outlet mm(inch) PT 40 + PT 40 PT 40 + PT 40

    Drain Outlet mm 20 20

    HP 22 24

    Model Combination unit ARWN220LAS4 ARWN240LAS4

    Independent unit ARWN120LAS4 ARWN120LAS4

    ARWN100LAS4 ARWN120LAS4

    CapacityCooling Nom kW 61.6 67.2

    Heating Nom kW 69.3 75.6

    Power InputCooling Nom kW 11.55 12.92

    Heating Nom kW 12.09 13.5

    EER 5.33 5.20

    COP 5.73 5.60

    Operation RangeCooling Min~Max C DB 10C ~ 45C 10C ~ 45C

    Heating Min~Max C DB -5C ~ 45C -5C ~ 45C

    CompressorType Hermetically Sealed Scroll Hermetically Sealed Scroll

    Number of Compressor 1 2

    Sound Pressure (Cooling) Nom dBA 57 57

    Sound Pressure (Heating) Nom dBA 57 57

    Sound Power (Cooling) Nom dBA 70 70

    Sound Power (Heating) Nom dBA 70 70

    Dimensions WxHxD mm (755 997 500) x 2 (755 997 500) x 2Net Weight kg 127 x 2 127 x 2

    Refrigerant

    Type R410A R410A

    Charge kg 5.8 + 5.8 5.8 + 5.8

    Control EEV EEV

    Refrigerant OilType FVC68D(PVE) FVC68D(PVE)

    Control cc 1,200 + 1,200 1,200 + 1,200

    Power Supply /V/Hz 3 / 380 - 415 / 50 3 / 380 - 415 / 50

    Transmission Cable (VCTF-SB) No.xmm 1.0 ~1.5 x 2C 1.0 ~1.5 x 2C

    Piping Length

    Total Max m 300(500)* 300(500)*

    Actual Longest Piping Length Max m 150(200)* 150(200)*

    After 1st Y branch Max m 40(90)* 40(90)*

    Piping Level DifferenceIDU-ODU Max m 50 50

    IDU-IDU Max m 40 40

    Piping ConnectionLiquid mm(inch) 19.05(3/4) 19.05(3/4)

    Gas mm(inch) 34.9(1-3/8) 34.9(1-3/8)

    Number of Outdoor Units 2 2

    Number of Connectable Indoor Units Max 35(44) 39(48)

    Ratio of the Connectable Indoor Units Min-Max 50 ~ 160% 50 ~ 160%

    Heat Exchanger

    Type Stainless Steel Plate Stainless Steel Plate

    Pressure Resistance Max kgf/cm 45 45

    Head Loss kPa 21.8 + 15.8 21.8 + 21.8Rated Water Flow LPM 116 + 96 116 + 116

    Water Connection pipe

    Inlet mm(inch) PT 40 + PT 40 PT 40 + PT 40

    Outlet mm(inch) PT 40 + PT 40 PT 40 + PT 40

    Drain Outlet mm 20 20

    ARWN220LAS4 ARWN240LAS4 ARWN260LAS4 ARWN280LAS4

    OUTDOORUNITS

    WATERHEATPUMP

    Note :

    1. Capacities and Inputs are based on the following conditions

    Cooling : Indoor temp. 27C (80.6F) DB/19C(66.2F) WB, Water inlet temp. 30C(86F), Interconnecting piping length 7.5m, Level difference of zero

    Heating : Indoor temp. 20C(68F) DB - Water inlet temp. 20C(68F)

    2. Capacities are net capacities

    3. Due to our policy of innovation some specications may be changed without notication

    4. EEV : Electronic Expansion Valve

    5. Add an anti freeze to circulation water when outside units is operating undet 10C (50F), and change the DIP switch on main PCB.(For more information oninstallation section.)

    * ( ) : Conditional application

    Note :

    1. Capacities and Inputs are based on the following conditions

    Cooling : Indoor temp. 27C (80.6F) DB/19C(66.2F) WB, Water inlet temp. 30C(86F), Interconnecting piping length 7.5m, Level difference of zero

    Heating : Indoor temp. 20C(68F) DB - Water inlet temp. 20C(68F)

    2. Capacities are net capacities

    3. Due to our policy of innovation some specications may be chan ged without notication

    4. EEV : Electronic Expansion Valve

    5. Add an anti freeze to circulation water when outside units is operating undet 10C (50F), and change the DIP switch on main PCB.(For more information oninstallation section.)

    * ( ) : Conditional application

  • 8/10/2019 LG Multi V VRF for Middle East Market

    24/86

    4544

    HP 36 38 40

    Model Combination unit ARWN360LAS4 ARWN380LAS4 ARWN400LAS4

    Independent unit ARWN180LAS4 ARWN200LAS4 ARWN200LAS4

    A RW N1 80 LAS 4 A RW N18 0L AS 4 A RW N2 00 LA S4

    CapacityCooling Nom kW 100.8 106.4 112

    Heating Nom kW 113.4 119.7 126

    Power InputCooling Nom kW 19.38 20.89 22.4

    Heating Nom kW 20.26 21.8 23.34

    EER 5.20 5.09 5.00

    COP 5.60 5.49 5.40

    Operation RangeCooling Min~Max C DB 10C ~ 45C 10C ~ 45C 10C ~ 45C

    Heating Min~Max C DB -5C ~ 45C -5C ~ 45C -5C ~ 45C

    CompressorType Hermetically Sealed Scroll Hermetically Sealed Scroll Hermetically Sealed Scroll

    Number of Compressor 2 2 2

    Sound Pressure (Cooling) Nom dBA 56 56 55

    Sound Pressure (Heating) Nom dBA 57 61 61

    Sound Power (Cooling) Nom dBA 69 69 68

    Sound Power (Heating) Nom dBA 70 74 74

    Dimensions WxHxD mm (755 997 500) x 2 (755 997 500) x 2 (755 997 500) x 2Net Weight kg 140 x 2 140 x 2 140 x 2

    Refrigerant

    Type R410A R410A R410A

    Charge kg 3.0 + 3.0 3.0 + 3.0 3.0 + 3.0

    Control EEV EEV EEV

    Refrigerant OilType FVC68D(PVE) FVC68D(PVE) FVC68D(PVE)

    Control cc 1,400 + 1,400 1,400 + 1,400 1,400 + 1,400

    Power Supply /V/Hz 3 / 380 - 415 / 50 3 / 380 - 415 / 50 3 / 380 - 415 / 50

    Transmission Cable (VCTF-SB) No.xmm 1.0 ~1.5 x 2C 1.0 ~1.5 x 2C 1.0 ~1.5 x 2C

    Piping Length

    Total Max m 300(500)* 300(500)* 300(500)*

    Actual Longest Piping Length Max m 150(200)* 150(200)* 150(200)*

    After 1st Y branch Max m 40(90)* 40(90)* 40(90)*

    Piping Level DifferenceIDU-ODU Max m 50 50 50

    IDU-IDU Max m 40 40 40

    Piping ConnectionLiquid mm(inch) 19.05(3/4) 19.05(3/4) 19.05(3/4)

    Gas mm(inch) 41.3(1-5/8) 41.3(1-5/8) 41.3(1-5/8)

    Number of Outdoor Units 2 2 2

    Number of Connectable Indoor Units Max 58(64) 61(64) 64

    Ratio of the Connectable Indoor Units Min-Max 50 ~ 160% 50 ~ 160% 50 ~ 160%

    Heat Exchanger

    Type Stainless Steel Plate Stainless Steel Plate Stainless Steel Plate

    Pressure Resistance Max kgf/cm 45 45 45

    Head Loss kPa 24.0 + 24.0 30.1 + 24.0 30.1 + 30.1Rated Water Flow LPM 173 + 173 192 + 173 192 + 192

    Water Connection pipe

    Inlet mm(inch) PT 40 + PT 40 PT 40 + PT 40 PT 40 + PT 40

    Outlet mm(inch) PT 40 + PT 40 PT 40 + PT 40 PT 40 + PT 40

    Drain Outlet mm 20 20 20

    HP 30 32 34

    Model Combination unit ARWN300LAS4 ARWN320LAS4 ARWN340LAS4

    Independent unit ARWN160LAS4 ARWN180LAS4 ARWN200LAS4

    A RW N14 0L AS 4 A RW N1 40 LA S4 A RW N1 40L AS 4

    CapacityCooling Nom kW 84 89.6 95.2

    Heating Nom kW 94.5 100.8 107.1

    Power InputCooling Nom kW 15.99 17.53 19.04

    Heating Nom kW 16.71 18.3 19.84

    EER 5.25 5.11 5.00

    COP 5.66 5.51 5.40

    Operation RangeCooling Min~Max C DB 10C ~ 45C 10C ~ 45C 10C ~ 45C

    Heating Min~Max C DB -5C ~ 45C -5C ~ 45C -5C ~ 45C

    CompressorType Hermetically Sealed Scroll Hermetically Sealed Scroll Hermetically Sealed Scroll

    Number of Compressor 2 2 2

    Sound Pressure (Cooling) Nom dBA 59 59 59

    Sound Pressure (Heating) Nom dBA 58 58 61

    Sound Power (Cooling) Nom dBA 72 72 72

    Sound Power (Heating) Nom dBA 71 71 74

    Dimensions WxHxD mm (755 997 500) x 2 (755 997 500) x 2 (755 997 500) x 2Net Weight kg (140 x 1) + (127 x 1) (140 x 1) + (127 x 1) (140 x 1) + (127 x 1)

    Refrigerant

    Type R410A R410A R410A

    Charge kg 3.0 + 5.8 3.0 + 5.8 3.0 + 5.8

    Control EEV EEV EEV

    Refrigerant OilType FVC68D(PVE) FVC68D(PVE) FVC68D(PVE)

    Control cc 1,400 + 1,200 1,400 + 1,200 1,400 + 1,200

    Power Supply /V/Hz 3 / 380 - 415 / 50 3 / 380 - 415 / 50 3 / 380 - 415 / 50

    Transmission Cable (VCTF-SB) No.xmm 1.0 ~1.5 x 2C 1.0 ~1.5 x 2C 1.0 ~1.5 x 2C

    Piping Length

    Total Max m 300(500)* 300(500)* 300(500)*

    Actual Longest Piping Length Max m 150(200)* 150(200)* 150(200)*

    After 1st Y branch Max m 40(90)* 40(90)* 40(90)*

    Piping Level DifferenceIDU-ODU Max m 50 50 50

    IDU-IDU Max m 40 40 40

    Piping ConnectionLiquid mm(inch) 19.05(3/4) 19.05(3/4) 19.05(3/4)

    Gas mm(inch) 34.9(1-3/8) 34.9(1-3/8) 34.9(1-3/8)

    Number of Outdoor Units 2 2 2

    Number of Connectable Indoor Units Max 49(60) 52(64) 55