16
Lessons Learned in Model Validation for NERC Compliance usa.siemens.com/digitalgrid Unrestricted © Siemens Industry, Inc. 2018

Lessons Learned in Model Validation for NERC Compliance ... · Estimated and Operating capability curve (D-curve) Page 6 ... • Active & reactive power through the high voltage side

Embed Size (px)

Citation preview

Lessons Learned in Model Validation for NERC Compliance

usa.siemens.com/digitalgrid Unrestricted © Siemens Industry, Inc. 2018

Page 2

Unrestricted © Siemens Industry, Inc. 2018

Digital Grid | PTI

NERC Modeling, Data, and Analysis

MOD‐025‐2: Generator Real and Reactive Power Capability Demonstration

MOD‐026‐1: Verification of Models for Generator Excitation Control Systems

MOD‐027‐1: Verification of Models for Turbine/Governor and Load Control Functions, including validation of turbine droop and determination of governor’s deadband

Page 3

Unrestricted © Siemens Industry, Inc. 2018

Digital Grid | PTI

Unit Size for NERC Model Validation Requirement (MVA)

ERCOT Eastern Interconnection WECC

Individual Unit Plant Individual

Unit Plant Individual Unit Plant

MOD-25-2 >20 >75 >20 >75 >20 >75

MOD-26-1 >50 >75 >100 >100 >75 >75

MOD-27-1 >50 >75 >100 >100 >75 >75

Page 4

Unrestricted © Siemens Industry, Inc. 2018

Digital Grid | PTI

Siemens PTI Services

• Onsite technical assistance for performing the tests • Field tests data processing • Model validation (PSS®E/PSLF) • Verification of generator OC excitation curve and generating unit inertia

constant • Adjustment of controllers parameters • AVR and PSS tuning • Over- and Under-excitation limiter adjustment • V/Hz limiter adjustment • Development of user-written models

Page 5

Unrestricted © Siemens Industry, Inc. 2018

Digital Grid | PTI

MOD-025-2 Generator Tests

Estimated and Operating capability curve (D-curve)

Page 6

Unrestricted © Siemens Industry, Inc. 2018

Digital Grid | PTI

MOD-025-2 Generator Tests

Measurements: • Active & reactive power, voltage at unit terminals (point A) • Active & reactive power, voltage at the high voltage side of the GSU (point F) • Active & reactive power through the high voltage side of the auxiliary transformer (point B) • Voltage at the low voltage side of the tertiary winding (point C) • Active and reactive power at the high voltage side of the

GSU of the other units (point D)

Page 7

Unrestricted © Siemens Industry, Inc. 2018

Digital Grid | PTI

MOD-026-1 Generator Excitation Control System Model Verification

• Open-circuit dynamic response calibration

• Interconnected dynamic performance calibration

• Validate model parameters by comparing field test records against current PSS®E or PSLF dynamic models

Page 8

Unrestricted © Siemens Industry, Inc. 2018

Digital Grid | PTI

MOD-026-1 Generator Excitation Control System Model Verification

• Open-circuit dynamic response calibration

• Interconnected dynamic performance calibration

• Validate model parameters by comparing field test records against current PSS®E or PSLF dynamic models

Page 9

Unrestricted © Siemens Industry, Inc. 2018

Digital Grid | PTI

MOD-027-1 Turbine/Governor and Load Control Functions Model Verification

• Validation of the speed governor response for an on-line perturbation test with synthetic speed signal of ±0.2Hz

Power Plant Model Validation using PSS®E Playback Model

usa.siemens.com/digitalgrid Unrestricted © Siemens Industry, Inc. 2018

Page 11

Unrestricted © Siemens Industry, Inc. 2018

Digital Grid | PTI

PSS®E Playback Model PLBVFU1 Overview

• The PLBVFU1 model plays back a known set of voltage and frequency signals

• The PLBVFU1 model acts as a generator model

(with no excitation system or turbine-governor models)

• The played-in voltage and frequency signals must be included in a data input file

Page 12

Unrestricted © Siemens Industry, Inc. 2018

Digital Grid | PTI

PSS®E Playback Model Playback Model for Voltage Signal

Page 13

Unrestricted © Siemens Industry, Inc. 2018

Digital Grid | PTI

PSS®E Playback Model Playback Model for Frequency Signal

Page 14

Unrestricted © Siemens Industry, Inc. 2018

Digital Grid | PTI

PSS®E Playback Model Playback Model Example Test System

Playback generator

Unit to be tested

Page 15

Unrestricted © Siemens Industry, Inc. 2018

Digital Grid | PTI

PSS®E Playback Model Playback Model – PMU data vs. PSS®E simulation results

Page 16

Unrestricted © Siemens Industry, Inc. 2018

Digital Grid | PTI

Contact Us

Carlos Grande-Moran Principal Consultant Siemens Power Technologies International E-mail: [email protected]

Dinemayer Silva Staff Consultant Siemens Power Technologies International E-mail: [email protected]

usa.siemens.com/digitalgrid