Upload
helena-dawson
View
213
Download
0
Embed Size (px)
Citation preview
Lesson 6Lesson 6
VoltageVoltageDo we need to MEASURE it? ORDo we need to DETECT it?
Test LampsTest LampsNeon Test Pencils/ScrewdriversNeon Test Pencils/ScrewdriversVoltage ProbesVoltage ProbesSteinel Combi-CheckSteinel Combi-CheckAC Voltage ProbeAC Voltage Probe
VoltmeterVoltmeterMultimeterMultimeter
Clamp meterClamp meter
AnalogueAnalogue DigitalDigital Digital simulated AnalogueDigital simulated Analogue
Last known earthly residence of automotive fuse used to replace original fuse
Test leads survived intact
13.8 kV arced over to test probes
Test leads destroyed
250V fuse didn’t open in time
Poor quality leads and probes led to injury.
Probe tips burned off
Fingerprints burned into probes
Arc from transients (lightning, load switching)
Voltage contact while in continuity or resistance
Measuring voltage with test leads in current sockets
Shock from accidental contact with live components
Using meter or tester above rated voltage
Protection
Independent certification to meet CAT III-1000 V or CAT IV 600 V
Protection
Overload protection in Ω up to the meter’s volt rating
ProtectionHigh fault current rated fuses
Use meters / testers without current sockets
Protection
• Double insulated• Recessed / shrouded Plugs/Sockets• Finger guards• CAT III – 1000 V• Replace when damaged
Test Leads
IEC 61010
New standard for low voltage “test, measurement and control equipment”.
Provides much improved protection against “overvoltage impulse transients” - voltage spikes.
Basis for:ANSI/ISA-S82.01-94 (US)CAN C22.2 No. 1010.1-92 (CAN)EN61010-1:1993 (EUR)AS 61010.1:2003 (Testers)AS 61010.031:2004 (Leads)
The closer the location is to the power source, the higher the available fault current, the higher the category
CATEGORIES: CAT I to CAT IV The greatest danger from transients is in the high categories, because they
could trigger an arc blast
IMPULSE TESTING: No failure allowed Meters must be tested by being hit with a specified number of transients,
with specified peak voltages
• CAT IV
• CAT III
• CAT II
• CAT I
“Origin of installation”Supply Authority level and any outside cable runs
Distribution wiring, including Consumer mainsand Sub-circuits; permanently installed loads.
Socket Outlets; plug-in loads.
Protected electronic circuits
WITHIN each Category:There are designated “working voltages”
(50, 150, 300, 600, 1000 V).
A higher voltage has a higher transient withstand
CAT IV
CAT III
CAT II
CAT IV – 600 V: 8 kV impulse
CAT III – 600 V: 6 kV impulse
CAT III – 1000 V: 8 kV impulse
CAT II – 600 V: 4 kV impulse
CAT II – 1000 V: 6 kV impulse
CAT III-600 V = 6 kV impulse 2 ohm test source
CAT II-1000 V = 6 kV impulse 12 ohm test source
The greater the source impedance, the lower the category:
A CAT III-600 V 6k V test impulse has 6 times the current of a CAT II-1000 V 6 kV test impulse!
First know the category you are working in, then choose the appropriate voltage rating
If you ever measure power circuits, you should use:
CAT III-600 V
OR
CAT IV 600 V
CAT III-1000 V
OR
AND CAT IV 600 V ORCAT III-1000 V test leads
CAT III-1000 V CAT IV-600 VCAT III-1000 V
CAT III-600 V
No meter is safe when improperly used
Don’t let test leads be a weak pointCAT III-1000 V or CAT IV 600 V/CAT III 1000 V ratingDouble insulationShrouded connectorsFinger guardsInsulation not damaged: not melted, cut, cracked, stretchedConnectors: no insulation pulled away from end connectorsProbe tips: not loose or broken off (too short)
Safe practices include but are not limited to:
Whenever possible, work on de-energized circuits. Follow proper Isolation procedures.
Use well maintained tools and appropriate safety gear Safety glasses, insulated tools, insulating gloves,
flash suits, insulating mats, etc.
Don’t work alone. Practice safe measurement techniques.
Always connect the EARTH FIRST, ACTIVE SECOND. Disconnect the ACTIVE lead first, EARTHED lead second.