4
Engine Make & Model: Perkins 1104A-44G Circuit Breaker Type: 3 Pole MCCB Fuel Tank Capacity: litres (US gal) 219 (57.9) Frequency: 50 Hz 60 Hz Fuel Consumption, Prime: l/hr (US gal/hr) 13.0 (3.4) 16.0 (4.2) Engine Speed: RPM 1500 1800 Alternator Model: LL2014H Base Frame Type: Fbc2 - (08Hr) Fuel Consumption, Standby : l/hr (US gal/hr) 14.5 (3.8) 18.9 (5.0) Output Ratings Generating Set Model Standby* 35.0 kVA 35.0 kW 40.0 kW 40.0 kVA Prime* 32.0 kVA 32.0 kW 36.0 kW 36.0 kVA 240/120V, 60 Hz 220-240V, 50 Hz * Refer to ratings definitions on page 4. Ratings at power factor. 1.0 GEP35SP11 Technical Data Diesel Generator Set Exclusively from your Cat dealer

LEHF0117-00

Embed Size (px)

DESCRIPTION

Datos de generadores

Citation preview

  • Engine Make & Model: Perkins 1104A-44G

    Circuit Breaker Type: 3 Pole MCCB

    Fuel Tank Capacity: litres (US gal) 219 (57.9)

    Frequency: 50 Hz 60 Hz

    Fuel Consumption, Prime: l/hr (US gal/hr) 13.0 (3.4) 16.0 (4.2)

    Engine Speed: RPM 1500 1800

    Alternator Model: LL2014H

    Base Frame Type: Fbc2 - (08Hr)

    Fuel Consumption, Standby : l/hr (US gal/hr) 14.5 (3.8) 18.9 (5.0)

    Output Ratings

    Generating Set Model Standby*

    35.0 kVA

    35.0 kW

    40.0 kW

    40.0 kVA

    Prime*

    32.0 kVA

    32.0 kW

    36.0 kW

    36.0 kVA240/120V, 60 Hz

    220-240V, 50 Hz

    * Refer to ratings definitions on page 4. Ratings at power factor.1.0

    GEP35SP11

    Technical Data

    Diesel Generator SetExclusively from your Cat dealer

  • 6.6 (26.5)

    74.4 (2627)

    Air Filter Type:

    Combustion Air Flow:

    m/min (cfm) -Standby:

    -Prime:

    Max. Combustion Air Intake

    Restriction: kPa (in H2O)

    Replaceable Element

    3.4 (120)2.8 (99)

    3.4 (120)2.8 (99)

    6.6 (26.5)

    Radiator Cooling Air Flow:

    m/min (cfm)

    External Restriction to

    Cooling Air Flow: Pa (in H2O) 120 (0.5)120 (0.5)

    97.8 (3454)

    Air System 60 Hz50 Hz

    Moment of Inertia: kg m (lb. in) 1.14 (3896)

    Governing Type:

    Governing Class:

    Compression Ratio:Displacement: l (cu.in)

    Engine Electrical System:

    -Voltage/Ground:

    -Battery Charger Amps:

    Weight: kg (lb) - Dry:

    - Wet:

    Cooling Method: Water

    Mechanical

    ISO 8528 G2

    19.25:1

    4.4 (268.5)

    Bore/Stroke: mm (in) 105.0 (4.1)/127.0 (5.0)

    12/Negative

    65445 (981)

    465 (1025)

    Induction:

    Manufacturer: Perkins

    Model: 1104A-44G

    No. of Cylinders/Alignment: 4 / In Line

    Cycle: 4 Stroke

    Naturally Aspirated

    9.07.0Regenerative Power: kW-Prime: 736.0 (106.8) 736.0 (106.8)

    818.0 (118.7)818.0 (118.7)-Standby:BMEP: kPa (psi)

    48.6 (65.0)40.5 (54.0) -Prime:

    -Standby:Gross Engine Power: kW (hp)

    45.0 (60.0) 54.0 (72.0)

    18001500Engine Speed: RPM

    Oil Pan l (US gal):

    Total Oil Capacity l (US gal):

    Oil Filter Type:

    Oil Type:

    Cooling Method:

    Spin-On, Full Flow

    8.0 (2.1)7.8 (2.1)

    API CG4 / CH4 15W-40

    Water

    Prime

    50 Hz 6.4 (1.7)60 Hz 7.6 (2.0)10.2 (2.7)16.0 (4.2)18.9 (5.0)

    8.8 (2.3)13.0 (3.4)14.5 (3.8)

    (based on diesel fuel with a specific gravity of 0.85 and conforming to BS2869, Class A2)

    Recommended Fuel:

    Fuel Consumption: l/hr (US gal/hr)Class A2 Diesel

    110%Load

    75%Load

    50%Load

    100%Load

    Fuel Filter Type: Replaceable Element

    Standby

    50 Hz 6.8 (1.8)9.6 (2.5)14.5 (3.8)

    60 Hz 8.1 (2.1)11.2 (3.0)18.9 (5.0)

    Level: dB

    Silencer System: kPa (in Hg)

    Pressure Drop Across

    Silencer Noise Reduction

    Silencer Type:

    Pressure: kPa (in. Hg)

    Max. Allowable Back

    -Prime:

    m/min (cfm) -Standby:

    Exhaust Gas Flow:

    -Prime:

    m/min (cfm) -Standby:

    Exhaust Gas Temperature: C (F)

    SD80 (1)Silencer Noise Reduction

    0.56 (0.165)0.24 (0.071)

    16.518.2

    15.0 (4.4)12.0 (3.5)

    13.0 (459)10.0 (353)

    12.0 (424)9.0 (318)

    660 (1220)621 (1150)

    650 (1202)610 (1130)

    IndustrialCooling System Capacity: l (US gal)

    Water Pump Type:

    Heat Rejected to Water &

    Lube Oil: kW (Btu/min)

    -Standby:

    -Prime:

    -Prime:

    kW (Btu/min) -Standby:Heat Radiation to Room:

    Radiator Fan Load: kW (hp)

    27.4 (1558)

    0.9 (1.2)

    12.8 (3.4)12.8 (3.4)Centrifugal

    31.0 (1763)

    30.7 (1746)24.6 (1399)

    8.0 (455)9.0 (512)

    7.0 (398)8.0 (455)

    0.5 (0.7)

    Cooling system designed to operate in ambient conditions up to 50C (122F). Contact your local Olympian dealer for power ratings at specific site conditions.

    Cooling System 60 Hz50 Hz

    Performance 60 Hz50 Hz

    Fuel System

    Exhaust System

    Lubrication systemPhysical Data

    Engine Techncial Data

    Consult your Olympian representative for more information

    60 Hz50 Hz

  • Data Item50 Hz 60 Hz

    Motor Starting Capability* kVA 130 122 115 - - 101 114 - -

    Reactances: Per Unit

    Xd

    X'd

    X''d

    1.510 1.650 1.800 - - 2.220 2.430 - -

    0.100 0.110 0.120 - - 0.140 0.160 - -

    0.048 0.053 0.058 - - 0.071 0.078 - -

    Reactances shown are applicable to standby ratings.* Based on 30% voltage dip.** With optional Permanent Magnet generator or AREP excitation.

    240V 230V 220V

    220V/110V 240V/120V

    Short Circuit Capacity** % - - - - - - - - -

    Manufacturer:

    Model:

    No. of Bearings:

    Insulation Class:

    Winding Pitch - Code:

    Wires:

    Ingress Protection Rating:

    Excitation System:

    AVR Model:

    LL2014H

    1

    H

    2/3 - 6

    12

    IP23

    SHUNT

    R250

    OLYMPIAN Overspeed: RPM

    Voltage Regulation (steady state) (%):

    Wave Form NEMA = TIF:

    Wave Form IEC = THF:

    Total Harmonic Content LL/LN:

    Radio Interference:

    Radiant Heat: kW (Btu/min)

    -50 Hz:

    -60 Hz:

    Supression is in line with European Standard EN61000-6

    8.3 (472)

    6.1 (347)

    4.0%

    2.0%

    50

    +/- 0.5

    2250

    Physical Data Operating Data

    Alternator Performance Data

    Alternator Technical Data

    Consult your Olympian representative for more information

  • 35.035.0

    35.035.0

    35.035.0

    kWkVA

    32.032.0

    32.0 32.0

    kWkVA

    220V

    240V

    230V

    32.032.0

    Technical Data Phase Ratings and Performance at 50 Hz, RPM15001

    Voltage Prime Standby

    Standby RatingThese ratings are applicable for supplying continuous electricalpower (at variable load) in the event of a utility power failure. Nooverload is permitted on these ratings. The alternator on this modelis peak continuous rated (as dened in ISO 8528-3).

    Prime RatingThese ratings are applicable for supplying continuous electricalpower (at variable load) in lieu of commercially purchased power.There is no limitation to the annual hours of operation and thismodel can supply 10% overload power for 1 hour in 12 hours.

    Standard Reference ConditionsNote: Standard reference conditions 25C (77F) air inlet temp,100m (328ft) A.S.L. 30% relative humidity. Fuel consumption dataat full load with diesel fuel with specic gravity of 0.85 andconforming to BS2869: 1998, Class A2.

    Definitions

    40.0

    40.0

    kW

    40.0

    40.0

    kVAkW

    36.0

    36.036.0

    36.0

    kVA

    240V/120V

    220V/110V

    Phase Ratings and Performance at 60 Hz, RPM18001

    Voltage Prime Standby

    Weights & Dimensions

    Weights: kg (lb)

    Net (+ lube oil)

    Wet (+ lube oil & coolant)

    Fuel, lube oil & coolant 1157 (2552)

    1023 (2255)

    959 (2114)

    Dimensions: mm (in)

    Height

    Width

    Length

    1361 (53.6)

    1120 (44.1)

    1925 (75.8)

    DocumentsA full set of operation and maintenance manuals and circuit wiring diagrams.

    Quality StandardsBS4999, BS5000, BSEN60034, BSEN61000, IEC60034.

    WarrantyAll equipment carries full manufacturer's warranty.

    General Data

    Market: International

    Information contained in this publication may be considered condential.Discretion is recommended when distributing.

    Materials and specications are subject to change without notice.CAT, CATERPILLAR, their respective logos OLYMPIAN, ''Caterpillar Yellow'' and the "Power Edge" trade dress, as well as

    corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.

    www.CAT-ElectricPower.com

    2010 CaterpillarAll rights reserved.

    Printed in U.S.A.

    Note: General conguration not to be usedfor installation. See general dimensiondrawings for detail.

    LEHF0117-00