DC LT PANEL-
3
DLM
FEEDER
CABLE
OUTGOING-2OUTGOING-1
200 kVA UPS-1
NO
RATING
3
DLM
TRIPON
MCCB, 4P
LSI
3
DLM
TRIPON
MCCB, 4P
LSI
325A
MCCB
325A
MCCB
3
DLM
TRIPON
MCCB, 4P
LSI
63A
MCCB
UPS -MECHANICAL
BYPASS IN
PU
T
BATTERY
STATIC SWITCH
RECTIFIER
STATIC SW
ITCH
INVERTER
BATT M
CCB
MU
LTIPLE STRIN
GS BATTERY
TO
PRO
VID
E 15M
IN
. BACKU
P
200 kVA
UPS-1
OUTGOING-5
BYPASS IN
PU
T
BATTERY
STATIC SWITCH
RECTIFIER
STATIC SW
ITCH
INVERTER
BATT M
CCB
MU
LTIPLE STRIN
GS BATTERY
TO
PRO
VID
E 15M
IN
. BACKU
P
20 kVA
UPS-3
UPS OUT PUT PANEL-2
FEEDER
CABLE
100A AL. BUS BAR
LM
MCB,TPN,4A
RS485
3
OUTGOING-1
RATING
100/5A
CT
CL:1,15VA
TRIPON OFF
LSI
63A, 25KA
MCCB. 4P
OUTGOING-2
DRY COOLER
OUTGOING-3
PUMP-1-PANEL
OUTGOING-4
PUMP-2 PANEL
OUTGOING-5 OUTGOING-6
BMS
OUTGOING-7
LIGHTING DB
PUMP -
OUTGOING-3
MCCB, 4P
LSI
325A
MCCB
MCCB, 4P
LSI
325A
MCCB
LM
MCB,TPN,4A
RS485
3
100/5A
CT
CL:1,15VA
TRIPON OFF
LSI
63A, 25KA
MCCB. 4P
LM
MCB,TPN,4A
CT 800/5A
CL:1,15VA
800A, 50KA
ACB 4P
LSIG
RS485
LVM
3
SPD
MCB,TP,63A
1200A AL. BUS BAR
TRIPON OFF
NOTES:
The panels will be built to relevant IEC specification
Unless otherwise stated and or where applicable :
Construction :
1. The panels will be dust and vermin proof with gaskets of the doors
Installed on the panel and not on door. The compartmentalized
construction is required with extendable bus bars. The entire
assembly must go through 7 tank process and will be oven baked .
2. Outdoor installation will be with IP55 enclosure
3. Bus bars will be tinned copper with current density of not more than
800A / Sq. inches.
4. Base frame of at-least 4" made out of steel sections is to be provided.
5. Panel will have :
Top Entry Bottom Entry
Floor Mounted Installation/Wall Mounted Installation
6. Bus bar system supports will be CPRI or equal test laboratory
approved.
7. All panel compartments shall have identification etched on Aluminum
strip.
8. All MCB DB will have each MCB identification
9. Stands should be provided for the installation of switch board
matching to height of the false floor.
10. All VFDs shall have an active-front-end design
11. All UPSs shall have an active-front-end design
12. KVAR Requirement for each transformer is 400 KVAR steps size
should be appropriate considering data centre application & to
maintain p.f .98 to unity.
Components :
1. MCCBs will be atleast 35 kA or as specified In SLD.
2. MCBs will be atleast 10 kA short circuit withstand of the curve to suit
discrimination
3. ALL protections will be coordinated
4. The range of the instruments be such that the readings will shown
the mid-range of the instrument.
5. The load manager will be installed with communication port and
win95 or similar graphic OS based software.
6. All ACBs will be draw out type with static relays provided for
over-curent, earth fault.
For DG set protection restricted earth fault protection is required.
7. MCCB to have following :
Shunt trip , fault indications, Electronics trip mechanism.
Earthing :
1. All doors will have flying earth.
2. Copper earth bus is to be installed.
3. Where applicable UPS system, VS system and Raw power earth shall
be separate. All the earth bus installed on suitable insulators
Drawings and Tests :
1. Shop drawings are required to be submitted for the review and
approval
2. Test certificates for all components and the panel's routine tests are
required to be provided in triplicate
3. Panel is required to be tested at site and works
8. All Panel Should Have Tvss Protection
BYPASS IN
PU
T
BATTERY
STATIC SWITCH
RECTIFIER
STATIC SW
ITCH
INVERTER
BATT M
CCB
MU
LTIPLE STRIN
GS BATTERY
TO
PRO
VID
E 15M
IN
. BACKU
P
200 kVA
UPS-2
BYPASS IN
PU
T
BATTERY
STATIC SWITCH
RECTIFIER
STATIC SW
ITCH
INVERTER
BATT M
CCB
MU
LTIPLE STRIN
GS BATTERY
TO
PRO
VID
E 15M
IN
. BACKU
P
20 kVA
UPS-4
200 kVA UPS-2
3
DLM
TRIPON
MCCB, 4P
LSI
63A
MCCB
PAC-1
OUTGOING-6
DLC-R2DLC-R3
SERVICE
RACK-RACK PDU
STORAGE
RACK-RACK
PDU
CU UNARMOURED
4 R ... SQMM
DLM
3
OUTGOING-4
SPARE
OUTGOING-7
UPS -MECHANICAL
OUTGOING-8
3
DLM
TRIPON
MCCB, 4P
LSI
100 A
MCCB
EB POWER BY IIT MANDI
DLC-R1
LOCT- DC ROOM
3
DLM
TRIPON
MCCB, 4P
MCCB
3
DLM
TRIPON
MCCB, 4P
125 A
MCCB
3
DLM
TRIPON
MCCB, 4P
125A
MCCB
TRIPON
MCCB, 4P
63A
MCCB
3
DLM
TRIPON
MCCB, 4P
63A
MCCB
TRIPON
MCCB, 4P
63A
MCCB
PAC-2
OUTGOING-8
In Row Unit
OUTGOING-9
SPARE
OUTGOING-10
SPARE
OUTGOING-11
OUTGOING-12
OUTGOING-13
SPARE
SPARE
20 KVA
20 KVA
3
DLM
TRIPON
MCCB, 4P
3
DLM
TRIPON
MCCB, 4P
OUTGOING-1OUTGOING-2 OUTGOING-3
OUTGOING-4 OUTGOING-5
OUTGOING-6
OUTGOING-7 OUTGOING-8
OUTGOING-9
OUTGOING-10OUTGOING-11
OUTGOING-12
OUTGOING-13
SPARE
OUTGOING-14
SPARE
OUTGOING-15
SERVICE
RACK-RACK PDU
STORAGE
RACK-RACK
PDU
DLC-R2DLC-R3
DLC-R1
DLC-R2DLC-R3
DLC-R1
LOCATION OF IEC SOCKET BOX IS ABOVE FALSE CEILING ON CABLE TRAY
400 AMP
400 AMP
LI
LI
UPS OUT PUT PANEL-1
63A
MCB. 4P
32A
MCB. 4P
32A
MCB. 4P
32A
MCB. 4P
32A
MCB. 4P
32A
MCB. 4P
32A
MCB. 4P
32A
MCB. 4P
LOCATION- DC AREA
LOCATION- DC AREA
32A
MCB. 4P
UPS POWER
OUTGOING-9
SOCKET - DB
SOFT STARTER SOFT STARTER
PUMP-3-PANEL PUMP-4 PANEL
VFD STARTER VFD STARTER
SPARE
32A
MCB. 4P
OUTGOING-10
32A
MCB. 4P
OUTGOING-11
POWER INPUT
LM
MCB,TPN,4A
CT 800/5A
CL:1,15VA
800A, 50KA
ACB 4P
LSIG
RS485
LVM
3
TRIPON OFF
CT 800/5A
CL:1,15VA
TRIPON OFF
500 KVA DG SET-AMF PANEL
ELECTRICAL/MECHANICAL INTERLOCK
BOOSTER
SPARE
200 kVA UPS-3
BYPASS IN
PU
T
BATTERY
STATIC SWITCH
RECTIFIER
STATIC SW
ITCH
INVERTER
BATT M
CCB
MU
LTIPLE STRIN
GS BATTERY
TO
PRO
VID
E 15M
IN
. BACKU
P
CU UNARMOURED
4 R ...... SQMM
3
DLM
TRIPON
MCCB, 4P
400 AMP
LI
200 kVA
UPS-3
OUTGOING-16
OUTGOING-37OUTGOING-36
FOR NEW HPC ,ITC AND IT RACKS- IN THIS TENDER SCOPE , LOCATION OF THESE 5 PIN
SOCKET WILL BE ABOVE FALSE CEILING IN CABLE TRAY
100 A
OUTGOING-14
PAC-3
OUTGOING-15
PAC-4
OUTGOING-16
SPARE
3
DLM
TRIPON
MCCB, 4P
100A
MCCB
3
DLM
TRIPON
MCCB, 4P
100A
MCCB
3
DLM
TRIPON
MCCB, 4P
100A
MCCB
150
DLM
OUTGOING-17OUTGOING-18 OUTGOING-19
OUTGOING-20OUTGOING-21
OUTGOING-22OUTGOING-23
OUTGOING-24OUTGOING-25
OUTGOING-26 OUTGOING-27OUTGOING-28
OUTGOING-29OUTGOING-30
OUTGOING-31
OUTGOING-32OUTGOING-33
OUTGOING-34 OUTGOING-33OUTGOING-34
OUTGOING-35
Power DB
RACK PDURACK PDU
RACK PDU
RACK PDURACK PDU
RACK PDU
RACK PDURACK PDU
RACK PDU RACK PDU
RACK PDURACK PDU
RACK PDU
RACK PDURACK PDU
RACK PDU
RACK PDU
RACK PDURACK PDU
RACK PDU
RACK PDURACK PDU
RACK PDU
RACK PDU
SPARES
POWER INPUTPOWER INPUT -
LINE VOLTAGE MONITOR & CONTROL FOR
DIGITAL LOAD MONITOR - EM6436
LVM
DLM
MANUALLY OPERATED DRAWOUT (MDO) TYPE ACB
CURRENT TRANSFORMER (CT) RESIN CAST
POTENTIAL TRANSFORMER (PT)
MINIATURE CIRCUIT BREAKER (MCB)
LOAD BREAK SWITCH
MANUALLY OPERATED FIXED TYPE MCCB
MANUALLY OPERATED FIXED TYPE MCCB
WITH O/L, S/C & E/F RELEASE (LSIG).
WITH O/L & S/C RELEASE (LSI).
MANUALLY OPERATED DRAWOUT (MDO) TP+N(100%) TYPE ACB
WITH O/L, S/C & E/F RELEASE (LSIG).
WITH O/L & S/C RELEASE (LSI).
ELECTRICALLY OPERATED DRAWOUT (EDO) TYPE ACB
WITH O/L, S/C & E/F RELEASE (LSIG).
M
ELECTRICALLY OPERATED DRAWOUT (ED0) TYPE ACB
WITH O/L & S/C RELEASE (LSI).
M
LEGENDS
TRANSIENT VOLTAGE SURGE SUPPRESSOR
R,Y,B (RED,YELLOW,BLUE) INDICATING LAMPS
TVSS
R BY
TRIPOFF
ON-OFF-TRIP INDICATING LAMPS
MAIN SWITCH BOARD
MOTOR CONTROL CENTRE
MSB
MCC
TRANSFORMERTFR
MAXIMUM DEMAND CONTROLLER - EM6400MDC
OVER, UNDER VOLTAGE, SINGLE PHASE &
PHASE REVERSAL PROTECTION
INTEGRATED BASIC POWER & ENERGY PARAMETERS
CHANGEOVER SWITCH
MOTOR PROTECTION CIRCUIT BREAKER (MPCB)
RESIDUAL CURRENT CIRCUIT BREAKER (RCCB)
BASIC ENERGY METER - A,kW,kWHkWH
H
ALARM - HOOTER / BUZZER
MOE (MOTOR OPERATED) FIXED TYPE MCCB
WITH O/L & S/C RELEASE (LSI).
M
ONAN 11KV/433V STEPDOWN TRANSFORMER
AIR COOLED K-20 400/400V ISOLATION TRANSFORMER
ABBREVIATIONS
L S I G L : OVER CURRENT WITH TIMER DELAY
S : SHORT CIRCUIT CURRENT WITH TIMER DELAY
I : CONTINUOS SHORT CIRCUIT
G : GROUND FAULT CURRENT WITH TIME DELAY
12 ANNUNCIATION PANEL WITH HOOTER
HOOTER
1 2 3 4
5 6 7 8
9 10 11 12
MANUALLY OPERATED DRAWOUT (MDO) TYPE MCCB
WITH O/L & S/C RELEASE (LSI).
A/M
AUTO MANUAL SELECTOR SWITCH
FIXED TYPE MCCB WITH O/L & S/C RELEASE (LSIG).
MANUALLY OPERATED MICROPROCESSOR BASED
µP
TNC SWITCH WITH SPRING RETURN TO NEUTRAL AUTO /
MANUAL SELECTOR SWITCH
ON
MOTORISED LOAD BREAK CHANGEOVER SWITCH (ATS)
ONAN 11KV/433V STEPDOWN TRANSFORMER WITH OLTC
AIR COOLED K-20 400/400V ISOLATION TRANSFORMER
BYPASS IN
PU
T
BATTERY
STATIC SWITCH
RECTIFIER
STATIC SW
ITCH
INVERTER
BATT M
CCB
MU
LTIPLE STRIN
GS BATTERY
TO
PRO
VID
E 15M
IN
. BACKU
P
UNINTERRUPTED POWER SUPPLY (UPS)
ATS
ELECTRICAL SINGLE LINE DIAGRAM-SLD
ISSUED FOR APPROVAL
TITLE
OWNERCONSULTANTDRAWING NO.
DRAWN
APPROVED
REV
SCALE
CKD
REV DESCRIPTION DATE
NTSDATE
R5
---
INDIAN INSTITUTE OF TECHNOLOGY MANDI
00 SUBMITTED FOR APPROVAL
CENTER FOR DEVELOPMENT OFADVANCED COMPUTING
R1 FUTURE EXPANSION ADDED
14 SEP 2021
R2 FUTURE EXPANSION ADDED- ModifiedR3 FUTURE EXPANSION Removed- ModifiedR4 FUTURE EXPANSION - Modified