I. INTERIOR ILLUMINATION LIGHTING POWER DENSITY LOCATIONS AND TASKS LEVEL (LUX) WATTS/SF WATTS/SQ. M. Charting and mapping ________________ 750 Graphs 750 Keylining 750 Layout and artwork 500 Photographs, moderate detail 500 Health Care Facilities Ambulance (local) 500 0.5 5.4 Anesthetizing 1000 2.2 23.7 Autopsy and morgue Autopsy, general 500 2.2 23.7 Autopsy table____________ 5000 2.2 23.7 Morgue, general * Cardiac function laboratory 500 2.2 23.7 Central sterile supply Inspection, general 300 1.4 15.1 Inspection 300 1.4 15.1 Work areas, general 300 1.2 12.9 Processed storage 300 0.9 9.7 Corridors 200 1.0 10.8

LEED Hospital Lux Requirements

Embed Size (px)

DESCRIPTION

LEED Lux requirements

Citation preview

Page 1: LEED Hospital Lux Requirements

I. INTERIOR ILLUMINATION LIGHTING POWER DENSITYLOCATIONS AND TASKS LEVEL (LUX) WATTS/SF WATTS/SQ. M.

Charting and mapping ________________ 750Graphs 750Keylining 750Layout and artwork 500Photographs, moderate detail 500

Health Care FacilitiesAmbulance (local) 500 0.5 5.4Anesthetizing 1000 2.2 23.7Autopsy and morgue

Autopsy, general 500 2.2 23.7Autopsy table____________ 5000 2.2 23.7Morgue, general ♦ ♦ *

Cardiac function laboratory 500 2.2 23.7Central sterile supplyInspection, general 300 1.4 15.1Inspection 300 1.4 15.1W ork areas, general 300 1.2 12.9Processed storage 300 0.9 9.7

Corridors 200 1.0 10.8

Page 2: LEED Hospital Lux Requirements

Table 5.1: lES-Recommended Illumination Levels and LEED-Allowed Lighting Power Density {Continued)I. INTERIOR ILLUMINATION LIGHTING POWER DENSITY

LOCATIONS AND TASKS LEVEL (LUX) WATTS/SF WATTS/SQ. M.Nursing areas, day 100 1.0 10.8

| Nursing areas, night 300 1.0 10.8Operating areas, delivery, recovery, 500 2.2 23.7and laboratory suite and service

Critical care areasGeneral 500 2.2 23.7Examination 300 1.5 16.1Surgical task lighting 1000 2.2 23.7Handwashing 1000

Cystoscopy room 500Dental suite

General 500 2.2 23.7Instrument tray 500 2.2 23.7Oral cavity 500 2.2 23.7

Recovery roomGeneral 250 0.8 8.6

Dialysis unit, medical 500 2.2 23.7Elevators 50EKG and specimen room 2.2 23.7

General * * *

* Facilities not covered by LEED requirements.

Page 3: LEED Hospital Lux Requirements

Table 5,1: lES-Recommended Illumination Levels and LEED-Aiiowed Lighting Power Density (Continued)I. INTERIOR

LOCATIONS AND TASKSILLUMINATION

LEVEL (LUX)LIGHTING POWER DENSITYWATTS/SF WATTS/SQ. M.

General 500 1.6 17.2Endoscopy rooms

General 300 2.2 23.7300

_

Culdoscopy 300Eye surgery 1000 2.2 23.7Fracture room * * *

General 500 2.2 23.7Local 500 2.2 23.7

Inhalation therapy * * *

LaboratoriesSpecimen collecting 1000 2.2 23.7

LinensSorting soiled linen 300 0.6 6.5Central (clean) linen room 300 0.6 6.5Sewing room, general 750 0.6 6.5Linen closet 300 0.6 6.5

Lobby 300 1.2 r 12.9Locker rooms 300 0.6 6.5

* Facilities not covered by LEED requirements.

Page 4: LEED Hospital Lux Requirements

Tabic 5.1: IES~Reconnnended Illumination Levels and LEED-Allowed Lighting Power Density (Continued)I. INTERIOR

LOCATIONS AND TASKSILLUMINATION

LEVEL (LUX)LIGHTING POWER DENSITYWATTS/SF WATTS/SQ. M.

Medical illustration studio 1000Medical records 500 1.1 11.8Nurseries

General 300 0.6 6.5Observation and treatment 300 1.5 16.1

Nursing stationsGeneral 300 1.0 10.8Desk 500 1.0 10.8Corridors, day 200 1.0 10.8Corridors, night 50 1.0 10.8Medication station 500 1.2 12.9

Obstetric delivery suite 300 2.2 23.7Labor rooms

General 300 2.2 23.7Local 300 2.2 23.7Birthing room 1000 2.2 23.7Delivery area 1000 2.2 23.7

Scrub, general 200General 1000Delivery table 1000Resuscitation 1000

Page 5: LEED Hospital Lux Requirements

Table 5.1: lES-Reeommended Illumination Levels and LEED-Allowed Lighting Power Density (<Continued)I. INTERIOR ILLUMINATION LIGHTING POWER DENSITY

LOCATIONS AND TASKS LEVEL (LUX) WATTS/SF WATTS/SQ. M.Postdelivery recovery area 500 0.8 8.6

Occupational therapyj W ork areas, general 500 0.9 9.7

Work tables or benches 500 0.9 9.7Patient roomsGeneral 100 0.7 7.5Observation 300 0.7 7.5Critical examination 1000 1.5 16.1Reading 300Toilets 200 0.9 9.7

Physical therapy departments 0.9 9.7Gymnasiums 300 0.9 9.7Tank rooms 500Treatment cubicles 500 2.2 23.7

Postanesthetic recovery roomGeneral 500 0.8 8.6Local 500 0.8 8.6

Pulmonary function laboratories 500Radiological suiteGeneral 300 0.4 4.3Rad iography /fluoroscopy room 300 0.4 4.3

Page 6: LEED Hospital Lux Requirements

Table 5*1:I ES-Recom mended Illumination Levels and LEED-AIlowed Lighting Power Density (iContinued)I. INTERIOR ILLUMINATION LIGHTING POWER DENSITY

LOCATIONS AND TASKS LEVEL (LUX) WATTS/SF WATTS/SQ, M.Radiation therapy sectionGeneral 300 0.4 4.3

SolariumGeneral 200Local for reading 300

Stairways 150 0.6 6.5Surgical suiteOperating room, general 500 2.2 23.7Operating table 1000 2.2 23.7Scrub room 500 0.6 6,5Instruments and sterile supply room 300Clean-up room, instruments 300 1.4 15.1Anesthesia storage 100 1.4 15.1Substerilizing room 300 1.4 15.1

Surgical induction room 500 1.4 15.1Surgical holding area 500Toilets 200 0.9 9.7Utility room 300Waiting areas 1.0 10.8

General 200 1.0 10.8Local for reading 300