Lecture2 Direct Indirect 2011

Embed Size (px)

Citation preview

  • 8/6/2019 Lecture2 Direct Indirect 2011

    1/28

    DEPARTAMENT DENGINYERIA ELCTRICA

    Qualitat del Subministrament Elctric enSistemes amb forta Penetraci de

    Renovables

  • 8/6/2019 Lecture2 Direct Indirect 2011

    2/28

    DEPARTAMENT DENGINYERIA ELCTRICA

    Qualitat del Subministrament Elctric en Sistemes amb forta Penetraci de Renovables

    II I. Non periodic disturbances

    Lecture 2 30/3/2009

    1. Overvoltages from direct lightning flashes to overhead lines2. Overvoltages from indirect lightning flashes to overhead lines3. Distribution lines insulation levels

  • 8/6/2019 Lecture2 Direct Indirect 2011

    3/28

    1. Introduction

    Two cases should be considered whit lightning effects to distribution lines, lightningmight cause flashovers from :

    Direct lightning flashes to a line.

    Induced voltages from nearby lightning flashes.

    DEPARTAMENT DENGINYERIA ELCTRICA

  • 8/6/2019 Lecture2 Direct Indirect 2011

    4/28

    1.1 Direct lightning to a line

    DEPARTAMENT DENGINYERIA ELCTRICA

    Direct flashes to unprotected power distribution lines cause insulation flashovers in thegreat majority of the cases.

    For example, a stroke of as little as 10 kA would produce an overvoltage of around 2000kV, far in excess of the insulation levels of overhead distribution lines operating up to 69kV.

    Lightning incidence to a line: basic approach

    The flash collection rate N, in open ground (no trees, buildings, etc), is estimated byErikssons equation:

    h: is the phase conductor height at the pole (m)b: is the structure width (m)Ng: ground flash density (flashes /km^2 year)N: flash collection rate (flashes /100 km / year)

  • 8/6/2019 Lecture2 Direct Indirect 2011

    5/28

    1.1 Direct lightning to a line

    DEPARTAMENT DENGINYERIA ELCTRICA

    h: is the phase conductor height at the pole (m)b: is the structure width (m)Ng: ground flash density (flashes /km^2 year)

    N: flash collection rate (flashes /100 km / year)

    Source SMC report

  • 8/6/2019 Lecture2 Direct Indirect 2011

    6/28

    1.1 Direct lightning to a line

    DEPARTAMENT DENGINYERIA ELCTRICA

    h: is the phase conductor height at the pole (m)b: is the structure width (m)Ng: ground flash density (flashes /km^2 year)

    N: flash collection rate (flashes /km^2 year)

    Source UNE 21186

  • 8/6/2019 Lecture2 Direct Indirect 2011

    7/28

    7

    DEPARTAMENT DENGINYERIA ELCTRICA

    Lightning incidence to a line

  • 8/6/2019 Lecture2 Direct Indirect 2011

    8/28

    DEPARTAMENT DENGINYERIA ELCTRICA

    Electrogeometrical models

  • 8/6/2019 Lecture2 Direct Indirect 2011

    9/28

    DEPARTAMENT DENGINYERIA ELCTRICA

    Electrogeometrical models

    Including the height of the structure

  • 8/6/2019 Lecture2 Direct Indirect 2011

    10/28

    DEPARTAMENT DENGINYERIA ELCTRICA

    Preparative models

  • 8/6/2019 Lecture2 Direct Indirect 2011

    11/28

    DEPARTAMENT DENGINYERIA ELCTRICA

    Lightning incidence to a line: Insulation level

  • 8/6/2019 Lecture2 Direct Indirect 2011

    12/28

    DEPARTAMENT DENGINYERIA ELCTRICA

    Lightning incidence to a line

    For a particular current I:

  • 8/6/2019 Lecture2 Direct Indirect 2011

    13/28

    13

    Lightning incidence to a line: Shielding Failure Rate (SFR)

    DEPARTAMENT DENGINYERIA ELCTRICA

  • 8/6/2019 Lecture2 Direct Indirect 2011

    14/28

    1.1 Direct lightning to a line

    DEPARTAMENT DENGINYERIA ELCTRICA

    CFO: Critical Flashover Voltage

    This is the peak voltage for a 50% probability of flashover or disruptive discharge.Air density (humidity too) should be taken in to account. Also pollution affects to the CFO.

    Basic Impulse Insulation Level (BIL)

    This is the reference insulation level expressed as an impulse crest (or peak) voltage with a standard wavenot longer than a 1.2/50 us impulse voltage waveform.

    Withstand Voltage

    This is the BIL level that can repeatedly be applied to an equipment without flashover, disruptive charge orother electrical failure under test conditions.

  • 8/6/2019 Lecture2 Direct Indirect 2011

    15/28

    1.1 Direct lightning to a line

    DEPARTAMENT DENGINYERIA ELCTRICA

    Systemvoltage (kV) BIL (kV)

    15.0 110

    23.0 150

    34.5 200

    46.0 250

    69.0 350

    115.0 450

    138.0 550

    230.0 825-900

    287.5 1050

    245.0 1175-1300

    500.0 1550

    The insulators strings are such that:

    1.The power frequency wet withstand voltage (CFO) must belarger than the highest voltage of the switching surge.

    2.The critical impulse withstand voltage (CFO) must be nearthe maximum electrical potential rise of the tower during a

    direct lighting stroke.

  • 8/6/2019 Lecture2 Direct Indirect 2011

    16/28

    1.1 Direct lightning to a line

    DEPARTAMENT DENGINYERIA ELCTRICA

    Sobretensiones

    generadas por

    rayos

    Tensin

    soportable por

    las lneas

  • 8/6/2019 Lecture2 Direct Indirect 2011

    17/28

    1.1 Direct lightning to a line

    DEPARTAMENT DENGINYERIA ELCTRICA

    fo(U)

    fo(U)P

    T(U)

    1

    PT(U)

  • 8/6/2019 Lecture2 Direct Indirect 2011

    18/28

    1.1 Direct lightning to a line

    DEPARTAMENT DENGINYERIA ELCTRICA

    Low-frequency, low current surge impedance of phase conductor

    The surge impedance of an unprotected phase conductor of radius r=1 cm and height h=10 m over perfectground is about 228 , considering that the lightning current from the source splits into two directions. Thesurge impedance of a single wire over ground in one direction is calculated:

    Several effects occur under lightning surge conditions with high current and fast rate of rise over imperfectsoil of finite conductivity.

  • 8/6/2019 Lecture2 Direct Indirect 2011

    19/28

    1.1 Direct lightning to a line

    DEPARTAMENT DENGINYERIA ELCTRICA

    MVAV

    ZcIV

    C

    LZc

    5.1300*5000

    *

    ==

    =

    =

    MVAV

    ZoIV

    C

    LZo

    14.1228*5000

    *

    ==

    =

    =

    10 kA

    Zc 228

    V

    CZ

    BILI

    20 =

    Mxima corrienteMxima corrientesoportablecsoportablec

    Si V > BIL hay falla

  • 8/6/2019 Lecture2 Direct Indirect 2011

    20/28

    1.1 Direct lightning to a line

    DEPARTAMENT DENGINYERIA ELCTRICA

    Effects of corona at high voltage

    The product of the impressed first-stroke current and the phase conductor surge impedance in twodirections:

    Will be a voltage that exceeds 1 MV about 99 % of the time for flashes higher than 4.4 kA.

    Whit this voltage on the conductor, its effective radius will increase from the corona effects, therebyincreasing the capacitance of the conductor and lowering its surge impedance.

    If the radius of the corona envelope envelops the adjacent conductors, these will have nearly the samevoltage as the stricken phase from common-mode coupling and the differential-mode stress on phase-to-phase insulation will be further reduced.

    Rc is the corona radius of the conductor at agradient of 1500 kV/m (m); Eo = 15 kV/cm is the critical corona gradient.

    e is the voltage

    Anderson formula:

  • 8/6/2019 Lecture2 Direct Indirect 2011

    21/28

    1.1 Direct lightning to a line

    DEPARTAMENT DENGINYERIA ELCTRICA

    Effects of imperfect soil at high frequency

    The impedance of the conductor will increase with decreasing soil conductivity and with decreasingfrequency.

    For great accuracy, the height h should be a complex number based on the soil conductivity and frequency.

    The impedance over wide range of frequency should be performed to obtain time-domain result by theinverse Fourier transform.

    The effect of finite soil conductivity on surge impedance can be modeled with acceptable accuracy inlightning calculations by replacing the real height of the line (h) by the effective height:

    Where is the soil conductivity (mS/m).

    To be realistic soil conductivity would be calculated at 124 kHz (1st RS).

    The effects tend to limit the conductivity at 124 kHz to a minimum of about 1 mS/m.

  • 8/6/2019 Lecture2 Direct Indirect 2011

    22/28

    1.1 Direct lightning to a line

    DEPARTAMENT DENGINYERIA ELCTRICA

    Flashover rate from direct flashes

    Both corona and imperfect soil effects could introduce changes within a 30 %.

    Unless the distribution line is protected by overhead ground wires (OHGW) or arresters, more than 99 % ofall direct lightning flashes will cause flashovers regardless of insulation level, conductor spacing orgrounding.

    Then, to estimate the number of flashovers an approach could be obtained by previous equation:

  • 8/6/2019 Lecture2 Direct Indirect 2011

    23/28

    1.1 Indirect lightning to a line

    DEPARTAMENT DENGINYERIA ELCTRICA

    Experience shows that many of the lightning-related outages of low-insulation lines are due to lightning thathits the nearby ground or structures in the proximity.

    Most voltages induced on a distribution line by flashes that terminate near the line are less than 300 kV.Maximum peak voltages are around 400 kV.

    The induced voltages tend to be unipolar and have short pulse witdhs.

  • 8/6/2019 Lecture2 Direct Indirect 2011

    24/28

    1.1 Indirect lightning to a line

    DEPARTAMENT DENGINYERIA ELCTRICA

    Overvoltage level of 300 kV BIL is considered sufficient for lines in areas of high soil conductivity.

    An insulation lever of 400 kV BIL may be more appropriate fro areas of low 1 mS/m conductivity.

    The calculation of the induced voltages requires electromagnetic coupling.

    Some analytical formulas for simple configuration exists. One of these formulas is the Rusk formula.

    The Rusk model serves to predict the maximum overvoltage Um (kV) for a peak stroke current Ip (kA) at adistance d (m) from a line of height h (m):

    Where v is the speed of propagation return stroke (m/s) and c is the speed of light (c=3e8m/s).

    Return stroke speed for natural lightning varies between 0.29x108 m/s and 2.4x108 m/s

  • 8/6/2019 Lecture2 Direct Indirect 2011

    25/28

    1.1 Indirect lightning to a line

    DEPARTAMENT DENGINYERIA ELCTRICA

    The limitation of Rusk model for imperfect soil could be resolved by adopting the effective height (heff).

    Lightning may be collected by tall objects as wind turbines. For tall structures Rusk formula fails becausev=c (at the tower).

    By means of numerical methods, Baba suggested that lightning flashes to tall objects (100 m) such aswind turbines located within 100 m of distribution lines may induce 50 to 80 % higher overvoltage thanflashes to ground at the same location.

    Example of the flashover as a function of the CFO of a 10 m high single conductor infinite line:

    0.001

    0.010

    0.100

    1.000

    10.000

    100.000

    50 100 150 200 250 300

    CFO (kV)

    Flashovers/100km/yr

    ideal ground

    ground conductivity = 10 mS/m

    ground conductivity = 1 mS/m

  • 8/6/2019 Lecture2 Direct Indirect 2011

    26/28

    1.1 Indirect lightning to a line

    DEPARTAMENT DENGINYERIA ELCTRICA

    As a reference, a 10 m tall distribution line in open ground with GFD = 1 flash/km2/yr will haveapproximately 11 flashes/100 km/yr due to direct strokes.

    In open ground, induced voltages will be a problem for lines characterized by low insulation levels and/orabove a poor conducting ground.

    A grounded neutral w ire or overhead OHGW will reduce the voltage across the insulation by a

    factor that depends on the spacing between adjacent groundings, on the grounding impedance and on theproximity of the grounded conductor to the phase conductors. This factor is typically between 0.6 and 0.9.

    Grounded ci rcuits , i .e. ci rcu its w i th a grounded neutral w i re or overhead OHGW, are generallyexpected to have fewer number of flashovers for a g iven CFO because the grounded conductorreduces via i ts electromagnet ic shielding effect the voltage stress across the insulation.

  • 8/6/2019 Lecture2 Direct Indirect 2011

    27/28

    1.1 Indirect lightning to a line

    DEPARTAMENT DENGINYERIA ELCTRICA

    Estimation of failures due to direct and indirect effects

    0 - ymin : Direct strikes

    ymin ymax: Induced voltages that

    produce failures

    > ymax: Induced voltages that do

    not produce failures

    Number of failures associated to

    indirect lightning

  • 8/6/2019 Lecture2 Direct Indirect 2011

    28/28

    Proposed activities

    DEPARTAMENT DENGINYERIA ELCTRICA

    1.-Calculate the SFR for a three-phase overhead line (h = 10 m) with a ground wire 50 cm above of the centerphase. Three phases are distributed horizontally. Line lenght is 50 km and Ng is 3 flash/km^2 year. First calculatefor a particular current of 20 kA and then for all the current range.

    2.- Estimate the (undamped) voltages on the previous overhead line when a 15 kA lightning strikes one phase.

    3.- Calculate a list of induced overvoltages in a phase for the previous line for lightning of 5 kA, 10 kA, 20 kA , 50 kA

    and 100 kV at distances: the minimum (to determinate), the minimum plus 25 m, the minimum plus 100 m and theminimum plus 500 m.

    4.- Simulate the previous line behavior when it is exposed to 500 lightning flashes.