Lecture 19: HVAC Outside Air Systems and Modeling Guidelines

Material prepared by GARD Analytics, Inc. and University of Illinoisat Urbana-Champaign under contract to the National Renewable Energy

Laboratory. All material Copyright 2002-2003 U.S.D.O.E. - All rights reserved

Page 2: Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under

2

Purpose of this Lecture

Discuss Outside Air IAQ requirements force us to draw

fresh air in from the outside environment

Outside air (OA) can have a significant impact on the building energy requirements

Show how OA is specified in EnergyPlus

Page 3: Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under

3

Keywords Covered in this Lecture

Air Loop Equipment ListOutside Air SystemOutside Air MixerController:Outside AirOutside Air Inlet Node ListReview of other related keywords

Page 4: Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under

4

Components: Special Case - Outside Air System

OUTSIDE AIR SYSTEM is a subsystem component

OA System Controller ListOA System Equipment ListOA System Availability Manager

List

Page 5: Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under

5

OA System Equipment List

System component type outside air mixer, coil, heat

exchanger

System component name

Repeat for each air loop component

Page 6: Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under

6

Air Loop Equipment List - Example

AIR LOOP EQUIPMENT LIST,

OA Sys 1 Equipment, !- Name

OUTSIDE AIR MIXER, !- KEY--System Component 1

OA Mixing Box 1; !- Component Name 1

Page 7: Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under

7

Outside Air System - Example

OUTSIDE AIR SYSTEM,

OA Sys 1, !- Name

OA Sys 1 Controllers, !- Name: Controller List

OA Sys 1 Equipment, !- Name of an Air Loop Equipment List

VAV Sys 1 Avail List; !- Name of a System Availability Manager List

Page 8: Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under

8

Outside Air Mixer

Mixed_Air_NodeOutside_Air_Stream_NodeRelief_Air_Stream_NodeReturn_Air_Stream_Node

Page 9: Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under

9

Outside Air Mixer - Example

OUTSIDE AIR MIXER, OA Mixing Box 1, !- Name Mixed Air Node 1, !- Mixed_Air_Node Outside Air Inlet Node 1, !- Outside_Air_Stream_Node Relief Air Outlet Node 1, !- Relief_Air_Stream_Node VAV Sys 1 Inlet Node; !- Return_Air_Stream_Node

Page 10: Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under

10

CONTROLLER LIST, OA Sys 1 Controllers, !- Name CONTROLLER:OUTSIDE AIR, !- Controller Type 1 OA Controller 1; !- Controller Name 1

Outside Air Mixer – Controller List

Page 11: Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under

11

Controller:Outside Air

Control_NodeActuated_NodeMinimum outside air flow rateMaximum outside air flow rateTemperature limitTemperature lower limit

Page 12: Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under

12

Controller:Outside Air - Example

CONTROLLER:OUTSIDE AIR, OA Controller 1, !- Name ECONOMIZER, !- EconomizerChoice NO RETURN AIR TEMP LIMIT, !- ReturnAirTempLimit NO RETURN AIR ENTHALPY LIMIT, !- ReturnAirEnthalpyLimit NO LOCKOUT, !- Lockout FIXED MINIMUM, !- MinimumLimit Mixed Air Node 1, !- Control_Node Outside Air Inlet Node 1, !- Actuated_Node autosize, !- min outside air flow rate {m3/s} autosize, !- max outside air flow rate {m3/s} 19., !- temperature limit {C} 4., !- temperature lower limit {C} 0.0, !- enthalpy limit {J/kg} Relief Air Outlet Node 1, !- Relief_Air_Outlet_Node VAV Sys 1 Inlet Node, !- Return_Air_Node Min OA Sched; !- Minimum Outside Air Schedule Name

Page 13: Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under

13

TermReheat with Outside Air Example

North

Zone

East

Zone

Resistive

Zone

Supply FanR

etu

rn A

ir M

ixe

r

Zo

ne A

ir Sp

litter

CC

VAV Box:ReHeat

VAV Box:ReHeat

Mixed OutsideAir Box

Relief Air

Outside Air

VAV Box: ReHeat

North

Zone

East

Zone

Resistive

Zone

Supply FanR

etu

rn A

ir M

ixe

r

Zo

ne A

ir Sp

litter

CC

VAV Box:ReHeat

VAV Box:ReHeat

Mixed OutsideAir Box

Relief Air

Outside Air

VAV Box: ReHeat

Air Loop contains the Mixed Air System

Page 14: Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under

14

TermReheat Main Branch with OA

SystemSupply Fan

CCMixed OutsideAir Box

Relief Air

Outside AirSupply Fan

CCMixed OutsideAir Box

Relief Air

Outside Air

BRANCH, Air Loop Main Branch, !- Branch Name 1.3, !- Maximum Branch Flow Rate {m3/s} OUTSIDE AIR SYSTEM, !- Comp1 Type OA Sys 1, !- Comp1 Name VAV Sys 1 Inlet Node, !- Comp1 Inlet Node Name Mixed Air Node, !- Comp1 Outlet Node Name PASSIVE, !- Comp1 Branch Control Type FAN:SIMPLE:ConstVolume, !- Comp2 Type Supply Fan 1, !- Comp2 Name Mixed Air Node, !- Comp2 Inlet Node Name< cooling coil >

Page 15: Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under

15

TermReheat Outside Air Node List

Mixed OutsideAir Box

Relief Air

Outside Air

Mixed OutsideAir Box

Relief Air

Outside Air

OUTSIDE AIR INLET NODE LIST,

OutsideAirInletNodes; !- 1st Node name or node list name

NODE LIST,

OutsideAirInletNodes, !- Node List Name

Outside Air Inlet Node 1; !- Node_ID_1

Page 16: Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under

16

TermReheat Outside Air System

Mixed OutsideAir Box

Relief Air

Outside Air

Mixed OutsideAir Box

Relief Air

Outside Air

OUTSIDE AIR SYSTEM,

OA Sys 1, !- Name

OA Sys 1 Controllers, !- Name: Controller List

OA Sys 1 Equipment, !- Name of an Air Loop Equipment List

VAV Sys 1 Avail List; !- Name of a System Availability Manager List

Page 17: Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under

17

TermReheat Outside Air Controller List

Mixed OutsideAir Box

Relief Air

Outside Air

Mixed OutsideAir Box

Relief Air

Outside Air

CONTROLLER LIST,

OA Sys 1 Controllers, !- Name

CONTROLLER:OUTSIDE AIR, !- Controller Type 1

OA Controller 1; !- Controller Name 1

Page 18: Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under

18

TermReheat Outside Air Equipment List

Mixed OutsideAir Box

Relief Air

Outside Air

Mixed OutsideAir Box

Relief Air

Outside Air

AIR LOOP EQUIPMENT LIST,

OA Sys 1 Equipment, !- Name

OUTSIDE AIR MIXER, !- KEY--System Component 1

OA Mixing Box 1; !- Component Name 1

Page 19: Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under

19

TermReheat Outside Air Controller

CONTROLLER:OUTSIDE AIR, OA Controller 1, !- Name ECONOMIZER, !- EconomizerChoice NO RETURN AIR TEMP LIMIT, !- ReturnAirTempLimit NO RETURN AIR ENTHALPY LIMIT, !- ReturnAirEnthalpyLimit NO LOCKOUT, !- Lockout FIXED MINIMUM, !- MinimumLimit Mixed Air Node 1, !- Control_Node Outside Air Inlet Node 1, !- Actuated_Node 0.468, !- minimum outside air flow rate {m3/s} 1.56, !- maximum outside air flow rate {m3/s} 19., !- temperature limit {C} 4., !- temperature lower limit {C} 0.0, !- enthalpy limit {J/kg} Relief Air Outlet Node 1, !- Relief_Air_Outlet_Node VAV Sys 1 Inlet Node, !- Return_Air_Node Min OA Sched; !- Minimum Outside Air Schedule Name

Page 20: Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under

20

TermReheat Outside Air Mixer

Mixed OutsideAir Box

Relief Air

Outside Air

Mixed OutsideAir Box

Relief Air

Outside Air

OUTSIDE AIR MIXER,

OA Mixing Box 1, !- Name

Mixed Air Node 1, !- Mixed_Air_Node

Outside Air Inlet Node 1, !- Outside_Air_Stream_Node

Relief Air Outlet Node 1, !- Relief_Air_Stream_Node

VAV Sys 1 Inlet Node; !- Return_Air_Stream_Node

Page 21: Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under

21

Outdoor Air Economizer

TermReheatOA.idf example file CONTROLLER:OUTSIDE AIR, OA Controller 1, !- Name ECONOMIZER, !- EconomizerChoice NO RETURN AIR TEMP LIMIT, !- ReturnAirTempLimit NO RETURN AIR ENTHALPY LIMIT, !- ReturnAirEnthalpyLimit NO LOCKOUT, !- Lockout FIXED MINIMUM, !- MinimumLimit Mixed Air Node, !- Control_Node Outside Air Inlet Node, !- Actuated_Node 0.4333, !- minimum outside air flow rate {m3/s} 1.3, !- maximum outside air flow rate {m3/s} 19., !- temperature limit {C} 4., !- temperature lower limit {C} 0.0, !- enthalpy limit {J/kg} Relief Air Outlet Node, !- Relief_Air_Outlet_Node VAV Sys 1 Inlet Node; !- Return_Air_Node

Page 22: Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under

22

Outdoor Air Economizer (cont’d)

Scheduled mixed air setpoint

SET POINT MANAGER:SCHEDULED, Mixed Air Temp Manager, !- Name TEMP, !- Control variable Seasonal Reset Mixed Air Temp Sch, !- Schedule Name Mixed Air Nodes; !- Name of the set point Node List NODE LIST, Mixed Air Nodes, !- Node List Name Mixed Air Node; !- Node_ID_1

Page 23: Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under

23

Outdoor Air Economizer (cont’d)

Mixed air setpoint adjusted for fan heat SET POINT MANAGER:SCHEDULED,

Supply Air Temp Manager 1, !- Name TEMP, !- Control variable Seasonal Reset Supply Air Temp Sch, !- Schedule Name Supply Air Temp Nodes 1; !- Name of the set point Node List

SET POINT MANAGER:MIXED AIR, Mixed Air Temp Manager 1, !- Name TEMP, !- Control variable: VAV Sys 1 Outlet Node, !- reference set point node name Main Heating Coil 1 Outlet Node, !- fan inlet node name VAV Sys 1 Outlet Node, !- fan outlet node name Mixed Air Node 1; !- Name of the set point Node or Node List

NODE LIST, Supply Air Temp Nodes 1, !- Node List Name VAV Sys 1 Outlet Node; !- Node_ID_1

Page 24: Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under

24

Economizer with Furnace/DX

Furnace/DX does not set a supply air setpoint

Must use setpoint managers to establish a setpoint

Page 25: Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under

25

Summary

Introduction of outside air into a forced air system is necessary to meet indoor air quality (IAQ) standards

Outside air (mixing box) in EnergyPlus is a component on an air loop branch

Outside air system also contains controllers that can be operated in economizer mode