63
1 Prof. Dr. Qaisar Ali Reinforced Concrete Design – II Department of Civil Engineering, University of Engineering and Technology Peshawar Topics Behavior Moment Coefficient Method Steps in Moment Coefficient Method Design Example 1 (Typical House with 2 Rooms and Verandah) Design Example 2 (100′ × 60′, 3-Storey Commercial Building) Practice Examples References 2

Lecture-04€¦ · Prof. Dr. Qaisar Ali Reinforced Concrete Design –II Department of Civil Engineering, University of Engineering and Technology Peshawar Lecture-04 Analysis and

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

  • 1

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Lecture-04

    Analysis and Design of Two-way Slab System

    (Part-I: Two Way Slabs Supported on Stiff Beams Or Walls)

    By: Prof Dr. Qaisar Ali

    Civil Engineering Department

    UET Peshawar

    www.drqaisarali.com

    1

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Topics

    Behavior

    Moment Coefficient Method

    Steps in Moment Coefficient Method

    Design Example 1 (Typical House with 2 Rooms and Verandah)

    Design Example 2 (100′ × 60′, 3-Storey Commercial Building)

    Practice Examples

    References

    2

  • 2

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab System (Long span/short span < 2)

    3

    25′ 25′ 25′ 25′

    20′

    20′

    20′

    Behavior

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    4

    One-Way Behavior Two-Way Behavior

    Behavior

    Two-Way Bending of Two-Way Slabs

  • 3

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    5

    Behavior

    Two-Way Bending of Two-Way Slabs

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    6

    Short Direction

    Behavior

    Short Direction Moments in Two-Way Slab

  • 4

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    7

    Long Direction

    Behavior

    Long Direction Moments in Two-Way Slab

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    More Demand (Moment) in short direction due to size

    of slab

    Δcentral Strip = (5/384)wl4/EI

    As these imaginary strips are part of monolithic slab, the deflection at

    any point, of the two orthogonal slab strips must be same:

    Δa = Δb

    (5/384)wala4/EI = (5/384)wblb

    4/EI

    wa/wb = lb4/la

    4 wa = wb (lb4/la

    4)

    Thus, larger share of load (Demand) is taken by the shorter direction.

    8

    Behavior

  • 5

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    The Moment Coefficient Method included for the first time in

    1963 ACI Code is applicable to two-way slabs supported on

    four sides of each slab panel by walls, steel beams relatively

    deep, stiff, edge beams (h = 3hf).

    Although, not included in 1977 and later versions of ACI code,

    its continued use is permissible under the ACI 318-11 code

    provision (13.5.1). Visit ACI 13.5.1.

    9

    Moment Coefficient Method

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Moments:

    Ma, neg = Ca, negwula2

    Mb, neg = Cb, negwulb2

    Ma, pos, (dl + ll) = M a, pos, dl + M a, pos, ll = Ca, pos, dl × wu, dl × la2 + Ca, pos, ll × wu, ll × la

    2

    Mb, pos, (dl + ll) = Mb, pos, dl + Mb, pos, ll = Cb, pos, dl × wu, dl × lb2 + Cb, pos, ll × wu, ll × lb

    2

    Where Ca, Cb = Tabulated moment coefficients

    wu = Ultimate uniform load, psf

    la, lb = length of clear spans in short and long directions respectively.

    10

    Ma,neglb

    la

    Ma,neg

    Ma,posMb,neg Mb,negMb,pos

    Moment Coefficient Method

  • 6

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Cases

    Depending on the support conditions, several cases are possible:

    11

    Moment Coefficient Method

    4 spans @ 25′-0″

    3 sp

    ans @ 20

    ′-0″

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    12

    Moment Coefficient Method

    Cases

    Depending on the support conditions, several cases are possible:

    4 spans @ 25′-0″

    3 spans @ 20

    ′-0″

  • 7

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    13

    Moment Coefficient Method

    Cases

    Depending on the support conditions, several cases are possible:

    4 spans @ 25′-0″

    3 sp

    ans @ 20

    ′-0″

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    14

    Moment Coefficient Method

    Cases

    Depending on the support conditions, several cases are possible:

    4 spans @ 25′-0″

    3 spans @ 20

    ′-0″

  • 8

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    15

    Moment Coefficient Method

    Note: Horizontal sides of the figure represents longer side while vertical side

    represents shorter side.

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    16

    Moment Coefficient Method

    Note: Horizontal sides of the figure represents longer side while vertical side

    represents shorter side.

  • 9

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    17

    Moment Coefficient Method

    Note: Horizontal sides of the figure represents longer side while vertical side

    represents shorter side.

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    18

    Moment Coefficient Method

    Note: Horizontal sides of the figure represents longer side while vertical side

    represents shorter side.

  • 10

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    19

    Moment Coefficient Method

    Note: Horizontal sides of the figure represents longer side while vertical side

    represents shorter side.

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    20

    Moment Coefficient Method

    Note: Horizontal sides of the figure represents longer side while vertical side

    represents shorter side.

  • 11

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    21

    Moment Coefficient Method

    Note: Horizontal sides of the figure represents longer side while vertical side

    represents shorter side.

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    hmin = perimeter/ 180 = 2(la + lb)/180

    Calculate loads on slab

    Calculate m = la/ lb

    Decide about case of slab

    Use table to pick moment coefficients

    Calculate Moments and then design

    Apply reinforcement requirements (smax = 2hf, ACI 13.3.2)

    22

    Steps in Moment Coefficient Method

  • 12

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    3D Model of the House

    In this building we will design a two-way slab (for rooms), a one-way

    slab, beam and column (for verandah)

    23

    Design Example 1(Typical House with 2 Rooms and Verandah)

    16' X 12' 16' X 12'

    9' Wide Verandah

    B1B1

    RCC Column

    9" brick masonry wall

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Given Data:

    Service Dead Load

    4″ thick mud

    2″ thick brick tile

    Live Load = 40 psf

    f′c = 3 ksi

    fy = 40 ksi

    24

    Design Example 1(Typical House with 2 Rooms and Verandah)

    16' X 12' 16' X 12'

    9' Wide Verandah

    B1B1

    RCC Column

    9" brick masonry wall

  • 13

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Sizes

    For two way slab system

    hmin = perimeter / 180 = 2(la + lb)/180

    hmin = 2 (12 +16) /180 = 0.311 ft = 3.73 inch

    Assume 5 inch slab

    For one way slab system

    For 5″ slab, span length l is min. of:

    l = ln+ hf = 8 + (5/12) = 8.42′

    c/c distance between supports = 8.875′

    Slab thickness (hf) = (8.42/20) × (0.4+��/100000)

    = 4.04″ (min. by ACI)

    Taking 5 in. slab

    25

    Design Example 1(Typical House with 2 Rooms and Verandah)

    9′ Wide Verandah

    ln = 8′

    lc/c = (8 + (9/12) / 2 + 0.5) = 8.875′

    9″ Brick Wall

    Slab

    h

    16' X 12' 16' X 12'

    9' Wide Verandah

    B1B1

    RCC Column

    9" brick masonry wall

    A

    A

    Section AA

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Loads

    5 inch Slab = 5/12 x 0.15 = 0.0625 ksf

    4 inch mud = 4/12 x 0.12 = 0.04 ksf

    2 inch tile = 2/12 x 0.12 = 0.02 ksf

    Total DL = 0.1225 ksf

    Factored DL = 1.2 x 0.1225 = 0.147 ksf

    Factored LL = 1.6 x 0.04 = 0.064 ksf

    Total Factored Load = 0.211 ksf

    26

    Design Example 1(Typical House with 2 Rooms and Verandah)

  • 14

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Analysis

    This system consist of both one way and two way slabs. Rooms

    (two way slabs) are continuous with verandah (one way slab).

    A system where a two way slab is continuous with a one way slab

    or vice versa is called a mixed slab system.

    27

    Design Example 1(Typical House with 2 Rooms and Verandah)

    16' X 12' 16' X 12'

    9' Wide Verandah

    B1B1

    RCC Column

    9" brick masonry wall

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Analysis

    The ACI approximate methods of analysis are not applicable to

    such systems because:

    In case of two way slabs, the moment coefficient tables are applicable

    to two way slab system where a two way slab is continuous with a two

    way slab.

    In case of one ways slabs, the ACI approximate analysis is applicable

    to one way slab system where a one way slab is continuous with a one

    way slab.

    28

    Design Example 1(Typical House with 2 Rooms and Verandah)

  • 15

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Analysis

    The best approach to analyze a mixed system is to use FE

    software.

    However, such a system can also be analyzed manually by making

    certain approximations.

    In the next slides, We will analyze this system using both of the

    above mentioned methods.

    29

    Design Example 1(Typical House with 2 Rooms and Verandah)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Analysis using FE Software (SAFE)

    30

    Design Example 1(Typical House with 2 Rooms and Verandah)

    Moments in Longer Direction in Two Way Slabs

    Moments in Shorter Direction in Two Way Slabs & Moment in Verandah One Way Slab

    Two Way Slab Moments (ft-kip/ft)(Rooms)

    One Way Slab Moment (ft-kip/ft)(Verandah)

    Ma,pos Mb,pos Ma,neg Mb,neg Mver (+ve)

    1.58 1.17 2.10 1.67 1.10

    Mb,pos Mb,posMb,neg Ma

    ,po

    s

    Ma

    ,po

    s

    Ma

    ,ne

    g

    Ma

    ,ne

    g

    Mv

    er

    (+v

    e)

    Mb,pos

    Ma,p

    os

    Ma,n

    eg

    Mb,negMb,pos

    Ma,n

    eg

    Ma,p

    os

    Mver

    (+v

    e)

  • 16

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Analysis using Manual Approach

    For approximate manual analysis of two way slab of rooms, we

    know that two way slabs of rooms are not only continuous along the

    long direction but also continuous along the short direction with the

    verandah slab. We assume that the verandah slab is a two way slab

    instead of one way slab in order to calculate Mb,neg

    Now, using Moment Coefficient Method for analysis.

    31

    Design Example 1(Typical House with 2 Rooms and Verandah)

    Mb,pos

    Ma,p

    os

    Ma,n

    eg

    Mb,negMb,pos

    Ma,n

    eg

    Ma,p

    os

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis

    Case = 4

    m = la/lb = 12/16 = 0.75

    Ca,neg = 0.076

    Cb,neg = 0.024

    Ca,posDL = 0.043

    Cb,posDL = 0.013

    Ca,posLL = 0.052

    Cb,posLL = 0.016

    Design Example 1(Typical House with 2 Rooms and Verandah)

    32

    16′

    12′

    Mb,negMb,pos

    Ma

    ,po

    s

    Case 4

    Ma,n

    eg

  • 17

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis

    Case = 4

    m = la/lb = 12/16 = 0.75

    Ca,neg = 0.076

    Cb,neg = 0.024

    Ca,posDL = 0.043

    Cb,posDL = 0.013

    Ca,posLL = 0.052

    Cb,posLL = 0.016

    Design Example 1(Typical House with 2 Rooms and Verandah)

    33

    16′

    12′

    Mb,negMb,pos

    Ma

    ,po

    s

    Case 4

    Ma,n

    eg

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Case = 4

    m = la/lb = 12/16 = 0.75

    Ca,neg = 0.076

    Cb,neg = 0.024

    Ca,posDL = 0.043

    Cb,posDL = 0.013

    Ca,posLL = 0.052

    Cb,posLL = 0.016

    Two-Way Slab Analysis

    Design Example 1(Typical House with 2 Rooms and Verandah)

    34

    16′

    12′

    Mb,negMb,pos

    Ma

    ,po

    s

    Case 4

    Ma,n

    eg

  • 18

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Case = 4

    m = la/lb = 12/16 = 0.75

    Ca,neg = 0.076

    Cb,neg = 0.024

    Ca,posDL = 0.043

    Cb,posDL = 0.013

    Ca,posLL = 0.052

    Cb,posLL = 0.016

    Two-Way Slab Analysis

    Design Example 1(Typical House with 2 Rooms and Verandah)

    35

    16′

    12′

    Mb,negMb,pos

    Ma

    ,po

    s

    Case 4

    Ma,n

    eg

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Case = 4

    m = la/lb = 12/16 = 0.75

    Ca,neg = 0.076

    Cb,neg = 0.024

    Ca,posDL = 0.043

    Cb,posDL = 0.013

    Ca,posLL = 0.052

    Cb,posLL = 0.016

    Two-Way Slab Analysis

    Design Example 1(Typical House with 2 Rooms and Verandah)

    36

    16′

    12′

    Mb,negMb,pos

    Ma

    ,po

    s

    Case 4

    Ma,n

    eg

  • 19

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Case = 4

    m = la/lb = 12/16 = 0.75

    Ca,neg = 0.076

    Cb,neg = 0.024

    Ca,posDL = 0.043

    Cb,posDL = 0.013

    Ca,posLL = 0.055

    Cb,posLL = 0.016

    Two-Way Slab Analysis

    Design Example 1(Typical House with 2 Rooms and Verandah)

    37

    16′

    12′

    Mb,negMb,pos

    Ma

    ,po

    s

    Case 4

    Ma,n

    eg

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    38

    Design Example 1(Typical House with 2 Rooms and Verandah)

    Two-Way Slab Analysis

    Calculating moments using ACI Coefficients:

    Ma, neg = Ca, negwula2

    Mb, neg = Cb, negwulb2

    Ma, pos, (dl + ll) = M a, pos, dl + M a, pos, ll = Ca, pos, dl × wu, dl × la2 + Ca, pos, ll × wu, ll × la

    2

    Mb, pos, (dl + ll) = Mb, pos, dl + Mb, pos, ll = Cb, pos, dl × wu, dl × lb2 + Cb, pos, ll × wu, ll × lb

    2

    Using above relations the moments calculated are:

    Ca,neg = 0.076 Cb,neg = 0.024

    Ca,posLL = 0.052 Cb,posLL = 0.016

    Ca,posDL = 0.043 Cb,posDL = 0.013

    wu, dl = 0.147 ksf, wu, ll = 0.064 ksf, wu = 0.211 ksf

    Ma,neg = 2.31 ft-kip

    Mb,neg = 1.29 ft-kip

    Ma,pos = 1.39 ft-kip

    Mb,pos = 0.76 ft-kip

    16′

    12′

    Mb,negMb,pos

    Ma

    ,po

    s

    Case 4

    Ma,n

    eg

  • 20

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    One Way Slab Analysis

    For calculation of Mver (+ve) along the short direction in the verandah

    slab, we will pick the coefficients of continuous one way slabs having

    two spans.

    Now, using ACI Approximate analysis procedure (ACI 8.33) for analysis.

    39

    Design Example 1(Typical House with 2 Rooms and Verandah)

    Mver(

    +v

    e)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    40

    Design Example 1(Typical House with 2 Rooms and Verandah)

    One-Way Slab Analysis

    For two span one way slab system, positive moment at midspan is given as

    follows:

    Mver (+ve) = wuln2/11

    Mver (+ve) = 0.211 × (8)2/11

    = 1.23 ft-k/ft

    9′ Wide Verandah

    ln = 8′

    9″ Brick Wall

    Wu = 0.211 ksf

    h

    1/11 1/11

    1/91/9Simply Supported

    Simply Supported

  • 21

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    41

    Design Example 1(Typical House with 2 Rooms and Verandah)

    Design of Two-Way Slab

    Comparison of Analysis Results from FE Analysis and Manual Analysis

    Analysis results from both approaches are almost similar.

    Hence the intelligent use of manual analysis yields fairly reasonable results in most cases.

    Analysis Type

    Ma,neg Mb,neg Ma,pos Mb,pos Mver (+ve)

    SAFE 2.10 1.67 1.58 1.17 1.10

    Manual 2.31 1.3 1.39 0.76 1.23

    NOTE: All values are in ft-kip units

    Mb,pos

    Ma,p

    os

    Ma,n

    eg

    Mb,negMb,pos

    Ma,n

    eg

    Ma,p

    os

    Mver

    (+v

    e)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    42

    Design Example 1(Typical House with 2 Rooms and Verandah)

    Design of Two-Way Slab

    First determining capacity of min. reinforcement:

    As,min = 0.002bhf = 0.12 in2

    Using #3 bars: Spacing for As,min = 0.12 in2 = (0.11/0.12) × 12 = 11″ c/c

    However ACI max spacing for two way slab = 2h = 2(5) = 10″ or 18″ = 10″ c/c

    Hence using #3 bars @ 10″ c/c

    For #3 bars @ 10″ c/c: As,min = (0.11/10) × 12 = 0.132 in2

    Capacity for As,min: a = (0.132 × 40)/(0.85 × 3 × 12) = 0.17″

    ΦMn = ΦAsminfy(d – a/2) = 0.9 × 0.132 × 40(4 – (0.17/2)) = 18.60 in-kip

    Therefore, for Mu values ≤ 18.60 in-k/ft, use As,min (#3 @ 10″ c/c) & for Mu

    values > 18.6 in-kip/ft, calculate steel area using trial & error procedure.

  • 22

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    43

    Design Example 1(Typical House with 2 Rooms and Verandah)

    Design of Two-Way Slab

    For Ma,neg = 2.31 ft-kip = 27.71 in-kip > 18.60 in-kip: As = 0.20 in2 (#3 @ 6.6″ c/c)

    Using #3 @ 6″ c/c

    For Mb,neg = 1.29 ft-kip = 15.56 in-kip < 18.60 in-kip: Using #3 @ 10 c/c

    For Ma,pos = 1.39 ft-kip = 16.67 in-kip < 18.60 in-kip: Using #3 @ 10 c/c

    For Mb,pos = 0.76 ft-kip = 9.02 in-kip < 18.60 in-kip: Using #3 @ 10″ c/c

    16′

    12′

    Mb,negMb,pos

    Ma,p

    os

    Case 4

    Ma,n

    eg

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    44

    Design Example 1(Typical House with 2 Rooms and Verandah)

    Design of Two-Way Slab

    Reinforcement at Discontinuous Ends

    Reinforcement at discontinuous ends in a two way slab is 1/3 of the positive

    reinforcement.

    Positive reinforcement at midspan in this case is #3 @ 10 c/c. Therefore

    reinforcement at discontinuous end may be provided @ 30 c/c.

    However, in field practice, the spacing of reinforcement at discontinuous ends

    seldom exceeds 18 c/c. The same is provided here as well.

    Supporting Bars

    Supporting bars are provided to support negative reinforcement.

    They are provided perpendicular to negative reinforcement, generally at spacing

    of 18 c/c.

  • 23

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    45

    Design Example 1(Typical House with 2 Rooms and Verandah)

    Design of One-Way Slab

    Main Reinforcement:

    Mver (+ve) = 14.73 in-kip

    As,min = 0.002bhf = 0.002(12)(5) = 0.12 in2

    Using #3 bars, spacing = (0.11/0.12) × 12 = 11″ c/c

    For one-way slabs, max spacing by ACI = 3h = 3(5) = 15″ or 18″ = 15″ c/c

    For #3 bars @ 15″ c/c, As = (0.11/15) × 12 = 0.09 in2. Hence using As,min = 0.12 in

    2

    a = (0.12 × 40)/(0.85 × 3 × 12) = 0.16″

    ΦMn = ΦAsminfy(d – a/2) = 0.9 × 0.12 × 40(4 – (0.16/2)) = 16.94 in-kip > Mver (+ve)

    Therefore, using #3 @ 11″ c/c

    However, for facilitating field work, we will use #3 @ 10″ c/c

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    46

    Design Example 1(Typical House with 2 Rooms and Verandah)

    Design of One-Way Slab

    Shrinkage Reinforcement:

    Ast = 0.002bhf = 0.12 in2 (#3 @ 11″ c/c)

    However, for facilitating field work, we will use #3 @ 10″ c/c

  • 24

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    47

    Verandah Beam Design

    Step 01: Sizes

    Let depth of beam = 18″

    ln + depth of beam = 15.875′ + (18/12) = 17.375′

    c/c distance between beam supports

    = 16.375 + (4.5/12) = 16.75′

    Therefore l = 16.75′

    Depth (h) = (16.75/18.5) × (0.4 + 40000/100000) × 12

    = 8.69″ (Minimum requirement of ACI 9.5.2.2).

    Take h = 1.5′ = 18″

    d = h – 3 = 15″

    b = 12″

    Design Example 1(Typical House with 2 Rooms and Verandah)

    Verandah Beam

    16.375 16.375

    ln = 16.375 – 0.5(12/12) = 15.875 ln = 16.375 – 0.5(12/12) = 15.875

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    48

    Verandah Beam Design

    Step 02: Loads

    Load on beam will be equal to

    Factored load on beam from slab + factored

    self weight of beam web

    Factored load on slab = 0. 211 ksf

    Load on beam from slab = 0. 211 ksf x 5 =

    1.055 k/ft

    Factored Self load of beam web =

    = 1.2 x (13 × 12/144) × 0.15 = 0.195 k/ft

    Total load on beam = 1.055 + 0.195

    = 1.25 k/ft

    5′

    Design Example 1(Typical House with 2 Rooms and Verandah)

    ln = 8′

    9″ Brick Wall

    8/2 = 4′

    12″ Column

    4′ + 1′ = 5′

  • 25

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    49

    Verandah Beam

    Design

    Step 03: Analysis

    Using ACI Moment

    Coefficients for analysis

    of verandah beam

    Design Example 1(Typical House with 2 Rooms and Verandah)

    16.375

    ln = 16.375 – 0.5(12/12) = 15.875 ln = 16.375 – 0.5(12/12) = 15.87516.375

    16.375

    ln = 15.875 ln = 15.875

    9.92 k

    11.41 k

    Vu(ext) = 8.34 k

    Vu(int) = 9.61 k

    343.66 in-kip 343.66 in-kip

    420.03 in-kip

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Beam Design

    Flexure Design:

    Shear Design:

    Smax is min. of: (1) Avfy/(50bw) = 14.67″ (2) d/2 =7.5″ (3) 24″ c/c (4) Avfy/ 0.75√(fc′)bw = 17.85″

    50

    Design Example 1(Typical House with 2 Rooms and Verandah)

    Mu(in-kip)

    d (in.)

    b (in.)

    As(in2)

    Asmin(in2)

    Asmax(in2)

    As(governing)

    Bar used

    # of bars

    343.66 (+) 15 28.75 (beff) 0.64 0.90 3.654 0.90 #4 5

    #5 3

    420.03 (-) 15 12 0.81 0.90 3.654 0.90 #4 5

    #4 + #5 2 + 2

    Location Vu (@ d)(kip)

    ΦVc = Φ2 �′�bwd (kips) ΦVc > Vu, Hence

    providing minimum reinforcement.

    smax, ACI

    S taken(#3 2-legged)

    Exterior 8.34 14.78 7.5″ 7.5″

    Interior 9.61 14.78 7.5″ 7.5″

  • 26

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    51

    Design Example 1(Typical House with 2 Rooms and Verandah)

    Column Design

    Sizes:

    Column size = 12″ × 12″

    Loads:

    Pu = 11.41 × 2 = 22.82 kip

    Verandah Column

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    52

    Design Example 1(Typical House with 2 Rooms and Verandah)

    Column Design

    Main Reinforcement Design:

    Nominal strength (ΦPn) of axially loaded column is:

    ΦPn = 0.80Φ {0.85fc′ (Ag – Ast) + Astfy} {for tied column, ACI 10.3.6}

    Let Ast = 1% of Ag (Ast is the main steel reinforcement area)

    ΦPn = 0.80 × 0.65 × {0.85 × 3 × (144 – 0.01 × 144) + 0.01 × 144 × 40}

    = 218.98 kip > Pu = 22.82 kip, O.K.

    Ast =0.01 × 144 =1.44 in2

    Using 3/4″ Φ (#6) with bar area Ab = 0.44 in2

    No. of bars = 1.44/0.44 = 3.27 ≈ 4 bars

    Use 4 #6 bars (or 8 #4 bars) and #3 ties @ 9″ c/c

  • 27

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    53

    Design Example 1(Typical House with 2 Rooms and Verandah)

    Drafting Details for

    Slabs

    Panel Depth (in) Mark Bottom Reinforcement Mark Top reinforcement

    S1 5"M1 #3 @ 10" c/c

    MT1 #3 @ 10" c/c Continuous EndMT1 #3 @ 18" c/c Non Continuous End

    M2 #3 @ 10" c/cMT2 #3 @ 6" c/c Continuous EndMT2 #3 @ 18" c/c Non Continuous End

    S2 5"M1 #3 @ 10" c/c MT2 #3 @ 6" c/c Continuous EndM2 #3 @ 10" c/c MT2 #3 @ 18" c/c Non Continuous End

    S2 9' wide

    M1 M1

    M2M2

    MT1 MT1 MT1

    MT2 MT2

    MT2MT2

    M1

    M2

    C1

    AA

    B

    S1 16' x 12' S1 16' x 12'

    B MT2

    B1 B1

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    54

    Design Example 1(Typical House with 2 Rooms and Verandah)

    Drafting Details for Slabs

    SECTION A-A

    L /4 = 4'-0" L /3 = 5'-3"

    L = 16'-0"

    #3 @ 10" c/c

    #3 @ 10" c/c

    #3 @ 18" c/c #3 @ 18" c/c

    1 1

    h = 5"

    #3 @ 10" c/c

    #3 @ 10" c/c

    L/3=2'-8" L/4=2'-0"

    #3 @ 10" c/c

    #3 @ 10" c/c

    #3 @ 18" c/c#3 @ 10" c/c

    9" Brick Masonry Wall

    12" x 18" Beam

    #3 @ 10" c/c

    #3 @ 10" c/c#3 @ 10" c/c

    #3 @ 18" c/c #3 @ 6" c/c

    2

    2

    SECTION B-B

    L = 12'-0" L = 8'-0"

    L /4 = 4'-0"2 L /3 = 4'-0"

  • 28

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    55

    Design Example 1(Typical House with 2 Rooms and Verandah)

    Drafting Details for Verandah Beam

    2 #5 Bars

    2 #4 Bars

    SECTION B-B

    12"

    18"

    5"

    3 #5 Bars

    #3,2 legged stirrups @ 7.5" c/c

    SECTION A-A

    12"

    18"

    5"

    3 #5 Bars

    #3,2 legged stirrups @ 7.5" c/c

    2 #4 Bars

    A

    A

    A

    A

    2 #4 + 2 #5 Bars

    BEAM (B1)

    B

    B

    L = 11'-10.5" L = 11'-10.5"

    0.33L = 4'-0" 0.33L = 4'-0"

    2 #4 Bars

    3 #5 Bars #3, 2 legged stirrups @ 7.5" c/c

    s /2=3.75"

    3 #5 Bars 3 #5 Bars

    B

    B

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    56

    Design Example 1(Typical House with 2 Rooms and Verandah)

    Drafting Details for Verandah Column

    OR

    12"

    4 #6 Bars

    #3 ties @ 9" c/c

    12"

    12"

    #3 Ties @ 9" c/c

    4 #6 Bars

    8#4 bars

    #3 ties @ 9" c/c

    12"

    12"

    12"

    8 #4 Bars

    #3 Ties @ 9" c/c

  • 29

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    A 100′ 60′, 3-storey commercial building is to be designed. The grids of

    column plan are fixed by the architect.

    In this example, the slab of one of the floors of this 3-storey building will

    be designed.

    57

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Given Data:

    Material Properties:

    f′c = 3 ksi, fy = 40 ksi

    Sizes:

    Slab thickness = 7″

    Columns = 14″ 14″

    Beams = 14″ 20″

    Loads:

    S.D.L = Nil

    Self Weight = 0.15 x (7/12) = 0.0875 ksf

    L.L = 144 psf = 0.144 ksf ; wu = 0.336 ksf

    58

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

  • 30

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Complete analysis of the slab is done by analyzing four panels

    59

    Panel I Panel I

    Panel I Panel I

    Panel II Panel II

    Panel III Panel III

    Panel III Panel III

    Panel IV Panel IV

    4 spans @ 25′-0″

    3 sp

    ans @

    20′-0″

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis (Panel-I)

    Case = 4

    m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

    Ca,neg = 0.071

    Cb,neg = 0.029

    Ca,posDL = 0.039

    Cb,posDL = 0.016

    Ca,posLL = 0.048

    Cb,posLL = 0.020

    Case 4la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,neg

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    60

  • 31

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis (Panel-I)

    Case = 4

    m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

    Ca,neg = 0.071

    Cb,neg = 0.029

    Ca,posDL = 0.039

    Cb,posDL = 0.016

    Ca,posLL = 0.048

    Cb,posLL = 0.020

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    61

    Case 4la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,neg

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis (Panel-I)

    Case = 4

    m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

    Ca,neg = 0.071

    Cb,neg = 0.029

    Ca,posDL = 0.039

    Cb,posDL = 0.016

    Ca,posLL = 0.048

    Cb,posLL = 0.020

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    62

    Case 4la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,neg

  • 32

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis (Panel-I)

    Case = 4

    m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

    Ca,neg = 0.071

    Cb,neg = 0.029

    Ca,posDL = 0.039

    Cb,posDL = 0.016

    Ca,posLL = 0.048

    Cb,posLL = 0.020

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    63

    Case 4la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,neg

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis (Panel-I)

    Case = 4

    m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

    Ca,neg = 0.071

    Cb,neg = 0.029

    Ca,posDL = 0.039

    Cb,posDL = 0.016

    Ca,posLL = 0.048

    Cb,posLL = 0.020

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    64

    Case 4la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,neg

  • 33

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis (Panel-I)

    Case = 4

    m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

    Ca,neg = 0.071

    Cb,neg = 0.029

    Ca,posDL = 0.039

    Cb,posDL = 0.016

    Ca,posLL = 0.048

    Cb,posLL = 0.020

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    65

    Case 4la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,neg

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    66

    Two-Way Slab Analysis (Panel-I)

    Calculating moments using ACI Coefficients:

    Ma, neg = Ca, negwula2

    Mb, neg = Cb, negwulb2

    Ma, pos, (dl + ll) = M a, pos, dl + M a, pos, ll = Ca, pos, dl × wu, dl × la2 + Ca, pos, ll × wu, ll × la

    2

    Mb, pos, (dl + ll) = Mb, pos, dl + Mb, pos, ll = Cb, pos, dl × wu, dl × lb2 + Cb, pos, ll × wu, ll × lb

    2

    Using above relations the moments calculated are:

    Ca,neg = 0.071 Cb,neg = 0.029

    Ca,posLL = 0.048 Cb,posLL = 0.020

    Ca,posDL = 0.039 Cb,posDL = 0.016

    wu, dl = 0.105 ksf, wu, ll = 0.2304 ksf, wu = 0.336 ksf

    Ma,neg = 8.44 ft-k (101.2 in-k)

    Mb,neg = 5.52 ft-k (66.2 in-k)

    Ma,pos = 5.37 ft-k (64.4 in-k)

    Mb,pos = 3.57 ft-k (42.8 in-k)

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Case 4la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,neg

  • 34

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis (Panel-II)

    Case = 9

    m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

    Ca,neg = 0.075

    Cb,neg = 0.017

    Ca,posDL = 0.029

    Cb,posDL = 0.010

    Ca,posLL = 0.042

    Cb,posLL = 0.017

    Case 9la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,negMb,neg

    Ma

    ,ne

    g

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    67

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis (Panel-II)

    Case = 9

    m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

    Ca,neg = 0.075

    Cb,neg = 0.017

    Ca,posDL = 0.029

    Cb,posDL = 0.010

    Ca,posLL = 0.042

    Cb,posLL = 0.017

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    68

    Case 9la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,negMb,neg

    Ma

    ,ne

    g

  • 35

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis (Panel-II)

    Case = 9

    m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

    Ca,neg = 0.075

    Cb,neg = 0.017

    Ca,posDL = 0.029

    Cb,posDL = 0.010

    Ca,posLL = 0.042

    Cb,posLL = 0.017

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    69

    Case 9la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,negMb,neg

    Ma

    ,ne

    g

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis (Panel-II)

    Case = 9

    m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

    Ca,neg = 0.075

    Cb,neg = 0.017

    Ca,posDL = 0.029

    Cb,posDL = 0.010

    Ca,posLL = 0.042

    Cb,posLL = 0.017

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    70

    Case 9la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,negMb,neg

    Ma

    ,ne

    g

  • 36

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis (Panel-II)

    Case = 9

    m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

    Ca,neg = 0.075

    Cb,neg = 0.017

    Ca,posDL = 0.029

    Cb,posDL = 0.010

    Ca,posLL = 0.042

    Cb,posLL = 0.017

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    71

    Case 9la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,negMb,neg

    Ma

    ,ne

    g

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis (Panel-II)

    Case = 9

    m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

    Ca,neg = 0.075

    Cb,neg = 0.017

    Ca,posDL = 0.029

    Cb,posDL = 0.010

    Ca,posLL = 0.042

    Cb,posLL = 0.017

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    72

    Case 9la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,negMb,neg

    Ma

    ,ne

    g

  • 37

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    73

    Two-Way Slab Analysis (Panel-II)

    Calculating moments using ACI Coefficients:

    Ma, neg = Ca, negwula2

    Mb, neg = Cb, negwulb2

    Ma, pos, (dl + ll) = M a, pos, dl + M a, pos, ll = Ca, pos, dl × wu, dl × la2 + Ca, pos, ll × wu, ll × la

    2

    Mb, pos, (dl + ll) = Mb, pos, dl + Mb, pos, ll = Cb, pos, dl × wu, dl × lb2 + Cb, pos, ll × wu, ll × lb

    2

    Using above relations the moments calculated are:

    Ca,neg = 0.075 Cb,neg = 0.017

    Ca,posLL = 0.042 Cb,posLL = 0.017

    Ca,posDL = 0.029 Cb,posDL = 0.010

    wu, dl = 0.105 ksf, wu, ll = 0.2304 ksf, wu = 0.336 ksf

    Ma,neg = 8.91 ft-k (106.9 in-k)

    Mb,neg = 3.24 ft-k (38.8 in-k)

    Ma,pos = 4.51 ft-k (54.1 in-k)

    Mb,pos = 2.82 ft-k (33.8 in-k)

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Case 9la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,negMb,neg

    Ma

    ,ne

    g

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis (Panel-III)

    Case = 8

    m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

    Ca,neg = 0.055

    Cb,neg = 0.041

    Ca,posDL = 0.032

    Cb,posDL = 0.015

    Ca,posLL = 0.044

    Cb,posLL = 0.019

    Case 8la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,negMb,neg

    Ma

    ,ne

    g

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    74

  • 38

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis (Panel-III)

    Case = 8

    m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

    Ca,neg = 0.055

    Cb,neg = 0.041

    Ca,posDL = 0.032

    Cb,posDL = 0.015

    Ca,posLL = 0.044

    Cb,posLL = 0.019

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    75

    Case 8la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,negMb,neg

    Ma

    ,ne

    g

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis (Panel-III)

    Case = 8

    m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

    Ca,neg = 0.055

    Cb,neg = 0.041

    Ca,posDL = 0.032

    Cb,posDL = 0.015

    Ca,posLL = 0.044

    Cb,posLL = 0.019

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    76

    Case 8la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,negMb,neg

    Ma

    ,ne

    g

  • 39

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis (Panel-III)

    Case = 8

    m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

    Ca,neg = 0.055

    Cb,neg = 0.041

    Ca,posDL = 0.032

    Cb,posDL = 0.015

    Ca,posLL = 0.044

    Cb,posLL = 0.019

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    77

    Case 8la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,negMb,neg

    Ma

    ,ne

    g

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis (Panel-III)

    Case = 8

    m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

    Ca,neg = 0.055

    Cb,neg = 0.041

    Ca,posDL = 0.032

    Cb,posDL = 0.015

    Ca,posLL = 0.044

    Cb,posLL = 0.019

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    78

    Case 8la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,negMb,neg

    Ma

    ,ne

    g

  • 40

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis (Panel-III)

    Case = 8

    m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

    Ca,neg = 0.055

    Cb,neg = 0.041

    Ca,posDL = 0.032

    Cb,posDL = 0.015

    Ca,posLL = 0.044

    Cb,posLL = 0.019

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    79

    Case 8la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,negMb,neg

    Ma

    ,ne

    g

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    80

    Two-Way Slab Analysis (Panel-III)

    Calculating moments using ACI Coefficients:

    Ma, neg = Ca, negwula2

    Mb, neg = Cb, negwulb2

    Ma, pos, (dl + ll) = M a, pos, dl + M a, pos, ll = Ca, pos, dl × wu, dl × la2 + Ca, pos, ll × wu, ll × la

    2

    Mb, pos, (dl + ll) = Mb, pos, dl + Mb, pos, ll = Cb, pos, dl × wu, dl × lb2 + Cb, pos, ll × wu, ll × lb

    2

    Using above relations the moments calculated are:

    Ca,neg = 0.055 Cb,neg = 0.041

    Ca,posLL = 0.044 Cb,posLL = 0.019

    Ca,posDL = 0.032 Cb,posDL = 0.015

    wu, dl = 0.105 ksf, wu, ll = 0.2304 ksf, wu = 0.336 ksf

    Ma,neg = 6.54 ft-k (78.4 in-k)

    Mb,neg = 7.80 ft-k (93.6 in-k)

    Ma,pos = 4.78 ft-k (57.4 in-k)

    Mb,pos = 3.38 ft-k (40.5 in-k)

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Case 8la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,negMb,neg

    Ma

    ,ne

    g

  • 41

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis (Panel-IV)

    Case = 2

    m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

    Ca,neg = 0.065

    Cb,neg = 0.027

    Ca,posDL = 0.026

    Cb,posDL = 0.011

    Ca,posLL = 0.041

    Cb,posLL = 0.017

    Case 2la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,negMb,neg

    Ma

    ,ne

    g

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    81

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis (Panel-IV)

    Case = 2

    m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

    Ca,neg = 0.065

    Cb,neg = 0.027

    Ca,posDL = 0.026

    Cb,posDL = 0.011

    Ca,posLL = 0.041

    Cb,posLL = 0.017

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    82

    Case 2la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,negMb,neg

    Ma

    ,ne

    g

  • 42

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis (Panel-IV)

    Case = 2

    m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

    Ca,neg = 0.065

    Cb,neg = 0.027

    Ca,posDL = 0.026

    Cb,posDL = 0.011

    Ca,posLL = 0.041

    Cb,posLL = 0.017

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    83

    Case 2la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,negMb,neg

    Ma

    ,ne

    g

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis (Panel-IV)

    Case = 2

    m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

    Ca,neg = 0.065

    Cb,neg = 0.027

    Ca,posDL = 0.026

    Cb,posDL = 0.011

    Ca,posLL = 0.041

    Cb,posLL = 0.017

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    84

    Case 2la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,negMb,neg

    Ma

    ,ne

    g

  • 43

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis (Panel-IV)

    Case = 2

    m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

    Ca,neg = 0.065

    Cb,neg = 0.027

    Ca,posDL = 0.026

    Cb,posDL = 0.011

    Ca,posLL = 0.041

    Cb,posLL = 0.017

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    85

    Case 2la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,negMb,neg

    Ma

    ,ne

    g

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Two-Way Slab Analysis (Panel-IV)

    Case = 2

    m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

    Ca,neg = 0.065

    Cb,neg = 0.027

    Ca,posDL = 0.026

    Cb,posDL = 0.011

    Ca,posLL = 0.041

    Cb,posLL = 0.017

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    86

    Case 2la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,negMb,neg

    Ma

    ,ne

    g

  • 44

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    87

    Two-Way Slab Analysis (Panel-IV)

    Calculating moments using ACI Coefficients:

    Ma, neg = Ca, negwula2

    Mb, neg = Cb, negwulb2

    Ma, pos, (dl + ll) = M a, pos, dl + M a, pos, ll = Ca, pos, dl × wu, dl × la2 + Ca, pos, ll × wu, ll × la

    2

    Mb, pos, (dl + ll) = Mb, pos, dl + Mb, pos, ll = Cb, pos, dl × wu, dl × lb2 + Cb, pos, ll × wu, ll × lb

    2

    Using above relations the moments calculated are:

    Ca,neg = 0.065 Cb,neg = 0.027

    Ca,posLL = 0.041 Cb,posLL = 0.017

    Ca,posDL = 0.026 Cb,posDL = 0.011

    wu, dl = 0.105 ksf, wu, ll = 0.2304 ksf, wu = 0.336 ksf

    Ma,neg = 7.72 ft-k (92.7 in-k)

    Mb,neg = 5.14 ft-k (61.6 in-k)

    Ma,pos = 4.31 ft-k (51.8 in-k)

    Mb,pos = 2.88 ft-k (34.5 in-k)

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Case 2la = 18.83′

    lb = 23.83′

    Ma

    ,ne

    gM

    a,p

    os

    Mb,posMb,negMb,neg

    Ma

    ,ne

    g

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    88

    Analysis Results (All values are in ft-kip)

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    8.42

    4 spans @ 25′-0″

    3 spans @ 2

    0′-0″

    5.375.523.57

    8.91

    8.91

    3.244.51

    2.82

    6.54

    7.80 7.804.783.38

    7.72

    7.72

    5.145.144.31

    2.881.50

    1.79

    1.19 1.19 Mneg at Non-

    Continuous End =

    1/3 of Mpos

    NOTE: White: Longer Direction Moments, Yellow: Shorter Direction Moments

  • 45

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    89

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Slab Design

    First determining the capacity of min. reinforcement:

    As,min = 0.002bhf = 0.002 × 12 × 7 = 0.17 in2

    For #4 bars, spacing = (0.20/0.17) × 12 = 14.2 c/c.

    ACI max spacing for two-ways slabs = 2h = 2(7) = 14 or 18

    Using #4 @ 12 c/c

    For the 12 spacing: As = (0.20/12) × 12 = 0.20 in2. Hence As,min = 0.20 in

    2

    Capacity for As,min: a = (0.20 × 40)/(0.85 × 3 × 12) = 0.26

    ΦMn = ΦAsminfy(d – a/2) = {0.9 × 0.20 × 40(6 – (0.26/2))}/12 = 3.52 ft-kip

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    90

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Slab Design

    Positive Moments in Long Direction:

    3.57 ft-kip/ft

    3.38 ft-kip/ft

    2.82 ft-kip/ft

    2.88 ft-kip/ft

    Since all the above moments values are almost equal to or less than

    3.52 ft-kip/ft. Therefore using #4 @ 12 c/c for all positive moments in

    short direction.

  • 46

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    91

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Slab Design

    Positive Moments in Short Direction:

    5.37 ft-kip/ft

    4.51 ft-kip/ft

    4.78 ft-kip/ft

    4.31 ft-kip/ft

    Using trial and success method for determining As for 5.37 ft-kip/ft:

    Assume a = 0.2d= 0.2(6) = 1.2, As = (5.37 × 12)/{0.9 × 40(6 – (1.2/2))} = 0.33 in2

    Now, a = (0.33 × 40)/(0.85 × 3 × 12) = 0.43, As = 0.31 in2

    For #4 bars, spacing = (0.20/0.31) × 12 = 7.7

    As all the above moments are almost same, we will use #4 @ 7 c/c for all above

    moments.

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    92

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Slab Design

    Negative Moments at Non-Continuous Ends in Short & Long Directions:

    1.19 ft-kip/ft

    1.79 ft-kip/ft

    1.50 ft-kip/ft

    Since, all the above moments are

    less than 3.52 ft-kip/ft, therefore using

    #4 @ 12 c/c

  • 47

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    93

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Slab Design

    Negative Moments at Continuous Ends in Short Direction:

    8.42 ft-kip/ft

    8.91 ft-kip/ft

    7.72 ft-kip/ft

    6.54 ft-kip/ft

    Using trial and success method:

    For 8.91 ft-kip/ft: As = 0.52 in2

    Using #4 bars, spacing = 4.5 c/c

    As all above moments are almost same, we will use #4 @ 4.5 c/c

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    94

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Slab Design

    Negative Moments at Continuous Ends in Long Direction:

    5.52 ft-kip/ft

    3.24 ft-kip/ft

    7.80 ft-kip/ft

    5.14 ft-kip/ft

    Reinforcement:

    7. 80 ft-kip/ft is almost equal to 8.91 ft-kip/ft:

    Therefore using #4 bars @ 4.5 c/c

    7. 80 ft-kip/ft is almost equal to 8.91 ft-kip/ft:

    Therefore using #4 bars @ 7 c/c

  • 48

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Slab Reinforcement Details

    95

    A

    BBB

    C

    C

    A

    C CB

    A

    A

    BA

    C

    C

    A

    A B

    A

    A= #4 @ 12″B = #4 @ 7″C = #4 @ 4.5″

    4 spans @ 25′-0″

    3 sp

    ans @

    20

    ′-0″

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    NOTE: White: Longer Direction Moments, Yellow: Shorter Direction Moments

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    96

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Load Transfer from Slab to the Beam

    Review of Load transfer to Beam from One-Way Slabs

    • In case of one-way slab system the entire slab load is transferred in short direction.

    • Load transfer in short direction = (Wu × l / 2 × 1) + (Wu × l / 2 × 1)

    • Load transfer in long direction = Wu × l / 2 × 0

    l/2

    l/2

    l/2 l/2

  • 49

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    97

    Load transfer from Slab to Beam

    Load Transfer to Beam from Two-Way Slab

    • In case of two way slab system, entire slab load is NOT transferred in shorter direction.

    • Load transfer in shorter direction = (Wu × l / 2 × Wa ) + (Wu × l / 2 × Wa )

    Longer Direction

    4 spans @ 25′-0″

    3 sp

    ans @

    20′-0

    Sh

    orte

    r Dire

    ctio

    n

    Panel I Panel I

    Panel I Panel I

    Panel II Panel II

    Panel III Panel III

    Panel III Panel III

    Panel IV Panel IV

    This value will NOT be 1 in this case, It is specified by ACI Table• Load transfer in longer direction = (Wu × l / 2 × Wb ) + (Wu × l / 2 × Wb )

    Wb = 1 - Wa

    ACI Table for Wa values

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    98

    Load transfer from Slab to Beam

    Load Transfer to Beam from Two-Way Slab

    4 spans @ 25′-0″

    3 sp

    an

    s @ 2

    0′-0

    Panel I Panel I

    Panel I Panel I

    Panel II Panel II

    Panel III Panel III

    Panel III Panel III

    Panel IV Panel IV

    Load Transfer from Slab to Beam B1

    • Load is transferred to B1 from Panel-I and Panel-II in

    short direction

    = Wu × l / 2 × Wa,Panel-I + Wu × l / 2 × Wa,Panel-II

    = 0.336 × 20/2 × 0.71 + 0.336 × 20/2 × 0.83

    = 5.17 k/ft

    (For Wa Values, refer to the tables on next slides)• Wu = 0.336 ksf

    • Wa,Panel-I = 0.71

    • Wa,Panel-II = 0.83

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

  • 50

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    99

    Load transfer from Slab to Beam

    Load Transfer to Beam from Two-Way Slab (For Beam B1)

    Sh

    orte

    r Dire

    ction

    20′

    Wu = 0.336 ksf

    Sh

    orte

    r Dire

    ctio

    n

    20′

    Wu = 0.336 ksf

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    100

    Load transfer from Slab to Beam

    Load Transfer to Beam from Two-Way Slab

    4 spans @ 25′-0″

    3 sp

    an

    s @ 2

    0′-0

    Panel I Panel I

    Panel I Panel I

    Panel II Panel II

    Panel III Panel III

    Panel III Panel III

    Panel IV Panel IV

    Load Transfer from Slab to Beam B2

    • Load is transferred to B2 from Panel-I and Panel-III in

    long direction

    = Wu × l / 2 × Wb,Panel-I + Wu × l / 2 × Wb,Panel-III

    = 0.336 × 25/2 × (1 - 0.71) + 0.336 × 25/2 × (1 - 0.55)

    = 3.11 k/ft

    (For Wa values, refer to the tables on next slide)• Wu = 0.336 ksf

    • Wb,Panel-I = (1 – Wa,Panel-I) = 1 - 0.71 = 0.29

    • Wb,Panel-III = (1 – Wa,Panel-III) = 1 - 0.55 = 0.45

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

  • 51

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    101

    Load transfer from Slab to Beam (For Beam B2)

    Load Transfer to Beam from Two-Way Slab

    = 0.336 × 25/2 × (1 - 0.71) + 0.336 × 25/2 ×

    (1 - 0.55)

    = 3.11 k/ft

    Sh

    orte

    r Dire

    ction

    20′

    Wu = 0.336 ksf

    Sh

    orte

    r Dire

    ctio

    n

    20′

    Wu = 0.336 ksf

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Moment Coefficient Method: Example 2

    Load On Beams from coefficient tables

    102

    Table: Load on beam in Panel I, usingCoefficients

    (wu = 0.336 ksf)

    BeamLength

    (ft)

    Width (bs) of slab panel

    supported by beam

    Wa Wb

    Load due to slab, Wwubs(k/ft)

    B1 25 10 0.71 - 2.39

    B2 25 10 0.71 - 2.39

    B3 20 12.5 - 0.29 1.22

    B4 20 12.5 - 0.29 1.22

    Panel I

    4 spans @ 25′-0″

    3 spans @ 20

    ′-0″

    B1

    B1

    B2

    B2

    B3 B3 B3 B4B4

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

  • 52

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Table: Load on beam in Panel I, usingCoefficients

    (wu = 0.336 ksf)

    BeamLength

    (ft)

    Width (bs) of slab panel

    supported by beam

    Wa Wb

    Load due to slab, Wwubs(k/ft)

    B1 25 10 0.71 - 2.39

    B2 25 10 0.71 - 2.39

    B3 20 12.5 - 0.29 1.22

    B4 20 12.5 - 0.29 1.22

    Moment Coefficient Method: Example 2

    Load On Beams from coefficient tables

    B1

    B1

    B2

    B2

    B3 B3 B3 B4B4

    4 spans @ 25′-0″

    3 sp

    ans @

    20

    ′-0″

    Panel I

    103

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Panel I

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Moment Coefficient Method: Example 2

    Load On Beams from coefficient tables

    104

    4 spans @ 25′-0″

    3 spans @ 20

    ′-0″

    B1

    B1

    B2

    B2

    B3 B3 B3 B4B4

    Table: Load on beam in Panel II, usingCoefficients

    (wu = 0.336 ksf)

    BeamLength

    (ft)

    Width (bs) of slab panel

    supported by beam

    Wa Wb

    Load due to slab, Wwubs(k/ft)

    B1 25 10 0.83 - 2.78

    B3 20 12.5 - 0.17 0.714

    B4 20 12.5 - 0.17 0.714

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Panel II

  • 53

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Table: Load on beam in Panel II, usingCoefficients

    (wu = 0.336 ksf)

    BeamLength

    (ft)

    Width (bs) of slab panel

    supported by beam

    Wa Wb

    Load due to slab, Wwubs(k/ft)

    B1 25 10 0.83 - 2.78

    B3 20 12.5 - 0.17 0.714

    B4 20 12.5 - 0.17 0.714

    Moment Coefficient Method: Example 2

    Load On Beams from coefficient tables

    B1

    B1

    B2

    B2

    B3 B3 B3 B4B4

    Panel II

    4 spans @ 25′-0″

    3 sp

    ans @

    20

    ′-0″

    105

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Panel II

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Moment Coefficient Method: Example 2

    Load On Beams from coefficient tables

    106

    4 spans @ 25′-0″

    3 spans @ 20

    ′-0″

    B1

    B1

    B2

    B2

    B3 B3 B3 B4B4

    Table: Load on beam in Panel III, usingCoefficients

    (wu = 0.336 ksf)

    BeamLength

    (ft)

    Width (bs) of slab panel

    supported by beam

    Wa Wb

    Load due to slab, Wwubs(k/ft)

    B1 25 10 0.55 - 1.84

    B2 25 10 0.55 - 1.84

    B3 20 12.5 - 0.45 1.89

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Panel III

  • 54

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Table: Load on beam in Panel III, usingCoefficients

    (wu = 0.336 ksf)

    BeamLength

    (ft)

    Width (bs) of slab panel

    supported by beam

    Wa Wb

    Load due to slab, Wwubs(k/ft)

    B1 25 10 0.55 - 1.84

    B2 25 10 0.55 - 1.84

    B3 20 12.5 - 0.45 1.89

    Moment Coefficient Method: Example 2

    Load On Beams from coefficient tables

    B1

    B1

    B2

    B2

    B3 B3 B3 B4B4

    Panel III

    4 spans @ 25′-0″

    3 sp

    ans @

    20

    ′-0″

    107

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Panel III

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Moment Coefficient Method: Example 2

    Load On Beams from coefficient tables

    108

    4 spans @ 25′-0″

    3 spans @ 20

    ′-0″

    B1

    B1

    B2

    B2

    B3 B3 B3 B4B4

    Table: Load on beam in Panel IV, usingCoefficients

    (wu = 0.336 ksf)

    BeamLength

    (ft)

    Width (bs) of slab panel

    supported by beam

    Wa Wb

    Load due to slab, Wwubs(k/ft)

    B1 25 10 0.71 - 2.39

    B3 20 12.5 - 0.29 1.22

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Panel IV

  • 55

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Table: Load on beam in Panel IV, usingCoefficients

    (wu = 0.336 ksf)

    BeamLength

    (ft)

    Width (bs) of slab panel

    supported by beam

    Wa Wb

    Load due to slab, Wwubs(k/ft)

    B1 25 10 0.71 - 2.39

    B3 20 12.5 - 0.29 1.22

    Moment Coefficient Method: Example 2

    Load On Beams from coefficient tables

    B1

    B1

    B2

    B2

    B3 B3 B3 B4B4

    Panel IV

    4 spans @ 25′-0″

    3 sp

    ans @

    20

    ′-0″

    109

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Panel IV

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Moment Coefficient Method: Example 2

    Load On Beams

    110

    2.39 k/ft

    1.22 k/ft

    2.39 k/ft

    1.22 k/ft

    2.77 k/ft

    2.77 k/ft

    0.71 k/ft 0.71 k/ft

    1.84 k/ft

    1.89 k/ft

    1.84 k/ft

    1.89 k/ft

    2.39 k/ft

    1.22 k/ft

    2.39 k/ft

    1.22 k/ft

    4 spans @ 25′-0″

    3 spans @ 20

    ′-0″

    B1

    B1

    B2

    B2

    B3 B3 B3 B4B4

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

  • 56

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Moment Coefficient Method: Example 2

    Load On Beams

    111

    5.16 k/ft

    1.22 k/ft

    2.39 k/ft

    3.11 k/ft

    5.16 k/ft

    0.71 k/ft 1.93 k/ft

    4.23 k/ft

    1.84 k/ft

    3.11 k/ft

    4.23 k/ft

    1.93 k/ft

    4 spans @ 25′-0″

    3 sp

    ans @

    20

    ′-0″

    B1

    B1

    B2

    B2

    B3 B3 B3 B4B4

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Moment Coefficient Method: Example 2

    Load On Beams

    112

    Self weight of beam

    = 1.2 × (14 ×

    13/144) × 0.15

    = 0.23 kip/ft

    Adding this with the

    calculated loads on

    beams:

    14

    20

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    5.16 k/ft

    1.22 k/ft

    2.39 k/ft

    3.11 k/ft

    5.16 k/ft

    0.71 k/ft 1.93 k/ft

    4.23 k/ft

    1.84 k/ft

    3.11 k/ft

    4.23 k/ft

    1.93 k/ft

    4 spans @ 25′-0″

    3 spans @ 20

    ′-0″

    B1

    B1

    B2

    B2

    B3 B3 B3 B4B4

  • 57

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Moment Coefficient Method: Example 2

    Load On Beams (including self-weight)

    113

    1.45 k/ft

    2.62 k/ft

    5.39 k/ft

    0.94 k/ft

    3.34 k/ft

    2.07 k/ft

    2.16 k/ft

    4.46 k/ft

    4 spans @ 25′-0″

    3 sp

    ans @

    20

    ′-0″

    B1

    B1

    B2

    B2

    B3 B3 B3 B4B4

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    114

    lnln ln

    Simplesupport

    Integral withsupport

    wu

    Spandrelsupport

    NegativeMoment

    x wuln2

    1/24 1/10* 1/11 1/11 1/10* 0

    *1/9 (2 spans)

    * 1/11(on both faces of other interior supports)

    Columnsupport

    1/16

    PositiveMomentx

    1/14 1/16 1/11

    wuln2

    Note: For simply supported slab, M = wul2/8, where l = span length (ACI 8.9).

    * 1/12 (for all spans with ln < 10 ft)

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

  • 58

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    115

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Analysis of Beams

    Interior Beam B1

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    116

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Analysis of Beams

    Exterior Beam B2

  • 59

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    117

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

    Analysis of Beams

    Interior Beam B3

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Analysis of Beams

    Exterior Beam B4

    118

    Design Example 2(100′ × 60′, 3-Storey Commercial Building)

  • 60

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    119

    Pictures of a Multi-StoreyCommercial Building

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    120

    Pictures of a Multi-StoreyCommercial Building

  • 61

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Different Stages of Building Construction

    121

    Phases of Construction

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Moment Coefficient Method: Home Work

    Design the given slab system

    122

    Panel I Panel I

    Panel I Panel I

    Panel II Panel II

    Panel III Panel III

    Panel III Panel III

    Panel IV Panel IV

    4 spans @ 25′-0″

    3 spans @ 20

    ′-0″

    Slab thickness = 6″

    SDL = 40 psf

    LL = 60 psf

    fc′ =3 ksi

    fy = 40 ksi

    Practice Examples

  • 62

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Moment Coefficient Method: Home Work

    Design the given slab system

    123

    Panel I Panel I

    Panel I Panel I

    Panel II Panel II

    Panel III Panel III

    Panel III Panel III

    Panel IV Panel IV

    4 spans @ 20′-0″

    3 sp

    ans @

    15′-0″

    Slab thickness = 6″

    SDL = 40 psf

    LL = 60 psf

    fc′ =3 ksi

    fy = 40 ksi

    Practice Examples

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    CRSI Design Handbook

    ACI 318

    Design of Concrete Structures 13th Ed. by Nilson, Darwin and

    Dolan.

    124

    References

  • 63

    Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    The End

    125