30
MX350 GEZC Service School Slide 1 of 30 MX350 Controller Overview Last update: 14-Apr-2010

Last update: 14-Apr-2010 - cccusi.comcccusi.com/GEZC/class_materials/MX350 ATS Controllers Intro R1_2.pdf · Last update: 14-Apr-2010. Contents 1. Introduction 2. ... alarms, 10 channel

Embed Size (px)

Citation preview

MX350 GEZC Service School Slide 1 of 30

MX350 Controller Overview

Last update: 14-Apr-2010

Contents

1. Introduction

2. Order Options

3. Order Code

4. Ordering Information

5. Terminals

6. UTA

7. Customer Connection Block

8. System Connections

9. Display Hierarchy

10. Flex Logic

GEZC Service School Slide 2 of 30

11. SCADA

12. Communications – General

13. Communications – Memory Map

14. Setup Software

15. Brochures

16. Manuals

17. Frequently Asked Questions (FAQ)

MX350

1. Introduction

GEZC ATS Controller

• Health Care / Data Center / Waste-to-Energy / Mfg

• Have I/Os option

• Metering functions – Harmonic Analysis, power, current

• Modbus / Modbus TCP

• Std/Delay/Closed Transition ATS

• Flex Logic

• UTA – One part number

Slide 3 of 30MX350

2. Order Options

Option A: Based package, 256 eventsOption B: Option A + 20 channel data logger, 10 programmable digital + 10 Analog

alarms, 10 channel of waveform capture, Auto Loadshed

Option C: Option B + 4 Additional Inputs & Outputs (Total 8-In, 8-Out)

Option D: Option C + 4 Additional Inputs & Outputs (Total 12-In, 12-Out), Flex

Logic

Option M: Manual Operation

GEZC ATS Controller Slide 4 of 30

As shown in Page 8 of document: 1601-9071-A1

MX350

3. Order Code

GEZC ATS Controller Slide 5 of 30

As shown in Page 17 of document: 1601-9071-A1

MX350

Sample Model #: MX350-GEHE4BBAKLLLX

4. Ordering Information

GEZC ATS Controller Slide 6 of 30

As shown in Page 22 of document: DEA-405

Power panel related =>

MX350

4. Ordering Information – Cont.

GEZC ATS Controller Slide 7 of 30

As shown in Page 23 of document: DEA-405

MX350

5. Terminals

GEZC ATS Controller Slide 8 of 30

Picture as shown in Page 25 of document: 1601-9071-A1

MX350

6. UTA – 200VA

GEZC ATS Controller Slide 9 of 30

Picture as shown in Page 8 of document: DEA-405

MX350

6. UTA – Interface

GEZC ATS Controller Slide 10 of 30

Picture as shown in Page 12 of document: 91R-1000

MX350

6. UTA – Test Point

GEZC ATS Controller Slide 11 of 30

Picture as shown in Page 12 of document: 91R-1000

MX350

6. UTA – Schematic

GEZC ATS Controller Slide 12 of 30MX350

7. Customer Connection Block

GEZC ATS Controller Slide 13 of 30

Picture as shown in Page 8 of document: DEA-405

MX350

8. System Connections

GEZC ATS Controller Slide 14 of 30

Picture as shown in Page 10 of document: 1601-9071-A1

MX350

9. Display Hierarchy

GEZC ATS Controller Slide 15 of 30

Picture as shown in Page 38 of document: 1601-9071-A1

MX350

10. Flex Logic

GEZC ATS Controller Slide 16 of 30

Picture as shown in Page 10 of document: DEA-405

• Control Logic• Create customized Protection & control• Minimized aux components• Have registers for Flex Logic

MX350

11. SCADA

GEZC ATS Controller Slide 17 of 30

• EnerVista Viewpoint software• Modbus or Modbus TCP• RS485 or Ethernet• Plug & Play• System Single Line Monitoring + Control• Trending Reports• Auto Event and Waveform Retrieval

One-line diagram

Plug & Play Screen

MX350

12. Communications - General

GEZC ATS Controller Slide 18 of 30

• RS485• Modbus or Modbus TCP• Address: 1 to 254, default 254• Baud rate: 9600, 19200, 38400, 57600, and 115200 bps (default 115200)• Parity: None• Data bits: 8• Stop bits: 1• Supported Modbus function codes: 1, 3, 4, 5, 6, 8, 16• User Definable Memory Map – Increase Throughput (see P17 of document 1601-9072-A1)

• Use PC software to map the addresses• Use Function code 06H to do Single Write Register• Use Function code 03H to perform One single read of registers.

• Memory map address 0x0000H begins at 30001• Memory map ranges (30001 ~ 32272) & (40001 ~ 43479)• Format Codes (see P48~64 of document 1601-9072-A1)

• Half-Duplex only• Slave device• Can be connected in Daisy Chain• Use Termination Resistor (i.e. 120 ohm)• Polarity Specific• Ground at one end but not both (to avoid ground loop effect)• Use shielded cable

MX350

13. Communications – Memory Map

GEZC ATS Controller Slide 19 of 30

30860DATA LOG INFORMATION18

30720TRACE MEMORY SAMPLES17

30710TRACE MEMORY16

30659EVENT RECORDER15

30657SELF TEST14

30524USER MAP VALUES13

30509GCP FACTORY TEST12

30505LED STATUS FOR GRAPHICAL AND BASIC CONTROL PANEL11

30384POWER METERING10

30340VOLTAGE METERING9

30326CURRENT METERING8

30323NET CONTROL STATUS7

30318STATUS - ATS6

30302SECURITY5

30283CONTACT/VIRTUAL INPUTS/OUTPUTS STATUS4

30223REAL-TIME CLOCK3

30186LAST FAULT DATA2

30001PRODUCT INFORMATION1

Starting AddressSECTIONS

32256LOAD CONTROL TIMERS37

32237ATS TIMERS36

32221ATS S2 STATUS35

32205ATS S1 STATUS34

32182ATS S2 COUNTERS33

32159ATS S1 COUNTERS32

32148ATS R5031

32121ATS GEN30

32119ATS PREFERRED SRC29

32117ATS TEST28

32105ATS EXERCISER27

32093ATS CONTROL26

32080ATS OPERATION COUNTERS25

32064REPORT24

32037ATS TRANSFER COUNTERS23

31396TOTAL HARMONIC DISTORTION22

31378COMMUNICATION21

30987FLEXLOGIC20

30952STATUS BUFFER19

Starting AddressSECTIONSActual Values

MX350

13. Communications – Memory Map (cont.)

GEZC ATS Controller Slide 20 of 30

Set Points

41040CALIBRATION15

40857CURRENT UNBALANCE (REQUIRED=IO_A)14

40679DATA LOGGER13

40672MEMORY12

40659EVENT RECORDER11

40524COMMUNICATION SETUP10

40517COMMUNICATION SETUP9

40317PROCESS INTERLOCK8

40284CONTROLLER SETUP7

40276VOLTAGE SENSING6

40266CURRENT SENSING5

40262VIRTUAL INPUT4

40228REAL-TIME CLOCK/DAYLIGHT SAVINGS3

40172COMMUNICATION SETTINGS2

40001COMMANDS1

Starting AddressSECTIONS

43463ANALOG ALARM SETTINGS31

43286ATS EXERCISER30

43276VOLTAGE IMBALANCE29

43253ATS SOURCE 2 CONFIGURATION28

43234ATS SOURCE 1 CONFIGURATION27

43208ATS R5026

43179ATS CONTROL TIMERS25

43168ATS CONTROL24

43119ATS23

41697FLEXLOGIC EQUATION22

41515CONTACT OUTPUTS21

41476LEDs20

41471SELF TEST19

41375CONTACT INPUT ASSIGNMENT18

41117FLEXLOGIC TIMERS17

41106SECURITY16

Starting AddressSECTIONS

MX350

14. Setup Software

GEZC ATS Controller Slide 21 of 30

Link to MX350 Setup Software – http://www.gedigitalenergy.com/app/Resources.aspx?prod=zte&type=7

MX350

14. Setup Software – Cont.

Slide 22 of 30GEZC Service School

• Program and modify settings• Load and save setting files to and from a disk• Read actual values• Monitor status• Read pre-trip data and event records• Get help on any topic• Upgrade the MX350 firmware• Uses Virtual Comport

MX350

Software features:

14. Setup Software – Cont.

Slide 23 of 30GEZC Service SchoolMX350

1) Click > Device Setup > Add Site > Add Device2) Enter Order Code as “MX350”3) Select Version as “1.0x”

14. Setup Software – Cont.

Slide 24 of 30GEZC Service SchoolMX350

1) Click > Quick Connect2) In USB device, select “MX350 USB Serial Emulation”

1) If communication is established, “Quick Connect Device” shall appear.2) Expand the “Quick Connect Device” by left click on the ‘+’.

14. Setup Software – Cont.

Slide 25 of 30GEZC Service SchoolMX350

14. Setup Software – Device Definition

Slide 26 of 30GEZC Service SchoolMX350

14. Setup Software – Setpoints

Slide 27 of 30GEZC Service SchoolMX350

Note: Enter “41532” as password to change setting(s).

Under “Setpoints”, one will find:• Configure• Operation• Control• Security Settings• Modbus User Map• Flex Logic

15. Brochures

GEZC ATS Controller Slide 28 of 30

Link to MX350 Brochure – http://www.gedigitalenergy.com/app/Resources.aspx?prod=zte&type=1

MX350

16. Manuals

GEZC ATS Controller Slide 29 of 30

Link to MX350 Manuals – http://www.gedigitalenergy.com/app/Resources.aspx?prod=zte&type=3

MX350

17. FAQ

Slide 30 of 30

• Return whole unit if one of the modules is defective• Disengage front end AC plug (of 23W-3026) before removing connections at B-cards• Make sure System Voltage Jumper (JP1 ~ JP6) is set correctly on UTA before powered up• 5-pin shorting jumper not required for configuration• Use order code to determine MX350 configuration (See Section 3)• EnerVista Software license valid for one year. $350 to renew.

GEZC Service SchoolMX350

Harness part #: 23W-3026

Model #: MX350-GEHE4BBAKLLLX