Upload
truongnhan
View
214
Download
0
Embed Size (px)
Citation preview
Contents
1. Introduction
2. Order Options
3. Order Code
4. Ordering Information
5. Terminals
6. UTA
7. Customer Connection Block
8. System Connections
9. Display Hierarchy
10. Flex Logic
GEZC Service School Slide 2 of 30
11. SCADA
12. Communications – General
13. Communications – Memory Map
14. Setup Software
15. Brochures
16. Manuals
17. Frequently Asked Questions (FAQ)
MX350
1. Introduction
GEZC ATS Controller
• Health Care / Data Center / Waste-to-Energy / Mfg
• Have I/Os option
• Metering functions – Harmonic Analysis, power, current
• Modbus / Modbus TCP
• Std/Delay/Closed Transition ATS
• Flex Logic
• UTA – One part number
Slide 3 of 30MX350
2. Order Options
Option A: Based package, 256 eventsOption B: Option A + 20 channel data logger, 10 programmable digital + 10 Analog
alarms, 10 channel of waveform capture, Auto Loadshed
Option C: Option B + 4 Additional Inputs & Outputs (Total 8-In, 8-Out)
Option D: Option C + 4 Additional Inputs & Outputs (Total 12-In, 12-Out), Flex
Logic
Option M: Manual Operation
GEZC ATS Controller Slide 4 of 30
As shown in Page 8 of document: 1601-9071-A1
MX350
3. Order Code
GEZC ATS Controller Slide 5 of 30
As shown in Page 17 of document: 1601-9071-A1
MX350
Sample Model #: MX350-GEHE4BBAKLLLX
4. Ordering Information
GEZC ATS Controller Slide 6 of 30
As shown in Page 22 of document: DEA-405
Power panel related =>
MX350
4. Ordering Information – Cont.
GEZC ATS Controller Slide 7 of 30
As shown in Page 23 of document: DEA-405
MX350
5. Terminals
GEZC ATS Controller Slide 8 of 30
Picture as shown in Page 25 of document: 1601-9071-A1
MX350
6. UTA – 200VA
GEZC ATS Controller Slide 9 of 30
Picture as shown in Page 8 of document: DEA-405
MX350
6. UTA – Interface
GEZC ATS Controller Slide 10 of 30
Picture as shown in Page 12 of document: 91R-1000
MX350
6. UTA – Test Point
GEZC ATS Controller Slide 11 of 30
Picture as shown in Page 12 of document: 91R-1000
MX350
7. Customer Connection Block
GEZC ATS Controller Slide 13 of 30
Picture as shown in Page 8 of document: DEA-405
MX350
8. System Connections
GEZC ATS Controller Slide 14 of 30
Picture as shown in Page 10 of document: 1601-9071-A1
MX350
9. Display Hierarchy
GEZC ATS Controller Slide 15 of 30
Picture as shown in Page 38 of document: 1601-9071-A1
MX350
10. Flex Logic
GEZC ATS Controller Slide 16 of 30
Picture as shown in Page 10 of document: DEA-405
• Control Logic• Create customized Protection & control• Minimized aux components• Have registers for Flex Logic
MX350
11. SCADA
GEZC ATS Controller Slide 17 of 30
• EnerVista Viewpoint software• Modbus or Modbus TCP• RS485 or Ethernet• Plug & Play• System Single Line Monitoring + Control• Trending Reports• Auto Event and Waveform Retrieval
One-line diagram
Plug & Play Screen
MX350
12. Communications - General
GEZC ATS Controller Slide 18 of 30
• RS485• Modbus or Modbus TCP• Address: 1 to 254, default 254• Baud rate: 9600, 19200, 38400, 57600, and 115200 bps (default 115200)• Parity: None• Data bits: 8• Stop bits: 1• Supported Modbus function codes: 1, 3, 4, 5, 6, 8, 16• User Definable Memory Map – Increase Throughput (see P17 of document 1601-9072-A1)
• Use PC software to map the addresses• Use Function code 06H to do Single Write Register• Use Function code 03H to perform One single read of registers.
• Memory map address 0x0000H begins at 30001• Memory map ranges (30001 ~ 32272) & (40001 ~ 43479)• Format Codes (see P48~64 of document 1601-9072-A1)
• Half-Duplex only• Slave device• Can be connected in Daisy Chain• Use Termination Resistor (i.e. 120 ohm)• Polarity Specific• Ground at one end but not both (to avoid ground loop effect)• Use shielded cable
MX350
13. Communications – Memory Map
GEZC ATS Controller Slide 19 of 30
30860DATA LOG INFORMATION18
30720TRACE MEMORY SAMPLES17
30710TRACE MEMORY16
30659EVENT RECORDER15
30657SELF TEST14
30524USER MAP VALUES13
30509GCP FACTORY TEST12
30505LED STATUS FOR GRAPHICAL AND BASIC CONTROL PANEL11
30384POWER METERING10
30340VOLTAGE METERING9
30326CURRENT METERING8
30323NET CONTROL STATUS7
30318STATUS - ATS6
30302SECURITY5
30283CONTACT/VIRTUAL INPUTS/OUTPUTS STATUS4
30223REAL-TIME CLOCK3
30186LAST FAULT DATA2
30001PRODUCT INFORMATION1
Starting AddressSECTIONS
32256LOAD CONTROL TIMERS37
32237ATS TIMERS36
32221ATS S2 STATUS35
32205ATS S1 STATUS34
32182ATS S2 COUNTERS33
32159ATS S1 COUNTERS32
32148ATS R5031
32121ATS GEN30
32119ATS PREFERRED SRC29
32117ATS TEST28
32105ATS EXERCISER27
32093ATS CONTROL26
32080ATS OPERATION COUNTERS25
32064REPORT24
32037ATS TRANSFER COUNTERS23
31396TOTAL HARMONIC DISTORTION22
31378COMMUNICATION21
30987FLEXLOGIC20
30952STATUS BUFFER19
Starting AddressSECTIONSActual Values
MX350
13. Communications – Memory Map (cont.)
GEZC ATS Controller Slide 20 of 30
Set Points
41040CALIBRATION15
40857CURRENT UNBALANCE (REQUIRED=IO_A)14
40679DATA LOGGER13
40672MEMORY12
40659EVENT RECORDER11
40524COMMUNICATION SETUP10
40517COMMUNICATION SETUP9
40317PROCESS INTERLOCK8
40284CONTROLLER SETUP7
40276VOLTAGE SENSING6
40266CURRENT SENSING5
40262VIRTUAL INPUT4
40228REAL-TIME CLOCK/DAYLIGHT SAVINGS3
40172COMMUNICATION SETTINGS2
40001COMMANDS1
Starting AddressSECTIONS
43463ANALOG ALARM SETTINGS31
43286ATS EXERCISER30
43276VOLTAGE IMBALANCE29
43253ATS SOURCE 2 CONFIGURATION28
43234ATS SOURCE 1 CONFIGURATION27
43208ATS R5026
43179ATS CONTROL TIMERS25
43168ATS CONTROL24
43119ATS23
41697FLEXLOGIC EQUATION22
41515CONTACT OUTPUTS21
41476LEDs20
41471SELF TEST19
41375CONTACT INPUT ASSIGNMENT18
41117FLEXLOGIC TIMERS17
41106SECURITY16
Starting AddressSECTIONS
MX350
14. Setup Software
GEZC ATS Controller Slide 21 of 30
Link to MX350 Setup Software – http://www.gedigitalenergy.com/app/Resources.aspx?prod=zte&type=7
MX350
14. Setup Software – Cont.
Slide 22 of 30GEZC Service School
• Program and modify settings• Load and save setting files to and from a disk• Read actual values• Monitor status• Read pre-trip data and event records• Get help on any topic• Upgrade the MX350 firmware• Uses Virtual Comport
MX350
Software features:
14. Setup Software – Cont.
Slide 23 of 30GEZC Service SchoolMX350
1) Click > Device Setup > Add Site > Add Device2) Enter Order Code as “MX350”3) Select Version as “1.0x”
14. Setup Software – Cont.
Slide 24 of 30GEZC Service SchoolMX350
1) Click > Quick Connect2) In USB device, select “MX350 USB Serial Emulation”
1) If communication is established, “Quick Connect Device” shall appear.2) Expand the “Quick Connect Device” by left click on the ‘+’.
14. Setup Software – Setpoints
Slide 27 of 30GEZC Service SchoolMX350
Note: Enter “41532” as password to change setting(s).
Under “Setpoints”, one will find:• Configure• Operation• Control• Security Settings• Modbus User Map• Flex Logic
15. Brochures
GEZC ATS Controller Slide 28 of 30
Link to MX350 Brochure – http://www.gedigitalenergy.com/app/Resources.aspx?prod=zte&type=1
MX350
16. Manuals
GEZC ATS Controller Slide 29 of 30
Link to MX350 Manuals – http://www.gedigitalenergy.com/app/Resources.aspx?prod=zte&type=3
MX350
17. FAQ
Slide 30 of 30
• Return whole unit if one of the modules is defective• Disengage front end AC plug (of 23W-3026) before removing connections at B-cards• Make sure System Voltage Jumper (JP1 ~ JP6) is set correctly on UTA before powered up• 5-pin shorting jumper not required for configuration• Use order code to determine MX350 configuration (See Section 3)• EnerVista Software license valid for one year. $350 to renew.
GEZC Service SchoolMX350
Harness part #: 23W-3026
Model #: MX350-GEHE4BBAKLLLX