62
12/20/2014 1 Prof. Dr. Qaisar Ali Reinforced Concrete Design – II Department of Civil Engineering, University of Engineering and Technology Peshawar Lecture - 06 Introduction to Earthquake Resistant Design of Reinforced Concrete Structures By: Prof Dr. Qaisar Ali Civil Engineering Department UET Peshawar www.drqaisarali.com 1 Prof. Dr. Qaisar Ali Reinforced Concrete Design – II Department of Civil Engineering, University of Engineering and Technology Peshawar Topics Introduction to Earthquakes and Its Effects on Buildings Earthquake Design Philosophy Seismic Loading Criteria Example 1 (Static Lateral Load Procedure) Gravity vs. Earthquake Loading in RC Buildings ACI Special Provisions for Seismic Design ACI Provisions for Special Moment Resisting Frames (SMRF) 2

L-06-EQ-Resistant-Design-of RCC Structures

Embed Size (px)

DESCRIPTION

THE BEST

Citation preview

  • 12/20/2014

    1

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Lecture - 06

    Introduction to Earthquake Resistant Design of Reinforced

    Concrete Structures

    By: Prof Dr. Qaisar Ali

    Civil Engineering Department

    UET Peshawar

    www.drqaisarali.com

    1

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Topics

    Introduction to Earthquakes and Its Effects on Buildings

    Earthquake Design Philosophy

    Seismic Loading Criteria

    Example 1 (Static Lateral Load Procedure)

    Gravity vs. Earthquake Loading in RC Buildings

    ACI Special Provisions for Seismic Design

    ACI Provisions for Special Moment Resisting Frames (SMRF)

    2

  • 12/20/2014

    2

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Topics

    ACI Provisions for Intermediate Moment Resisting Frames

    (IMRF)

    Miscellaneous Considerations

    Design Example 2 (SMRF)

    Design Example 3 (SMRF)

    3

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Introduction to Earthquakes and Its Effects on Buildings

    Earths Interior

    4

  • 12/20/2014

    3

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Earthquake results from the sudden movement of

    the tectonic plates in the earths crust.

    5

    Introduction to Earthquakes and Its Effects on Buildings

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Effect of Earthquake

    The movement, taking place at the fault lines, causes

    energy release which is transmitted through the earth in

    the form of waves. These waves reach the structure

    causing shaking.

    6

    Introduction to Earthquakes and Its Effects on Buildings

  • 12/20/2014

    4

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Seismic Events around the globe

    Mostly takes place at boundaries of Tectonic plates

    7

    Dots represents an earthquake

    Introduction to Earthquakes and Its Effects on Buildings

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Types of Waves Generated Due to Earthquake

    8

    Body Waves Surface Waves

    Introduction to Earthquakes and Its Effects on Buildings

  • 12/20/2014

    5

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Displacement due to Earthquake

    9

    Introduction to Earthquakes and Its Effects on Buildings

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    10

    Introduction to Earthquakes and Its Effects on Buildings

    Horizontal and Vertical Shaking

    Earthquake causes shaking of the ground in all three directions.

    The structures designed for gravity loading (DL+LL) will be

    normally safe against vertical component of ground shaking.

    The vertical acceleration during ground shaking either adds to or

    subtracts from the acceleration due to gravity.

  • 12/20/2014

    6

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    11

    Introduction to Earthquakes and Its Effects on Buildings

    Horizontal and Vertical Shaking

    The structures are normally designed for horizontal shaking to

    minimize the effect of damages due to earthquakes.

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Earthquake Types with respect to Depth of Focus

    Shallow

    Depth of focus varies between 0 and 70 km.

    Deep

    Depth of focus varies between 70 and 700 km.

    12

    Introduction to Earthquakes and Its Effects on Buildings

  • 12/20/2014

    7

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Earthquake characteristics with respect to distance

    from epicenter

    0.05 T 0.320 Hz f 3.33 Hz

    Low period & high frequency field

    0.3 T 1.0 sec3.33 Hz f 1 Hz

    1.0 T 10 sec

    25 km

    Large period & low frequency field

    Moderate period & low frequency field

    Epicenter

    1 Hz f 0.1 Hz

    Near Field: 0 to 25 km

    Intermediate Field: 25 to 50 km

    Far Field: Beyond 50 km

    13

    Introduction to Earthquakes and Its Effects on Buildings

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Resonance risk for structures w.r.t near, intermediate

    and far field earthquakes

    The natural time period of a structure is its important characteristic

    to predict behavior during an earthquake of certain time period

    (Resonance phenomenon).

    For a particular structure, the natural time period is a function of

    mass and stiffness {T = 2p(m/k)}

    T can be roughly estimated from: T = 0.1 number of stories

    14

    Introduction to Earthquakes and Its Effects on Buildings

  • 12/20/2014

    8

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Resonance risk for structures w.r.t near, intermediate

    and far field earthquakes

    Low rise Structure

    (upto 3 stories)

    Epicenter

    Medium rise Structure

    (upto 5 stories)

    High rise Structure

    (Above 5 stories)

    15

    Introduction to Earthquakes and Its Effects on Buildings

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Earthquake Recording

    Seismograph

    Using multiple seismographs

    around the world, accurate

    location of the epicenter of the

    earthquake, as well as its

    magnitude or size can be

    determined.

    Working of seismograph shown

    in figure.

    16

    Introduction to Earthquakes and Its Effects on Buildings

  • 12/20/2014

    9

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Earthquake Recording

    Richter Scale

    In 1935, Charles Richter (US)

    developed this scale.

    The Richter scale is logarithmic,

    So, a magnitude 5 Richter

    measurement is ten times

    greater than a magnitude 4;

    while it is 10 x 10, or 100 times

    greater than a magnitude 3

    measurement.

    17

    Introduction to Earthquakes and Its Effects on Buildings

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Earthquake Recording

    Some of the famous

    earthquake records

    18

    Introduction to Earthquakes and Its Effects on Buildings

  • 12/20/2014

    10

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Earthquake Occurrence

    19

    Introduction to Earthquakes and Its Effects on Buildings

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Seismic Zones

    20

    Introduction to Earthquakes and Its Effects on Buildings

  • 12/20/2014

    11

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Importance of Architectural Features

    The behavior of a building during

    earthquakes depend critically on its overall

    shape, size and geometry, in addition to

    how the earthquake forces are carried to the

    ground.

    21

    Introduction to Earthquakes and Its Effects on Buildings

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    22

    Introduction to Earthquakes and Its Effects on Buildings

    Importance of Architectural Features

    At the planning stage, architects and structural engineers

    must work together to ensure that the unfavorable features

    are avoided and a good building configuration is chosen.

  • 12/20/2014

    12

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    23

    Introduction to Earthquakes and Its Effects on Buildings

    Other Undesirable Scenarios

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Soft Storey

    24

    Introduction to Earthquakes and Its Effects on Buildings

  • 12/20/2014

    13

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Earthquake Design Philosophy

    Performance level

    25

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Building Code of Pakistan

    In Pakistan, the design criteria for earthquake loading are based

    on design procedures presented in chapter 5, division II of

    Building Code of Pakistan, seismic provision 2007 (BCP, SP

    2007), which have been adopted from chapter 16, division II of

    UBC-97 (Uniform Building Code), volume 2.

    Seismic Loading Criteria

    26

  • 12/20/2014

    14

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Lateral Force Determination Procedures

    The total design seismic force imposed by an earthquake on

    the structure at its base is referred to as base shear V in the

    UBC-97.

    The design seismic force can be determined based on:

    Dynamic lateral force procedure [sec. 1631, UBC-97 or sec. 5.31, BCP-2007].

    Static lateral force procedure [sec. 1630.2, UBC-97 or Sec. 5.30.2, BCP 2007],

    Seismic Loading Criteria

    27

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Dynamic Lateral Force Procedure

    UBC-97 section 1631 include information on dynamic lateral force

    procedures that involve the use of:

    Time history analysis.

    Response spectrum analysis.

    The details of these methods are presented in sections 1631.5

    and 1631.6 of the UBC-97.

    Seismic Loading Criteria

    28

  • 12/20/2014

    15

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Dynamic Lateral Force Procedure

    Time History Analysis (THA)

    T

    Ground acceleration

    T

    LateralDisplacement

    Seismic Loading Criteria

    29

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Dynamic Lateral Force Procedure

    Response Spectrum Analysis (RSA)

    T

    a (ft/sec2)

    T

    Response

    a (ft/sec2)

    T

    a (ft/sec2)

    T

    Response

    Response

    Ts1 = 0.3 sec

    Ts2 = 1.0 sec

    Ts3 = 2.0 sec

    D1

    D2

    D3

    (Ts1,D1)

    (Ts2,D2)

    (Ts3,D3)

    Structural Time period

    Peak Response

    T

    T

    Seismic Loading Criteria

    30

  • 12/20/2014

    16

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    UBC-97 Response Spectrum Curve(Acceleration vs. Time period)

    Dynamic Lateral Force Procedure

    Response Spectrum Analysis (RSA)

    Seismic Loading Criteria

    31

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    =

    Static Lateral Force Procedure

    Seismic Loading Criteria

    32

  • 12/20/2014

    17

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Static Lateral Force Procedure

    The total design base shear (V) in a given direction can be

    determined from the following formula:

    V = (CI/RT) W

    Where,

    C = Seismic coefficient (Table 16-R of UBC-97).

    I = Seismic importance factor (Table 16-K of UBC-97 )

    R = numerical coefficient representative of inherent over strength and

    global ductility capacity of lateral force-resisting systems (Table 16-N

    or 16-P).

    W = the total seismic dead load defined in Section 1630.1.1.

    Seismic Loading Criteria

    33

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Static Lateral Force Procedure

    The total design base need not exceed [ V = (2.5CaI/R) W ]

    Where, Ca = Seismic coefficient (Table 16-Q of UBC-97)

    The total design base shear shall not be less than [ V = 0.11CaIW ]

    In addition for seismic zone 4, the total base shear shall also not

    be less [ V = (0.8ZNI/R) W ]

    Where, N = near source factor (Table 16-T of UBC-97);

    Z = Seismic zone factor (Table 16-I of UBC-97)

    Seismic Loading Criteria

    34

  • 12/20/2014

    18

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Static Lateral Force Procedure

    Steps for Calculation of V:

    Step 1: Find Site Specific details.

    Step 2: Determine Seismic Coefficients

    Step 3: Determine Seismic Importance factor I

    Step 4: Determine R factor

    Step 5: Determine structures time period

    Step 6:Determine base shear V and apply code maximum and

    minimum.

    Step 7: Determine vertical distribution of V.

    Seismic Loading Criteria

    35

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Static Lateral Force Procedure

    Steps for Calculation of V:

    Step 1: Find Site Specific details.

    Following list of data needs to be obtained:

    Seismic Zone

    Soil type

    Past earthquake magnitude (required only for highest seismic zone).

    Closest distance to known seismic source (required only for highest seismic

    zone).

    Seismic Loading Criteria

    36

  • 12/20/2014

    19

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Static Lateral Force Procedure

    Steps for Calculation of V:

    Step 1: Site Specific details.

    i. Seismic ZoneSource: BCP SP-2007

    Seismic Loading Criteria

    37

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Static Lateral Force Procedure

    Steps for Calculation of V:

    Step 1: Find Site Specific details.

    ii. Soil Type

    As per UBC code, if soil type is not known, type SD shall be taken.

    Seismic Loading Criteria

    38

  • 12/20/2014

    20

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Static Lateral Force Procedure

    Steps for Calculation of V:

    Step 1: Find Site Specific details.

    iii. Past Earthquake magnitude: This is required only for seismic zone 4

    to decide about seismic source type so that certain additional coefficients

    can be determined.

    iv. Distance to known seismic zone is also required to determine

    additional coefficients for zone 4.

    Seismic Loading Criteria

    39

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Static Lateral Force Procedure

    Steps for Calculation of V:

    Step 2: Determination of Seismic Coefficients.

    Cv:

    Nv (required only for zone 4):

    Seismic Loading Criteria

    40

  • 12/20/2014

    21

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Static Lateral Force Procedure

    Steps for Calculation of V:

    Step 2: Determination of Seismic Coefficients.

    Ca:

    Na (required only for zone 4):

    Seismic Loading Criteria

    41

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Static Lateral Force Procedure

    Steps for Calculation of V:

    Step 3: Determination of Seismic Importance Factor.

    Seismic Loading Criteria

    42

  • 12/20/2014

    22

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Static Lateral Force Procedure

    Steps for Calculation of V:

    Step 4: Determination of R Factor.

    R factor basically reduces base shear V to make the system

    economical. However the structure will suffer some damage as explained

    in the earthquake design philosophy.

    R factor depends on overall structural response of the structure under

    lateral loading.

    For structures exhibiting good performance, R factor will be high.

    Seismic Loading Criteria

    43

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Static Lateral Force Procedure

    Steps for Calculation of V:

    Step 4: Determination of R Factor.

    Seismic Loading Criteria

    44

  • 12/20/2014

    23

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Static Lateral Force Procedure

    Steps for Calculation of V:

    Step 5: Determination of structures time period.

    Structural Period (By Method A, UBC 97): For all buildings, the value T

    may be approximated from the following formula:

    T = Ct (hn)3/4

    Where,

    Ct = 0.035 (0.0853) for steel moment-resisting frames.

    Ct = 0.030 (0.0731) for reinforced concrete moment-resisting frames and eccentrically

    braced frames.

    Ct = 0.020 (0.0488) for all other buildings.

    hn = Actual height (feet or meters) of the building above the base to the nth level.

    Seismic Loading Criteria

    45

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Static Lateral Force Procedure

    Steps for Calculation of V:

    Step 6: Determination of Base Shear (V).

    Calculate base shear meeting the following criteria:

    0.11CaIW V = (CI/RT) W (2.5CaI/R) W

    For zone 4, the total base shear shall also not be less than:

    V = (0.8ZNI/R) W

    Seismic Loading Criteria

    46

  • 12/20/2014

    24

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Static Lateral Force Procedure

    Steps for Calculation of V:

    Step 7: Vertical Distribution of V to storeys.

    The joint force at a particular level x of the structure is given as:

    Fx = (V Ft)xhx/ihi (UBC sec. 1630.5)

    { i ranges from 1 to n, where n = number of stories }

    Ft = Additional force that is applied to the top level (i.e., the roof) in

    addition to the Fx force at that level.

    Ft = 0.07TV {for T > 0.7 sec}

    Ft = 0 {for T 0.7 sec}

    Seismic Loading Criteria

    47

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Example: Calculate the base shear and storey forces of a five storey

    building given in the figure. The structure is constructed on stiff soil

    which comes under soil type SD of table 16-J of UBC-97. The

    structure is located in zone 3.

    Example 1(Static Lateral Force Procedure)

    60-0

    12-0

    800 kip

    800 kip

    800 kip

    800 kip

    700 kip

    48

  • 12/20/2014

    25

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution: Selection of Ca and Cv.

    Base Shear (V) = {CvI/RT}W

    49

    Example 1(Static Lateral Force Procedure)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution: Selection of I.

    Base Shear (V) = {CvI/RT}W

    Therefore, I = 1.00

    50

    Example 1(Static Lateral Force Procedure)

  • 12/20/2014

    26

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution: Selection of R.

    Base Shear (V) = {CvI/RT}W

    Therefore, R = 8.5 (for SMRF)

    51

    Example 1(Static Lateral Force Procedure)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution: Calculation of T and W

    Base Shear (V) = {CvI/RT}W

    T = Ct (hn)3/4

    = 0.030 (60)3/4

    = 0.646 sec.

    W = w1 + w2 + w3 + w4 + w5

    = 4 800 + 700

    = 3900 kip

    hn = 60-0

    12-0

    w1 = 800 kip

    w2= 800 kip

    w3 = 800 kip

    w4 = 800 kip

    w5 = 700 kip

    52

    Example 1(Static Lateral Force Procedure)

  • 12/20/2014

    27

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution: Therefore,

    V = {CvI/RT}W

    = {0.54 1.00/ (8.5 0.646)} 3900 = 383 kips

    The total design base need not exceed the following:

    V = (2.5CaI/R) W

    = {(2.5 0.36 1.00)/ (8.5)} 3900 = 413 kips

    The total design base shear shall not be less than the following:

    V = 0.11CaIW

    = 0.11 0.36 1.00 3900 = 154.44 kips

    Therefore, V = 383 kip

    53

    Example 1(Static Lateral Force Procedure)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution: Vertical distribution of base shear to stories

    The joint force at a level x of the structure is given as:

    Fx = (V Ft)xhx/ihi

    { i ranges from 1 to n, where n = number of stories }

    Ft = Additional force that is applied to the top level (i.e., the roof) in addition to the

    Fx force at that level.

    Ft = 0.07TV {for T > 0.7 sec}

    Ft = 0 {for T 0.7 sec}

    54

    Example 1(Static Lateral Force Procedure)

  • 12/20/2014

    28

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution: Vertical distribution of base shear to stories

    Fx = (V Ft)xhx/ihi

    ihi = 80012 + 80024 + 80036 + 80048 + 70060 = 138000 kip

    Therefore for the case under consideration, Force for storey 1 is:

    F1 = (383 0) 800 12/ {(138000)} = 27 kip

    Storey forces for other stories are given in table below.

    Table Storey shears.Level

    xhx (ft)

    wx(kip)

    wxhx (ft-kip)wxhx

    /(wihi)Fx (kip)

    5 60 700 42000 0.304 1174 48 800 38400 0.278 1073 36 800 28800 0.209 802 24 800 19200 0.139 531 12 800 9600 0.070 27

    wihi = 138000Check SFx =V = 383 kip OK

    55

    Example 1(Static Lateral Force Procedure)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution: Vertical distribution of base shear to stories

    Table: Storey shearsLevel

    xhx (ft)

    wx(kip)

    wxhx (ft-kip)wxhx

    /(wihi)Fx (kip)

    5 60 700 42000 0.304 1174 48 800 38400 0.278 1073 36 800 28800 0.209 802 24 800 19200 0.139 531 12 800 9600 0.070 27

    wihi = 138000Check Fx =V = 383 kip OK

    800 kip

    800 kip

    800 kip

    800 kip

    700 kip

    383 kips

    117 kips

    107 kips

    80 kips

    53 kips

    27 kips

    56

    Example 1(Static Lateral Force Procedure)

  • 12/20/2014

    29

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Reversal of stresses takes place

    during earthquake shaking, fig.

    Earthquake shaking reverses

    tension and compression in

    members

    Reinforcement is required on

    both faces of members.

    Gravity vs. Earthquake Loading in Reinforced Concrete Building

    57

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    The principal goal of the Special Provisions is to ensure adequate

    toughness under inelastic displacement reversals brought on by

    earthquake loading.

    The provisions accomplish this goal by requiring the designer to

    provide for concrete confinement and inelastic rotation capacity.

    No special requirements are placed on structures subjected to low or

    no seismic risk.

    Structural systems designed for high and moderate seismic risk are

    referred to as Special and Intermediate respectively.

    ACI Special Provisions for Seismic Design

    58

  • 12/20/2014

    30

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Based on moment resisting capacity, there are three types of RC

    frames,

    SMRF (Special Moment Resisting Frame),

    IMRF (Intermediate Moment Resisting Frame),

    OMRF (Ordinary Moment Resisting Frame).

    Some general requirements will be presented first, which are

    common to all frames. Specific requirements for each type of frame

    are presented later on.

    ACI Special Provisions for Seismic Design

    59

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    General Requirements

    Concrete in members resisting earthquake induced forces

    Min fc = 3000 Psi (cylinder strength) for all types

    No maximum limit on ordinary concrete

    5000 psi is maximum limit for light weight

    ACI Special Provisions for Seismic Design

    60

  • 12/20/2014

    31

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    General Requirements

    Reinforcement in members resisting earthquake induced forces

    Grade 60, conforming to ASTM A 706 (low alloy steel)

    Grade 40 or 60, conforming to ASTM A 615 (billet steel) provided that

    Fy (actual) Fy (specified) +18 Ksi

    Actual Ultimate / Actual Fy 1.25

    ACI Special Provisions for Seismic Design

    61

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    General Requirements

    Hoops, Ties and Cross Ties

    Confinement for concrete is provided by transverse reinforcement

    consisting of stirrups. hoops, and crossties.

    To ensure adequate anchorage, a seismic hook (shown in figure) is used

    on stirrups, hoops and crossties .

    62

    (Seismic Hook)

    ACI Special Provisions for Seismic Design

  • 12/20/2014

    32

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    General Requirements

    Hoops, ties and Crossties: Advantages

    Closely spaced horizontal closed ties in column help in three ways:

    i. they carry the horizontal shear forces induced by earthquakes, and thereby

    resist diagonal shear cracks,

    ii. they hold together the vertical bar and prevent them from excessively

    bending outwards (in technical terms, this bending phenomenon is called

    buckling), and

    iii. they contain the concrete in the column. The ends of the ties must be bent

    at 135 hooks. Such hook ends prevent opening of hoops and

    consequently buckling of concrete and buckling of vertical bars.

    ACI Special Provisions for Seismic Design

    63

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Provisions for Flexural Members

    These provision applies to flexural members with:

    Factored axial compressive force Agfc/10.

    Note: These provisions generally apply to beams because axial load

    on beams is generally 0 or less than Agfc/10.

    However they are also applicable to columns subjected to axial load less

    than Agfc/10.

    ACI Provisions for Special Moment Resisting Frames (SMRF)

    64

  • 12/20/2014

    33

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Provisions for Flexural Members

    1. Size: The members must have:

    a. clear span-to-effective-depth ratio of at least 4, (Ln/d 4)

    e.g., for Ln = 15 ft, d = 16, Ln/d = 15 12/16 = 11.25 > 4, O.K.

    b. a width-to-depth ratio of at least 0.3, b/h 0.3

    e.g., for width (b) = 12 and depth (h) = 18, b/h = 12/18 = 0.67 > 0.3, O.K.

    c. A web width of not less 10 inches.

    ACI Provisions for Special Moment Resisting Frames (SMRF)

    65

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Provisions for Flexural Members

    2. Flexural Reinforcement

    Asl

    Asl+ (Asl)/2

    As or As+ (at all section) (maximum of As at either joint)/4

    Asr

    Asr+ (Asr)/2

    rmin = 3fc/fy, 200/fy (at critical sections)

    rmax = 0.025 (at critical sections)

    Min. 2 bars continuous at all sections

    ACI Provisions for Special Moment Resisting Frames (SMRF)

    66

  • 12/20/2014

    34

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Provisions for Flexural Members

    3. Transverse Reinforcement

    s

    d/4

    8 smallest longitudinal bar diameter

    24 hoop bar diameter

    12 2

    2h 2hs d/2

    Column

    Column

    ACI Provisions for Special Moment Resisting Frames (SMRF)

    67

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Provisions for Flexural Members

    4. Lap Splice Lap splice length =1.3 ld = 1.3 0.05 (fy/ fc)db50 db for fc 3 and fy 40 ksi

    70 db for fc 3 and fy 60 ksi

    Spacing of stirrups Least of d/4 or 4 inches

    Lapping prohibited in regions where longitudinal bars can yield in tension

    Lapping of Longitudinal bars

    2h 2h

    ACI Provisions for Special Moment Resisting Frames (SMRF)

    68

  • 12/20/2014

    35

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    ACI Provisions for Special Moment Resisting Frames (SMRF)

    69

    Mechanical Splice of Longitudinal Reinforcement

    Mechanical Splices shall conform to 21.2.6.

    Section 21.2.6 says that welded splice shall conform to 12.14.3.2

    which states A full mechanical splice shall develop in tension or

    compression, as required, at least 125 % of the specified yield

    strength (fy) of the bar.

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    ACI Provisions for Special Moment Resisting Frames (SMRF)

    70

    Welded Splice of Longitudinal Reinforcement

    Welded Splices shall conform to 21.2.7.

    Section 7.3.6 says that welded splice shall conform to 12.14.3.4

    which states A full welded splice shall develop at least 125 % of

    the specified yield strength (fy) of the bar.

  • 12/20/2014

    36

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    ACI Provisions for Special Moment Resisting Frames (SMRF)

    71

    Provision for Frame Members Subjected to Bending

    and Axial Load

    The provision applies to members with:

    Factored axial compressive force > Agfc/10

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Provision for Frame Members Subjected to Bending

    and Axial Load

    1. Size

    a) Each side at least 12 inches

    b) Shorter to longer side ratio 0.4.

    i.e. 12/12, 12/18, 12/24 OK; but 12/36 not O.K

    ACI Provisions for Special Moment Resisting Frames (SMRF)

    72

  • 12/20/2014

    37

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Provision for Frame Members

    Subjected to Bending and Axial

    Load

    2. Longitudinal Reinforcement

    0.01 rg 0.06

    Clear span, hc

    ACI Provisions for Special Moment Resisting Frames (SMRF)

    73

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Provision for Frame

    Members Subjected

    to Bending and

    Axial Load

    3. Trans. Rein.

    h2

    h1

    s 0.25 (smaller of h1 or h2)

    6 long. bar dia.

    so

    s 6 long. bar dia.6

    lo

    lo Larger of h1 or h2

    Clear span/6

    18

    ACI Provisions for Special Moment Resisting Frames (SMRF)

    74

  • 12/20/2014

    38

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Provision for Frame Members Subjected to Bending and Axial Load

    3. Trans. Rein.

    4 so = 4 + [(14 hx)/3] 6

    hx = max. value of hx on all column faces

    hx 14

    hx hx hx

    hx

    hx

    6db 3 6db extension

    Alternate90-deg hooks

    Provide add.trans. reinf. if thickness > 4

    ACI Provisions for Special Moment Resisting Frames (SMRF)

    75

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Provision for Frame Members Subjected

    to Bending and Axial Load

    4. Lap Splice

    Tension lap splicewithin center half ofmember length

    Lap splice length =1.3 ld = 1.3 0.05 (fy/ fc)db

    50 db for fc 3 and fy 40 ksi

    70 db for fc 3 and fy 60 ksi

    Spacing of ties in lap splice not more than smaller of d/4 or 4

    ACI Provisions for Special Moment Resisting Frames (SMRF)

    76

  • 12/20/2014

    39

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Joints of Special Moment Frame

    Beam

    Column

    Beam Column Joint

    Column ties (with 135o) hook continued through joint(ACI 21.5.2)

    77

    ACI Provisions for Special Moment Resisting Frames (SMRF)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Joints of Special Moment Frame

    Successful seismic design of frames require that the structures be

    proportioned so that hinges occur at locations that least

    compromise strength. For this, weak-beam strong-column

    approach is used.

    After design, the member capacities are calculated based on

    designed section.

    At joint, Column flexural capacity 1.20 x Beam flexural capacity

    ACI Provisions for Special Moment Resisting Frames (SMRF)

    78

  • 12/20/2014

    40

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Joints of Special Moment Frame

    Minimum Flexural Strength of Column at Joint

    M+nc,t

    M-nc,b

    M+nb,r

    M-nb,l

    M+nc,b + M-nc,t 6(M

    +nb,l + M

    -nb,r)/5

    M-nc,t

    M+nc,b

    M+nb,l M-nb,r

    M-nc,b + M+

    nc,t 6(M-nb,l + M

    +nb,r)/5

    ACI Provisions for Special Moment Resisting Frames (SMRF)

    79

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Joints of Special Moment Frame

    To prevent beam column joint cracking, ACI Code 21.5.1

    requires that the column dimension parallel to the beam

    reinforcement must be at least 20 times the diameter of the

    largest longitudinal bar.

    Beam longitudinal reinforcement with diameter (db)

    20db

    Beam

    Column

    ACI Provisions for Special Moment Resisting Frames (SMRF)

    80

  • 12/20/2014

    41

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Joints of Special Moment Frame

    Beam longitudinal reinforcement that is terminated within a

    column. must be extended to the far face of the column core.

    The development length (ldh) of bars with 90 hooks must be not

    less than 8db, 6 inch, Or fydb/ (65 fc).

    Beam longitudinal reinforcement

    Beam

    Column

    ldh

    ACI Provisions for Special Moment Resisting Frames (SMRF)

    81

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Provision for Flexural Members

    1. Size: No special requirement (Just as ordinary beam

    requirement).

    2. Flexural steel: Less stringent requirement as discussed next.

    3. Transverse steel: Same as for SMRF.

    4. Lap: No special requirement (Just as ordinary beam

    requirement).

    ACI Provisions for Intermediate Moment Resisting Frames (IMRF)

    82

  • 12/20/2014

    42

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Provisions for Flexural Members

    2. Flexural Reinforcement

    Asl

    Asl+ (Asl)/3

    As or As+ (at all section) (maximum of As at either joint)/5

    Asr

    Asr+ (Asr)/3

    rmin = 3fc/fy, 200/fy (at critical sections)

    t 0.004

    ACI Provisions for Intermediate Moment Resisting Frames (IMRF)

    83

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Provision for Columns

    1. Size: No special requirement (Just as ordinary column

    requirement)

    2. Flexural steel: No special requirement (Just as ordinary column

    requirement)

    3. Transverse steel: Less Stringent requirement as given next.

    4. Lap: No special requirement (Just as ordinary column

    requirement)

    ACI Provisions for Intermediate Moment Resisting Frames (IMRF)

    84

  • 12/20/2014

    43

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Provision for Columns

    h2

    h1

    so/2

    Trans. reinf. based on Mn and factored tributary gravity load

    so

    8 smallest long. bar dia.

    24 tie bar dia.

    0.5 min. (h1 or h2)

    12

    lo

    lo

    Larger of h1 or h2

    Clear span/6

    18

    s d/2 (As per ACI 11.5.4)

    ACI Provisions for Intermediate Moment Resisting Frames (IMRF)

    85

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    IMRF are not allowed in regions of high seismic risk, however,

    SMRF are allowed in regions of moderate seismic risk.

    Unlike regions of high seismic risk, two way slab system without

    beams are allowed in regions of moderate seismic risk.

    In regions of low or no seismic risk ordinary moment resisting

    frames OMRF are allowed but IMRF and SMRF may also be

    provided.

    Miscellaneous Considerations

    86

  • 12/20/2014

    44

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Example 2: Detail the selected frame of E-W interior frame of the

    given structure as per SMRF requirements. The structure is

    already designed for the following seismic zone data.

    Seismic zone: 4

    Magnitude of earthquake 7.0

    Slip rate 5.0

    Closest distance to known seismic source > 15 km.

    Soil type: SD (stiff).

    Concrete compressive strength = 3 ksi,

    Steel yield strength = 40 ksi

    Modulus of elasticity of concrete = 3000 ksi.

    Design Example 2 (SMRF)

    87

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Given 3D structure:

    20 ft 20 ft 20 ft 20 ft

    15 ft

    15 ft

    15 ft

    10.5 ft

    10.5 ft

    10.5 ft (floor to floor)

    SDL = 40 psfLL = 60 psf

    SDL = 40 psfLL = 60 psf

    SDL = 40 psfLL = 60 psf

    fc = 3 ksify = 40 ksi

    Slab-Beam Frame Structure

    Beams: 15 18 (d =15 inch)Columns: 15 square

    Design Example 2 (SMRF)

    88

  • 12/20/2014

    45

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Selected portion of E-W interior Frame:

    20 ft 20 ft 20 ft 20 ft

    Portion of frame considered

    Design Example 2 (SMRF)

    89

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Reinforcement from Design:

    For the beam in the given frame, we have

    Asmin = 0.005 x15 x 15 = 1.125 in2

    Asmax = 0.025x15 x 15 = 5.625 in2

    Negative reinforcement at the ends and positive

    reinforcement at the mid span must be greater

    than Asmin and reinforcement at all locations must

    be less than the Asmax

    This is OK for the values on the given beam.

    For the column, we have

    Asmin = 0.01 x15 x 15 = 2.25 in2

    This is also OK.20 ft 20 ft 20 ft 20 ft

    1.61 1.61

    1.02 1.021.21

    2.25 2.25

    Reinforcement in in2

    Design Example 2 (SMRF)

    90

  • 12/20/2014

    46

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Calculation of number of bars:

    20 ft 20 ft 20 ft 20 ft

    No. of bars = As/Ab

    Use No. 5 bar,

    Negative reinforcement at joint:

    Left joint:

    1.61/0.31= 5.19 (take 6 bars in 2 layers)

    Right joint:

    1.61/0.31= 5.19 (take 6 bars in 2 layers)

    Positive bars (mid span):

    1.21/0.31 = 3.9 (take 4 bars in 1 layer)

    Positive bars (at joint):

    1.01/0.31 = 3.29 (take 4 bars in 1 layer)

    Column reinforcement:

    2.25/ 0.31 = 7.25 (take 8 bars for even distribution

    of bars at all faces of column)

    6 bars 6 bars

    4 bars 4 bars4 bars

    8 bars 8 bars

    No. of #5 bars

    Design Example 2 (SMRF)

    91

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    SMRF Requirements Checklist

    Provisions for Beams

    Sizes

    ln/d = 20 12/15 = 16 > 4 (ACI 21.3.1.2 satisfied)

    Width/ depth = 15/18= 0.833 > 0.3 (ACI 21.3.1.3 satisfied)

    Width = 15 > 10, O.K.

    Therefore 12 wide and 18 beams are OK

    Design Example 2 (SMRF)

    92

  • 12/20/2014

    47

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    SMRF Requirements Checklist

    Provisions for Beams

    Flexural Reinforcement

    As+ (at joints) As (at joints)

    4 #5 bars (6 #5 bars)

    As (any section) Max. As at joints

    2 #5 bars (6 #5 bars)OK OK

    Asl = 6 #5 Asr = 6 #5

    Asmid+ = 4 #5Asl+ = 4 #5 Asr+ = 4 #5

    Design Example 2 (SMRF)

    93

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    SMRF Requirements Checklist

    Provisions for Beams

    Transverse Reinforcement

    s

    d/4 = /4 = 3.75

    8 smallest long. bar dia.= 8 5/8= 5

    24 hoop bar diameter = 24 3/8= 9

    12 2

    2h = 36s d/2 = 15/2 = 7.5

    Column

    2h = 36

    94

    Design Example 2 (SMRF)

  • 12/20/2014

    48

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    SMRF Requirements Checklist

    Provisions for Beams

    Lap Splice: If required then,

    Not to be provided within joints. Not to be provided within 2h region from face of

    the support.

    Spacing of hoops within lap = least of d/4 or 4 c/c = 3.75 c/c

    Lap splice length =1.3 ld = 1.30.05 (fy/ fc)db 30 = 2.5

    50 db = 50 (5/8) = 31.25 2.5 for fc 3 and fy 40 ksi

    2h=36 2h=36

    95

    Design Example 2 (SMRF)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    SMRF Requirements Checklist

    Provisions for Columns

    Size: All columns are 15 square, therefore the size is more than the

    least required for SMRF (i.e., 12).

    Flexural Reinforcement: All columns are reinforced with 8 #5 bars

    which gives g = 0.011, within the specified range 0.01 g 0.06.

    96

    Design Example 2 (SMRF)

  • 12/20/2014

    49

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    SMRF Requirements

    Checklist

    Provision for Columns

    Transverse Reinforcement:

    lo = max (larger column

    dimension, hc/6, 18) = 18

    Spacing of ties in lo region is

    least of = smaller column

    dimension/4, 6 long bar

    dia = 3.75

    Spacing in the remaining

    region will be least of 6

    long bar dia or 6 = 3.75

    hc = 8.5

    lo

    lo

    15 15 column

    8, #5 bars

    97

    #3 @ 3.75 c/cthroughout height

    Design Example 2 (SMRF)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    SMRF Requirements Checklist

    Provisions for Columns

    Lap Splice:

    Tension lap splice within center

    half of member length.

    Spacing of ties in lap splice not

    more than smaller of d/4 or 4.

    Continue 3.75 inch spacing.

    Lap length = 1.3 0.05 (fy/ fc )db=

    30 2.5

    And from 50db = 50(5/8) =

    31.25

    hc = 8.5

    98

    Design Example 2 (SMRF)

  • 12/20/2014

    50

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    SMRF Requirements Checklist

    Provision for Joints

    To prevent beam column joint cracking, ACI Code 21.5.1 requires that

    the column dimension parallel to the beam reinforcement must be at

    least 20 times the diameter of the largest longitudinal bar.

    20 5/8 = 12.5

    Column dimension parallel to beam long bar = 15, OK

    99

    Design Example 2 (SMRF)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    SMRF Requirements Checklist

    Provision for Joints

    6 #5 bars

    6 #5 bars

    2

    ColumnBeam

    Joint

    100

    Design Example 2 (SMRF)

  • 12/20/2014

    51

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Example 3: A two dimensional frame of the building is shown in

    figure 01. All beams in the frame are 12 wide and 18 deep. All

    columns are 12 square. It is required only for frame BFGC to:

    a. Provide suitable number of bars in beams and columns for which flexural

    reinforcement is shown in the figure (Use only #5 bars as main reinforcement

    and #3 bars as transverse reinforcement).

    b. Provide suitable spacing for stirrups and ties when shear reinforcement as

    per design is 0.23 in2/ft in all parts of the frame.

    c. Satisfy all SMRF requirements for beams and columns.

    d. Present appropriately proportioned structural details of beam and column.

    Also draw the beam to column joint detail at detail X as shown in fig. 01.

    Take fc = 3 ksi and fy = 40 ksi.

    101

    Design Example 3 (SMRF)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Given Building:

    Figure 01: RC Building Frame

    3.2 in2

    2.4 in2

    1.2 in22.6 in2 2.6 in2 2.4 in2

    1.2 in21.8 in23.0 in2 3.0 in2

    Detail X

    3.2 in2 3.2 in2 3.2 in2

    F G

    E H

    B CA D

    J K

    1.44 in2 1.44 in2

    1.0 in21.2 in2 1.2 in2

    10 ft ln =15 ft 10 ft

    10 ft

    10 ft

    1.2 in2 1.2 in2 1.0 in21.0 in2 1.0 in2 1.0 in2

    102

    Design Example 3 (SMRF)

  • 12/20/2014

    52

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution of Part (a)

    As given in problem, # of bars using #5 bars are as below:

    2.6 in2 2.6 in2

    1.8 in23.0 in2 3.0 in2

    3.2 in2 3.2 in2

    F G

    E H

    B CA D

    J K

    10 ft 15 ft 10 ft

    1.2 in2 1.2 in2

    # of bars = As/Ab

    Negative reinforcement at joint:

    2.6/0.31= 8.38 (take 9 bars in 2 layers)

    3.0/0.31= 9.67 (take 10 bars in 2 layers)

    Take 10 bars at joint for beam FG.

    Positive bars (mid span):

    1.8/0.31 = 5.80 (take 6 bars in 2 layers)

    Positive bars (at joint):

    1.2/0.31 = 3.87 (take 4 bars in 1 layer)

    Column reinforcement:

    3.2/ 0.31 = 10.32 (take 12 bars for even

    distribution of bars at all faces of column)

    103

    Design Example 3 (SMRF)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution of Part (a)

    (4+2) #5

    (5+5) #5 (5+5) #5

    12 #5 12 #5

    F G

    E H

    B CA D

    J K

    10 ft 15 ft 10 ft

    4 #5 4 #5

    104

    Design Example 3 (SMRF)

  • 12/20/2014

    53

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution of Part (b)

    As given in problem, Shear reinforcement spacing with #3 bar is:

    0.23 in2/ft

    F G

    E H

    B CA D

    J K

    10 ft 15 ft 10 ft

    Spacing= (Ab/As) 12

    With #3, 2 leg vertical stirrups (Ab = 0.22 in2)

    Stirrup spacing for beams:

    sb = (0.22/0.23) 12 = 11.47 c/c

    As per ACI minimum reinforcement and maximum

    spacing requirement, spacing should not exceed:

    i. Avfy/50bw = 14 c/c

    ii. d/2 = 16.5/2 = 8.25 c/c

    iii. 24 c/c

    iv. Avfy/{0.75(fc)bw = 17.85 c/c

    Finally sb = 8.25 c/c

    Tie spacing for column:

    s = (0.22/0.23) 12 = 11.47 c/c

    Spacing for tie bars according to ACI 7.10.5.1 is minimum of:16 dia of main bar =16 5/4 =10 c/c48 dia of tie bar = 48 (3/8) =18 c/cLeast column dimension =12 c/cFinally sc = 10 c/c

    0.23 in2/ft

    0.23 in2/ft

    105

    Design Example 3 (SMRF)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution of Part (b)

    As given in problem, Shear reinforcement spacing with #3 bar is:

    F G

    E H

    B CA D

    J K

    10 ft 15 ft 10 ft

    #3, 2 legged @ 8.25 c/c

    #3, ties @ 10 c/c #3, ties @ 10 c/c

    106

    Design Example 3 (SMRF)

  • 12/20/2014

    54

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution of Part (c)

    SMRF Requirements Checklist

    Provisions for Beams

    Sizes

    ln/d = 15 12/15 = 15 > 4 (ACI 21.3.1.2 satisfied)

    Width/ depth = 12/18 = 0.66 > 0.3 (ACI 21.3.1.3 satisfied)

    Width = 12 > 10, O.K.

    Therefore 12 wide and 18 beams are OK.

    107

    Design Example 3 (SMRF)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution of Part (c): SMRF Requirements Checklist

    Provisions for Beams

    Flexural Reinforcement

    Asl = (5+5) #5Asr = (5+5) #5

    Asmid+ = (4+2) #5Asl+ = 4 #5 Asr+ = 4 #5

    As (at all critical sections) Asmin

    As Asmin = 4 #5 bars

    As (at any section) Asmax

    Asmax = 0.025bd = 16 #5 barsOK

    As+ (at joints) As (at joints)

    4 #5 bars {(5+5) #5 bars}

    As (any section) Max. As at joints

    Provide at least 3 bar

    N.G

    Provide at least 5 bars at joint.O.K

    108

    Design Example 3 (SMRF)

  • 12/20/2014

    55

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution of Part (c): SMRF Requirements Checklist

    Provisions for Beams

    Recommended Flexural Reinforcement

    109

    Asl = (5+5) #5 Asr = (5+5) #5

    Asmid+ = (4+2) #5Asl+ = (4+2) #5 Asr+ = (4+2) #5

    3 #5

    Design Example 3 (SMRF)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution of Part (c): SMRF Requirements Checklist

    Provisions for Beams

    Transverse Reinforcement

    s

    d/4 = 15/4 = 3.75

    8 smallest long. bar dia.= 8 5/8= 5

    24 hoop bar diameter = 24 3/8= 9

    12 2

    2h = 36s d/2 = 15/2 = 7.5

    Column

    2h = 36

    110

    Design Example 3 (SMRF)

  • 12/20/2014

    56

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution of Part (c): SMRF Requirements Checklist

    Provisions for Beams

    Lap Splice: If required then,

    Not to be provided within joints. Not to be provided within 2h region from face of

    the support.

    Spacing of hoops within lap = least of d/4 or 4 c/c = 4 c/c

    Lap splice length =1.3 ld = 1.30.05 (fy/ fc)db 30 = 2.5

    50 db = 50 (5/8) = 31.25 2.5 for fc 3 and fy 40 ksi

    2h=36 2h=36

    111

    Design Example 3 (SMRF)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution of Part (c): SMRF Requirements Checklist

    Provisions for Columns

    Size: All columns are 12 square, which is equal to least required for

    SMRF (i.e., 12).

    Flexural Reinforcement: All columns are reinforced with 12 #5 bars

    which gives g = 0.025, within the specified range 0.01 g 0.06.

    112

    Design Example 3 (SMRF)

  • 12/20/2014

    57

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution of Part (c): SMRF

    Requirements Checklist

    Provision for Columns

    Transverse Reinforcement:

    lo = max (larger column dimension,

    hc/6, 18) = 18.5

    Spacing of ties in lo region is least of =

    smaller column dimension/4, 6 long

    bar dia = 3

    Spacing in the remaining region will be

    least of 6 long bar dia or 6 = 3.75

    hc = 9.25

    lo

    lo

    12 12 column

    12, #5 bars

    G.L

    113

    Design Example 3 (SMRF)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution of Part (c): SMRF

    Requirements Checklist

    Provisions for Columns

    Lap Splice:

    Tension lap splice within center

    half of member length.

    Spacing of ties in lap splice not

    more than smaller of d/4 or 4

    Lap length = 1.3 0.05 (fy/ fc )db=

    30 2.5

    And from 50db = 50(5/8) =

    31.25

    hc = 9.25

    lo

    lo

    12 12 column

    G.L

    114

    Design Example 3 (SMRF)

  • 12/20/2014

    58

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution of Part (c): SMRF Requirements Checklist

    Provision for Joints

    To prevent beam column joint cracking, ACI Code 21.5.1 requires that

    the column dimension parallel to the beam reinforcement must be at

    least 20 times the diameter of the largest longitudinal bar.

    20 5/8 = 12.5

    Column dimension parallel to beam long bar = 12, Almost OK.

    115

    Design Example 3 (SMRF)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution of Part (c): SMRF Requirements Checklist

    Provision for Joints

    (5+5) #5 bars

    (4+2) #5 bars

    2

    ColumnBeam

    Joint

    116

    Design Example 3 (SMRF)

  • 12/20/2014

    59

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution of Part (d):

    Presentation of appropriately proportioned structural details of

    beam, column and selected joint.

    In this part, structural drawings showing all calculated SMRF details

    have been asked to draw. This has already been done in part (c) along

    with each member (beam and column) SMRF checks.

    However in the examination, it is better to draw all drawings here in part

    (d) at the same place to avoid waste of time.

    Part (d) is shown next.

    117

    Design Example 3 (SMRF)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution of Part (d):

    Structural Details for beam (Long section):

    s = 3.75

    2

    2h = 36s = 7.5

    Column

    2h = 36

    (5+5) #5

    (5+5) #5

    (4+2) #5(4+2) #5 (4+2) #5

    Note: Lap splice is provided only if required.

    A

    A

    B

    B

    118

    3 #5

    Design Example 3 (SMRF)

  • 12/20/2014

    60

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution of Part (d):

    Structural Details for Beam (Cross sections):

    12

    18

    (5+5) #5

    (4+2) #5

    Section A-A

    12

    18

    3 #5

    (4+2) #5

    Section B-B

    #3, 2 legged @ 3.75 c/c

    #3, 2 legged @ 7.5 c/c

    119

    Design Example 3 (SMRF)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution of Part (d):

    Structural Details for Column:

    lo = 18.5

    12 12 column

    12, #5 bars

    G.L

    lo = 18.5

    #3 ties @ 3 c/c (throughout)

    Lap length = 2.5

    12 #5

    #3ties @ 3 c/c

    12

    12

    120

    Design Example 3 (SMRF)

  • 12/20/2014

    61

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    Solution of Part (d):

    Structural Details for Joints:

    (5+5) #5 bars

    (4+2) #5 bars

    2

    ColumnBeam

    Joint

    121

    Design Example 3 (SMRF)

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    References

    ACI 318

    UBC-97

    BCP SP-2007

    Earthquake tips from IITK.

    122

  • 12/20/2014

    62

    Prof. Dr. Qaisar Ali Reinforced Concrete Design II

    Department of Civil Engineering, University of Engineering and Technology Peshawar

    The End

    123