Upload
abdul-hamid-bhatti
View
13
Download
0
Tags:
Embed Size (px)
DESCRIPTION
THE BEST
Citation preview
12/20/2014
1
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Lecture - 06
Introduction to Earthquake Resistant Design of Reinforced
Concrete Structures
By: Prof Dr. Qaisar Ali
Civil Engineering Department
UET Peshawar
www.drqaisarali.com
1
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Topics
Introduction to Earthquakes and Its Effects on Buildings
Earthquake Design Philosophy
Seismic Loading Criteria
Example 1 (Static Lateral Load Procedure)
Gravity vs. Earthquake Loading in RC Buildings
ACI Special Provisions for Seismic Design
ACI Provisions for Special Moment Resisting Frames (SMRF)
2
12/20/2014
2
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Topics
ACI Provisions for Intermediate Moment Resisting Frames
(IMRF)
Miscellaneous Considerations
Design Example 2 (SMRF)
Design Example 3 (SMRF)
3
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Introduction to Earthquakes and Its Effects on Buildings
Earths Interior
4
12/20/2014
3
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Earthquake results from the sudden movement of
the tectonic plates in the earths crust.
5
Introduction to Earthquakes and Its Effects on Buildings
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Effect of Earthquake
The movement, taking place at the fault lines, causes
energy release which is transmitted through the earth in
the form of waves. These waves reach the structure
causing shaking.
6
Introduction to Earthquakes and Its Effects on Buildings
12/20/2014
4
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Seismic Events around the globe
Mostly takes place at boundaries of Tectonic plates
7
Dots represents an earthquake
Introduction to Earthquakes and Its Effects on Buildings
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Types of Waves Generated Due to Earthquake
8
Body Waves Surface Waves
Introduction to Earthquakes and Its Effects on Buildings
12/20/2014
5
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Displacement due to Earthquake
9
Introduction to Earthquakes and Its Effects on Buildings
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
10
Introduction to Earthquakes and Its Effects on Buildings
Horizontal and Vertical Shaking
Earthquake causes shaking of the ground in all three directions.
The structures designed for gravity loading (DL+LL) will be
normally safe against vertical component of ground shaking.
The vertical acceleration during ground shaking either adds to or
subtracts from the acceleration due to gravity.
12/20/2014
6
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
11
Introduction to Earthquakes and Its Effects on Buildings
Horizontal and Vertical Shaking
The structures are normally designed for horizontal shaking to
minimize the effect of damages due to earthquakes.
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Earthquake Types with respect to Depth of Focus
Shallow
Depth of focus varies between 0 and 70 km.
Deep
Depth of focus varies between 70 and 700 km.
12
Introduction to Earthquakes and Its Effects on Buildings
12/20/2014
7
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Earthquake characteristics with respect to distance
from epicenter
0.05 T 0.320 Hz f 3.33 Hz
Low period & high frequency field
0.3 T 1.0 sec3.33 Hz f 1 Hz
1.0 T 10 sec
25 km
Large period & low frequency field
Moderate period & low frequency field
Epicenter
1 Hz f 0.1 Hz
Near Field: 0 to 25 km
Intermediate Field: 25 to 50 km
Far Field: Beyond 50 km
13
Introduction to Earthquakes and Its Effects on Buildings
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Resonance risk for structures w.r.t near, intermediate
and far field earthquakes
The natural time period of a structure is its important characteristic
to predict behavior during an earthquake of certain time period
(Resonance phenomenon).
For a particular structure, the natural time period is a function of
mass and stiffness {T = 2p(m/k)}
T can be roughly estimated from: T = 0.1 number of stories
14
Introduction to Earthquakes and Its Effects on Buildings
12/20/2014
8
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Resonance risk for structures w.r.t near, intermediate
and far field earthquakes
Low rise Structure
(upto 3 stories)
Epicenter
Medium rise Structure
(upto 5 stories)
High rise Structure
(Above 5 stories)
15
Introduction to Earthquakes and Its Effects on Buildings
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Earthquake Recording
Seismograph
Using multiple seismographs
around the world, accurate
location of the epicenter of the
earthquake, as well as its
magnitude or size can be
determined.
Working of seismograph shown
in figure.
16
Introduction to Earthquakes and Its Effects on Buildings
12/20/2014
9
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Earthquake Recording
Richter Scale
In 1935, Charles Richter (US)
developed this scale.
The Richter scale is logarithmic,
So, a magnitude 5 Richter
measurement is ten times
greater than a magnitude 4;
while it is 10 x 10, or 100 times
greater than a magnitude 3
measurement.
17
Introduction to Earthquakes and Its Effects on Buildings
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Earthquake Recording
Some of the famous
earthquake records
18
Introduction to Earthquakes and Its Effects on Buildings
12/20/2014
10
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Earthquake Occurrence
19
Introduction to Earthquakes and Its Effects on Buildings
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Seismic Zones
20
Introduction to Earthquakes and Its Effects on Buildings
12/20/2014
11
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Importance of Architectural Features
The behavior of a building during
earthquakes depend critically on its overall
shape, size and geometry, in addition to
how the earthquake forces are carried to the
ground.
21
Introduction to Earthquakes and Its Effects on Buildings
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
22
Introduction to Earthquakes and Its Effects on Buildings
Importance of Architectural Features
At the planning stage, architects and structural engineers
must work together to ensure that the unfavorable features
are avoided and a good building configuration is chosen.
12/20/2014
12
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
23
Introduction to Earthquakes and Its Effects on Buildings
Other Undesirable Scenarios
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Soft Storey
24
Introduction to Earthquakes and Its Effects on Buildings
12/20/2014
13
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Earthquake Design Philosophy
Performance level
25
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Building Code of Pakistan
In Pakistan, the design criteria for earthquake loading are based
on design procedures presented in chapter 5, division II of
Building Code of Pakistan, seismic provision 2007 (BCP, SP
2007), which have been adopted from chapter 16, division II of
UBC-97 (Uniform Building Code), volume 2.
Seismic Loading Criteria
26
12/20/2014
14
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Lateral Force Determination Procedures
The total design seismic force imposed by an earthquake on
the structure at its base is referred to as base shear V in the
UBC-97.
The design seismic force can be determined based on:
Dynamic lateral force procedure [sec. 1631, UBC-97 or sec. 5.31, BCP-2007].
Static lateral force procedure [sec. 1630.2, UBC-97 or Sec. 5.30.2, BCP 2007],
Seismic Loading Criteria
27
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Dynamic Lateral Force Procedure
UBC-97 section 1631 include information on dynamic lateral force
procedures that involve the use of:
Time history analysis.
Response spectrum analysis.
The details of these methods are presented in sections 1631.5
and 1631.6 of the UBC-97.
Seismic Loading Criteria
28
12/20/2014
15
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Dynamic Lateral Force Procedure
Time History Analysis (THA)
T
Ground acceleration
T
LateralDisplacement
Seismic Loading Criteria
29
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Dynamic Lateral Force Procedure
Response Spectrum Analysis (RSA)
T
a (ft/sec2)
T
Response
a (ft/sec2)
T
a (ft/sec2)
T
Response
Response
Ts1 = 0.3 sec
Ts2 = 1.0 sec
Ts3 = 2.0 sec
D1
D2
D3
(Ts1,D1)
(Ts2,D2)
(Ts3,D3)
Structural Time period
Peak Response
T
T
Seismic Loading Criteria
30
12/20/2014
16
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
UBC-97 Response Spectrum Curve(Acceleration vs. Time period)
Dynamic Lateral Force Procedure
Response Spectrum Analysis (RSA)
Seismic Loading Criteria
31
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
=
Static Lateral Force Procedure
Seismic Loading Criteria
32
12/20/2014
17
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Static Lateral Force Procedure
The total design base shear (V) in a given direction can be
determined from the following formula:
V = (CI/RT) W
Where,
C = Seismic coefficient (Table 16-R of UBC-97).
I = Seismic importance factor (Table 16-K of UBC-97 )
R = numerical coefficient representative of inherent over strength and
global ductility capacity of lateral force-resisting systems (Table 16-N
or 16-P).
W = the total seismic dead load defined in Section 1630.1.1.
Seismic Loading Criteria
33
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Static Lateral Force Procedure
The total design base need not exceed [ V = (2.5CaI/R) W ]
Where, Ca = Seismic coefficient (Table 16-Q of UBC-97)
The total design base shear shall not be less than [ V = 0.11CaIW ]
In addition for seismic zone 4, the total base shear shall also not
be less [ V = (0.8ZNI/R) W ]
Where, N = near source factor (Table 16-T of UBC-97);
Z = Seismic zone factor (Table 16-I of UBC-97)
Seismic Loading Criteria
34
12/20/2014
18
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Static Lateral Force Procedure
Steps for Calculation of V:
Step 1: Find Site Specific details.
Step 2: Determine Seismic Coefficients
Step 3: Determine Seismic Importance factor I
Step 4: Determine R factor
Step 5: Determine structures time period
Step 6:Determine base shear V and apply code maximum and
minimum.
Step 7: Determine vertical distribution of V.
Seismic Loading Criteria
35
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Static Lateral Force Procedure
Steps for Calculation of V:
Step 1: Find Site Specific details.
Following list of data needs to be obtained:
Seismic Zone
Soil type
Past earthquake magnitude (required only for highest seismic zone).
Closest distance to known seismic source (required only for highest seismic
zone).
Seismic Loading Criteria
36
12/20/2014
19
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Static Lateral Force Procedure
Steps for Calculation of V:
Step 1: Site Specific details.
i. Seismic ZoneSource: BCP SP-2007
Seismic Loading Criteria
37
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Static Lateral Force Procedure
Steps for Calculation of V:
Step 1: Find Site Specific details.
ii. Soil Type
As per UBC code, if soil type is not known, type SD shall be taken.
Seismic Loading Criteria
38
12/20/2014
20
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Static Lateral Force Procedure
Steps for Calculation of V:
Step 1: Find Site Specific details.
iii. Past Earthquake magnitude: This is required only for seismic zone 4
to decide about seismic source type so that certain additional coefficients
can be determined.
iv. Distance to known seismic zone is also required to determine
additional coefficients for zone 4.
Seismic Loading Criteria
39
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Static Lateral Force Procedure
Steps for Calculation of V:
Step 2: Determination of Seismic Coefficients.
Cv:
Nv (required only for zone 4):
Seismic Loading Criteria
40
12/20/2014
21
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Static Lateral Force Procedure
Steps for Calculation of V:
Step 2: Determination of Seismic Coefficients.
Ca:
Na (required only for zone 4):
Seismic Loading Criteria
41
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Static Lateral Force Procedure
Steps for Calculation of V:
Step 3: Determination of Seismic Importance Factor.
Seismic Loading Criteria
42
12/20/2014
22
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Static Lateral Force Procedure
Steps for Calculation of V:
Step 4: Determination of R Factor.
R factor basically reduces base shear V to make the system
economical. However the structure will suffer some damage as explained
in the earthquake design philosophy.
R factor depends on overall structural response of the structure under
lateral loading.
For structures exhibiting good performance, R factor will be high.
Seismic Loading Criteria
43
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Static Lateral Force Procedure
Steps for Calculation of V:
Step 4: Determination of R Factor.
Seismic Loading Criteria
44
12/20/2014
23
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Static Lateral Force Procedure
Steps for Calculation of V:
Step 5: Determination of structures time period.
Structural Period (By Method A, UBC 97): For all buildings, the value T
may be approximated from the following formula:
T = Ct (hn)3/4
Where,
Ct = 0.035 (0.0853) for steel moment-resisting frames.
Ct = 0.030 (0.0731) for reinforced concrete moment-resisting frames and eccentrically
braced frames.
Ct = 0.020 (0.0488) for all other buildings.
hn = Actual height (feet or meters) of the building above the base to the nth level.
Seismic Loading Criteria
45
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Static Lateral Force Procedure
Steps for Calculation of V:
Step 6: Determination of Base Shear (V).
Calculate base shear meeting the following criteria:
0.11CaIW V = (CI/RT) W (2.5CaI/R) W
For zone 4, the total base shear shall also not be less than:
V = (0.8ZNI/R) W
Seismic Loading Criteria
46
12/20/2014
24
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Static Lateral Force Procedure
Steps for Calculation of V:
Step 7: Vertical Distribution of V to storeys.
The joint force at a particular level x of the structure is given as:
Fx = (V Ft)xhx/ihi (UBC sec. 1630.5)
{ i ranges from 1 to n, where n = number of stories }
Ft = Additional force that is applied to the top level (i.e., the roof) in
addition to the Fx force at that level.
Ft = 0.07TV {for T > 0.7 sec}
Ft = 0 {for T 0.7 sec}
Seismic Loading Criteria
47
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Example: Calculate the base shear and storey forces of a five storey
building given in the figure. The structure is constructed on stiff soil
which comes under soil type SD of table 16-J of UBC-97. The
structure is located in zone 3.
Example 1(Static Lateral Force Procedure)
60-0
12-0
800 kip
800 kip
800 kip
800 kip
700 kip
48
12/20/2014
25
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution: Selection of Ca and Cv.
Base Shear (V) = {CvI/RT}W
49
Example 1(Static Lateral Force Procedure)
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution: Selection of I.
Base Shear (V) = {CvI/RT}W
Therefore, I = 1.00
50
Example 1(Static Lateral Force Procedure)
12/20/2014
26
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution: Selection of R.
Base Shear (V) = {CvI/RT}W
Therefore, R = 8.5 (for SMRF)
51
Example 1(Static Lateral Force Procedure)
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution: Calculation of T and W
Base Shear (V) = {CvI/RT}W
T = Ct (hn)3/4
= 0.030 (60)3/4
= 0.646 sec.
W = w1 + w2 + w3 + w4 + w5
= 4 800 + 700
= 3900 kip
hn = 60-0
12-0
w1 = 800 kip
w2= 800 kip
w3 = 800 kip
w4 = 800 kip
w5 = 700 kip
52
Example 1(Static Lateral Force Procedure)
12/20/2014
27
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution: Therefore,
V = {CvI/RT}W
= {0.54 1.00/ (8.5 0.646)} 3900 = 383 kips
The total design base need not exceed the following:
V = (2.5CaI/R) W
= {(2.5 0.36 1.00)/ (8.5)} 3900 = 413 kips
The total design base shear shall not be less than the following:
V = 0.11CaIW
= 0.11 0.36 1.00 3900 = 154.44 kips
Therefore, V = 383 kip
53
Example 1(Static Lateral Force Procedure)
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution: Vertical distribution of base shear to stories
The joint force at a level x of the structure is given as:
Fx = (V Ft)xhx/ihi
{ i ranges from 1 to n, where n = number of stories }
Ft = Additional force that is applied to the top level (i.e., the roof) in addition to the
Fx force at that level.
Ft = 0.07TV {for T > 0.7 sec}
Ft = 0 {for T 0.7 sec}
54
Example 1(Static Lateral Force Procedure)
12/20/2014
28
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution: Vertical distribution of base shear to stories
Fx = (V Ft)xhx/ihi
ihi = 80012 + 80024 + 80036 + 80048 + 70060 = 138000 kip
Therefore for the case under consideration, Force for storey 1 is:
F1 = (383 0) 800 12/ {(138000)} = 27 kip
Storey forces for other stories are given in table below.
Table Storey shears.Level
xhx (ft)
wx(kip)
wxhx (ft-kip)wxhx
/(wihi)Fx (kip)
5 60 700 42000 0.304 1174 48 800 38400 0.278 1073 36 800 28800 0.209 802 24 800 19200 0.139 531 12 800 9600 0.070 27
wihi = 138000Check SFx =V = 383 kip OK
55
Example 1(Static Lateral Force Procedure)
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution: Vertical distribution of base shear to stories
Table: Storey shearsLevel
xhx (ft)
wx(kip)
wxhx (ft-kip)wxhx
/(wihi)Fx (kip)
5 60 700 42000 0.304 1174 48 800 38400 0.278 1073 36 800 28800 0.209 802 24 800 19200 0.139 531 12 800 9600 0.070 27
wihi = 138000Check Fx =V = 383 kip OK
800 kip
800 kip
800 kip
800 kip
700 kip
383 kips
117 kips
107 kips
80 kips
53 kips
27 kips
56
Example 1(Static Lateral Force Procedure)
12/20/2014
29
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Reversal of stresses takes place
during earthquake shaking, fig.
Earthquake shaking reverses
tension and compression in
members
Reinforcement is required on
both faces of members.
Gravity vs. Earthquake Loading in Reinforced Concrete Building
57
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
The principal goal of the Special Provisions is to ensure adequate
toughness under inelastic displacement reversals brought on by
earthquake loading.
The provisions accomplish this goal by requiring the designer to
provide for concrete confinement and inelastic rotation capacity.
No special requirements are placed on structures subjected to low or
no seismic risk.
Structural systems designed for high and moderate seismic risk are
referred to as Special and Intermediate respectively.
ACI Special Provisions for Seismic Design
58
12/20/2014
30
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Based on moment resisting capacity, there are three types of RC
frames,
SMRF (Special Moment Resisting Frame),
IMRF (Intermediate Moment Resisting Frame),
OMRF (Ordinary Moment Resisting Frame).
Some general requirements will be presented first, which are
common to all frames. Specific requirements for each type of frame
are presented later on.
ACI Special Provisions for Seismic Design
59
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
General Requirements
Concrete in members resisting earthquake induced forces
Min fc = 3000 Psi (cylinder strength) for all types
No maximum limit on ordinary concrete
5000 psi is maximum limit for light weight
ACI Special Provisions for Seismic Design
60
12/20/2014
31
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
General Requirements
Reinforcement in members resisting earthquake induced forces
Grade 60, conforming to ASTM A 706 (low alloy steel)
Grade 40 or 60, conforming to ASTM A 615 (billet steel) provided that
Fy (actual) Fy (specified) +18 Ksi
Actual Ultimate / Actual Fy 1.25
ACI Special Provisions for Seismic Design
61
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
General Requirements
Hoops, Ties and Cross Ties
Confinement for concrete is provided by transverse reinforcement
consisting of stirrups. hoops, and crossties.
To ensure adequate anchorage, a seismic hook (shown in figure) is used
on stirrups, hoops and crossties .
62
(Seismic Hook)
ACI Special Provisions for Seismic Design
12/20/2014
32
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
General Requirements
Hoops, ties and Crossties: Advantages
Closely spaced horizontal closed ties in column help in three ways:
i. they carry the horizontal shear forces induced by earthquakes, and thereby
resist diagonal shear cracks,
ii. they hold together the vertical bar and prevent them from excessively
bending outwards (in technical terms, this bending phenomenon is called
buckling), and
iii. they contain the concrete in the column. The ends of the ties must be bent
at 135 hooks. Such hook ends prevent opening of hoops and
consequently buckling of concrete and buckling of vertical bars.
ACI Special Provisions for Seismic Design
63
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Provisions for Flexural Members
These provision applies to flexural members with:
Factored axial compressive force Agfc/10.
Note: These provisions generally apply to beams because axial load
on beams is generally 0 or less than Agfc/10.
However they are also applicable to columns subjected to axial load less
than Agfc/10.
ACI Provisions for Special Moment Resisting Frames (SMRF)
64
12/20/2014
33
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Provisions for Flexural Members
1. Size: The members must have:
a. clear span-to-effective-depth ratio of at least 4, (Ln/d 4)
e.g., for Ln = 15 ft, d = 16, Ln/d = 15 12/16 = 11.25 > 4, O.K.
b. a width-to-depth ratio of at least 0.3, b/h 0.3
e.g., for width (b) = 12 and depth (h) = 18, b/h = 12/18 = 0.67 > 0.3, O.K.
c. A web width of not less 10 inches.
ACI Provisions for Special Moment Resisting Frames (SMRF)
65
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Provisions for Flexural Members
2. Flexural Reinforcement
Asl
Asl+ (Asl)/2
As or As+ (at all section) (maximum of As at either joint)/4
Asr
Asr+ (Asr)/2
rmin = 3fc/fy, 200/fy (at critical sections)
rmax = 0.025 (at critical sections)
Min. 2 bars continuous at all sections
ACI Provisions for Special Moment Resisting Frames (SMRF)
66
12/20/2014
34
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Provisions for Flexural Members
3. Transverse Reinforcement
s
d/4
8 smallest longitudinal bar diameter
24 hoop bar diameter
12 2
2h 2hs d/2
Column
Column
ACI Provisions for Special Moment Resisting Frames (SMRF)
67
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Provisions for Flexural Members
4. Lap Splice Lap splice length =1.3 ld = 1.3 0.05 (fy/ fc)db50 db for fc 3 and fy 40 ksi
70 db for fc 3 and fy 60 ksi
Spacing of stirrups Least of d/4 or 4 inches
Lapping prohibited in regions where longitudinal bars can yield in tension
Lapping of Longitudinal bars
2h 2h
ACI Provisions for Special Moment Resisting Frames (SMRF)
68
12/20/2014
35
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
ACI Provisions for Special Moment Resisting Frames (SMRF)
69
Mechanical Splice of Longitudinal Reinforcement
Mechanical Splices shall conform to 21.2.6.
Section 21.2.6 says that welded splice shall conform to 12.14.3.2
which states A full mechanical splice shall develop in tension or
compression, as required, at least 125 % of the specified yield
strength (fy) of the bar.
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
ACI Provisions for Special Moment Resisting Frames (SMRF)
70
Welded Splice of Longitudinal Reinforcement
Welded Splices shall conform to 21.2.7.
Section 7.3.6 says that welded splice shall conform to 12.14.3.4
which states A full welded splice shall develop at least 125 % of
the specified yield strength (fy) of the bar.
12/20/2014
36
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
ACI Provisions for Special Moment Resisting Frames (SMRF)
71
Provision for Frame Members Subjected to Bending
and Axial Load
The provision applies to members with:
Factored axial compressive force > Agfc/10
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Provision for Frame Members Subjected to Bending
and Axial Load
1. Size
a) Each side at least 12 inches
b) Shorter to longer side ratio 0.4.
i.e. 12/12, 12/18, 12/24 OK; but 12/36 not O.K
ACI Provisions for Special Moment Resisting Frames (SMRF)
72
12/20/2014
37
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Provision for Frame Members
Subjected to Bending and Axial
Load
2. Longitudinal Reinforcement
0.01 rg 0.06
Clear span, hc
ACI Provisions for Special Moment Resisting Frames (SMRF)
73
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Provision for Frame
Members Subjected
to Bending and
Axial Load
3. Trans. Rein.
h2
h1
s 0.25 (smaller of h1 or h2)
6 long. bar dia.
so
s 6 long. bar dia.6
lo
lo Larger of h1 or h2
Clear span/6
18
ACI Provisions for Special Moment Resisting Frames (SMRF)
74
12/20/2014
38
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Provision for Frame Members Subjected to Bending and Axial Load
3. Trans. Rein.
4 so = 4 + [(14 hx)/3] 6
hx = max. value of hx on all column faces
hx 14
hx hx hx
hx
hx
6db 3 6db extension
Alternate90-deg hooks
Provide add.trans. reinf. if thickness > 4
ACI Provisions for Special Moment Resisting Frames (SMRF)
75
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Provision for Frame Members Subjected
to Bending and Axial Load
4. Lap Splice
Tension lap splicewithin center half ofmember length
Lap splice length =1.3 ld = 1.3 0.05 (fy/ fc)db
50 db for fc 3 and fy 40 ksi
70 db for fc 3 and fy 60 ksi
Spacing of ties in lap splice not more than smaller of d/4 or 4
ACI Provisions for Special Moment Resisting Frames (SMRF)
76
12/20/2014
39
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Joints of Special Moment Frame
Beam
Column
Beam Column Joint
Column ties (with 135o) hook continued through joint(ACI 21.5.2)
77
ACI Provisions for Special Moment Resisting Frames (SMRF)
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Joints of Special Moment Frame
Successful seismic design of frames require that the structures be
proportioned so that hinges occur at locations that least
compromise strength. For this, weak-beam strong-column
approach is used.
After design, the member capacities are calculated based on
designed section.
At joint, Column flexural capacity 1.20 x Beam flexural capacity
ACI Provisions for Special Moment Resisting Frames (SMRF)
78
12/20/2014
40
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Joints of Special Moment Frame
Minimum Flexural Strength of Column at Joint
M+nc,t
M-nc,b
M+nb,r
M-nb,l
M+nc,b + M-nc,t 6(M
+nb,l + M
-nb,r)/5
M-nc,t
M+nc,b
M+nb,l M-nb,r
M-nc,b + M+
nc,t 6(M-nb,l + M
+nb,r)/5
ACI Provisions for Special Moment Resisting Frames (SMRF)
79
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Joints of Special Moment Frame
To prevent beam column joint cracking, ACI Code 21.5.1
requires that the column dimension parallel to the beam
reinforcement must be at least 20 times the diameter of the
largest longitudinal bar.
Beam longitudinal reinforcement with diameter (db)
20db
Beam
Column
ACI Provisions for Special Moment Resisting Frames (SMRF)
80
12/20/2014
41
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Joints of Special Moment Frame
Beam longitudinal reinforcement that is terminated within a
column. must be extended to the far face of the column core.
The development length (ldh) of bars with 90 hooks must be not
less than 8db, 6 inch, Or fydb/ (65 fc).
Beam longitudinal reinforcement
Beam
Column
ldh
ACI Provisions for Special Moment Resisting Frames (SMRF)
81
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Provision for Flexural Members
1. Size: No special requirement (Just as ordinary beam
requirement).
2. Flexural steel: Less stringent requirement as discussed next.
3. Transverse steel: Same as for SMRF.
4. Lap: No special requirement (Just as ordinary beam
requirement).
ACI Provisions for Intermediate Moment Resisting Frames (IMRF)
82
12/20/2014
42
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Provisions for Flexural Members
2. Flexural Reinforcement
Asl
Asl+ (Asl)/3
As or As+ (at all section) (maximum of As at either joint)/5
Asr
Asr+ (Asr)/3
rmin = 3fc/fy, 200/fy (at critical sections)
t 0.004
ACI Provisions for Intermediate Moment Resisting Frames (IMRF)
83
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Provision for Columns
1. Size: No special requirement (Just as ordinary column
requirement)
2. Flexural steel: No special requirement (Just as ordinary column
requirement)
3. Transverse steel: Less Stringent requirement as given next.
4. Lap: No special requirement (Just as ordinary column
requirement)
ACI Provisions for Intermediate Moment Resisting Frames (IMRF)
84
12/20/2014
43
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Provision for Columns
h2
h1
so/2
Trans. reinf. based on Mn and factored tributary gravity load
so
8 smallest long. bar dia.
24 tie bar dia.
0.5 min. (h1 or h2)
12
lo
lo
Larger of h1 or h2
Clear span/6
18
s d/2 (As per ACI 11.5.4)
ACI Provisions for Intermediate Moment Resisting Frames (IMRF)
85
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
IMRF are not allowed in regions of high seismic risk, however,
SMRF are allowed in regions of moderate seismic risk.
Unlike regions of high seismic risk, two way slab system without
beams are allowed in regions of moderate seismic risk.
In regions of low or no seismic risk ordinary moment resisting
frames OMRF are allowed but IMRF and SMRF may also be
provided.
Miscellaneous Considerations
86
12/20/2014
44
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Example 2: Detail the selected frame of E-W interior frame of the
given structure as per SMRF requirements. The structure is
already designed for the following seismic zone data.
Seismic zone: 4
Magnitude of earthquake 7.0
Slip rate 5.0
Closest distance to known seismic source > 15 km.
Soil type: SD (stiff).
Concrete compressive strength = 3 ksi,
Steel yield strength = 40 ksi
Modulus of elasticity of concrete = 3000 ksi.
Design Example 2 (SMRF)
87
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Given 3D structure:
20 ft 20 ft 20 ft 20 ft
15 ft
15 ft
15 ft
10.5 ft
10.5 ft
10.5 ft (floor to floor)
SDL = 40 psfLL = 60 psf
SDL = 40 psfLL = 60 psf
SDL = 40 psfLL = 60 psf
fc = 3 ksify = 40 ksi
Slab-Beam Frame Structure
Beams: 15 18 (d =15 inch)Columns: 15 square
Design Example 2 (SMRF)
88
12/20/2014
45
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Selected portion of E-W interior Frame:
20 ft 20 ft 20 ft 20 ft
Portion of frame considered
Design Example 2 (SMRF)
89
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Reinforcement from Design:
For the beam in the given frame, we have
Asmin = 0.005 x15 x 15 = 1.125 in2
Asmax = 0.025x15 x 15 = 5.625 in2
Negative reinforcement at the ends and positive
reinforcement at the mid span must be greater
than Asmin and reinforcement at all locations must
be less than the Asmax
This is OK for the values on the given beam.
For the column, we have
Asmin = 0.01 x15 x 15 = 2.25 in2
This is also OK.20 ft 20 ft 20 ft 20 ft
1.61 1.61
1.02 1.021.21
2.25 2.25
Reinforcement in in2
Design Example 2 (SMRF)
90
12/20/2014
46
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Calculation of number of bars:
20 ft 20 ft 20 ft 20 ft
No. of bars = As/Ab
Use No. 5 bar,
Negative reinforcement at joint:
Left joint:
1.61/0.31= 5.19 (take 6 bars in 2 layers)
Right joint:
1.61/0.31= 5.19 (take 6 bars in 2 layers)
Positive bars (mid span):
1.21/0.31 = 3.9 (take 4 bars in 1 layer)
Positive bars (at joint):
1.01/0.31 = 3.29 (take 4 bars in 1 layer)
Column reinforcement:
2.25/ 0.31 = 7.25 (take 8 bars for even distribution
of bars at all faces of column)
6 bars 6 bars
4 bars 4 bars4 bars
8 bars 8 bars
No. of #5 bars
Design Example 2 (SMRF)
91
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
SMRF Requirements Checklist
Provisions for Beams
Sizes
ln/d = 20 12/15 = 16 > 4 (ACI 21.3.1.2 satisfied)
Width/ depth = 15/18= 0.833 > 0.3 (ACI 21.3.1.3 satisfied)
Width = 15 > 10, O.K.
Therefore 12 wide and 18 beams are OK
Design Example 2 (SMRF)
92
12/20/2014
47
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
SMRF Requirements Checklist
Provisions for Beams
Flexural Reinforcement
As+ (at joints) As (at joints)
4 #5 bars (6 #5 bars)
As (any section) Max. As at joints
2 #5 bars (6 #5 bars)OK OK
Asl = 6 #5 Asr = 6 #5
Asmid+ = 4 #5Asl+ = 4 #5 Asr+ = 4 #5
Design Example 2 (SMRF)
93
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
SMRF Requirements Checklist
Provisions for Beams
Transverse Reinforcement
s
d/4 = /4 = 3.75
8 smallest long. bar dia.= 8 5/8= 5
24 hoop bar diameter = 24 3/8= 9
12 2
2h = 36s d/2 = 15/2 = 7.5
Column
2h = 36
94
Design Example 2 (SMRF)
12/20/2014
48
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
SMRF Requirements Checklist
Provisions for Beams
Lap Splice: If required then,
Not to be provided within joints. Not to be provided within 2h region from face of
the support.
Spacing of hoops within lap = least of d/4 or 4 c/c = 3.75 c/c
Lap splice length =1.3 ld = 1.30.05 (fy/ fc)db 30 = 2.5
50 db = 50 (5/8) = 31.25 2.5 for fc 3 and fy 40 ksi
2h=36 2h=36
95
Design Example 2 (SMRF)
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
SMRF Requirements Checklist
Provisions for Columns
Size: All columns are 15 square, therefore the size is more than the
least required for SMRF (i.e., 12).
Flexural Reinforcement: All columns are reinforced with 8 #5 bars
which gives g = 0.011, within the specified range 0.01 g 0.06.
96
Design Example 2 (SMRF)
12/20/2014
49
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
SMRF Requirements
Checklist
Provision for Columns
Transverse Reinforcement:
lo = max (larger column
dimension, hc/6, 18) = 18
Spacing of ties in lo region is
least of = smaller column
dimension/4, 6 long bar
dia = 3.75
Spacing in the remaining
region will be least of 6
long bar dia or 6 = 3.75
hc = 8.5
lo
lo
15 15 column
8, #5 bars
97
#3 @ 3.75 c/cthroughout height
Design Example 2 (SMRF)
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
SMRF Requirements Checklist
Provisions for Columns
Lap Splice:
Tension lap splice within center
half of member length.
Spacing of ties in lap splice not
more than smaller of d/4 or 4.
Continue 3.75 inch spacing.
Lap length = 1.3 0.05 (fy/ fc )db=
30 2.5
And from 50db = 50(5/8) =
31.25
hc = 8.5
98
Design Example 2 (SMRF)
12/20/2014
50
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
SMRF Requirements Checklist
Provision for Joints
To prevent beam column joint cracking, ACI Code 21.5.1 requires that
the column dimension parallel to the beam reinforcement must be at
least 20 times the diameter of the largest longitudinal bar.
20 5/8 = 12.5
Column dimension parallel to beam long bar = 15, OK
99
Design Example 2 (SMRF)
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
SMRF Requirements Checklist
Provision for Joints
6 #5 bars
6 #5 bars
2
ColumnBeam
Joint
100
Design Example 2 (SMRF)
12/20/2014
51
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Example 3: A two dimensional frame of the building is shown in
figure 01. All beams in the frame are 12 wide and 18 deep. All
columns are 12 square. It is required only for frame BFGC to:
a. Provide suitable number of bars in beams and columns for which flexural
reinforcement is shown in the figure (Use only #5 bars as main reinforcement
and #3 bars as transverse reinforcement).
b. Provide suitable spacing for stirrups and ties when shear reinforcement as
per design is 0.23 in2/ft in all parts of the frame.
c. Satisfy all SMRF requirements for beams and columns.
d. Present appropriately proportioned structural details of beam and column.
Also draw the beam to column joint detail at detail X as shown in fig. 01.
Take fc = 3 ksi and fy = 40 ksi.
101
Design Example 3 (SMRF)
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Given Building:
Figure 01: RC Building Frame
3.2 in2
2.4 in2
1.2 in22.6 in2 2.6 in2 2.4 in2
1.2 in21.8 in23.0 in2 3.0 in2
Detail X
3.2 in2 3.2 in2 3.2 in2
F G
E H
B CA D
J K
1.44 in2 1.44 in2
1.0 in21.2 in2 1.2 in2
10 ft ln =15 ft 10 ft
10 ft
10 ft
1.2 in2 1.2 in2 1.0 in21.0 in2 1.0 in2 1.0 in2
102
Design Example 3 (SMRF)
12/20/2014
52
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution of Part (a)
As given in problem, # of bars using #5 bars are as below:
2.6 in2 2.6 in2
1.8 in23.0 in2 3.0 in2
3.2 in2 3.2 in2
F G
E H
B CA D
J K
10 ft 15 ft 10 ft
1.2 in2 1.2 in2
# of bars = As/Ab
Negative reinforcement at joint:
2.6/0.31= 8.38 (take 9 bars in 2 layers)
3.0/0.31= 9.67 (take 10 bars in 2 layers)
Take 10 bars at joint for beam FG.
Positive bars (mid span):
1.8/0.31 = 5.80 (take 6 bars in 2 layers)
Positive bars (at joint):
1.2/0.31 = 3.87 (take 4 bars in 1 layer)
Column reinforcement:
3.2/ 0.31 = 10.32 (take 12 bars for even
distribution of bars at all faces of column)
103
Design Example 3 (SMRF)
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution of Part (a)
(4+2) #5
(5+5) #5 (5+5) #5
12 #5 12 #5
F G
E H
B CA D
J K
10 ft 15 ft 10 ft
4 #5 4 #5
104
Design Example 3 (SMRF)
12/20/2014
53
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution of Part (b)
As given in problem, Shear reinforcement spacing with #3 bar is:
0.23 in2/ft
F G
E H
B CA D
J K
10 ft 15 ft 10 ft
Spacing= (Ab/As) 12
With #3, 2 leg vertical stirrups (Ab = 0.22 in2)
Stirrup spacing for beams:
sb = (0.22/0.23) 12 = 11.47 c/c
As per ACI minimum reinforcement and maximum
spacing requirement, spacing should not exceed:
i. Avfy/50bw = 14 c/c
ii. d/2 = 16.5/2 = 8.25 c/c
iii. 24 c/c
iv. Avfy/{0.75(fc)bw = 17.85 c/c
Finally sb = 8.25 c/c
Tie spacing for column:
s = (0.22/0.23) 12 = 11.47 c/c
Spacing for tie bars according to ACI 7.10.5.1 is minimum of:16 dia of main bar =16 5/4 =10 c/c48 dia of tie bar = 48 (3/8) =18 c/cLeast column dimension =12 c/cFinally sc = 10 c/c
0.23 in2/ft
0.23 in2/ft
105
Design Example 3 (SMRF)
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution of Part (b)
As given in problem, Shear reinforcement spacing with #3 bar is:
F G
E H
B CA D
J K
10 ft 15 ft 10 ft
#3, 2 legged @ 8.25 c/c
#3, ties @ 10 c/c #3, ties @ 10 c/c
106
Design Example 3 (SMRF)
12/20/2014
54
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution of Part (c)
SMRF Requirements Checklist
Provisions for Beams
Sizes
ln/d = 15 12/15 = 15 > 4 (ACI 21.3.1.2 satisfied)
Width/ depth = 12/18 = 0.66 > 0.3 (ACI 21.3.1.3 satisfied)
Width = 12 > 10, O.K.
Therefore 12 wide and 18 beams are OK.
107
Design Example 3 (SMRF)
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution of Part (c): SMRF Requirements Checklist
Provisions for Beams
Flexural Reinforcement
Asl = (5+5) #5Asr = (5+5) #5
Asmid+ = (4+2) #5Asl+ = 4 #5 Asr+ = 4 #5
As (at all critical sections) Asmin
As Asmin = 4 #5 bars
As (at any section) Asmax
Asmax = 0.025bd = 16 #5 barsOK
As+ (at joints) As (at joints)
4 #5 bars {(5+5) #5 bars}
As (any section) Max. As at joints
Provide at least 3 bar
N.G
Provide at least 5 bars at joint.O.K
108
Design Example 3 (SMRF)
12/20/2014
55
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution of Part (c): SMRF Requirements Checklist
Provisions for Beams
Recommended Flexural Reinforcement
109
Asl = (5+5) #5 Asr = (5+5) #5
Asmid+ = (4+2) #5Asl+ = (4+2) #5 Asr+ = (4+2) #5
3 #5
Design Example 3 (SMRF)
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution of Part (c): SMRF Requirements Checklist
Provisions for Beams
Transverse Reinforcement
s
d/4 = 15/4 = 3.75
8 smallest long. bar dia.= 8 5/8= 5
24 hoop bar diameter = 24 3/8= 9
12 2
2h = 36s d/2 = 15/2 = 7.5
Column
2h = 36
110
Design Example 3 (SMRF)
12/20/2014
56
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution of Part (c): SMRF Requirements Checklist
Provisions for Beams
Lap Splice: If required then,
Not to be provided within joints. Not to be provided within 2h region from face of
the support.
Spacing of hoops within lap = least of d/4 or 4 c/c = 4 c/c
Lap splice length =1.3 ld = 1.30.05 (fy/ fc)db 30 = 2.5
50 db = 50 (5/8) = 31.25 2.5 for fc 3 and fy 40 ksi
2h=36 2h=36
111
Design Example 3 (SMRF)
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution of Part (c): SMRF Requirements Checklist
Provisions for Columns
Size: All columns are 12 square, which is equal to least required for
SMRF (i.e., 12).
Flexural Reinforcement: All columns are reinforced with 12 #5 bars
which gives g = 0.025, within the specified range 0.01 g 0.06.
112
Design Example 3 (SMRF)
12/20/2014
57
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution of Part (c): SMRF
Requirements Checklist
Provision for Columns
Transverse Reinforcement:
lo = max (larger column dimension,
hc/6, 18) = 18.5
Spacing of ties in lo region is least of =
smaller column dimension/4, 6 long
bar dia = 3
Spacing in the remaining region will be
least of 6 long bar dia or 6 = 3.75
hc = 9.25
lo
lo
12 12 column
12, #5 bars
G.L
113
Design Example 3 (SMRF)
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution of Part (c): SMRF
Requirements Checklist
Provisions for Columns
Lap Splice:
Tension lap splice within center
half of member length.
Spacing of ties in lap splice not
more than smaller of d/4 or 4
Lap length = 1.3 0.05 (fy/ fc )db=
30 2.5
And from 50db = 50(5/8) =
31.25
hc = 9.25
lo
lo
12 12 column
G.L
114
Design Example 3 (SMRF)
12/20/2014
58
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution of Part (c): SMRF Requirements Checklist
Provision for Joints
To prevent beam column joint cracking, ACI Code 21.5.1 requires that
the column dimension parallel to the beam reinforcement must be at
least 20 times the diameter of the largest longitudinal bar.
20 5/8 = 12.5
Column dimension parallel to beam long bar = 12, Almost OK.
115
Design Example 3 (SMRF)
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution of Part (c): SMRF Requirements Checklist
Provision for Joints
(5+5) #5 bars
(4+2) #5 bars
2
ColumnBeam
Joint
116
Design Example 3 (SMRF)
12/20/2014
59
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution of Part (d):
Presentation of appropriately proportioned structural details of
beam, column and selected joint.
In this part, structural drawings showing all calculated SMRF details
have been asked to draw. This has already been done in part (c) along
with each member (beam and column) SMRF checks.
However in the examination, it is better to draw all drawings here in part
(d) at the same place to avoid waste of time.
Part (d) is shown next.
117
Design Example 3 (SMRF)
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution of Part (d):
Structural Details for beam (Long section):
s = 3.75
2
2h = 36s = 7.5
Column
2h = 36
(5+5) #5
(5+5) #5
(4+2) #5(4+2) #5 (4+2) #5
Note: Lap splice is provided only if required.
A
A
B
B
118
3 #5
Design Example 3 (SMRF)
12/20/2014
60
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution of Part (d):
Structural Details for Beam (Cross sections):
12
18
(5+5) #5
(4+2) #5
Section A-A
12
18
3 #5
(4+2) #5
Section B-B
#3, 2 legged @ 3.75 c/c
#3, 2 legged @ 7.5 c/c
119
Design Example 3 (SMRF)
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution of Part (d):
Structural Details for Column:
lo = 18.5
12 12 column
12, #5 bars
G.L
lo = 18.5
#3 ties @ 3 c/c (throughout)
Lap length = 2.5
12 #5
#3ties @ 3 c/c
12
12
120
Design Example 3 (SMRF)
12/20/2014
61
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
Solution of Part (d):
Structural Details for Joints:
(5+5) #5 bars
(4+2) #5 bars
2
ColumnBeam
Joint
121
Design Example 3 (SMRF)
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
References
ACI 318
UBC-97
BCP SP-2007
Earthquake tips from IITK.
122
12/20/2014
62
Prof. Dr. Qaisar Ali Reinforced Concrete Design II
Department of Civil Engineering, University of Engineering and Technology Peshawar
The End
123