Ktps v Stg Boe-Vol-1boiler

Embed Size (px)

Citation preview

  • 8/13/2019 Ktps v Stg Boe-Vol-1boiler

    1/4

    VOLUME I (KTPS-V Stage) :

    UNIT OPERATING PROCEDURE

    Boile !e"#i$tio%:Natural circulation,

    Single drum,

    Radiant reheat,

    Balanced draft boiler with

    Tangential tilt type burners.

    Remote controlled HEA High Energy Arc! igniters, air cooled oil guns.

    "SSS # "urnace safeguard super$isory systemRAH # Regenerati$e Air Heater % & Nos.

    "' fans # & Nos A(ial reaction

    )A fans # & Nos A(ial reaction

    *' fans # & Nos Radial 'ouble Suction

    ES)s # + Nos.

    DO":

    A) Pe$aatio% o& lig'ti%g $:

    . -hec and remo$e any foreign material from boiler. Ensure all

    manholes and others should be closed.

    &. Remo$e any restriction obstructing the boiler e(pansion.

    /. Ensure "urnace hopper water sealing.

    +. Ensure a$ailability of compressed air, power, chemicals, cooling

    water etc.

    0. 1eep all $ents and drains as per the $al$e operating diagram.

    2. Burner tilt in hori3ontal position.4. Ensure 5il system and firing e6uipment is ready.

    7. Ensure all interlocs and protections.

    8. -hec up the wind bo( for proper damper positioning.

    9. -hec the functioning of all instruments.

    . 1eep all dampers in air : ;as side in start up condition.

    &. -hec the correct functioning of furnace probe.

  • 8/13/2019 Ktps v Stg Boe-Vol-1boiler

    2/4

    /. -hec all the e6uipments are properly lubricated and ept ready for

    start up.

    +. "ill the boiler up to normal le$el.

    0. -lose all de%super heating control $al$es.

    B) I%itial ii%g:

    . -hec that no boiler trip condition e(ists.

    &. Air flow is ust the au( air or total air flow.4. -hec for rotation of burners for uniform heating.

    7. -hec the e(pansion of furnace and record it.

    8. "iring rate should be with in limits.

    9. ?aintain the drum le$el nearer to normal.

    . -hec and control Boiler water, "eed water and steam conditions as

    per the recommended.

    &. "re6uent soot blowing of RAHs.

    /. )ut S-A)H Steam coiled air )re%heater! into ser$ice during fuel oil

    firing.

    C) No*al Loa!i%g:

    . *ncrease the boiler load as per start up cur$e.

    &. Start coal firing if sufficient ignition energy is a$ailable.

    /. )ut all automatics in ser$ice.

    +. -hec and record SH : RH metal temp.

    0. ?aintain windbo( pressures e6ual on all sides.

    2. Ensure the following#

    a! "lue gas analysisb! @uality of "eed water, Boiler water : Steam

    c! )ul$erised coal fineness.

    4. "re6uent soot blowing of RAHs to a$oid fire.

    7. 1eep S-A)H into ser$ice upto the recommended cold end temps are

    reached.

    &

  • 8/13/2019 Ktps v Stg Boe-Vol-1boiler

    3/4

    D) No*al Re!#tio% o& Loa!:

    . Reduce the load as per the recommendations.

    &. Ad>ust the 'ESH spray.

    /. Tae the controls into manual where e$er re6uired for better control.

    E) No*al "'t !o+% to #ol!:

    . Reduce the load gradually.

    &. ?aintain normal drum le$el.

    /. Enough purging after tripping the fuel.

    +. "ill drum to 09mm during bo(ing up.

    0. -hec and maintain drum le$el till it cools sufficiently.

    2. Run *' : "' fans : RAH till the inlet "; temp drops down to

    &999-.

    DON,T":

    A) I%itial ii%g:

    . 'o not continue firing if drum le$el is $ery low.

    &. "urnace 5C temp should not be more than 0+99- if there is no flow

    in RH./. 'o not light up or continue if RAH is not running.

    +. 'o not eep furnace probe inside the furnace if ".; temp e(ceeds

    0+99-.

    B) No*al Loa!i%g:

    . 'o not put mill into ser$ice until sufficient ignition energy is

    a$ailable.

    &. 'o not operate at higher )r. : Temp.

    /

  • 8/13/2019 Ktps v Stg Boe-Vol-1boiler

    4/4

    COLD START UP

    . Air flow is