2
UK T 020 7241 8787 | F 020 7241 8700 | [email protected] | www.elandcables.com International T +44 20 7241 8740 | F +44 20 7241 8700 | [email protected] Find this product online: elandcables.com | Cables & Accessories Profibus & Profinet Cable | KNX/EIB Cable technicalspecification | 1 of 2 ISSUE NO 01-03-2014 CABLE STANDARDS BS EN 50090, BS EN 50090-2-2, CEI-EN 60669-2-1, BS EN/IEC 60332-1, BS EN 50396 A8P KNX/EIB Cable Eland Product Group: The electrical and dimensional properties of this product are measured by the Technical and Quality Assurance department at the Eland Cables laboratory. Cable performance in respect of conductor resistance, construction quality (workmanship), dimensional consistency, and other parameters are verified to published standards and approved product drawings. Conformance to RoHS (Restriction of the use of Hazardous Substances) is determined and confirmed. CONSTRUCTION Conductor Solid, bare copper wire conductor Insulation LSZH (Low Smoke Zero Halogen) Tape Plastic foil Screen Aluminium/Polyester tape (Al/PET) Drain Wire Tinned copper wire Sheath LSZH (Low Smoke Zero Halogen) APPLICATION For use in bus systems (EIB - European Installaton Bus) and as ICA cable in power installations. Laying in/on plaster, even in moist and wet rooms. Not approved for power and underground installation. CHARACTERISTICS Test Rating 300V Test Voltage 4 kV Minimum Bending Radius Fixed: 7.5 x overall diameter Temperature Range Fixed: - 30°C to + 70°C Core Identification Red Black Yellow White Sheath Colour Green

KNX/EIB Cable - elandcables.com · BS EN 50090, BS EN 50090-2-2, CEI-EN 60669-2-1, BS EN/IEC 60332-1, BS EN 50396 A8P KNX/EIB Cable Eland Product Group:

  • Upload
    dothuy

  • View
    239

  • Download
    1

Embed Size (px)

Citation preview

Page 1: KNX/EIB Cable - elandcables.com · BS EN 50090, BS EN 50090-2-2, CEI-EN 60669-2-1, BS EN/IEC 60332-1, BS EN 50396 A8P KNX/EIB Cable Eland Product Group:

UK T 020 7241 8787 | F 020 7241 8700 | [email protected] | www.elandcables.comInternational T +44 20 7241 8740 | F +44 20 7241 8700 | [email protected]

Find this product online: elandcables.com | Cables & Accessories Profibus & Profinet Cable | KNX/EIB Cable

technicalspecification | 1 of 2

ISS

UE

NO

01-

03-2

014

CABLE STANDARDSBS EN 50090, BS EN 50090-2-2, CEI-EN 60669-2-1, BS EN/IEC 60332-1, BS EN 50396

A8P

KNX/EIB Cable

Eland Product Group:

The electrical and dimensional properties of this product are measured by the Technical and Quality Assurance department at the Eland Cables laboratory. Cable performance in respect of conductor resistance, construction quality (workmanship), dimensional consistency, and other parameters are verified to published standards and approved product drawings. Conformance to RoHS (Restriction of the use of Hazardous Substances) is determined and confirmed.

CONSTRUCTION Conductor Solid, bare copper wire conductor

Insulation LSZH (Low Smoke Zero Halogen)

TapePlastic foil

Screen Aluminium/Polyester tape (Al/PET)

Drain Wire Tinned copper wire

Sheath LSZH (Low Smoke Zero Halogen)

APPLICATION For use in bus systems (EIB - European Installaton Bus) and as ICA cable in power installations. Laying in/on plaster, even in moist and wet rooms. Not approved for power and underground

installation.

CHARACTERISTICSTest Rating 300V

Test Voltage 4 kV

Minimum Bending Radius Fixed: 7.5 x overall diameter

Temperature Range Fixed: - 30°C to + 70°C

Core Identification Red Black Yellow White

Sheath Colour Green

Page 2: KNX/EIB Cable - elandcables.com · BS EN 50090, BS EN 50090-2-2, CEI-EN 60669-2-1, BS EN/IEC 60332-1, BS EN 50396 A8P KNX/EIB Cable Eland Product Group:

UK T 020 7241 8787 | F 020 7241 8700 | [email protected] | www.elandcables.comInternational T +44 20 7241 8740 | F +44 20 7241 8700 | [email protected]

Find this product online: elandcables.com | Cables & AccessoriesProfibus & Profinet Cable | KNX/EIB Cable

ISS

UE

NO

01-

03-2

014

2 of 2 | technicalspecification

The information contained within this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is believed to be correct at the time of publication. When selecting cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.

DIMENSIONS

ELAND PART NO. NO. OF PAIRS DIAMETER OF CONDUCTOR

mm

NOMINAL OVERALL DIAMETER

mm

NOMINAL WEIGHTkg/km

A8P-KNX2PLSZH 2 Pair (Quad) 0.8 6.2 64

ELECTRICAL CHARACTERISTICS

MAXIMUM (CONDUCTOR) LOOP RESISTANCE

Ω/km

MINIMUM INSULATION RESISTANCE AT 20ºC

MΩ x km

MAXIMUM CAPACITANCE UNBALANCE C1

pF/100m

MAXIMUM MUTUAL CAPACITANCE

nF/km

73.2 100 200 100