Kendall Area Supply Presentation to NEPOOL Reliability Committee July 22, 2004

Kendall Area Supply

Embed Size (px)

DESCRIPTION

Kendall Area Supply. Presentation to NEPOOL Reliability Committee July 22, 2004. Kendall Area Load At Risk. Based on projected 2005 peak load conditions for Cambridge the following constraints exist: - PowerPoint PPT Presentation

Citation preview

Page 1: Kendall Area Supply

Kendall Area Supply

Presentation to NEPOOL Reliability Committee

July 22, 2004

Page 2: Kendall Area Supply

Kendall Area Load At Risk• Based on projected 2005 peak load conditions for

Cambridge the following constraints exist:– All lines in conditions require at least 25 MW of

generation to be running calling for two steam units to be dispatched

– N-1 conditions call for either dispatching a Jet or closing Mirant’s T43 115 kV tie

– N-1 + Generator out calls for both dispatching a Jet and closing Mirant’s T43 115 kV tie (see diagram)

• Conclusion is that two steam generating units as well as one jet generator are needed for system reliability until the new East Cambridge substation is in service

Page 3: Kendall Area Supply

Cambridge Supply Concernsw/ Somerville Xfm Out and Loss of One Steam Unit