2
Johnson Controls JMW-Series water-to-water heat pumps deliver premium efficiency from 3 to 70 tons. Water-to-water heat pumps can be used in a multitude of applications, including chilled water, potable hot water generation, radiant floor heating, industrial process control, snow/ice melt, and many other types of comfort HVAC or industrial applications. Units 10 tons and larger utilize 2 compressors. Multiple JMW units can be utilized in a system to provide simultaneous heating/cooling capabilities, lead/lag operation, and increased system redundacy. JMW-Series units can provide efficiencies up to 16 EER (boiler/tower). Johnson Controls JMW-Series Hydronic Water Source Heat Pump Models JMW – 3-70 Tons – 16 EER Unit Size Model W D H 036-060 in. cm 25.4 (64.5) 30.6 (77.8) 33.0 (83.8) 120 in. cm 52.9 (134.4) 30.6 (77.8) 37.0 (94.0) 170-340 in. cm 26.3 (66.9) 45.1 (114.6) 64.5 (163.8) 360-840 in. cm 34.0 (86.4) 55.5 (141.0) 65.1 (165.4) Advantages of the JMW-Series: Exceeds ASHRAE 90.1 efficiencies. Copeland scroll compressor(s). Dual independent refrigeration circuits on size 120, 340, 360, and 600. Coaxial heat exchanger (sizes 036-340). Brazed plate heat exchanger (sizes 360-840). Exclusive single side service access (front of unit) allows multiple units to be installed side-by-side for large capacity installations (360 through 840 require front and rear access). Top water connections on sizes 170, 340, 360, 600, and 840 staggered for ease of manifolding multiple units. Heavy gauge galvanized steel construction with polyester powder coat paint and stainless steel front access panels (036-340). Insulated compressor compartment. Small footprint. Load leaving temperature range from 25 to 140°F, -4.4 to 60°C (see submittal for specific model range). Source entering temperature range from 20 to 130°F, -6.7 to 54.4°C (see submittal for specific model range). Microprocessor controls for 036- 340. DDC controls for 360-840.

Johnson Controls JMW-Series Hydronic Water Source Heat Pump

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Johnson Controls JMW-Series Hydronic Water Source Heat Pump

Johnson Controls JMW-Series water-to-water heat pumps deliver premium efficiency from 3 to 70 tons. Water-to-water heat pumps can be used in a multitude of applications, including chilled water, potable hot water generation, radiant floor heating, industrial process control, snow/ice melt, and many other types of comfort HVAC or industrial applications. Units 10 tons and larger utilize 2 compressors. Multiple JMW units can be utilized in a system to provide simultaneous heating/cooling capabilities, lead/lag operation, and increased system redundacy. JMW-Series units can provide efficiencies up to 16 EER (boiler/tower).

Johnson Controls JMW-Series Hydronic Water Source Heat PumpModels JMW – 3-70 Tons – 16 EER

Unit Size

Model W D H

036-060in.cm

25.4 (64.5)

30.6 (77.8)

33.0 (83.8)

120in.cm

52.9 (134.4)

30.6 (77.8)

37.0 (94.0)

170-340in.cm

26.3 (66.9)

45.1 (114.6)

64.5 (163.8)

360-840in.cm

34.0 (86.4)

55.5 (141.0)

65.1 (165.4)

Advantages of the JMW-Series:

• Exceeds ASHRAE 90.1 efficiencies.

• Copeland scroll compressor(s).

• Dual independent refrigeration circuits on size 120, 340, 360, and 600.

• Coaxial heat exchanger (sizes 036-340). Brazed plate heat exchanger (sizes 360-840).

• Exclusive single side service access (front of unit) allows multiple units to be installed side-by-side for large capacity installations (360 through 840 require front and rear access).

• Top water connections on sizes 170, 340, 360, 600, and 840 staggered for ease of manifolding multiple units.

• Heavy gauge galvanized steel construction with polyester powder coat paint and stainless steel front access panels (036-340).

• Insulated compressor compartment.

• Small footprint.

• Load leaving temperature range from 25 to 140°F, -4.4 to 60°C (see submittal for specific model range).

• Source entering temperature range from 20 to 130°F, -6.7 to 54.4°C (see submittal for specific model range).

• Microprocessor controls for 036-340. DDC controls for 360-840.

Page 2: Johnson Controls JMW-Series Hydronic Water Source Heat Pump

Model Refrigerant

Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump

Cooling Heating Cooling Heating Cooling Heating

Indoor 53.6°F [12°C]Outdoor 86°F [30°C]

Indoor 104°F [40°C]Outdoor 68°F [20°C]

Indoor 53.6°F [12°C]Outdoor 59°F [15°C]

Indoor 104°F [40°C]Outdoor 50°F [10°C]

Indoor 53.6°F [12°C]Outdoor 77°F [25°C]

Indoor 104°F [40°C]Outdoor 32°F [0°C]

Capacity Btuh

EER Btuh/W

Capacity Btuh

COPCapacity

Btuh EER

Btuh/WCapacity

Btuh COP

Capacity Btuh

EER Btuh/W

Capacity Btuh

COP

JMW-036 HFC-410A32,300 [9.47]

14.60 [4.28]

43,100 [12.64]

4.9036,200 [10.62]

23.10 [6.77]

35,300 [10.35]

4.0033,300 [9.77]

16.40 [4.81]

27,400 [8.04]

3.10

JMW-060 HFC-410A52,800 [15.48]

14.00 [4.10]

72,700 [21.32]

4.6056,600 [16.60]

20.30 [5.95]

60,300 [17.68]

3.8055,600 [16.31]

15.10 [4.43]

48,500 [14.22]

2.90

JMW-120 HFC-410A105,600 [30.97]

13.80 [4.04]

145,400 [42.64]

4.50113,200 [33.20]

20.10 [5.89]

120,600 [35.37]

3.70111,200 [32.61]

15.00 [4.40]

97,000 [28.45]

2.90

JMW-170 HFC-410A123,500 [36.22]

13.30 [3.90]

164,600 [48.27]

4.30138,400 [40.59]

19.30 [5.66]

136,200 [39.94]

3.70130,300 [38.21]

15.30 [4.49]

108,600 [31.85]

2.90

JMW-340 HFC-410A253,500 [74.34]

13.60 [3.99]

336,000 [98.53]

4.40282,000 [82.70]

19.60 [5.75]

277,000 [81.23]

3.70266,600 [78.18]

15.60 [4.57]

220,000 [64.52]

3.00

JMW-360 HFC-410A380,300 [111.46]

16.00 [4.70]

531,000 [155.63]

5.10438,000 [128.37]

24.20 [7.10]

416,000 [121.92]

4.20399,600 [117.12]

18.40 [5.39]

316,000 [92.61]

3.40

JMW-600 HFC-410A619,800 [181.65]

16.00 [4.70]

873,000 [255.86]

5.20707,400 [207.33]

23.20 [6.80]

680,000 [199.30]

4.30649,600 [190.39]

18.20 [5.33]

517,000 [151.52]

3.40

JMW-840 HFC-410A814,800 [238.80]

16.20 [4.75]

1,141,000 [334.41]

5.30925,700 [271.31]

23.30 [6.83}

894,000 [262.02]

4.40852,600 [249.88]

18.40 [5.39]

677,000 [198.42]

3.40

Physical Data

Tested To ASHRAE/AHRI/ISO 13256-1 English (I-P) Units

JMW-Series JMW036 JMW060 JMW120 JMW170 JMW340

Compressor (1 qty) Scroll (1) Scroll (2) Scroll (1) Scroll (2)

Factory Charge HFC-410A (lbs) [kg] per circuit 4.5 [2.04] 5.5 [2.49] 5.5 [2.49] 14.9 [6.8] 14.9 [6.8]

Commercial FPT (in) Load/Source ¾ 1 1½ 2

HWG Water In/Out FPT (in) ½ N/A

Weight - Operating (lbs) [kg] 348 [158] 360 [163] 726 [329] 790 [358] 1330 [604]

Weight - Packaged (lbs) [kg] 373 [169] 385 [175] 770 [349] 800 [363] 1340 [608]

Water Volume (Source)

Gallons (Liters) 0.96 (3.64) 1.33 (5.04) 2.65 (10.02) 3.50 (13.27) 6.72 (25.44)

JMWL-Series JMW360 JMW600 JMW840

Compressor (1 qty) Scroll (2)

Compressor Oil TypeAll

POEREVB, C

PVEAllPVE

Factory Charge HFC-410A (lbs) [kg] per circuit 15 [6.8] 27.5 [12.5] 33.8 [15.4]

Indoor / Load Water connection sizes FPT (in) 2 2-1/2

Outdoor / Source Water connection sizes FPT (in) 2 2-1/2

Weight - Operating (lbs) [kg] 1400 [635] 2055 [932] 2305 [1042]

Weight - Shipping (lbs) [kg] 1325 [601] 1925 [873] 2175 [983]

Water Volume (Source)

Gallons (Liters) 4.7 [17.8] 8.3 [31.4] 9.5 [36]

Water Volume (Load)

Gallons (Liters) 4.4 [16.7] 7.3 [27.6] 8.5 [32.2]

All ratings based upon operation at the lower voltage of dual voltage rated models.Indoor = Load side heat exchanger; Outdoor = Source side heat exchanger.

Johnson Controls works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact Johnson Controls for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely Johnson Controls’ opinion or commendation of its products. The latest version of this document is available at www.johnsoncontrols.com.

100 JCI WayYork, PA 17406www.johnsoncontrols.com

© 2020 Johnson Controls. All rights reserved. LC1030. Rev. : 5-14-20

Dual isolated compressor mounting. Balanced port expansion valve (TXV). Compressor on (green) and fault (red) light.