13

JNCC DOMSTIC Catalouge

Embed Size (px)

DESCRIPTION

Technical Data

Citation preview

Page 1: JNCC DOMSTIC Catalouge
Page 2: JNCC DOMSTIC Catalouge

INTRODUCTION

The Domestic Cables & wiring catalogue contains all indoor cables, and copper conductors insulated with PVC material. These cables include regular wires and cables, fire retardant cables (FR), low smoke fumes cables (LSF), halogen free cables and flexible cables with sizes ranging from �.5 mm2 up to 630 mm2.

Single core cables, solid, stranded or flexible circular copper conductors as per BS 6004 standard are used for installation in surface mounted or embedded conduits, or similar closed systems. These cables are suitable for use in channels with cover, fixed protection installation or on lighting fittings and inside appliances, switchgear and control gear.

PVC insulated cord (NYZ) as per VDE 028� standard are used in dry rooms for fixed installation where particular flexibility is required. They can be laid in conduits over or under the walls as well as steel support brackets. These are used for light portable appliances such as lamps, TVs sets and table fans.

Flat-Twin and Flat-Three core cable as per BS 6004 standard are used for indoor fixed installations in dry locations, laid over walls, surface clipped or embedded in plaster, or over support brackets in domestic, commercial and industrial applications.

Indoor Multi core flexible cables as per BS 6500 standard are used in domestic premises, kitchens, offices, and household appliances, including damp situation. They are suitable for connecting washing machines, spin extractors, refrigerators, portable lamps, fans, vacuum cleaners, TV and household heating and ventilating apparatus, where the cord can not be in touch with surface temperature exceeding 85oC.

THHN/THWN AWG wires are widely used in new constructions. These wires are suitable for lighting and power purposes in industrial, commercial and residential buildings. Type THHN/THWN wires are designed to operate at conductor temperatures of 75oC for 600 volts service in wet and dry locations.Type THHN/THWN wires are also suitable for control circuits, machine tools and appliances. The Nylon jacket provides mechanical ruggedness and resistance to Acids, Alkalis, Oils, Gasoline and Chemicals.

Page 3: JNCC DOMSTIC Catalouge

2

JORDAN NEW CABLE COMPANY DOMESTIC CABLES

450 / 750 Volts - Copper Conductor PVC Insulated

Cu/PVC - SOLID CONDUCTOR IEC 60227 & BS 6004

Harmonized Code Designation: H07V-U

Code No.

Nominal Area

Construction Insulation Thickness

Approx. Overall Diameter

Approx. Cable Weight

Standard Length

Sq. mm No. / mm mm mm Kg/Km (Mt)

B32-0��0600�-�00xx-2 �.0 � / �.�3 0.60 2.3 �4 9�.4 C

B32-0��0700�-�00xx-2 �.5 � / �.38 0.70 2.8 2� 9�.4 C

B32-0��0900�-�00xx-2 2.5 � / �.78 0.80 3.4 33 9�.4 C

B32-0����00�-�00xx-2 4 � / 2.25 0.80 3.9 48 9�.4 C

B32-0���200�-�00xx-2 6 � / 2.76 0.80 4.4 68 9�.4 C

B32-0���300�-�00xx-2 �0 � / 3.57 �.00 5.6 ��3 9�.4 C

Color Black Blue Brown Green/Yellow Gray Green

xx Color Code BK BL BR GY GR GN

Color Orange Pink Red Red/Yellow Turqos Violet

xx Color Code OR PK RD RY TR VL

Color White Yellow

xx Color Code WT YL

C : Coil

Application:

Construction:

used for installation in surface mounted or embedded conduits or similar closed systems; it is suitable for use in channels with cover, as well as it is suitable for fixed protected installation in or on light fittings and inside appliances, switchgear and control gear, for voltages up to �000V a.c. or up to 750 V to earth d.c.

Plain annealed copper conductor class � as per BS 6360, or IEC 60228 PVC insulation type TI� colored as per BS 6746.

Page 4: JNCC DOMSTIC Catalouge

3

Application:

Construction:

used for installation in surface mounted or embedded conduits or similar closed systems; it is suitable for use in channels with cover, as well as it is suitable for fixed protected installation in or on light fittings and inside appliances, switchgear and control gear, for voltages up to �000V a.c. or up to 750 V to earth d.c.

Plain annealed copper conductor class 2 as per BS 6360, or IEC 60228 PVC insulation type TI� colored as per BS 6746.

JORDAN NEW CABLE COMPANY DOMESTIC WIRING 450 / 750 Volts - Copper Conductor PVC Insulated

CU/PVC - STRANDED CONDUCTOR IEC 60227 & BS 6004

Harmonized Code Designation: H07V-R

Code No.Nominal

AreaConstruction

Nominal Insulation Thickness

Approx. Overall

Diameter

Approx. Cable Weight

Standard Length

Sq. mm No. / mm mm mm Kg/Km (Mt)B32-0��06002-�00xx-2 �.0 7 / 0.44 0.60 2.5 �4.5 9�.4 CB32-0��07002-�00xx-2 �.5 7 / 0.53 0.70 3.0 2�.3 9�.4 CB32-0��09002-�00xx-2 2.5 7 / 0.67 0.80 3.6 33.0 9�.4 CB32-0����002-�00xx-2 4 7 / 0.85 0.80 4.2 48.5 9�.4 CB32-0���2002-�00xx-2 6 7 / �.04 0.80 4.7 67.7 9�.4 CB32-0���3002-�00xx-2 �0 7 / �.34 �.00 6.0 ��3 9�.4 CB32-0���4002-�00xx-2 �6 7 / �.68 �.00 7.� �66 9�.4 CB32-0���5003-�00xx-2 25 7 / 2.25 �.20 8.3 260 9�.4 CB32-0���6003-�00xx-2 35 7 / 2.65 �.20 9.4 356 9�.4 CB32-0���7003-�00xx-J 50 7 / 3.00 �.40 �0.9 484 �000 DB32-0���8003-�00xx-J 70 �9 / 2.25 �.40 �2.5 676 �000 DB32-0���9003-�00xx-J 95 �9 / 2.65 �.60 �4.8 943 �000 DB32-0��20003-�00xx-J �20 37 / 2.�3 �.60 �6.� ��6� �000 DB32-0��2�003-�00xx-J �50 37 / 2.35 �.80 �8.� �463 �000 DB32-0��22003-�00xx-J �85 37 / 2.65 2.00 20.0 �8�2 �000 DB32-0��23003-�00xx-J 240 37 / 3.00 2.20 22.8 2365 �000 DB32-0��24003-�00xx-J 300 37 / 3.35 2.40 25.3 2955 �000 DB32-0��25003-�00xx-J 400 6� / 2.96 2.60 28.6 3766 500 DB32-0��26003-�00xx-J 500 6� / 3.32 2.80 32.2 4777 500 DB32-0��27003-�00xx-J 630 6� / 3.75 2.80 35.4 6024 500 D

Color Black Blue Brown Green/Yellow Gray Greenxx Color Code BK BL BR GY GR GN

Color Orange Pink Red Red/Yellow Turquoise Violetxx Color Code OR PK RD RY TR VL

Color White Yellowxx Color Code WT YL

C : Coil / D : Drum

Page 5: JNCC DOMSTIC Catalouge

4

JORDAN NEW CABLE COMPANY DOMESTIC WIRING 450 / 750 Volts - Copper Conductor PVC Insulated

Cu/PVC - FLEXIBLE CONDUCTOR IEC 60227 & BS 6004

Harmonized Code Designation: H07V-K

Code No.Nominal

Area *** Construction

Insulation Thickness

Approx. Overall

Diameter

Approx. Cable

Weight

Standard Length

Sq. mm No. / mm mm mm Kg/Km (Mt)B22-0��05005-�00xx-2 0.75 22 / 0.20 0.60 2.3 ��.2 9�.4 CB22-0��06005-�00xx-2 �.0 29 / 0.20 0.60 2.4 �3.7 9�.4 CB32-0��07005-�00xx-2 �.5 30 / 0.24 0.70 2.9 20.3 9�.4 CB32-0��09005-�00xx-2 2.5 48 / 0.24 0.80 3.5 3�.6 9�.4 CB32-0����005-�00xx-2 4 78 / 0.24 0.80 4.0 47.0 9�.4 CB32-0���2005-�00xx-2 6 �20 / 0.24 0.80 4.6 66.9 9�.4 CB32-0���3005-�00xx-2 �0 �92 / 0.24 �.00 5.8 �08.� 9�.4 CB32-0���4005-�00xx-2 �6 3�2 / 0.24 �.00 6.9 �66 9�.4 CB32-0���5005-�00xx-2 25 �96 / 0.40 �.20 8.9 253 9�.4 CB32-0���6005-�00xx-2 35 276 / 0.40 �.20 �0.� 355 9�.4 CB32-0���7005-�00xx-J 50 396 / 0.40 �.40 �2.0 487 �000 DB32-0���8005-�00xx-J 70 360 / 0.50 �.40 �3.8 675 �000 DB32-0���9005-�00xx-J 95 475 / 0.50 �.60 �5.8 898 �000 DB32-0��20005-�00xx-J �20 592 / 0.50 �.60 �7.3 ���� �000 DB32-0��2�005-�00xx-J �50 756 / 0.50 * �.80 �9.5 �405 �000 DB32-0��22005-�00xx-J �85 925 / 0.50 * 200 2�.6 �789 �000 DB32-0��23005-�00xx-J 240 �22� / 0.50 * 2.20 24.6 23�5 �000 DB32-0��24005-�00xx-J 300 �525 / 0.50 * 2.40 ** 27.4 2927 �000 D

Used for installation in surface mounted or embedded conduits or similar closed systems; it is suitable for use in channels with cover, as well as it is suitable for fixed protected installation in or on light fittings and inside appliances, switchgear and control gear, for voltages up to �000V a.c. or up to 750 V to earth d.c.

Plain annealed copper conductor class 5 as per BS 6360, or IEC 60228 PVC insulation type TI� colored as per BS 6746.

Application:

Construction:

* Conceptual Construction** General as per BS 6004*** Extra Flexible Coductors can be manufactured using 0.24mm wire diameter

Color Black Blue Brown Green/Yellow Gray Greenxx Color Code BK BL BR GY GR GN

Color Orange Pink Red Red/Yellow Turquoise Violetxx Color Code OR PK RD RY TR VL

Color White Yellowxx Color Code WT YL

C : Coil / D : Drum

Page 6: JNCC DOMSTIC Catalouge

5

JORDAN NEW CABLE COMPANY DOMESTIC WIRING 300 / 300 Volts - PVC Insulated Flexible Cord

Cu/PVC - NYZ VDE 028�:�985

Code No.

Nominal Area

Construction Insulation Thickness

Approx. Overall Dimensions

Approx. Cable Weight

Standard Length

Sq. mm No. / mm mm mm Kg/Km (Mt)

B�5-02�0�005-�00WT-2 2 x 0.25 �4 / 0.�5 0.70 2.25 x 4.50 �4.2 9�.4 C

B�5-02�02005-�00WT-2 2 x 0.38 2� / 0.�5 0.80 2.40 x 4.80 �9.3 9�.4 C

B�5-02�04005-�00WT-2 2 x 0.50 �5 / 0.20 0.80 2.50 x 5.00 22.5 9�.4 C

B�5-02�05005-�00WT-2 2 x 0.75 22 / 0.20 0.80 2.70 x 5.40 27.7 9�.4 C

B�5-02�06005-�00WT-2 2 x �.00 29 / 0.20 0.80 2.84 x 5.70 3�.� 9�.4 C

Application:

Construction:

Used in dry room for fixed installation where particular flexibility is required. They can be laid in conduits over or under the walls as well as steel support brackets. These are used for light portable appliances such as lamps, TV sets and table fans.

Plain annealed copper conductor class 5 as per BS 6360, or IEC 60228The conductors shall be laid parallel and covered with PVC insulation type TI2 white colored as per BS 6746.The insulation shall be provided with a groove on each side between the conductors to facilitate separation of the cores.

C : Coil

Page 7: JNCC DOMSTIC Catalouge

6

Application:

Construction:

These cables are used for installation in surface mounted or embedded conduits, or similar closed systems.

Plain annealed copper conductor class � as per BS 6360, or IEC 60228 PVC insulation type TI� colored as per BS 6746.The insulated conductors shall be laid in parallel and covered with PVC sheath type TM� black colored as per BS 6746.The sheath shall be closely fitting but shall adhere to the cores, the sheath shall be provided with a groove on each side between the cores to facilitate separation of the cores.

Core Identification: Twin: Black & Blue Three-core: Black, Blue (Center) & Green.

JORDAN NEW CABLE COMPANY DOMESTIC WIRING 220 / 380 Volts - PVC Insulated PVC Sheathed

Cu/PVC/PVC - FLAT TWIN & THREE CORES (NYIFY) DIN VDE 0250:�99�

Code No.

Nominal Area

Construction Ins. Thick.Nominal Sheath Thick.

Approx. Overall

Dimensions

Approx. Cable

Weight

Standard Length

Sq. mm No. / mm mm mm mm Kg/Km (Mt)

B35-02�0700�-�0NBK-2 2 x �.5 � / �.38 0.40 0.80 3.8 x �0.8 63 9�.4 C

B35-02�0900�-�0NBK-2 2 x 2.5 � / �.78 0.50 0.90 4.6 x �2.4 96 9�.4 C

B35-02���00�-�0NBK-2 2 x 4.0 � / 2.25 0.60 0.90 5.3 x �3.9 �34 9�.4 C

B35-03�0700�-�0NBK-2 3 x �.5 � / �.38 0.40 0.80 3.8 x �7.� 95 9�.4 C

B35-03�0900�-�0NBK-2 3 x 2.5 � / �.78 0.50 0.90 4.6 x 22.3 �49 9�.4 C

B35-03���00�-�0NBK-2 3 x 4.0 � / 2.25 0.60 0.90 5.3 x 24.4 200 9�.4 C

C : Coil

Page 8: JNCC DOMSTIC Catalouge

7

JORDAN NEW CABLE COMPANY DOMESTIC CABLES300/500 Volts - PVC Insulated PVC sheathed Flat Cables

Cu/PVC/PVC - FLAT TWIN & FLAT THREE CORES BS 6004:2000

Code No.Nominal

AreaConstruction Ins. Thick.

Nominal Sheath Thick,

Approx. Overall

Dimensions

Approx. Cable

Weight

Standard Length

Sq. mm No. / mm mm mm mm Kg/Km (Mt)

T22-02�06002-�0NGR-2 2 x �.0 7 / 0.44 0.60 0.90 4.40 x 6.90 52 9�.4 C

T22-02�07002-�0NGR-2 2 x �.5 7 / 0.53 0.70 0.90 4.80 x 7.80 70 9�.4 C

T22-02�09002-�0NGR-2 2 x 2.5 7 / 0.67 0.80 �.00 5.60 x 9.20 �04 9�.4 C

T22-02���002-�0NGR-2 2 x 4.0 7 / 0.85 0.80 �.00 6.20 x �0.30 �38 9�.4 C

T22-02��2002-�0NGR-2 2 x 6.0 7 / �.04 0.80 �.�0 6.92 x ��.70 �89 9�.4 C

T22-02��3002-�0NGR-2 2 x �0 7 / �.34 �.00 �.20 8.42 x �4.50 300 9�.4 C

T22-03�06002-�0NGR-2 3 x �.0 7 / 0.44 0.60 0.90 4.32 x 9.40 75 9�.4 C

T22-03�07002-�0NGR-2 3 x �.5 7 / 0.53 0.70 0.90 4.80 x �0.80 �02 9�.4 C

T22-03�09002-�0NGR-2 3 x 2.5 7 / 0.67 0.80 �.00 5.60 x �2.80 �52 9�.4 C

T22-03���002-�0NGR-2 3 x 4.0 7 / 0.85 0.80 �.�0 6.40 x �4.70 �95 9�.4 C

T22-03��2002-�0NGR-2 3 x 6.0 7 / �.04 0.80 �.�0 6.92 x �6.40 257 9�.4 C

Application:

Construction:

For Fixed Installation in dry or damp premises; suitable for installation in walls, on boards and in channels or embedded in plaster.

Plain annealed copper conductor class 2 colored as per BS 6360, or IEC 60228 PVC insulation type TI� colored as per BS 6746.PVC sheath type 6 grey colored as per BS 6746. The sheath shall be closely fitting but shall not adhere to the cores and in the case of twin and three-core, the cores shall be laid parallel.

Core Identification: Twin: Red & Black.Three-core: Red, Yellow (Center) & Blue.

C : Coil

Page 9: JNCC DOMSTIC Catalouge

8

JORDAN NEW CABLE COMPANY DOMESTIC CABLES300/300 Volts - PVC Insulated PVC Sheathed Flexible Cables

Cu/PVC/PVC - Light Flexible Cables BS 6500:2000

Harmonized Code Designations:H03VVH2-F - Parallel Cords

H03VV-F - Circular Cords

Code No.Nominal

AreaConstruction Ins. Thick.

Nominal Sheath Thick.

Approx. Overall

Diameter

Approx. Cable

Weight

Standard Length

Sq. mm No. / mm mm mm mm Kg/Km (Mt)

F�2-02�04005-�0NWT-2 2 x 0.50 �5 / 0.20 0.50 0.60 5.0 47 9�.4 C

F�2-02�05005-�0NWT-2 2 x 0.75 22 / 0.20 0.50 0.60 5.4 55 9�.4 C

F�2-03�04005-�0NWT-2 3 x 0.50 �5 / 0.20 0.50 0.60 5.3 55 9�.4 C

F�2-03�05005-�0NWT-2 3 x 0.75 22 / 0.20 0.50 0.60 5.7 65 9�.4 C

F�2-04�04005-�0NWT-2 4 x 0.50 �5 / 0.20 0.50 0.60 5.8 68 9�.4 C

F�2-04�05005-�0NWT-2 4 x 0.75 22 / 0.20 0.50 0.60 6.3 8� 9�.4 C

Application:

Construction:

These cords are used in domestic premises, kitchens, offices, for household appliances, including damp situation. They are suitable for connecting washing machines, spin extractor, refrigerators, portable lamps, fans, vacuum cleaners, TV and household heating and ventilating apparatus, where the cord can not be in touch with a surface temperature exceeding 85ºC.

Plain annealed copper conductor class 5 as per BS 6360, or IEC 60228PVC insulation type TI2 colored as per BS 6746.PVC sheath TM2 white colored as per BS 6746.The sheath shall be closely fitting but shall not adhere to the cores

Core Identification: Two-core: Blue & BrownThree-core: Green/Yellow, Blue,& Brown.Four-core: Green/Yellow, Blue, Brown, & Black.

C : Coil

Page 10: JNCC DOMSTIC Catalouge

9

JORDAN NEW CABLE COMPANY DOMESTIC CABLES300/500 Volts - PVC Insulated PVC sheathed Flexible Cables

Cu/PVC/PVC - Ordinary Flexible Cables BS 6500:2000

Harmonized Code Designations: H05VVH2-F - Parallel Cords

H05VV-F - Circular Cords

Code No.Nominal

AreaConstruction Ins. Thick.

Nominal Sheath Thick.

Approx. Overall

Diameter

Approx. Cable

Weight

Standard Length

Sq. mm No. / mm mm mm mm Kg/Km (Mt)F22-02�06005-�0NWT-2 2 x �.0 29 / 0.20 0.60 0.80 6.5 63 9�.4 CF22-02�07005-�0NWT-2 2 x �.5 30 / 0.24 0.70 0.80 7.5 86 9�.4 CF22-02�09005-�0NWT-2 2 x 2.5 48 / 0.24 0.80 �.00 9.� �3� 9�.4 CF22-02���005-�0NWT-2 2 x 4.0* 78 / 0.24 0.80 �.20 �0.5 �86 9�.4 CF22-02��2005-�0NWT-2 2 x 6.0* �20 / 0.24 0.80 �.20 ��.7 244 9�.4 CF22-03�06005-�0NWT-2 3 x �.0 29 / 0.20 0.60 0.80 6.9 76 9�.4 CF22-03�07005-�0NWT-2 3 x �.5 30 / 0.24 0.70 0.90 8.� �08 9�.4 CF22-03�09005-�0NWT-2 3 x 2.5 48 / 0.24 0.80 �.00 9.6 �59 9�.4 CF22-03���005-�0NWT-2 3 x 4.0* 78 / 0.24 0.80 �.20 ��.2 230 9�.4 CF22-03��2005-�0NWT-2 3 x 6.0* �20 / 0.24 0.80 �.40 �2.8 3�8 9�.4 CF22-04�06005-�0NWT-2 4 x �.0 29 / 0.20 0.60 0.90 7.7 94 9�.4 CF22-04�07005-�0NWT-2 4 x �.5 30 / 0.24 0.70 �.00 9.� �38 9�.4 CF22-04�09005-�0NWT-2 4 x 2.5 48 / 0.24 0.80 �.�0 �0.8 203 9�.4 CF22-04���005-�0NWT-2 4 x 4.0* 78 / 0.24 0.80 �.40 �2.6 297 9�.4 CF22-04��2005-�0NWT-2 4 x 6.0* �20 / 0.24 0.80 �.40 �4.� 397 9�.4 C

*Generally as per BS 6500:2000

Application:

Construction:

These cords are used in domestic premises, kitchens, offices, for household appliances, including damp situation. They are suitable for connecting washing machines, spin extractor, refrigerators, portable lamps, fans, vacuum cleaners, TV and household heating and ventilating apparatus, where the cord can not be in touch with a surface temperature exceeding 85ºC

Plain annealed copper conductor class 5 as per BS 6360, or IEC 60228PVC insulation type TI2 colored as per BS 6746.PVC sheath TM2 white colored as per BS 6746. The sheath shall be closely fitting but shall not adhere to the cores

Core Identification: Two-core: Blue & BrownThree-core: Green/Yellow, Blue, & Brown.Four-core: Green/Yellow, Blue, Brown, & Black.

C : Coil

Page 11: JNCC DOMSTIC Catalouge

�0

JORDAN NEW CABLE COMPANY DOMESTIC WIRING600 Volts - THHN / THWN AWG WIRES

Cu/PVC/NYLON UL-83, UL-�58�

Code No. AWGEquiv. Area

Conductor Cons.Ins.

Thick.

Nylon Jacket Thick.

Approx. Overall

Diameter

Approx. Cable

Weight

Standard Length

Sq. mm No. / mm mm mm mm Kg/Km (Mt.)

B64-0��96002-800xx-5 �8* 0.82 �6 / 0.254 0.38 0.�� 2.3 �2.0 �52.4 C (500ft)

B64-0��34002-800xx-5 �6* �.3� 26 / 0.254 0.38 0.�� 2.6 �7.0 �52.4 C (500ft)

B64-0��33002-800xx-5 �4 2.08 �3x0.404 + 6x0.296 0.38 0.�� 2.9 24.8 �52.4 C (500ft)

B64-0��32002-800xx-5 �2 3.3� �3x0.5�0 + 6x0.373 0.38 0.�� 3.4 37.4 �52.4 C (500ft)

B64-0��3�002-800xx-5 �0 5.26 �3x0.643 + 6x0.47� 0.5� 0.�� 4.2 59.3 �52.4 C (500ft)

B64-0��30002-800xx-5 8 8.37 �3x0.8�0 + 6x0.593 0.76 0.�3 5.5 96.8 �52.4 C (500ft)

* Listed as TFFN wires.

UL 83 Underwriters Laboratories, Thermoplastic Insulated Wires and Cables.UL �063 Underwriters Laboratories, Machine Tool Wires and Cables.UL �58� Underwriters Laboratories, Reference standard for Electrical wires, Cables and Flexible Cords.

Color Black Blue Color Red Red/Yellow

xx Color Code BK BL xx Color Code RD RY

Color Brown G/Y Color Turquoise Violet

xx Color Code BR GY xx Color Code TR VL

Color Gray Green Color White Yellow

xx Color Code GR GN xx Color Code WT YL

Color Orange Pink

xx Color Code OR PK

Standards:

C : Coil

Page 12: JNCC DOMSTIC Catalouge

��

APPLICATION:

Widely used in new constructions. Suitable for lighting and power purposes in industrial, commercial and residential buildings. THHN/THWN wires are designed to operate at conductor temperatures of 75ºC for 600 volts service in wet and dry locations. THHN/THWN wires are also suitable for control circuits, machine tools and appliances. Nylon jacket provides mechanical ruggedness and resistance to Acids, Alkalis, Oils, Gasoline and Chemicals.

CONSTRUCTION:

Conductor

Soft drawn annealed copper conductors, solid or �9 wires combination unilay for sizes �4, �2 and �0 AWG. Size 8 AWG available in stranded only.

Insulation

Extruded Polyvinyl Chloride (PVC) compound meets all the performance requirement as per UL83. UL rated VW� conductors. PVC insulation also meets the UL758 requirements for �05ºC appliance wiring material.

Jacket

Tough, smooth, heat and light stabilized, low moisture absorption nylon conforming to UL requirements for type THHN or THWN. This jacket offers a great degree of protection to the PVC insulation from abrasion and cut through which may be encountered in pulling wire through conduits. Nylon has long been recognized as one of the toughest jacketing materials used in wire and cable manufacturing.

FEATURES:

* Meets UL “VW-�” Flame Test requirements. * Wet or dry locations, rated 90oC dry, 75oC wet. * Resistance to gas and oil exposure, rated gasoline and oil resistance II as per UL83. * Versatile - can be used as follows: THHN - 90ºC dry building wires. THWN - 75ºC wet and dry building wires. * Pulls easier - tough, smooth nylon jacket over PVC insulation. * Small diameter - more conductors per conduit.

JORDAN NEW CABLE COMPANY DOMESTIC WIRING600 Volts - THHN / THWN AWG WIRES

Cu/PVC/NYLON UL-83, UL-�58�

Page 13: JNCC DOMSTIC Catalouge