Upload
ah-tiang
View
14
Download
0
Embed Size (px)
DESCRIPTION
JJ102 Electrical Technology
Citation preview
Prepared By:
Sheilani bt Shaari
Department of Electrical Engineering, PKB
Course Learning Outcome (CLO)
Department of Electrical Engineering PKB
Introduction
Transformer
Construction
Department of Electrical Engineering PKB
Construction
Operating Principle
Transformer Ratio
Types of Transformer
GENERAL OBJECTIVE
Understand the principles of transformer.
SPECIFIC OBJECTIVES
At the end of the unit you will be able to :
Department of Electrical Engineering PKB
At the end of the unit you will be able to :
1. Explain the operating principles of
transformer
2. Describe the relationship between primary
winding and secondary winding.
3. Name types of transformer.
4. Explain step up and step down transformer
A transformer is a device which uses the
phenomenon of mutual induction to
change the values of alternating voltages
and currents.
Department of Electrical Engineering PKB
One of the main advantages of alternating
current transmission and distribution
Department of Electrical Engineering PKB
an alternating voltage an alternating voltage
can be increased or
decreased by
transformers.
Basically the transformer :
LOSSES are generally LOW
EFFICIENCY is HIGH
Department of Electrical Engineering PKB
EFFICIENCY is HIGH
Have a LONG LIFE and VERY STABLE
Transformers have various range in size from:
the miniature units used in electronic applications
Department of Electrical Engineering PKB
the large power transformers used in power stations.
applications
A transformer consists of 2 windings
connected by a magnetic core.
1 winding is connected to a power supply and
the other to a load.
Department of Electrical Engineering PKB
the other to a load.
N1 N2AC supplyLoad
Flux
Secondary windingPrimary winding Core
Transformer ratio is the comparison between
primary and secondary elements
Flux produced by primary winding induces secondary winding via
corePrimary Winding
Department of Electrical Engineering PKB
Primary Turns, Np
Secondary Turns,
NsPrimary Voltage, Vp
Secondary Voltage,Vs
coreSecondary winding
Primary Winding
Conductors CUT the flux flux CUT the Conductors
Current Flow through Primary
Winding
Department of Electrical Engineering PKB
Secondary winding
Open Circuit
Produce Magnetic Flux
Apply AC Voltage (V1)at Primary winding
E1
Induce emf, E1
E2
Produce emf, E2
Current Flow through Secondary
Winding
The induced e.m.f., E in a coil of N turns is
given by
E = -N volts
dtd
Department of Electrical Engineering PKB
where
is the rate of change of flux.
dt
dtd
In the ideal transformer, losses are neglected
and a transformer is considered to be 100%
efficient.
the rate of change of flux is the same for
Department of Electrical Engineering PKB
the rate of change of flux is the same for
both primary and secondary
=
The induced e.m.f per turn is constant
1
1
2
2
Assuming no losses,
E1 = V1 and E2 = V2
V V
Department of Electrical Engineering PKB
=
=
1
1V 2
2V
2
1
VV
2
1N
The input powers = output power
V1I1 = V2I2
Department of Electrical Engineering PKB
Or the primary and secondary volt-amperes are equal.
Thus
=
2
1
VV
1
2
II
Combining equations gives
1N1V 2I
Department of Electrical Engineering PKB
= =
2
1N2
1
VV
1
2
II
Transformer ratio is the comparison
between primary and secondary
elements.
Department of Electrical Engineering PKB
elements.
Flux which is produced by primary
winding completely inducing to
secondary winding.
Therefore, e.m.f induced in all the
winding are similar for primary and
secondary winding.
Department of Electrical Engineering PKB
secondary winding.
==
/ windinge.m.f x Np / windinge.m.f x Ns
ndingprimary wiin induced e.m.f of Totalwindingsecondary in induced e.m.f of Total
sNNp
Constant K is known as transformer ratio:
K = s2s
VV
EE
NN
==
Department of Electrical Engineering PKB
Where
E2 = secondary e.m.f induced
E1 = primary e.m.f induced
Vs = secondary terminal voltage
Vp = primary terminal voltage
p1p VEN
If Ns < Np then K < 1
this is step-down transformer
If Ns > Np then K > 1
Department of Electrical Engineering PKB
Np(3000
)
Ns
(2000)
If Ns > Np then K > 1
this is step-up transformer
If Ns = Np then K = 1
this is coupling transformer
Np(100)
Ns
(2000)
Ns
(100)Np
(100)
The number of windings for the three transformers are
Np = 100, Ns = 2000
Np = 3000, Ns = 2000
Np = 100, Ns =100
Department of Electrical Engineering PKB
Np = 100, Ns =100
Calculate the value of K for each transformer then determine the type of transformer and draw the symbol of transformer to differentiate the number of windings
A transformer is to be used to provide
a 60 V output from a 240 V A.C supply.
If the secondary is wound with 500
turns. Calculate
Vs or V2 Vp or V1
Department of Electrical Engineering PKB
turns. Calculate
(a) the turns of ratio required and
(b) the number of primary turns
N2
A 2000/200V, 20kVA transformer has 66 turns
in the secondary. Calculate
(i) primary turns
(ii) primary and secondary full-load currents
Vp or V1 Vs or V2
N2N1
I1 & I2
P
Department of Electrical Engineering PKB
Neglect the losses.
There 2 types of single-phase double-wound
transformer construction
core type and shell type
Department of Electrical Engineering PKB
the winding surround considerable part of the core
the core surround is considerable portion of the winding.
Single phase core type transformer
consists of two windings and one
core
Core type provides better
Department of Electrical Engineering PKB
Core type provides better
insulation between the primary
and secondary because of its
inherent two winding.
The main application for a core
type transformer is to increase
voltage from a standard 240v
supply up to 415v, instead of using
three phase supply.
shell type consists of one
winding and two cores.
Shell types provide a higher
degree of mechanical
Department of Electrical Engineering PKB
degree of mechanical
protection to the winding
because it is surrounded by
core.
Shell type transformer is
used in transmission of
multiple high and low
voltages.
The advantages of each type are:
Core type is the most commonly
used method of construction, the
Department of Electrical Engineering PKB
used method of construction, the
smaller core means less weight and
expense.
Shell type is used for larger
transformer because they can be
made with a reduce height.
(Q1 Q7)
Department of Electrical Engineering PKB
(Q1 Q7)
Department of Electrical Engineering PKB
GENERAL OBJECTIVE
Understand the principles of auto transformer.
SPECIFIC OBJECTIVES
At the end of the unit you will be able to :
Department of Electrical Engineering PKB
At the end of the unit you will be able to :
1. Explain the operating principles of auto
transformer
2. Describe the differences between auto
transformer and application
3. Explain ideal transformer and its
relationship with power losses
Introduction
Auto Transformer
Losses
Department of Electrical Engineering PKB
Losses
Efficiency
+ m
Magnetic Flux, (Wb)flux has to change from +m
to -m in the half cycle
Department of Electrical Engineering PKB
Time,T (s)
- m
f
Average rate of change of flux
= 2 m =4 f m webers /second
f21
Department of Electrical Engineering PKB
Average e.m.f induced per turn is
E1/N1= 4 f m volts
A sinusoidal wave the r.m.s or
effective value is 1.11 times the
average value
Department of Electrical Engineering PKB
RMS value of e.m.f induced per turn
E1/N1= 1.11 4 f m
Hence r.m.s value of e.m.f induced for
primary:
E1 = 4.44 N1 f m volts
Department of Electrical Engineering PKB
E1 = 4.44 N1 f m volts
secondary:
E2 = 4.44 N2 f m volts
A 250 kVA, 1100 V / 400 V, 50 Hz
single-phase transformer has 80 turns
on a secondary. Calculate :
the primary and secondary currents.
P Vp or V1
N2
Vs or V2
I & I
Department of Electrical Engineering PKB
the primary and secondary currents.
the number of primary turns.
the maximum values of flux.
I1 & I2
N1
An ideal 25 kVA transformer has 500 turns on
the primary winding and 40 turns on the
secondary winding. The primary is connected
to 3000 V, 50 Hz supply. Calculate
PNp
Vp or V1
Ns
Department of Electrical Engineering PKB
i. primary and secondary currents on
full-load
ii. secondary e.m.f. and
iii. the maximum core flux
I1 & I2
V2
m
An autotransformer has only a single
winding which is tapped at some
point along the winding.
The primary and secondary windings
Department of Electrical Engineering PKB
The primary and secondary windings
are not electrically separate, hence
if an open-circuit occurs in the
secondary winding the full primary
voltage appears across the
secondary
Primary no. of turns
Primary Current
Secondary Current
Ai1
Secondary
Laminated Ferromagnetic Core
Department of Electrical Engineering PKB
of turns
Secondary no. of turns
B
C Load
N1
N2
i2
V1
V2
Primary Voltage
Secondary Voltage
Connected to the end of the end of
the winding
Department of Electrical Engineering PKB
IPIS
AC voltage is applied across a portion of the winding.
VP NP
IS - IP
NS VS
IS
VP NP
IS - IP
IP
NS VS230 V 230 V
115 V
115 V
LOWER voltage is produce across another portion of the same winding for STEP DOWN
HIGHER voltage is produce across another portion of the same winding for STEP UP
Auto Transformer ratio (n) is the ratio of the smaller voltage to the larger voltage
(Neglecting the losses, the leakage reactance and the magnetizing current)
n = = = V I N
Department of Electrical Engineering PKB
n = = =
The nearer the ratio of transformation to unity, the greater the economy of conductor material.
1
2
VV
2
1
II
1
2
NN
For the same current density in the
windings and the same peak values
of the flux and flux density
the I2R loss in the auto transformer is
Department of Electrical Engineering PKB
the I2R loss in the auto transformer is
lower and
the efficiency higher than in the two
winding transformer.
Generally, an auto transformer
should not be used for
interconnecting high voltage and low
voltage systems.
Department of Electrical Engineering PKB
voltage systems.
The most important thing is the
common connection to the earth ,
otherwise there is a risk of serious
shock.
Mainly used for :
interconnecting systems that are
operating at roughly the same
Department of Electrical Engineering PKB
operating at roughly the same
voltage and
starting cage-type induction motors.
saving in a cost since less copper is
needed.
less volume, hence less weight.
Department of Electrical Engineering PKB
less volume, hence less weight.
higher efficiency, resulting from lower I2R
losses
continuously variable output voltage is
achievable if a sliding contact is used.
smaller percentage voltage regulation
There is a direct metallic connection
between the input and the output, where
the coupling in a double wound
transformer is magnetic only when giving
Department of Electrical Engineering PKB
transformer is magnetic only when giving
electrical isolation of the two winding.
In the event of an open circuit fault in the
common part of the winding, the input
voltage of a step down autotransformer
would appear on the output terminals.
An ideal transformer is one which
has no losses,
its winding have no ohmic resistance,
Department of Electrical Engineering PKB
its winding have no ohmic resistance,
no magnetic leakage and
no I2R and core losses.
An ideal transformer consists of two
purely inductive coils wound on the
loss free core.
2 cases consider for transformer
with losses but no magnetic leakage.
No Load
Department of Electrical Engineering PKB
is assumed as an ideal No Load
Loaded/ Full load
is assumed as an ideal transformer which there is no losses.
The losses only can occur in a loaded transformer. There are two types of losses :iron loss in the core and copper loss in the winding.
Copper losses
can result from power loss in the form of heating of the conductors.
Department of Electrical Engineering PKB
If R1 and R2 are the primary and secondary
winding resistances than
total copper loss =I12R1 + I2
2R2
Core losses
(i) Hysteresis loss
the heating of the core so the internal
molecular structure reversals which occur as
Department of Electrical Engineering PKB
molecular structure reversals which occur as
the magnetic flux alternates.
Core losses
(i) Hysteresis loss
The loss is proportional to the area of
the hysterisis loop and thus low loss nickel
Department of Electrical Engineering PKB
the hysterisis loop and thus low loss nickel
iron alloys are used for the core since
their hysteresis loop have small areas.
Core losses
(ii)Eddy current loss
the heating of the core due to emfs being
induced not only in the transformer windings
Department of Electrical Engineering PKB
induced not only in the transformer windings
but also in the core.
Core losses
(ii)Eddy current loss
These induced e.m.f.s set up circulating
currents called eddy currents. Owing to the low
Department of Electrical Engineering PKB
currents called eddy currents. Owing to the low
resistance of the core, eddy currents can be
quite considerable and can cause a large power
loss and excessive heating of the core.
total losses in transformer
= Pc + I 2R + I 2R
Department of Electrical Engineering PKB
= Pc + I12R1 + I22R2
total core loss
=powerinput poweroutput
lossespower input poweroutput
+
Department of Electrical Engineering PKB
=
powerinput lossespower input +
22
212
122
22
p.f.p.f.
RIRIPVIVI
c +++
=powerinput poweroutput
power input losses -powerinput
Department of Electrical Engineering PKB
=
= 1 -
powerinput power input
powerinput losses
The primary and secondary windings of a 500
kVA transformer have resistances of 0.42 and 0.0019 respectively. The primary and secondary voltages are 11 000
Department of Electrical Engineering PKB
The primary and secondary voltages are 11 000
V and 400 V respectively and the core loss is 2.9
kW, assuming the power factor of the load to be
0.8.
Calculate the efficiency on :
full load
half load
In a 50 kVA transformer, the iron loss
is 500 W and full-load copper loss is
800W. Find the efficiency at :
Department of Electrical Engineering PKB
1. full-load and
2. half-load
at 0.8 p.f. lagging.
Department of Electrical Engineering PKB
Transformer Drum
(Q8 Q18)
Department of Electrical Engineering PKB
(Q8 Q18)
Department of Electrical Engineering PKB
AC ELECTRICAL MECHINES