Upload
carlos-bellatin
View
215
Download
0
Embed Size (px)
Citation preview
8/13/2019 Jiang-Jian Wang - Research of Cascade Control With an Application to Central Air-conditioning System
1/6
Proceedings of Sixth International Conference on Machine Learning Cybernetics, Hong Kong, 19-22 August 2007
RESEARCH OF CASCADE CONTROL WITH AN APPLICATION TOCENTRAL AIR-CONDITIONING SYSTEM
JIANG-JIANG WANG, CHUN-FA ZHANG, YOU-YIN JING
School of Energy and Power Engineering, North China Electric Power University, Baoding 071003, ChinaE-MAIL: [email protected]
Abstract:
The heat exchanger and air-conditioning space in thecentral air-conditioning system are modeled in mathematic.
Based on the models, we propose a cascade control strategy
for temperature control of air-conditioning system. The
setpoint response controller in the cascade control system is
designed in terms of the robust control H2 optimal
performance specification. According to the system operation
requirement for disturbance rejection, a closed-loop for
rejecting disturbance signals is configured and the controller
in internal loop is figured out by proposing the desired
closed-loop complementary function. Finally, the three
controllers, the designed cascade control, traditional cascade
PID control and single PID control are simulated in central
air-conditioning system. It is found that the setpoint response,
the disturbance rejection, the robust and the performance of
the designed cascade control system are better.
Keywords:Cascade control; Robust; H2 optimal performance
specification; Air-conditioning system
1. Introduction
In the central air-conditioning systems, the function ofair handling units (AHU) is to transfer cooling load from airloop to chilled water loop by forcing airflow over the heatexchanger and into the space to the conditioned. Theperformance of AHU directly influences the performance of
air-conditioning system. Traditionally, AHU is controlledby single loop PID type controller [1] due to their relativelysimple structure. However, in cases where the environmentof process equipment must be controlled to extremely highspecifications, such as cleanrooms (in class one cleanrooms,tolerances of 0.50and 2% RH, respectively), it would bedesirable to integrated PID controllers into complex control
structures to achieve better performance.To obtain better performance, cascade control in
central air-conditioning system has been attracting interestin both academic and application areas. Cascade control has
the characteristics such as faster response and stronger
disturbance rejection and the cascade control is appropriate
to the air-conditioning system that has larger inertia andpure time delay as in [2]. A chip controller combined fuzzycontrol and cascade control is designed to apply centralair-conditioning system as in [3]. An online cascade controlstrategy is proposed and validated, which optimizes thesetpoints of head of secondary pump and chiller watertemperature in series based on the positions of air handling
unit (AHU) as in [4].A novel cascade control system has been implemented
to improve supply air temperature control performance ofAHU in a pilot HVAC system, whose outer loop is used aneural network in [5]. The multiplayer neural network is
trained online by a special training algorithm
simultaneous perturbation stochastic approximation (SPSA)based training algorithm.
Additionally the cascade control system is used to saveenergy. Some researchers used the cascade controlalgorithm to evaluate the data from the sensor network and
manipulate supply air temperature and flow rate fromindividual computer room air conditionings to ensurethermal management while reducing operational expense[6]. The constructed control system was tested in a smartdata center and results show 50% reduction energyconsumption by cooling resources in addition to
improvement in use of critical data center space.In this paper a cascade control system is designed
based on the central air-conditioning system. Finally, thethree controllers, the designed cascade control, traditionalcascade PID control and single PID control are simulated.
2. Math model of central air-conditioning system
The control of humidity and temperature in theair-conditioning space are concerned here. The considered
system has two main parts in a cascade structure, the firstpart is the air-processing unit (heating/cooling system) andthe second part is the air-conditioning room. These towparts are connected by air shaft. In the air processing unit
1-4244-0973-X/07/$25.00 2007 IEEE
498
Authorized licensed use limited to: Norges Teknisk-Naturvitenskapelige Universitet. Downloaded on December 4, 2009 at 08:32 from IEEE Xplore. Restrictions apply.
8/13/2019 Jiang-Jian Wang - Research of Cascade Control With an Application to Central Air-conditioning System
2/6
Proceedings of Sixth International Conference on Machine Learning Cybernetics, Hong Kong, 19-22 August 2007
recycled and injected air are mixed by means of a flapallowing to take into account the air flows with respect tothe speed. The mixed air is processed by the heat exchanger
and humidifier. The air processed is injected into theair-conditioning room by the means of a fan. Theair-conditioning system is shown in Figure 1.
Figure 1. Control theory of central air-conditioning system
Based on the law conservation of energy [7], the
transfer function of heat exchanger can be expressed:
111
1
( )
1
sKG s e
T s
=
+
(1)
where K1 is the coefficient of amplify, ( s /kg); T1 is
time constant, (s); 1 is the pure time delay of the
controlled object, (s).The thermal balance equation of air-conditioning space
is similar to the heat exchanger, which is shown in (4).
222
2
( )1
sKG s eT s
=
+
. (2)
whereK2is the amplify coefficient of room, ( s /kg); T 2
is time constant, (s); 2 is the pure time delay of the
controlled object, (s).
3. Control System Design
The controlled object has two segments that are oneorder inertia process with time delays so that the cascadecontrol system can be used to obtain better performance.
When the fresh air has disturbance, the internal loop canreject the disturbance and keep the supply air temperatureconstant. The cascade control system has some advantagesof disturbance rejection and stable output, but the tuning ofcontroller parameters is very difficult. There are some
researches to study simple controller design and tuning ruleof traditional cascade control system [8, 9 and 10].Here we designed the cascade control system for the
air-conditioning system, which is shown in Figure 2.G1andG2are respectively the controlled process of heat exchangerand air-conditioning room; G1m and G2m are respectivelyidentification models, C is the setpoint response controllerandFis the internal loop controller .
Figure 2. Cascade control system of air temperature in theair-conditioning space
3.1. Setpoint response controller
When identification models G1mand G2mare matchedwith the controlled process G1and G2, the transfer functionof setpoint response in the cascade control system can be
simplified the below form:
1 2( ) ( ) ( ) ( )
cH s C s G s G s= . (7)
The controller C is solved in terms of the robust
control H2 optimal performance specification min||e||
and here it satisfies the performance specification
min||W(s)(1-H(s))|| ,in which W(s)is the input function of
setpoint. To the central air-conditioning system, the step
signal is often used and W(s) is correspondingly equal to1/s.
22
22
The pure time segments in the controlled object can be
approximately replaced to (8) and (9) in n/norders all-passpade.
1 1
1
( )
( )
s nn
nn
Q se
Q s
= . (8)
2 2
2
( )
( )
s nn
nn
Q se
Q s
= . (9)
499
Authorized licensed use limited to: Norges Teknisk-Naturvitenskapelige Universitet. Downloaded on December 4, 2009 at 08:32 from IEEE Xplore. Restrictions apply.
8/13/2019 Jiang-Jian Wang - Research of Cascade Control With an Application to Central Air-conditioning System
3/6
Proceedings of Sixth International Conference on Machine Learning Cybernetics, Hong Kong, 19-22 August 2007
where,
0
(2 )! !( ) ( )
(2 )! !( )!
ni
nn j j
i
n i nQ s s
n i n i
=
=
. (10)
j=1,2; i=1,2,,n
Here the integer n is enough large, which makes thatthe error due to the approximation is quite less than theerror of identification model and actual process, so that the
controller C can be shoveled. Put (8) and (9) into theperformance specification and the below form can begotten:
2
2( )(1 ( ))cW s H s 2
1 2 1 2
1 2 1 2 2
( ) ( )1(1 )
( 1)( 1) ( ) ( )
nn nn
nn nn
K K Q s Q s
s T s T s Q s Q s
=
+ +
2
1 2 1 2
1 2 1 2 2
( ) ( ) ( ))
( ) ( ) ( 1)( 1)
nn nn
nn nn
Q s Q s K K C s
sQ s Q s s T s T s
=
+ +
(11)
Then using the orthogonal property of H2norms, (11)
can be transferred to the form as following:
2
2( )(1 ( ))
cW s H s
2
1 2 1 2
1 2 2
( 1)( 1) ( ))
( 1)( 1)
T s T s K K C s
s T s T s
+ + =
+ +
+
2
1 2 1 2
1 2 2
( ) ( ) ( ) ( )
( ) ( )
nn nn nn nn
nn nn
Q s Q s Q s Q s
sQ s Q s
(12)
The above equation is minimized and the first item in
the right should be equal to zero, thus the ideal controllercan be gotten and C is shown in (13)
1 2
1 2
( 1)( 1( )
T s T sC s
K K
+ +=
) (13)
However, it is non-regular and it is not to implementpsychically and so a low-pass filter is added in the
controller, which is shown as following:
2
1( )
( 1)c
c
J ss
=
+
(14)
So the regular controller C can be got as following:
1 2
2
1 2
( 1)( 1( )( 1)
c
T s T sC sK K s
+ +=
+
) (15)
where cis a control parameter.
cis needed to tuning in control system. Whencis
relatively little, the response of setpoint is quick, but theneeded energy of controller is relatively large. When
enlargingc,the response of setpoint will be slow, but the
needed energy of controller is relatively little. So both
should be considered to the tuning ofc. In practical
application, c can be initialized to (1+2) and then be
tuned monotonically on-line to obtain better control
performance.
3.2. Internal loop controller
As Figure.2 shows, the disturbance transfer function ofmiddle process is shown as following:
1
1
( )( )
1 ( ) ( )
ad
s
T G sH s
T F s G= =
+ s. (16)
Then the closed-loop complementary sensitivityfunction is obtained as following:
1
1
( ) ( )
( ) 1 ( ) (d
a
F s G sf
T s T F s G= = + )s . (17)
In the ideal condition, Td(s) should be as the form:
Td(s)=1se , which means that when the Ta disturbance
inputs to the middle process, the internal loop controller F
should detect the error of Ts after1 time delay. Then the
controller F outputs a reverse isoparametric signal to reject
the disturbance. Actually it is considered that the output ofcontroller is limited and the error is gradually offset. Herebased on the robust control H2 optimal performanceobjective, the actual desired closed-loop complementary
sensitivity function is designed as the following:
11
( )1
s
d
f
T s es
=
+
(18)
wheref is another control parameter.
TheF(s)can be solved from (17) and is shown in (19).
1
( ) 1( )
1 ( ) (
d
d
T sF s
T s G s=
). (19)
To carry out conveniently, (19) is transferred and F(s)can be is shown as following:
500
Authorized licensed use limited to: Norges Teknisk-Naturvitenskapelige Universitet. Downloaded on December 4, 2009 at 08:32 from IEEE Xplore. Restrictions apply.
8/13/2019 Jiang-Jian Wang - Research of Cascade Control With an Application to Central Air-conditioning System
4/6
Proceedings of Sixth International Conference on Machine Learning Cybernetics, Hong Kong, 19-22 August 2007
1
1 1
( )( )1 ( ) (
F sF sF s G s
=
). (20)
whereF1(s)can be expressed as following:
11
1 1
( ) ( 1)( )
( ) ( 1)
d
f
T s T sF s
G s K s
+= =
+
. (21)
So the configuration of observer F can be shown inFigure 3.
Figure 3. Configuration of observerF
fis needed for tuning in control system. Whenf is
relatively large, the robust of control system is relativelystrong, but at the meantime the disturbance rejection will be
weak. When lesseningf, robust of control system is
relatively weak, the disturbance rejection will be relatively
strong. So the robust and disturbance rejection should beboth considered to be the tuning off. In practical
application, f can be initialized near the time delay of
P1,1. If the process P1 has not pure time delay, f can
also be initialized near to the time constant of P1. Thenfis tuned automatically on-line to obtain better controlperformance.
4. Simulation
To certify the validation of the designed cascadecontrol system in central air-conditioning system, wechoose the summer work condition and compare thedesigned cascade control system to the traditional singleclosed-loop PID control and the traditional cascade control
PID control.The parameters of central air-conditioning system: the
volume of air-conditioning room is 10m long, 8m wide and
4.5m high, the air specific heat capacity is Ca=1.0 kJ/kg ,
the air density is 1.2 kg/m3, Based on the criterion in theheating, ventilation and air-conditioning field, the number
of taking a breath in air-conditioning room and thecalculation of the supply air is Ga=1.08kg/s, the heat
resistance of wall is 1/R=0.2kw/ and the temperature
error of supply cold-water and back-water to the heat
exchanger in summer is Twin-Twout=-5.At last the parameters of middle process, heat
exchanger, are calculated as following: K1= -19.35 s
/kg, T
1=30s [12] and1=3s due to the short distance. The
parameters of air-conditioning room are calculated as
following: K2=0.4 s /kg, T 2=338s and2=60s [13].
Additionally, the gains of disturbances, Ta and Qroom, are
k1= -0.05 kg/ s , k2=0.2 kw/and k3=0.93/kw.
The simulation includes the setpoint response anddisturbance rejection. First, the desired step compares thethree controllers and at 1500s the step of disturbance, Ta, is
-1 to compare the disturbance rejection. The simulation
includes four kinds of comparison and certifies thevalidation the designed cascade control system.
4.1. Simulation 1
The PID parameters are tuned in the robust PID tuningmethod [14]. The PID parameters of the traditional single
PID control are tuned as following: Kp=0.199, Ki= 0.0006and Kd= 7.063. In the traditional cascade control system,the parameters of the internal-loop PID controller are firstlytuned toKp=0.227,Ki=0.001 andKd=0.37, the internal-loopforms the closed-loop and the internal PID controller run inthe system and then the parameters of the outer-loop PID
controller are tuned toKp=4.343,Ki=0.012 andKd=138.7.The parameters of the designed cascade control is
initializedc=(1+2)=63 andf =1=3.
The comparison curves of three controllers are shownin Figure 4, where N PID, T PID and S PID respectively
denotes the designed cascade control system, the traditionalcascade PID control system and the single PID controlsystem.
Temperatu
re()
Time (s)
Figure 4. The simulation results of three controllers
It is seen that the setpoint response of the designedcontrol system has not overshoot while the others have bothovershoot and the cascade PID control responses quicker
501
Authorized licensed use limited to: Norges Teknisk-Naturvitenskapelige Universitet. Downloaded on December 4, 2009 at 08:32 from IEEE Xplore. Restrictions apply.
8/13/2019 Jiang-Jian Wang - Research of Cascade Control With an Application to Central Air-conditioning System
5/6
Proceedings of Sixth International Conference on Machine Learning Cybernetics, Hong Kong, 19-22 August 2007
than single PID control. Although the setpoint response ofthe designed cascade control system is slower than the PIDcontrol system, the governing time of designed control
system is shorter than the PID control system.Additionally it is also found that the disturbance
rejection of the designed control and the traditional cascadePID control are similar and is better than the single PIDcontrol system, but the adjusting time of the designedcontrol is relatively long.
4.2. Simulation 2
To certify the robust of three controllers, some control
process parameters are changed to simulate. In G1andG2the gain both increase 10% and becomes 21.3 s /kg
and 0.924 s /kg. The other parameters still keep
constant in simulation 1, which include controllers andprocess. The comparison curves of three controllers areshown in Figure.5. It is seen that the setpoint response andthe disturbance rejection are similar to the simulation 1.However, the overshoot of single PID control is bigger thanthe simulation 1. The simulation 2 can prove the robust of
the designed cascade control system.
Time (s)
Figure 5. The robust simulation results of three controllers
4.3. Simulation 3
To fasten the response of the designed cascade control
system, the parameters, candf , are only tuned to half
andc =(1+2)/2=32 andf =1/2=1.5. The other
controllers and the parameters in simulation 1 are kept
constant. The simulation results are shown in Figure 6.As Figure 6 shows, it is seen that the setpoint response
of the designed control system becomes quicker than theother controllers and the performance is better than thetraditional cascade PID control and single PID control.
From this point, it can be seen that the tuning of thedesigned cascade control is easier than the PID controls.
As long ascandf are monotonically tuned, the controlsystem can obtain better performance.
Temperature()
Time (s)
Figure 6. The simulation results of three controllers
4.4. Simulation 4
The identification models G1mandG2mare absolutelymatched with the process G1and G2in simulation 1, 2 and
3. The simulation 4 certifies the validation of the designedcascade control system when the identification models arenot matched with the process. In G1m and G2m the T1
decease 30% and becomes 21s and2also deceases 30% to
become 42s. The other parameters still keep constant. Thetuning method of the PID parameters in simulation 4 is the
same in simulation 1. Based on these parameters, theparameters of controllers are tuned.
The PID parameters of the traditional single PIDcontrol are tuned as following: Kp= 0.239, Ki= 0.0007 andKd= 6.214. The parameters of the internal-loop PIDcontroller are firstly tuned to Kp=0.185, Ki=0.011 and
Kd=0.278 and the parameters of the outer-loop PIDcontroller are tuned toKp=4.343,Ki= 0.015 andKd= 114.98.
Based on the identification models G1m and G2m, the
parameters of the designed cascade control is initializedc
=(1+2)=45 andf =1=3. The simulation results of
three controllers are shown in Figure 7.
Temperature()
Temperature()
Time (s)
Figure 7. The simulation results of three controllers
(identification model is not matched with the process)
502
Authorized licensed use limited to: Norges Teknisk-Naturvitenskapelige Universitet. Downloaded on December 4, 2009 at 08:32 from IEEE Xplore. Restrictions apply.
8/13/2019 Jiang-Jian Wang - Research of Cascade Control With an Application to Central Air-conditioning System
6/6
Proceedings of Sixth International Conference on Machine Learning Cybernetics, Hong Kong, 19-22 August 2007
It is seen that the overshoot of the setpoint response ofthe designed control system is less than the cascade PIDcontrol and single PID control. It is also found that the
disturbance rejection of the designed control and thetraditional cascade PID control are similar and is better thanthe single PID control system. Although the adjusting timeof the designed control is relatively longer, the parameter
c is tuned simply and the performance of system will be
better than PID control.
5. Conclusion
In this paper a designed cascade control system was
applied to central air-conditioning system. The designedcascade control system has only two tuned parameters, c
andf, which is less than the parameters of PID control
system. Additionally,c andf are easily tuned, which
dont effects each other. Through the three controllers weresimulated, it is found that the setpoint response and thedisturbance rejection of cascade control system are both
better than single PID control system. The governing timeof the designed cascade control system is shorter than thePID control system, although sometimes the setpointresponse of the designed cascade control system is slowerthan the PID control system. On the whole, the performanceof the designed cascade control system is better than the
traditional cascade PID control system and single PIDcontrol system.
Acknowledgements
The authors would like to acknowledge the financialand technical support of the school of Energy and PowerEngineering and the major lab of power station in NorthChina Electric Power University during the course of thisresearch.
References
[1] J.E. Seem, A new pattern recognition adaptivecontroller with application to HVAC systems,Automatica, vol. 34, no. 8, pp 969-982, August 1998.
[2] M. Yu and Z. Liu, Application and Development ofAutomatic Control in HVAC System, Energy
Conservation Technology, vol. 21, no. 118, pp13-15,19, February 2003.
[3] L. Tian and X. Liu, Temperature Fuzzy ControllerDesign for Central Air-conditioning Space,Application of Electronic Technique, no. 4, pp 40-41,April 2002.
[4] X. Xiao, X. Jin, P. Liu and Z. Du, Research onOptimal Control of Chilled Water Temperature andHead of Secondary Pump in VWV Systems, Fluid
Machinery, vol. 32, no. 5, pp 42-45, May 2004.[5] C. Guo S. Qing and W. Cai, Supply air temperature
control of AHU with a cascade control strategy and aSPSA based neural controller, Proceedings ofInternational Joint Conference on Neural Networks,pp 2243-2248, Montreal, Canada, July 31 August 4,
2005.[6] C E. Bash, C D. Patel and R K. Sharma, Dynamic
thermal management of air cooled data centers,Thermal and Thermomechanical Phenomena in
Electronics Systems, pp 445-452, 30 May-2 June2006.
[7] C. Li, W. Zhang and Y. Liang, The Decouplingcontrol of constant temperature and humidityair-conditioning system, Refrigeration andAir-conditioning, vol. 6, no. 4, pp 42-47, August 2006.
[8] K.K. Tan, T.H. Lee and R. Ferdous, Simultaneousonline automatic tuning of cascade control for open
loop stable processes, ISA Transactions, vol. 39, no.2, pp 233-242, February 2000.
[9] Y.H. Lee, S.W. Park and M.Y. Lee, PID controllertuning to obtain desired closed loop responses forcascade control systems, Industrial and Engineering
Chemistry Research, vol. 37, no. 5, pp 1859-1865,May 1998
[10] R. Lestage, A. Pomerleau and A. Desbiens, Improvedconstrained cascade control for parallel processes,Control Engineering Practice, vol. 7, no. 8, pp969-974, August 1999.
[11] T. Liu, W. Zhang and D. Gu, Decoupling controldesign for cascade processes with time delays,
Chinese Journal of Scientific Instrument, vol. 26, no. 8,pp 775-778,804, August 2005.
[12] D. An, J. Wang and C. Lou, Simulation research onapplication of single neuron adaptive control in highprecision air-conditioning system, Computer
Simulation, vol. 21, no. 2, pp 105-108,118, February2004.
[13] J. Shi, Theory and Application of Auto control ofRoom Temperature, Beijing: China ArchitectureIndustry Press, 1983.
[14] Q. Li, G. Zeng, X. Zhu and P. Sun, A comparativestudy of PID tuning methods, Techniques of
Automation and Application, vol. 24, no. 11, pp 28-31,November 2005.
503