ANSI/ASHRAE Standard 62.1
What’s new in ventilation?
Kelley Cramm
8/18/2019 January 2007 ASHRAE Meeting Ventilation
2/32
ANSI/ASHRAE Standard 62.1-2004Ventilation for Acceptable Indoor Air
Quality
8/18/2019 January 2007 ASHRAE Meeting Ventilation
3/32
8/18/2019 January 2007 ASHRAE Meeting Ventilation
4/32
Introduction to Standard 62.1
•Consensus standard
•First published in 1973
•Now on continuous maintenance
•Backed by years of research
•Initially prescribed ventilation rates only
•Introduced “IAQ” Procedure in 1981
•Specifies “Breathing Zone Ventilation Rates”
8/18/2019 January 2007 ASHRAE Meeting Ventilation
5/32
Introduction to Standard 62.1
•Applicable to new buildings and changes to
existing buildings
•Applies to all indoor or enclosed spaces
that people may occupy
•Also covers release of moisture inbathrooms, locker rooms, etc.
8/18/2019 January 2007 ASHRAE Meeting Ventilation
6/32
Does not address smoking
8/18/2019 January 2007 ASHRAE Meeting Ventilation
7/32
Includes Code Intended Language
• The standard has been incorporated in
one form or another in the model codes
8/18/2019 January 2007 ASHRAE Meeting Ventilation
8/32
2003 International Mechanical Code
8/18/2019 January 2007 ASHRAE Meeting Ventilation
9/32
IMC, UMC, OR
ASHRAE 62.1-2004???
8/18/2019 January 2007 ASHRAE Meeting Ventilation
10/32
• Available free for viewing on the ASHRAE
website
• Also available for purchase on the ASHRAE website
WWW.ASHRAE.ORG
8/18/2019 January 2007 ASHRAE Meeting Ventilation
11/32
8/18/2019 January 2007 ASHRAE Meeting Ventilation
12/32
Why do we need a ventilation
standard?• Help insure indoor air quality acceptable to
human occupants• Minimize potential for adverse health
effects
8/18/2019 January 2007 ASHRAE Meeting Ventilation
13/32
How do we define “Acceptable
Indoor Air Quality”?
• “Air in which there are no knowncontaminants at harmful
concentrations as determined by
cognizant authorities and which asubstantial majority (80% or more) of
the people exposed do not express
dissatisfaction.”
8/18/2019 January 2007 ASHRAE Meeting Ventilation
14/32
Ventilation Rate Procedure
8/18/2019 January 2007 ASHRAE Meeting Ventilation
15/32
• Verify outside air quality meets EPA
ambient air quality standards
• Treat outside air if required
• Carefully locate outside air intakes
8/18/2019 January 2007 ASHRAE Meeting Ventilation
16/32
8/18/2019 January 2007 ASHRAE Meeting Ventilation
17/32
• Determine “breathing zone outdoor air flow”
8/18/2019 January 2007 ASHRAE Meeting Ventilation
18/32
8/18/2019 January 2007 ASHRAE Meeting Ventilation
19/32
• Correct for Zone air distributioneffectiveness
• Correct for multiple zones (system
ventilation efficiency)
8/18/2019 January 2007 ASHRAE Meeting Ventilation
20/32
8/18/2019 January 2007 ASHRAE Meeting Ventilation
21/32
Other Requirements
• Ventilation air flow must be maintained
during any load condition and at all timesthe space is occupied
8/18/2019 January 2007 ASHRAE Meeting Ventilation
22/32
Other Requirements
• Drain pans must drain
• Maintenance access toequipment required
• Building envelope designed for
moisture control• Insulate to prevent
condensation
• Airstream surfaces must resistmold growth and erosion
8/18/2019 January 2007 ASHRAE Meeting Ventilation
23/32
Outdoor Air Intakes
• Must prevent rain intrusion
• Must manage snowentrainment
• Must have bird screens
8/18/2019 January 2007 ASHRAE Meeting Ventilation
24/32
Filters
• Minimum MERV 6 filters
required ahead of wet coils
8/18/2019 January 2007 ASHRAE Meeting Ventilation
25/32
Relative Humidity
• Limited to 65% or less at
design dew point condition
8/18/2019 January 2007 ASHRAE Meeting Ventilation
26/32
Smoking Areas
• Separate “ETS Free Areas”
from “ETS Areas”
8/18/2019 January 2007 ASHRAE Meeting Ventilation
27/32
• Air movement within building mustobserve air classification requirements
8/18/2019 January 2007 ASHRAE Meeting Ventilation
28/32
8/18/2019 January 2007 ASHRAE Meeting Ventilation
29/32
• Short term conditions
• CO2 measurement and control
8/18/2019 January 2007 ASHRAE Meeting Ventilation
30/32
Space Pressurization
+ ++
Building Must be Positive
A Word About Clarifications
8/18/2019 January 2007 ASHRAE Meeting Ventilation
31/32
A Word About Clarifications
Sometimes there are unstated
motives
8/18/2019 January 2007 ASHRAE Meeting Ventilation
32/32
What’s Next??
2007 EditionPick up addenda
Clarifications