29

J08086-FD-SPC-ENV-05 REV 0

Embed Size (px)

Citation preview

Page 1: J08086-FD-SPC-ENV-05 REV 0
Page 2: J08086-FD-SPC-ENV-05 REV 0
Page 3: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page i of i 

 

TOC  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

TABLE OF CONTENTS 

 

1.  Introduction ................................................................................................................ 1 

2.  Technical Requirements .............................................................................................. 2 

Appendix A: Transformer Rectifier and Solar Power Unit ................................................... 11 

A1. Cathodic Protection Transformer Rectifier Unit ................................................................. 11 

A2. Cathodic Protection Solar Cell Unit .................................................................................... 18 

 

Page 4: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 1 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

1. INTRODUCTION 

1.1 Scope  

This  specification  describes  the  requirements  for  the  cathodic  protection  equipment  and materials  required  for  systems  along  the  water  conveyor,  wellfield,  and  at Mudawarra, regulating tank, break pressure tank, Madaba Bridge, Abu Alanda and Dabuk sites. 

1.2 Applicable Standards 

NACE SP0286‐2007  Electrical  Isolation  of  Cathodically  Protected Pipelines 

NACE SP0572‐2007  Design,  Installation,  Operation,  and Maintenance  of  Impressed  Current  Deep anode Beds 

NACE SP0169‐2007  Control of External Corrosion on Underground or Submerged Metallic Piping Systems 

ASTM G 57‐95a  Field Measurement of Soil Resistivity Using the Wenner Four–Electrode Method 

ISO 15589‐1  Petroleum & Natural Gas Industries – Cathodic Protection of Pipeline Transportation Systems. On‐land Pipelines 

BS 7361:Part1  Cathodic Protection, Code of Practice for Land and Marine 

NACE RP0104‐2004  The  Use  of  Coupons  for  CP  Monitoring Applications 

NACE TM0497‐2002  Measurement  Techniques  Related  to  Criteria for CO on Underground of Submerged Metallic Piping Systems 

BS EN 50162  Protection  against  corrosion  by  stray  current from direct current systems 

Page 5: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 2 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

DD CEN/TS 15280  Evaluation of ac corrosion  likelihood of buried pipelines Application to cathodically protected pipelines 

NACE SP0177  Standard Recommended  Practice  ‐ Mitigation of Alternating Current and Lightning Effects on Metallic  Structures  and  Corrosion  Control Systems 

BS EN 12954:2001  Cathodic  Protection  of  buried  or  immersed metallic  Structures  General  principles  and application to pipelines 

2. TECHNICAL REQUIREMENTS 

2.1 Cathodic Protection Systems 

Cathodic protection for the water conveyor and wellfield piping shall be based on impressed current  systems  which  shall  have  a  50  year  design  life  from  the  completion  of  system commissioning. 

The entire conveyance system  including  the wellfield piping system will be segregated  into six  independent sections. Each section shall be protected independently with a separate CP system. The extremities of each  section  shall be  isolated  from  the above  ground  facilities utilising insulating flange kits. 

The CP designs shall be based on the availability of ac power source along the conveyor and the wellfield area. Consequently, the cathodic protection stations shall be  installed close to the conveyor inlet and outlet at the following sites:  

Wellfield Mudawarra Regulation Tank Break pressure Tank Madaba Abu Alanda Dabuk Reservoir  

Three other CP stations will be located remotely from the above stated sites (on the off‐road and highway  section)  in which  solar units may be used  in  case  the provision of  ac power source  is not possible. Actual  location of each CP  station will be  stated  in  the  final design drawings. 

Page 6: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 3 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

2.2 Environmental Conditions 

Ambient air temperature range throughout the project are as follows, 

Maximum ambient air temperature 50oC 

Minimum ambient air temperature ‐10oC

2.3 Inspection and Tests 

The Manufacturer  shall make  available  all  equipment  and materials  for  inspection by  the Employer and conduct all tests as necessary to show full compliance with the specification to the satisfaction of the Employer. 

In the event that inspection is waived, then this shall not release the Manufacturer from an obligation to supply completely satisfactory materials and equipment. 

2.4 Cable 

Cable  for DC  service  shall  be multiple  stranded  conductors,  single  core  copper  XLPE/PVC 600/1000 volt grade to IEC 60502. 

Cable for deep well groundbed service shall be single core, copper, Kynar/HMWPE 600/1000 volt grade to ASTM D‐1248. 

Cable for AC power supplies to CP stations shall be three core, copper XLPE/PVC/SWA/PVC 600/1000 volt grade to IEC 60502. 

Page 7: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 4 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

 

Cable sizing shall comply with the following, 

Items  Minimum Cable Core Size 

Magnesium  anode,  monitoring  coupon, reference electrode cable tails:‐ 

6 mm2 

Test/monitoring cables:‐  10 mm2 

Impressed  current  anode  cable  tails,  zinc ribbon/electrode connection at casings:‐ 

16 mm2 

Foreign crossing bonding station cable 16 mm2

AC  and  DC  stray  mitigation  bonding,  zinc electrode/ribbon  connections  for  earthing,  IJ surge arrestors cable tails:‐ 

25 mm2 

Negative  and  positive  DC  supply,  positive  DC groundbed  distribution  cables  ,  Interpipeline bonds  and electrical continuity jumper 

35 mm2 

 

Cable colour coding shall comply with the following, 

Items  Cable Insulation/Sheath 

Magnesium  anode,  foreign pipeline  cables,    zinc ribbon/electrode  connection  at casings:‐ 

red/red 

Monitoring coupons:‐ blue/grey

Permanent  reference electrodes:‐  brown/grey 

Zinc  electrode/ribbon connections for earthing:‐ 

green‐yellow 

Positive  DC  supply,  DC groundbed distribution cables:‐ 

red/red 

Other cables   black/black 

Page 8: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 5 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

2.5 Cable Joint Kits 

Cable joint kits shall be purpose made epoxy filled plastic joint boxes. Each kit supplied with a suitably sized electrolytic tinned brass through‐joint cable connector. 

2.6 Cable Identification Tags/Sleeves 

Temporary cable identification shall be effected by using write‐on self‐laminating vinyl cable markers. 

Permanent cable identification shall be effected by using slide on PVC Z–type and/or captive PVC oval cable markers. 

2.7 Cable Termination Lugs 

Cable lugs shall be electrolytic tinned copper crimp compression type, suitably sized to fit the cable to be terminated and the terminal connection. 

2.8 Cable to Pipe Connections 

All cable to pipe connections shall utilise threaded studs of M8 minimum size. 

Studs shall be connected to the pipe by drawn arc braze. All connections shall comply with Project welding procedures. 

Test/monitoring  cables  shall  not  utilise  the  same  stud  as  current  carrying  or mitigation earthing cables. 

2.9 Cable Marking for Burial 

Cable tiles shall be pre‐cast concrete, baked clay or recycled polyethylene, minimum width 200 mm, marked `Danger Electricity'. 

Cable  warning  tape  shall  be  yellow  polyethylene, minimum  width  100 mm  and marked `Caution Electricity Cable Below' every 500 mm. 

2.10 Carbonaceous Backfill 

Carbonaceous backfill shall be calcined petroleum coke meeting the following requirements, 

‐ Fixed carbon: > 99%

‐ Specific gravity  > 2.0 

‐ Bulk Density:  > 800 kg/m3 

Page 9: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 6 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

‐ Particle size range (dia)

  i) horizontal & shallow vertical groundbeds: 

0.1 to 10 mm 

  ii) deep well vertical groundbeds: 90% 1‐5 mm, max 12 mm

‐Resistivity:  < 0.15 ohm.cm @ 10 Bar 

‐ Ash content  >0.20% 

‐ Volatiles  >0.60% 

‐ Moisture content  >0.60% 

Backfill shall be supplied  in sacks or drums. Individual containers shall not weigh more than 25 kg. 

2.11 Groundbed Surface Markers 

Posts for the marking of horizontal and shallow vertical impressed current groundbeds shall be reinforced concrete having a section approximately 100 mm x 100 mm and length of 1000 mm. 

Cast into at least one face of the post shall be the inscription ‘GROUNDBED’. 

2.12 Impressed Current Anodes 

2.12.1 Silicon Iron Anodes 

Anodes shall be of a cast high silicon iron and shall meet the requirements of BS 1591 Grade Si14 with a 14‐15% by weight silicon.  

Anodes  for  horizontal  and  shallow  vertical  groundbeds  shall  be  supplied with  a  16 mm2 (7/1.70 mm) single core, copper, XLPE/PVC cable tail. The cable tail  length shall not be  less then 3 m. 

The cable/anode connection shall be caulked lead or approved equivalent method. The cable connection shall be sealed and protected overall by a cast resin cap which shall encase the insulation and sheathing ends of the cable, a section of the anode head and any additional cable retaining fixings. The resin used shall be compatible with the intended use. 

The cable/anode connection shall be provided overall with a heat‐shrink anode cap. 

Page 10: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 7 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

All anodes shall be generally free from shrinkage, porosity, blow holes and surface defects. Any  surface  defect  having  a  penetration  in  excess  of  6.5  mm  shall  render  the  anodes unacceptable. 

Each anode shall be tested and certified as conforming to the following: 

Ten amperes DC shall be passed through the cable and anode body and the initial volt drop across the cable/anode assembly, excluding the volt drop due to the cable resistance, shall not exceed five millivolts. The volt drop measured after 10 minutes continuous current flow shall not exceed the initial measurements by more than 10%.  

The anodes shall be pallet packaged and suitably protected against damage for freighting to site. 

2.12.2 Mixed Metal Oxide 

Anodes shall be titanium core to ASTM B338 or B265 Grade 1 provided with a mixed metal oxide coating of IrO2 and Ta2O5. 

Anodes  for  horizontal  and  shallow  vertical  groundbeds  shall  be  supplied with  a  16 mm2 (7/1.70 mm) single core, copper, XLPE/PVC cable tail. The cable tail  length shall be not  less then 3 m. 

Anodes for deep well groundbeds shall be supplied with a 16 mm2 (7/1.70 mm) single core, copper,  Kynar/HMWPE  cable  tail.  The  cable  tail  length  shall  depend  on  the  depth  of  the anodes in the deepwell. 

The anode cable connection shall be a proven factory made connection which shall be tested and certified as having a resistance of less than 0.001 ohms. 

The cable/anode junctions shall be provided overall with a heat‐shrink sleeve. 

The anodes shall be pallet packaged and suitably protected against damage for freighting to site. 

The size of each anode, the number of anodes per string and the spacing between anodes shall be as detailed in the Bill of Quantities. 

2.12.3 Linear Anodes 

Linear anodes shall be made of copper‐cored mixed metal oxide anode (MMO) powered by a 10  mm2    copper  cable  insulated  with  an  inner  layer  of  halar  and  outer  layer    of  high molecular weight  polyethylene.  The  central MMO wire  and  cable  shall  be  surrounded  by factory prepackaged, high  conductivity  coke breeze, held  in place by porous, woven  acid‐resistant jacket. 

Page 11: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 8 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

The  following  test method  shall  be  carried  out  and  test  results  shall  be  provided  by  the Manufacturer to the Employer prior to supply: 

Property  Test Method  Accepted  Value Copper 

Conductor    

Dimensions ASTM B‐263 10 mm2      

Coke Breeze     Fixed carbon  ASTM D‐172  99.5 % Resistivity  @23°C, 10 bar  <1 Ohm‐cm 

     Fabric Jacket     

Weight  ‐  Min. 200 g/m² Bursting strength ISO 3303 >500 N 

Abrasion Resistance 

ASTM D‐4157  200 cycles to fail 

Fluid resistance  Internal immersion test 6 months 

pass 

Chlorine resistance 

Internal immersion test 6 months 

pass 

UV resistance  ASTM G‐53  <50% tear strength loss 

 

2.13 Magnesium Anodes 

Magnesium anodes shall be to the following composition:‐ 

Manganese  :  0.5 ‐ 1.3% 

Aluminium  :  0.01% max 

Copper    :  0.02% max 

Iron    :  0.03% max 

Nickel    :  0.001% max 

Lead    :  0.01% max 

Silicon    :  0% 

Magnesium  :  remainder 

Page 12: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 9 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

Open circuit potential :  ‐1.75 volts ref. Cu/CuSO4 

Current efficiency  :  50% minimum 

Capacity     :  1230 amp.hrs per kg 

Melt analysis and test certificates certifying compliance with the above requirements shall be provided by the Contractor, with each batch of anodes, when directed by the Employer. 

Each  anode  shall  be  fitted  with  a  6  mm2  (7/1.04  mm)  single  core,  copper  PVC/PVC  or XLPE/PVC  red/red cable  tail, brazed  to  the  steel  insert. The cable connection  shall be  fully sealed to prevent moisture penetration. 

Anodes shall be supplied pre‐packaged in a backfill of the following composition, 

‐ Powdered gypsum:  75% 

‐ Granular bentonite:  20% 

‐ Anhydrous sodium sulphate: 

5%

The backfill shall be contained within a cotton bag and the anode shall be centrally  located within the backfill. 

2.14 AC Current Monitoring Coupons 

Monitoring coupons shall comprise a steel coupon set in a PVC housing complete with cable tail. Coupon/cable connection shall be fully encapsulated and be suitable for burial. 

The area of exposed steel coupon shall be 1.0 cm2. 

Cable tails shall be 6 mm2 (7/1.04 mm) single core, copper, PVC/PVC or XLPE/PVC blue/grey. 

2.15  Solar Power Units 

Solar power unit shall be utilised when cathodic protection station is located remote from ac power source. The solar power unit shall comprise of photovoltaic panels, charge regulator, CPCU  and battery bank.  Solar units  shall be  sized  to endorse  the operation of  the  SCADA system which shall provide output current, output voltage, pipe potential, and unauthorised access alarm transmitter for the unit. 

Solar power units shall fully comply with the requirements detailed in Appendix A. 

2.16 Test Post/Pillar Facilities 

Test post/pillars  shall be BigFink and FinkLet or equivalent which provides convenient and easy test /monitoring and full cable protection. 

Page 13: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 10 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

Cable connections  in posts shall be a minimum of M8 brass or stainless steel bolt, nut and washer assemblies, fully insulated from the facility housing where the housing is metallic or of concrete. 

Cable conduit shall be a minimum 75 mm diameter for the BigFink and 25 mm diameter for the FinkLet or equivalent test post. 

Each  test  post  shall  be  supplied  fitted  with  marker  plates  to  identify  the  pipeline location/sequence designation and facility type. 

2.17 Junction Boxes 

Positive and negative wall/frame mounting enclosures shall be manufactured from stainless steel plate of 1.5 mm thickness.  

The enclosure shall be fitted with cable entry plate and a M8 threaded stud for earthing to base, door and mounting plate.  

The door shall be secured to the base by means of at min. two hot galvanized hinges and its angle of opening  is at  least 130°. The direction of turn of the door shall be  left‐right and  is reversible, and are closed by min. two  locking system.   The doors shall be sealed from any outer contaminants or dust using seamless polyurethane gasket.  

The enclosure shall achieve a minimum protection degree of IP65.  

2.18 Transformer‐Rectifier Units 

Where  ac power  is  available  transformer‐rectifier units  for CP  stations  shall provide a  full wave rectified DC output from a single phase 230 volt, 50 Hz AC input supply. Units shall be variac controlled. Units shall be oil cooled and suitable for plinth mounting. 

Transformer‐rectifier units shall fully comply with the requirements detailed in Appendix A to ensure minimum standards and harmonisation of units throughout the pipeline system. 

2.19 Zinc Ribbon 

Zinc  ribbon  shall be of diamond  cross  section  cast  Zinc  to MIL‐A‐18001K, on  a  galvanised steel wire core. 

Melt analysis certificates certifying compliance with the above composition shall be provided by the Contractor, with each batch of ribbon, when directed by the Employer. 

Page 14: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 11 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

Appendix A: Transformer Rectifier and Solar Power Unit 

A1.  Cathodic Protection Transformer Rectifier Unit 

1. GENERAL 

Transformer‐rectifier unit shall provide a  full wave  rectified DC output  from a single phase 230 volt (+10%, ‐6%), 50 Hz (+ 2%) AC input supply. 

The maximum dc output voltage shall not exceed 48 volts. 

The unit  shall be oil  cooled and  suitable  for plinth mounting  in  the project environmental conditions. 

2. OIL TANK AND CONTROL ENCLOSURE 

The unit shall generally comprise a sealed oil tank and external control enclosure. 

The oil tank shall be a welded steel construction and be so sized that adequate oil cooling is provided when the unit is operating continuously at full load. 

The oil  tank  shall be provided with  a  silica  gel breather, oil  filler  cap, oil drain  valve, dial thermometer and pocket and oil level sight gauge and its complete filling of oil. 

The control enclosure for the unit shall be mounted on the oil tank, have front access via a hinged, lockable door and shall be constructed from 3 mm minimum thickness steel suitably stiffened to form a rigid unit. All cables from the tank shall enter the unit via the base or rear of the enclosure. All external cables shall enter the enclosure via a removable gland plate in the enclosure base. 

The control enclosure shall contain all controls mounted on a panel for easy and safe access. The enclosure shall conform to EN 60529 protection category IP65, proof against damage by dust and water. 

The tank and control enclosure shall be painted to meet as a minimum ‘High’ durability in a ‘C3’ corrosivity category  in accordance with EN 12944‐5. All paint coats shall differ in shade and the final paint coat colour shall be as advised by the Employer. 

3. GENERAL CONSTRUCTION  

All components within the oil tank shall be assembled on a common rack. The dimensions of the  rack  and  equipment  shall  be  such  that  it may  be  removed  and  installed within  the enclosure as one or two complete assemblies with only external wiring disconnections. 

The unit shall be constructed to facilitate ease of repair and maintenance 

Page 15: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 12 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

All  hinges,  fixings  and  items  liable  to  fretting  or mechanical  damage  of  coatings  during normal use, shall be either 18/8 stainless steel or non  ferrous materials or galvanised mild steel. 

All materials used in the construction of the control panel and internal fixings shall be made from non‐hydroscopic materials. 

All  equipment  and  wiring  shall  be  fully  insulated  from  the  support  frame,  tank,  control enclosure and if made of conducting material, the control panel. 

When the outer door of the control enclosure  is opened to gain access to the controls and meters, it shall not be possible to make contact to live terminals. 

A  viewing window  shall be  fitted  in  the  front  of  the  control  enclosure door  to  enable  all meters and the AC healthy light to be viewed with out the need to open the enclosure door. 

4. MODE OF OPERATION 

The  Unit  method  of  control  shall  utilise  variac  to  provide  infinite  variable  adjustment between minimum and maximum output of the unit.  

Variac  controls  shall  provide  constant  voltage  utilising  handgrip  for    manual  control  of output. All controls shall be mounted on the control panel. 

5. ALARM TRANSMITTERS 

The  unit  shall  be  provided  with  output  current,  output  voltage,  pipe  potential,  and unauthorised access alarm transmitters compatible with the pipeline SCADA system. 

6. TRANSFORMER 

The main  transformer  shall  be  in  accordance with  EN  60076  with  separate  primary  and secondary windings on a common core with Class "F" type insulation. It shall be continuously rated at full current and voltage load at the maximum operating temperature. 

An  earthed  shield  shall  be  placed  between  primary  and  secondary windings  of  the main transformer. 

The main transformer efficiency shall not be less than 95%. 

7. RECTIFIER 

The  rectifier  elements  shall  be  connected  for  full wave  rectification  using  a  single  phase bridge circuit in accordance with IEC 60747‐2. The bridge rectifier shall be continuously rated at the unit full load current and voltage at the maximum ambient temperature specified. 

Page 16: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 13 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

The bridge rectifier shall be rated to provide an adequate margin for over voltage and over current surges and the peak inverse voltage rating shall be 1.2 kV. Voltage protection circuits shall be provided  to  the bridge  rectifier. High  speed  fuses  shall be provided between  the transformer secondary and the rectifier bridge. 

8. OUTPUT RIPPLE 

The  unit  shall  be  fitted with  smoothing  filter  circuits  to  ensure  the  DC  output  does  not contain more than 5% ripple. 

9. ELECTROMAGNETIC COMPATIBILITY 

The unit shall comply with EU Electromagnetic Compatibility Directive 89/336/EEC amended by 92/31/EEC, 93/68/EEC and EN 50082 for Conducted and Radiated Immunity and EN 50081 for Emissions. 

10. METERS 

The unit shall be provided with the following meters mounted on the control panel behind the viewing window:‐ 

a) One 3½ digit LED DC output ammeter with 11 mm LEDs and scaled from 0.01 to 199.9 amps. 

b) One 3½ digit LED DC output voltmeter with 11 mm LEDs and scaled from 0.01 to 199.9 volts. 

c) One  3½  digit  LED  DC  potential  voltmeter with  11 mm  LEDs  and scaled from ‐0.01 to ‐199.9 volts. 

Fuses shall be placed in both leads of the voltmeter. 

Beneath  each  meter,  separate  4  mm  sockets  shall  be  provided  on  the  panel  so  that measurements of current, voltage and potential can be made with a portable voltmeter. 

11. AC/DC CIRCUIT PROTECTION 

A  two‐pole miniature circuit breaker  (MCB) complying with EN 60898 shall be provided  to interrupt  the  AC  supply  to  the  unit  The MCB  shall  be  capable  of  carrying  the maximum transformer inrush current without tripping. 

The MCB shall be accessible by opening the control enclosure door. 

The total DC output current in the negative circuit shall be fused. 

Suitably rated surge arrestors shall be fitted across the AC input and DC output. 

Page 17: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 14 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

12. AC AND DC TERMINALS 

The  AC  terminals  shall  be  suitably  shrouded  and  a  clear  warning  label  shall  be  fitted immediately adjacent to the terminals. 

The  label shall carry the words ‘SWITCH OFF AT SUPPLY POINT PRIOR TO DISCONNECTING’. The lettering shall be red on white background. 

The DC output terminals shall be sized and rated for 35 mm2 single core cables. 

DC terminals shall be  identified with white/black/white engraved  labels 3 mm  letter height, the negative bearing  the  inscription  ‘‐ve pipe’ and  the positive bearing  the  inscription  ‘+ve groundbed’. 

AC supply  terminals shall have a distinct and clean separation of at  least 150 mm  from DC terminals  and  all  terminals  shall  be  located  at  a minimum  height  of  250 mm  above  the bottom of the enclosure. 

13. CABLING 

All  internal  wiring  shall  be  PVC  insulated  with  a  glossy  finish  and  shall  be  incapable  of supporting combustion and capable of withstanding the temperatures to be met in service. 

The  cross‐section  of  copper  conductors  and  cable  terminations  shall  be  such  that  the maximum rated current carried shall not cause excessive volt drops or temperature rise. 

All cable terminations and terminal connections of components shall be of adequate cross‐section and shake‐proof. 

All  terminals  and  equipment operating  at AC  supply  voltage  levels  likely  to  cause  electric shock to operators shall be insulated or screened from accidental contact. 

Cable  shall  be  neatly  bunched,  properly  supported where  required  and  both  ends  of  the cable will be marked with ferrules identifying the cables. 

All wiring will be terminated with proprietary compression  lugs and will be numbered at all terminations. 

14. EARTHING 

A minimum of 2.5 mm2 single core PVC insulated green‐yellow cable shall be used within the unit  to earth all metallic components. The enclosure door, gland plates,  terminal  rails and similar metallic objects will be suitably grounded. 

A brass M10 earth stud shall be provided on the external surface of the unit.  

Page 18: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 15 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

Earth  terminals within  the  enclosure  shall  be  identified  by  a  label  bearing  the  inscription ‘Warning – Electrical Earth’ in red lettering. 

Pre‐insulated compression crimp tags will connect all earth wires and all earth terminals will be numbered. 

15. LABELLING 

The  function of all  instruments,  switches,  terminals,  indicators and  the  like on  the control panel shall be clearly and permanently marked, with  lettering not  less than 3 mm high. All terminals  shall  be  clearly  labelled  in  accordance  with  their  designation.  Labels  shall  be engraved; black letters on a white background except where red is required. The labels shall be secured with countersunk stainless steel screws. 

The outside of the unit shall carry a manufacturers standard rating plate, showing the name of  the manufacturer,  the  type of  equipment, maximum operating  temperature,  input  and output voltage and current, kVA rating, type and unique serial/identification number. 

A white/black/white engraved label with 12 mm high lettering shall be fixed on the front of the enclosure of dimensions 150 mm x 100 mm engraved with the following: 

CATHODIC PROTECTION SYSTEM 

TRANSFORMER 

RECTIFIER 

Voltage warning  labels  shall be  fitted  to  the outside of  the enclosure  and  shall be  clearly visible. 

All components within the unit shall be given a unique identification number. 

16. SUNDRIES 

The  transformer‐rectifier  shall  be  supplied  complete with  all  external  fittings  to  facilitate transportation, installation, operation and maintenance. 

These shall include but not be limited to the following items:‐ 

a) An engraved schematic diagram of the equipment circuitry securely attached to the inside of the enclosure door. 

b) A  flush  fitting  lock  fitted  to  the enclosure door and provided with three keys. 

Page 19: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 16 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

c) A spare silica gel cartridge 

d) Two complete sets of all cartridge fuses located on the panel or on the inside of the enclosure door. 

17. TEST AT MANUFACTURER'S WORKS 

The following tests shall be carried out at the Manufacturer's Works  in order to determine that  the units comply with  this specification. Unless otherwise specified, all electrical  tests shall  be  carried  out  in  a manner  prescribed  by  the  relevant  standard  or  specification  or where no standard or specification applies, in a manner approved by the Employer. 

The unit shall satisfactorily pass the following tests and the test result shall be recorded and up  to  three  copies  of  a  test  certificate  setting  out  the  result  in  an  approved  form made available to the Employer:‐ 

a) All  circuits and apparatus  shall withstand a power  frequency voltage test in accordance with the requirements of EN 60439. 

b) 500 volt megger insulation test comprising: 

-  Primary to Secondary 

- Primary to Earth 

- DC positive to Earth  

- DC negative to Earth 

c) The unit  shall be  connected up  and  run  continuously  for  at  least 24 hours  at  maximum  current  and  voltage  outputs.  The  500  volt insulation  test  shall  be  repeated  immediately  on  conclusion  of  the continuous 24 hour test run. 

d) Performance tests to EN 60076. The ratio, polarity, no load current, no load  losses,  full  load  losses,  volts  and  winding  resistance  shall  be measured and recorded. 

 

 

 

 

Page 20: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 17 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

 

 

 

 

 

Page 21: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 18 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

A2.  Cathodic Protection Solar Cell Unit 

In remote locations solar power units shall be used to power the CP system. The solar power unit shall consist of a Solar Power Supply Unit providing dc power to a Controller Unit. The solar power unit shall be a completely self‐contained installation incorporating the following main components: 

support frame photovoltaic array (solar array) storage batteries charge regulator and controller (power distribution unit) CP controller unit 

1. CODES AND STANDARDS 

The Solar Power Supply equipment shall conform to the latest editions of the following codes and Standards.  

IEC 60904  Photovoltaic Devices. 

IEC 60947  Low Voltage Switchgear and Control Gear. 

IEC 60157  Low Voltage Switchgear and Control Gear. 

IEC 60158  Low Voltage Control Gear. 

IEC 60185  Current Transformers. 

IEC 60186  Voltage Transformers. 

IEC 60269‐1  Low Voltage Fuses. 

IEC 38  Standard Voltages. 

IEC 60112  Methods  of  determining  the comparatives and the proof tracking indices  of  solid  insulating  material under moist conditions. 

IEC 60144  Degree  of  Protection  for  L.V. Switchgear and Control Gear. 

IEC 60277  Definitions  for  Switchgear  and Control Gear. 

IEC 60337  Control Switches. 

IEC 60364  Electrical Installations for Buildings. 

Page 22: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 19 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

IEC 60408  Low Voltage Air Break Switches, Air Break  Disconnectors  and  Fuse Combination Units. 

IEC 60439  Factory  Built  Assemblies  for  Low Voltage  Switchgear  and  Control Gear. 

IEC 60445  Identification  of  Apparatus Terminals  and  General  Rules  for  a Uniform  System  of  terminal marking,  using  alphanumeric notation. 

IEC 60529  Classification  of  degrees  of protection provided by enclosures 

IEC 60664  Insulation  co‐ordination  with  low voltage systems including clearances and  creepage  distances  for equipment. 

IEC 60896  Lead Acid Batteries 

 

In the event of conflict between Standards, the most stringent shall prevail. 

2. GENERAL DESIGN REQUIREMENTS 

The power output from the Solar Power Supply Unit shall be sufficient to supply the required load including the operation of the SCADA system plus simultaneous charging of the storage batteries. The unit shall be capable of operating between zero and the  full rated  load. The load shall be maintained by means of standby batteries during periods of low light (‘no sun’ days) and during the hours of darkness. 

The module shall be capable of operation for 24 hours (1 day) without sunlight. 

The Solar Power Supply Unit shall be designed to operate on 8 hours sunshine per day based on the solar insolation values (ie the level of radiation received from the sun) as per Section 6. 

The  Manufacturer  shall  submit  the  proposed  design  and  calculations  for  the  Employer approval. The design shall include all interconnections and interfaces. 

Page 23: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 20 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

3. DESIGN DATA 

The Manufacturer shall submit the following information for Employer approval prior to the commencement of detailed engineering: 

1. Full material description of the solar modules. 

2. The ratio of collecting area compared to the total area. 

3. The life of modules and battery. 

4. Conformance to hail‐stone test. 

5. Charge/discharge controller particulars. 

6. Tilt angle of the solar modules. 

 The following data shall be provided for the solar modules: 

1. Number of solar modules. 

2. Average output of each solar module under the expected operational and environmental conditions. 

3. I‐V Characteristics. 

4. Open Circuit Voltage (Voc). 

5. Short Circuit Current (Isc). 

6. Maximum  Power  Point  (P max)  and Operating  Point  under  standard test conditions and also at 40°C and 60°C cell temperatures. 

 The following data shall be provided for the storage batteries: 

1. Load pattern. 

2. Battery chargers factor (efficiency). 

3. Acceptable maximum Daily Depth of Discharge (DDOD). 

4. Calculated maximum DDOD. 

5. Calculated average DDOD. 

6. Acceptable minimum state of charge. 

7. Calculated minimum battery back‐up time. 

8. Calculated average battery back up time. 

9. The maximum time taken to fully charge the battery at the end of the back‐up time. 

Page 24: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 21 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

10. The maximum, average, and minimum terminal voltage supplied to the equipment during day and night. 

 System losses and de‐rating factors due to the following shall be stated: 

1. Charging efficiency of the batteries 

2. Ageing  

3. Dust deposit 

4. Environmental conditions (temperature, wind, sandstorms, hail) 

5. Insolation variation due to normal year to year statistical changes 

6. Current consumed by control equipment, metering and alarm system 

7. Losses in control equipment, wiring, fuses, diodes and circuit breakers 

 The Manufacturer shall submit evidence of satisfying the basic requirements by means of a design and system simulation taking into account all parameters mentioned above.  

4. AMPERE HOUR DESIGN REQUIREMENTS  

The size of the system shall be such that the energy requirements of the load can be met by the battery during ‘no sun’ days. 

The battery shall have sufficient capacity  to meet  the back‐up  time required  for  the  loads, with the batteries at the maximum DDOD and with minimum or insufficient insolation during the intervening days, considering a minimum state of charge of the battery of 20%. 

From the minimum state of charge level, the system shall also, under conditions of minimum daily  average  insolation,  recharge  the battery  to  full  charge  level, while at  the  same  time supplying rated power output to the load.  

The solar module rating shall be such that at any moment the battery charge factor shall be 1.2 minimum, and the DDOD shall not be more than 15% of full capacity, depending on type of battery and ambient temperature of the battery location. 

If  the  solar modules  are  installed  at  a  significant  distance  from  the  load  and/or  battery, attention shall be given to the selection of the output voltage and the cross‐sectional area of the cabling to avoid unacceptable losses. 

Site  and panel  temperature must be  taken  into  account  for  the performance of  the  solar modules. 

Page 25: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 22 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

Electrical  connections  shall  be made  to  a  junction  in which  two  by‐pass  diodes  shall  be incorporated to prevent hot spots. Each diode shall have a minimum direct current value of three times the short circuit current of the array on which it is installed. 

5. INSOLATION DATA 

The Manufacturer shall be responsible for obtaining  insolation data for the project  location from internationally recognized sources and use the same for the design of the Solar Power Supply Unit. 

The  Manufacturer  shall  submit  to  the  Employer  detailed  information  on  his  source  of insolation  data  together with  his  design  of  the  Solar  Power  Supply  Unit.  These  shall  be submitted to Employer for approval before implementing the design. 

6. SOLAR MODULES 

The solar modules shall be mounted on a frame suitable for installation at site. 

The support frame shall be constructed from corrosion resistant, heavy extruded aluminium alloy designed for the climatic conditions and the whole installation capable of withstanding the wind and storm conditions. 

This  frame shall be designed  for tilting to the optimum angle  for absorption of energy and also for creating a self‐cleaning washing of the module surface when it rains. 

The frame shall be supplied with holes or slides for mechanical attachment.   Should vandal protection be required adequate allowance shall be made for the shielding of solar radiation from the panels. 

7. BATTERY 

Batteries shall be the deep‐cycle, long‐life, maintenance‐free, and sealed type design, proven for  solar  power  system  use.    The  effects  of  site  temperatures  on  available  capacity  and lifetime expectancy shall be  taken  into account  in  the selection of  the battery  type and  its housing. 

The expected  service  life  shall be  stated  for  the  service conditions  stated herein and  shall have the following features: 

1. They shall not degrade more than 20 percent of full capacity over their service life. 

2. Storage  capacity  shall  be  calculated  to  allow  the  load  to  operate continuously for a minimum of one (1) ‘no sun’ days. 

Page 26: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 23 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

3. Battery  capacity  shall not be allowed  to  fall below 20 percent of  full capacity during operation. 

4. The self discharge rate shall be <2% per month at 20ºC. 

Cooling of  the batteries  shall be by natural air  flow and good design practice only,  forced cooling shall not be used. 

The  batteries  shall  be  arranged  to  facilitate  access  for maintenance  purposes.  Inter  cell connectors shall be provided.  

Batteries shall be of minimum five years lifespan. 

8. POWER DISTRIBUTION UNIT 

Each solar power supply unit shall have a power distribution unit (PDU).  The PDU shall be of modular  design  for  ease  of  component  replacement  and maintenance  and  shall  ensure proper charging and discharging of the batteries through the following functions: 

1. Dual voltage regulation to cater for boost and float operation. 

2. Overcharge protection of the batteries by switching off the solar array from the system if the battery is already fully charged. 

3. Battery  protection  by  switching  off  the  load  from  the  system  if  the voltage drops below a voltage  limits and alarm contact for warning of low battery voltage. 

4. Temperature compensation maximum charge voltage. 

5. Prevention  of  overnight  discharge  of  the  batteries  through  the  solar array. 

6. Protection against over voltage from the solar module output. 

7. Protection  against  overload  and  short  circuit  conditions  in  the connected load. 

The PDU shall  include a voltmeter and ammeter and LED  Indications  for all battery alarms etc. As a minimum the following shall be provided to indicate system status: 

1. Battery voltage below minimum voltage. 

2. Battery voltage above maximum voltage. 

3. Voltage free contacts for remote indication of battery low voltage. 

The PDU shall incorporate a SPDT (Single Pole Double Throw) contactor which is actuated on battery low voltage. The contactor rating shall allow for the inductive load during switching.  A local programmable module with display panel shall be provided. 

Page 27: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 24 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

Failure of the PDU shall not result in catastrophic failure of the whole system. 

The charge controller should be able to operate at various system voltages  (12V, 24V, 36V and 48V. 

9. CP CONTROLLER UNIT 

The CP controller unit (CPCU) shall regulate the voltage and current output to the cathodic protection  system  to  a  manually  set  level  (i.e.  the  CP  load).    The  dc  output  shall  be controllable  from  any  value  between  zero  and  maximum,  the  output  current  shall  be electronically limited to the rated maximum of the unit. 

The CPCU shall be specified and supplied to the following requirements: 

1. The  CPCU  shall  be  suitably  rated  for  the  requirements  of  the  CP system. 

2. The unit shall be protected against induced over‐voltages. 

3. The unit shall have a CP load MCB (miniature circuit breaker) with trip alarm. 

4. Display meters  shall  be  provided  for:  the  CP  output  voltage,  the  CP output current and the reference cell potential. 

5. Synchronized    Interrupt  timer  compatible  with  those  fitted  in  the transformer rectifiers 

Separate analogue meters shall be provided for the continuous display of the output voltage, output current and the pipeline drain point potential. The meters shall be flush mounted on the control panel and visible through the enclosure door. 

Meters shall have scale settings of 20% greater than the maximum output rating of the CPCU with a red line to show the maximum output value. 

Each controller unit shall  incorporate a synchronized GPS current  interrupter similar to that fitted in the transformer rectifiers. 

The CPCU shall  incorporate RTU designed  to collect  the DC output  , AC  input and pipeline potential data and transmit it using GSM text messaging to cell phone on a daily and weekly basis  in  addition  to  alarm messaging  in  case  inadequate  protection  arise  during  normal operation.. The RTU shall be supplied with data management software for data display and interpretation. 

Terminals shall be provided on the CPCU panel for termination of the DC supply cables to the groundbed , pipeline, and the potential monitoring cables. 

Page 28: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 25 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

All controls, switches, fuses, meters and cable entry glands shall be easily accessible. 

10. AUXILIARY EQUIPMENT 

Separate  enclosures  shall  be  provided  for  the  PDU  and  the  CPCU.  As  a  minimum  the enclosures shall be constructed to EN 60529 protection category IP65, proof against damage by dust and water. 

The enclosures shall be provided with DC circuit breaker protected terminals for the design loads and cable glands appropriate for the installation cables. 

The  interconnection between the solar array and the PDU shall be made by means of a DC circuit breaker to facilitate the electrical  isolation of the solar modules from the system for repair or replacement. 

The interconnection between the battery bank and the PDU shall also be made by means of a DC circuit breaker  to  facilitate  the electrical  isolation of  the battery  from  the  system  for inspection and maintenance purposes. 

11. INTERCONNECTION CABLES 

All interconnection cables between the solar modules, the solar array, the storage batteries and the control equipment enclosures shall be supplied. 

All cables shall be 600/1000 V grade, copper conductor, PVC  insulated, PVC sheathed, steel wire armoured with PVC outer sheath (PVC/PVC/SWA/PVC). 

12. EARTHING 

M8 earth studs shall be supplied on all cabinets and enclosures. 

13. TESTS 

The complete  solar  system complete with all  interconnecting cables  shall be  tested at  the Manufacturer’s  works  in  accordance  with  applicable  codes  and manufacturer’s  standard testing procedures. Comprehensive test for the solar system shall be carried out throughout each  process  along  the  project.  The Manufacturer  shall  submit  copies  of  the  subject  test certificates to the Employer.  

Testing shall include the following: 

1. Visual inspection. 

2. Insulation test on all cables. 

3. Functional testing of the complete system. 

Page 29: J08086-FD-SPC-ENV-05 REV 0

Gama Güç Sistemleri Mühendislik ve Taahhüt A.Ş.

Disi‐Mudawarra to Amman Water Conveyance System Project 

 

Specification for Cathodic Protection Equipment and Material 

Doc. No:  J08086‐FD‐SPC‐ENV‐05  REV 0  Page 26 of 26 

 

Cathodic Protection Equipment and Material  Doc. No: J08086‐FD‐SPC‐ENV‐05 REV 0 

4. Load testing of complete installation (under maximum CP load). 

5. Battery discharge test. 

6. Measurement  of  typical  values  of  solar module  short  circuit  current and open circuit voltage. 

14. DOCUMENTATION 

The Manufacturer shall supply  installation, operation, maintenance manuals  for each piece of equipment  supplied and other documents  as  required defined  in  an  approved  Supplier Data Requirement List (SDRL), and  including the following documentations to be submitted to the Employer for review and approval; 

− Track record of materials and equipment. − Materials certificates for anodes to BS EN 10204 Type 3.1.B. − Certificate of compliance for hot dip galvanizing. − Coating materials certificates. − Product/Equipment/Material  specifications,  Manufacturer’s  product  data  sheets 

and  drawings  including,  where  appropriate,  statements  of  manufacturing tolerances. 

− Quality plan covering manufacture, inspection and testing of sacrificial anodes. − Detailed instrument and spare parts list. − Batch analysis for all sacrificial anodes supplied against the specification. − Factory  test  report  of  tests  of  dimensions,  casting  quality  and  cable  connection 

resistance. − Operating and instruction manuals. − As‐built drawings. − Spare lists.