76
TECHNICAL HANDBOOK TECHNICAL HANDBOOK

Isopan Man Tecnico GB

Embed Size (px)

Citation preview

Page 1: Isopan Man Tecnico GB

TECH

NIC

AL

HA

ND

BO

OK

TECH

NIC

AL

HA

ND

BO

OK

TECHNICAL HANDBOOKTECHNICAL HANDBOOK

Ver

sion 1

0/2

00

4

Copyri

ght

© b

y Iso

pan S

.p.A

.

Any k

ind o

f re

pro

duct

ion,

even

part

ial,

if n

ot

auth

ori

zed, is

forb

idden

, w

hate

ver

mea

ns

utiliz

ed.

GRUPPO MANNI S.p.A.

www.isopan.i t

ISOPAN FRANCE

Zac du Parkile - BAT 2164 Avenue Joseph Kessel

F - 78960 VOISINS LE BRETONNEUXTel. (33) 1 30575578 - Fax (33) 1 30575097

[email protected]

ISOPAN IBERICA SLPolígono Industrial de ConstantíAvda. de les Puntes, parcela 23

E - 43120 Constantí (TARRAGONA)Tel. (34) 977524546Fax (34) [email protected]

ISOPAN S.p.A.TREVENZUOLO branch

Via Giona, 5I - 37060 TREVENZUOLO (VR)

Tel. (39) 045 7359111Fax (39) 045 7359100

[email protected]

ISOPAN S.p.A.PATRICA headquarters

S.P. MorolenseI - 03010 PATRICA (FR)

Tel. (39) 0775 2081Fax (39) 0775 293177

[email protected]

EN ISO 9001T V Italia S.r.l.certified

EN ISO 9001T V RheinlandcertifiedDIN EN ISO 9001:2000

Certificado Nº 01 100 048110

Page 2: Isopan Man Tecnico GB

INTRODUCTION

This Handbook contains technical information in relation to FAQs by

customers. It is easy to consult and includes a large amount of data for

the correct use of products here included and manufactured by Isopan

S.p.A. by designers and builders.

The technical information in the Handbook is derived from the techni-

cal know-how and experience of Isopan S.p.A. over 30 years of

manufacturing insulating monolithic panels in compliance with all sta-

tutory requirements. The company may amend, add to , or update the

contents of the Handbook at any time, without notice.

HOW TO CONSULT THE HANDBOOK

The Handbook is divided into sections, each with its own colour, as

listed in the Contents. Each Section has a detailed list of contents.

GRUPPO MANNI S.p.A.

Page 3: Isopan Man Tecnico GB

CONTENTS

Sandwich Panels A

General Conditions of Sale: Aippeg Regulations B

Construction Details C

Page 4: Isopan Man Tecnico GB

SANDWICH PANELS

INTRODUCTION A1Thermo-insulating polyurethane panels A1.1Mineral wool insulating panels A1.2Dimensional standards A1.3

RAW MATERIALS A2Principal characteristics of the metal facings A2.1Protection of prepainted bearing surfaces A2.2Expanded polyurethane A2.3Composition of the formulae A2.4Expansion A2.5

CHARACTERISTICS OF THE POLYURETHANE INSULATION A3Density A3.1Cell-structure A3.2Resistance to compression A3.3Dimensional stability A3.4Reaction to fire A3.5Water absorption A3.6Thermal conductivity A3.7Mixing of the components A3.8Environment A3.9

PRODUCT TECHNICAL SPECIFICATIONS A4Types and intended uses A4.1Dimensional characteristics A4.2Insulation A4.3Load-bearing capacity A4.4Tolerances A4.5

Page 5: Isopan Man Tecnico GB

FITTING THE PANELS A5Equipment necessary A5.1Fitting to roof (excluding Isodoga 1000) A5.2Fasteners and principles of fixing A5.3Instructions for handling, storage and transport A5.4Lifting and handling A5.5Instructions for fitting A5.6Preliminary information A5.6.1Preparation of the panels A5.6.2Fitting sequences for Isopan panels – wall panels A5.6.3Fitting sequences for Isopan panels – roofing panels A5.6.4Cutting the panels A5.6.5

INSULATING PANELS IN MINERAL FIBRE A6Types and intended uses A6.1Dimensional characteristics A6.2Overlaps A6.3Tolerances A6.4Insulation A6.5R.E.I. panels A6.6Fireproof compartment A6.6.1Smoke-proof filter A6.6.2Smokeproof stair wells or protected stairs A6.6.3Fire resistance A6.6.4Outline of fire safety legislation A6.6.5Suggestions for making connections and joints A6.6.6Principal types of operation A6.6.7

CERTIFICATION A7Certificates for polyurethane panels A7.1Isofire certification A7.2Certified Iso 9001 : 2000 A7.3

GENERAL TERMS OF SALE

Contract conditions B1AIPPEG recommendations: enclosure A B2AIPPEG recommendations: enclosure B B3AIPPEG recommendations: enclosure C B4

CONSTRUCTION DETAILS

Construction detail for curved panel C1Construction details for polyurethane panels C2Construction details for mineral fibre panels C3

Page 6: Isopan Man Tecnico GB

A - SANDWICH PANELS

Introduction A1

Raw materials A2

Characteristics of the polyurethane insulation A3

Product technical specifications A4

Fitting the panels A5

Insulating panels in mineral fibre A6

Certification A7

Page 7: Isopan Man Tecnico GB

INTRODUCTION

TYPESThe insulating panels produced by Isopan S.p.A. are monolithic, self-supporting sandwich panels,consisting of a layer of insulation between two facing skins. In terms of the diverse nature of thematerials used for these elements, these products can be divided into two principal families:

A1.1 THERMO-INSULATING POLYURETHANE PANELS:

THERMO-INSULATING POLYURETHANE PANELS FOR ROOFS• Isocop – 5 1000• Isoduplex 1000• Isotego 1000

THERMO-INSULATING POLYURETHANE PANELS FOR WALLS• Isotego 1000• Isopiano 1000; Isopiano 1155• Isorighe 1000• New Isoparete 1000• New flat Isoparete 1000

SINGLE-SKIN THERMO-INSULATING POLYURETHANE PANELS• Isogrecata 1000• Isodeck 40 1000• Isodoga 1000

The types of panel listed differ in respect of the external profiles of the facings, their static behaviour, theshape of the connecting joints and the uses for which they are designed. What they have in common isthe nature of the raw materials used: in particular, all the panels mentioned use an insulating layerconsisting of expanded polyurethane foam. When correctly mixed and controlled during the continuousproduction process, this confers on the product the property of outstanding thermo-insulating powerwhich is the distinguishing characteristic of this family of products.

A1.2 MINERAL WOOL INSULATING PANELS:

MINERAL WOOL PANELS FOR ROOFS• Isofire Roof 1000• Isofire Roof 1000 - Fono

MINERAL WOOL PANELS FOR WALLS• Isofire Wall 1000• Isofire Wall 1000 - Fono

A1.1

A1

Page 8: Isopan Man Tecnico GB

The panels in these last categories are of the sandwich type, monolithic and self-supporting, consisting oftwo metal skins, in steel (or on request, aluminium, stainless or copper), connected by an insulating layerin biosoluble high-density rock wool (100 – 110 kg/m3), with fibres oriented at right angles to thebearing surfaces. This type of panel is being used increasingly frequently in the construction of roofs andpanelling for industrial and public buildings, where there is a requirement not only for good thermalinsulation properties but also for a high level of fire resistance, to comply with strict fire safetyregulations. Isofire 1000 panels have certified characteristics for reaction to fire and resistance to firewhich are such as to make the product virtually incombustible (Class 0 for the outer skin and Class 1 forthe internal insulation and fire resistance ratings of R.E.I. 30 - 60 - 120). The panels are also availablein the sound-absorbing version, with micro-perforated facing, certified for its level of sound insulationand sound absorption.

A1.3 DIMENSIONAL STANDARDSThe panels offered by Isopan S.p.A. are produced with a standard modular width of 1000 mm, or inthe case of Isopiano, 1155 mm as well. The length, on the other hand, depends on the individual designrequirements of the customer. Please bear in mind, however, that the maximum length transportable byarticulated lorry is approximately 13.5 m, and this therefore represents in practice a dimensional limit,barring transport by special carriers. The thicknesses in production normally vary from 25 mm to 150mm and even 200 mm, according to the type, the nature of the bearing surfaces and the intended use.

A1.2

Page 9: Isopan Man Tecnico GB

RAW MATERIALS

A2.1 PRINCIPAL CHARACTERISTICS OF THE METAL FACINGS:Our panels use only top quality metal facings, with the following basic characteristics:• Steel, hot-dip galvanised by the SENDZIMIR process (UNI-EN 10147); no guarantees of resistance to

oxidisation or corrosion are offered beyond what is provided by the UNI standards or by thecorresponding European standards with regard to the gram weight per square metre of zincdeposited.

• Steel, galvanised and prepainted on continuous lines with cycles applying polyester resin, siliconisedpolyester and PVDF (polyvynilidene fluoride), on the outer side. On the inner side of the panel aprimer is applied.

• 3103 aluminium alloy with natural finish, embossed and prepainted with the cycles mentioned in theprevious paragraph. The natural aluminium facings are supplied with a primer applied to the innerside.

• Stainless steel AISI 304 (designation X5CrNi1810) to standard EN 10088-1.• Copper (for the ribbed side).• Especially in the use of facings in copper and aluminium, we recommend paying attention at the

design stage to the environmental conditions to which the product will be exposed, particularly directexposure to the sun and maximum temperatures reached, taking into account the characteristics of thematerial: in this regard, the Isopan Technical Office will be able to provide useful information toanyone who requests it.

The choice of organic coating to go with the metal facing depends on the environment in which theproduct will be installed. For explanation, please see the table below, which identifies the best coating inrelation to the environmental exposure. Isopan metal facings are required to comply with the strictestEuropean standards:• for Steel: UNI EN 10143, UNI EN 10147• for Stainless Steel: EN 10088-1, EN 10088-2• for Aluminium: UNI EN 485-4• for Copper: UNI 9329

A2.1

A2

Laboratory tests are carried out in accordance with the test methods laiddown by the European Coil Coating Association (ECCA)

Phosphating

Primer

Finishing coat of paint

Phosphating

Primer or back coat

Hot dip galvanising

Hot dip galvanising

Cold laminate steel

Page 10: Isopan Man Tecnico GB

A2.2 PROTECTION OF PREPAINTED BEARING SURFACESAll prepainted metal facings are normally supplied with a polythene film on the ribbed side, which helpsto avoid damage to the paint layer during the process of handling, transport and installation. If thematerial is specifically requested without the protective film, ISOPAN will not be held responsible for anydamage to the paintwork. On request, protection is also available on the inner side (lower face) of thepanel. The protective film covering the prepainted panels must be completely removed at the installationstage, and at all events not later than three months from the date of readiness of the materials. It isemphasised that Isopan S.p.A. will not accept responsibility for any abrasion of the prepainted bearingsurfaces attributable to the lack of the protective film (due to the load sliding during transport, forexample).

A2.3 EXPANDED POLYURETHANEThe word 'polyurethane' is normally used to denote a very heterogeneous family of plastics. Theparticular types used in thermo-insulating sandwich panels are expanded polyurethanes. An expandedmaterial is one which displays a cellular structure where the solid constituent, generally called thepolymer matrix, forms the walls of a complex of cells which may be closed or open, containing agaseous constituent of varying composition. All expanded polyurethanes are the product of the reactionof two or more liquid components which, when suitably mixed together, give rise in a relatively shorttime to the finished product.

A2.4 COMPOSITION OF THE FORMULAEGenerally speaking, polyurethanes are thought of as the product of the reaction of two componentscalled:component A = polyol mixture/polyol

A2.2

Guide to the choice of coating

Selection on the basis of exposure

INDUSTRIAL AND URBANMIXED OR CLEAN AND DAMP HOSTILE

RURAL NON- NORMAL HARD MARINE SPECIAL DRY

EXTERIOR INTERIOR

TYPE

IDEAL COATING

IDEAL CHOICE TO BE AGREED AFTER CONSULTATION WITH SUPPLIER

SUITABLE COATING

polyester PS

siliconisedpolyester PX

Page 11: Isopan Man Tecnico GB

component B = isocyanate

a) COMPONENT A - polyolIn addition to polyols, the polyol mixture is made up of catalysts, intermediaries to the reaction andexpanding agents.Polyols: these are particular chemical compounds characterised by the presence in their molecule of so-called hydroxide groups (-OH groups). These are oligomers with variable molecular weights andstructures. They are the product of the reaction between propylene and ethylene oxides and polyalcoholsor sugars such as saccherose and sorbitol.Catalysts: substances which act as promoters of the polymerisation and/or expansion reactionaccording to their composition. Generally these consist of aliphatic amines which are present in theformulation in relatively small quantities compared to the polyol.Stabilisers: they are generally called silicones and their function is to regulate the cell-structure as itforms, in order to obtain minimal and constant cell diameters.Fire retardants: halogenated and/or phosphorated compounds which act as flame retardants andtherefore regulate the reaction to fire of the expanded material when it is subjected to the action of flameor a source of intense radiant heat.Expanding agents: expanders in their turn may be divided into two families according to whether theexpansion involves a chemical reaction or a simple transformation of a liquid into a gas. We willtherefore speak of chemical expanders and physical expanders.

b) COMPONENT B - isocyanateComponent B is an isocyanate which normally belongs to the family of the so-called MDI polymers. Anisocyanate is distinguished by the presence in its molecule of isocyanic functional groups (NCO groups)and MDIs (diphenyl methane diisocyanates). These consist of 4,4’ diphenyl methane diisocyanate and itshigher oligomers.

A2.3

Page 12: Isopan Man Tecnico GB

A2.5 EXPANSIONExpansion is a process which occurs at the same time as the formation of the polymer matrix and iscaused by a gas being given off during the course of the reaction. The evolution of the gas can occureither as a result of a chemical reaction, or because of a change of state in a liquid with low boiling-point. We will therefore speak respectively of chemical expanders or physical expanders. It is the latterwhich concerns us.The physical expander is represented by a liquid with a boiling-point normally below 50°C. Thepolymerisation reaction is exothermic, and causes an increase in temperature in the reacting mass andthe low-boiling expander dispersed in it.Until a few years ago, the physical expander universally used was CFC 11, because of its convenientboiling-point, its low toxicity, its reasonable price, its non-flammability and above all its excellentinsulating properties. Unfortunately, it was discovered that it bears a considerable responsibility for thedestruction of the ozone in the upper reaches of the atmosphere, where it accumulates, preciselybecause of its stability, and in conjunction with ultra-violet radiation, tends to destroy the ozonemolecules. The discovery of this negative effect on the environment led to a process of replacing it with asubstitute, under the control of strict regulations on the protection of the ozone layer.The process has now been completed, and CFC 11 and HCFC have been replaced by expanding agentswhose molecular structure no longer contains chlorine, which is responsible for the interaction with theozone. The use of pentane and its isomers represents the best compromise in the direction of full respectfor the environment. The problems relating to flammability have been satisfactorily resolved. The costshave been high, but sustainable.

A2.4

Page 13: Isopan Man Tecnico GB

CHARACTERISTICS OF THE POLYURETHANE INSULATION

A3.1 DENSITYWhen considering the finished product, and also when considering free expansion, it is important todistinguish between total density and density at the core.‘Total density’ refers to the total volume of expanded material including the skin. In the case of asandwich panel, it is obtained by subtracting the weight of the facings from the weight of the completepanel and dividing the value obtained by the volume of the foam alone. The core density, on the otherhand, is obtained by eliminating the skin or high-density area of the foam from the calculation. Thedensity is a very important parameter because it has a direct influence on most of the physical andmechanical characteristics of the foam.

A3.2 CELL-STRUCTUREThe features of the cell-structure are the diameter of the cells, their shape and their uniformity. Talkingabout a rigid foam implies a structure which is predominantly closed-cell.The cell diameter can be estimated roughly by visual comparison with a standard sample, and assessedexactly by means of microscope images and subsequent computerised analysis. In the majority of cases,when shape and uniformity are within normal limits, the cell diameter is between 200 and 300 microns.Thermal conductivity is linked with cell diameter, but with variations which are relatively unimportant.The shape and uniformity of the cells are also characteristics which must be taken into account, as theycan be responsible for appreciable deficiencies in performance of the finished product. They are also anunequivocal index of the quality of the production process and of the correctness of the formulation.Briefly, we can say that a good cell structure is characterised by:

• a uniform appearance• absence of zones of discontinuity easily visible to the naked eye (bands of different colours)• absence of highly elongated or “stretched” cells, as they are known.

A3.3 RESISTANCE TO COMPRESSIONThe application of an external force deforms the cell-structure until it collapses completely. Normally, theresistance of a rigid foam to compression is calculated on the basis of the force necessary to induce adeformation of 10% and is expressed in kg/cm2 or in dimensionally equivalent units.In practice a test-piece of standard dimensions, generally 50x50x50 mm, is subjected to compressionbetween two flat surfaces, connected to a dynamometer, which move at a preset speed. A graph is thendrawn up in which the curve plots the deformation against the force applied. Compression resistance isaffected by the following factors:

• characteristics inherent in the formulation• the density of the foam• the orientation of the cells• the quality of the cell-structure.

Resistance to compression is a very important characteristic because it is directly linked to thedimensional stability of the foam when subjected to particular operating conditions.

A3.1

A3

Page 14: Isopan Man Tecnico GB

Accumulated experience tells us that for a sandwich panel we need to be sure of a minimumcompression resistance of 1 kg/cm2.

A3.4 DIMENSIONAL STABILITYBy ‘dimensional stability’ we mean the capacity of the foam to maintain its dimensions unchanged overtime and in actual conditions of use. Several factors, including temperature differences, diffusion of thegas contained in the cells, permeability to air, and operating conditions, give rise to forces acting inthree dimensions which, if not adequately opposed, can lead to irreversible deformation. Generally,dimensional stability is measured by accelerated tests where samples of known dimensions are subjectedto high temperatures (70-80°C, sometimes associated with high relative humidity in the air) and lowtemperatures (-25/-30°C) for a period of time (24-48 hours or more) and the variations which the foamundergoes in the three dimensions and in total volume are recorded, expressed as percentages of theoriginal dimensions.

A3.5 REACTION TO FIRE‘Reaction to fire’ is defined as the behaviour of the foam when exposed to the action of a flame or ofradiant heat. Reaction to fire is assessed on the basis of tests which simulate exposure to fire and radiantheat, carried out on samples of fixed shape and dimensions, in accordance with strict rules, thoughthese unfortunately vary from country to country. The reaction is then observed by measurement of:

• speed of propagation and maximum height of the flame• time required for extinguishing it• area damaged• occurrence of dripping.

Reaction to fire is controlled by making changes at the formulation level, with suitable additives, and atthe level of design and manufacture of the finished product. The results of the tests, which are specific tothe individual country, are used to assign products to classes of fire resistance. It must always bespecified whether the tests concerned just the foam or the finished product.

A3.6 WATER ABSORPTIONThis is a measure of the quantity of water that the foam can absorb by direct immersion in water. Sincewe are dealing with a material with predominantly closed cells, this value is always very small (<1%). Itcan be easily verified that the only cells involved are the ones cut in the process of preparing the sample.

A3.7 THERMAL CONDUCTIVITYThe thermal conductivity of a material is its capacity to transport heat from one surface to another.It is expressed in terms of the variable λ (lambda), with W/mK as the unit of measurement. The thermalconductivity of a foam is principally linked to the composition of the gas contained in the cells, and totheir size, and also to some extent linked to the nature of the polymeric matrix. In every case, thecomposition of the gas contained in the cells is the determining factor, and we can state positively that,next after a vacuum, pentane is actually among the best insulators (7.4 mW/mK). CO2 (15.3 mW/mK)and air (25 mW/mK) turn out to be among the worst.

A3.2

Page 15: Isopan Man Tecnico GB

A3.3

A3.8 MIXING OF THE COMPONENTSPolyurethane systems for continuous panel manufacture are generally supplied as a multi-componentsystem. It is essential to be able to adjust the expansion and catalysis to suit working conditions and thetype of panel being produced: for relatively thin panels (30-40 mm) we will have a high catalyst andexpander content, while for thick panels (120-200 mm) we will have a lower content of catalyst andexpander.A polyurethane system normally consists of the following components:

• polyol (polyols + stabilisers + fire retardant)• one or more catalysts• one or more expanders• isocyanate.

The polyol is first premixed with the expander and the catalyst. This mixture and the isocyanate are thensuitably measured out and transferred to the distribution location. It is here that the process of high-pressure mixing takes place. The temperature of the components has a considerable influence on theviscosity, and can therefore affect the quality of the mix, so it must be kept under constant control. Apoor quality mix is indicated by the presence of brown streaks, a coarse cell-structure and a ‘glassy’look to the foam.

MATERIAL

Polyurethane in panels with metal facings, UNIPLAST 517Polyurethane in panels with semi-permeable facings, UNIPLAST 9051Polyurethane in slabs cut from blocksPolyurethanes in slabs cut from blocksPolyisocyanurates in slabs cut from blocksExtruded expanded polystyrene, with skinIn situ expanded polystyreneExtruded expanded polystyrene, with skinGlass fibre – rigid panelsMineral fibres from feldspathic rocks – rigid panelsGlass fibre – semi-rigid panelsMineral fibres from feldspathic rocks – semi-rigid panelsSintered expanded polystyrene, in slabs cut from blocks, UNI 7819Expanded polystyrene in slabs moulded by thermocompressionExtruded expanded polystyrene, without skinPhenolic resins in slabsSintered expanded polystyrene, in slabs cut from blocksCork – expanded with bindersMineral fibres from basaltic rocks – felts on metal meshSintered expanded polystyrene, in slabs cut from blocksPhenolic resins in slabsPure expanded cork and cork expanded with bindersSintered expanded polystyrene, in slabs cut from blocksGlass fibre – resinated feltsUreic resins expanded in situExpanded cellular glassLow-volume loose materials – cellulose fibreSlabs composed of expanded perlite, fibre and bituminous bindersLow-volume loose materials – expanded vermiculite in granules from 0.1 mm to 12 mm

Thermal conductivity of the most important insulating materials

Page 16: Isopan Man Tecnico GB

A3.4

A3.9 ENVIRONMENTThe environmental impact of the products at the present time is of large and growing importance, in asociety conscious of the need to safeguard its natural resources. The manufactured products of IsopanS.p.A. have for some time been compliant with the strictest standards and legislative requirements whichhave been enacted in this field.

As regards the polyurethane foams used, we emphasise the following characteristics:• They are self-extinguishing in terms of standard ISO 3582 (formerly ASTM 1692).• Ozone: in compliance with the limits for safeguarding the stratospheric ozone agreed by the signatory

countries to the Montreal Protocol and European regulation 3093/94.• Classified in Group 3 of the I.A.R.C. (Lyon Institute for Cancer Research) This means that the

polyurethanes come under the heading of NON-CLASSIFIABLE AGENTS as regards their capacity forcausing cancer in man and animals. (“This classification reflects the fact that the numerous testscarried out to date have not indicated any carcinogenic or mutagenic effects on man or animalsderiving even from prolonged physical contact with polyurethane foams.”)

In the case of sandwich panels with a core of rock wool, we have the following characteristics:• Biosoluble inorganic material, free of asbestos, crystalline silica and CFCs and HFCs.• Material classified in Group 3 of the I.A.R.C. (Lyon Institute for Cancer Research).

Finally, as regards the external bearing surfaces such as the metal components, we have the followingcharacteristics:• Prepainting in conformity with current Italian regulations on the contact of materials with foodstuffs

(Ministerial Decree 21/03/1973 and subsequent amendments on hygienic discipline regardingpackaging, containers and utensils intended to come into contact with foodstuffs or substances forpersonal use). This certification relates to colours Grey White, White 21, plain white similar to Ral9010 and Top Class PVC coating.

Waste disposal:in terms of current Italian legislation (Legislative Decree 22/97; Ministerial Decree 5/2/98 and updatesand amendments), the “Residues of insulating materials in C.E.R. 170604 panels” have been certified as“special non-hazardous waste” intended for recycling (R4, R13) or, here this is impossible, suitable forwaste disposal in the normal way. The Safety Data Sheet for theinsulating panels is available on request,but this is purely of an informative nature, since the product is not considered “hazardous” and does notcome within the scope of Ministerial Decree 28/01/92 (Official Gazette no. 50 of 29/02/92,supplement no. 46).

Page 17: Isopan Man Tecnico GB

A4.1

A4 PRODUCT TECHNICAL SPECIFICATIONS

The following are the Technical Product Specifications of Isopan panels.

A4.1 TYPES AND INTENDED USESThere are the following categories:• Insulated metal roofing panels for industrial and civil buildings (category: roofing panels)• Insulated metal panels for infill, walls and suspended ceilings of industrial and civil buildings

(category: wall panels)• Single-skin insulated metal panels (category: single-skin panels)The latter category has very specific intended uses, summarised here:a) ISOGRECATA 1000. Single-skin insulated metal panel for pitched roofs on industrial and civilbuildings, with the lower skin in aluminium foil.b) ISODECK 40 1000. Single-skin insulated metal panel for pitched or flat roofs with outer facing inbituminised paper, for covering with an outer layer of bituminous membrane.c) ISODOGA 1000. Single-skin insulated metal panel for suspended ceilings and infill panels, with theupper skin in aluminium foil.

A4.2 DIMENSIONAL CHARACTERISTICSRoofing panels:• Length: as requested by customer up to the maximum transportable• Useful width/spacing: 1000 mm• Thickness outside ribs: 30, 40, 50, 60, 80, 100, 120 mm• Height of ribs: 40 mm• Spacing of ribs: 250 mm (500 mm for Isotego 1000)• Lower bearing surface: micro-ribbed.

Wall panels:• Length: as requested by customer up to the maximum transportable• Useful width/spacing: 1000 mm• Thickness: 30, 40, 50, 60, 80, 100, 120, 150 - 200 mm• Bearing surfaces smooth or micro-ribbed

Single-skin panels:• Length: as requested by customer up to the maximum transportable• Useful width/spacing: 1000 mm• Thickness outside ribs (excluding Isodoga 1000): 30, 40, 50, 60, 80 mm• Height of ribs (excluding Isodoga 1000): 40 mm• Spacing of ribs (excluding Isodoga 1000): 250 mm• Lower bearing surface: aluminium foil (excluding Isodeck 1000), thickness 0.07 mm• Upper bearing surface (Isodeck 1000 only): bituminised paper 350 g/m2.

Page 18: Isopan Man Tecnico GB

A4.2

A4.3 INSULATION• Composed of rigid polyurethane foam, self-extinguishing in accordance with current Europeanstandards

• Reaction to fire Class B2 or B3 in terms of DIN standard 4102 part 1• Average density 40 kg/m3 ± 10%• Compression resistance ≥ 11 N/ cm2 (at 10% deformation)• Resistance to stretching ≥ 1 N/ cm2

• Resistance to cutting ≥ 1 N/ cm2

• Coefficient of thermal conductivity I=0.022 Kcal/m.h.°C• Non-hygroscopic because made up of over 95% closed cells• Coefficient of heat transmission:For single- and double-skinned roofing panelsThickness (mm) 30 40 50 60 80 100 120

Coeff. K (W/m2*°C) 0,55 0,44 0,36 0,31 0,25 0,20 0,16

Coeff. K (kcal/h*m2*°C) 0,48 0,38 0,32 0,27 0,22 0,17 0,13

For single- and double-faced walling panels

Thickness (mm) 30 40 50 60 80 100 120 150

Coeff. K (W/m2*°C) 0,64 0,50 0,40 0,34 0,26 0,21 0,18 0,14

Coeff. K (kcal/h*m2*°C) 0,57 0,44 0,35 0,30 0,23 0,18 0,15 0,12

A4.4 LOAD-BEARING CAPACITYThis depends on the type of metal bearing surface, its thickness and the thickness of the layer of thermalinsulation, as stated in the tables in the specific product catalogues. Load-bearing capacities refer to the

860 mm Bricks380 mm Concrete140 mm Timber50 mm Cork45 mm Fibreglass40 mm Polystyrene25 mm Polyurethane

COMPARATIVE TABLE OF INSULATING MATERIALS

Equivalentthermal

insulation

Page 19: Isopan Man Tecnico GB

A4.3

panel fitted horizontally and under the action of a distributed load.If, in view of the climatic conditions in the place of installation, the designer thinks a detailed check isdesirable into the stresses caused by thermal action in the long term, he can refer to the ISOPANTechnical Office. It remains the responsibility of the designer to check the adequacy of the fixing system,with regard to the number and arrangement of the fixing points.

A4.5 TOLERANCES• Thickness of the facings: in accordance with the reference norms for the products used• Thickness of the panel: ± 2 mm• Length: ± 5 mm• 1000 mm module: ± 2 mm• Out-of-square: max 3 mm• Flatness: L= distance between the extremes of measurement, s= deviation

With L = 300 mm, s = 1%. With L > 300 mm, s = 3 mm max.

Page 20: Isopan Man Tecnico GB

A5.1

FITTING THE PANELS

A5.1 EQUIPMENT NECESSARYBelow is a list of the equipment needed on site for fitting the panels.

1) PORTABLE DRILL and drill-bits

2) ELECTRIC SCREWDRIVER with direction reversing, and thenecessary collets.We recommend the use of a screwdriver equipped with a torquelimiter. This means that the strain on the shank of the screws can beregulated so as not to damage the panel in the process of fitting.

3) JIG SAW

4) POP RIVETER and rivets

5) Series of PLIERS (locking and universal)

6) SHEARS for small manual adjustments to the panels

7) CLUB HAMMER

8) SCRAPER

9) PLUMB LINE to check the verticality of wall panelling

A5

Page 21: Isopan Man Tecnico GB

10) FASTENERS AS SPECIFIED IN THE DESIGN OR ORDER

11) POSSIBLE LIFTING-BEAM WITH CLAMPS OR SUCKERS for moving large-sized panels

12) VACUUM CLEANER

A5.2 FITTING TO ROOF (EXCLUDING ISODOGA 1000):In order to ensure that the water runs off correctly, and to avoid oxidisation of the metal supports whichcan otherwise follow, roofing panels must be laid with a minimum slope of 7%. In the case of pitchesconstructed with more than one panel lengthways, a longitudinal overlap must be provided, sufficient (inrelation to the slope) to avoid any ingress of water. In accordance with UNI 10372, ISOPANrecommends providing sufficient projection at the eaves to allow a suitable drip and prevent any ingressof water into the insulation or the inside of the building. After completing the fitting of the panels and thenecessary flashings, check carefully that no extraneous materials or residues from the job areabandoned on the roofing panels which could give rise to corrosion or prevent rainwater running offcorrectly, or cause a buildup of undesirable and harmful substances. In the accompanying illustration weshow examples of fitting roof panels in situations involving laps (overlapping longitudinal joints). Asregards flat roofs,Isopan’s recommen-dation is the Isodeck1000 panel, whichmust be laid with theribs facing downwardsand the side faced withbituminised paperfacing upwards. This inits turn is completedwith a finishingcovering in bituminousmembrane whichcompletely waterproofsthe building.

A5.3 FASTENERS ANDPRINCIPLES OF FIXINGThe type of fixingdepends on the type ofsupport used. Normally, self-tapping screws are used (also called ‘thread-forming screws’). Standardfixing is by means of 6.3 mm diameter self-tapping screws in galvanised carbon steel with hexagonheads, of the type “Kovervit BS 592”, or “592” and washer in galvanised steel incorporating a gasket inEPDM rubber to maintain the seal. If specifically requested, as an alternative to the self-tapping screwsdescribed above, ISOPAN can supply another two series of screw designated ‘self-drilling’ of type

A5.2

Strips of silicone material or gaskets

Prevailing winds

SLOPES OF 7 - 10%

SLOPES OF 11 - 13%

SLOPES OF 14% AND ABOVE

DIAGRAM OF SECTION AT

THE LAP

Page 22: Isopan Man Tecnico GB

A5.3

“Kovervit 671”, which have the advantage of reducing fitting time, as the hole is drilled and the paneldirectly anchored all in one operation. These screws, which are ideal for fixing to heavy steel sections,require specialised skills for their use, and correct torque adjustment on the power screwdriver used onsite.

ISOPAN will be happy to deal with any query from customers about the various fixing systemsdescribed, their mechanical performance and their methods of use. The principles of fixing are set outbelow:

A5.3.1 Fixing for roofing panelsThe panels should be installed with the direction of laying opposite to that of the prevailing winds,checking frequently that they are parallel and correctly aligned. They should be fixed to the supportingstructure by means of the devices specified by the system, both for timber and for metal roofframeworks. The holes must have a diameter smaller than that of the fixing device; these must not befully tightened, to allow the panel to expand and contract as a result of temperature and moisturechanges. The number of fixings required varies with the local climate situation. In the course of staticdeflection tests with positive and negative loads, we have defined the “normal density” for fixings as:one bolt on alternate ribs on the central purlins and one on every rib on the end purlins. This density hasbeen assumed as standard in determining the positive and negative overload threshold. The minimumfixing density is therefore one fixing on alternate ribs in the continuous part of the roof and one fixing onevery rib round the perimeter of the sheets, and in particularly windy areas, in the central part as well.

washer and cap in sheet metal

Page 23: Isopan Man Tecnico GB

Layout for normal and increased density of fixings

A5.3.2 Fixing for wall panelsThe panels must be anchored to continuous metal sections running at right angles to the direction of thepanels themselves, and these members in their turn must be adequately secured to the loadbearingstructure of the building in accordance with the conditions specified in the design as regards stability.The width of the support in contact with the panel must be not less than 50 mm. In the case of an end-to-end joint between two panels, the contact width must be 80 - 100 mm. The minimum width of thesupport area at the end of each panel must be an effective 30 mm in contact with the supporting framemembers. The panels should be fixed to the loadbearing structure by means of the fasteners specified bythe system. The number of fixings varies in accordance the different climatic situations in which thebuilding may be located. Normally, every panel requires the use of one fixing opposite each supportingmember. In areas which are particularly exposed to the action of the wind, the density of the fixings mustbe determined by the designer case by case, appropriately increasing the number of fixings from thestandard specification.

Layout for normal and increased density of fixings

A5.3.1

INCREASED

STANDARD

INCREASED

STANDARD

Panel (1 m)

Leng

th -

L

Panel (1 m)

Leng

th -

L

Page 24: Isopan Man Tecnico GB

A5.4

A5.4 INSTRUCTIONS FOR HANDLING, STORAGE AND TRANSPORTThe panels are supplied packaged and with an overall wrapping of stretch polythene film. On requestthey can be supplied in packaging with metal protective strips or in cardboard, with a view topreventing possible damage to the outer panels from contact with the arms of forklift trucks used tounload the products.The standard composition of the pack is as indicated below.Contents of one pack of sandwich or single-skin roofing panels:

Panel thickness (mm) 30 40 50 60 80 100 120

No. of panels per pack: 14 12 10 8 6 6 5

Contents of one pack of sandwich or single-skin wall panels:

Panel thickness (mm) 30 40 50 60 80 100 120 150 200

No. of panels per pack: 17 18 14 12 9 7 6 6 4

If packs with different composition from standard are required, this must be explicitly requested at thetime of ordering.

The height of the packs (in millimetres) depends on the number of panels, as in the following tables:Sandwich or single-skin roofing panelsISOCOP-5 1000 - ISODUPLEX 1000 - ISOTEGO 1000 - ISOGRECATA 1000 - ISODECK 1000

30 14 700 6 x 1440 12 720 6 x 1250 10 700 6 x 1060 8 640 4 x 8 + 2 x 1070 8 720 6 x 880 6 600 4 x 6 + 2 x 8

100 6 720 6 x 6120 5 700 6 x 5

Note: Each pack rests on strips of polystyrene with a thickness of 70 mm (not included in the statedheight of the pack).

Panel thickness (mm) No. of panels per pack Height of pack (mm) Packs per load

Page 25: Isopan Man Tecnico GB

Sandwich or single-skin wall panelsISORIGHE 1000 - ISOBOX 1000 - ISOPIANO 1000 - N. ISOPARETE 1000 - N. ISOPARETE PIANO1000 - ISODOGA 1000

Spessore pannello (mm) N. pannelli per pacco Altezza pacco (mm) Pacchi per caricoPanel thickness (mm) No. of panels per pack Height of pack (mm) Packs per load

25 21 525 8 x 2130 17 510 8 x 1735 15 525 8 x 1540 18 720 6 x 1850 14 700 6 x 1460 12 720 6 x 1280 9 720 6 x 9

100 7 700 6 x 7120 6 720 6 x 6

Note: Each pack rests on strips of polystyrene with a thickness of 70 mm (not included in the statedheight of the pack).

The weight of the packs varies, not only with the thickness of the insulation, but also with the length atwhich the panels are supplied, as well as with the type and thickness of the metal supporting face.

A5.5 LIFTING AND HANDLINGa) LIFTINGThe packs must always be lifted by means of slings positioned at a minimum of two points separated bya distance not less than half the length of the pack itself (§7.4 of Standard UNI 10372). The slings mustbe made of synthetic fibre (nylon or high-strength polyester), at least 200 mm wide, as shown in thedrawing. We recommend using suitable spacers consisting of wooden boards or polystyrene packingabove and below the pack, to avoid direct contact between the slings and the pack.

A5.5

Panel thickness (mm) No. of panels per pack Height of pack (mm) Packs per load

Page 26: Isopan Man Tecnico GB

A5.6

b) HANDLINGManual moving of individual panels must be performed by at least two people, keeping the panelupright as illustrated. Suitable protective equipment must be used (gloves, safety shoes, overalls etc.) incompliance with current regulations.

Panels over a certain size (4 metres in the case of a panel of thickness 80-100 mm) must be moved bymeans of a suitable hoist or crane, as the weight of the panel makes it impossible to move by hand. Thepanel is attached to the chosen mechanical lifting gear by a lifting-beam with two or more clampsconnected to it by cables. The clamps grip the edge of the panel itself. A lifting-beam equipped withsuckers is a satisfactory alternative.Note: In the case of any eventuality not covered above, the AIPPEG Recommendations (attached) apply.

Clamp for lifting panels Schematic drawing of lifting-beam with suckers

Spring Steel cable

Page 27: Isopan Man Tecnico GB

A5.6.1

A5.6 INSTRUCTIONS FOR FITTING

A5.6.1 Preliminary information1) Check that the storage on site is in compliance with the procedures described in the AIPPEGrecommendations.2) Check that the framework corresponds to the working drawing.3) Check that the entire site labour-force is equipped with safety footwear, gloves etc, and that the sitehas all the equipment necessary to ensure safety in accordance with current regulations.

A5.6.2 Preparation of the panelsRemove the polythene protective film from the panel before fitting it.Check that the surface of the panel does not have traces of adhesive remaining from the protective film.If necessary, use a solution of detergent in water to remove it.

A5.6.3 Fitting sequences for Isopan panels – wall panels:The correct sequence for fitting Isopan wall panels is as set out below.1) Fix the base metalwork (where required) at the foot of the wall, and also the metalwork which has tobe installed before the wall, such as drips, connectors for the roofing, corner connectors etc.2) Remove the protective film from the panels, as mentioned in the preliminary information.3) Fit the panels starting from the foot of the wall, taking care to execute joints correctly and to makesure the panels are upright.4) Secure the panels only after checking that they are perfectly lined up. The fixing screws must alwaysbe inserted at right angles to the panel.5) Fit the finishing components (corner strips, perimeter edging etc.).6) Carry out a general inspection and cleaning of the wall, paying particular attention to the fixings andthe joints with the door and window frames.

A5.6.4 Fitting sequences for Isopan panels – roofing panels:1) Start at the bottom and work upwards, finishing at the ridge.2) Fit gutters, sealing caps and rainwater flashings.3) After fixing the first row of panels, working away from the direction of the prevailing winds, lay thesucceeding panels, superimposing the hollow rib on the solid rib of the panel already laid, and gentlyrotating the panel (see diagram).

Page 28: Isopan Man Tecnico GB

A5.6.2

Manoeuvre for assembling the panels

A5.6.5 Cutting the panelsThe operation of cutting the panels comprises the following stages:1) Protect the area affected by the cut with adhesive tape.2) Use a panel to mark the required cut on the tape.3) Make the cut with a jig saw (equipped with dust extraction and filtration), following all theprecautions and safety procedures specified by current regulations.4) Remove the swarf produced by the cut because it can scratch the paintwork of the panel itself, andtherefore impair its long-term durability.5) Remove the protecting adhesive tape.

Page 29: Isopan Man Tecnico GB

INSULATING PANELS IN MINERAL FIBRE

• Isofire Roof 1000• Isofire Wall 1000• Isofire Roof Fono 1000• Isofire Wall Fono 1000

A6.1 TYPES AND INTENDED USESPanels designed for use on pitched roofs (Isofire Roof 1000) and in walls (Isofire Wall 1000).Characterised by a core of mineral fibre which guarantees the incombustibility of the product besidesensuring excellent thermal insulation. The “Fono” versions are expressly designed for sound insulation.The panels were created to satisfy the growing demand for improved performance in fire behaviour,while maintaining good mechanical characteristics.These panels have been tested at the Istituto Giordano S.p.A., obtaining the following certification:• Class 0/1 reaction to fire (in terms of Ministerial Decree 26/06/84);• Fire resistance: R.E.I. 30 / R.E.I. 60 / R.E.I. 120, depending on the thickness (in terms of Interior

Ministry Circular 91, 14/09/61);• Sound insulation to ISO 140 1995 and ISO 717 1996, and sound absorption to ISO 354 1985, for

Fono version.

Sound-absorbing panel

Note: our advice is that the longest mineral fibre panel which can sensibly be moved is 6000 mm.

A6.2 DIMENSIONAL CHARACTERISTICSOn this subject, please refer to the sections on roofing panels and wall panels in paragraph A4.2.

A6.1

A6

Page 30: Isopan Man Tecnico GB

A6.2

A6.3 OVERLAPSThere is no gasket provided for the longitudinal overlap joint, because the mineral wool must form asingle continuous insulating layer, to guarantee the specified incombustibility and fire resistance.In the case of transverse (overlapped) joints, incombustible (Class 0) tape and gaskets must be fitted inorder to ensure a perfect seal and complete impermeability without invalidating the fire-retardantproperties of the panel. On roofing panels, the overlap must be achieved using the same procedures ason polyurethane panels, cutting away part of the insulation of the upper panel.

Arrangement for the overlap

Note: please refer to the following chapter for an appropriate description of the properties of this type ofpanel, which merits detailed analysis, especially in connection with the evolution of the legislation on firesafety and prevention.

A6.4 TOLERANCESOn this subject, please refer to paragraph A4.5.

A6.5 INSULATIONISOFIRE ROOF 1000

Panel thickness (mm) 50 60 80 100

Coeff. K (W/m2*°C) 0,72 0,55 0,44 0,36

Coeff. K (kcal/h*m2*°C) 0,64 0,48 0,38 0,32

ISOFIRE WALL 1000Panel thickness (mm) 50 60 80 100

Coeff. K (W/m2*°C) 0,75 0,64 0,50 0,40

Coeff. K (kcal/h*m2*°C) 0,67 0,57 0,44 0,35

LEFT-HAND TYPE PANELRIGHT-HAND TYPE PANEL

Total length

Reduced length

Overlap

Page 31: Isopan Man Tecnico GB

A6.3

A6.6 R.E.I. PANELSThe ISOFIRE series of panels is specially designed for the construction of rooms where fire can safely bekindled, and conversely of rooms which are required to be protected from the attack of fire coming fromoutside sources.There is a variety of industrial uses for which ISOFIRE panels are particularly indicated, as for example:• Protection of escape routes• Fire escape stairs• Lifts• Fire barrier walls• Store rooms• Suspended ceilings• Clean rooms.In addition to the above, they can be correctly used for the creation of safe rooms or compartments inaccordance with the current regulations, particularly in terms of the “Definitions for the purposes ofAnnexe A of the Decree by the Interior Minister of 30/11/1983”, cited below:

A6.6.1 Fireproof Compartment:“Part of a building delimited by structural elements of a predetermined fire resistance, organised to fulfillthe requirements of the prevention of fires.”

A6.6.2 Smoke-proof filter:“Compartment delimited by structures with a predetermined R.E.I. fire resistance, in any event not lessthan 60 minutes, and provided with two or more doors equipped with self-closure devices with apredetermined R.E.I. fire resistance, in any event not less than 60 minutes, with a ventilation shaft ofadequate section, in any event not less than 0.10 m2, issuing above the roof of the building; orcompartment with the same fire resistance characteristics, maintained at an overpressure of at least 0.3bar, even in emergency conditions, or vented directly to the outside with unobstructed openings havingan area not less than 1 m? excluding ducts.”

A6.6.3 Smokeproof stair wells or protected stairs:“Protected staircase in well constituting a fire-resistant compartment having direct access from everyfloor with doors of R.E.I. fire resistance equipped with closing devices”. ISOFIRE panels are designed toprovide certificated high performance in fire resistance. (As provided by the current regulations, thecertification of the products, particularly for fire resistance, is effected by real furnace tests on limitedsamples of the product). These tests guarantee the R.E.I. value for the panels and their jointing(longitudinal joint) at the test dimensions.

Note: Obviously the standard trial is not carried out on the complete installation (every completedproject, however similar, has some unique and unrepeatable characteristics). In particular it cannot testthe actual situation at the junctions – panel/floor, panel/beams (of various materials), panel/ceiling andpanel/wall, or the various passageways for pipes, cables etc. It is therefore essential that the designertakes an engineering approach so that the intended performance can be guaranteed, especially as

Page 32: Isopan Man Tecnico GB

A6.4

Test of the efficacy of a portable extingui-sher on a hearth of type B (liquids)

Radiant panel for testing reaction to fire

TESTS FOR FIRE RESISTANCE

Vertical furnace 3000 x 3000 mm Horizontal furnace for testing loadbearingstructural elements and non-stressedfirestop elements

regards impermeability to flames, vapours and gases (E), and the thermal insulation (I) of the entiresystem.In reality, these qualities are more closely connected with the procedures followed in carrying out thework and assembling the components, than with the specific and individual characteristics of thesecomponents, important though these are.

A6.6.4 Fire resistanceISOFIRE insulated panels are certified in accordance with current national standards, in recognition oftheir performance in fire resistance, which contributes to the “R.E.I.” grading of the product. Followingthe definitions given in Point 1.11 of Annexe A of the Decree by the Interior Minister of 30/11/1983,we can provide an exact explanation of the terminology used in assigning the values and the variablesdescribed in the Decree. In particular, we draw attention to the following definitions:• Fire resistance: capacity of a construction element (component or structure) to maintain, for a fixedperiod of time:–• its stability “R”, the tendency of a construction element to retain its mechanical strength under theaction of fire;• its seal “E”, the tendency of a construction element when exposed to the action of fire on one side,not to let flames, vapours or hot gases pass, or produce them on the side not so exposed;• its thermal insulation “I”, the tendency of a construction element to reduce the transmission of heat.Accordingly:

Page 33: Isopan Man Tecnico GB

A6.5

• The symbol “R.E.I.” is used to identify a construction element which, to qualify, must maintain itsmechanical strength, its seal against flames and gas, and its thermal insulation, for a fixed period oftime.

• The symbol “RE” is used to identify a construction element which, to qualify, must maintain itsmechanical strength and its seal against flames and gas, for a fixed period of time.

• The symbol “R” is used to identify a construction element which, to qualify, must maintain itsmechanical strength for a fixed period of time.

In relation to the requirements which they have demonstrated, structural elements are classified by anumber, which represents the minutes. The time period for which the performance is guaranteed, in theclassification of elements not bearing the rating “R”, is automatically satisfied if criteria “E” and “I” aresatisfied.ISOFIRE panels have received the certification R.E.I. 30 / R.E.I. 60 / R.E.I. 120, depending on thedifferent thicknesses, when used as non-stressed partitions, as indicated in the certifications, which aredifferentiated as regards the models and as regards their uses as roofing panels (non-stressed) and asvertical dividers. In view of the large number of construction types in the panels, it is important whenusing and checking the certified performances in fire resistance, to correlate exactly the model of panelwith the certification obtained.For the detailed characteristics, always refer to the ISOPAN technical documentation. For example, the‘ROOF’ model of panel is certified both for use in roofing, and as a wall panel, but always with thespecification that the side which can be exposed to the fire is the flat side (without ribs).

The model ‘WALL’, on the other hand, can be used for possible exposure to the fire on both faces, butonly when positioned vertically in a wall. Strictly according to the standard, the certified performancesrefer to and are guaranteed only in the test conditions, which involve components of limited dimensionsassembled with the particular joint. It is the responsibility of the designer to justify in “engineering” termsthe extension of these performances to dimensions and procedures different from laboratory testconditions, particularly as regards length and therefore the scarcity of intermediate supports andbearings, and also as regards end-to-end joints, and the combination with other construction elements,especially structural members. As we have already stated, the object of this booklet is to supply thedesigner with advice and information to favour the identification of correct solutions and materials whichwill guarantee the fire resistance characteristics of the entire installation. The other components besidesthe panels, the structural elements in particular, must be able, in virtue of their composition, to resist firefor the necessary time.If this condition cannot be met, these structural elements must be treated with the usual protectivemethods (intumescent paints, insulating or intumescent plaster etc.) and checked by the designer forcompliance with the current applicable regulations, particularly Circular 91 and Standards CNVVF andUNI 9502, 9503 and 9504 etc.

A6.6.5 Outline of fire safety legislationThe use of ISOFIRE panels as elements resistant to fire is not structural, but aimed at contributing to thecreation of compartmentation, that is, a separation of zones to be protected or insulated (safe zones)from others where there exists a greater possibility of a fire starting, or, conversely, to delimit zones atgreater risk of fire.The principal aim of the panels in such applications is to retard the spread of the high temperature (and

Page 34: Isopan Man Tecnico GB

A6.6

therefore of the fire) and of the combustion gases, for a fixed length of time, allowing people, materialsand machinery to be brought to safety, and allowing action to be taken at the fire source itself before thefire spreads out of control. The Italian fire safety regulatory situation does not seem altogether systematicand functional, nor is it wholly consistent nor aligned with the legislation in other European countries. Alarge number of regulations have been drawn up or are in process of being drawn up, some of themlaying down new procedures for homologating materials and new systems and solutions for fireprotection.

A significant part of the legislation currently in force, which can be taken into consideration in theconstruction of partitions using ISOFIRE prefabricated panels, is listed below:• Circular 91 of the Minister of the Interior of 14 September 1961;• Ministerial decree of 30 November 1983 – “Terms, definitions and graphic symbols in fire prevention”

– which, among other things, defines fire resistance and the various R.E.I. characteristics;• Directive of the Council of the European Union 89/106/EEC of 21 December 1989, relating to

harmonisation of the various national regulations.In addition, for purposes of comparison and for the treatment of the structural components to which thepanels are attached, it may be useful to refer to the Standards:• UNI EN 10143, UNI EN 10147 for Steel• EN 10088-1, EN 10088-2 for Stainless Steel• UNI EN 485-4 for Aluminium

A6.6.6 Suggestions for making connections and jointsThis manual contains suggestions relating to the commonest cases of combining ISOFIRE panels withothers of the same type and with other building components. Naturally, the solutions put forward mustbe considered merely indicative, and require checking case by case. The joints which we need toconsider are the transverse joints, since the longitudinal joint in ISOFIRE panelling is tested in the trialsfor certification, and the characteristics required are thus guaranteed.In choosing the materials for fitting the products, it is important to remember that fire resistance must beensured by the construction materials used (panels, beams, columns etc.)Those elements among them which are not certified must be protected with guaranteed, certifiedmaterials (intumescent paints, intumescent or fire-retardant plaster etc.)

A6.6.7 Principal types of operationAlthough we believe that the attached sketches are sufficiently clear and simple to be understood and forthe principles to be extended to other similar cases, we describe some significant cases in the next fewparagraphs.

a) COMPARTMENTATION:

1 – Linking a vertical wall to the floor: the R.E.I. characteristics are ensured by the conformation of thewall (certified) and of the floor (concrete slab). Thermo-expanding seals (gaskets or sponge) arerecommended, which, by expanding under the influence of the flame or the temperature, tend toensure the seal. Smoke and gases are thus prevented from getting through any narrow gaps at the

Page 35: Isopan Man Tecnico GB

A6.7

joint, and consequently no uncontrolled rise in temperature takes place on the side not exposed to thefire.

2 – Linking a vertical wall to the ceiling: it is advisable to provide enough play to facilitate fitting and toabsorb deformation in the ceiling. In the case of a stressed slab or beam, the play provided must besufficient to absorb deflection in the stressed structure, taking its own deadweight into account. Thefire protection can be achieved by the use either of gaskets of suitable dimensions or of sponge ofappropriate thickness.

3 – Linking to elements different in type and composition from ISOFIRE panels (beams, slabs, columns inreinforced concrete, prestressed concrete, iron etc.): besides adequately protecting such elementswith specific fire-retardant products, take account of deformation which they may undergo as a resultof loading or thermal expansion. This can be achieved by providing sufficient free play and usingfire-retardant materials (seals, gaskets, felt etc.), which are thermo-expanding but sufficiently soft andelastic.

b) ITEMS CROSSING OR FITTED INTO THE PANELS:On the subject of pipes, ducts or cables passing through the ISOFIRE panels, or window-frames beingfitted into them, we list the commonest cases and the appropriate precautions to take to preserve the fireprotection characteristics of the panels:

1 – Combustible or heat-sensitive pipesWe suggest the following protection systems:• Recessed thermo-expanding collars, concentric with the pipes, set into the partition. It is importantto check the seal between partition and collar, caulking it if necessary with intumescent or fire-retardant mastic.• External thermo-expanding collars, concentric with the pipes, mounted visibly on one or both sidesof the partition: easy to fit, but aesthetically less pleasing than the preceding solution.• Intumescent tape, wrapped round the pipes and sealed with ceramic mastic or intumescent sealant.

2 – Small diameter plastic tubes carrying cablesFit collars in thin-gauge steel with a band of intumescent material of suitable thickness. Plug the cavityin which the cables run, following the procedure described below.

3 – Metal pipesSeal the gap with intumescent mastic. Alternatively, wrap the pipes with intumescent tape, and makethe final seal with intumescent or ceramic mastic or plaster.

4 – Electrical cables, single or in a compact bundleWrap with intumescent tape or fill with intumescent mastic or plaster.

5 – Open cable ductUse fire retardant thermo-expanding bags, or intumescent felt, combined with intumescent mortar orplaster, or infill with fire-resisting panels.

Page 36: Isopan Man Tecnico GB

A6.8

6 – Cable duct with coverSeal the spaces between the cables and inside the duct with intumescent sponge or mastic, and sealthe outside of the duct where it passes through the panel with intumescent or fire-retardant mastic orplaster.

7 – Air conditioning ductsWrap the ducts (not insulated and obviously fitted with firestop dampers) with intumescent felt ortape, sealing with intumescent or fire-retardant mastic or plaster

8 – Holes passing throughLarger-sized holes passing through the partition which cannot be sealed by the methods indicatedabove, must be closed by the usual methods or with other materials, such as for example panels inmineral wool treated with an intumescent or fire-retardant product, or intumescent, fire-resistant bagsetc. Particular care should be taken if fire-resistant mortar is used, because it will have a differentcapacity for deformation from the ISOFIRE panels, with a consequent risk of cracks and fissuresopening up.

9 – Doors and window-framesWhen positioning and installing doors and window-frames in firestop partitions formed with ISOFIREpanels, follow the instructions of the manufacturer of the frames. The model chosen must obviously becertified and consistent with the grade of fire resistance designed and guaranteed for the rest of thesystem.

Page 37: Isopan Man Tecnico GB

A7.1

A7 CERTIFICATION

Isopan panels have obtained technical approval from the strictest and most reputable internationalresearch institutes in Europe, charged with issuing such certification. In particular, the ITC, the ItalianInstitute for Construction Technologies, has issued Certificates of Technical Approval for our roofing andwall panels, while UGPU, the highly authoritative German Institute, has issued Approval for the panelsproduced by our plant at Patrica in Lazio. Many other European official bodies have certified the qualityof our manufactured goods, and also the compliance of the raw materials and the finished product withthe strictest standards of the individual countries and European standards. ISOPAN submits itselfperiodically to monitoring by the inspectors of the various Institutes, who oversee our production toensure that the Approval standard is maintained.Some of the best-known Certifications are illustrated below, with the corresponding attestations.Recently the list was increased by the addition of the Certificate of Conformity to the Standard UNI ENISO 9001:2000, which bears witness to the quality achieved in the production process for plain andribbed panels at the production plant in question.The ISOPAN Technical Office will be very happy to supply the list of the certificates available, and tosend out exact copies of the original.

Page 38: Isopan Man Tecnico GB

A7.2

A7.1 CERTIFICATES FOR POLYURETHANE PANELS

Page 39: Isopan Man Tecnico GB

A7.3

A7.2 ISOFIRE CERTIFICATION

Page 40: Isopan Man Tecnico GB

A7.4

Page 41: Isopan Man Tecnico GB

A7.5

Page 42: Isopan Man Tecnico GB

A7.6

A7.3 CERTIFIED ISO 9001:2000

Page 43: Isopan Man Tecnico GB

B - GENERAL TERMS OF SALE

Contract conditions B1

AIPPEG recommendations: enclosure A B2

AIPPEG recommendations: enclosure B B3

AIPPEG recommendations: enclosure C B4

Page 44: Isopan Man Tecnico GB

B

GENERAL TERMS OF SALEFOR RIBBED SHEETS,

INSULATED METAL PANELSAND ACCESSORIES

Contract Conditions

Enclosure ARegulations for transport, handlingand storage of corrugated sheets,

insulated metal panels and accessories

Enclosure BQuality standards for ribbed sheets

and insulated metal panels

Enclosure CRecommendations for the installation

of corrugated sheets and insulated metal panels

Page 45: Isopan Man Tecnico GB

B1.1

B1 AIPPEG RECOMMENDATIONS: CONTRACT CONDITIONS

1. PARTIES

The party hereinafter called the Vendor is the manufacturing company orthe company that provides and invoices the products hereof.

The party hereinafter called the Buyer is the receiver of the invoicesissued for the products hereof.

2. ORDER - ACCEPTANCE

The Buyer’s order shall be deemed a purchase proposal and shall beirrevocable for thirty days. The Vendor’s confirmation shall be deemed anorder acceptance and shall be the sole document binding the parties andgoverning all matters excluded from these “General Terms of Sale”.

The date of the order acceptance shall be the same date as postmark ortelefax with order confirmation.

If the confirmation applies to different categories of products or toseparate/part deliveries, each product category and/or delivery shall beconsidered a separate contract.

3. PRODUCT DELIVERY, SHIPMENT AND TRANSPORTATION

The Vendor shall comply with the agreed terms of delivery, with anallowance of fifteen working days.

Any events preventing or delaying product manufacturing including but notlimited to strike (including company strike), lock-out, fire, importation ban,delayed delivery of raw materials or power failure or other eventspreventing or delaying product manufacturing, shall be hereby consideredforce majeure and the Vendor shall not be deemed liable for late delivery.

In such case, the Vendor shall have the right to delay delivery until theforce majeure event ceases to exist.

Should such event continue for over thirty days, the Vendor shall have theright to terminate the agreement, without any rights for the Buyer toreceive an indemnification for any damages directly or indirectly causedby such delay.

Upon expiry of the terms of delivery agreed by the parties, and withinfifteen calendar days after receiving a notice stating that the goods areready, the Buyer shall collect the ordered products or, in case of deliveryto destination, require the delivery.

After such period, the Vendor has the right to store the products outdoorsand be exempted by any and all liabilities; any warranties shall bedeemed invalid and the Buyer shall be charged an additional 1% of theproduct value per week for handling and storage costs. The Vendorreserves the right to ship the products to a destination assigned to theBuyer or to store them at the Buyer’s expense.

Eight days after issuing the notice stating that the goods are ready, theVendor shall issue the related invoice and the payment term shall begin.

The Buyer shall be under obligation to check the product conditions uponreceipt. Products will be transported at the Buyer’s risk also in case ofC&F delivery.

Any claim for alleged missing goods or damages must be notified upondelivery by adding a remark on the packing list, otherwise the goodswarranty shall be deemed invalid.

Any stopover, storage or waiting shall be at the Buyer’s expense, also incase of C&F delivery and transportation carried out by the Vendor itself orcommissioned by the Vendor to a third party.

4. PACKAGING

The products are sold without packaging. Any packaging must be required

in the purchase order and shall be charged/billed in the related invoice.

5. TOLERANCES

The Buyer accepts the tolerances listed in the Vendor’s catalogues and/ortechnical specifications (latest version).

6. WARRANTIES

Any claims, except those set out in Art. 3 above, must be notified in writing(registered mail or telegram) to the Vendor within eight days afterreceiving the products. After such term, the Buyer waives any rights towarranty following faults and/or low quality and/or dissimilarity of theproducts.

Claims must be detailed in order to allow the Vendor to perform a timelyinspection. Claimed products must be kept at the Vendor’s disposal, in thesame conditions of the time of delivery, in compliance with the“Regulations on transport, handling and storage” contained in Enclosure Aof these “General Terms of Sale” and with any specific instructions of theVendor.

Should the Buyer use any products with patent faults, any warranty shallbe voided.

In case the products provided are not suitable for their intended use, theyshall be returned in a location agreed by the parties.

The Buyer is not entitled to any rights of terminating the contract, and theVendor shall not be deemed liable for any direct and/or indirect damagesto the Buyer, except to the extent set out in art. 1229 of the Civil Code.

In case of part deliveries, any claims, including timely ones, do not exemptthe Buyer from withdrawing the remaining amounts of products ordered.

In case a claim is found to be groundless, the Vendor shall charge to theBuyer all expenses for inspections and expert’s reports, including thosecarried out by third parties.

The Vendor warrants that the supplied products comply with thespecifications given in the catalogues and/or technical specifications(latest version).

The warranty for products with organic coating shall be performed by theVendor, at its discretion, as follows:

• by restoration of the products by the Vendor,

or

• by payment of an amount up to one third of the original price of thefaulted organic coating; the amount of such payment shall beprogressively reduced according to the period of use of the deliveredproduct.

Metal surfaces without organic coating are not subject to any warranty,except for their compliance with current regulations; the Vendor isexempted from any liability related to product tarnishing, being it an usualphenomenon.

The warranty provided by the Vendor for the restored elements shall notbe renewed.

The Vendor rejects any liability in case of restoration performed by thirdparties.

Specific warranties and/or certifications may be issued on specific requestby the Buyer in the purchase order.

Any warranty shall be voided following uses not compliant with the“performance” characteristics of the products, or lack of compliance with

GENERAL TERMS OF SALE FOR RIBBED SHEETS,INSULATED METAL PANELS AND ACCESSORIES

“General Terms of Sale for Corrugated Sheets, Insulated Metal Panels and Accessories” approved by AIPPEG (the Italian Association ofManufacturers of Corrugated Panels and Components) and enclosure A “Regulations for Transporting, Handling and Storing Corrugated

Sheets, Insulated Metal Panels, and Accessories “ deposited on 21 January 1993 with Notary Public Maria Celeste Pampuri of Milan,Registry no. 71034 Folder no. 2786, registered as a Deed on 22 January 1993 n°000430 1 B in Milan in the section of “Public Deeds”

and Registered for notification purposes with the Milan Chamber of Commerce in the section “Contractual Conditions and Charges” on 9 February 1993.

Page 46: Isopan Man Tecnico GB

B1.2

the “Regulations on transport, handling and storage” set out in EnclosureA and any special instructions given by the Vendor, and following the useof tools for product installation (such as fixing systems, tamponi chiudi-greca, ridges, ridge caps) not supplied and/or not expressly approved bythe Vendor.

The Vendor reserves the right to modify the products or carry out anyimprovement it deems necessary.

7. PRICING

Prices are calculated according to the current costs at the date of theorder.

In case of increases over 2% of the product costs, the prices shall bemodified and the increase applied upon invoicing, with fullacknowledgment of the actual variation according to the followingpercentages:

• ribbed sheets: 10% labour, 90% metal• panels: 10% labour, 30% insulating components, 60% external coating.

Labour shall be priced according to A.N.I.M.A. tables; metals shall bepriced according to the price list of the Chamber of Commerce of Milan;insulating materials and other materials shall be priced according to thedeclaration of the Vendor’s Supplier.

Any variation of the price of accessories shall be applied in a conventionalway, applying the relevant variations of the official ISTAT index of livingcost.

In case of part deliveries, any price variations shall apply only to productsdelivered after the price increase.

8. PAYMENT

Payments shall be made at the Vendor’s premises. The collection ofamounts of money by the Vendor upon presentation of the purchase ordershall not be deemed an acceptance of the order itself.

Should the Vendor subsequently reject the order, the amounts paid shallbe returned to the Buyer without interest.

In case of Buyer’s default of payment, the amounts paid shall be retainedby the Vendor as deposit, excluding any rights to indemnification of maindamages; in case of Vendor’s default, the Buyer shall receive twice theamount paid, excluding any rights to indemnification for any damages.

In case of late payment, the Buyer shall pay an interest equal to theofficial discount rate plus five points, from the expiry date of the paymentterm agreed by the parties to the date of the actual payment.

Any claims or disputes, both as legal action or exception, do not entitle toa suspension of payments.

In case the product payment occur by drafts or securities (checks, drafts,etc.), such securities must be received by the Vendor before or uponproduct withdrawal.

In case of default of payment at the expiry date, in whole or in part, theBuyer shall be subject to the acceleration clause also for the currentsupplies; the Vendor shall have the right to ask for execution of art. 1460and 1461 of the Civil Code.

The bill sent by the Vendor to the Buyer shall be deemed accepted by theBuyer unless objected within fifteen days after receipt.

9. CONTRACT TERMINATION

Other than in the cases set out in Art. 3 above, the Vendor reserves theright to terminate the contract in case of events or circumstances alteringmarket stability, currency value, the conditions of the industriesmanufacturing raw materials and the supplying conditions.

The Vendor shall have the right to terminate the contract without prejudiceshould it become aware of the existence of protests, or admonitory,ordinary, or concurrent proceedings against the Buyer, both judicial andextra-judicial.

10. GOVERNING LAW

Unless expressly set out in these “General Terms of Sale”, the contractshall be governed by the regulations on sale contained in art. 1470 andfollowing articles of the Civil Code, including product installation.

11. JURISDICTION

Any disputes that may arise from the construction, enforcement,execution, termination of the contract and/or these “General Terms ofSale”, or related to them, shall be settled in the Vendor’s jurisdiction,including joinder of claims.

Page 47: Isopan Man Tecnico GB

1. PACKAGING

Following is the unabridged text of article 7.1 of UNI 10372 Regulation (inItalics):

To maintain their durability after installation, metal roofing elements mustnot be damaged during storage, transport, handling or fitting operations. Itis recommended to provide temporary protection of the required productspecifications (aesthetic characteristics in particular).

During the manufacturing process, the above mentioned materials areusually protected by polyethylene film (adhesive or cling-film) or by othersystems.

During the following phases the Manufacturer must take precautions inorder to guarantee the following:- protection of the product surface against abrasion, especially duringhandling;- protection of corners and edges against impact and crushing;- protection against water stagnation or condensation;- protection against permanent deformation of elements bearing theweight of the whole pack or of stacked packs

Profiled sheets and panels are usually supplied in packs. The number ofsheets per pack must be such as to keep the overall pack weight withinthe limits of the hoisting and transport equipment used.

Materials used for packaging are usually as follows: wood, expandedplastic materials, cardboard, polyethylene film (heat-shrinkable orstretchable) or other materials; packs must be tied with straps (no metalwire) and suitable protection devices (edge-protectors, etc.). Straps mustnot be used as harnesses for hoisting.

It is also recommended to properly indicate the hoisting points forhandling and hoisting operations.

Product packs must always be equipped with a support system touniformly distribute weight and allow for proper handling.

Such support systems may include expanded plastic or dry wooden joists,or composite material sheets positioned at distances establishedaccording to product characteristics.

Packaging must be fully and properly specified in the purchase order onthe basis of the means to be used for transportation (cages or cases fortranshipment, rail transport or shipping). The type of packing varies withproduct characteristics.

Packaging must be carried out in compliance with Manufacturer’sparameters. Any different grouping of elements and/or special packagingmust be specified in the purchase order and acknowledged by the seller.

2. TRANSPORTATION

Following is the unabridged text of article 7.2 of UNI 10372 Regulation (inItalics):

Packs must be transported by suitable vehicles, and:- packs must be supported by expanded plastic or wooden spacers,positioned at distances established according to product characteristics;- the support surface must be compatible with the pack shape (flat for flatpacks, with a matching curve for curved packs);- packs must be stacked fitting suitable expanded plastic or woodenspacers between the packs, if not included in the packaging;- packs must not be more than 1 m. different in length, depth or height;- packs must be clearly marked with where to position hoisting harnesses,if such areas are not self-evident;- compliance with any other Manufacturer’s specification.

Packs must be placed on a flat surface and expanded plastic or woodenspacers of suitable size and number must be positioned under the packs.A perfect vertical alignment of spacers is required.

The carrier must secure packs to the vehicle using crosswise slingspositioned at a maximum distance of 3 m, provided that each pack issecured by at least two crosswise slings.

The load must always be covered during transportation and the siderunning along the vehicle must be waterproofed. The Buyer collectingproducts is responsible for instructing the drivers in this matter.

Packs must be loaded on a completely free and clean platform. Vehiclespartially loaded with other materials or with unsuitable loading platformsare not acceptable.

Products must be loaded on vehicles according to carrier instructions. Thecarrier is fully liable for damage to the load and shall take all thenecessary precautions to prevent damage due to the weight on thebottom pack or pressure at tying points, and shall prevent productdeformation caused by slings. Special loading conditions will only beaccepted upon written request by the Buyer, who shall be fully liable insuch cases.

3. STORAGE

Following is the unabridged text of article 7.3 of UNI 10372 Regulation (inItalics):

The shape of elements is designed to allow stacking, in order to minimizethe pack volume during storage and transportation; it is nonethelessnecessary to make sure that stacking does not damage product surfacesin any way.

Packs must always be stored lifted from the ground, both in thewarehouse and in the yard: they must be positioned on supports,preferably made of expanded plastic or wood, with flat surfaces longerthan the slabs and positioned at suitable distances according to productcharacteristics.

The support surface must be compatible with pack shape: flat for flatpacks, with a matching curve for curved packs.

Packs must be stored in dry places to prevent water stagnation andcondensation on the internal elements, which are less exposed to the air.Such phenomena are particularly dangerous for metals, and may causeoxidation (ex. white rust on zinc).

Packs must be stored in a suitable way to facilitate water run off,especially if they are to be temporarily stored outdoors (see figure).

If stored products are not collected for installation within a short period oftime, they should be covered with tarpaulin.

Take the necessary precautions against electrochemical corrosion due tocontact between different metals during storage.

It is preferable not to stack packs; when the stacking of lightweight packsis possible, always fit expanded plastic or wooden spacers betweenpacks. Spacers must be of the largest size applicable and in sufficientnumber, and must always be positioned vertically, on lower pack supports(see figure….).

B1.1

B2 AIPPEG REGULATIONS: ENCLOSURE A

ENCLOSURE A

REGULATIONS FOR TRANSPORT, HANDLINGAND STORAGE OF CORRUGATED SHEETS,

INSULATED METAL PANELS AND ACCESSORIES

B2.1

min. slope 5%

Page 48: Isopan Man Tecnico GB

B2.2

The best storage locations are closed spaces with some ventilation, freeof dust and humidity.

In all cases, and especially for yard storage, a steady support surfaceshould prevent water stagnation.

Packs must not be positioned near processing areas (such as metalcutting, sandblasting, painting, welding, etc.), or where vehicles pass by orstop (impact, splashing, fumes, etc.)

Do not stack more than three packs, or over a maximum overall height ofapproximately 2.6 m. Suitable supports are required for stacking.

If materials are wrapped in protective film, make sure the film iscompletely removed during installation, and in any case within threemonths of materials becoming usable. Carry out any other specificinstructions of the Manufacturer.

On the basis of experience and subject to compliance with currentregulations, it is recommended not to exceed twelve months ofuninterrupted storage in closed spaces, in order to maintain originalproduct characteristics. Outdoor storage should not exceed three months.Materials must be protected from direct sunlight at all times, since it maycause product alteration.

If tarpaulin is used, make sure it is waterproof and properly ventilated toprevent condensation and water stagnation.

4. HOISTING AND HANDLING

Following is the unabridged text of article 7.4 of UNI 10372 Regulation (inItalics):

Packs must always be lifted by means of slings positioned at a minimumof two points separated by a distance not less than half the length of thepack itself.

The slings used for hoisting must preferably be made of synthetic fibre(nylon), at least 10 cm wide, positioned in order to take the weight evenlyand correctly and to prevent deformation (see figure).

It is recommended to use suitable spacers consisting of heavy-dutywooden or plastic boards positioned above and below the pack, to avoiddirect contact between the slings and the pack.

Such spacers must be at least 4 cm longer than the pack and at least aswide as that of the sling. In all cases, lower spacers must be sufficientlywide to prevent deformation of the lower elements due to pack weight.

Make sure that harnesses and supports cannot move during hoisting andthat all operations are carried out with caution and gradually.

Packs must be laid down only on roof frameworks with suitable surface, interms of strength, support and safety conditions. Always take otherongoing operations into account. Before hoisting a pack, authorizationfrom the Work Management should be sought at all times.

Handling must always be carried out wearing suitable protectiveequipment (gloves, safety shoes, overalls etc.) in compliance with currentregulations.

Individual panels must be moved by hoisting the element without draggingit over the lower panel and rotating it upright alongside the pack; transportmust be carried out by at least two people according to panel length,keeping the panel upright as illustrated.

Hoisting equipment and gloves must be clean and able to preventdamage.

The use of fork-lifts is not recommended, as such equipment may damagethe packs.

Packs laid down at roof level must always be properly secured to theframework.

min. slope 5%

Page 49: Isopan Man Tecnico GB

B3.1

B3 AIPPEG RECOMMENDATIONS: ENCLOSURE B

The products listed in this enclosure are usually employed forindustrialized construction. The following quality standards include acomprehensive list of the characteristics and performance specificationsof such products.The Vendor warrants that the products comply with the following qualitystandards, according to the relevant national and European regulations(updated June 1999).

1. RIBBED SHEETS

1.1 Specifications

MATERIAL REGULATION REFERENCE VALUE-REMARKS

1.1.1 Carbon prEN 508-1 3.2 and 4.2steel UNI EN 10147 5.1 Fe E 250 G (min.

UNI 10372 2.1.4 yield point = 250 N/mm2)

1.1.2 Aluminium prEN 508-2 3.2 and 4.2 Alloys: Vendor’sUNI 10372 2.1.2 statement (min.

breakage load = 150 MPa)

1.1.3 Stainless prEN 508-3 3.2 and 4.2 Type: AISI 304steel UNI 10372 2.1.3 (unless

different request)

1.1.4 Copper prEN 506 3.2 and 4.2 Type: Vendor’sUNI 10372 2.1.1 statement (ifUNI EN 1172 4-5-9 specifically required)

1.1.5 Metal prEN 508-1 3.2 and 4.2coating UNI EN 10147 6.4

UNI 10372 2.1.4 Incl. differentiatedUNI EN 1396 coating and crack-

free zinc-coated steel

1.1.6 Organic EN 10169-1coating: ENV 10169-2pre-painted prEN 10169-3and prEN 508 1-2-3 Enclosure Bplasticized UNi 10372 2.1.4.3

UNi EN 1396

1.1.7 Multi-layer prEN 508-1 3.2.6bituminous UNI 10372 2.1.4.4coating

1.2 Thickness tolerance

1.2.1 Carbon prEN 508-1 4.3.4 Class 1steel UNI EN 10143 6.1 Tab. 1 = Fe E 250G

Tab. 2 ≥ Fe E 280G

1.2.2 Aluminium prEN 508-2 4.3.4 Class 1UNI EN 485-4UNI 3813 2-3-4

1.2.3 Stainless prEN 508-3 4.3.4 Class 1steel UNI EN 10088-2

1.2.4 Copper UNi EN 1172 6.4

1.3 Shape tolerance

1.3.1 Carbon prEN 508-1 Enclosure A See appendix for steel values

1.3.2 Aluminium prEN 508-2 Enclosure A See appendix for values

1.3.3 Stainless prEN 508-3 Enclosure A See appendix for steel values

1.3.4 Copper prEN 506 Enclosure A See appendix forUNI EN 1172 6.4.2 values6.4.36.4.4

1.4 Performance (maximum load)

1.4.1 Carbon CNR Instructions 10022-84steel AIPPEG Recommendations

Eurocode 3 Section 1.3

1.4.2 Aluminium UNI 8634 6.5Eurocode 9prEN 508-2 4.3.2 Enclosure F

(information)

1.4.3 Stainless CNR Instructions 10022-84steel Eurocode 3 Section 1.3

Eurocode 3 Section 1-4

1.5 Durability

1.5.1 Characte- prEN 508-1-2-3ristics EN 10169-1

ENV 10169-2prEN 10169-3UNI EN 1396

1.5.2 Corrosion ASTM B 117 Values and(test ASTM B 287 (Al) tolerances as statedmethod) by the Vendor

1.5.3 Colour ECCS Recommendations(pre-painted)European Convention for

Constructional Steelwork Section I “Design” – Art. 2.5.3 Values andEN 10169-1 tolerances as stated

by the Vendor

1.5.4 Brilliance EN 10169-1 Values and tolerances as stated by the Vendor

(Colour and brilliance not considered for multi-layer bituminous coating)

1.5.5 Maintenance UNI 10372 Chapter 6and inspection

2. INSULATED METAL PANELS

2.1 Specifications

MATERIAL REGULATION REFERENCE VALUE-REMARKS

Faces

2.1.1 Hard Same regulations, references, values and remarks metal faces applicable to point 1.1 above.

Insulating material

2.1.2 Hard Pr UNIPLAST 517 3.1 and 3.2cellular UNI 9029 4.3.2plastic UNI 10386

2.1.3 Mineral Health Ministry’s Circular n. 23 - 25.11.91fibres

2.2 Thickness tolerance

Faces

ENCLOSURE BQUALITY STANDARDS FOR RIBBED SHEETS

AND INSULATED METAL PANELSEnclosure B “Quality Standards for Corrugated Sheets and Insulated Metal Panels” approved by AIPPEG ( the Italian Association of

Manufacturers of Corrugated Panels and Components) . Deposited on 21 January 1993 with Notary Public Maria Celeste Pampuri of Milan,Registry no. 76364 Folder no. 3001 registered as a Deed on 30 July 1993 in Milan n° 14284 1 B in the section of “Public Deeds” and

Registered for notification purposes with the Milan Chamber of Commerce in the section “Contractual Conditions and Charges” on 23 July 1993.

Page 50: Isopan Man Tecnico GB

B3.2

2.2.1 Hard Same regulations, references, values and remarks metal faces applicable to point 1.2 above.

2.2.2 Panels Compared to nominal h ≤ 100 mm = ± 2 mmvalues declared by Vendor h >100 mm = ± 3 mm

The measurement of h thickness includes all kinds of faces and excludesmulti-layer bituminous coating.

2.3 Shape tolerance

2.3.1 Length ± 10 mm

2.3.2 Misalignment of metal faces 3 mm

2.3.3 Planarity L = distance between L ≤ 300 mmmeasurement endpoints s ≤ 1%(max. 1000 mm) d = deviation L > 300 mm

s = max. 3 mm(d must be measured every 1000 mm)

2.3.4 Other Same regulations, references, values and remarks parameters applicable to point 1.3 above.

2.3.5 Bubbles Bubbles are defined as convex areas with no adherencebetween insulating material and coating. In absence of relevant regulations, it is deemed on the basis of experience that any bubbles up to 5% of the surface of

a single panel and with maximum size of 0.2 m2 per bubble cannot affect panel functionality. This applies to panels where the insulating material has also the function of transferring loads.

2.3.6 Esthetical ECCS Recommendationsrequire- Section II “Good Practice”, 2.5ments

2.4 Performance

2.4.1 Maximum ECCS Recommendations Statement of load Section I calculation or test

Reference to the Vendor’s methodTechnical Specifications

2.4.2 Insulation Industry Ministry Decree Statement of available02.04.98 lambda of the

insulating materials for thermal calculation purposes

2.4.3 Fire Ministry of the Interior Certified referenceresistance Decree 26.06.84 or M.I. homologation

Ministry of the Interior with statement ofDecree 14.01.85 compliance by the

Vendor

2.4.4 Fire Ministry of the Interior Certified referenceresistance Decree 30.11.83 with statement of(for specific Ministry of the Interior compliance by therequire- Circular n. 91 14.09.61 Vendorments)

2.4.5 Acoustic UNI 8270 Certified reference performance with statement of (for specific compliance by the Vendorrequirements)

2.5 Durability

2.5.1 Faces Same regulations, references, values and remarks applicable to point 1.5 above.

2.5.2 Products ECCS Recommendations Vendor’s statementSection II 2.4 (on request)

2.5.3 Mainte- UNI 10372 Chapter 6nance and ECCS Recommendationsinspection Section II Chapter 7

Quality standards for products different from those listed above must beagreed in advance in writing by the parties. The esthetical qualities of thefinished products depend on the specific use. The esthetical qualities ofthese products match those of the products in use in the field ofindustrialized construction and depend on the tolerances specified in thisenclosure.

APPENDIX – prEN 508-1-2-3 and 506 – SIZE TOLERANCES

A.1.1 Corrugation height:h ≤ 50 mm ± 1.0 mm50 mm < h ≤ 100 mm ± 1.5 mmh > 100 mm ± 2.0 mm

A.1.2 Height of stiffening ribs: ± 1 mm

A.1.3 Distance between corrugations:h ≤ 50 mm ± 2 mm50 mm < h ≤ 100 mm ± 3 mmh > 100 mm ± 4 mm

A.1.4 Width of ridges and valleys of corrugations: + 2 mm- 1 mm

A.1.5 Actual cover width:h ≤ 50 mm ± 5 mm50 mm < h ≤ 100 mm ± 1/10 hh > 100 mm ± 15 mm

A.1.6 Curvature radius: + 2 mm- 0 mm

A.1.7 Camber:h ≤ 2 mm/m (max 10 mm)

A.1.8 Out of perpendicular:S ≤ 0.5 % available width

A.1.9 Sheet length:+ 10 mm up to 3000 mm+ 20 mm over 3000 mm (unless otherwise agreed)- 5 mm for all lengths

A.1.10 Edge undulation:max. deviation S = ± 2 mm/500 mm

Overlap:min. 15 mm

A.1.11 Arch radius and angles (curved ribbed sheets)radius : ± 5% of nominal radiusangle: ± 3 % of nominal angle

Page 51: Isopan Man Tecnico GB

B4.1

B4 AIPPEG REGULATIONS: ENCLOSURE C

SUMMARY

1. INTRODUCTION2. CONSTRUCTION ELEMENTS3. PRELIMINARY OPERATIONS4. ROOFS (slopes, fitting sequences)5. WALLS (fitting sequences)6. FLOORS (fitting sequences)7. FASTENERS8. FINISHING COMPONENTS

1. INTRODUCTION

The following Recommendations provide reference information for theinstallation of corrugated sheets and insulated metal panels. They arecomplementary to UNI 10372 Regulation “Discontinuous cover panels –Instructions for the design and production of metal sheets”.

Each project shall take into account the needs of individual building yards,which shall be equipped with suitable handling and installation tools, incompliance with current safety and accident prevention regulations.

The company responsible for installing the corrugated sheets/panels shallnot only be fully conversant with the characteristics of the materials in use,but also have qualified personnel suitable for yard operations, to ensurethat the installation is carried out in compliance with project specifications.

The Seller shall not be liable in cases in which the followingRecommendations are disregarded or yard operations are carried outimproperly.

An efficient, well-organized and properly coordinated yard is the bestguarantees of overall installation productivity.

2. CONSTRUCTION ELEMENTS

Corrugated sheets/panels are used in civil and industrial constructionapplications in order to build roofs, walls and floors; they can be fitted toall kinds of support framework: metalwork, normal and prestressedreinforced concrete, and wood.

Support frameworks and fixing elements of corrugated sheets/panels shallbe of suitable size and shall comply with project conditions in terms ofsafety, stability and functioning.

Corrugated sheets and insulated metal panels are quick and easy toinstall, covering the entire pitch length, or wall height, or several floorspans, with a single element. The length of metal elements essentiallydepends on transportation and handling requirements, on the materialused and on production technology.

Support surfaces shall be suitable for use with corrugated sheets andinsulated metal panes and related fixing methods.

Most frequent conditions:

1. ROOFING1.1 corrugated sheet1.1.1 single corrugated sheet1.1.2 sandwich carried out during installation1.1.3 deck carried out during installation

1.2 monolithic insulated panels1.2.1 prefabricated monolithic sandwich1.2.2 pre-insulated deck

2. WALLS2.1 corrugated sheet2.1.1 single corrugated sheet

2.1.2 sandwich carried out during installation2.2 monolithic insulated panels2.2.1 prefabricated monolithic sandwich

3. FLOORS3.1 single sheet3.2 sheet with supporting concrete3.3 corrugated sheet as disposable formwork

The fitting sequences of roofs, walls and floors differ.

3. PRELIMINARY OPERATIONS

Before starting operations in the yard, the operator shall:

1. Examine project drawings and comply with the instructions;

2. Make sure that support frameworks for corrugated sheets/panels arecorrectly aligned;

3. Make sure that the support framework surfaces which will come intocontact with the corrugated sheets/panels are compatible with oneanother or otherwise protected from electrochemical corrosion;

4. Make sure that overhead electric cables or other materials do notinterfere with the corrugated sheets/panels;

5. Make sure that operations at ground and roof level are compatible withyard activities;

6. Make sure that the building yard is suitable for material storage andhandling, in order to prevent damage to sheets/panels.

The operator shall carry out all operations in compliance with currentsafety regulations. Hoisting, handling and storage of corrugatedsheets/panels at roof level shall be carried as set out in Enclosure A,section 4.

The sole of boots worn by personnel responsible for installation shall notdamage the outer facing of sheets/panels. For all cutting operations in theyard, always use suitable tools (reciprocating saw, shears). The use ofabrasive disc tools is not recommended.

For fixing operations we recommend the use of a screwdriver with torquelimiter.

To prevent condensation, elements (roofing panels in particular) shall becorrectly overlaid.

4. ROOFING

SLOPE

The roof slope depends on environmental conditions, the design and typeof rook.

For roofing with pitch elements without end-to-end joints (pitch-lengthsheets), the slope is generally no less than 7%. For flatter roofs, follow theSupplier’s instructions.

In the event of overlap at the head of panels, the slope is determined on thebasis of the type of joint, the materials used and environmental conditions.

For deck roofing, the slope may be reduced to the minimum allowingwater to run off correctly.

FITTING SEQUENCE

The correct sequence for fitting roof panels is as set out below.

A) Single corrugated sheet and prefabricated monolithic sandwich

ENCLOSURE C RECOMMENDATIONS FOR THE INSTALLATIONOF CORRUGATED SHEETS AND INSULATED METAL PANELS

Enclosure C ‘RECOMMENDATIONS FOR THE INSTALLATION OF CORRUGATED SHEETS AND INSULATED METAL PANELS’approved by AIPPEG (the Italian Association of Manufacturers of Corrugated Panels and Components deposited on 14 February 1994 withNotary Public Maria Celeste Pampuri of Milan, Registry no. 81115 Folder no. 3208, registered as a Deed on 22 February 1994 n°02379 1 B

in Milan in the section of “Public Deeds” and Registered for notification purposes with the Milan Chamber of Commerce in the section“Contractual Conditions and Charges” on 10 February 1994.

Page 52: Isopan Man Tecnico GB

B4.2

(type 1.1.1 and 1.2.1)

1. Fit gutters, under-ridges and joint flashings, if used.

2. Remove the protective film from roofing elements and accessories,where required.3. Fit roofing elements starting from the gutter and one edge of thebuilding, making sure that the elements are correctly overlapped andaligned and that they are perfectly perpendicular to the underlyingstructure.

4. Secure all panels after checking that they are perfectly lined up. Allwaste material, especially metal scrapings, shall be immediately removed.

5. Lay the succeeding panels, superimposing them to those already laidalong the gutter (in the event of pitch made of two or more elements). Forpanel installation, the insulating material shall be removed in advancefrom the overlapping area.

6. Secure all corrugations to ridge lines, gutter, drains and head overlaps.

7. Fit finishing components (ridges, sealing caps and all flashingelements) and insulating materials.

8. Remove all waste material and carry out a general inspection of theroofing, paying particular attention to the fixings and joints with otherroofing elements.

B. Sandwich carried out during installation (type 1.1.2)

B.1) Parallel corrugated sheet sandwich

1. Fit gutters and joint flashings, if used. These elements can be installedbefore fitting the inside sheet or before fitting the outside sheet, asrequired by the project.

2. Remove protective film from roofing elements and accessories, whererequired.

3. Fit the inside sheets starting from the gutter and one edge of thebuilding, making sure that the elements are correctly overlapped andaligned and that they are perfectly perpendicular to the underlyingstructure.

4. Secure all panels after checking that they are perfectly lined up. Anywaste, especially metal scrapings, shall be immediately removed.

5. Lay the succeeding panels, superimposing them to those already laidalong the gutter (in the event of pitch made of two or more elements).

6. Secure all corrugations to ridge lines, gutter, drains and head overlaps.

7. Fit rigid spacers of suitable size, positioned as shown in the drawings. Ifmetal spacers are used, it is recommended to make a heat break betweenthe spacers and the outside corrugated sheet. If the secondary supportframework can be fitted directly with an inside sheet, rigid spacers are notrequired.

8. Fit the insulating material (making sure that heat insulation is uniform),any special layers (such as steam barrier, separating layer, etc.) and anyhead “buffers”.

9. Lay the outside sheet in compliance with steps 2 to 6 of this sectionB.1).

10. Remove all waste material and carry out a general inspection of theroofing, paying particular attention to the fixings and joints with otherroofing elements.

B.2) Crossed corrugated sandwich sheeting

1. Remove protective film from roofing elements and accessories, whererequired.

2. Fit the inside sheets starting from the gutter and one edge of thebuilding, making sure that the elements are correctly overlapped andaligned and that they are perfectly perpendicular to the underlyingstructure.

3. Secure all panels after checking that they are perfectly lined up. Anywaste, especially metal scrapings, shall be immediately removed.

4. Fit all flashing elements for the first sheet (under-ridges, joints, specialelements).

5. Fit rigid spacers of suitable size, positioned as shown in the drawings. If

metal spacers are used, it is recommended to provide for a heat breakbetween the spacers and the outside corrugated sheet. If the secondarysupport framework can be fitted directly with an inside sheet, rigid spacersare not required.

6. Fit the insulating material (making sure that heat insulation is uniform),any special layers (as steam barrier, separating layer, etc.) and any head“buffers”.

7. Lay the outside sheet in compliance with steps 1 to 8 of section A)Single corrugated sheet.

C) Deck carried out during installation (type 1.1.3) and pre-insulatedDeck (type 1.2.2)

Follow the instructions that apply to inside sheets, as set out in section B.The sheets shall be joined along longitudinal overlaps.

For the following Deck carried out during installation, insulation isguaranteed by the insulating material to be fitted later.

For pre-insulated Deck, sheets shall be fixed after temporary removal ofthe insulating materials.Waterproofing is guaranteed by the layers to be fitted later (bituminous orsynthetic membrane, etc.)

5. WALLS

FITTING SEQUENCE

The correct sequence for fitting wall panels is as set out below.

A) Single corrugated sheet and prefabricated monolithic sandwich(type 2.1.1 and 2.2.1)

1. Fix the base metalwork (where required) at the foot of the wall, and alsothe metalwork which has to be installed before the wall (such as drips,connectors for the openings, internal corner connectors etc). Remove thepolythene protective film from all accessories before fitting them.

2. Remove the protective film from the wall panels.

3. Fit the panels starting from the foot of the wall, taking care to makejoints correctly and to make sure the panels are upright.

4. Secure the panels after checking that they are perfectly lined up.

5. If the wall height or the type of material require the installation of two ormore series of vertical panels, the joint shall be carried out on thecontinuous part of the framework as follows:- flat panel: end-to-end joint with a properly moulded flashing between thepanels;- corrugated panel and corrugated sheet: as for flat panel or byoverlapping the panels.

6. Fit the finishing components (corner strips, perimeter edging,connectors for roofing and openings, etc.).

7. Carry out a general inspection and cleaning of the wall, payingparticular attention to the fixings and the joints with the door and windowframes. For horizontally positioned corrugated sheets/panels, consultproject instructions.

B. Sandwich carried out during installation (type 2.1.2)

B.1) Parallel corrugated sandwich sheeting

1. Fix the base metalwork (where required) and the joint flashings: theseelements can be installed before fitting the inside sheet or before fittingthe outside sheet, after having removed the protective film.

2. Remove the protective film from the wall panels, where required.

3. Fit the panels starting from the foot of the wall, taking care to makejoints correctly and to make sure the panels are upright.

4. Secure the panels after checking that they are perfectly lined up.

5. If the wall height or the type of material require the installation of two ormore vertical panels, the joint shall be carried out on the continuous partof the framework.

6. Fit rigid spacers of suitable size, positioned as shown in the drawings. Ifmetal spacers are used, it is recommended to make a heat break between

Page 53: Isopan Man Tecnico GB

B4.3

the spacers and the outside corrugated sheet. If the secondary supportframework can be fitted directly with an inside sheet, rigid spacers are notrequired.

7. Fit the insulating material (making sure that heat insulation is uniform),any special layers (as steam barrier, separating layer, etc., in compliancewith the requirements of each building). This operation shall be carried outduring fitting of the inside sheet.

8. Fit the outside sheet in compliance with section B.1), steps 2 to 5.

9. Fit the finishing components (corner strips, perimeter edging,connectors for roofing and walls, etc.).

10. Carry out a general inspection and cleaning of the wall, payingparticular attention to the fixings and the joints with the door and windowframes.

B.2) Crossed corrugated sheet sandwich

1. Remove the protective film from the wall panels, where required.

2. Fit the panels starting from the foot of the wall, taking care to makejoints correctly and to make sure the panels are upright.

3. Secure the panels after checking that they are perfectly lined up.

4. Fit flashing elements for the first sheet (joints, special elements).

5. Fit rigid spacers of suitable size, positioned as shown in the drawings. Ifmetal spacers are used, it is recommended to make a heat break betweenthe spacers and the outside corrugated sheet. If the inside sheet is madeof staves, rigid spacers are not required, but a heat break isrecommended.

6. Fix the base metalwork (where required) at the foot of the wall.

7. Fit the insulating material (making sure that heat insulation is uniform),any special layers (as steam barrier, separating layer, etc., in compliancewith the requirements of each building). This operation shall be carried outduring fitting of the external sheet.

8. Fit the outside sheet in compliance with section B.1), steps 2 to 5.

9. Fit the finishing components (corner strips, perimeter edging,connectors for roofing and walls, etc.).

10. Carry out a general inspection and cleaning of the wall, payingparticular attention to the fixings and the joints with the door and windowframes. For horizontally positioned corrugated sheets/panels, consultproject instructions.

6. FLOORS

FITTING SEQUENCES

The correct sequence for fitting wall panels is as set out below.

A) Single sheet (type 3.1)

1. Fix the perimeter edging, where applicable.

2. Remove the protective film from the floor panels, where required.

3. Fit the sheets making sure that they are correctly juxtaposed andoverlapped. Check that the sheets are perfectly lined up andperpendicular to the underlying framework.

4. Secure the sheets in compliance with project instructions, afterchecking that they are perfectly lined up, then join the sheets alonglengthwise overlaps. All waste material, especially metal scrapings, shallbe immediately removed.

5. Complete the floor in compliance with project instructions, payingattention not to load the floor panels with concentrated loads.

B) Sheet with supporting concrete (type 3.2)

1. Fit concrete containing elements.

2. Fit the sheets making sure that they are correctly juxtaposed andoverlapped. Check that the sheets are perfectly lined up andperpendicular to the underlying framework.

3. Secure the sheets in compliance with project instructions, afterchecking that they are perfectly lined up, then join the sheets alonglengthwise overlaps. It is necessary to make sure that corrugated sheetsare free from oxide and oil stains, or any other substance that mayprevent adhesion to the concrete. All waste material, especially metalscrapings, shall be immediately removed.

4. Use sealing adhesive tape to prevent concrete from dripping at thehead junctions of corrugated sheets.

5. Position the electrically welded wire mesh and/or framework bars at thesupports in compliance with project instructions.

6. Cast the concrete paying attention to avoid accumulation, especially inthe centre of the floor span.

7. If the project design requires the use of props, put them in place beforeconcrete casting, providing corrugated sheets with the required countertracing.

C) Corrugated sheet as disposable formwork (type 3.3)

1. Fit concrete containing elements.

Follow the instructions set out at section B), except for step 5, whereframework bars are required.

7. FASTENERS

Fasteners are essential components of the roofing, siding and flooringsystem. It is thus necessary to use the fasteners recommended by theManufacturer of corrugated sheets/panels.

Instructions for a correct installation:

Roofs:

- external facing (type 1.1.1, 1.1.2 and 1.2.1): a whole kit, usually includingscrews, caps and sealing gaskets, to be fitted to the corrugation ridge.- internal facing (type 1.1.2, 1.1.3 and 1.2.2): screw and gasket (whererequired).

Walls:

- external facing (type 2.1.1, 2.1.2 and 2.2.1): screw and gasket.- internal facing (type 2.1.2): screw and gasket (where required).- prefabricated monolithic panels with “hidden” fixing: specific fixing kit

Floors: screws, nails, washers to be welded during installation.

The density and position of fixings required varies with the characteristicsof the construction elements, the type and size of support, and localclimate situation (wind in particular). In any case, always consult projectinstructions.

In most cases, corrugated sheets/panels are fixed with screws of differenttype, in compliance with the support framework.

1. Fixing to metal framework:

- self-tapping and self-threading screws (depending on support thickness)- thread-forming screws - fired in nails (for floors and inside sheets of sandwich carried out duringinstallation)- threaded hooks with nut (usually for fixing to tube elements)

2. Fixing to wood framework:

- wood screws- threaded hooks

3. Fixing to reinforced concrete and prestressed reinforced concrete:

This fixing method applies to steel or wood support elements incompliance with the types set out at point 1 and 2.

Direct fixing to reinforced concrete and prestressed reinforced concrete isnot recommended.

For deck roofing and floors, ribbed fixings are required, usually with rivetsfitted along the longitudinal overlap, at a maximum distance of 1000 mm.

For other roofing and siding elements, ribbed fixing is also recommended,in compliance with the type of overlap.

Page 54: Isopan Man Tecnico GB

B4.4

8. FINISHING COMPONENTS

Finishing components are an integral part of the whole installation, andplay an important role in guaranteeing the performance characteristics ofa project.

The Manufacturer of corrugated sheets/panels is usually able to providefinishing components as well, which shall be fitted in compliance withproject and/or supply instructions.

The Buyer shall define the range of finishing components required incompliance with its needs. The Manufacturer of corrugated sheets/panelsis responsible for the compliance of materials with the order confirmationonly for directly supplied and properly installed components.

The finishing components include gaskets of different shapes, flashing(ridges, under-ridges, gutters, drains and rainwater downpipes, lighningconductors, drips, corner connectors, etc.), translucent slabs, cups,ventilators, door and window frames and secondary components.

Page 55: Isopan Man Tecnico GB

C - CONSTRUCTION DETAILS

Construction detail for curved panel C1

Construction details for polyurethane panels C2

Construction details for mineral fibre panels C3

Page 56: Isopan Man Tecnico GB

C1.1

In this section we illustrate by way of suggestion for designers and fitters, some of the commonestconstruction details used in installation, with simplified diagrams which go some way towards answeringsome of the most widespread problems which we are asked to clarify at the installation stage.

CONSTRUCTION DETAIL FOR CURVED PANELC1

CURVED PANEL

SECTION

250

40

épaisseur

25 25 22

1000

Prefabricated beam in R.C.

Distance between centres

L as required

Curved panel

Thickness

Page 57: Isopan Man Tecnico GB

C2.1

CONSTRUCTION DETAILS FOR POLYURETHANE PANELS

GUTTER DETAIL – Central valley

GUTTER DETAIL – External gutter (with the possibility of enlargement)

C2

GASKET(RECOMMENDED)

PROVIDESUPPORTFOR GUTTER

RAINWATEROUTLET

INSULATEDGUTTER

MINERALWOOL

GASKET(RECOMMENDED)CAPPING

GASKET(RECOMMENDED)

INSULATED GUTTER

RAINWATER OUTLET

THERMAL BREAK

Page 58: Isopan Man Tecnico GB

C2.2

CAPPING

PANEL

DRIP

GASKET (RECOMMENDED)

INSULATEDGUTTER

GUTTERSUPPORT

RAINWATEROUTLET

THERMALBREAK

MINERALWOOL

ANGLEIRON

COLUMN

GUTTER DETAIL – External gutter (with parapet)

PANEL TO PANEL JOINT

Page 59: Isopan Man Tecnico GB

C2.3

JOINTCAPPING

INNER CONNECTOR

MINERAL WOOL

ANGLE IRON FORFIXING WALL

DIRECTIONOF FITTING

EDGE DETAIL – Curved connector

SEALANTB (min 200 mm)

Z - SUPPORT

CURVED INNERFLASHING

CURVED JOINT **

ANGLE

**MINIMUM INTERNAL RADIUS 500 mm

A (m

in 2

00 m

m)

* DEPENDING ON THE SLOPE

IN SITUINSULATION

*

EDGE DETAIL – Joint at head of wall

Page 60: Isopan Man Tecnico GB

C2.3

RIBBED SHEETCAPPING

FLASHING

INNER CONNECTOR

ANGLE IRONFOR FIXING WALL

DIRECTIONOF FITTING

MINERAL WOOL

EDGE DETAIL – Joint at head of wall (with parapet)

Page 61: Isopan Man Tecnico GB

C2.4

HINGED RIDGE

GASKET (RECOMMENDED)

PUNCHED RUBBER BUFFER(RECOMMENDED)

UNDER-RIDGE

MINERAL WOOL

GASKET (RECOMMENDED)

PUNCHED RUBBER BUFFER

UNDER-RIDGE

SIMPLE RIDGE

MINERAL WOOL

RIDGE DETAIL – Simple ridge

RIDGE DETAIL – Hinged ridge

Page 62: Isopan Man Tecnico GB

C2.5

FOLDED RIDGE

GASKET (RECOMMENDED)

PUNCHED RUBBER BUFFER(RECOMMENDED)

UNDER-RIDGE

MINERAL WOOL

UNDER-RIDGE

A (min 200 mm) *

SEALANT

IN SITU INSULATION

B (min 200 mm) *

* DEPENDING ON THE SLOPE

GASKET(RECOMMENDED)

CURVED RIDGE

RIDGE DETAIL – Curved ridge

RIDGE DETAIL – Folded ridge

Page 63: Isopan Man Tecnico GB

C2.6

PUNCHED RUBBER BUFFER(RECOMMENDED)SINGLE-PITCH RIDGE

GASKET (RECOMMENDED)

OUTER WEATHERING

INNER WEATHERING

PUNCHED RUBBER BUFFER(RECOMMENDED)

RIDGE DETAIL – Single-pitch ridge

RIDGE DETAIL – Single-pitch ridge below wall

Page 64: Isopan Man Tecnico GB

C2.7

SEALANTGASKET

FIXTURE ASSEMBLY

* DEPENDING ON THE SLOPE

*

SEALANT

FIXTURE ASSEMBLY(on every rib)

70 m

m

PANEL

END PLUG(RECOMMENDED)

ISOPLAST DOUBLE SLABdependingon the slope

SPACER IF NECESSARY(for panel thicknessesover 30 mm)

OVERLAP AT HEAD OF PANEL

ISOPLAST DETAIL - Overlap at head of panel

Page 65: Isopan Man Tecnico GB

C2.8

SEALANT

FIXTURE ASSEMBLY

dependingon the slope

70 m

m

PANEL

SPACER IF NECESSARY(for panel thicknessesover 30 mm)

END PLUG(RECOMMENDED)

ISOPLAST DOUBLE SLAB

ISOPLAST DETAIL - Overlap at head of Isoplast panel

GASKET(RECOMMENDED)

SLOPE 3°

DRIP

BASE SUPPORT

DRIP AT BASE

Page 66: Isopan Man Tecnico GB

C2.9

DRIP

SLOPE 3°

GASKET (RECOMMENDED)

DRIP

JOINT AT SOFFIT

SEALANT

WINDOWFRAME

SEALANT

SLOPE 3°

DRIP

HEI

GH

T O

F W

IND

OW

FRA

ME

DRIP AT BASE

FITTING OF WINDOW FRAME (vertical section)

Page 67: Isopan Man Tecnico GB

C2.10

WIDTH OF WINDOW FRAME STEEL UPRIGHT

JOINT FLASHING SEALANT

WINDOWFRAME

MINERAL WOOL

PANEL

FITTING OF WINDOW FRAME (horizontal section)

Page 68: Isopan Man Tecnico GB

C3.1

CONSTRUCTION DETAILS FOR MINERAL FIBRE PANELSC3

WALL to R.E.I. ROOFING PANEL JOINT

NON-FLAMMABLEINSULATING MATERIAL

THERMO-EXPANDINGSEALANT

FINISHING PROFILE

SUPPORT PROFILE

FINISHING PROFILE

FIRE

Page 69: Isopan Man Tecnico GB

C3.2

RIDGE JOINT FOR R.E.I. PANELS

WALL to R.E.I. ROOFING PANEL JOINT

THERMO-EXPANDING SEALANT

SPECIAL RIDGESHEET

FIXINGS

FINISHING PROFILE

SUPPORT STRUCTURE

THERMO-EXPANDING SEALANT

FIRE

THERMO-EXPANDINGSEALANT

FINISHING PROFILE CORNER PROFILE

FIRE

FINISHING PROFILE

Page 70: Isopan Man Tecnico GB

C3.3

WALL to R.E.I. ROOFING PANEL JOINT

RIDGE JOINT

FLASHING FOR FIXINGWALL PANEL

GUTTER SUPPORTBRACKET

GUTTER

RAINWATERDOWNPIPE

METAL STRUCTURE

SMOOTH CURVED SECTION TO FACILITATE THEOVERLAP BETWEEN THE TWO FLASHINGS

RIDGE FLASHING SECTION SHAPED TO MATCHTHE RIBBED FACE OF THEROOFING PANEL

DOUBLE-SIDED ADHESIVE TAPE

METAL STRUCTURE

Page 71: Isopan Man Tecnico GB

C3.4

WALL PANEL to R.E.I. MASONRY JOINT

DIRECTION OF (FINISHING) LAYING

FIRE

THERMO-EXPANDINGSEALANT

CORNER PROFILE

FINISHINGPROFILE

WALL PLUG

WALLFIRE

Page 72: Isopan Man Tecnico GB

C3.5

PANEL to R.E.I. WALL JOINT

CORNER PROFILE

THERMO-EXPANDINGSEALANT

SUPPORTPROFILE

FINISHINGPROFILE

FLOOR

WALL PLUG

FLASHING

FIRE

Page 73: Isopan Man Tecnico GB

C3.6

PANEL to R.E.I. FLOOR JOINT

CORNER PROFILE

THERMO-EXPANDINGSEALANT

FLOORWALL PLUG

FIREFIRE

Page 74: Isopan Man Tecnico GB

C3.7

JOINT: WALL to WALL, R.E.I. RATED

FIRE

CORNER PROFILE

THERMO-EXPANDINGSEALANT

SUPPORT PROFILE

FINISHING PROFILE

DIRECTION OF LAYING

DIR

ECTI

ON

OF

LAYI

NG

FINISHING PROFILE

Page 75: Isopan Man Tecnico GB

C3.8

WALL PANEL to R.E.I. MASONRY JOINT

DIRECTION OF (STARTING) LAYING

FIRE

THERMO-EXPANDINGSEALANT

CORNER PROFILE

FINISHING PROFILE

WALL PLUG

WALLFIRE

SUPPORT PROFILE

Page 76: Isopan Man Tecnico GB

TECH

NIC

AL

HA

ND

BO

OK

TECH

NIC

AL

HA

ND

BO

OK

TECHNICAL HANDBOOKTECHNICAL HANDBOOK

Ver

sion 1

0/2

00

4

Copyri

ght

© b

y Iso

pan S

.p.A

.

Any k

ind o

f re

pro

duct

ion,

even

part

ial,

if n

ot

auth

ori

zed, is

forb

idden

, w

hate

ver

mea

ns

utiliz

ed.

GRUPPO MANNI S.p.A.

www.isopan.i t

ISOPAN FRANCE

Zac du Parkile - BAT 2164 Avenue Joseph Kessel

F - 78960 VOISINS LE BRETONNEUXTel. (33) 1 30575578 - Fax (33) 1 30575097

[email protected]

ISOPAN IBERICA SLPolígono Industrial de ConstantíAvda. de les Puntes, parcela 23

E - 43120 Constantí (TARRAGONA)Tel. (34) 977524546Fax (34) [email protected]

ISOPAN S.p.A.TREVENZUOLO branch

Via Giona, 5I - 37060 TREVENZUOLO (VR)

Tel. (39) 045 7359111Fax (39) 045 7359100

[email protected]

ISOPAN S.p.A.PATRICA headquarters

S.P. MorolenseI - 03010 PATRICA (FR)

Tel. (39) 0775 2081Fax (39) 0775 293177

[email protected]

EN ISO 9001T V Italia S.r.l.certified

EN ISO 9001T V RheinlandcertifiedDIN EN ISO 9001:2000

Certificado Nº 01 100 048110