DATE 01.11.2012
MICROMAX SYSTEMS PRIVATE LIMITED
W.O No. 12 - 031
TRICHY
SHEET No. 01 OF 13
PLC I/O LIST PROJECT: ET200S NON REDUNDANT PLC - ASH (1 x 60MW Thermal Power Plant)
P.O REF : MBK069/0290/S/27.6.12
M/s.CL A/C ARS METAL
REV NIL A B C D
ANALOG INPUT
S. Panel PLC Card Ch. Ch. TagDescription
Process Value Display Value SignalSignal Card Panel TB Client
No. No. Tier No. No. Add.
Unit Min. Max. Unit Min. Max. TypeSo./Des. TB Nos. Nos. Ref. Dwg.
1 1 1 1 1 PIW256 AISPARE1
AIC1 - 1,3 X1- 1, 2
2 1 1 1 2 PIW258 AISPARE2
AIC1 - 5,7 X1 - 3,4
3 1 1 2 1 PIW260 AISPARE3
AIC2 - 1,3 X2- 1, 2
4 1 1 2 2 PIW262 AISPARE4
AIC2 - 5,7 X2 - 3,4
8/16/2019 Io List (Ash) - Rev d - 01.11.12
http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 2/24
MICROMAX
CUSTOMER
----------------------- Page 2-----------------------
DATE 01.11.2012
MICROMAX SYSTEMS PRIVATE LIMITED
W.O No. 12 - 031
TRICHY
SHEET No. 06 OF 13
PLC I/O LISTPROJECT: ET200S NON REDUNDANT PLC - ASH (1x60MW Thermal Power Plant)
P.O REF : MBK069/0290/S/27.6.12M/s.CL A/C ARS METAL
REV NIL A B C D
DIGITAL INPUT
S. Panel PLC Card Ch. Ch. TagDescription
Process Value Display Value Signal Signal Card Panel TB ClientNo. No. Tier No. No. Add.
Unit Min. Max. Unit Min. Max. Type So./Des. TB Nos. Nos. Ref. Dwg.
1 1 1 1 1 I0.0 DPC-SYSON-111 BED ASH COOLERS AT HOOPER-I ON/OFF SELECTOR SWITCH SYS-I(MV)
DIC1-1 X3 -1,2
2 1 1 1 2 I0.1 DPC-PUR-111 LINE PURG
E PUSH BUTTON SYS-I (MV)
DIC1-5 X3 - 3 ,4
3 1 1 1 3 I0.2 DPC-OVDPOR-111 PROBE OVER RIDE PUSH BUTTON SYS-I (MV)
DIC1-2 X3-5,6
4 1 1 1 4 I0.3 DPC-HLS-111 SURGE HOP
8/16/2019 Io List (Ash) - Rev d - 01.11.12
http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 3/24
LEVEL SWITCH SYS-I (MV)
DIC1-6 X3-7,8
5 1 1 1 5 I0.4 DPC-IVSP-111 INLET VALVE SEAL PRESSURE SWITCH SYS-I (MV)
DIC1-3 X3-9,10
6 1 1 1 6 I0.5 DPC-VLPS-111 CONVEYING VESSEL LOW PRESSURE SWITCH SYS-I (MV)
DIC1-7 X3-11,12
7 1 1 1 7 I0.6 DPC-VHPS-111 CONVEYING VESSEL HIGH PRESSURE SWITCH SYS-I (MV)
DIC1-4 X3-13,14
8 1 1 1 8 I0.7 DPC-IBSW-111 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-I (MV)
DIC1-8 X3-15,16
9 1 1 2 1 I1.0 DPC-HLS-132 SURGE HOPPER LEVEL SWITCH SYS-I (SV)
DIC2-1 X4-1,2
10 1 1 2 2 I1.1 DPC-IVSP-132 INLET VALVE SEAL PRESSURE SWITCH SYS-I (SV)
DIC2-5 X4-3,4
11 1 1 2 3 I1.2 DPC-IBSW-132 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-I (SV)
DIC2-2 X4-5,612 1 1 2 4 I1.3 DPC-SYSON-121 BED ASH C
OOLERS AT HOOPER-I ON/OFF S S/W SYS-II(MV)
DIC2-6 X4-7,8
13 1 1 2 5 I1.4 DPC-PUR-121 LINE PURGE PUSH BUTTON SYS-II (MV)
DIC2-3 X4-9,10
14 1 1 2 6 I1.5 DPC-OVDPOR-121 PROBE OVE
R RIDE PUSH BUTTON SYS-II (MV)
DIC2-7 X4-11,12
15 1 1 2 7 I1.6 DPC-HLS-121 SURGE HOP LEVEL SWITCH SYS-II (MV)
DIC2-4 X4-13,14
16 1 1 2 8 I1.7 DPC-IVSP-121 INLET VAL
8/16/2019 Io List (Ash) - Rev d - 01.11.12
http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 4/24
VE SEAL PRESSURE SWITCH SYS-II (MV)
DIC2-8 X4-15,16
17 1 1 3 1 I2.0 DPC-VLPS-121 CONVEYING VESSEL LOW PRESSURE SWITCH SYS-II (MV)
DIC3-1 X5-1,2
18 1 1 3 2 I2.1 DPC-VHPS-121 CONVEYING VESSEL HIGH PRESSURE SWITCH SYS-II (MV)
DIC3-5 X5-3,4
19 1 1 3 3 I2.2 DPC-IBSW-121 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-II (MV)
DIC3-2 X5-5,6
20 1 1 3 4 I2.3 DPC-HLS-122 SURGE HOPPER LEVEL SWITCH SYS-II (SV)
DIC3-6 X5-7,8
21 1 1 3 5 I2.4 DPC-IVSP-122 INLET VALVE SEAL PRESSURE SWITCH SYS-II (SV)
DIC3-3 X5-9,10
22 1 1 3 6 I2.5 DPC-IBSW-122 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-II (SV)
DIC3-7 X5-11,12
23 1 1 3 7 I2.6 DPC-SYSON-131 BUFFER HOOPER-I ON/OFF SELECTOR SWITCH (DPV)
DIC3-4 X5-13,1424 1 1 3 8 I2.7 DPC-PUR-131 LINE PURG
E PUSH BUTTON (DPV)
DIC3-8 X5-15,16
25 1 1 4 1 I3.0 DPC-OVDPOR-131 PROBE OVER RIDE PUSH BUTTON (DPV)
DIC4-1 X6-1,2
26 1 1 4 2 I3.1 DPC-HLS-131 SURGE HOP
LEVEL SWITCH (DPV)
DIC4-5 X6-3,4
27 1 1 4 3 I3.2 DPC-IVSP-131 INLET VALVE SEAL PRESSURE SWITCH (DPV)
DIC4-2 X6-5,6
28 1 1 4 4 I3.3 DPC-VLPS-131 CONVEYING
8/16/2019 Io List (Ash) - Rev d - 01.11.12
http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 5/24
VESSEL LOW PRESSURE SWITCH (DPV)
DIC4-6 X6-7,8
29 1 1 4 5 I3.4 DPC-VHPS-131 CONVEYING VESSEL HIGH PRESSURE SWITCH (DPV)
DIC4-3 X6-9,10
30 1 1 4 6 I3.5 DPC-SYSON-141 BUFFER HOOPER-II ON/OFF SELECTOR SWITCH(DPV)
DIC4-7 X6-11,12
31 1 1 4 7 I3.6 DPC-PUR-141 LINE PURGE PUSH BUTTON (DPV)
DIC4-4 X6-13,14
32 1 1 4 8 I3.7 DPC-OVDPOR-141 PROBE OVER RIDE PUSH BUTTON (DPV)
DIC4-8 X6-15,16
MICROMAX
CUSTOMER
----------------------- Page 3-----------------------
DATE 01.11.2012
MICROMAX SYSTEMS PRIVATE LIMITED
W.O No. 12 - 031
TRICHY
SHEET No. 07 OF 13
PLC I/O LISTPROJECT: ET200S NON REDUNDANT PLC - ASH (1x60MW Thermal Power Plant)
P.O REF : MBK069/0290/S/27.6.12M/s.CL A/C ARS METAL
REV NIL A B C D
DIGITAL INPUT
S. Panel PLC Card Ch. Ch. TagDescription
8/16/2019 Io List (Ash) - Rev d - 01.11.12
http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 6/24
Process Value Display Value SignalSignal Card Panel TB ClientNo. No. Tier No. No. Add.
Unit Min. Max. Unit Min. Max. TypeSo./Des. TB Nos. Nos. Ref. Dwg.
33 1 1 5 1 I4.0 DPC-HLS-141 SURGE HOP LEVEL SWITCH (DPV)
DIC5-1 X7-1,2
34 1 1 5 2 I4.1 DPC-IVSP-141 INLET VALVE SEAL PRESSURE SWITCH (DPV)
DIC5-5 X7-3,4
35 1 1 5 3 I4.2 DPC-VLPS-141 CONVEYING VESSEL LOW PRESSURE SWITCH (DPV)
DIC5-2 X7-5,6
36 1 1 5 4 I4.3 DPC-VHPS-141 CONVEYING VESSEL HIGH PRESSURE SWITCH (DPV)
DIC5-6 X7-7,8
37 1 1 5 5 I4.4 DPC-SYSON-151 SYSTEM ON/OFF SELECTOR SWITCH SYS-V (MV)
DIC5-3 X7-9,10
28 1 1 5 6 I4.5 DPC-PUR-151 LINE PURGE PUSH BUTTON SYS-V (MV)
DIC5-7 X7-11,12
39 1 1 5 7 I4.6 DPC-OVDPOR-151 PROBE OVER RIDE PUSH BUTTON SYS-V (MV)
DIC5-4 X7-13,14
40 1 1 5 8 I4.7 DPC-HLS-151 SURGE HOPPER LEVEL SWITCH SYS-V (MV)
DIC5-8 X7-15,16
41 1 1 6 1 I5.0 DPC-IVSP-151 INLET VALVE SEAL PRESSURE SWITCH SYS-V (MV)
DIC6-1 X8-1,2
42 1 1 6 2 I5.1 DPC-VLPS-151 CONVEYING VESSEL LOW PRESSURE SWITCH SYS-V (MV)
DIC6-5 X8-3,4
43 1 1 6 3 I5.2 DPC-VHPS-151 CONVEYING VESSEL HIGH PRESSURE SWITCH SYS-V (MV)
8/16/2019 Io List (Ash) - Rev d - 01.11.12
http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 7/24
DIC6-2 X8-5,6
44 1 1 6 4 I5.3 DPC-IBSW-151 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-V (MV)
DIC6-6 X8-7,8
45 1 1 6 5 I5.4 DPC-HLS-152 SURGE HOPPER LEVEL SWITCH SYS-V (SV)
DIC6-3 X8-9,10
46 1 1 6 6 I5.5 DPC-IVSP-152 INLET VALVE SEAL PRESSURE SWITCH SYS-V (SV)
DIC6-7 X8-11,12
47 1 1 6 7 I5.6 DPC-IBSW-152 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-V (SV)
DIC6-4 X8-13,14
48 1 1 6 8 I5.7 DPC-HLS-153 SURGE HOPPER LEVEL SWITCH SYS-V (SV)
DIC6-8 X8-15,16
49 1 1 7 1 I6.0 DPC-IVSP-153 INLET VALVE SEAL PRESSURE SWITCH SYS-V (SV)
DIC7-1 X9-1,2
50 1 1 7 2 I6.1 DPC-IBSW-153 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-V (SV)
DIC7-5 X9-3,4
51 1 1 7 3 I6.2 DPC-HLS-154 SURGE HOPPER LEVEL SWITCH SYS-V (SV)
DIC7-2 X9-5,6
52 1 1 7 4 I6.3 DPC-IVSP-154 INLET VALVE SEAL PRESSURE SWITCH SYS-V (SV)
DIC7-6 X9-7,8
53 1 1 7 5 I6.4 DPC-IBSW-154 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-V (SV)
DIC7-3 X9-9,10
54 1 1 7 6 I6.5 DPC-SYSON-161 SYSTEM ON/OFF SELECTOR SWITCH SYS-VI (MV)
DIC7-7 X9-11,12
55 1 1 7 7 I6.6 DPC-PUR-161 LINE PURGE PUSH BUTTON SYS-VI (MV)
8/16/2019 Io List (Ash) - Rev d - 01.11.12
http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 8/24
DIC7-4 X9-13,14
56 1 1 7 8 I6.7 DPC-OVDPOR-161 PROBE OVER RIDE PUSH BUTTON SYS-VI (MV)
DIC7-8 X9-15,16
57 1 1 8 1 I7.0 DPC-HLS-161 SURGE HOPPER LEVEL SWITCH SYS-VI (MV)
DIC8-1 X10-1,2
58 1 1 8 2 I7.1 DPC-IVSP-161 INLET VALVE SEAL PRESSURE SWITCH SYS-VI (MV)
DIC8-5 X10-3,4
59 1 1 8 3 I7.2 DPC-VLPS-161 CONVEYING VESSEL LOW PRESSURE SWITCH SYS-VI (MV)
DIC8-2 X10-5,6
60 1 1 8 4 I7.3 DPC-VHPS-161 CONVEYING VESSEL HIGH PRESSURE SWITCH SYS-VI (MV)
DIC8-6 X10-7,8
61 1 1 8 5 I7.4 DPC-IBSW-161 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-VI (MV)
DIC8-3 X10-9,10
62 1 1 8 6 I7.5 DPC-HLS-162 SURGE HOPPER LEVEL SWITCH SYS-VI (SV)
DIC8-7 X10-11,12
63 1 1 8 7 I7.6 DPC-IVSP-162 INLET VALVE SEAL PRESSURE SWITCH SYS-VI (SV)
DIC8-4 X10-13,14
64 1 1 8 8 I7.7 DPC-IBSW-162 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-VI (SV)
DIC8-8 X10-15,16
MICROMAX
CUSTOMER
----------------------- Page 4-----------------------
DATE 01.11.2012
8/16/2019 Io List (Ash) - Rev d - 01.11.12
http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 9/24
MICROMAX SYSTEMS PRIVATE LIMITED
W.O No. 12 - 031
TRICHY
SHEET No. 08 OF 13
PLC I/O LISTPROJECT: ET200S NON REDUNDANT PLC - ASH (1x60MW Thermal Power Plant)
P.O REF : MBK069/0290/S/27.6.12M/s.CL A/C ARS METAL
REV NIL A B C D
DIGITAL INPUT
S. Panel PLC Card Ch. Ch. TagDescription
Process Value Display Value SignalSignal Card Panel TB ClientNo. No. Tier No. No. Add.
Unit Min. Max. Unit Min. Max. Type So./Des. TB Nos. Nos. Ref. Dwg.
65 1 1 9 1 I8.0 DPC-HLS-163 SURGE HOPPER LEVEL SWITCH SYS-VI (SV)
DIC9-1 X11-1,2
66 1 1 9 2 I8.1 DPC-IVSP-163 INLET VA
LVE SEAL PRESSURE SWITCH SYS-VI (SV)DIC9-5 X11-3,4
67 1 1 9 3 I8.2 DPC-IBSW-163 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-VI (SV)
DIC9-2 X11-5,6
68 1 1 9 4 I8.3 DPC-HLS-164 SURGE HOPPER LEVEL SWITCH SYS-VI (SV)
DIC9-6 X11-7,8
69 1 1 9 5 I8.4 DPC-IVSP-164 INLET VALVE SEAL PRESSURE SWITCH SYS-VI (SV)
DIC9-3 X11-9,10
70 1 1 9 6 I8.5 DPC-IBSW-164 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-VI (SV)
DIC9-7 X11-11,12
8/16/2019 Io List (Ash) - Rev d - 01.11.12
http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 10/24
71 1 1 9 7 I8.6 DPC-SYSON-171 SYSTEM ON/OFF SELECTOR SWITCH SYS-VII (MV)
DIC9-4 X11-13,14
72 1 1 9 8 I8.7 DPC-PUR-171 LINE PURGE PUSH BUTTON SYS-VII (MV)
DIC9-8 X11-15,16
73 1 1 10 1 I9.0 DPC-OVDPOR-171 PROBE OVER RIDE PUSH BUTTON SYS-VII (MV)
DIC10-1 X12-1,2
74 1 1 10 2 I9.1 DPC-HLS-171 FEED HOPPER LEVEL SWITCH SYS-VII (MV)
DIC10-5 X12-3,4
75 1 1 10 3 I9.2 DPC-IVSP-171 INLET VALVE SEAL PRESSURE SWITCH SYS-VII (MV)
DIC10-2 X12-5,676 1 1 10 4 I9.3 DPC-VLPS-171 CONVEYIN
G VESSEL LOW PRESSURE SWITCH SYS-VII (MV)
DIC10-6 X12-7,8
77 1 1 10 5 I9.4 DPC-VHPS-171 CONVEYING VESSEL HIGH PRESSURE SWITCH SYS-VII (MV)
DIC10-3 X12-9,10
78 1 1 10 6 I9.5 DPC-IBSW-171 IN-CIRCU
IT/BYPASS SELECTOR SWITCH SYS-VII (MV)DIC10-7 X12-11,12
79 1 1 10 7 I9.6 DPC-HLS-172 FEED HOPPER LEVEL SWITCH SYS-VII (SV)
DIC10-4 X12-13,14
80 1 1 10 8 I9.7 DPC-IVSP-172 INLET VALVE SEAL PRESSURE SWITCH SYS-VII (SV)
DIC10-8 X12-15,16
81 1 1 11 1 I10.0 DPC-IBSW-172 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-VII (SV)
DIC11-1 X13-1,2
82 1 1 11 2 I10.1 DPC-SYSON-181 SYSTEM ON/OFF SELECTOR SWITCH SYS-VIII (MV)
DIC11-5 X13-3,4
8/16/2019 Io List (Ash) - Rev d - 01.11.12
http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 11/24
83 1 1 11 3 I10.2 DPC-PUR-181 LINE PURGE PUSH BUTTON SYS-VIII (MV)
DIC11-2 X13-5,6
84 1 1 11 4 I10.3 DPC-OVDPOR-181 PROBE OVER RIDE PUSH BUTTON SYS-VIII (MV)
DIC11-6 X13-7,8
85 1 1 11 5 I10.4 DPC-HLS-181 FEED HOPPER LEVEL SWITCH SYS-VIII (MV)
DIC11-3 X13-9,10
86 1 1 11 6 I10.5 DPC-IVSP-181 INLET VALVE SEAL PRESSURE SWITCH SYS-VIII (MV)
DIC11-7 X13-11,12
87 1 1 11 7 I10.6 DPC-VLPS-181 CONVEYING VESSEL LOW PRESSURE SWITCH SYS-VIII (MV)
DIC11-4 X13-13,1488 1 1 11 8 I10.7 DPC-VHPS-181 CONVEYIN
G VESSEL HIGH PRESSURE SWITCH SYS-VIII (MV)
DIC11-8 X13-15,16
89 1 1 12 1 I11.0 DPC-IBSW-181 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-VIII (MV)
DIC12-1 X14-1,2
90 1 1 12 2 I11.1 DPC-HLS-182 FEED HOP
PER LEVEL SWITCH SYS-VIII (SV)DIC12-5 X14-3,4
91 1 1 12 3 I11.2 DPC-IVSP-182 INLET VALVE SEAL PRESSURE SWITCH SYS-VIII (SV)
DIC12-2 X14-5,6
92 1 1 12 4 I11.3 DPC-IBSW-182 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-VIII (SV)
DIC12-6 X14-7,8
93 1 1 12 5 I11.4 DISPARE1 RESERVE
DIC12-3 X14-9,10
94 1 1 12 6 I11.5 DISPARE2 RESERVE
DIC12-7 X14-11,12
8/16/2019 Io List (Ash) - Rev d - 01.11.12
http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 12/24
95 1 1 12 7 I11.6 DISPARE3 RESERVE
DIC12-4 X14-13,14
96 1 1 12 8 I11.7 DISPARE4 RESERVE
DIC12-8 X14-15,16
MICROMAX
CUSTOMER
----------------------- Page 5-----------------------
DATE 01.11.2012
MICROMAX SYSTEMS PRIVATE LIMITED
W.O No. 12 - 031
TRICHY
SHEET No. 09 OF 13
PLC I/O LISTPROJECT: ET200S NON REDUNDANT PLC - ASH (1x60MW Thermal Power Plant)
P.O REF : MBK069/0290/S/27.6.12M/s.CL A/C ARS METAL
REV NIL A B C D
DIGITAL INPUT
S. Panel PLC Card Ch. Ch. TagDescription
Process Value Display Value Signal Signal Card Panel TB Client
No. No. Tier No. No. Add.
Unit Min. Max. Unit Min. Max. Type So./Des. TB Nos. Nos. Ref. Dwg.
97 1 1 13 1 I12.0 DPC-SYSON-191 SYSTEM ON/OFF SELECTOR SWITCH SYS-IX (MV)
DIC13-1 X15-1,2
98 1 1 13 2 I12.1 DPC-PUR-191 LINE PURG
8/16/2019 Io List (Ash) - Rev d - 01.11.12
http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 13/24
E PUSH BUTTON SYS-IX (MV)
DIC13-5 X15-3,4
99 1 1 13 3 I12.2 DPC-OVDPOR-191 PROBE OVER RIDE PUSH BUTTON SYS-IX (MV)
DIC13-2 X15-5,6
100 1 1 13 4 I12.3 DPC-HLS-191 FEED HOPPER LEVEL SWITCH SYS-IX (MV)
DIC13-6 X15-7,8
101 1 1 13 5 I12.4 DPC-IVSP-191 INLET VALVE SEAL PRESSURE SWITCH SYS-IX (MV)
DIC13-3 X15-9,10
102 1 1 13 6 I12.5 DPC-VLPS-191 CONVEYING VESSEL LOW PRESSURE SWITCH SYS-IX (MV)
DIC13-7 X15-11,12
103 1 1 13 7 I12.6 DPC-VHPS-191 CONVEYING VESSEL HIGH PRESSURE SWITCH SYS-IX (MV)
DIC13-4 X15-13,14
104 1 1 13 8 I12.7 DPC-IBSW-191 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-IX (MV)
DIC13-8 X15-15,16
105 1 1 14 1 I13.0 DPC-HLS-192 FEED HOPPER LEVEL SWITCH SYS-IX (SV)
DIC14-1 X16-1,2106 1 1 14 2 I13.1 DPC-IVSP-192 INLET VAL
VE SEAL PRESSURE SWITCH SYS-IX (SV)
DIC14-5 X16-3,4
107 1 1 14 3 I13.2 DPC-IBSW-192 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-IX (SV)
DIC14-2 X16-5,6
108 1 1 14 4 I13.3 DPC-SYSON-211 SYSTEM ON
/OFF SELECTOR SWITCH SYS-X (MV)
DIC14-6 X16-7,8
109 1 1 14 5 I13.4 DPC-PUR-211 LINE PURGE PUSH BUTTON SYS-X (MV)
DIC14-3 X16-9,10
110 1 1 14 6 I13.5 DPC-OVDPOR-211 PROBE OVE
8/16/2019 Io List (Ash) - Rev d - 01.11.12
http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 14/24
R RIDE PUSH BUTTON SYS-X (MV)
DIC14-7 X16-11,12
111 1 1 14 7 I13.6 DPC-HLS-211 FEED HOPPER LEVEL SWITCH SYS-X (MV)
DIC14-4 X16-13,14
112 1 1 14 8 I13.7 DPC-IVSP-211 INLET VALVE SEAL PRESSURE SWITCH SYS-X (MV)
DIC14-8 X16-15,16
113 1 1 15 1 I14.0 DPC-VLPS-211 CONVEYING VESSEL LOW PRESSURE SWITCH SYS-X (MV)
DIC15-1 X17-1,2
114 1 1 15 2 I14.1 DPC-VHPS-211 CONVEYING VESSEL HIGH PRESSURE SWITCH SYS-X (MV)
DIC15-5 X17-3,4
115 1 1 15 3 I14.2 DPC-IBSW-211 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-X (MV)
DIC15-2 X17-5,6
116 1 1 15 4 I14.3 DPC-HLS-212 FEED HOPPER LEVEL SWITCH SYS-X (SV-1)
DIC15-6 X17-7,8
117 1 1 15 5 I14.4 DPC-IVSP-212 INLET VALVE SEAL PRESSURE SWITCH SYS-X (SV-1)
DIC15-3 X17-9,10118 1 1 15 6 I14.5 DPC-IBSW-212 IN-CIRCUI
T/BYPASS SELECTOR SWITCH SYS-X (SV-1)
DIC15-7 X17-11,12
119 1 1 15 7 I14.6 DPC-HLS-213 FEED HOPPER LEVEL SWITCH SYS-X (SV-2)
DIC15-4 X17-13,14
120 1 1 15 8 I14.7 DPC-IVSP-213 INLET VAL
VE SEAL PRESSURE SWITCH SYS-X (SV-2)
DIC15-8 X17-15,16
121 1 1 16 1 I15.0 DPC-IBSW-213 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-X (SV-2)
DIC16-1 X18-1,2
122 1 1 16 2 I15.1 DPC-HLS-214 FEED HOPP
8/16/2019 Io List (Ash) - Rev d - 01.11.12
http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 15/24
ER LEVEL SWITCH SYS-X (SV-3)
DIC16-5 X18-3,4
123 1 1 16 3 I15.2 DPC-IVSP-214 INLET VALVE SEAL PRESSURE SWITCH SYS-X (SV-3)
DIC16-2 X18-5,6
124 1 1 16 4 I15.3 DPC-IBSW-214 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-X (SV-3)
DIC16-6 X18-7,8
125 1 1 16 5 I15.4 DISPARE5 RESERVE
DIC16-3 X18-9,10
126 1 1 16 6 I15.5 DISPARE6 RESERVE
DIC16-7 X18-11,12
127 1 1 16 7 I15.6 DISPARE7 RESERVE
DIC16-4 X18-13,14
128 1 1 16 8 I15.7 DISPARE8 RESERVE
DIC16-8 X18-15,16
MICROMAX
CUSTOMER----------------------- Page 6-----------------------
DATE 01.11.2012
MICROMAX SYSTEMS PRIVATE LIMITED
W.O No. 12 - 031
TRICHY
SHEET No. 10 OF 13
PLC I/O LISTPROJECT: ET200S NON REDUNDANT PLC - ASH (1x60MW Thermal Power Plant)
P.O REF: MBK069/0290/S/27.6.12M/s.CL A/C ARS METAL
8/16/2019 Io List (Ash) - Rev d - 01.11.12
http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 16/24
REV NIL A B C D
DIGITAL INPUT
S. Panel PLC Card Ch. Ch.Description P
rocess Value Display Value Signal SignalCard Panel TB ClientNo. No. Tier No. No. Add.
UnitMin. Max. Unit Min. Max. Type So./Des.
TB Nos. Nos. Ref. Dwg.
1 1 1 17 1 I16.0 DPC-BASHLS-802 BED ASH SILO LEVEL SWITCH
DIC17-1 X19-1,2
2 1 1 17 2 I16.1 DPC-FASHLS-802 FLY ASH SILO LEVEL SWITCH
DIC17-5 X19-3,4
3 1 1 17 3 I16.2 DPC-BSBFOF-801 BED ASH SILO BAG FILTER ON FEED BACK
DIC17-2 X19-5,6
4 1 1 17 4 I16.3 DPC-FSBFOF-801 FLY ASH SILO BAG FILTER ON FEED BACK
DIC17-6 X19-7,8
5 1 1 17 5 I16.4 DPC-ARPS-201 CONVEYING AIR RECIEVER PRESSURE SWITCH
DIC17-3 X19-9,10
6 1 1 17 6 I16.5 DPC-CWPS-201 COOLING WATER HEADER PRESSURE SWITCH
DIC17-7 X19-11,12
7 1 1 17 7 I16.6 DPC-RWPS-201 RETURN WATER HEADER PRESSURE SWITCH
DIC17-4 X19-13,14
8 1 1 17 8 I16.7 DPC-IBSHLS-802 INTERMEDIATE BED ASH SILO LEVEL SWITCH HIGH
DIC17-8 X19-15,16
9 1 1 18 1 I17.0 DPC-BMSHLS-802 BED MATERIAL BUNKER LEVEL SWITCH HIGH
8/16/2019 Io List (Ash) - Rev d - 01.11.12
http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 17/24
DIC18-1 X20-1,2
10 1 1 18 2 I17.1 DPC-IBSBFOF-801 INTERMEDIATE BED ASH SILO BAG FILTER ON FEED BACK
DIC18-5 X20-3,4
11 1 1 18 3 I17.2 DPC-BMBFOF-801 BED MATERIAL BUNKER BAG FILTER ON FEED BACK
DIC18-2 X20-5,6
12 1 1 18 4 I17.3 DISPARE9 RESERVE
DIC18-6 X20-7,8
13 1 1 18 5 I17.4 DISPARE10 RESERVE
DIC18-3 X20-9,10
14 1 1 18 6 I17.5 DISPARE11 RESERVE
DIC18-7 X20-11,12
15 1 1 18 7 I17.6 DISPARE12 RESERVE
DIC18-4 X20-13,14
16 1 1 18 8 I17.7 DISPARE13 RESERVE
DIC18-8 X20-15,16
17 1 1 19 1 I18.0 DISPARE14 RESERVE
DIC19-1 X21-1,2
18 1 1 19 2 I18.1 DISPARE15 RESERVE
DIC19-5 X21-3,4
19 1 1 19 3 I18.2 DISPARE16 RESERVE
DIC19-2 X21-5,6
20 1 1 19 4 I18.3 DISPARE17 RESERVE
DIC19-6 X21-7,8
21 1 1 19 5 I18.4 DISPARE18 RESERVE
8/16/2019 Io List (Ash) - Rev d - 01.11.12
http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 18/24
DIC19-3 X21-9,10
22 1 1 19 6 I18.5 DISPARE19 RESERVE
DIC19-7 X21-11,12
23 1 1 19 7 I18.6 DISPARE20 RESERVE
DIC19-4 X21-13,14
24 1 1 19 8 I18.7 DISPARE21 RESERVE
DIC19-8 X21-15,16
MICROMAX
CUSTOMER
----------------------- Page 7-----------------------
DATE 01.11.2012
MICROMAX SYSTEMS PRIVATE LIMITED
W.O No. 12 - 031
TRICHY
SHEET No. 11 OF 13
PLC I/O LISTPROJECT: ET200S NON REDUNDANT PLC - ASH (1x60MW Thermal Power Plant)
P.O REF : MBK069/0290/S/27.6.12M/s.CL A/C ARS METAL
REV NIL A B C D
DIGITAL OUTPUT
S. Panel PLC Card Ch. Ch. TagDescription
Process Value Display Value Signal Signal Card Panel TB Client
No. No. Tier No. No. Add.Unit
Min. Max. Unit Min. Max. Type So./Des. TB Nos. Nos. Ref. Dwg. REMARKS
8/16/2019 Io List (Ash) - Rev d - 01.11.12
http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 19/24
33 1 1 1 1 Q0.0 DPC-SOI-111 SYSTEM ONINDICATION SYS-I (DPV)
DOC1-1 X22-2, DPV-1 Wet contact
34 1 1 1 2 Q0.1 DPC-IVS-111 INLET VALVE SOLENOID COIL SYS-I (DPV)
DOC1-5 X22-4 , DPV-2 Wet contact
35 1 1 1 3 Q0.2 DPC-CVS-111 CONVEYINGAIR VALVE SOLENOID COIL SYS-I (DPV)
DOC1-2 X22-6, DPV-3 Wet contact
36 1 1 1 4 Q0.3 DPC-IVS-112 INLET VALVE SOLENOID COIL SYS-I (DPV)
DOC1-6 X22-8, DPV-4 Wet contact
37 1 1 1 5 Q0.4 DPC-SOI-121 SYSTEM ONINDICATION SYS-II (DPV)
DOC1-3 X22-10,DPV-5 Wet contact
38 1 1 1 6 Q0.5 DPC-IVS-121 INLET VALVE SOLENOID COIL SYS-II (DPV)
DOC1-7 X22-12 , DPV-6 Wet contact
39 1 1 1 7 Q0.6 DPC-CVS-121 CONVEYINGAIR VALVE SOLENOID COIL SYS-II (DPV)
DOC1-4 X22-14, DPV - 7 Wet contact
40 1 1 1 8 Q0.7 DPC-IVS-122 INLET VALVE SOLENOID COIL SYS-II (DPV)
DOC1-8 X22-16, DPV-8 Wet contact
41 1 1 1 1 Q1.0 DPC-SOI-131 SYSTEM ONINDICATION (MV)
DOC2-1 X23-2 , DPV-9 Wet contact
42 1 1 2 2 Q1.1 DPC-IVS-131 INLET VALVE SOLENOID COIL (MV)
DOC2-5 X23-4,DPV-10 Wet contact
43 1 1 2 3 Q1.2 DPC-CVS-131 CONVEYINGAIR VALVE SOLENOID COIL (MV)
DOC2-2 X23-6, DPV-11 Wet contact
44 1 1 2 4 Q1.3 DPC-SOI-141 SYSTEM ONINDICATION (MV)
DOC2-6 X23-8 , DPV-12 Wet contact
8/16/2019 Io List (Ash) - Rev d - 01.11.12
http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 20/24
45 1 1 2 5 Q1.4 DPC-IVS-141 INLET VALVE SOLENOID COIL (MV)
DOC2-3 X23-10, DPV -13 Wet contact
46 1 1 2 6 Q1.5 DPC-CVS-141 CONVEYINGAIR VALVE SOLENOID COIL (MV)
DOC2-7 X23-12,DPV-14 Wet contact
47 1 1 2 7 Q1.6 DPC-SOI-151 SYSTEM ONINDICATION SYS-V (MV)
DOC2-4 X23-14,DPV-15 Wet contact
48 1 1 2 8 Q1.7 DPC-IVS-151 INLET VALVE SOLENOID COIL SYS-V (MV)
DOC2-8 X23-16, DPV-16 Wet contact
49 1 1 3 1 Q2.0 DPC-CVS-151 CONVEYINGAIR VALVE SOLENOID COIL SYS-V (MV)
DOC3-1 X24-2, DPV-17 Wet contact
50 1 1 3 2 Q2.1 DPC-IVS-152 INLET VALVE SOLENOID COIL SYS-V (SV-1)
DOC3-5 X24-4,DPV-18 Wet contact
51 1 1 3 3 Q2.2 DPC-IVS-153 INLET VALVE SOLENOID COIL SYS-V (SV-2)
DOC3-2 X24-6, DPV-19 Wet contact
52 1 1 3 4 Q2.3 DPC-IVS-154 INLET VALVE SOLENOID COIL SYS-V (SV-3)
DOC3-6 X24-8, DPV-20 Wet contact
53 1 1 3 5 Q2.4 DPC-SOI-161 SYSTEM ONINDICATION SYS-VI (MV)
DOC3-3 X24-10, DPV-21 Wet contact
54 1 1 3 6 Q2.5 DPC-IVS-161 INLET VALVE SOLENOID COIL SYS-VI (MV)
DOC3-7 X24-12, DPV-22 Wet contact
55 1 1 3 7 Q2.6 DPC-CVS-161 CONVEYINGAIR VALVE SOLENOID COIL SYS-VI (MV)
DOC3-4 X24-14, DPV-23 Wet contact
56 1 1 3 8 Q2.7 DPC-IVS-162 INLET VALVE SOLENOID COIL SYS-VI (SV-1)
DOC3-8 X24-16, DPV-24 Wet contact
8/16/2019 Io List (Ash) - Rev d - 01.11.12
http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 21/24
57 1 1 4 1 Q3.0 DPC-IVS-163 INLET VALVE SOLENOID COIL SYS-VI (SV-2)
DOC4-1 X25-2, DPV-25 Wet contact
58 1 1 4 2 Q3.1 DPC-IVS-164 INLET VALVE SOLENOID COIL SYS-VI (SV-3)
DOC4-5 X25-4, DPV-26 Wet contact
59 1 1 4 3 Q3.2 DPC-SOI-171 SYSTEM ONINDICATION SYS-VII (MV)
DOC4-2 X25-6, DPV-27 Wet contact
60 1 1 4 4 Q3.3 DPC-IVS-171 INLET VALVE SOLENOID COIL SYS-VII (MV)
DOC4-6 X25-8, DPV-28 Wet contact
61 1 1 4 5 Q3.4 DPC-CVS-171 CONVEYINGAIR VALVE SOLENOID COIL SYS-VII (MV)
DOC4-3 X25-10, DPV-29 Wet contact
62 1 1 4 6 Q3.5 DPC-IVS-172 INLET VALVE SOLENOID COIL SYS-VII (SV-1)
DOC4-7 X25-12,DPV-30 Wet contact
63 1 1 4 7 Q3.6 DOSPARE1 RESERVE
DOC4-4 X25-12, DPV -31
64 1 1 4 8 Q3.7 DOSPARE2 RESERVE
DOC4-8 X25-16, DPV-32
MICROMAX
CUSTOMER
----------------------- Page 8-----------------------
DATE 01.11.2012
MICROMAX SYSTEMS PRIVATE LIMITED
W.O No. 12 - 031
TRICHY
SHEET No. 12 OF 13
8/16/2019 Io List (Ash) - Rev d - 01.11.12
http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 22/24
PLC I/O LISTPROJECT: ET200S NON REDUNDANT PLC - ASH (1x60MW Thermal Power Plant)
P.O REF : MBK069/0290/S/27.6.12
M/s.CL A/C ARS METAL
REV NIL A B C D
DIGITAL OUTPUT
S. Panel PLC Card Ch. Ch. TagDescription
Process Value Display Value Signal Signal Card Panel TB Client REMARKS
No. No. Tier No. No. Add.Uni
t Min. Max. Unit Min. Max. Type So./Des. TB Nos. Nos. Ref. Dwg.
65 1 1 5 1 Q4.0 DPC-SOI-181 SYSTEMON INDICATION SYS-VIII (MV)
DOC5-1 X26-2,DPV-33 Wet contact
66 1 1 5 2 Q4.1 DPC-IVS-181 INLET VALVE SOLENOID COIL SYS-VIII (MV)
DOC5-5 X26-4,DPV-34 Wet contact
67 1 1 5 3 Q4.2 DPC-CVS-181 CONVEYING AIR VALVE SOLENOID COIL SYS-VIII (MV)
DOC5-2 X26-6 ,DPV-35 Wet contact
68 1 1 5 4 Q4.3 DPC-IVS-182 INLET VALVE SOLENOID COIL SYS-VIII (SV-1)
DOC5-6 X26-8 ,DPV-36 Wet contact
69 1 1 5 5 Q4.4 DPC-SOI-191 SYSTEMON INDICATION SYS-IX (MV)
DOC5-3 X26-10,DPV-37 Wet contact
70 1 1 5 6 Q4.5 DPC-IVS-191 INLET VALVE SOLENOID COIL SYS-IX (MV)
DOC5-7 X26-12,DPV-38 Wet contact
71 1 1 5 7 Q4.6 DPC-CVS-191 CONVEYING AIR VALVE SOLENOID COIL SYS-IX (MV)
DOC5-4 X26-14,DPV-39 Wet contact
8/16/2019 Io List (Ash) - Rev d - 01.11.12
http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 23/24
72 1 1 5 8 Q4.7 DPC-IVS-192 INLET VALVE SOLENOID COIL SYS-IX (SV-1)
DOC5-8 X26-16,DPV-40 Wet contact
73 1 1 6 1 Q5.0 DPC-SOI-211 SYSTEMON INDICATION SYS-X (MV)
DOC6-1 X27- 2,DPV-41 Wet contact
74 1 1 6 2 Q5.1 DPC-IVS-211 INLET VALVE SOLENOID COIL SYS-X (MV)
DOC6-5 X27-4,DPV-42 Wet contact
75 1 1 6 3 Q5.2 DPC-CVS-211 CONVEYING AIR VALVE SOLENOID COIL SYS-X (MV)
DOC6-2 X27- 6,DPV-43 Wet contact
76 1 1 6 4 Q5.3 DPC-IVS-212 INLET VALVE SOLENOID COIL SYS-X (SV-1)
DOC6-6 X27- 8,DPV-44 Wet contact
77 1 1 6 5 Q5.4 DPC-IVS-213 INLET VALVE SOLENOID COIL SYS-X (SV-2)
DOC6-3 X27- 10,DPV-45 Wet contact
78 1 1 6 6 Q5.5 DPC-IVS-214 INLET VALVE SOLENOID COIL SYS-X (SV-1)
DOC6-7 X27- 12 ,DPV-46 Wet contact
79 1 1 6 7 Q5.6 DPC-BBFST2-801 BED ASH SILO BAG FILTER SEQUENTIAL TIMER
DOC6-4 X27- 13 ,14 Dry contact
80 1 1 6 8 Q5.7 DPC-FBFST-801 FLY ASH SILO BAG FILTER SEQUENTIAL TIMER
DOC6-8 X27- 15,16 Dry contact
81 1 1 6 1 Q6.0 DPC-IBBFST2-801 INTERMEDIATE BED ASH SILO BAG FILTER SEQUENTIAL TIMER
DOC7-1 X28- 1,2 Dry contact
82 1 1 7 2 Q6.1 DPC-BMBFST2-801 BED MATERIAL BUNKER BAG FILTER SEQUENTIAL TIMER
DOC7-5 X28-3,4 Dry contact
83 1 1 7 3 Q6.2 DOSPARE4 RESERVE
DOC7-2 X28- 5,6
8/16/2019 Io List (Ash) - Rev d - 01.11.12
http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 24/24
84 1 1 7 4 Q6.3 DOSPARE5 RESERVE
DOC7-6 X28- 7,8
85 1 1 7 5 Q6.4 DOSPARE6 RESERVE
DOC7-3 X28- 9,10
86 1 1 7 6 Q6.5 DOSPARE7 RESERVE
DOC7-7 X28- 11,12
87 1 1 7 7 Q6.6 DOSPARE8 RESERVE
DOC7-4 X28- 13,14
88 1 1 7 8 Q6.7 DOSPARE9 RESERVE
DOC7-8 X28- 15,16
:CONTACT RATING FOR INTERPOSSING RELAYS RELATED TO DIGITAL OUTPUT COMMANDS FROMPLC TO PNEUMATIC PANELS SHALL BE 230V AC .AND ITS POWER SUPPLY SHALL BE DERIVED FROM PLC ONLY.
DRY CONTACT:CONTACT RATING FOR INTERPOSSING RELAYS RELATED TO DIGITAL OUTPUT COMMANDS FROM PLC TO Bag filter timer panel SHALL BE 230V AC.
MICROMAX