Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
1
INVITATION OF TENDER
INSTRUCTION TO TENDERERS
AND
GENERAL CONDITIONS OF CONTRACT
FOR
COMPOSITE TENDER FOR CIVIL, INTERIOR
FURNISHING, AIR CONDITIONING, ELECTRICAL & LAN
WORK
AT
DENA BANK – ZONAL OFFICE AVANI HEIGHTS
1ST
FLOOR, 59A CHOWRINGHEE ROAD, KOLKATA- 700020
ARCHITECTS
DESIGN DEI GRATIA PVT. LTD.
DELHI, KOLKATA, HYDRABAD
Kolkata Office:
91/A/2, N.S.C. Bose Road, Tollygunge KOLKATA- 700 040
Email: [email protected] [email protected]
Phone – 9874797212/9874797597
DENA BANK
ZONAL OFFICE, KOLKATA - 700071 NOTE: Necessary drawings may be collected from Architects office
2
SECTION – I
TENDER NOTICE
Sealed item rate tenders are invited on behalf of:
Zonal Manager, Dena Bank, Mangal Kalash, 5th
Floor, 2A, Shakespeare Sarani Kolkata – 71
Name of Work Name of the Work: Composite tender for Civil , Furnishing, Air Conditioning, Electrical & LAN works of the Dena Bank
Location Dena Bank, Zonal Office, Avani Height, 1st floor, 59 A Chowrenghee Road , Kolkata- 700020 (Near Rabindra Sadan Metro)
Time of Completion 60 Days (Sixty Days) from the date of Work Order.
Earnest Money Rs- 92500 /- (Rupees Ninety Two thousand five hundred only) to be deposited in the form of Crossed Demand Draft / Pay order /Bankers Cheque drawn in favour of Dena Bank , payable at Kolkata. No interest will be paid on the Earnest Money deposit.
Tender Cost 3000/- (Rupees Three Thousand Only) Non refundable, drawn in favour of Dena Bank, payable at Kolkata.
Eligibility Only Composite Empanelled Contractor (Please see Pre qualification)
Availability of Tender Document Dena Bank Zonal Office, Mangal Kalash, 5th floor, 2A Shakespeare Sarani, Kolkata – 700071 from 10 a.m to 4.30 p.m (Except Sunday & Bank Holidays).
Submission of Tender At Dena Bank, Zonal Office, 2A , Shakespeare Sarani ,Kolkata – 700071
Last date of Submission On or before 2.00 p.m on 07. 07.2015
Opening of Technical Bid At 12.30 p.m on 08.07.2015
Opening of Financial Bid At 3.30 p.m on 09.07.2015 At Dena Bank, Zonal Office, 2 A Shakespeare Sarani, Kolkata – 700071
Mode of submission of Tender The tender shall be submitted in accordance to the procedure detailed herein., Specified documents shall be sealed & signed by authorized person of the firm in envelope of appropriate size, each of which shall be sealed.
Envelope marked No.1 (Technical Bid) shall contain earnest money deposit, Tender Cost and all other certificates /documents etc. with covering letter signed by authorized person of the firm / Co.
Envelope marked no.2 (Price Bid) Shall contain the price bid and approved make of materials.
Envelope marked no 3 Envelope marked no1&2 shall be placed in a large envelope of adequate size marked no 3 which shall be properly sealed and be Super scribed . “Tender for Avani Height” and be addressed to The Zonal Manager, Dena Bank, Zonal Office Mangal Kalash, 5th Floor, 2A, Shakespeare Sarani, Kolkata –
3
700071.
Clarification , if any To be obtained from, DESIGN DEI GRATIA PVT. LTD., 91/A/2, N.S.C. Bose Road, Tollygunge ,. KOLKATA- 700 040
Validity of tenders Six calendar months from the last date of submission of Tender
The Bank does not bind it to accept the lowest tender and reserves the right to reject any or all
the tenders received without assigning any reason/s there of. The notification of award of
contract will be made to the successful tenderer only in writing by the Bank.
Yours faithfully
For Dena Bank
Sd/-
Zonal Manager
4
PREQUALIFICATION CRITERIA FOR COMPOSITE WORK.
1. Work order and completion certificate for similar type of composite works
inclusive of Civil, Interior, Electrical, LAN & A/C, under the financial category
not less than One Crore.
2. Contractor should provide 1 Work order for similar job amounting at least 75
lac.
3. Contractor should provide 2 work order for similar Job amounting at least 55
lac.
.
4. Contractor should provide 3 work order for similar job amounting at least 35
lac
5. Bank solvency certificate at least for Rs. 75 Lakhs not older than 3 months
from the date of Tender Notice.
6. Average annual financial turnover during last 3-years should be at least one
crore as on 31.03.2015. In support of which, the tenderer should submit audited balance sheet.
7. List of works in hand.
8. The contractor must be empanelled in the Composite Contractor panel of SBI
& its Associate Banks OR PSU OR Government Organizations under the
financial category not less than One Crore.
9. The Contractor must produce a certificate from the Bank/organization about
his empanelment & Satisfactory conduct , such certificate should not be older
than 3 months from the date of Tender. The Bank also reserves the right to
make independent inquiry from the concerned Bank/ organization.
10. Interested parties are requested to submit the tender along-with the required
certificates / documents in technical Bid.
11. The tenderer shall furnish copy of Current Sales Tax (Vat), Income Tax and Service Tax Registration Certificate.
Tenderer should declare by way of affidavit stating that:
12. They were never been defaulted in paying Statutory Taxes & Duties.
13. They were never been black listed / debarred/de-panelled from any Organisation.
14. No civil suits / litigation / arbitration pending in their name nor same have ever aroused during execution of any contract.
Tender submitted without earnest Money Deposit, Tender Cost and other documents specified
above will be disqualified . Further, if any of the above information found false or incorrect the
Bank reserves the right to summarily reject the application without assigning any reason thereof.
5
OTHER T E R M S & C O N D I T I O N
1 Defect Liability Period : One year after actual completion of work.
2 Total security deposit (TSD) : 5 % of the total value of the work, This will
be released after the defect liability period.
3 The contractor shall have the responsibility of complying with the local
shops/ establishments Act and other labour / minimum wages Act and
shall keep all such records/ accounts on payment of wages/attendance as
deemed necessary.
4 Arbitration: As per the standard arbitration clause under the jurisdiction of
Calcutta.
5 Organization: The contractor shall employ competent / qualified supervisor
/ Engineer-in-charge who shall be responsible for the day to day work and
coordinate as necessary with the Architect’s supervisor. Any workman
found guilty of misconduct / theft shall be removed from the site.
6 Damage to property: Any damage to the Bank’s property during the work
period will be recovered from the contractor.
7 The Contractor shall be penalized if the work is not completed within the
scheduled time at a rate of Rs.2000 per day .
8 The Contractor should be registered under VAT, failing which the tender will
be rejected.
9 Deduction : Income tax at source as per I.T Act.
10 TERMS OF PAYMENT : ONLY ONE RUNNING BILL WILL BE PAID
AFTER COMPLETION OF 60 % OF TOTAL WORK CERTIFIED BY
ARCHITECT, THEREAFTER REST PAYMENT WILL BE MADE ON
COMPLETION OF TOTAL WORK.
11 Billing Procedure : All measurements shall be recorded in duplicate on
standard measurement sheets prepared jointly by the Architect’s Site
engineer & The contractor’s representatives duly signed by them. All bills
shall be submitted along with this checked measurement sheets.
12 The payment of the bill shall be made as per the actual measurement as
certified by the architect.
13 The Architect or any officer of the Employers will be free to inspect the work at
the site during the period of execution. Any suggestion of change or
modification to improve the quality of work will be carried out subject to prior
6
approval of the competent authority of the employers and that of the Architect
14 In case of failure to take up the work even after accepting the work order, or
leaving the work incomplete, or for defective work not rectified, or violation of
the terms and conditions, the Bank may take suitable action against the
contractor as appropriate.
15 The Contractor shall have to make their own arrangement at their own cost for
storing arterials, plants, tools etc. The employers will not be liable for security
of the Contractor’s materials.
16 In case of breach of contract by the Contractor for slow progress or works or
any other claim of damage, the Employer or the Architect may have the power
to re assign the contract without assigning any reasons thereof.
17 The Architect shall have the power to ask the contractor to furnish the sample,
colour etc. for any materials used / to be used in the works.
18 The Employer shall not be liable for any damages or compensation payable
as a consequence of any accident or injury to any workman or other persons
in the employment of the Contractor.
19 On completion of the Works, all rubbish, debris, materials, tools, Labourers,
etc. to be removed by the contractor from the site and the contractor will hand
over the site clean & clear & in usable condition within 3 days of completion of
the works. Failing which, the employer may dispose the materials at the cost
of the contractor.
20 In case of any dispute, the matter will be referred to the Zonal Manager, Dena
Bank , Zonal Office Kolkata .
21 The rates quoted in the tender should be inclusive of all sales tax,
excise tax, octroi & other taxes, no escalation of rates will be
allowed under any circumstances.
7
LIST OF APPROVED MATERIALS FOR FURNISHING WORK
SL NO ITEM APPROVED MAKE/ MODEL
1 False Ceiling India Gypsum Ceiling
2 Inter mediate Channel/Ceiling Section Gypsteel
3 Wood Frame Work/ Wood Section All wood must be well seasoned, free from knots, other defects, decay and defects due to handling and transportation. Wherever necessary, provide with anti – termite Treatment.
KAPOOR
4 Wood Skirting / Moulding/ Lipping/ Bidding / Door frame
White Beach / White Ceader
5 Modular furniture Godrej/decor x/space wood
6 Modular Toilet Mario, Green
7 Fire Reterdent Paint : Industrial grade of Noble / Viper
8 Commercial Ply/ Block board Sylvan ply / Green Ply/Century Ply
9 Flush Door Green / Century / Sylvan ply
10 Laminate (1.0mm thk.) Sunmica/Century lam/Royal touche
11 Door Closure Evarite/ Godrej/ Archi (Heavy Duty)
12 Floor Spring : Evarite/ Godrej/ Archi (Heavy Duty)
13 Floor Spring : Evarite/ Godrej/ Archi (Heavy Duty)
14 Door Lock/ Door Handles
Godrej Cylindrical / Hafele/ Hettich / Doorset ( 7 lever )
15 Drawer/ Storage Handle Neki / Hassley
16 Drawer/ Storage Lock Ebco / Hafel / Hettich Dooset/Godrej
17 Screws GKW / Nettle fold / Approved Equivalent
18 Hinges CIEF / Approved equivalent
19 Sliding Drawer Chanels Earl Behari / CIEF
20 Adhesive Fevicol SH / Fevimate TL
21 Soft board Jolly Board / Approved equivalent
22 Vertical Blinds Mac / Annums / Window Fashion
23 PVC Flooring Krishna Vinyl / Armstrong /LG
24 Glass Modiguard / Saint Gobain
25 Ceramic Tiles Kajaria/JHONSON
26 Vitrified Tiles Naveen /Jhonson
27 Tiles Chemical Bal-endura / Latticrete
28 European WC / Wash Basin Parryware / Hindware
29 Sanitary Fittings Jaquar / Essco
30 G.I Pipe ( For Plumbing) Tata / Jindal / Bansal
31 P.V.C Pipe ( For Plumbing Supreme / Oriplast
32 Readymate Keyboard / CPU Trolley ( metal
Ebco / Dortel
33 Paints ( Enamel / Acrylic Emulsion) Asian Paints ( Colour world)/Berger ( Colour Bank) Spectrum
34 Mirror Modiguard / Saint Gobain
35 Carpet Synthetic ( Close loop)
36 Wood Preservatives STP Pentaphene Pale / Chloriphyrophosh
37 Chairs Décor – X
38 Wall Paper Menara/Legend
39 All other items not covered above As per sample approved by Employer /Consultant.
8
LIST OF APPROVED MAKE OF MATERIALS FOR ELECTRCAL WORKS
SL NO ITEM APPROVED MAKE
1 MS pipe ISI mark. 16 SWG BEC / NIC
2 MS pipe ISI mark. 16 SWG BEC / NIC
3 M.S. fittings (Bend / Elbow / G.I Saddle / 3way circular box)
BEC / NIC
4 Wire PVC insulated copper flexible wire. FR Finolex / Havell’s/ R.R.Kable
5 A.C. Starter
North-West / Crabtree/ MDS Legrand
6 250 Volt 6/16 Amp. 3 pin modular type switch,socket
MDS Legrand / Crabtree / ABB/ Anchor AVE
7 Capacitor Mamal / L&T
8 Current Transformer Kappa / L&T/ Schneider (CG) A.E
9 Changeover Switch L&T / HPL / GEC / Havell’s
10 Amps meter & Voltmeter 96x96 mm (Analog) AE / IMP / L&T / ALSTOM / HPL / Havell’s
11 Miniature Circuit Breaker & MCB Distribution Boards,RCBO
MDS / ABB / L&T(Hager) / Schneider(CG)/Siemens/LK Fuga / Havell’s
12 Armoured Cable NICCO / Fort Gloster / Havell’s / CCI
13 Telephone Socket RJ – 11 Crabtree / ABB / MDS Legrand
14 Telephone Cable (0.51mmsq) 10/20 pair National / Delton / Netco / Finolex / Retco
15 Lugs Dowells
16 Light Fittings/ Fixtures Havells/Syska/philips
17 Terminal Connector ESSEN
18 Exhaust Fan E.P.C / G.E.C / Crompton
19 Wall mounted ( Osyliating Type) / Pedestal Fan
Orient / Crompton / Khaitan
20 SFU / SPN / TPN S.M. housing / Open execution front handle with housing
L&T / Siemens / Havell’s
21 Telephone Connector KORN type
22 Selector switch (Rotary type) Kaycee / A.E / L&T/ Siemens
23 Rigid PVC conduit B.E.C., Kalinga, Plaza, AKG, Precession
24 Sliding fuse / DZ fuse Bharat Lender / BCH
25 Clock switch/time switch L&T, MDS, GIC, T&C
26 PVC Tape Steel Grip / Anchor
27 Join box 6”x4” MS box heavy type Local make
28 Bearer Call Bell Anchor / Max / Roma
29 Brass Cable gland Arun(heavy type) / Dowells
30 LED Indicator ( bright type) Mikadov / L&T / MDS
31 PVC flexible pipe Hanuman / Precession / Kalinga
32 MCCB Siemens / L& T / MDS / Havell’s
33 Metal Clad socket & plug having scraping earth arrangement
Siemens / L&T / MDS / Schneider
34 All other items not covered above As per sample approved by Employer/Consultant
9
Summary
FOR DENA BANK AVANI HEIGHTS REGIONAL OFFICE KOLKATA
CIVIL, PLUMBING WORK - A Rs
INTERIOR WORK - B Rs
ELECTRICAL, LAN- C Rs
FIRE ALARM WORK - D Rs
MODULAR FURNITURE – E Rs
AIR CONDITION – F Rs
LOFT AREA- G Rs
TOTAL
(Rs )
DATE
SIGNATURE OF
CONTRACTOR
DATE SIGNATURE OF
ARCHITECT
DATE SIGNATURE OF
ZONAL MANAGER,
DENA BANK, CONTRACTORS ARE REQUESTED TO VISIT THE SITE AND COLLECT ALL OTHER
NECESSARY DETAIL DRAWINGS FROM THE CONSULTANTS OFFICE BEFORE QUOTING.
FOR ANY CONFUSION IN THE DRAWING AND SPECIFICATION PLEASE GET IT CLARIFIED
FROM THE CONSULTANT ARCHITECT BEFORE SUBMISSION OF TENDER.
NO EXTRA WILL BE PAID TO COMPLETE ONE SINGEL ITEM MENTIONED IN THE TENDER
10
PRICE BID OF INTERIOR & FURNITURE WORKS FOR AVANI HEIGHTS, ZO OFFICE, KOLKATA
SL No:
PARTICULARS UNIT Total RATE Amount
1 PARTITION
Providing and fixing partition in position as per design with 2" x 2" sal wood finished section frame work @ 2'0" c/c both ways screwed to the floor and ceiling with M.S. Cleats and to be treated with anti termite oil .The measurement will be taken upto the false ceiling visible height in case of full height partition.The frame work will be claded with 6mm thk commercial ply both sides and to be finished with approved 1.5mm laminate( color with vertical grain) as per design 3"high laminate skirting . Extra frame work to be fixed for fixing glass. In the glazed partition 10mm thk. Etched glass with sand blusting/granular blasting to be provided duly fixed with . wooden lipping 50mm x 25mm all complete duly polished. The work to be completed as per design approval of the archiect.
2 PARTLY GLAZED PARTITION
(I) PARTLY GLAZED FULL HT. PARTITION : SFT 118
(II) Full HT. Partition : One side laminate and One Side Veneer Finish ( Match to Laminate hall area ) for conference room.
SFT 0
3 BLOCKED PARTITION
(I) FULL HT BLOOKED PARTITION (RECEPTION AREAS)
SFT 0
(II)
Full HT. Partition : One side laminate and One Side Veneer Finish ( Match to Laminate Hall areas ) for conference room.
SFT 1260
(III) Full HT. Partition : Both side laminate SFT 200
4 DOORS
Providing and fixing solid core 38 mm solid core flush door finished with lippings in all side with necessary door hinges , cylindrical locks(golden, Godrej) , door clouser, door stoppers, etc with a frame work of T.W. size 75mm x 62.5mm with necessary hold fast fixed to the wall/partition. 1.5mm laminate to be fixed on both sides duly finished,edges to be finished with wooden lippings.A wooden moulding size 11/2" x 1/2" to be provided all along the periferi of the frame work in the both sides . All the wooden area to be duly polished as per specification of the Architect.In case of Partly glazed door 8mm thk etched glass
11
with granular blasting/sand blasting as per design of the Architect to be fixed with necessary mouldings.
A Partly glazed door
(I) Partly glazed door with etching
(7'x3'-0") Nos 5
(ii) Partly glazed door without etching & frosting
7'-0" x 3'-0" /2'-6" for store, server,ups, pantry,
No 3
B Blocked door (7'-00" x 2'-6") IN TOILETS Nos. 3
Full ht. Blocked door.
(I) 7'x2'-6' STORE ROOM No 0
5 MAIN Entrance Glazing with door
Full Ht. Glass Partition & Door FOR MAIN ENTRANCE: The work will be finish 12 thk. toughened glass with (patch fittings) door spring/door closer fittings, including cost of doors. The quoted rate should include for fixing frosted film / one way vision film work, write up in the top two bands of film (frosted /one way vision film) as directed by the Architects. SS handles of size up to 450mm long best make, brass locking arrangement (at top) to be fixed to the door. Glass may be fixed in a ss channel on the floor and wood work.
SFT 70
6 TABLE
A RUNING COUNTER for utility counter RFT. 10
B
MEETING TABLE FOR CONFERENCE ROOM 18'0" X 4'0" AS PER ARCHITECT DESIGN
NOS 1
7 Side and Back Unit (BACK SIDE OF OFFICER)
Providing and fixing Side Unit/ Back unit made out of 19mm
comm. board finished with 1.0mm laminate in all exposed areas
The drawers to be made out of 19mm comm. board in the front
cladded with 1.0mm laminate. sides to be made out of 12mm
comm.ply and bottom made out of 6mm comm ply duly painted in
matching tone and it should play on drawer sliding channels . The
shutters to be made out of 19mm comm. board and should play
12
on drawer sliding castors on powder coated channels. The
necessary locks , handles, etc to be provided . 3" high laminate
skiritng to be provide bottom side of the side and back unit.
Inside of the unit to be enamel painted in
matching tone . All the exposed edeges of the boards/plywoods
be coverd with woden lippings/mouldings duly polished all
complete.The work to be completed as per approval and
specificaion of the Architect.(Match to modular furniture) SFT 80
8 STORAGE
Providing and fixing Full height storage made out of 19mm thk. commercial board finished with 1.5mm laminate in all exposed areas . The drawers to be made out of 19mm comm. board in the front cladded with 1.5mm laminate( color, vertical grain) .sides to be made out of 12mm thk. comm.ply and bottom made out of 6mm thk. comm. ply duly painted in matching tone and it should play on drawer sliding channels . The shutters to be made out of 19mm thk. comm. board and should play on drawer sliding castors on powder coated channels. The necessary locks , handles, etc to be provided . 3" laminated skiritng to be provided bottom side of the unit. . Inside of the unit to be enamel painted in matching tone . All the exposed edeges of the boards/plywoods to be coverd with wooden lippings/mouldings duly polished all complete.The work to be completed as per approval and specificaion of the Architect. (Match to modular furniture)
Full/Low ht storage up to 7'ht. SFT 725
Low ht. storage up to 2'-6" ht. SFT 0
9 SOFT BOARD / NOTICE BOARD
13
Providing and fixing soft board with necessary framework with 12mm thk. commercail ply on top 12 jolly board to be fixed finished with fabric @Rs80 , with necessary mouldings duly polished along the periferi.
SFT 100
10 SOFA
Providing and placing sofa made out of suitable wooden section of approved shape and design ,fixed with springs supported on canvas strapping. The sofa seats should have filling of coir cotton ans high density foam to provide right cousioning.
8" high density foam then 4" low density foam covered with fabric @ Rs120/- as per approval of the Architect.
Seats 4
11 Metal armed Chairs / sofa
Seat & Back made up of 1.5mm thickness perforated cold-rolled steel plate;
with antirust dealing,electronic polishing, Crome coating
Arms & legs are Die casting from deep drawing steel plate
with high strength jointing & polishing in crome plating.
Seats 3
12 Cornice
Providing and fixing wooden cornice moulding along the pheriferi wherever the walls/ partition meets the ceiling.Size 1 1/2" x 1 1/2" duly polished as per approval of the architect.
RFT 350
13 Suggestion Box
Providing and fixing suggestion box as per drawing &approval of the architect
Nos 2
14 Centre Table
Providing centre table as per drawing &approval of the architect .
Nos 2
15 Side Table
Providing centre table as per drawing &approval of the architect . (22"x22" avarage)
Nos 8
16 HALF HT COLUMN PANELLING
Providing & fixing in position column and wall cladding consisting of 12mm thk solid ply and 2" X 1" hard wood section finished with 1mm laminate.
SFT 800
17 Roller Blinds
Providing and fixing Roller blinds of approved design and shade by the Sqft. 780
14
Architect,incl all std fittings as per manufacturer's specification.
18 WALL DISPLAY BEHIND VISITOR AREA
Structure made by 18mm plywood and gypsum board 6" depth boxing ,finish with imm laminate, splot light,flower vase, abstrac paintings as per drawings.
sft 100
19 BACK DROP BEHIND RECEPTION AREA
Structure made by 19mm plywood and gypsum board finish with laminate/veneer, and 10mm frosted glass panelling with splot light,flower vase, abstrac paintings as per drawings.
Sft 75
20 CONSOLE ( CONFERENCE ROOM )
Structure made by 18mm plywood board 1'-6" depth, lower storage 2'-6" boxing, finish with 1mm thick laminate, Top to be granite, spot light, Abstract painting, projector display Glass as per drawing complete
Sft 40
21 OUTER SHUTTTER BOX
Overhead outside shutter box: p/f sal wood frame fixing of 12mm plywood with 1mm thk. Laminate finish and openable shutter for out side area
sft 180
22 Synthetic Door Mat
Providing & fixing synthetic door mat 6mm thk. As per approval of the Architect. Nos 5
TOTAL
15
PRICE BID OF CIVIL WORKS FOR AVANI HEIGHTS, ZO OFFICE, KOLKATA
Sl.No DESCRIPTION Unit Total Rate Amount
CIVIL CAPITAL PART
1 FALSE CEILING ( Gypboard)
Providing and fixing Gypsum false ceiling as per India Gypsum specification for ceiling with drops as per drawing including of providing and fixing G.I. Frame work as per specification of India gypsum at a distance of 2'0" c/c both ways complete with 12.5mm board and all necessary perimeter channels etc. No extra payment will be made for the cutting of light points , stain glass,cove lighting etc. The measurement will be taken in one level , rate should include the drops also, no extra amount will be paid for the drops. The joints to be properly mended with paper tapes and gypsum compound all complete. The rate should include the full completion of the ceiling. At the time of handing over the site all necessary repairing work to be considered if required. The work to be completed as per specification , approval of the Architect.No Drop or design(if any )will be considered as extra measurement it will be considered flat ceiling.
Sft 2000
2 FALSE CEILING (24"x24" GRID FALSE CEILING)
24"x24" Grid False Ceiling ( SILHOULTE GRID ): Providing and Fixing False ceiling Grid using hot dipped Galvonised steel sections, exposed surface chemically cleaned capping pre-finished in baked polyster paint. Main tee of size 3000 x 32 x 24 mm at every 1200mm c/c maximum, 1200mm cross Tee of size 1200 x 27 x 24mm at every 600mm intervals and 600 mm cross Tee of size 600 x 25 x 24mm at every 1200mm max and 3000 x 19 x 19mm wall angle all around the wall to form grid size of 600mm x 600mm . The Main grid to be suspended to the MS frame with 2mm pre-straightened GI wire and GI adjustable clamp and Laying of fibre wool board having Fire rating of 60 min. as per BS 476/23 of 1987 , Noise reduction co-eff. ( NRC ) of 0.50, Light reflectance of 83%, Sound atteneuation of 32db, thermal conductivity of k=0.052 W/m, wt of 4kgs/mts and humidity resistance of RH-95 , with paint finish of 600x600mm x 12mm thick over the Grid. All as per the design and instructions Architects.
Sft 2750
3 ROLLING SHUTTERS
16
Providing and fixing rolling shutters of M.S. sheets of 18 gauge. On the top of the system there will be guide on both sides Sq. bar of 20mm x 20mm is fixed with it and the a clamp 'U'shaped is rolled on it . One no. M.S. pipe fixed over the clamp and a spring is attached with it . The whole system is covered by M.S. sheet.There are both way clips to be attahed two consequitive M.S. curved sheets. At the bottom of the shutters there is a 12 gauge M.S. sheets of 6" high for locking arrangements with lock plate and an angle of 40mm x 40mm x6mm is fitted with it .All these arrangement to ist done including enamel pain . The job to be completed as per approval of the Architect.Position changing as per design.
SFT 120
4 S.S. Railing in stair
Supply, fitting & fixing of Stainless Steel of 304 grade in hand railing using 50mm dia of 2mm thick circular pipe with bolustrade of size 32mm x 32mm x 2mm @ .900 Mtr C/C and stainless steel Square/round pipe bracing of size 32mm x 32mm x 2mm 3 Row in stair case as per approved drawing, design and specification, buffing, polishisng etc with cost of all material, labour, T&P etc required for the complete in all respects.
R.F. 10
5 FLOORING
i Vitrified Flooring
Providing and laying mirror polished vitrified tiles 2'x2' of approved quality (NITCO or approved equivalent) and shade in flooring over a bed of 30mm thick Cement mortar1:4 (1 cement : 4 coarse sand), laid to patterns including necessary cutting, mitring, grouting of joints finished with pigment to match the shade,complete as per detailed drawings. The rate should include protection coat of POP over polythene till handing over. (Basic Rate of Tile Rs. 65/- per sft.)
Sqft. 4300
ii Vitrified Skirting
Providing and laying mirror polished vitrified tiles of approved quality (Kajaria or approved equivalent) and shade, in dado, skirting (6"), etc..over a bed of 25-30mm thick Cement mortar 1:3 (1 cement : 3 coarse sand) / adhesives, laid to patterns including necessary cutting, mitring, grouting of joints white antifungal grout etc., complete as per detailed drawings.
Sqft. 400
6 P.C.C IN FLOORING
i
Providing and laying in position cement concrete 40mm Thick finished with cement sulary including necessary form work, machine mixing, consolidation, finishing, curing etc. in all works at all depth/height & levels. Complete as per specifications,
17
drawings and as directed :The mix proportion shall be by volume.
1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 12.5 mm nominal size) ) with water profing compound.
sft 0
7 CEMENT PLASTER (IN COARSE SAND)
15MM Cement plaster in Toilets on rough side of single or half brick wall of mix 1:6(1 Cement : 4 Coarse sand)
Sft 150
8 Waterproofing in toilets
i
Providing and laying water proofing treatment in sankan portion of WCs bath room etc.,by applying cement slurry mixed with Armourcrete of M/s The Structural Water Proofing Company Pvt. Ltd., or Tapecrete of M/s CICO Engg. Services consisting of applying : (a) after surface preparation, first layer of slurry of cement @ 0.488 kg/sqm mixed with Armourcrete or Tapecrete @ 0.253 kg/sqm. (b) laying second layer of Fibre glass cloth manufactured by M/s The Structural Water Proofing Company Pvt. Ltd. when the first layer is still green. Overlaps of joints of fibre cloth should not be less than 10 cm. (c) third layer of 1.5 mm thickness consisting of slurry of cement @ 1.289 kg/sqm mixed with Armourcrete or Tapecrete @ 0.670 kg/sqm and coarse sand @ 1.289 kg/sqm. This will be allowed to air cure for 4 hours followed by water curing for 48 hours.The entrie treatment will be taken upto 30cm on sidewall. The rate is inclusive of dismantling of toilet floor, taken out Malba from sankan portion & clearing off the debri at ground floor level and shifting out side by mechanical transport to the nearest authorised dumping station, complete
Sqft 700
ii
Providing and fixing fly Ash block in sankan portion toilet and gape filled with cement morter 1:4 (1 Cement : 4 Coarse Sand complete after completing the water proofing work
Cft 200
9 Toilet Wall Tiles
i
Providing & fixing of Wall Tiles of Kajaria with designer series tiles or approved equivalent make on to the walls including base cement plaster of 1:4 ratio (1 cement : 4 fine sand) in proper line and plumb, fixing of tiles with neat cement slurry, filling the tiles joints with matching colour tile grouting material as per detail drawings/ Architects instructions at site complete. UPTO 7'-00" HEIGHT IN TOILET (BACIS COST OF TILE RS 80/- PER SQ.FT.)
Sqft 690
18
ii
Providing and laying flooring and skirting in toilets with Vetrified tile of approved quality with pattern as per drawings laid over 20mm thick chemical gue, jointed with white cement slurry mixed with pigment to match the shade of slab including edge chamfering, surfaces pointing & polishing, etc. complete as per specification & drawing. BACIS COST OF TILE RS.60/- PER SQ.FT.
Sqft 100
10 Granite Stone IN STAIRS (only for Stair Case Riser, treads & lift Lobby)
i
Providing and fixing 18mm thick Mirror polished, pre-moulded, prepolished granite machine cut approved shade in Stair Riser & tread (each step round or patterned as per drawing & Making Groove to the specified size in the stair case step), skirting (Chamfering & Edge Polished) in stair lobby and in similar area with 20mm thick base cement morter 1:4 (1 Cement : 4 Coarse sand) joint treated with white cement mixed with matching pigment complete at all levels.
Sqft 0
ii
Providing and fixing RCC counter 75mm thick with 8mm dia reinforcement @ 150 c/c both ways. The Concrete to be 1:2:4 (1 cement:2 coarse sand :4 stone aggregate 12mm nominal size). Item includes making opening for Wash Basins, Scafollding, Curing and finishing in 12mm plaster on under side. Item also includes provising and fixing 18mm Jet black Granite stone on top and on front edge of the counter. The granite to have opening for wash basin with moulding around the opening and also at leading edge complete.
Sqft 75
iii
Providing and fixing Granite stone Door/Window sills/Jams slabs machine cut, machine polish with moulded edges as per design fixed on wall in cement mortar 1:3 including filling the joints with colour cement complete in all respect.
Sqft. 80
11 Brick Work
i Providing and erecting 4 1/2"
thk,Single brick wall (first class bricks)
in cement and Coarse Sand mortar 1:3
with flush joint complete with material,
labour, scaffolding, curing etc. The rate
to include RCC stiffner at every 1 metre
intervals in 1:2:4 concrete. (Excluding
plastering). The work to include cost
for lintels / cills in RCC required for
Doors , windows, openings etc.
excluding plaster.
Sq.ft -
ii Same as 2.1 but 9" thk ( Double brick
wall) Sq.ft
1,425.00
19
12 PLASTER
P/A 1:4 cement plaster with
waterproofing compound to brick work
in single coat of avg 3/4 " thick finished
to receive plaster of paris levelling
coat.
Sq.ft
2,850.00
13 SANITARY FIXTURES (PROVIDING & FIXING)
I
Providing and fixing vitreous china wall hung type European Water Closet with C.P. bolts, nuts C.I. chair or other hanging arrangement, solid white plastic seat with lid C.P brass hinged and rubber buffers, 32mm dia flush pipe (G.I. of medium class)
Roca Nexo (wall hung type) Each 2
II
Supply and fixing Metropol Flush valve conceal type with cover plate 40mm size including all assorted fittings complete. (
Jaquar - Allied Cat. No. 1091) Each
III
Providing and fixing slim concealed cistern WC with wall Mounting frame & installation kit for wall hung WC with control Plate Smarty Design All Chrome complete
Jaquar Code : CIB-WHT-31801011 XW & CONTROL Plate code : cis-chr-31191510 X
Each 3
IV
Providing & fixing vitreous china Oval wash basin complete with 32mm C.P.cast brass bottle trap and connection pipe to wall with C.P. wall flange and rubber adopter for waste connection
Roca Diverta (undercounter) Each 4
V Providing and fixing Aquasense Senro faucet for under counter wash basin
Jaquar Code SNR-51011 Each 4
VI
Providing and fixing vitreous china corner wash basin complete with 32mm C.P. Cast brass bottle trap and connection pipe to wall with C.P. wall flange and rubber adopter for waster connection
Each 4
Jacquar JDS-WHT-0544 (Corner Basin)
VII
Providing and fixing 15mm C.P brass bib
tap with C.P brass threaded flange
complete, including cutting and making
good the walls wherever required.
Pillar Cock Jaquar Pressmatic taps -
Cat. No. 031) or suitable for Corner
Wash Basin
Each 2
20
VIII
Providing and fixing vitreous china large flat back Urinal Basin , 15 mm dia C.P. spreader pipe, 32 mm C.P. brass waste with domical grating, 32 mm C.P brass bottle trap and unions complete, cast iron hangers for support, including cutting and making good the walls wherever required, of the following make and type:
Roca Chic Each 2
IX
Providing and fixing 12 mm thk toughened frosted glass urinal partition of 690x85x325mm app. size, fixed with SS brackets brass bolts and washers.
12 mm Thk. Toughened frosted - Edge Moulded
Each 4
X
Providing, installing and commissioning Battery operated automatic urinal flushing system, including cutting and making good the walls complete with all necessary fittings to make it operational as required,of the following make and type:
Jaquar - code:SNR-51087 Each 2
XI
Providing and fixing 15mm C.P brass bib tap with C.P brass threaded flange complete, including cutting and making good the walls wherever required.
Jaquar taps - Cat. No. 047 KN) Each 5
XII
Providing and fixing 15mm C.P.brass angle valve with C.P copper connecting pipe 375mm long and nuts, washer with C.P. brass flange complete, including cutting and making good the walls, wherever required.
Each 3
Jaquar - Cat. No. 15053)
XIII
Providing and fixing hand drier of best quality, to be operated with 230 volts, single phase, with fully hygienic condition, with all accessories including cutting and making good the walls, wherever required. (Kopal Model- 20 R or approved equiv
Each 2
XIV
Providing and fixing tissue dispenser complete including cutting and making good the walls wherever required. ("Kimberly Clark" make Cat. 01010 or approved equivalent)
Each 4
XV
Providing and fixing ABS body 0.5litre liquid soap dispenser with simple push lever fitted with liquid soap (one time) including cutting and making good the walls, wherever required. (KIMBERLY - CLARK MAKE or approved equivalent)
Each 4
21
XVI
Providing and fixing C.P. brass towel ring fixed to wooden cleats with C.P. brass screws including cutting and making good the walls wherever required. (Size 300mm dia)
Each 4
XVII
Providing and fixing C.P cast brass twin coat hook fixed to wooden cleats with C.P. brass screws.
Each 4
XVIII
Providing and fixing C.P brass airpurifier container, fixed to wooden cleats with C.P brass screws, complete including cutting and making good the walls wherever required.
Each 4
XIX
Providing and fixing Health faucet in PVC Flexible Tube with wall hook Each 4
Jaquar - (Cat. No. 573)
XX
Providing and fixing Toilet Paper holder in Toilets complete as per drawing vendors specification
Each 4
Jaguar - (Code AHS - 1553)
XXI Provididng and fixing concealed stop cock 15mm
Code con-083 KN Each 4
XXII Providing and fixing C.P. Jaali
100mm Dia Each 2
75mm Dia Each 2
14 Internal Water supply and Drainage
I
Providing and fixing Chloronated Polyvinyl
Chloride (CPVC) Pipes, having thermal stability
for hot & Cold water supply, including all CPVC
plain & brass threaded fitting i/n fixing the pipe
with clamps at 1.00 M spacing. This includes
jointing of pipes & fittings with one step CPVC
solvent cement and the cost of cutting and
making good the same including testing of joints
complete as per direction of Engineer in Charge.
(CONCEALED WORK: including cutting chases
and making good the same walls etc. complete
a 15.00 mm nominal outer dia. R.F. 20
b 20.00 mm nominal outer dia R.F. 50
II
Providing & fixing UPVC soil, waste, vent pipework comprising UPVC pipe conforming to IS :4985-1983 and of required class as specified below and fittings (moulded as well as fabricated) like elbows, bends, reducers, threaded tail pieces, caps and and other specials. jointing with cement solvent, chasing, cutting and making good the walls, complete in all respects including testing of
22
complete installation.
a 50mm dia Rft. 15
b 75 mm dia Rft. 15
c 100mm dia Rft. 15
iii
Providing & fixing UPVC deep seal P or S trap of self cleansing design with or without vent arm with provision for connecting G.I.inlet fitting complete including cost of cutting and making good the walls and floors wherever required.
a For 100mm inlet and100mm outlet. Each 3
b For 100mm inlet and 75mm outlet. Each 4
iv
Providing and fixing cast brass Clean Out / Floor Clean Out plug with suitable insert keys for opening, male threaded joint with G.I. socket lead caulked to soil pipe / waste pipe of C.I. and C.I.(LA) pipe as required complete as shown in the Sketch.
a 100mm dia R.O.
b 150mm dia R.O.
Providing & fixing 6 mm thick looking mirror of Modi, Atul or approved equivalent make. The mirror will be fixed on 3/4" dia SS finish stud, all complete as per instructions at site.
nos 4
TOTAL OF CAPITAL PART
PRICE BID OF CIVIL WORKS FOR AVANI HEIGHTS, ZO OFFICE, KOLKATA Sl.No DESCRIPTION Unit Total Rate Amount
CIVIL CAPITAL PART
`
1 POP
Providing and applying pop on wall & column as per required and to give a smooth surface as per approval of the Architect .
SFT 2000
2 PAINTING
a
Providing and applying Acrylic emulsion paints after removing the damaged plaster , replastering with 12mm thk cement morter finished with P.O.P to make the necessary smoothnes , reparing all damages . Then two coats of Primer of approved make to be applied finished with two or more coats of acrylic emulsion paints .The work to be completed as per approval and satisfaction of the Architect.
SFT 9000
23
3 TEXTURE PAINT
Providing , spraying and applying Texture paint as per approved shade as per approval of the architect. Bi colour texture paint will be used. The wall surface has to duly prepared by scraping , removing the damaged plaster and applying P.O.P to give a smooth surface as per approval of the Architect.
SFT 400
4 SYNTHETIC ENAMEL PAINT : FOR WINDOW GRILL, ROLLING SHUTTER & COLLAPSEABLE GATE
SFT 400
5 DISMENTALING
i Dismantling & Removing of Wall Tile manually in ladies and Gents Toilet with rough plaster and stacking the Malba at all floor/level
Sft. 850
ii
Dismantaling of breaking stone/tiles in stairs,
Riser and Tread and in lobby from Ground Floor
to 3rd floor and removing/shifting Malba at
ground floor level and shifting out side by
mechanical transport & dump at nearest
authorised dumyard, complete.
Sft. 0
iii Removing Plumbing C.P. Fitting and Chinaware From G/F to 4th Floor
LS
iv Removing Electrical fiting in hall and toilet area all floor/level
LS
v M.S Railing for stair case from ground floor to Mezzanine floor (7'-6")
LS 0
vi
Taken out existing window and stacking upto ground floor level including repairing the sills, Jams & Lantel
Sft. 0
6 Rubberized vinyl FLOORING
Providing and fixing 8.0mm thick Rubberized vinyl FLOORING complete in all respect as per architect choice in Server and Electric Room
SFT 150
7 ANTI TERMITE
Providing & Injecting chemical emulsion for post constructional (Anti Termite treatment etc. complete covered area shall be measured for payment) using Aldrin or equivalent emulsifiable concentrate (0.5%)
Sft. 5500
TOTAL OF CAPITAL PART
GRAND TOTAL FOR CIVIL
24
PRICE BID OF ELECTRICAL WORKS FOR AVANI HEIGHTS DENA BANK,ZO
KOLKATA
S.NO. DESCRIPTION QTY.
UNIT RATE AMOUNT
VII ELECTRICALS
I MAIN PANEL & SWITCHGEAR
Supply, installation, testing &
commissioning of Wall Mounting
compartmentalised panels
fabricated out of CRCA sheet
steel sections after carrying out 7
tank cleaning process and duly
powder coated using Siemens
Grey Shade No. RAL 7032. The
frame structure, doors and gland
plates shall have 2.0 mm thk
sheets and partitions shall be
with 1.6 mm thick CRCA sheet.
The panel shall be dust and
vermin proof with neoprene
gasketing. The doors shall be
provided with concealed hinges
and with brazing wherever
required to avoid deformation
and shall be earthed. The busbar
shall be of Electrolytic Grade
Aluminium with epoxy supports
and shall be insulated with colour
coded heat shrink sleeves. The
Panel shall be provided with CTs,
phase indication lamps, meters,
relays whereever it has included
in the respective panels along
with all switchgear, etc. as per
the SLD. The panel shall be
complete in all respects as per
the final approval of the
Consultant.
1.1a Providing & installing MAIN
PANEL--1A :
ii Digital VAF Meter and 1 SET -
phase indicating lamps with MCB
BACK UP.
iii Busbar chamber - 1 set, 4 pole
150 AMPS electrolyte grade
Aluminium busbar with necessary
gland plate. Busbar shall be
having necessary number of
poles of suitable sizes alongwith
double washers and nut, bolts for
taking connections for various
loads.
25
1.1B MAIN VTPN DB
Supplying, installing, testing &
commissioning
of 24 Slots, Vertical busbar, MCB
type Power Distribution
Board (MAIN VTPN DB), flush
mounted on wall, sheet
metal fabricated , powder coated,
having
dust-proof and vermin proof ,
and hinged door
with all internals such as DIN
rails, neutral-link,
interconnected wiring complete
with earthing
lugs housing following
switchgears.
1 no., 160A, 4P MCCB as incomer
4 no., 63/40A, TP MCB
8 no.,40/32/25 A SP MCB
6 nos, 20/16A, SP, MCB outgoing
1.00 SET
d.1 160 amps 4P CHANGE
OVERSWITCH ON LOAD TYPE in
sheet steel enclosure complete
with all mounting accessories
before lighting DB with necessary
cable jointing adaptor box
1.00 No
i 32/25A roll socket complete with
32/25/16/10 amps DPMCB with 3
pin metal clad socket -
waterproof tight (IP 65) for wall
unit split AC machine
22.00 Nos
k.2 40A/32A DP MCB in sheet steel
enclosure complete with all
mounting accessories for UPS &
others
2.00 Nos
Providing and Supplying 40 A TP
MCB as a master Switch to switch
off all the LDB Loads,located at
the Entrance of the Branch.
2.00
Nos.
II DISTRIBUTION BOARDS
26
Supply, installation, testing &
commissioning of Distribution
Boards surface / flush mounted
with Double door containing
MCB/ELMCB as incomer and
SPMCB as outgoing. All MCBs
are of 10KA breaking capacity
and ELMCBs/RCCB should be of
30mA/100 MA sensivity. The DB
shall have appropriate no. of top
and bottom knock outs for
outgoing circuits and shall be
complete with necessary
busbars, interconnection
terminals and earth studs. All
terminations in DB shall be
complete with ferulling, dressing
and all circuits shall be properly
labeled with PVC strip (sticker
type) having identification as per
the final approval of Consultant.
For UPS DB MCB shall be 'D' type
and other MCBs shall be 'C'
category for lighting and raw
power DB
1 Lighting & power Distribution
Board -
4.00 No
12 way TPN DB
Incomer40A 4P MCB C
TYPE+elcb30mA
Outgoings :6/10 SP MCB, 'C'
Type - 36 Nos
2 Power Distribution Board
(ATM ROOM) - No
4 way TPN DB
Incomer:40A 4PMCB+ ELCB 100
ma
Outgoings : 32 A SP MCB - 2 Nos
; 16/20 SP MCB, 'C' Type - 4
Nos
3 UPS Power Distribution Board
-(FOR 5KVA UPS)
4.00 No
12 way SPN DB
Incomer:40A DP MCB, 'D' Type
Outgoings :16/10 SP MCB, 'D'
Type – 10Nos
4 UPS Power Distribution Board
- UPS DB-2KVA-ATM) - No
6 way SPN DB
Incomer20A DP MCB, 'D' Type
Outgoings :16/20 SP MCB, 'D'
Type - 4 Nos
27
III CABLES & ACCESSORIES
Supply & installation of following
LT cables rates for 600 / 1100
volts AC as per IS standard 1554
Part 1 with necessary M.S.
clamps. All cables shall be
properly clamped or tied when
run on cable trays. All such
cables shall be provided with
temporary labelling at every 20
mtrs and ten finally with metal
identification tags showing the
size and the location from/to the
specific Panel/DB at both ends.
2 3.5C x 50sq. mm AYFY ( AI ).
300.00 Mtr
6 4C x 10sq. mm YWY ( Cu )
300.00 Mtr
7 4C x 6sq. mm YWY cable ( Cu )
280.00 Mtr
8 3C x 6sq. mm YWY cable
200.00 Mtr
9 3C x 4sq. mm YWY cable ( Cu )
250.00 Mtr
10 3C x 2.5sq. mm YWY cable ( Cu )
240.00 Mtr
13 1C x 10sq. mm YY cable ( Cu ) - Mtr
B Termination of following sizes
of cables
1 3.5C x 35sq. mm AYFY ( AI )
18.00 Nos
2 4C x 10sq. mm YWY ( Cu )
18.00 Nos
3 4C x 6sq. mm YWY cable ( Cu )
25.00 Nos
4 3C x 6sq. mm YWY cable
25.00 Nos
5 3C x 4sq. mm YWY cable ( Cu )
25.00 Nos
6 3C x 2.5sq. mm YWY cable ( Cu )
18.00 Nos
7 1C x 10sq. mm YY cable ( Cu ) - Nos
IV WIRING & ACCESSORIES
28
Supply, installation, testing &
commissioning of wiring for light
points, power points.Circuit
wiring shall include wiring from
Distribution Board upto switch
board or first light point for
circuits controlled directly by MCB
and shall be measured per point
basis as primary point in
numbers. Secondary points shall
also be measured in nos.and
shall include the remaining light
points of the circuit. If two switch
boards are looped on the same
circuit but located at a distance
of more than 5 mtrs., then wiring
shall be measured as primary
points ( 2 nos) NOTE: (Location
of Distribution Board and
switches are shown on the
drawing are indicative and these
can change as per the site
conditions. No extra cost shall be
paid to the contractor for any
such change. All PVC conduit
rigid pipes shall be of MMS type
and wires shall be of FRLS or FR
type)
1 PRIMARY POINT WIRING
including circuit wiring from
DB/MCB to switch board or first
light point in 25 mm dia. PVC
conduit heavy gauge of 2 mm
wall thickness, using 2 x 2.5 sq.
mm PVC insulated coper wires
and 1.5 sq. mm green colour PVC
insulated copper wire for
earthing. Conduits to be surface
mounted on ceiling, concealed in
wall or through partitions of
cabins, complete with junction
box/pull box. Ceiling - rose or
brass light holder and proper
clamping as per the final
approval of Architect / Consultant
( Wires shall be FRLS type )
54.00 Nos
29
2 Providing point wiring for
Secondary light points using 2 x
1.5 sq. mm copper conductor
PVC insulated wires and 1.0 sq.
mm PVC insulated green colour
copper earth wire for continuous
earthing upto fixture & switch
board in PVC conduits of 20 mm
dia & 2 mm wall thickness,
surface mounted on ceiling,
concealed in wall and or through
partitions with necessary boxes /
pull boxes, ceiling - rose or bright
light holder and proper clamping
complete as per the final
approval of Architect / Consultant
( Wires shall be FRLS type )
40.00 Nos
3 PRIMARY POINT WIRING
including circuit wiring from
DB/MCB to switch board or first
light point in 25 mm dia. PVC
conduit OF FIRE RETARDENT
(FLAME PROOF), using 2 x 2.5
sq. mm FRLS PVC insulated
coper wires and 1.5 sq. mm
green colour FRLS PVC insulated
copper wire for earthing.
Conduits to be surface mounted
on ceiling, concealed in wall or
through partitions of cabins,
complete with junction box/pull
box. Ceiling - rose or brass light
holder and proper clamping as
per the final approval of Architect
/ Consultant ( Wires shall be
FRLS type )
16.00 NOS
3.1 SIMILAR TO ITEM NO 3 BUT
SECONDARY LIGHT POINT
10.00 NOS
4 Point wiring Emergency Light
Point from DB/MCB to switch
board or first light point in 25
mm dia. PVC conduit heavy
gauge of 2 mm wall thickness,
using 2 x 2.5 sq. mm PVC
insulated coper wires and 1.5 sq.
mm green colour PVC insulated
copper wire for earthing.
Conduits to be surface mounted
on ceiling, concealed in wall or
through partitions of cabins,
complete with junction box/pull
box. Ceiling - rose or brass light
holder and proper clamping as
per the final approval of Architect
/ Consultant (Wires shall be FRLS
type )
Nos
30
5 Providing point wiring for
Secondary light points using 2 x
1.5 sq. mm copper conductor
PVC insulated wires and 1.0 sq.
mm PVC insulated green colour
copper earth wire for continuous
earthing upto fixture & switch
board in PVC conduits of 20 mm
dia & 2 mm wall thickness,
surface mounted on ceiling,
concealed in wall and or through
partitions with necessary boxes /
pull boxes, ceiling - rose or bright
light holder and proper clamping
complete as per the final
approval of Architect / Consultant
( Wires shall be FRLS type )
Nos
6 Providing point wiring for
Exhaust/wall Fan point looped
from the existing lighting circuit
using 2 x 2.5 sq. mm copper
conductor PVC insulated wires
and 1.0 sq. mm PVC insulated
green colour copper earth wire in
PVC conduit of 20 mm dia,
2dmm wall thickness with
necessary junction box / pull
boxes complete as per final
approval of Architect /
Consultant. (Cost of switch
socket to be considered
elsewhere). ( Wires shall be
FRLS type )
28.00 Nos
31
7 Providing primary point wiring for
a cluster of 3 nos., 13 amps
socket outlets for Computer
Power Primary Point using 2 x 4
sq. mm PVC insulated copper
conductor wires and minimum
2.5 mm copper conductor PVC
insulated green colour earth wire
for continuous earthing from
UPSDB to first point of the circuit
in underfloor raceways or PVC
conduits as specified and then in
flexible PVC conduit. (maximum
4 nos. clusters shall be connected
on one circuit) switch and
sockets to be mounted on front
plate on partitions of furniture on
hot dipped GI boxes concealed in
wall 16A single pole plate switch
with interconnections complete
as per final approval of
Architect/Consultant. (Cost of
raceways and switch sockets to
be considered elsewhere). (
Wires shall be FRLS type )
12.00 Set
8 Providing point wiring for
Computer Power Secondary
Points using 2 x 2.5 sq. mm PVC
insulated copper conductor wires
and minimum 1.5 mm copper
conductor PVC insulated green
colour copper earth wire for
continuous earthing upto 6A
socket outlet, in PVC conduits
through partitions of cubicles. (
Wires shall be FRLS type )
10.00 Nos
9 Providing point wiring for Raw
Power 6A switch socket outlet
from PDB using 2 x 2.5 sq. mm
PVC insulated copper conductor
wires and minimum 2.5 mm
copper conductor PVC insulated
green colour earth wire for
continuous earthing upto 6A
socket outlet in underfloor
trunking / cable tray & PVC
conduit of 20 mm dia concealed
in wall or / and through partition
of cubicles with 6A SP switch and
sockets mounted on front plate
with hot dipped GI boxes. (
Max. 8 nos. sockets shall be
looped on one circuit - Wires
shall be FRLS type )
a Primary points of 6A switch
socket outlet
8.00 Nos
32
b Secondary points of 6A switch
socket outlet looped from
primary point
10.00 Nos
10 Providing point wiring for Raw
Power 6A switch socket outlet to
be looped from the nearest point
using 2 x 2.5 sq. mm copper
conductor wires and minimum
1.5 sq. mm copper conductor
PVC insulated green colour earth
wire in 20mm PVC conduit of 2
mm wall thickness as per
approval of Architect /
Consultant. ( Wires shall be
FRLS type )
Nos
11 Providing point wiring for Raw
Power 6/16A switch socket outlet
from PDB using 2 x 4 sq. mm
PVC insulated copper conductor
wires and minimum 2.5 mm
copper conductor PVC insulated
green colourearth wire for
continuous earthing upto 16A
socket outlet in underfloor
trunking / cable tray & PVC
conduit ( RIGID/FLEXIBLE) of
20/25 mm dia concealed in wall
or / and through partition of
cubicles with 16A SP switch and
sockets mounted on front plate
with hot dipped GI boxes. (
Max. 2 nos. sockets shall be
looped on one circuit - Wires
shall be FRLS type )
a Primary points of 16A switch
socket outlet
5.00 Nos
b Secondary points of 16A switch
socket outlet looped from
primary point - Nos
33
12 Providing point wiring for UPS
Power 6/16A switch socket outlet
for Access Control, Fire Alarm
Panel & CCTV Monitor from UPDB
using 2 x 2.5 sq. mm PVC
insulated copper conductor wires
and minimum 2.5 mm copper
conductor PVC insulated green
colour earth wire for continuous
earthing upto 16A socket outlet
in underfloor trunking / cable
tray & PVC conduit of 20/25 mm
dia concealed in wall or / and
through partition of cubicles with
16A SP switch and sockets
mounted on front plate with hot
dipped GI boxes. ( Max. 2 nos.
sockets shall be looped on one
circuit - Wires shall be FRLS type
)
a Primary points of 16A switch
socket outlet
5.00 Nos
b Secondary points of 16A switch
socket outlet looped from
primary point nos
14 Providing point wiring for UPS
Power 20A industrial socket
outlet for ATM Machine from
UPDB using 2 x 4 sq. mm PVC
insulated copper conductor wires
and minimum 2.5 mm copper
conductor PVC insulated green
colour earth wire for continuous
earthing upto 16A socket outlet
in underfloor trunking /PVC
conduit pipe (RIGID/FLEXIBLE) of
20 mm/25mm concealed in wall
or / and through partition of
cubicles with 16A SP switch and
sockets mounted on front plate
with hot dipped GI boxes. (
Max. 2 nos. sockets shall be
looped on one circuit - Wires
shall be FRLS type )
2.00 Nos
15 Supply and installation of
Perforated Cable Tray out of 14
gauge GI sheet complete with
necessary fixing arrangement
with Anchor Fastener and all
other accessories as per the final
approval of the
Consultant/Architect
c 150 x 50 x 2mm Mtr
34
16 Supply and installation of AL
raceway with 2 mm thickness &
proper ties/clamps at appropriate
intervals & as per the route
approved by
Architect/Consultant. (Cost of
cutting the floor for laying of
raceways to be included).
e 3 runs of underfloor AL raceways
of size 65 x 40 mm - Mtr
17 Supply & installation of GI
junction boxes with 2 mm
thickness, openable cover on top
and having screw fixed plates on
all four sides with knock out
holes for conduits. The plates
shall be retained on the sidezs
having no conduit or raceway so
as to avoid the entry of any
unwanted material. Earth stud to
be provided for all Junction boxes
for earthing. Junction box to be
prepared as per the final
approval of Architect/Consultant.
c suitable for 350 x 350 x 50/65
mm - Nos
18 Supply & installation of 25 mm
dia heavy gauge (MMS) PVC
conduit of 2 mm wall thickness
with pull box / junction box & all
accessories for Voice/Data &
Power wiring as per the
requirement
500.00 Mtr
18a - do - but flexible conduit pipe
150.00 Mtr
20 Supply, installation, testing &
commissioning of flush mounted
plate type switch and switch +
sockets with hot dipped GI box
complete as per the final
approval of Architect/Consultant
a 6A one way plate type switch
155.00 Nos
b 6A 5pin switch socket outlet
(Raw power)
60.00 Nos
c 3 nos. 6/13A flat pin Universal
socket & 1 no. 16A switch with
indicator (UPS Power)
22.00 Sets
d 6/16A switch socket outlet (UPS
/ Raw power)
22.00 Nos
e 20A switch socket outlet with
indication
4.00 Nos
f 3 x 3 MS box for data & voice
(Duplicate / Quadruplicate plate )
45.00 Nos
35
g Electronic Regulator for Ceiling
fan Heavy duty - Nos
V LIGHTING FITTINGS
Supply, installation, testing &
commissioning of the following
concealed / surface mounted or
suspended light fixtures with
lamps, ballast & all necessary
mounting & supporting
accessories & as per the final
approval of Architect / Consultant
1 2x2 48W SCOOP LED HAVELS
MAKE FITTING (LHEWEE P7 PL
1W048
58.00 Nos
2 18W 6" DIA led Edge - lit Panal
(Ultra Slim) (LHEBJN P7IZ1W018
60.00 Nos
3 2 x 18W downlighter CFL - Nos
4 1 x 18W downlighter CFL - Nos
5 28W tube 4' 0" T5 .
36.00 Nos
6 1x36W tube Industrial (WIF
14240)
4.00 Nos
7 CEILING FAN24"/36"/48"
4.00 Nos
8 1X11W PL LIGHT Fitting
4.00 Nos
9 12 x50W Halogen Spot Light
5.00 Nos
10 Exhaust fan - 225 mm size
3.00 Nos
11 WALL FAN
18.00 Nos
VI EARTHING
36
1 Supply & erection of Earth
Station of copper earth plate type
, size: 600 x 600 x 3 mm buried
in specifically prepared earth pit
2.5/3 mtr below ground &
having put 40KG each of
charcoal and salt with alternate
layers & provided with 19 mm
dia GI Watering pipe with funnel
duly prvided with wire mesh for
watering and complete with
brick masonary block for Earth
Station chamber with Hinges
type C.I. TOP cover complete as
per para 7.3 of I.S. 3043 with
25x3mm copper earth strip
bolted to the plate of 2.5 mtr
long & brought up till E/Stn
masonery Chamber & duly
provided & connected to Test
Terminals strip as per IS 3043.&
as per directions of
Architect/consultant and carrying
out necessary test with Earth
Megger for measuring the Each
E/Stns ER Value and recording
the results & submit the same to
consultant/Architect for
verification..
2.00 Nos
PROVIDING AND FIXING OF G.I
EARTHNG AS PER IS 3043
STANDARD
2.00 NOS
2 Supply & erection of copper strip
of 25 x 3 mm used for earthing
on wall with necessary copper
clamps fixed on wall painted with
bituminous paint in an approved
manner (Joints to be tinned and
rivetted)
50.00 Mtr
3 Suplying and erecting Cu strip of
30 x 6 mm of 300 mm length in
350 x 200 x 85 box with acrylic
fascia used for earthing on wall
with necessary clamps fixed on
wall painted with bituminous
paint in an approved manner
(Joints to be tinned and rivetted)
- Nos
4 1 no. 16 sq. mm YY cable in 25
mm PVC conduit for UPS earthing
85.00 Mtr
5 Supplying & erecting bare copper
conductor of 12 swg for earthing
purpose of DBs
85.00 Mtr
6 Supplying & erecting bare copper
conductor of 8 swg for earthing
purpose of AC machines
85.00 Mtr
37
7 Supplying & erecting 4 sq mm
copper conductor PVC insulated
wire in 20 mm PVC conduit for
earthing of UPDB machines
45.00 Mtr
8 Wiring for intrusion alarm-
Supply & laying of cables - LS
9 Supply & laying of 2C x 1.0 sq.
mm non-FRLS flexible PVC
insulated cable in pvc conduit
pipe
- Mtr
10 Supply & laying of Unarmoured
RG 6 non-FRLS flexible PVC
insulated cable for video
transmission in PVC CODUT pipe
- Mtr
D Data /Voice Network System
1 Supply & Installation of cat - 6
Data Cable
600.00 Mtr
2 RJ - 45 Data Socket With Plate
600.00 Nos
3 RJ - 11 Voice Socket
60.00 Nos
4 Supply & Installation of Voice
Cable - 4 pair Telephone Cable
un armoured PVC Sheated .
300.00 Mtr
5 20 Pair Tag Block Crome type on
MS box
1.00 Nos
6 P/F 9U Rack - Nos
7 EPABX Box - Nos
8 Patch code-3 Meter
60.00 Nos
9 Patch code- 1.5 Meter( inside
rack to connect router to patch
panel)
60.00 Nos
10 24 Port Switch - Nos
11 24 Port Jack Panel - Nos
GRAND TOTAL SUPPLY +
INSTALLATION TOTAL
38
PRICE BID FOR FIRE ALARM WORKS DENA BANK ZO OFFICE , KOLKATA
S.NO. PARTICULARS WITH DESCRIPTION UNIT TOTAL RATE AMOUNT
1
Cabling with 1.5 sqmm 2 core copper conductor Pvc insulated ,PVC sheated armoured cable. mtr 950
2 Smoke detector (Applo /godrej) No 25
3 Heat detector (Applo /godrej) No 35
4 Hooter No 2
5 Respones Indicator No 12
5 Manual call bell point No 5
6 6 Zone fire panel (Apollo /godrej) No 2
7 Auto dialler No 2
8 Exit Sign Board No 2
TOTAL
39
PRICE BID FOR MODULER WORKS AT AVANI HEIGHT, DENA BANK ZO KOLKATA
Sr. No.
Category Size
Qty. Unit Rate Amount
H W D (Rs.) (Rs.)
1 LINEAR WORKSTATION 0.76 1.371 0.610 5 Nos
Comprises of Partition: Low height partition of 1219mm height and 52mm thickness having internal framework with dual raceways made of MS (CRCA) duly powder coated and trims made of extruded aluminium sections duly powder coated. Panels available in following options: Laminate / Fabric / or White board as per requirement. Worktop: Made of 25mm thick prelaminate particle board having edge bandings on all exposed areas. Metal Key Board Tray and cpu trolley and Pedestal.
2 CURVILINEAR WORKSTATION 1.5 1.370 0.610 38 Nos
Comprises of Partition: Low height partition of 1219mm height and 52mm thickness having internal framework with dual raceways made of MS (CRCA) duly powder coated and trims made of extruded aluminium sections duly powder coated. Panels available in following options: Laminate / Fabric / or White board as per requirement. Worktop: Made of 25mm thick prelaminate particle board having edge bandings on all exposed areas. Metal Key Board Tray and cpu trolley and Pedestal.
3 CM CABIN 0.73 1.650 0.750 1 Nos
Main table of size 1650x750mm - Fabricating and fixing of main table formed of 25mm thk prelam board. Table top to have pvc edge lipping as per architects instructions. to have one no. of side storage of size : .900mm (L)x 750mm (H) X 450mm (D), and back storage of size : .1500mm (L)x 750mm (H) X 450mm (D), Metal CPU Trolley,KBT and pedestals.
4 DGM/DZM 0.73 1.650 0.750 2 Nos
40
Main table of size 1950x750mm - Fabricating and fixing of main table formed of 25mm thk prelam board. Table top to have pvc edge lipping as per architects instructions. to have one no. of side storage of size : .1050mm (L)x 750mm (H) X 450mm (D), and back storage of size : .1500mm (L)x 750mm (H) X 450mm (D), Metal CPU Trolley,KBT and pedestals.
5 GM/ZM 0.73 1.950 0.900 2 Nos
Main table of size 1950x900mm - Fabricating and fixing of main table formed of 25mm thk prelam board. Table top to have pvc edge lipping as per architects instructions. to have one no. of side storage of size : .1050mm (L)x 750mm (H) X 450mm (D), and back storage of size : .1500mm (L)x 750mm (H) X 450mm (D), Additinal Strage 900m(L) x 750(H) x 450 mm(D) Metal CPU Trolley,KBT and pedestals.
Total (Basic + Excise)
TOTAL
Grand Total
TOILET CUBICAL Size Qty. Unit
Rate Amount
H W D (Rs.) (Rs.)
I)
TOILET COMPLETE CUBICAL WITH STANDARD DIMENSION OF 1995MM HT X 1000MM WDH X 1550 DEPTH WHICH INCLUDS 600MM DOOR SIZE WDH
1995 1000 1550 4 NOS
VAT 14.5%
TOTAL
GRAND TOTAL OF MODULAR SYSTEM
41
PRICE BID OF LOFT AREA FOR AVANI HEIGHTS, ZO OFFICE, KOLKATA
Sl.No DESCRIPTION Unit Total Rate Amount
Rs.
2 FLOORING
i NORMAL WOODEN FLOORING Sqft. 900
ii MS STRUCTURE FOR MEZZANINE
Mezzanine floor fixed on suitable M.S. section framework
Sqft. 1000
Sqft. 52
iii Iron stair case for mezzanine floor
TOTAL
42
PRICE BID FOR AC WORKS,DENA BANK - Avani Heights
I PART A - SUPPLY OF DUCTED SPLIT UNIT
Sl No Description Qty Unit Supply Rate
Supply Amount
A
Supply of Ceiling Suspended Ducted Split Unit, consist Hemetrically sealed scroll compressor, hudro[hilic coated cooling coil, Centrifugal Forward Curve DIDW Blower Fan Moter, Thermostatic Expansion Valve , Non woven Polyster midea enclosed by HDPE Mesh Air Filter & with outdoor advance micro channel Heat Exchangers. Capacity : 17.0 TR
2 Nos
Total Basic Price
VAT @ 14.5%
Total Price including VAT
II PART B - INSTALLATION, TESTING, COMMISSIONING OF DUCTED SPLIT UNIT
Sl No Description Qty Unit Supply Rate
Supply Amount
Labour Rate
Labour Amount
1
Installation, testing & commissioning with vacummising , Nitrogen pressure testing, lifting & shifting.
A Installation of Ceiling Suspended Ducted Split Unit : 17 TR
2 Nos
2 Gas Charge of Refrigerant ( R -22 )
30 Kgs
3
Supply, Laying of Hard drawn copper refrigerant piping, with 6mm thick cross link polyethelyne nitrile rubber insulation on pipes & supports accessories,
43 Rmt
43
4
Supply & Laying of HDPE Drain pipe with 25 mm with Nitrile rubber insulation, to drain out condensate drain water, along with supports. limited upto --- Rmt per unit
15 Rmt
5 Supply & Fixing of Canvass connections at Duct mouth.
2 Nos
6
Supply & Laying of Control Cable Shielded, to be connected bewtween Indoor & Outdoor unit for communication purpose, along with supports
47 Rmt
7
Supply & Fixing of Supply Air GI Ducting work required with supporting rods and angles, rubber gasket, anchor fasteners. Return Air Ducting not considered
24 Gauge GI Ducting 143 Sqmt
22 Gauge GI Ducting 61 sqmt
8
Supply & Fixing of Acoustic insulation of ducting from inside with 25mm thick fibre glass and tissue paper with perforated aluminium foil and GI screw.
65 Sqmt
9
Supply & Fixing of 50mm thick glasswool, on hot bitumin layer on GI duct, and tightened by tap to insulate the Ducting.
145 Sqmt
10 Grills/ Coller Damper / Alu powder Coated
A Supply Grill with VCD 4 Sqmt
B Return Air Grill 8 Sqmt
44
11 Ceiling Under Deck Insulation with 50MM Thick
0 Sqmt
Supply Total
Labour Total
Vat @ 14.5%
S. Tax @12.36%
with VAT
Total with S. tax
TOTAL COST FOR PART B : LO-SIDE WORKS & ACCESSORIES ( INCLUSIVE TAXES )
GRAND TOTAL PART A + PART B
45
INTERIOR LAYOUT
46
FALSE CEILING LAYOUT
47
LOFT AREA LAYOUT