189
FEC Cables (M) Sdn Bhd file:///E|/contents/intro.htm[10/14/2010 3:41:04 PM] Introduction of Company When there is talk of high quality electric wires and cables, the one company that comes to mind is FEC Cables (Malaysia) Sdn. Bhd. FEC is a subsidiary of Permodalan Nasional Berhad and was formerly known as Furukawa Electric Cables (M) Sdn. Bhd. Having established its Shah Alam plant in 1967 on a 7- acre site at the Shah Alam Industrial Estate, Furukawa has come a long way. The technical collaboration with our Japanese counterpart, Furukawa Japan, has brought about an amazing success for us. In terms of quality, we have climbed the ladders of product manufacturing, steadily and successfully, pushing FEC towards the pinnacle of excellence. Putting our customers’ demands and needs as our number one priority, we opened our second plant in 1995, on a 27-acre freehold land site in Bukit Raja Industrial area, Klang. In our quest for excellence, we equip the plant with the latest technological aids for the manufacture of a wide range of low and medium voltage cables. The certification of the ISO 9001 for both plants only proves that we do not compromise on quality and customer satisfaction. Our dedicated and hard- working employees are the backbone of our success. This was greatly helped by the state-of-the-art technology equipment which has led us towards excellence. Moving towards a new century, we pledge to continually strive towards progressive and dynamic growth as FEC Cables continues its efforts in contributing to the development Malaysia. FEC CABLES (M) SDN. BHD. Sales Office : Persiaran Raja Muda, 40000 Shah Alam, Selangor Darul Ehsan Malaysia. Tel : 6 03 - 5519 1110 (Hotline) Fax : 6 03 - 5519 1296 / 5513 8688 © 2008 FEC CABLES (M) SDN BHD. All Rights Reserved Home About Us Product Range Quality Assurance Manufacturing Process Contact Us

Introduction of Company - Top Entitytopentity.com.my/downloads/fec.pdf · Introduction of Company When there is talk of high quality electric wires and cables, ... Cables inherited

  • Upload
    lymien

  • View
    214

  • Download
    0

Embed Size (px)

Citation preview

FEC Cables (M) Sdn Bhd

file:///E|/contents/intro.htm[10/14/2010 3:41:04 PM]

Introduction of Company

When there is talk of high quality electric wires and cables, the one company that comes to mind is FEC Cables (Malaysia) Sdn. Bhd. FEC is a subsidiary ofPermodalan Nasional Berhad and was formerly known as Furukawa Electric Cables (M) Sdn. Bhd. Having established its Shah Alam plant in 1967 on a 7-acre site at the Shah Alam Industrial Estate, Furukawa has come a long way.

The technical collaboration with our Japanese counterpart, Furukawa Japan, has brought about an amazing success for us. In terms of quality, we haveclimbed the ladders of product manufacturing, steadily and successfully, pushing FEC towards the pinnacle of excellence.

Putting our customers’ demands and needs as our number one priority, we opened our second plant in 1995, on a 27-acre freehold land site in Bukit RajaIndustrial area, Klang. In our quest for excellence, we equip the plant with the latest technological aids for the manufacture of a wide range of low andmedium voltage cables.

The certification of the ISO 9001 for both plants only proves that we do not compromise on quality and customer satisfaction. Our dedicated and hard-working employees are the backbone of our success. This was greatly helped by the state-of-the-art technology equipment which has led us towardsexcellence.

Moving towards a new century, we pledge to continually strive towards progressive and dynamic growth as FEC Cables continues its efforts in contributingto the development Malaysia.

FEC CABLES (M) SDN. BHD.

Sales Office : Persiaran Raja Muda, 40000 Shah Alam, Selangor Darul Ehsan Malaysia.

Tel : 6 03 - 5519 1110 (Hotline) Fax : 6 03 - 5519 1296 / 5513 8688

© 2008 FEC CABLES (M) SDN BHD. All Rights Reserved

Home About Us Product Range Quality Assurance Manufacturing Process Contact Us

FEC Cables (M) Sdn. Bhd.

Telephone Cables

CORPORATEHISTORY

INTRODUCTION OF

COMPANYWhen there is talk of high quality electric wires and cables, the one company that comes to mind is FEC Cables (Malaysia) Sdn. Bhd. FEC is a subsidiary of Permodalan Nasional Berhad and was formerly known as Furukawa Electric Cables (M) Sdn. Bhd. Having established its Shah Alam plant in 1967 on a 7-acre site at the Shah Alam Industrial Estate, Furukawa has come a long way.

The technical collaboration with our Japanese counterpart, Furukawa Japan, has brought about an amazing success for us. In terms of quality, we have climbed the ladders of product manufacturing, steadily and successfully, pushing FEC towards the pinnacle of excellence. Putting our customers’ demands and needs as our number one priority, we opened our second plant in 1995, on a 27-acre freehold land site in Bukit Raja Industrial area, Klang. In our quest for excellence, we equip the plant with the latest technological aids for the manufacture of a wide range of low and medium voltage cables.

The certification of the ISO 9001 for both plants only proves that we do not compromise on quality and customer satisfaction. Our dedicated and hard-working employees are the backbone of our success. This was greatly helped by the state-of-the-art technology equipment which has led us towards excellence.

Moving towards a new century, we pledge to continually strive towards progressive and dynamic growth as FEC Cables continues its efforts in contributing to the development of Malaysia.

FEC Cables (M) Sdn. Bhd. was first established in 1967 and was previously known as Furukawa Electric Cables (M) Sdn. Bhd. In all the years until 2003, the company had been under the management and control of Furukawa Electric Co. Ltd. of Japan.

In 2003, the company was renamed FEC Cables (M) Sdn. Bhd. following the acquisition of its major equity stake by Permodalan Nasional Berhad, Malaysia’s government-owned premier multi-billion dollar investment institution.

The Company had started a technical collaboration from world renowned cable manufacturer, The Furukawa Electric Co. Ltd Japan (Furukawa Japan).

FEC Cables has benefited enormously from the technical collaboration and the subsequent technology transfer with Furukawa Japan. FEC Cables inherited from Furukawa Japan not only its advanced technology and technical know-how but also the disciplines of producing quality products using material conforming to the international standards of manufacturing cables.

Today FEC Cables plays a prominent role as a forerunner in the cable industry.

FEC Cables has been actively involved in serving various industrial sectors, namely the power, telecommunications, construction as well as the oil and gas sectors.

Telephone Cables

Cable Size Nom. Sheath Thickness

(mm)Approx. Overall Diameter

(mm)Approx. Cable Weight

(kg/km)No. of pairsNom. Conductor Diameter

(mm)

200400600800

100012001400160020002400

0.40

2.12.22.32.42.52.82.82.93.03.1

22.529.534.539.543.547.550.554.059.565.5

7001,2901,8602,4303,0003,5904,1404,7105,8206,940

200400600800

100012001400

0.50

2.22.32.52.82.93.03.0

26.535.542.548.554.058.062.0

1,0301,9202,8103,7004,5805,4406,290

200400600800

1000

0.63

2.32.52.93.03.1

32.544.053.561.067.5

1,5602,9504,3605,7207,070

FEC Cables (M) Sdn. Bhd.

SPECIFICATION

Dimensional Dimensional

Nom. Conductor Diameter

Conductor Resistance Capacitance Unbalance Max. Ave. Mutal Capacitance

(nF/km)

Min Insulation Resistance(MΩ.km)

Min. Dielectric Strength

Max. Ave.(Ω/km)

Max. for 99% case(Ω/km)

P-P Max. Ave.(pF/500 m)

P-G Max. Ave.(pF/500 m)

C-C(kV/3Sec.)

C-S(kV/3sec.)

0.400.500.63

1439158

1509660

200 574 54 10,000 0.6 4

Binder Tape

Twisted PE Insulated Pair

PE Sheath

PE/AL/PE Tape Screen

Electrical Data

TM SPEC. LINES CL 0522

Foam Skin Polyethylene Insulated, Polyethylene Sheathed, Paired, Unit Type, Air-core And Moisture Barrier Sheathed With Copper Conductor (PEUT)

Cable Size Nom. Sheath Thickness

(mm)Approx. Overall Diameter

(mm)Approx. Cable Weight

(kg/km)No. of pairsNom. Conductor Diameter

(mm)

10203050

100200

0.50

2.12.12.12.12.12.2

11.013.014.517.021.529.0

130200260380670

1,270

10203050

100200

0.63

2.12.12.12.12.22.3

12.014.516.520.026.034.5

180280370560

1,0101,890

TELEPHONE CABLES

SPECIFICATION

Dimensional

Nom. Conductor Diameter

Conductor Resistance Capacitance Unbalance Max. Ave. Mutal Capacitance

(nF/km)

Min Insulation Resistance(MΩ.km)

Min. Dielectric Strength

Max. Ave.(Ω/km)

Max. for 99% case(Ω/km)

P-P Max. Ave.(pF/500 m)

P-G Max. Ave.(pF/500 m)

C-C(kV/3Sec.)

C-S(kV/3sec.)

0.500.63

9158

9560

200 574 54 10,000 2 4

Binder Tape

Twisted PE Insulated Pair

PE Sheath

PE/AL/PE Tape Screen

Filling Compound

Electrical Data

Foam Skin Polyethylene Insulated, Polyethylene Sheathed, Paired, Unit Type, Fully-filled And Moisture Barrier Sheathed With Copper Conductor (PEUT FF)

TM SPEC. LINES CL 0543

Cable Size Nom. Sheath Thickness

(mm)Approx. Overall Diameter

(mm)Approx. Cable Weight

(kg/km)No. of pairsNom. Conductor Diameter

(mm)

10203050

100200

0.50

2.12.12.12.12.12.2

12.013.015.017.522.029.5

190240330440760

1,350

10203050

100200

0.63

2.12.12.12.12.22.3

12.515.017.520.527.036.0

220310430600

1,0701,930

FEC Cables (M) Sdn. Bhd.

SPECIFICATION

Dimensional

Nom. Conductor Diameter

Conductor Resistance Capacitance Unbalance Max. Ave. Mutal Capacitance

(nF/km)

Min Insulation Resistance(MΩ.km)

Min. Dielectric Strength

Max. Ave.(Ω/km)

Max. for 99% case(Ω/km)

P-P Max. Ave.(pF/500 m)

P-G Max. Ave.(pF/500 m)

C-C(kV/3Sec.)

C-S(kV/3sec.)

0.500.63

9158

9560

200 574 54 10,000 2 4

Electrical Data

Twisted PE Insulated Pair

Binder Tape

PE/AL/PE Tape Screen

PE Sheath

Web

Galvanised Steel Bearer Wire

Solid Polyethylene Insulated, Polyethylene Sheathed, Paired, Unit Type, Moisture Barrier Sheathed And Integral Barrier With Copper Conductor (PEUTIB)

TM SPEC. LINES AC 0001

Factory 1Persiaran Raja Muda, 40000 Shah Alam, Selangor Darul Ehsan, Malaysia.(P.O. Box 7006, 40700 Shah Alam)Tel : 6 03 - 5519 1110 (Hotline) Fax : 6 03 - 5519 1296

Factory 2No. 16, Jalan Keluli 2, Bukit Raja Industrial Area, 41050 Klang, Selangor Darul Ehsan, Malaysia. Tel : 6 03 - 3343 5837 (Hotline) Fax : 6 03 - 3343 5843

Sales OfficePersiaran Raja Muda, 40000 Shah Alam, Selangor Darul Ehsan, MalaysiaTel : 6 03 - 5519 1110 (Hotline) Fax : 6 03 - 5519 1296 / 5513 8688Email : [email protected]

www.fec.com.my

FEC Cables (M) Sdn. Bhd.(7293-W)

Des

ign

by

Tel :

03

- 772

2 48

18

FEC Cables (M) Sdn. Bhd.

Medium Voltage Cables

CORPORATEHISTORY

INTRODUCTION OF

COMPANYWhen there is talk of high quality electric wires and cables, the one company that comes to mind is FEC Cables (Malaysia) Sdn. Bhd. FEC is a subsidiary of Permodalan Nasional Berhad and was formerly known as Furukawa Electric Cables (M) Sdn. Bhd. Having established its Shah Alam plant in 1967 on a 7-acre site at the Shah Alam Industrial Estate, Furukawa has come a long way.

The technical collaboration with our Japanese counterpart, Furukawa Japan, has brought about an amazing success for us. In terms of quality, we have climbed the ladders of product manufacturing, steadily and successfully, pushing FEC towards the pinnacle of excellence. Putting our customers’ demands and needs as our number one priority, we opened our second plant in 1995, on a 27-acre freehold land site in Bukit Raja Industrial area, Klang. In our quest for excellence, we equip the plant with the latest technological aids for the manufacture of a wide range of low and medium voltage cables.

The certification of the ISO 9001 for both plants only proves that we do not compromise on quality and customer satisfaction. Our dedicated and hard-working employees are the backbone of our success. This was greatly helped by the state-of-the-art technology equipment which has led us towards excellence.

Moving towards a new century, we pledge to continually strive towards progressive and dynamic growth as FEC Cables continues its efforts in contributing to the development of Malaysia.

FEC Cables (M) Sdn. Bhd. was first established in 1967 and was previously known as Furukawa Electric Cables (M) Sdn. Bhd. In all the years until 2003, the company had been under the management and control of Furukawa Electric Co. Ltd. of Japan.

In 2003, the company was renamed FEC Cables (M) Sdn. Bhd. following the acquisition of its major equity stake by Permodalan Nasional Berhad, Malaysia’s government-owned premier multi-billion dollar investment institution.

The Company had started a technical collaboration from world renowned cable manufacturer, The Furukawa Electric Co. Ltd Japan (Furukawa Japan).

FEC Cables has benefited enormously from the technical collaboration and the subsequent technology transfer with Furukawa Japan. FEC Cables inherited from Furukawa Japan not only its advanced technology and technical know-how but also the disciplines of producing quality products using material conforming to the international standards of manufacturing cables.

Today FEC Cables plays a prominent role as a forerunner in the cable industry.

FEC Cables has been actively involved in serving various industrial sectors, namely the power, telecommunications, construction as well as the oil and gas sectors.

Medium Voltage Cables

1. Non armoured cables (One core)

3.6/6 kV

6/10 kV

8.7/15 kV

12/20 kV

18/30 kV

2. Non armoured cables (Three core)

3.6/6 kV

6/10 kV

8.7/15 kV

12/20 kV

18/30 kV

3. Armoured(AWA) cables (One core)

3.6/6 kV

6/10 kV

8.7/15 kV

12/20 kV

18/30 kV

4. Armoured(SWA) cables (Three core)

3.6/6 kV

6/10 kV

8.7/15 kV

12/20 kV

18/30 kV

5. Armoured(DSTA) cables (Three core)

3.6/6 kV

6/10 kV

8.7/15 kV

12/20 kV

18/30 kV

6. Short Circuit Current, Calculation Base for

Electrical Characteristics and Correction Factors for

Continuous Current Rating

5

6

7

8

9

10

11

12

13

1�

15

16

17

18

19

20

21

22

23

2�

25

26

27

28

29

30

Table Of Contents

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500 630

Conductor dia. (approx.) mm 4.7 5.9 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3 30.3

Nominal insulation thickness

mm 2.5 2.6 2.8 3.0 3.2

Nominal outer-sheath thickness

mm 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.3

Approx. overall dia. mm 17.5 18.5 20.0 21.5 23.0 25.0 26.5 28.0 30.0 32.5 35.5 38.5 42.5 47.0

Cable net. weight (approx.)

kg/kmCu 420 540 670 820 1,060 1,350 1,610 1,910 2,300 2,930 3,570 4,460 5,510 7,020

Al - 380 450 520 620 750 860 980 1,130 1,390 1,650 2,000 2,410 3,010

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500 630

Max. conductor resistance DC at 20°C

Ω /kmCu 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

Al - 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

Max. conductor resistance 50Hz at 90°C

Ω /kmCu 1.47 0.927 0.668 0.494 0.342 0.247 0.196 0.159 0.128 0.0983 0.0794 0.0635 0.0512 0.0418

Al - 1.54 1.11 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.130 0.102 0.0800 0.0633

Capacitance µF/km Cu 0.21 0.24 0.28 0.31 0.35 0.40 0.43 0.47 0.52 0.56 0.57 0.60 0.62 0.71

Reactance at 50Hz Ω /km Cu 0.134 0.125 0.119 0.114 0.108 0.104 0.100 0.0973 0.0946 0.0920 0.0904 0.0883 0.0868 0.0849

Current rating In air at 40°C

ACu 105 135 165 200 250 305 355 410 470 560 645 750 865 1,000

Al - 105 130 155 195 240 280 320 365 435 505 590 690 815

Current rating In the ground at 25°C

ACu 110 145 170 205 250 300 340 380 430 495 560 635 720 810

Al - 110 135 160 195 235 265 300 340 390 445 505 580 660

Short circuit current for 1 sec.

kACu 2.41 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 72.1 90.8

Al - 2.48 3.45 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 38.1 47.6 59.8

MEDIUM VOLTAGE CABLES

5

Dimensional

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Sheathed

3.6/6 (Max. 7.2) kV

1 Core

PVC Outer Sheath Binder Tape Metalic Screen Insulation Screen XLPE Insulation

Conductor Screen

Copper/Aluminium

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500 630

Conductor dia. (approx.)

mm 4.7 5.9 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3 30.3

Nominal insulation thickness

mm 3.4

Nominal outer-sheath thickness

mm 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.3

Approx. overall dia. mm 19.5 20.5 22.0 23.0 25.0 27.0 28.5 30.0 32.0 34.5 36.5 39.5 42.5 47.5

Cable net. weight (approx.)

kg/kmCu 490 600 740 880 1,140 1,430 1,710 2,000 2,400 3,030 3,640 4,510 5,540 7,050

Al - 440 520 580 710 830 950 1,070 1,240 1,490 1,720 2,050 2,440 3,040

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500 630

Max. conductor resistance DC at 20°C

Ω /kmCu 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

Al - 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

Max. conductor resis-tance 50Hz at 90°C

Ω /kmCu 1.47 0.927 0.668 0.494 0.342 0.247 0.196 0.159 0.128 0.0981 0.0793 0.0634 0.0511 0.0417

Al - 1.54 1.11 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.130 0.102 0.0800 0.0633

Capacitance µF/km Cu 0.17 0.19 0.22 0.24 0.27 0.31 0.33 0.36 0.40 0.44 0.48 0.53 0.59 0.68

Reactance at 50Hz Ω /km Cu 0.142 0.132 0.126 0.120 0.114 0.109 0.106 0.102 0.0994 0.0958 0.0927 0.0900 0.0876 0.0856

Current rating In air at 40°C

ACu 105 140 170 205 255 310 360 415 475 565 645 750 865 1,000

Al - 110 130 160 200 245 280 320 370 440 505 590 690 815

Current rating In the ground at 25°C

ACu 110 145 170 205 250 300 340 380 430 500 560 635 720 810

Al - 110 135 160 195 235 265 300 340 390 445 505 580 660

Short circuit current for 1 sec.

kACu 2.41 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 72.1 90.8

Al - 2.48 3.45 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 38.1 47.6 59.8

FEC Cables (M) Sdn. Bhd.

6

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Dimensional

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Sheathed

6/10 (Max. 12) kV

1 Core

PVC Outer Sheath Binder Tape Metalic Screen Insulation Screen XLPE Insulation

Conductor Screen

Copper/Aluminium

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500 630

Conductor dia. (approx.)

mm - 5.9 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3 30.3

Nominal insulation thickness

mm 4.5

Nominal outer-sheath thickness

mm - 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.3 2.4

Approx. overall dia. mm - 23.0 24.5 25.5 27.5 29.0 31.0 32.5 34.0 36.5 39.0 42.0 45.0 50.0

Cable net. weight (approx.)

kg/kmCu - 700 840 990 1,240 1,550 1,840 2,140 2,550 3,170 3,810 4,690 5,730 7,160

Al - 540 620 690 810 950 1,080 1,210 1,380 1,630 1,890 2,230 2,630 3,280

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500 630

Max. conductor resistance DC at 20°C

Ω /kmCu - 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

Al - 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

Max. conductor resis-tance 50Hz at 90°C

Ω /kmCu - 0.927 0.668 0.494 0.342 0.247 0.196 0.159 0.128 0.0979 0.0790 0.0630 0.0507 0.0413

Al - 1.54 1.11 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.130 0.102 0.0798 0.0631

Capacitance µF/km Cu - 0.16 0.18 0.20 0.22 0.25 0.27 0.29 0.31 0.35 0.38 0.42 0.46 0.53

Reactance at 50Hz Ω /km Cu - 0.142 0.136 0.130 0.122 0.117 0.113 0.110 0.106 0.102 0.0986 0.0955 0.0926 0.0901

Current rating In air at 40°C

ACu - 140 175 210 260 320 365 420 480 570 655 760 875 1,010

Al - 110 135 160 200 245 285 325 375 445 510 595 695 815

Current rating In the ground at 25°C

ACu - 145 170 205 250 300 340 380 430 500 560 640 720 815

Al - 110 135 160 195 235 265 300 340 390 445 505 580 660

Short circuit current for 1 sec.

kACu - 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 72.1 90.8

Al - 2.48 3.45 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 38.1 47.6 59.8

MEDIUM VOLTAGE CABLES

7

Dimensional

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Sheathed

8.7/15 (Max. 17.5) kV

1 Core

PVC Outer Sheath Binder Tape Metalic Screen Insulation Screen XLPE Insulation

Conductor Screen

Copper/Aluminium

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500 630

Conductor dia. (approx.)

mm - - 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3 30.3

Nominal insulation thickness

mm 5.5

Nominal outer-sheath thickness

mm - - 1.7 1.8 1.9 2.0 2.1 2.2 2.3 2.4 2.5

Approx. overall dia. mm - - 26.0 27.5 29.5 31.0 32.5 34.5 36.0 38.5 41.0 44.0 47.5 52.0

Cable net. weight (approx.)

kg/kmCu - - 920 1,080 1,340 1,660 1,930 2,250 2,650 3,300 3,940 4,830 5,900 7,450

Al - - 700 790 910 1,060 1,180 1,320 1,490 1,760 2,020 2,370 2,810 3,450

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500 630

Max. conductor resistance DC at 20°C

Ω /kmCu - - 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

Al - - 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

Max. conductor resistance 50Hz at 90°C

Ω /kmCu - - 0.668 0.494 0.342 0.247 0.196 0.159 0.128 0.0978 0.0788 0.0629 0.0505 0.0410

Al - - 1.11 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.129 0.101 0.0797 0.0629

Capacitance µF/km Cu - - 0.16 0.17 0.19 0.21 0.23 0.25 0.27 0.30 0.32 0.35 0.39 0.44

Reactance at 50Hz Ω /km Cu - - 0.141 0.135 0.128 0.122 0.117 0.114 0.110 0.105 0.102 0.0988 0.0956 0.0928

Current rating In air at 40°C

ACu - - 175 210 265 320 370 420 485 575 660 760 880 1,010

Al - - 135 165 205 250 285 325 375 445 510 595 695 815

Current rating In the ground at 25°C

ACu - - 170 205 250 300 340 380 430 500 565 640 725 815

Al - - 135 160 195 235 265 300 340 390 445 505 575 660

Short circuit current for 1 sec.

kACu - - 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 72.1 90.8

Al - - 3.45 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 38.1 47.6 59.8

FEC Cables (M) Sdn. Bhd.

8

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Dimensional

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Sheathed

12/20 (Max. 24) kV

1 Core

PVC Outer Sheath Binder Tape Metalic Screen Insulation Screen XLPE Insulation

Conductor Screen

Copper/Aluminium

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500 630

Conductor dia. (approx.)

mm - - - 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3 30.3

Nominal insulation thickness

mm 8.0

Nominal outer-sheath thickness

mm - - - 1.9 2.0 2.1 2.2 2.3 2.5 2.7

Approx. overall dia. mm - - - 33.0 35.0 36.5 38.0 39.5 41.5 44.0 46.5 49.5 52.5 57.5

Cable net. weight (approx.)

kg/kmCu - - - 1,350 1,640 1,970 2,260 2,570 3,000 3,670 4,320 5,270 6,330 7,950

Al - - - 1,050 1,210 1,370 1,500 1,640 1,840 2,130 2,390 2,820 3,230 3,940

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500 630

Max. conductor resistance DC at 20°C

Ω /kmCu - - - 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

Al - - - 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

Max. conductor resistance 50Hz at 90°C

Ω /kmCu - - - 0.494 0.342 0.247 0.196 0.159 0.127 0.0976 0.0786 0.0625 0.0501 0.0405

Al - - - 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.129 0.101 0.0795 0.0627

Capacitance µF/km Cu - - - 0.13 0.15 0.16 0.18 0.19 0.20 0.22 0.24 0.26 0.29 0.32

Reactance at 50Hz Ω /km Cu - - - 0.147 0.139 0.132 0.127 0.123 0.119 0.115 0.110 0.106 0.102 0.0993

Current rating In air at 40°C

ACu - - - 215 270 325 375 430 490 580 665 770 885 1,020

Al - - - 165 210 255 290 330 380 450 515 600 700 820

Current rating In the ground at 25°C

ACu - - - 205 250 300 340 380 430 500 565 640 725 820

Al - - - 160 195 235 265 300 340 390 445 505 580 660

Short circuit current for 1 sec.

kACu - - - 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 72.1 90.8

Al - - - 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 38.1 47.6 59.8

MEDIUM VOLTAGE CABLES

9

Dimensional

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Sheathed

18/30 (Max. 36) kV

1 Core

PVC Outer Sheath Binder Tape Metalic Screen Insulation Screen XLPE Insulation

Conductor Screen

Copper/Aluminium

Nominal cross sectional area mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Conductor dia. (approx.) mm 4.7 5.9 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3

Nominal insulation thickness mm 2.5 2.6 2.8 3.0 3.2

Nominal outer-sheath thickness

mm 2.0 2.1 2.1 2.2 2.3 2.5 2.6 2.7 2.8 3.0 3.2 3.4 3.7

Approx. overall dia. mm 34.0 36.5 39.5 42.0 46.0 50.5 53.5 57.0 61.0 67.0 73.0 80.0 88.0

Cable net. weight (approx.) kg/kmCu 1,370 1,750 2,150 2,610 3,400 4,370 5,240 6,180 7,430 9,460 11,530 14,380 17,800

Al - 1,270 1,480 1,710 2,100 2,560 2,950 3,370 3,900 4,780 5,710 6,930 8,410

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Max. conductor resistance DC at 20°C

Ω /kmCu 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366

Al - 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605

Max. conductor resis-tance 50Hz at 90°C

Ω /kmCu 1.47 0.927 0.668 0.494 0.342 0.247 0.196 0.160 0.128 0.0988 0.0800 0.0643 0.0522

Al - 1.54 1.11 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.130 0.102 0.0801

Capacitance µF/km 0.21 0.24 0.28 0.31 0.35 0.40 0.43 0.47 0.52 0.56 0.57 0.60 0.62

Reactance at 50Hz Ω /km 0.118 0.109 0.105 0.100 0.0949 0.0914 0.0885 0.0860 0.0837 0.0817 0.0805 0.0790 0.0779

Current rating In air at 40°C

ACu 100 130 160 195 240 295 340 385 445 525 600 690 790

Al - 105 125 150 190 230 265 300 350 410 475 550 640

Current rating In the ground at 25°C

ACu 110 140 170 200 245 290 330 370 420 485 545 620 695

Al - 110 130 155 190 225 255 290 325 380 430 490 560

Short circuit current for 1 sec.

kACu 2.41 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 72.1

Al - 2.48 3.45 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 38.1 47.6

FEC Cables (M) Sdn. Bhd.

10

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Dimensional

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Sheathed

3.6/6 (Max. 7.2) kV

3 Core

PVC Outer Sheath Binder Tape FillerInsulation Screen

XLPE Insulation

Conductor Screen

Copper/Aluminium

Metalic Screen

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Conductor dia. (approx.)

mm 4.7 5.9 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3

Nominal insulation thickness

mm 3.4

Nominal outer-sheath thickness

mm 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 3.1 3.3 3.5 3.7

Approx. overall dia. mm 38.0 41.0 44.0 46.5 50.5 54.5 57.5 61.0 65.0 70.5 75.5 82.0 89.0

Cable net. weight (approx.)

kg/kmCu 1,590 1,990 2,420 2,920 3,730 4,680 5,570 6,530 7,800 9,820 11,830 14,610 17,900

Al - 1,500 1,750 2,010 2,430 2,870 3,270 3,710 4,270 5,140 6,000 7,160 8,520

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Max. conductor resistance DC at 20°C

Ω /kmCu 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366

Al - 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605

Max. conductor resis-tance 50Hz at 90°C

Ω /kmCu 1.47 0.927 0.668 0.494 0.342 0.247 0.196 0.160 0.128 0.0986 0.0798 0.0641 0.0521

Al - 1.54 1.11 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.130 0.102 0.0801

Capacitance µF/km 0.17 0.19 0.22 0.24 0.27 0.31 0.33 0.36 0.40 0.44 0.48 0.53 0.59

Reactance at 50Hz Ω /km 0.128 0.118 0.113 0.108 0.102 0.0976 0.0944 0.0915 0.0888 0.0856 0.0833 0.0809 0.0788

Current rating In air at 40°C

ACu 105 135 165 195 245 300 345 390 450 530 600 690 790

Al - 105 130 155 190 235 270 305 350 415 475 550 640

Current rating In the ground at 25°C

ACu 110 140 170 200 245 295 330 375 420 485 545 620 695

Al - 110 130 155 190 225 260 290 325 380 430 490 560

Short circuit current for 1 sec.

kACu 2.41 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 72.1

Al - 2.48 3.45 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 38.1 47.6

MEDIUM VOLTAGE CABLES

11

Dimensional

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Sheathed

6/10 (Max. 12) kV

3 Core

PVC Outer Sheath Binder Tape FillerInsulation Screen

XLPE Insulation

Conductor Screen

Copper/Aluminium

Metalic Screen

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Conductor dia. (approx.)

mm - 5.9 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3

Nominal insulation thickness

mm 4.5

Nominal outer-sheath thickness

mm - 2.4 2.5 2.6 2.7 2.8 2.9 3.0 3.1 3.3 3.4 3.7 3.9

Approx. overall dia. mm - 46.0 49.0 51.5 56.0 59.5 63.0 66.5 70.0 76.0 80.5 87.0 94.0

Cable net. weight (approx.)

kg/kmCu - 2,370 2,830 3,330 4,170 5,150 6,060 7,050 8,350 10,410 12,420 15,290 18,640

Al - 1,890 2,160 2,420 2,870 3,340 3,770 4,240 4,820 5,740 6,600 7,840 9,250

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Max. conductor resistance DC at 20°C

Ω /kmCu - 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366

Al - 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605

Max. conductor resis-tance 50Hz at 90°C

Ω /kmCu - 0.927 0.668 0.494 0.342 0.247 0.196 0.159 0.128 0.0983 0.0794 0.0636 0.0515

Al - 1.54 1.11 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.130 0.102 0.0799

Capacitance µF/km - 0.16 0.18 0.20 0.22 0.25 0.27 0.29 0.31 0.35 0.38 0.42 0.46

Reactance at 50Hz Ω /km - 0.131 0.124 0.118 0.112 0.107 0.103 0.0994 0.0962 0.0924 0.0896 0.0868 0.0842

Current rating In air at 40°C

ACu - 140 170 200 250 305 350 395 455 530 610 695 795

Al - 105 130 155 195 235 270 310 355 420 480 555 645

Current rating In the ground at 25°C

ACu - 140 170 200 245 295 335 375 420 485 550 620 700

Al - 110 130 155 190 225 260 290 330 380 430 495 565

Short circuit current for 1 sec.

kACu - 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 72.1

Al - 2.48 3.45 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 38.1 47.6

FEC Cables (M) Sdn. Bhd.

12

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Dimensional

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Sheathed

3 Core

8.7/15 (Max. 17.5) kV

PVC Outer Sheath Binder Tape FillerInsulation Screen

XLPE Insulation

Conductor Screen

Copper/Aluminium

Metalic Screen

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Conductor dia. (approx.)

mm - - 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3

Nominal insulation thickness

mm 5.5

Nominal outer-sheath thickness

mm - - 2.6 2.7 2.8 2.9 3.0 3.1 3.3 3.4 3.6 3.8 4.0

Approx. overall dia. mm - - 53.0 56.0 60.0 64.0 67.0 70.5 74.5 80.0 85.0 91.0 98.0

Cable net. weight (approx.)

kg/kmCu - - 3,130 3,650 4,520 5,520 6,440 7,450 8,810 10,870 12,940 15,800 19,190

Al - - 2,470 2,750 3,210 3,710 4,150 4,640 5,280 6,190 7,120 8,360 9,810

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Max. conductor resistance DC at 20°C

Ω /kmCu - - 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366

Al - - 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605

Max. conductor resistance 50Hz at 90°C

Ω /kmCu - - 0.668 0.494 0.342 0.247 0.196 0.159 0.128 0.0981 0.0792 0.0634 0.0512

Al - - 1.11 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.130 0.101 0.0798

Capacitance µF/km - - 0.16 0.17 0.19 0.21 0.23 0.25 0.27 0.30 0.32 0.35 0.39

Reactance at 50Hz Ω /km - - 0.130 0.124 0.117 0.112 0.108 0.104 0.100 0.0963 0.0933 0.0902 0.0873

Current rating In air at 40°C ACu - - 170 205 250 305 350 400 455 535 610 700 800

Al - - 130 160 195 240 275 310 355 420 480 555 645

Current rating In the ground at 25°C

ACu - - 170 200 245 295 335 375 420 490 550 620 700

Al - - 130 155 190 225 260 290 330 380 430 495 565

Short circuit current for 1 sec.

kACu - - 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 72.1

Al - - 3.45 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 38.1 47.6

MEDIUM VOLTAGE CABLES

13

Dimensional

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Sheathed

3 Core

12/20 (Max. 24) kV

PVC Outer Sheath Binder Tape FillerInsulation Screen

XLPE Insulation

Conductor Screen

Copper/Aluminium

Metalic Screen

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Conductor dia. (approx.)

mm - - - 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 -

Nominal insulation thickness

mm 8.0

Nominal outer-sheath thickness

mm - - - 3.1 3.2 3.3 3.4 3.5 3.6 3.8 4.0 4.2 -

Approx. overall dia. mm - - - 67.5 71.5 75.5 79.0 82.0 86.0 91.5 97.0 103.0 -

Cable net. weight (approx.)

kg/kmCu - - - 4,720 5,650 6,710 7,690 8,750 10,140 12,320 14,480 17,440 -

Al - - - 3,810 4,340 4,900 5,400 5,940 6,610 7,640 8,660 10,000 -

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Max. conductor resistance DC at 20°C

Ω /kmCu - - - 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 -

Al - - - 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 -

Max. conductor resis-tance 50Hz at 90°C

Ω /kmCu - - - 0.494 0.342 0.247 0.196 0.159 0.128 0.0978 0.0789 0.0629 -

Al - - - 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.129 0.101 -

Capacitance µF/km - - - 0.13 0.15 0.16 0.18 0.19 0.20 0.22 0.24 0.26

Reactance at 50Hz Ω /km - - - 0.137 0.129 0.123 0.118 0.114 0.110 0.105 0.102 0.0981 -

Current rating In air at 40°C

ACu - - - 205 255 310 355 400 460 540 610 700 -

Al - - - 160 200 240 280 315 360 425 480 560 -

Current rating In the ground at 25°C

ACu - - - 200 245 295 330 375 420 490 550 625 -

Al - - - 155 190 225 260 290 330 380 430 495 -

Short circuit current for 1 sec.

kACu - - - 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 -

Al - - - 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 38.1 -

FEC Cables (M) Sdn. Bhd.

1�

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Dimensional

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Sheathed

3 Core

18/30 (Max. 36) kV

PVC Outer Sheath Binder Tape FillerInsulation Screen

XLPE Insulation

Conductor Screen

Copper/Aluminium

Metalic Screen

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500 630

Conductor dia. (approx.) mm 4.7 5.9 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3 30.3

Nominal insulation thickness

mm 2.5 2.6 2.8 3.0 3.2

Nominal separation thickness

mm 1.2 1.3 1.4

Separation sheath dia. (approx.)

mm 16.3 17.5 18.8 19.9 21.7 23.4 24.8 26.3 28.0 30.6 33.2 36.3 39.9 44.7

Nominal of hard-drawn Al wire

mm 1.0 1.6 2.0 2.5 2.5

Nominal outer-sheath thickness

mm 1.8 1.9 2.0 2.1 2.2 2.3 2.5 2.6

Approx. overall dia. mm 22.0 24.5 26.0 27.0 28.5 30.5 32.0 33.5 36.0 39.0 42.0 45.0 50.0 55.0

Cable net weight (approx.) kg/kmCu 660 870 1,020 1,180 1,440 1,770 2,050 2,380 2,870 3,560 4,250 5,200 6,500 8,150

Al - 710 800 880 1,010 1,170 1,300 1,450 1,710 2,010 2,330 2,740 3,400 4,100

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500 630

Max. conductor resistance DC at 20°C

Ω /kmCu 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

Al - 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

Max. conductor resistance 50Hz at 90°C

Ω /kmCu 1.47 0.927 0.668 0.494 0.342 0.247 0.196 0.159 0.127 0.0976 0.0786 0.0625 0.0499 0.0402

Al - 1.54 1.11 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.129 0.101 0.0796 0.0628

Capacitance µF/km 0.21 0.24 0.28 0.31 0.35 0.40 0.43 0.47 0.52 0.56 0.57 0.60 0.62 0.71

Reactance at 50Hz Ω /km 0.150 0.142 0.135 0.128 0.120 0.114 0.109 0.106 0.104 0.0999 0.0973 0.0944 0.0937 0.0916

Current rating In air at 40°C

ACu 110 145 180 215 265 325 375 425 490 580 665 770 890 1,030

Al - 115 140 165 205 250 290 330 385 455 520 605 710 830

Current rating In the ground at 25°C

ACu 115 145 175 210 255 305 345 385 440 505 570 645 725 815

Al - 115 135 160 195 235 270 300 340 395 445 510 580 660

Short circuit current for 1 sec.

kACu 2.41 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 72.1 90.8

Al - 2.48 3.45 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 38.1 47.6 59.8

MEDIUM VOLTAGE CABLES

15

Dimensional

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Separation Sheathed, Aluminium Wire Armour, PVC Sheathed

1 Core

3.6/6 (Max. 7.2) kV

Binder TapePVC Outer Sheath PVC Separation Sheath Metalic Screen Insulation Screen

XLPE Insulation

Conductor Screen

Copper/Aluminium

Aluminium Wire

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500 630

Conductor dia. (approx.) mm 4.7 5.9 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3 30.3

Nominal insulation thickness

mm 3.4

Nominal separation thickness

mm 1.2 1.3 1.4

Separation sheath dia. (approx.)

mm 18.1 19.3 20.6 21.7 23.5 25.2 26.6 28.1 29.8 32.2 34.4 37.1 40.3 45.1

Nominal of hard-drawn Al wire

mm 1.6 2.0 2.5 2.5

Nominal outer-sheath thickness

mm 1.8 1.9 2.0 2.1 2.2 2.4 2.5 2.6

Approx. overall dia. mm 25.0 26.5 27.5 28.5 30.5 32.5 34.0 36.5 38.0 41.0 43.0 46.0 50.5 55.5

Cable net. weight (approx.)

kg/kmCu 820 970 1,110 1,270 1,560 1,880 2,180 2,600 3,010 3,700 4,340 5,280 6,550 8,200

Al - 810 890 970 1,130 1,280 1,420 1,670 1,850 2,150 2,420 2,820 3,450 4,190

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500 630

Max. conductor resistance DC at 20°C

Ω /kmCu 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

Al - 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

Max. conductor resistance 50Hz at 90°C

Ω /kmCu 1.47 0.927 0.668 0.494 0.342 0.247 0.196 0.159 0.127 0.0976 0.0785 0.0624 0.0499 0.0402

Al - 1.54 1.11 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.129 0.101 0.0796 0.0628

Capacitance µF/km 0.17 0.19 0.22 0.24 0.27 0.31 0.33 0.36 0.40 0.44 0.48 0.53 0.59 0.68

Reactance at 50Hz Ω /km 0.158 0.147 0.139 0.132 0.125 0.118 0.113 0.111 0.107 0.102 0.0991 0.0957 0.0942 0.0921

Current rating In air at 40°C

ACu 115 150 180 215 270 325 375 430 495 585 665 770 890 1,030

Al - 115 140 165 210 255 290 335 385 455 520 610 710 830

Current rating In the ground at 25°C

ACu 115 145 175 205 255 305 345 390 435 505 570 645 725 815

Al - 115 135 160 195 235 270 300 340 395 445 510 580 660

Short circuit current for 1 sec.

kACu 2.41 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 72.1 90.8

Al - 2.48 3.45 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 38.1 47.6 59.8

FEC Cables (M) Sdn. Bhd.

16

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Dimensional

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Separation Sheathed, Aluminium Wire Armour, PVC Sheathed

1 Core

6/10 (Max. 12) kV

Binder TapePVC Outer Sheath PVC Separation Sheath Metalic Screen Insulation Screen

XLPE Insulation

Conductor Screen

Copper/Aluminium

Aluminium Wire

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500 630

Conductor dia. (approx.) mm - 5.9 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3 30.3

Nominal insulation thickness

mm - 4.5

Nominal separation thickness

mm 1.2 1.3 1.3 1.4

Separation sheath dia. (approx.)

mm - 21.5 22.8 23.9 25.7 27.4 28.8 30.3 32.0 34.4 36.6 39.5 42.5 47.3

Nominal of hard-drawn Al wire

mm - 1.6 2.0 2.5

Nominal outer-sheath thickness

mm - 1.8 1.9 2.0 2.1 2.1 2.2 2.3 2.3 2.5 2.6 2.7

Approx. overall dia. mm - 28.5 30.0 31.0 33.0 35.5 37.0 38.5 40.5 43.0 45.5 49.5 53.0 58.0

Cable net. weight (approx.)

kg/kmCu - 1,090 1,250 1,420 1,700 2,120 2,440 2,760 3,210 3,890 4,550 5,680 6,800 8,450

Al - 930 1,030 1,120 1,270 1,530 1,680 1,830 2,050 2,350 2,630 3,220 3,700 4,440

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500 630

Max. conductor resistance DC at 20°C

Ω /kmCu - 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

Al - 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

Max. conductor resis-tance 50Hz at 90°C

Ω /kmCu - 0.927 0.668 0.494 0.342 0.247 0.196 0.159 0.127 0.0975 0.0784 0.0623 0.0497 0.0400

Al - 1.54 1.11 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.129 0.101 0.0795 0.0627

Capacitance µF/km - 0.16 0.18 0.20 0.22 0.25 0.27 0.29 0.31 0.35 0.38 0.42 0.46 0.53

Reactance at 50Hz Ω /km - 0.152 0.144 0.137 0.129 0.124 0.119 0.115 0.111 0.106 0.102 0.100 0.0972 0.0948

Current rating In air at 40°C

ACu - 150 180 215 270 330 380 435 495 585 670 775 890 1,025

Al - 115 140 170 210 255 295 335 385 455 520 610 710 830

Current rating In the ground at 25°C

ACu - 145 175 205 255 305 345 385 435 505 565 645 725 810

Al - 115 135 160 195 235 270 300 340 395 445 510 580 660

Short circuit current for 1 sec.

kACu - 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 72.1 90.8

Al - 2.48 3.45 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 38.1 47.6 59.8

MEDIUM VOLTAGE CABLES

17

Dimensional

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Separation Sheathed, Aluminium Wire Armour, PVC Sheathed

1 Core

8.7/15 (Max. 17.5) kV

Binder TapePVC Outer Sheath PVC Separation Sheath Metalic Screen Insulation Screen

XLPE Insulation

Conductor Screen

Copper/Aluminium

Aluminium Wire

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500 630

Conductor dia. (approx.) mm - - 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3 30.3

Nominal insulation thickness

mm - - 5.5

Nominal separation thickness

mm - 1.2 1.3 1.4

Separation sheath dia. (approx.)

mm - - 24.6 25.7 27.5 29.2 30.6 32.1 33.8 36.2 38.6 41.3 44.5 49.1

Nominal of hard-drawn Al wire

mm - - 1.6 2.0 2.5

Nominal outer-sheath thickness

mm - - 1.9 2.0 2.0 2.1 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8

Approx. overall dia. mm - - 32.0 33.0 35.5 37.5 39.0 40.5 42.5 45.0 48.5 51.5 55.0 60.0

Cable net. weight (approx.) kg/kmCu - - 1,360 1,540 1,910 2,260 2,560 2,910 3,340 4,040 4,890 5,840 6,990 8,660

Al - - 1,140 1,240 1,480 1,660 1,800 1,980 2,180 2,490 2,970 3,380 3,890 4,660

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500 630

Max. conductor resistance DC at 20°C

Ω /kmCu - - 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

Al - - 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

Max. conductor resistance 50Hz at 90°C

Ω /kmCu - - 0.668 0.494 0.342 0.247 0.196 0.159 0.127 0.0975 0.0783 0.0622 0.0496 0.0399

Al - - 1.11 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.129 0.101 0.0794 0.0626

Capacitance µF/km - - 0.16 0.17 0.19 0.21 0.23 0.25 0.27 0.30 0.32 0.35 0.39 0.44

Reactance at 50Hz Ω /km - - 0.148 0.141 0.134 0.127 0.122 0.118 0.114 0.109 0.106 0.102 0.0995 0.0969

Current rating In air at 40°C

ACu - - 185 220 275 335 380 435 495 585 675 775 890 1,025.0

Al - - 140 170 210 260 295 335 385 455 525 610 710 830

Current rating In the ground at 25°C

ACu - - 175 205 255 305 345 385 435 505 570 645 725 810

Al - - 135 160 195 235 270 300 340 395 445 510 580 660

Short circuit current for 1 sec.

kACu - - 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 72.1 90.8

Al - - 3.45 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 38.1 47.6 59.8

FEC Cables (M) Sdn. Bhd.

18

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Dimensional

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Separation Sheathed, Aluminium Wire Armour, PVC Sheathed

1 Core

12/20 (Max. 24) kV

Binder TapePVC Outer Sheath PVC Separation Sheath Metalic Screen Insulation Screen

XLPE Insulation

Conductor Screen

Copper/Aluminium

Aluminium Wire

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500 630

Conductor dia. (approx.) mm - - - 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3 30.3

Nominal insulation thickness

mm - - - 8.0

Nominal separation thickness

mm - - 1.2 1.3 1.4 1.5

Separation sheath dia. (approx.)

mm - - - 30.8 32.6 34.3 35.7 37.4 39.1 41.5 43.9 46.6 49.8 54.4

Nominal of hard-drawn Al wire

mm - - - 2.0 2.5

Nominal outer-sheath thickness

mm - - - 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9

Approx. overall dia. mm - - - 39.5 41.0 43.0 44.5 47.5 49.5 51.5 54.5 57.0 60.5 65.5

Cable net. weight (approx.) kg/kmCu - - - 2,000 2,300 2,670 2,990 3,500 3,980 4,680 5,420 6,400 7,580 9,290

Al - - - 1,700 1,870 2,070 2,230 2,580 2,810 3,140 3,500 3,940 4,480 5,280

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500 630

Max. conductor resistance DC at 20°C

Ω /kmCu - - - 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

Al - - - 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

Max. conductor resis-tance 50Hz at 90°C

Ω /kmCu - - - 0.494 0.342 0.247 0.196 0.159 0.127 0.0974 0.0782 0.0620 0.0494 0.0396

Al - - - 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.129 0.101 0.0793 0.0624

Capacitance µF/km - - - 0.13 0.15 0.16 0.18 0.19 0.20 0.22 0.24 0.26 0.29 0.32

Reactance at 50Hz Ω /km - - - 0.152 0.143 0.136 0.130 0.128 0.123 0.117 0.113 0.109 0.105 0.102

Current rating In air at 40°C

ACu - - - 220 275 335 385 440 500 590 675 775 890 1025

Al - - - 170 215 260 300 340 390 460 525 610 710 825

Current rating In the ground at 25°C

ACu - - - 205 255 305 345 385 435 505 565 640 720 810

Al - - - 160 195 235 265 300 340 395 445 505 575 655

Short circuit current for 1 sec.

kACu - - - 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 72.1 90.8

Al - - - 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 38.1 47.6 59.8

MEDIUM VOLTAGE CABLES

19

Dimensional

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Separation Sheathed, Aluminium Wire Armour, PVC Sheathed

1 Core

18/30 (Max. 36) kV

Binder TapePVC Outer Sheath PVC Separation Sheath Metalic Screen Insulation Screen

XLPE Insulation

Conductor Screen

Copper/Aluminium

Aluminium Wire

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Conductor dia. (approx.) mm 4.7 5.9 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3

Nominal insulation thickness

mm 2.5 2.6 2.8 3.0 3.2

Nominal separation thickness

mm 1.2 1.3 1.4 1.5 1.6 1.7 1.8 2.0 2.1

Separation sheath dia. (approx.)

mm 31.6 34.2 37.0 39.6 43.7 47.3 50.6 53.8 57.7 63.5 69.3 76.3 83.9

Nominal of galvanized steel wire

mm 2.0 2.5 3.15

Nominal outer-sheath thickness

mm 2.2 2.3 2.5 2.6 2.7 2.8 2.9 3.0 3.2 3.5 3.8 4.0

Approx. overall dia. mm 40.5 43.0 46.0 50.0 54.0 58.0 61.5 65.0 69.0 75.0 83.0 90.5 98.5

Cable net. weight (approx.)

kg/kmCu 2,830 3,330 3,840 4,870 5,910 7,020 8,080 9,210 10,710 13,090 16,410 19,880 23,820

Al - 2,850 3,170 3,960 4,600 5,200 5,790 6,400 7,180 8,420 10,590 12,440 14,440

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Max. conductor resistance DC at 20°C

Ω /kmCu 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366

Al - 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605

Max. conductor resistance 50Hz at 90°C

Ω /kmCu 1.47 0.927 0.668 0.494 0.342 0.247 0.196 0.160 0.128 0.0988 0.0800 0.0643 0.0522

Al - 1.54 1.11 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.130 0.102 0.0801

Capacitance µF/km 0.21 0.24 0.28 0.31 0.35 0.40 0.43 0.47 0.52 0.56 0.57 0.60 0.62

Reactance at 50Hz Ω /km 0.117 0.109 0.105 0.100 0.0949 0.0914 0.0885 0.0860 0.0837 0.0817 0.0805 0.0790 0.0779

Current rating In air at 40°C

ACu 105 135 165 195 245 300 340 385 440 515 585 665 745

Al - 105 130 155 190 235 270 305 345 405 460 530 605

Current rating In the ground at 25°C

ACu 110 140 170 200 245 290 330 365 415 475 530 590 650

Al - 110 130 155 190 225 255 285 320 370 415 470 530

Short circuit current for 1 sec.

kACu 2.41 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 72.1

Al - 2.48 3.45 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 38.1 47.6

FEC Cables (M) Sdn. Bhd.

20

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Dimensional

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Separation Sheathed, Zinc-Coated SteelWire Armour, PVC Sheathed

3 Core

3.6/6 (Max. 7.2) kV

PVC Outer Sheath PVC Separation Sheath Metalic ScreenInsulation Screen

XLPE Insulation

Conductor Screen

Copper/Aluminium

Galvanized Steel Wire

Binder Tape

Filler

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Conductor dia. (approx.) mm 4.7 5.9 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3

Nominal insulation thickness

mm 3.4

Nominal separation thickness

mm 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1

Separation sheath dia. (approx.)

mm 35.5 38.3 41.1 43.7 47.6 51.4 54.6 57.9 61.7 67.1 72.1 78.1 84.7

Nominal of galvanized steel wire

mm 2.0 2.5 3.15

Nominal outer-sheath thickness

mm 2.3 2.4 2.5 2.6 2.7 2.9 3.0 3.1 3.2 3.4 3.6 3.8 4.0

Approx. overall dia. mm 44.5 48.5 51.5 54.0 58.0 62.5 66.0 69.5 73.5 80.5 86.0 92.0 99.5

Cable net. weight (approx.) kg/kmCu 3,220 4,130 4,740 5,380 6,420 7,600 8,690 9,840 11,370 14,560 16,960 20,210 24,000

Al - 3,650 4,070 4,480 5,110 5,790 6,400 7,030 7,840 9,880 11,140 12,770 14,610

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Max. conductor resistance DC at 20°C

Ω /kmCu 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366

Al - 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605

Max. conductor resis-tance 50Hz at 90°C

Ω /kmCu 1.47 0.927 0.668 0.494 0.342 0.247 0.196 0.160 0.128 0.0986 0.0798 0.0641 0.0521

Al - 1.54 1.11 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.130 0.102 0.0801

Capacitance µF/km 0.17 0.19 0.22 0.24 0.27 0.31 0.33 0.36 0.40 0.44 0.48 0.53 0.59

Reactance at 50Hz Ω /km 0.128 0.118 0.113 0.108 0.102 0.0976 0.0944 0.0915 0.0888 0.0856 0.0833 0.0809 0.0788

Current rating In air at 40°C

ACu 105 140 170 200 250 300 345 390 445 520 585 665 745

Al - 110 130 155 195 235 270 305 345 410 460 530 605

Current rating In the ground at 25°C

ACu 110 140 170 200 245 290 330 365 410 475 525 590 650

Al - 110 130 155 190 225 255 285 320 370 415 470 530

Short circuit current for 1 sec.

kACu 2.41 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 72.1

Al - 2.48 3.45 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 38.1 47.6

MEDIUM VOLTAGE CABLES

21

Dimensional

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Separation Sheathed, Zinc-Coated SteelWire Armour, PVC Sheathed

3 Core

6/10 (Max. 12) kV

PVC Outer Sheath PVC Separation Sheath Metalic ScreenInsulation Screen

XLPE Insulation

Conductor Screen

Copper/Aluminium

Galvanized Steel Wire

Binder Tape

Filler

Nominal cross sectional area mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Conductor dia. (approx.) mm - 5.9 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3

Nominal insulation thickness mm - 4.5

Nominal separation thickness mm - 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2

Separation sheath dia. (approx.)

mm - 43.3 46.1 48.7 52.6 56.4 59.7 62.9 66.7 72.1 77.1 83.1 89.7

Nominal of galvanized steel wire

mm - 2.5 3.15

Nominal outer-sheath thickness

mm - 2.6 2.7 2.8 2.9 3.0 3.1 3.2 3.4 3.6 3.7 4.0 4.2

Approx. overall dia. mm - 54.0 57.0 59.5 63.5 67.5 71.0 74.5 80.0 86.0 91.0 97.5 104.5

Cable net. weight (approx.) kg/kmCu - 4,790 5,420 6,080 7,160 8,350 9,460 10,640 13,090 15,550 17,950 21,300 25,140

Al - 4,310 4,760 5,180 5,850 6,530 7,170 7,820 9,560 10,870 12,130 13,860 15,760

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Max. conductor resistance DC at 20°C

Ω /kmCu - 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366

Al - 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605

Max. conductor resis-tance 50Hz at 90°C

Ω /kmCu - 0.927 0.668 0.494 0.342 0.247 0.196 0.159 0.128 0.0983 0.0794 0.0636 0.0515

Al - 1.54 1.11 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.130 0.102 0.0799

Capacitance µF/km - 0.16 0.18 0.20 0.22 0.25 0.27 0.29 0.31 0.35 0.38 0.42 0.46

Reactance at 50Hz Ω /km - 0.131 0.124 0.118 0.112 0.107 0.103 0.0994 0.0962 0.0924 0.0896 0.0868 0.0842

Current rating In air at 40°C

ACu - 140 170 200 250 305 350 395 450 520 590 665 750

Al - 110 130 155 195 235 270 305 350 410 465 535 610

Current rating In the ground at 25°C

ACu - 140 170 200 245 290 330 370 410 475 530 590 650

Al - 110 130 155 190 225 255 285 320 370 415 470 530

Short circuit current for 1 sec.

kACu - 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 72.1

Al - 2.48 3.45 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 38.1 47.6

FEC Cables (M) Sdn. Bhd.

22

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Dimensional

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Separation Sheathed, Zinc-Coated SteelWire Armour, PVC Sheathed

3 Core

8.7/15 (Max. 17.5) kV

PVC Outer Sheath PVC Separation Sheath Metalic ScreenInsulation Screen

XLPE Insulation

Conductor Screen

Copper/Aluminium

Galvanized Steel Wire

Binder Tape

Filler

Nominal cross sectional area mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Conductor dia. (approx.) mm - - 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 -

Nominal insulation thickness mm - - 5.5 -

Nominal separation thickness

mm - - 1.5 1.6 1.7 1.8 1.9 2.0 2.2 -

Separation sheath dia. (approx.)

mm - - 50.2 52.8 56.6 60.5 63.5 67.0 70.8 76.2 80.9 87.2 -

Nominal of galvanized steel wire

mm - - 2.5 3.15

Nominal outer-sheath thickness

mm - - 2.8 2.9 3.1 3.2 3.3 3.4 3.6 3.7 3.9 4.1 -

Approx. overall dia. mm - - 61.0 64.0 68.0 72.0 76.5 80.5 84.5 90.0 95.5 102.0 -

Cable net. weight (approx.) kg/kmCu - - 5,980 6,660 7,740 9,000 10,930 12,190 13,870 16,330 18,770 22,150 -

Al - - 5,310 5,750 6,440 7,190 8,640 9,380 10,340 11,650 12,950 14,710 -

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 -

Max. conductor resistance DC at 20°C

Ω /kmCu - - 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 -

Al - - 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 -

Max. conductor resistance 50Hz at 90°C

Ω /kmCu - - 0.668 0.494 0.342 0.247 0.196 0.159 0.128 0.0981 0.0792 0.0634 -

Al - - 1.11 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.129 0.101 -

Capacitance µF/km - - 0.16 0.17 0.19 0.21 0.23 0.25 0.27 0.30 0.32 0.35 -

Reactance at 50Hz Ω /km - - 0.130 0.124 0.117 0.112 0.108 0.104 0.100 0.0963 0.0933 0.0902 -

Current rating In air at 40°C

ACu - - 170 205 250 305 350 395 450 520 590 665 -

Al - - 135 160 195 240 275 310 350 410 465 535 -

Current rating In the ground at 25°C

ACu - - 170 200 240 290 330 365 410 470 525 585 -

Al - - 130 155 190 225 255 285 320 370 415 470 -

Short circuit current for 1 sec.

kACu - - 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 -

Al - - 3.45 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 38.1 -

MEDIUM VOLTAGE CABLES

23

Dimensional

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Separation Sheathed, Zinc-Coated SteelWire Armour, PVC Sheathed

3 Core

12/20 (Max. 24) kV

PVC Outer Sheath PVC Separation Sheath Metalic ScreenInsulation Screen

XLPE Insulation

Conductor Screen

Copper/Aluminium

Galvanized Steel Wire

Binder Tape

Filler

Nominal cross sectional area mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Conductor dia. (approx.) mm - - - 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 - -

Nominal insulation thickness mm - - - 8.0 - -

Nominal separation thickness mm - - - 1.8 1.9 2.0 2.1 2.2 2.3 - -

Separation sheath dia. (approx.)

mm - - - 64.2 68.0 71.9 75.1 78.4 82.2 87.6 92.5 - -

Nominal of galvanized steel wire

mm - - - 3.15 -

Nominal outer-sheath thickness

mm - - - 3.4 3.5 3.6 3.7 3.8 4.0 4.1 4.3 - -

Approx. overall dia. mm - - - 77.5 81.5 85.5 89.0 92.5 97.0 102.5 107.5 - -

Cable net. weight (approx.) kg/kmCu - - - 9,310 10,470 11,850 13,080 14,360 16,120 18,670 21,240 - -

Al - - - 8,410 9,160 10,040 10,790 11,550 12,590 13,990 15,420 - -

Nominal cross sectional area mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Max. conductor resistance DC at 20°C

Ω /kmCu - - - 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 - -

Al - - - 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 - -

Max. conductor resistance 50Hz at 90°C

Ω /kmCu - - - 0.494 0.342 0.247 0.196 0.159 0.128 0.0978 0.0789 - -

Al - - - 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.129 - -

Capacitance µF/km - - - 0.13 0.15 0.16 0.18 0.19 0.20 0.22 0.24 - -

Reactance at 50Hz Ω /km - - - 0.137 0.129 0.123 0.118 0.114 0.110 0.105 0.102 - -

Current rating In air at 40°C ACu - - - 205 255 310 350 395 450 520 590 - -

Al - - - 160 200 240 275 310 350 410 465 - -

Current rating In the ground at 25°C

ACu - - - 200 240 290 325 365 410 470 525 - -

Al - - - 155 190 225 255 285 320 370 415 - -

Short circuit current for 1 sec. kACu - - - 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 - -

Al - - - 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 - -

FEC Cables (M) Sdn. Bhd.

2�

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Dimensional

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Separation Sheathed, Zinc-Coated SteelWire Armour, PVC Sheathed

3 Core

18/30 (Max. 36) kV

PVC Outer Sheath PVC Separation Sheath Metalic ScreenInsulation Screen

XLPE Insulation

Conductor Screen

Copper/Aluminium

Galvanized Steel Wire

Binder Tape

Filler

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Conductor dia. (approx.) mm 4.7 5.9 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3

Nominal insulation thickness

mm 2.5 2.6 2.8 3.0 3.2

Nominal separation thickness

mm 1.2 1.3 1.4 1.5 1.6 1.7 1.8 2.0 2.1

Separation sheath dia. (approx.)

mm 31.6 34.2 37.0 39.6 43.7 47.3 50.6 53.8 57.7 63.5 69.3 76.3 83.9

Nominal of galvanized steel tape

mm 0.2 0.5 0.8

Nominal outer-sheath thickness

mm 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 3.1 3.3 3.6 3.9

Approx. overall dia. mm 37.0 41.0 44.0 46.5 51.0 55.0 58.0 61.5 65.5 72.0 78.0 87.0 95.0

Cable net. weight (approx.)

kg/kmCu 1,790 2,620 3,110 3,660 4,570 5,590 6,560 7,590 8,960 11,170 13,420 17,500 21,260

Al - 2,140 2,440 2,750 3,260 3,780 4,270 4,770 5,430 6,490 7,600 10,050 11,870

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Max. conductor resistance DC at 20°C

Ω /kmCu 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366

Al - 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605

Max. conductor resis-tance 50Hz at 90°C

Ω /kmCu 1.47 0.927 0.668 0.494 0.342 0.247 0.196 0.160 0.128 0.0988 0.0800 0.0643 0.0522

Al - 1.54 1.11 0.866 0.568 0.411 0.325 0.265 0.211 0.161 0.130 0.102 0.0801

Capacitance µF/km 0.21 0.24 0.28 0.31 0.35 0.40 0.43 0.47 0.52 0.56 0.57 0.60 0.62

Reactance at 50Hz Ω /km 0.118 0.109 0.105 0.100 0.0949 0.0914 0.0885 0.0860 0.0837 0.0817 0.0805 0.0790 0.0779

Current rating In air at 40°C

ACu 100 135 160 195 240 295 340 385 440 520 590 680 775

Al - 105 130 155 190 235 270 305 350 410 470 545 630

Current rating In the ground at 25°C

ACu 110 140 170 200 240 290 330 370 415 480 540 610 685

Al - 110 130 155 190 225 255 285 325 375 425 485 555

Short circuit current for 1 sec.

kACu 2.41 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 72.1

Al - 2.48 3.45 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 38.1 47.6

MEDIUM VOLTAGE CABLES

25

Dimensional

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Separation Sheathed, Zinc-Coated SteelTape Armour, PVC Sheathed

3 Core

3.6/6 (Max. 7.2) kV

m

PVC Outer SheathGalvanized Steel Tape(Double Tape)

PVC Separation Sheath Metalic Screen

Insulation Screen

XLPE Insulation

Conductor Screen

Copper/Aluminiu

Binder Tape

Filler

Nominal cross sectional area mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Conductor dia. (approx.) mm 4.7 5.9 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3

Nominal insulation thickness

mm 3.4

Nominal separation thickness

mm 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1

Separation sheath dia. (approx.)

mm 35.5 38.3 41.1 43.7 47.6 51.4 54.6 57.9 61.7 67.1 72.1 78.1 84.7

Nominal of galvanized steel tape

mm 0.5 0.8

Nominal outer-sheath thickness

mm 2.2 2.3 2.4 2.5 2.6 2.7 2.9 3.0 3.1 3.3 3.4 3.7 3.9

Approx. overall dia. mm 42.0 45.0 48.0 51.0 55.0 59.0 62.5 66.0 70.0 76.0 81.0 89.0 96.0

Cable net. weight (approx.) kg/kmCu 2,490 2,980 3,480 4,050 4,960 6,030 7,050 8,100 9,500 11,690 13,830 17,790 21,400

Al - 2,500 2,810 3,140 3,650 4,220 4,760 5,280 5,970 7,020 8,010 10,350 12,010

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Max. conductor resistance DC at 20°C

Ω /kmCu 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366

Al - 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605

Max. conductor resistance 50Hz at 90°C

Ω /kmCu 1.47 0.927 0.668 0.494 0.342 0.247 0.196 0.160 0.128 0.0986 0.0798 0.0641 0.0521

Al - 1.54 1.11 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.130 0.102 0.0801

Capacitance µF/km 0.17 0.19 0.22 0.24 0.27 0.31 0.33 0.36 0.40 0.44 0.48 0.53 0.59

Reactance at 50Hz Ω /km 0.128 0.118 0.113 0.108 0.102 0.0976 0.0944 0.0915 0.0888 0.0856 0.0833 0.0809 0.0788

Current rating In air at 40°C

ACu 105 135 165 195 245 300 340 385 445 520 590 680 775

Al - 105 130 155 190 230 265 300 345 405 465 540 625

Current rating In the ground at 25°C

ACu 110 140 170 200 240 290 330 370 415 480 540 610 685

Al - 110 130 155 190 225 255 285 325 375 425 485 555

Short circuit current for 1 sec.

kACu 2.41 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 72.1

Al - 2.48 3.45 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 38.1 47.6

FEC Cables (M) Sdn. Bhd.

26

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Dimensional

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Separation Sheathed, Zinc-Coated SteelTape Armour, PVC Sheathed

3 Core

6/10 (Max. 12) kV

m

PVC Outer SheathGalvanized Steel Tape(Double Tape)

PVC Separation Sheath Metalic Screen

Insulation Screen

XLPE Insulation

Conductor Screen

Copper/Aluminiu

Binder Tape

Filler

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Conductor dia. (approx.) mm - 5.9 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3

Nominal insulation thickness

mm - 4.5

Nominal separation thickness

mm - 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2

Separation sheath dia. (approx.)

mm - 43.3 46.1 48.7 52.6 56.4 59.7 62.9 66.7 72.1 77.1 83.1 89.7

Nominal of galvanized steel tape

mm - 0.5 0.8

Nominal outer-sheath thickness

mm - 2.5 2.6 2.7 2.8 2.9 3.0 3.1 3.3 3.4 3.6 3.9 4.1

Approx. overall dia. mm - 50.5 53.5 56.5 60.5 64.5 68.0 71.5 75.5 81.0 87.5 94.5 101.5

Cable net. weight (approx.)

kg/kmCu - 3,490 4,020 4,600 5,550 6,650 7,670 8,750 10,210 12,420 15,570 18,720 22,380

Al - 3,010 3,350 3,700 4,240 4,840 5,380 5,930 6,680 7,750 9,750 11,270 12,990

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Max. conductor resistance DC at 20°C

Ω /kmCu - 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366

Al - 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605

Max. conductor resistance 50Hz at 90°C

Ω /kmCu - 0.927 0.668 0.494 0.342 0.247 0.196 0.159 0.128 0.0983 0.0794 0.0636 0.0515

Al - 1.54 1.11 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.130 0.102 0.0799

Capacitance µF/km - 0.16 0.18 0.20 0.22 0.25 0.27 0.29 0.31 0.35 0.38 0.42 0.46

Reactance at 50Hz Ω /km - 0.131 0.124 0.118 0.112 0.107 0.103 0.0994 0.0962 0.0924 0.0896 0.0868 0.0842

Current rating In air at 40°C

ACu - 140 170 200 250 300 345 395 450 525 600 685 780

Al - 105 130 155 195 235 270 305 350 410 470 545 630

Current rating In the ground at 25°C

ACu - 140 170 200 245 290 330 370 415 480 540 610 690

Al - 110 130 155 190 225 255 285 325 375 425 485 555

Short circuit current for 1 sec.

kACu - 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 72.1

Al - 2.48 3.45 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 38.1 47.6

MEDIUM VOLTAGE CABLES

27

Dimensional

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Separation Sheathed, Zinc-Coated SteelTape Armour, PVC Sheathed

3 Core

8.7/15 (Max. 17.5) kV

m

PVC Outer SheathGalvanized Steel Tape(Double Tape)

PVC Separation Sheath Metalic Screen

Insulation Screen

XLPE Insulation

Conductor Screen

Copper/Aluminiu

Binder Tape

Filler

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Conductor dia. (approx.) mm - - 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3

Nominal insulation thickness

mm - - 5.5

Nominal separation thickness

mm - - 1.5 1.6 1.7 1.8 1.9 2.0 2.0 2.2 2.3

Separation sheath dia. (approx.)

mm - - 50.2 52.8 56.6 60.5 63.5 67.0 70.8 76.2 80.9 87.2 93.8

Nominal of galvanized steel tape

mm - - 0.5 0.8

Nominal outer-sheath thickness

mm - - 2.7 2.8 2.9 3.1 3.2 3.3 3.4 3.6 3.8 4.0 4.2

Approx. overall dia. mm - - 58.0 60.5 64.5 69.0 72.0 76.0 80.0 87.0 92.0 98.5 105.5

Cable net. weight (approx.)

kg/kmCu - - 4,450 5,050 6,020 7,180 8,190 9,320 10,780 13,980 16,240 19,440 23,140

Al - - 3,780 4,150 4,720 5,370 5,900 6,510 7,250 9,300 10,420 11,990 13,760

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Max. conductor resistance DC at 20°C

Ω /kmCu - - 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366

Al - - 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605

Max. conductor resis-tance 50Hz at 90°C

Ω /kmCu - - 0.668 0.494 0.342 0.247 0.196 0.159 0.128 0.0981 0.0792 0.0634 0.0512

Al - - 1.11 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.130 0.101 0.0798

Capacitance µF/km - - 0.16 0.17 0.19 0.21 0.23 0.25 0.27 0.30 0.32 0.35 0.39

Reactance at 50Hz Ω /km - - 0.130 0.124 0.117 0.112 0.108 0.104 0.100 0.0963 0.0933 0.0902 0.0873

Current rating In air at 40°C

ACu - - 170 200 250 305 350 395 450 530 600 685 780

Al - - 130 155 190 235 270 305 350 415 470 545 630

Current rating In the ground at 25°C

ACu - - 170 200 245 290 330 370 415 480 545 615 690

Al - - 130 155 190 225 255 285 325 375 425 485 555

Short circuit current for 1 sec.

kACu - - 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 72.1

Al - - 3.45 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 38.1 47.6

FEC Cables (M) Sdn. Bhd.

28

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Dimensional

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Separation Sheathed, Zinc-Coated SteelTape Armour, PVC Sheathed

3 Core

12/20 (Max. 24) kV

m

PVC Outer SheathGalvanized Steel Tape(Double Tape)

PVC Separation Sheath Metalic Screen

Insulation Screen

XLPE Insulation

Conductor Screen

Copper/Aluminiu

Binder Tape

Filler

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Conductor dia. (approx.) mm - - - 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 - -

Nominal insulation thickness

mm - - - 8.0 - -

Nominal separation thickness

mm - - - 1.8 1.9 2.0 2.0 2.1 2.2 2.3 - -

Separation sheath dia. (approx.)

mm - - - 64.2 68.0 71.9 75.1 78.4 82.2 87.6 92.5 - -

Nominal of galvanized steel tape

mm - - - 0.5 0.8 - -

Nominal outer-sheath thickness

mm - - - 3.2 3.3 3.5 3.6 3.7 3.9 4.0 4.2 - -

Approx. overall dia. mm - - - 73.0 77.0 81.0 86.0 89.0 93.5 99.0 104.5 - -

Cable net. weight (approx.)

kg/kmCu - - - 6,480 7,520 8,750 10,760 11,950 13,570 15,970 18,370 - -

Al - - - 5,580 6,210 6,940 8,470 9,140 10,040 11,290 12,550 - -

Nominal cross sectional area

mm² 16 25 35 50 70 95 120 150 185 240 300 400 500

Max. conductor resistance DC at 20°C

Ω /kmCu - - - 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 - -

Al - - - 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 - -

Max. conductor resistance 50Hz at 90°C

Ω /kmCu - - - 0.494 0.342 0.247 0.196 0.159 0.128 0.0978 0.0789 - -

Al - - - 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.129 - -

Capacitance µF/km - - - 0.13 0.15 0.16 0.18 0.19 0.20 0.22 0.24 - -

Reactance at 50Hz Ω /km - - - 0.137 0.129 0.123 0.118 0.114 0.110 0.105 0.102 - -

Current rating In air at 40°C

ACu - - - 205 255 305 350 395 450 530 600 - -

Al - - - 160 195 240 275 310 355 415 475 - -

Current rating In the ground at 25°C

ACu - - - 200 240 290 330 370 415 480 540 - -

Al - - - 155 190 225 255 285 325 375 425 - -

Short circuit current for 1 sec.

kACu - - - 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 - -

Al - - - 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 - -

MEDIUM VOLTAGE CABLES

29

Dimensional

MEDIUM VOLTAGE IEC 60502-2SPECIFICATION

Electrical Data

Copper And Aluminium Conductor XLPE Insulated, Copper Tape Screened, PVC Separation Sheathed, Zinc-Coated SteelTape Armour, PVC Sheathed

3 Core

18/30 (Max. 36) kV

m

PVC Outer SheathGalvanized Steel Tape(Double Tape)

PVC Separation Sheath Metalic Screen

Insulation Screen

XLPE Insulation

Conductor Screen

Copper/Aluminiu

Binder Tape

Filler

The thermally permissible short circuit current for a conductor of specified size may be calculated from the equations below (based on IEC 609�9). For purposes of calculation, the standard short circuit duration period is up to 5 sec.

1. Copper Conductor :

2. Aluminium Conductor :

where s : conductor size in mm²

t : short circuit period in seconds

Short Circuit Current

Calculation Base for Electrical Characteristics

Installation

In air (Ambient temperature : 40 °C) In the ground (Ambient temperature : 25 °C)

Multi-core cable Single-core cable

Correction Factors For Continuous Current Rating

Ambient Temperature (°C)

Instalation15 20 25 30 35 �0 �5 50 55

In Air 1.22 1.18 1.1� 1.10 1.05 1.0 0.95 0.89 0.8�

In Ground 1.07 1.0� 1.0 0.96 0.92 0.88 0.83 0.78 0.73

I =1�3 • S

t1 + 0.�1 + 0.12t

sts (A)

I =9� • S

t1 + 0.57 + 0.16t

sts (A)

Multi-core cable Single-core cable

GroundLevel

700

mm

700

mm

Thermal Resistivity :120° C. cm/W

FEC Cables (M) Sdn. Bhd.

30

Factory 1Persiaran Raja Muda, �0000 Shah Alam, Selangor Darul Ehsan, Malaysia.(P.O. Box 7006, �0700 Shah Alam)Tel : 6 03 - 5519 1110 (Hotline) Fax : 6 03 - 5519 1296

Factory 2No. 16, Jalan Keluli 2, Bukit Raja Industrial Area, �1050 Klang, Selangor Darul Ehsan, Malaysia. Tel : 6 03 - 33�3 5837 (Hotline) Fax : 6 03 - 33�3 58�3

Sales OfficePersiaran Raja Muda, �0000 Shah Alam, Selangor Darul Ehsan, MalaysiaTel : 6 03 - 5519 1110 (Hotline) Fax : 6 03 - 5519 1296 / 5513 8688Email : [email protected]

www.fec.com.my

FEC Cables (M) Sdn. Bhd.(7293-W)

Des

ign

by

Tel :

03

- 772

2 48

18

FEC Cables (M) Sdn. Bhd.

Low Voltage Cables

CORPORATEHISTORY

INTRODUCTION OF

COMPANYWhen there is talk of high quality electric wires and cables, the one company that comes to mind is FEC Cables (Malaysia) Sdn. Bhd. FEC is a subsidiary of Permodalan Nasional Berhad and was formerly known as Furukawa Electric Cables (M) Sdn. Bhd. Having established its Shah Alam plant in 1967 on a 7-acre site at the Shah Alam Industrial Estate, Furukawa has come a long way.

The technical collaboration with our Japanese counterpart, Furukawa Japan, has brought about an amazing success for us. In terms of quality, we have climbed the ladders of product manufacturing, steadily and successfully, pushing FEC towards the pinnacle of excellence. Putting our customers’ demands and needs as our number one priority, we opened our second plant in 1995, on a 27-acre freehold land site in Bukit Raja Industrial area, Klang. In our quest for excellence, we equip the plant with the latest technological aids for the manufacture of a wide range of low and medium voltage cables.

The certification of the ISO 9001 for both plants only proves that we do not compromise on quality and customer satisfaction. Our dedicated and hard-working employees are the backbone of our success. This was greatly helped by the state-of-the-art technology equipment which has led us towards excellence.

Moving towards a new century, we pledge to continually strive towards progressive and dynamic growth as FEC Cables continues its efforts in contributing to the development Malaysia.

FEC Cables (M) Sdn. Bhd. was first established in 1967 and was previously known as Furukawa Electric Cables (M) Sdn. Bhd. In all the years until 2003, the company had been under the management and control of Furukawa Electric Co. Ltd. of Japan.

In 2003, the company was renamed FEC Cables (M) Sdn. Bhd. following the acquisition of its major equity stake by Permodalan Nasional Berhad, Malaysia’s government-owned premier multi-billion dollar investment institution.

The Company had started a technical collaboration from world renowned cable manufacturer, The Furukawa Electric Co. Ltd Japan (Furukawa Japan).

FEC Cables has benefited enormously from the technical collaboration and the subsequent technology transfer with Furukawa Japan. FEC Cables inherited from Furukawa Japan not only its advanced technology and technical know-how but also the disciplines of producing quality products using material conforming to the international standards of manufacturing cables.

Today FEC Cables plays a prominent role as a forerunner in the cable industry.

FEC Cables has been actively involved in serving various industrial sectors, namely the power, telecommunications, construction as well as the oil and gas sectors.

Low Voltage Cables

1. BS 6004

a. U/PVC Non-Sheathed Cables For General Purpose �50/750 V b. CU/PVC/PVC/PVC Sheathed Light Cables 300/500 V c. CU/PVC/PVC Sheathed Cables 300/500 V d. CU/PVC Non-Sheathed Cables For Internal Wiring 300/500 V

2. BS 6346(MS 274) (600/1000V)

a. CU/PVC/PVC/SWA(AL)/PVC Sheathed Power Cable(1-CORE) b. CU/PVC/PVC/SWA/PVC Sheathed Power Cable (i) 2-Core (ii) 3-Core (iii) �-Core (iv) 3 ½-Core c. CU/PVC/PVC/SWA/PVC Sheathed Control Cable (i) 1.5 mm² (ii) 2.5 mm² (iii) � mm²

3. IEC 60502-1 (600/1000 V)

a. CU/PVC/PVC Sheathed Power Cable (i) 1-Core (ii) 2-Core (iii) 3-Core (iv) �-Core (v) 3 ½-Core

b. CU/PVC/PVC/SWA(AL)/PVC Sheathed Power Cable(1-core)

c. CU/PVC/PVC/SWA/PVC Sheathed Power Cable (i) 2-Core (ii) 3-Core (iii) �-Core (iv) 3 ½-Core d. CU/XLPE/PVC Sheathed Power Cable (i) 1-Core (ii) 2-Core (iii) 3-Core (iv) �-Core (v) 3 ½-Core

e. CU/XLPE/PVC/SWA(AL)/PVC Sheathed Power Cable(1-Core)

6789

10

1112131�

151617

1819202122

23

2�252627

2829303132

33

Table Of Contents

LOW VOLTAGE CABLES

5

f. CU/XLPE/PVC/SWA/PVC Sheathed Power Cable (i) 2-Core (ii) 3-Core (iii) �-Core (iv) 3 ½-Core

g. CU/PVC/PVC Sheathed Control Cable (i) 1.5 mm² (ii) 2.5 mm² (iii) � mm²

h. CU/PVC/PVC Sheathed(Screened-CU) Control Cable (i) 1.5 mm² (ii) 2.5 mm² (iii) � mm²

i. CU/PVC/PVC/SWA/PVC Sheathed Control Cable (i) 1.5 mm² (ii) 2.5 mm² (iii) � mm²

j CU/PVC/PVC/SWA/PVC Sheathed(Screened-CU) Control Cable (i) 1.5 mm² (ii) 2.5 mm² (iii) � mm² k. CU/XLPE/PVC Sheathed Control Cable (i) 1.5 mm² (ii) 2.5 mm² (iii) � mm²

l. CU/XLPE/PVC Sheathed(Screened-CU) Control Cable (i) 1.5 mm² (ii) 2.5 mm² (iii) � mm²

m. CU/XLPE/PVC/SWA/PVC Sheathed Control Cable (i) 1.5 mm² (ii) 2.5 mm² (iii) � mm²

n. CU/XLPE/PVC/SWA/PVC Sheathed(Screened-CU) Control Cable (i) 1.5 mm² (ii) 2.5 mm² (iii) � mm²

3. Short Circuit Current, Calculation Base for Electrical Characteristics and Correction Factors for Continuous Current Rating

3�353637

3839�0

�1�2�3

���5�6

�7�8�9

505152

535�55

565758

596061

62

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630

No./Diameter of Wires

No./mm 7/0.53 7/0.67 7/0.85 7/1.04 7/1.35 7/1.70 7/2.14 19/1.53 19/1.78 19/2.14 19/2.52 37/2.03 37/2.25 37/2.52 61/2.25 61/2.52 61/2.85 61/3.20 127/2.52

Nominal insulation thickness

mm 0.7 0.8 0.8 0.8 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 2.6 2.8 2.8

Mean Overall Diameter(mm)

Lower Limit

2.7 3.3 3.8 4.3 5.6 6.4 8.1 9.0 10.6 12.1 14.1 15.6 17.3 19.3 22.0 24.5 27.5 30.5 34.0

Upper Limit

3.3 4.0 4.6 5.2 6.7 7.8 9.7 10.9 12.8 14.6 17.1 18.8 20.9 23.3 26.6 29.6 33.2 36.9 41.1

Cable net. weight (approx.)

kg/km 23 35 52 73 120 181 283 377 513 721 994 1,234 1,517 1,904 2,485 3,112 3,960 4,968 6,325

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630

Max. conductor resistance DC at 20°C

Ω /km 12.10 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

Min. insulation resistance at 70°C

MΩ /km

0.010 0.009 0.0077 0.0065 0.0065 0.0050 0.0050 0.0043 0.0043 0.0035 0.0035 0.0032 0.0032 0.0032 0.0032 0.0030 0.0028 0.0028 0.0025

FEC Cables (M) Sdn. Bhd.

6

LOW VOLTAGE 450/750 V BS 6004SPECIFICATION

Dimensional

1 Core

FEC Cables (M) Sdn. Bhd.

6

LOW VOLTAGE 450/750 V BS 6004SPECIFICATION

Circular Stranded Copper Conductor,PVC Non-seathed Cables For General Purpose

PVC Insulation Copper

Core Identification : Green/Yellow

Electrical Data

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 1.5 2.5 4 6 10 1.5 2.5 4 6 10 1.5 2.5 4 6 10

No. of cores 2 3 4 5

No./Diameter of Wires No./mm 7/0.53 7/0.67 7/0.85 7/1.04 7/1.35 7/0.53 7/0.67 7/0.85 7/1.04 7/1.35 7/0.53 7/0.67 7/0.85 7/1.04 7/1.35 7/0.53 7/0.67 7/0.85 7/1.04 7/1.35

Nominal insulation thickness

mm 0.7 0.8 0.8 0.8 1.0 0.7 0.8 0.8 0.8 1.0 0.7 0.8 0.8 0.8 1.0 0.7 0.8 0.8 0.8 1.0

Nominal inner cover-ing thickness

mm 0.4 0.4 0.4 0.4 0.6 0.4 0.4 0.4 0.4 0.6 0.4 0.4 0.4 0.6 0.6 0.4 0.4 0.6 0.6 0.6

Nominal sheath thickness

mm 1.2 1.2 1.2 1.2 1.4 1.2 1.2 1.2 1.4 1.4 1.2 1.2 1.4 1.4 1.4 1.2 1.2 1.4 1.4 1.4

Mean Overall Diameter(mm)

Lower Limit

8.4 9.6 10.5 11.5 15.0 8.8 10.0 11.0 12.5 15.5 9.6 11.0 12.5 14.0 17.0 10.0 12.0 14.0 15.5 18.5

Upper Limit

10.5 12.0 13.0 14.0 17.5 10.5 12.5 13.5 15.5 19.0 12.0 13.5 15.0 17.0 20.5 12.5 14.5 17.0 18.5 22.0

Cable net. weight (approx.)

kg/km 114 155 200 255 417 140 193 255 347 542 169 237 333 447 682 201 284 413 539 829

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 1.5 2.5 4 6 10 1.5 2.5 4 6 10 1.5 2.5 4 6 10

No. of cores 2 3 4 5

Max. conductor resistance DC at 20°C

Ω /km 12.10 7.41 4.61 3.08 1.83 12.10 7.41 4.61 3.08 1.83 12.10 7.41 4.61 3.08 1.83 12.10 7.41 4.61 3.08 1.83

Min. insulation resistance at 70°C

MΩ /km

0.010 0.009 0.0077 0.0065 0.0065 0.010 0.009 0.0077 0.0065 0.0065 0.010 0.009 0.0077 0.0065 0.0065 0.010 0.009 0.0077 0.0065 0.0065

LOW VOLTAGE CABLES

7

LOW VOLTAGE SPECIFICATION

Dimensional

Electrical Data

Circular Stranded Copper Conductor,PVC Insulated, Pvc Inner Covering, PVC Sheathed Light Cables

5 Core

300/500 V BS 6004

Binder Tape

Inner Covering

PVC Sheath

Filler

PVC Insulation

Copper

Core Identification : Two-core = Red & Black Three-core = Red,Yellow & Blue. Four-core = Red, Yellow, Blue & Black Five-core = Red, Yellow, Blue, Black & Green/Yellow

Nominal cross sectional area

mm² 1.0 1.25 1.5 1.5 2.5 4 6 10 16 25 35

No./Diameter of Wires

No./mm 1/1.13 3/0.73 1/1.38 7/0.53 7/0.67 7/0.85 7/1.04 7/1.35 7/1.70 7/2.14 19/1.53

Nominal insulation thickness

mm 0.6 0.7 0.8 1.0 1.2

Nominal sheath thickness

mm 0.8 0.9 1.0 1.1

Mean Overall Diameter(mm)

Lower Limit 3.8 4.3 4.2 4.3 5.0 5.4 6.0 7.2 8.4 10.0 11.0

Upper Limit 4.5 5.1 4.9 5.0 6.0 6.8 7.4 8.8 10.5 12.5 13.5

Cable net. weight (approx.)

kg/km 27 36 35 38 54 75 99 152 221 337 438

Nominal cross sectional area

mm² 1.0 1.25 1.5 1.5 2.5 4 6 10 16 25 35

Max. conductor resistance DC at 20°C

Ω /km 18.10 14.60 12.10 12.10 7.41 4.61 3.08 1.83 1.15 0.727 0.524

Min. insulation resistance at 70°C

MΩ /km 0.011 0.011 0.011 0.010 0.009 0.0077 0.0065 0.0065 0.0052 0.0050 0.0044

FEC Cables (M) Sdn. Bhd.

8

LOW VOLTAGE SPECIFICATION

Dimensional

1 Core

Electrical Data Electrical Data

Circular Stranded Copper Conductor,PVC Insulation, PVC Sheathed Cables

300/500 V BS 6004

Copper

PVC Insulation

PVC Sheath

Core Identification : Black

Nominal cross sectional area mm² 0.5 0.75 1.0

No./Diameter of Wires No./mm 1/0.80 1/0.98 1/1.13

Nominal insulation thickness mm 0.6 0.6 0.6

Mean Overall Diameter(mm)Lower Limit 1.9 2.1 2.2

Upper Limit 2.3 2.5 2.7

Cable net. weight (approx.) kg/km 9 11 14

Nominal cross sectional area mm² 0.5 0.75 1.0

Max. conductor resistance DC at 20°C Ω /km 36.0 24.5 18.1

Min. insulation resistance at 70°C MΩ /km 0.015 0.012 0.011

LOW VOLTAGE CABLES

9

LOW VOLTAGE SPECIFICATION

Dimensional

1 Core

Electrical Data

Solid Copper Conductor,PVC Non-Sheathed Cables For Internal Wiring

300/500 V BS 6004

PVC Insulation Copper

Core Identification : Green/Yellow

Nominal cross sectional area mm² 50 70 95 120 150 185 240 300 400 500 630 800 1000

Shape of Conductor Circular Compacted Circular Non-Compacted

Conductor dia. (approx) 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3 32.76 37.05 41.60

Nominal insulation thickness mm 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0

Nominal bedding thickness mm 0.8 1.0 1.2 1.4

Bedding dia. (approx) mm 12.6 14.2 16.3 18.1 20.0 22.2 25.0 27.7 31.2 34.6 41.1 45.8 50.8

Nominal of hard-drawn Al wire mm 1.25 1.6 2.0 2.5

Nominal outer-sheath thickness mm 1.5 1.6 1.7 1.8 1.9 2.1 2.2 2.4 2.5

Approx. overall dia. mm 19.1 21.1 23.4 26.3 28.3 30.8 34.1 37.0 42.0 45.6 49.7 55.8 61.0

Cable net weight (approx) kg/km 740 980 1,280 1,620 1,940 2,380 3,020 3,690 4,750 5,820 7,530 9,560 11,830

Nominal cross sectional area

mm² 50 70 95 120 150 185 240 300 400 500 630 800 1000

Max. conductor resistance DC at 20°C

Ω /km 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221 0.0176

Current rating In air at 30°C

ATrefoil 193 243 298 347 395 452 532 607 690 776 869 937 1,010

Spaced* 223 279 339 386 433 486 555 618 666 718 778 819 873

Current rating In the ground at 15°C

ATrefoil 203 248 297 337 376 423 485 542 600 660 721 756 797

Spaced* 211 257 305 341 377 417 469 515 549 586 627 648 679

Voltage drop mVTrefoil 0.82 0.58 0.44 0.36 0.31 0.27 0.23 0.20 0.19 0.18 0.16 0.16 0.15

Spaced* 0.87 0.65 0.52 0.45 0.41 0.38 0.35 0.33 0.32 0.31 0.31 - -

FEC Cables (M) Sdn. Bhd.

10

LOW VOLTAGE SPECIFICATION

Dimensional

1 Core

Electrical Data

Copper Conductor, PVC Insulated,PVC Bedded, Aluminium Wire Armour, PVC Sheathed

600/1000 V BS 6346 (MS 274)

Armouring

Binder Tape

PVC Outer Sheath

PVC Insulation

Copper

PVC Bedding

* Installed vertically spacedDepth of laying = 500 mm

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Shape of Conductor Circular Non-Compacted CC Shaped Stranded

Nominal insulation thickness

mm 0.6 0.7 0.8 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6

Nominal bedding thickness

mm 0.8 1.0 1.2 1.4 1.6

Bedding dia. (approx) mm 7.3 8.6 10.3 11.4 13.4 15.4 16.3 17.7 20.5 23.1 26.9 28.9 31.7 35.7 40.1 44.7 49.1

Nominal of galvanized steel wire

mm 0.9 1.25 1.6 2.0 2.5

Nominal outer-sheath thickness

mm 1.4 1.5 1.6 1.7 1.8 1.9 2.1 2.2 2.3 2.4 2.5 2.7 2.9

Approx. overall dia. mm 12.3 13.6 15.1 16.5 20.1 21.9 23.0 24.9 27.8 30.4 35.5 38.0 41.3 46.4 51.2 56.4 61.9

Cable net weight (approx)

kg/km 260 320 410 490 740 930 1,300 1,570 1,970 2,490 3,480 4,080 4,810 6,200 7,730 9,260 11,330

ominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Max. conductor resistance DC at 20°C

Ω /km 12.10 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Current rating In air at 30°C

A 23 32 42 54 74 102 136 166 201 252 312 360 409 473 558 636 729

Current rating In the ground at 15°C

A 30 40 53 66 88 119 158 190 225 277 332 377 422 478 551 616 693

Voltage Drop (mV) 29 18 12 7.4 4.3 2.8 1.7 1.3 0.94 0.66 0.49 0.40 0.34 0.29 0.24 0.21 0.19

LOW VOLTAGE CABLES

11

LOW VOLTAGE SPECIFICATION

Dimensional

Electrical Data

Copper Conductor, PVC Insulated,PVC Bedded, Zinc-Coated Steel Wire Armour, PVC Sheathed

2 Core

600/1000 V BS 6346 (MS 274)

PVC Bedding

Armouring

PVC Outer Sheath

CopperPVC Insulation

Filler

Binder Tape

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Shape of Conductor Circular Non-Compacted CC Shaped Stranded

Nominal insulation thickness

mm 0.6 0.7 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6

Nominal bedding thickness

mm 0.8 1.0 1.2 1.4 1.6

Bedding dia. (approx)

mm 7.8 9.1 10.9 12.2 14.3 16.4 18.6 20.6 23.8 27.2 31.6 33.7 37.0 41.6 47.2 52.0 57.6

Nominal of galva-nized steel wire

mm 0.9 1.25 1.6 2.0 2.5

Nominal outer-sheath thickness

mm 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.4 2.5 2.6 2.8 3.0

Approx. overall dia. mm 12.8 14.1 15.8 18.0 21.2 23.1 25.0 27.3 30.5 35.0 39.3 42.2 47.5 51.9 57.8 63.2 69.6

Cable net weight (approx)

kg/km 290 360 470 670 880 1,140 1,650 2,040 2,590 2,630 4,690 5,530 6,990 8,440 10,670 12,770 15,810

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Max. conductor resistance DC at 20°C

Ω /km 12.10 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Current rating In air at 30°C

A 20 27 36 46 63 87 116 142 172 218 268 310 355 407 480 547 627

Current rating In the ground at 15°C

A 26 34 45 57 75 101 132 159 188 233 279 317 355 401 462 517 580

Voltage Drop (mV) 25 16 9.6 6.3 3.8 2.4 1.5 1.1 0.82 0.57 0.42 0.35 0.29 0.25 0.21 0.18 0.17

FEC Cables (M) Sdn. Bhd.

12

LOW VOLTAGE SPECIFICATION

Dimensional

Electrical Data

Copper Conductor, PVC Insulated, PVC Bedded,Zinc-Coated Steel Wire Armour, PVC Sheathed

3 Core

600/1000 V BS 6346 (MS 274)

PVC Bedding

Armouring

Copper

PVC Insulation

FillerBinder Tape

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Shape of Conductor

Circular Non-Compacted CC Shaped Stranded

Nominal insulation thickness

mm 0.6 0.7 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6

Nominal bedding thickness

mm 0.8 1.0 1.2 1.4 1.6 1.8

Bedding dia. (approx)

mm 8.5 10 12.1 13.4 15.8 18.6 20.4 22.7 26.6 30.1 34.6 37.8 42.0 47.3 52.9 59.0 66.0

Nominal of galvanized steel wire

mm 0.9 1.25 1.6 2.0 2.5 3.15

Nominal outer-sheath thickness

mm 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.4 2.5 2.6 2.8 3.0 3.3

Approx. overall dia. mm 13.5 15.0 17.8 19.2 22.8 26.3 27.8 30.5 35.4 39.2 44.3 49.3 53.6 59.0 65.7 72.0 81.3

Cable net weight (approx)

kg/km 330 420 650 790 1,050 1,550 2,020 2,510 3,460 4,500 5,810 7,420 8,820 10,750 13,550 16,470 21,260

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Max. conductor resistance DC at 20°C

Ω /km 12.10 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Current rating In air at 30°C

A 20 27 36 46 63 87 116 142 172 218 268 310 355 407 480 547 627

Current rating In the ground at 15°C

A 26 34 45 57 75 101 132 159 188 233 279 317 355 401 462 517 580

Voltage Drop (mV) 25 16 9.6 6.3 3.8 2.4 1.5 1.1 0.82 0.57 0.42 0.35 0.29 0.25 0.21 0.18 0.17

LOW VOLTAGE CABLES

13

LOW VOLTAGE SPECIFICATION

Dimensional

Electrical Data

Copper Conductor, PVC Insulated, PVC Bedded,Zinc-Coated Steel Wire Armour, Sheathed

4 Core

600/1000 V BS 6346 (MS 274)

PVC Bedding

Armouring

PVC Outer Sheath

Copper

PVC InsulationFiller

Binder Tape

Nominal cross sectional area(Phase)

mm² 25 35 50 70 95 120 150 185 240 300 300 400

Shape of Conductor(Phase) Shaped Stranded

Nominal insulation thickness(Phase)

mm 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6

Nominal cross sectional area(RNC)

mm² 16 25 35 50 70 95 120 150 185

Shape of Conductor(RNC) Circular Non-Compacted

Nominal insulation thickness(RNC)

mm 1.0 1.2 1.4 1.6 1.8 2.0

Nominal bedding thickness mm 1.0 1.2 1.4 1.6 1.8

Bedding dia. (approx) mm 20.1 22.3 25.7 29.6 34.0 37.1 41.2 46.1 51.9 57.9 64.8

Nominal of galvanized steel wire

mm 1.6 2.0 2.5 3.15

Nominal outer-sheath thickness

mm 1.8 1.9 2.0 2.2 2.3 2.4 2.5 2.7 2.9 3.1

Approx. overall dia. mm 27.8 29.6 33.1 38.0 43.7 49.0 52.0 57.2 63.7 69.8 71.8 78.6

Cable net weight (approx) kg/km 1,920 2,310 2,980 4,150 5,350 6,890 8,050 9,810 12,330 14,840 15,190 19,270

Nominal cross sectional area

mm² 25 35 50 70 95 120 150 185 240 300 400

Max. conductor resistance DC at 20°C(Phase)

Ω /km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0601 0.0470

Max. conductor resistance DC at 20°C(RNC)

Ω /km 1.15 1.15 0.727 0.524 0.387 0.268 0.268 0.193 0.153 0.124 0.0991 0.0991

FEC Cables (M) Sdn. Bhd.

1�

LOW VOLTAGE SPECIFICATION

Dimensional

Electrical Data

Copper Conductor, PVC Insulated, PVC Bedded, Zinc-Coated Steel Wire Armour, PVC Sheathed

3½ Core

600/1000 V MS 274 (BS 6346)

PVC Bedding

Armouring

PVC Outer Sheath

Copper (Phase)

PVC Insulation (Phase)

Filler

Binder Tape

Copper (RNC)PVC Insulation (RNC)

Note :- RNC = Reduced Neutral Conductor

No. of cores 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

Shape of Conductor Circular Stranded

Conductor dia. (approx.)

1.59

Nominal insulation thickness

mm 0.6

Nominal bedding thickness

mm 0.8

Bedding dia. (approx.) mm 10.2 11.1 12.0 12.9 14.0 14.5 14.8 15.3 15.7 16.1 16.6 17.0 17.6 17.9

Nominal of galvanized steel wire

mm 0.9 1.25

Nominal outer-sheath thickness

mm 1.4 1.5 1.6

Approx. overall dia. mm 14.4 15.3 16.4 18.0 19.1 19.6 20.1 20.6 21.0 21.4 21.9 22.3 22.9 23.2

Cable net weight (approx.)

kg/km 390 440 450 510 650 700 720 760 800 840 880 910 960 990 1,000 1,060 1,090

No. of cores 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 1.59

Nominal insulation thickness mm 0.6

Nominal bedding thickness mm 1.0

Bedding dia. (approx.) mm 18.9 19.3 20.4 20.9 21.1 21.7 23.4 24.3 26.9

Nominal of galvanized steel wire mm 1.6

Nominal outer-sheath thickness mm 1.7 1.8 1.9

Approx. overall dia. mm 25.1 25.5 26.6 27.1 27.4 27.9 29.8 30.7 33.5

Cable net weight (approx.) kg/km 1,300 1,350 1,400 1,430 1,450 1,490 1,510 1,540 1,580 1,810 1,930 2,230 2,270

LOW VOLTAGE CABLES

15

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, PVC Insulated, PVC Bedded, Zinc Coated Steel Wire Armour, PVC Sheathed Control

1.5 mm²

600/1000 V BS 6346 (MS 274)

PVC Outer Sheath

PVC Bedding

Armouring

Copper

PVC Insulation

Filler (If Necessary)

Binder Tape

Max. conductor resistance DC at 20°C = 12.10 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.01

Nominal insulation thickness mm 0.7

Nominal bedding thickness mm 0.8 1.0

Bedding dia. (approx.) mm 11.8 12.9 14.0 15.1 16.5 17.1 17.4 18.4 18.9 19.5 20.0 20.5 21.2 21.6

Nominal of galvanized steel wire mm 0.9 1.25 1.6

Nominal outer-sheath thickness mm 1.5 1.6 1.7 1.8

Approx. overall dia. mm 16.2 18.0 19.1 20.4 21.8 22.4 22.7 24.6 25.1 25.7 26.3 26.8 27.6 28.1

Cable net weight (approx.) kg/km 510 650 670 760 850 920 950 1,000 1,050 1,260 1,330 1,380 1,440 1,490 1,510 1,590 1,650

No. of cores 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.01

Nominal insulation thickness

mm 0.7

Nominal bedding thickness

mm 1.0 1.2

Bedding dia. (approx.) mm 22.3 22.7 24.1 24.4 24.7 25.0 25.6 27.8 29.3 32.3

Nominal of galvanized steel wire

mm 1.6 2.0

Nominal outer-sheath thickness

mm 1.8 1.9 2.0 2.1

Approx. overall dia. mm 28.7 29.2 30.6 30.6 31.1 31.6 32.3 34.4 36.9 40.2

Cable net weight (approx.)

kg/km 1,710 1,770 1,860 1,890 1,920 1,980 2,010 2,070 2,140 2,460 2,880 3,330 3,400

FEC Cables (M) Sdn. Bhd.

16

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, PVC Insulated, PVC Bedded,Zinc-Coated Steel Wire Armour, PVC Sheathed Control

2.5 mm²

600/1000 V BS 6346 (MS 274)

PVC Outer Sheath

PVC Bedding

Armouring

Copper

PVC Insulation

Filler (If Necessary)

Binder Tape

Electrical Data

Max. conductor resistance DC at 20°C = 7.41 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.55

Nominal insulation thickness

mm 0.8

Nominal bedding thickness

mm 0.8 1.0

Bedding dia. (approx.) mm 13.8 15.1 16.5 18.2 19.9 20.6 20.9 21.7 22.3 22.9 23.6 24.2 25.0 25.6

Nominal of galvanized steel wire

mm 1.25 1.6

Nominal outer-sheath thickness

mm 1.5 1.6 1.7 1.8 1.9 2.0

Approx. overall dia. mm 18.9 20.4 21.8 24.4 26.1 26.8 27.1 28.1 28.7 29.4 30.1 30.7 31.7 32.4

Cable net weight (approx.) kg/km 750 860 890 1,000 1,280 1,380 1,430 1,510 1,580 1,670 1,760 1,820 1,930 2,000 2,020 2,130 2,220

No. of cores 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.55

Nominal insulation thickness

mm 0.8

Nominal bedding thickness

mm 1.0 1.2

Bedding dia. (approx.) mm 26.4 26.9 28.6 29.0 29.7 30.0 30.8 33.3 34.7 38.4

Nominal of galvanized steel wire

mm 1.6 2.0

Nominal outer-sheath thickness

mm 2.0 2.1 2.1 2.2

Approx. overall dia. mm 33.2 33.7 35.4 36.6 37.3 37.7 38.4 41.2 42.5 46.4

Cable net weight (approx.) kg/km 2,320 2,410 2,510 2,560 2,880 2,960 3,010 3,100 3,180 3,660 3,900 4,540 4,640

LOW VOLTAGE CABLES

17

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, PVC Insulated, PVC Bedded,Zinc-Coated Steel Wire Armour, PVC Sheathed Control

4 mm²

600/1000 V BS 6346 (MS 274)

PVC Outer Sheath

PVC Bedding

Armouring

Copper

PVC Insulation

Filler (If Necessary)

Binder Tape

Max. conductor resistance DC at 20°C = 4.61 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

Nominal cross sectional area

mm² 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000

Shape of Conductor Cicular Compacted Shaped Stranded

Conductor dia. (approx.)

3.7 4.7 5.9 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3 32.76 37.05 41.6

Nominal insulation thickness

mm 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0

Nominal sheath thickness

mm 1.4 1.5 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.3 2.5

Approx. overall dia. mm 9.0 10.0 12.0 13.0 14.5 16.0 18.5 20.0 22.0 24.5 27.5 30.5 33.5 37.0 44.0 48.5 54.0

Cable net. weight (approx.)

kg/km 170 230 340 440 580 800 1,080 1,330 1,630 2,040 2,640 3,300 4,170 5,200 6,770 8,520 10,700

Nominal cross sectional area

mm² 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000

Max. conductor resistance DC at 20°C

Ω /km 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221 0.0176

Max. conductor resistance 50Hz at 70°C

Ω /km 2.19 1.38 0.870 0.627 0.463 0.321 0.232 0.184 0.150 0.120 0.0926 0.0748 0.0600 0.0486 0.0395 0.0333 0.0290

Reactance at 50Hz Ω /km 0.115 0.107 0.102 0.0967 0.0950 0.0903 0.0887 0.0860 0.0855 0.0850 0.0836 0.0831 0.0819 0.0807 0.0773 0.0757 0.0753

Current rating In air at 40°C

A 52 69 90 115 140 175 220 255 295 340 405 470 550 635 760 865 970

Current rating In the ground at 25°C

A 75 98 125 150 175 215 260 295 330 375 435 490 555 630 720 795 870

FEC Cables (M) Sdn. Bhd.

18

LOW VOLTAGE SPECIFICATION

Dimensional

1 Core

Electrical Data Electrical Data

Copper Conductor, PVC Insulated, PVC Sheathed

600/1000 V IEC 60502-1

Copper

PVC Insulation

PVC Sheath

Nominal cross sectional area mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Shape of Conductor Circular Stranded CC Shaped Stranded

Nominal insulation thickness mm 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6

Nominal sheath thickness mm 1.8 1.8 1.9 2.0 2.1 2.2 2.4 2.6 2.7 3.0

Approx. overall dia. mm 11.0 12.0 14.0 15.0 16.0 18.0 18.5 20.0 23.0 26.0 29.5 31.5 34.5 38.5 43.5 48.0 53.0

Cable net weight (approx.) kg/km 140 170 230 290 380 530 720 930 1,230 1,680 2,280 2,800 3,410 4,270 5,580 6,820 8,710

Nominal cross sectional area mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Max. conductor resistance DC at 20°C

Ω /km 12.10 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Max. conductor resistance 50Hz at 70°C

Ω /km 14.5 8.87 5.52 3.69 2.19 1.38 0.870 0.627 0.464 0.321 0.232 0.185 0.150 0.121 0.0931 0.0755 0.0610

Reactance at 50Hz Ω /km 0.107 0.0994 0.0983 0.0928 0.0886 0.0834 0.0879 0.0847 0.0851 0.0812 0.0805 0.0786 0.0788 0.0789 0.0780 0.0778 0.0772

Current rating In air at 40°C A 20 26 35 45 61 81 100 125 150 190 235 275 310 360 430 490 565

Current rating In the ground at 25°C

A 30 39 51 64 85 110 135 165 195 240 290 330 370 415 480 545 610

LOW VOLTAGE CABLES

19

LOW VOLTAGE SPECIFICATION

Dimensional

Electrical Data

Copper Conductor, PVC Insulated, PVC Sheathed

2 Core

600/1000 V IEC 60502-1

PVC Sheath

Copper

PVC Insulation

Filler

Binder Tape

Note : CC = Circular Compacted

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Shape of Conductor Circular Stranded CC Shaped Stranded

Nominal insulation thickness

mm 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6

Nominal sheath thickness

mm 1.8 1.8 2.0 2.1 2.2 2.3 2.5 2.7 2.9 3.1

Approx. overall dia. mm 11.5 12.5 14.5 16.0 17.0 19.0 21.0 23.0 26.0 29.5 34.0 36.5 39.5 44.5 50.5 55.5 61.5

Cable net weight (approx.)

kg/km 170 210 290 370 500 700 1,010 1,320 1,750 2,440 3,310 4,070 4,950 6,220 8,130 9,980 12,720

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Max. conductor resistance DC at 20°C

Ω /km 12.10 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Max. conductor resis-tance 50Hz at 70°C

Ω /km 14.5 8.87 5.52 3.69 2.19 1.38 0.870 0.627 0.463 0.321 0.232 0.184 0.150 0.121 0.0928 0.0751 0.0603

Reactance at 50Hz Ω /km 0.107 0.0994 0.0983 0.0928 0.0886 0.0834 0.0879 0.0847 0.0851 0.0812 0.0805 0.0786 0.0788 0.0789 0.0780 0.0778 0.0772

Current rating In air at 40°C

A 17 22 30 38 52 69 90 110 135 170 210 245 280 325 385 445 510

Current rating In the ground at 25°C

A 25 33 43 54 72 94 120 140 170 205 250 280 315 360 415 465 525

FEC Cables (M) Sdn. Bhd.

20

LOW VOLTAGE SPECIFICATION

Dimensional

Electrical Data Electrical Data

Copper Conductor, PVC Insulated, PVC Sheathed

3 Core

600/1000 V IEC 60502-1

PVC Sheath

Copper

PVC Insulation

Filler

Binder Tape

Note : CC = Circular Compacted

Nominal cross sectional area mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Shape of Conductor Circular Stranded CC Shaped Stranded

Nominal insulation thickness

mm 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6

Nominal sheath thickness mm 1.8 1.9 2.1 2.2 2.4 2.5 2.7 2.9 3.1 3.4

Approx. overall dia. mm 12.5 13.5 16.0 17.0 18.5 21.0 23.0 25.0 29.0 33.0 37.5 40.5 45.0 50.5 56.5 63.0 70.5

Cable net weight (approx.) kg/km 200 250 360 470 630 900 1,300 1,700 2,290 3,170 4,310 5,360 6,560 8,200 10,720 13,190 16,870

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Max. conductor resistance DC at 20°C

Ω /km 12.10 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Max. conductor resis-tance 50Hz at 70°C

Ω /km 14.5 8.87 5.52 3.69 2.19 1.38 0.870 0.627 0.463 0.321 0.232 0.184 0.150 0.121 0.0928 0.0751 0.0603

Reactance at 50Hz Ω /km 0.107 0.0994 0.0983 0.0928 0.0886 0.0834 0.0879 0.0847 0.0851 0.0812 0.0805 0.0786 0.0788 0.0789 0.0780 0.0778 0.0772

Current rating In air at 40°C

A 17 22 30 38 52 69 90 110 135 170 210 245 280 325 385 445 510

Current rating In the ground at 25°C

A 25 33 43 54 72 94 120 140 170 205 250 280 315 360 415 465 525

LOW VOLTAGE CABLES

21

LOW VOLTAGE SPECIFICATION

Dimensional

Electrical Data

Copper Conductor, PVC Insulated, PVC Sheathed

4 Core

600/1000 V IEC 60502-1

PVC Sheath

Copper

PVC Insulation

Filler

Binder Tape

Note : CC = Circular Compacted

Nominal cross sectional area(Phase) mm² 25 35 50 70 95 120 150 185 240 300 400

Shape of Conductor(Phase) Shaped Stranded

Nominal insulation thickness(Phase) mm 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 2.6

Nominal cross sectional area(RNC) mm² 16 16 25 35 50 70 70 95 120 150 185

Shape of Conductor(RNC) Circular Compacted

Nominal insulation thickness(RNC) mm 1.0 1.0 1.2 1.2 1.4 1.4 1.4 1.6 1.6 1.8 2.0

Nominal sheath thickness mm 1.8 1.8 1.9 2.0 2.2 2.3 2.4 2.6 2.8 3.0 3.2

Approx. overall dia. mm 22.5 24.5 28.5 32.0 37.0 39.5 44.0 49.5 55.0 62.0 68.5

Cable net weight (approx) kg/km 1,200 1,520 2,070 2,840 3,870 4,860 5,810 7,350 9,520 11,730 14,910

Nominal cross sectional area mm² 25 35 50 70 95 120 150 185 240 300 400

Max. conductor resistance DC at 20°C(Phase)

Ω /km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Max. conductor resistance DC at 20°C(RNC)

Ω /km 1.15 1.15 0.727 0.524 0.387 0.268 0.268 0.193 0.153 0.124 0.0991

FEC Cables (M) Sdn. Bhd.

22

LOW VOLTAGE SPECIFICATION

Dimensional

Electrical Data Electrical Data

Copper Conductor, PVC Insulated, PVC Sheathed

3½ Core

600/1000 V IEC 60502-1

PVC Sheath

Copper (Phase)

PVC Insulation (Phase)

Filler

Binder Tape

Copper (RNC)PVC Insulation (RNC)

Note : RNC = Reduced Neutral Conductor

Nominal cross sectional area mm² 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000

Shape of Conductor Cicular Compacted Shaped Stranded

Conductor dia. (approx.) 3.7 4.7 5.9 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3 32.76 37.05 41.6

Nominal insulation thickness mm 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0

Nominal inner covering thickness

mm 1.0 1.2 1.4

Inner covering dia. (approx.) mm 7.9 8.9 10.5 11.6 13.0 14.6 16.7 18.1 20.0 22.2 25.0 27.7 31.2 34.6 41.1 45.8 50.8

Nominal of hard-drawn Al wire

mm 1.0 1.25 1.6 2.0 2.5

Nominal outer-sheath thickness

mm 1.8 1.9 2.0 2.1 2.2 2.4 2.5 2.7

Approx. overall dia. mm 13.5 14.5 16.0 17.5 19.5 21.0 23.0 25.0 27.0 29.5 32.5 36.0 39.5 43.5 50.5 56.0 61.5

Cable net. weight (approx.) kg/km 280 360 480 600 790 1,020 1,330 1,640 1,960 2,380 3,020 3,800 4,750 5,850 7,580 9,580 11,900

Nominal cross sectional area

mm² 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000

Max. conductor resistance DC at 20°C

Ω /km 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221 0.0176

Max. conductor resistance 50Hz at 70°C

Ω /km 2.19 1.38 0.870 0.627 0.463 0.321 0.232 0.184 0.149 0.120 0.0921 0.0743 0.0593 0.0478 0.0387 0.0323 0.0279

Reactance at 50Hz Ω /km 0.141 0.130 0.123 0.116 0.113 0.107 0.103 0.101 0.0988 0.0967 0.0941 0.0939 0.0923 0.0902 0.0859 0.0849 0.0837

Current rating In air at 40°C

A 57 73 100 125 150 190 235 275 310 360 430 500 580 670 795 910 1020

Current rating In the ground at 25°C

A 80 105 135 155 180 220 265 300 335 380 440 500 570 645 735 820 900

LOW VOLTAGE CABLES

23

LOW VOLTAGE SPECIFICATION

Dimensional

1 Core

Electrical Data

Copper Conductor, PVC Insulated, PVC Inner Covering, Aluminium Wire Armour, Sheathed

600/1000 V IEC 60502-1

Armouring

Binder Tape

PVC Outer Sheath

PVC Insulation

Copper

PVC Inner Covering

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Shape of Conductor Circular Stranded CC Shaped Stranded

Nominal insulation thickness

mm 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6

Nominal inner covering thickness

mm 1.0 1.2 1.4 1.6

Inner covering dia. (approx.)

mm 8.7 9.6 11.5 12.6 13.8 15.8 16.3 17.7 20.5 23.1 26.9 28.9 31.7 35.7 40.1 44.7 49.1

Nominal of galvanized steel wire

mm 0.9 1.6 2.0 2.5

Nominal outer-sheath thickness

mm 1.8 1.9 2.0 2.2 2.3 2.4 2.6 2.8 2.9 3.2

Approx. overall dia. mm 14.0 15.0 17.0 18.0 19.0 21.0 23.0 24.5 27.5 31.0 35.5 37.5 40.5 46.0 50.5 55.5 60.5

Cable net weight (approx.)

kg/km 340 380 490 570 680 870 1,310 1,570 1,970 2,700 3,500 4,110 4,830 6,240 7,810 9,320 11,420

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Max. conductor resistance DC at 20°C

Ω /km 12.10 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Max. conductor resis-tance 50Hz at 70°C

Ω /km 14.48 8.87 5.52 3.69 2.19 1.38 0.870 0.627 0.464 0.321 0.232 0.185 0.150 0.121 0.0931 0.0755 0.0610

Reactance at 50Hz Ω /km 0.107 0.0994 0.0983 0.0928 0.0886 0.0834 0.0879 0.0847 0.0851 0.0812 0.0805 0.0786 0.0788 0.0789 0.0780 0.0788 0.0772

Current rating In air at 40°C

A 21 28 37 47 63 84 105 130 155 200 245 280 320 370 435 495 560

Current rating In the ground at 25°C

A 30 39 51 64 85 110 140 165 195 240 290 330 365 415 475 535 595

FEC Cables (M) Sdn. Bhd.

2�

LOW VOLTAGE SPECIFICATION

Dimensional

Electrical Data Electrical Data

Copper Conductor, PVC Insulated, PVC Inner Covering, Zinc-Coated Steel Wire Armour, PVC Sheathed

2 Core

600/1000 V IEC 60502-1

CopperPVC Insulation

Filler

PVC Inner Covering

Armouring

PVC Outer SheathBinder Tape

Note : CC = Circular Compacted

Nominal cross sectional area mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Shape of Conductor Circular Stranded CC Shaped Stranded

Nominal insulation thickness

mm 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6

Nominal inner covering thickness

mm 1.0 1.2 1.4 1.6

Inner covering dia. (approx.) mm 9.3 10.2 12.2 13.4 14.7 16.8 18.6 20.6 23.8 27.2 31.6 33.7 37.0 41.6 47.2 52.0 57.6

Nominal of galvanized steel wire

mm 0.9 1.6 2.0 2.5 3.15

Nominal outer-sheath thickness

mm 1.8 2.0 2.1 2.2 2.3 2.5 2.7 2.9 3.1 3.4

Approx. overall dia. mm 14.5 15.5 17.5 19.0 20.0 22.0 25.5 27.5 31.0 35.5 40.0 42.0 47.0 52.0 58.0 63.0 70.5

Cable net weight (approx.) kg/km 370 430 560 660 820 1,070 1,670 2,050 2,610 3,650 4,720 5,560 7,010 8,490 10,750 12,870 16,680

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Max. conductor resistance DC at 20°C

Ω /km 12.10 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Max. conductor resis-tance 50Hz at 70°C

Ω /km 14.48 8.87 5.52 3.69 2.19 1.38 0.870 0.627 0.463 0.321 0.232 0.185 0.150 0.121 0.0928 0.0751 0.0603

Reactance at 50Hz Ω /km 0.107 0.0994 0.0983 0.0928 0.0886 0.0834 0.0879 0.0847 0.0851 0.0812 0.0805 0.0786 0.0788 0.0789 0.0780 0.0778 0.0772

Current rating In air at 40°C

A 18 23 31 40 53 71 94 115 140 175 215 245 280 325 380 435 490

Current rating In the ground at 25°C

A 25 33 43 54 72 93 120 140 170 205 245 280 310 350 400 450 490

LOW VOLTAGE CABLES

25

LOW VOLTAGE SPECIFICATION

Dimensional

Electrical Data

Copper Conductor, PVC Insulated, PVC Inner Covering, Zinc-Coated Steel Wire Armour, PVC Sheathed

3 Core

600/1000 V IEC 60502-1

PVC Insulation

Filler

PVC Inner Covering

Armouring

PVC Outer Sheath

Copper

Binder Tape

Note : CC = Circular Compacted

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Shape of Conductor Circular Stranded CC Shaped Stranded

Nominal insulation thickness

mm 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6

Nominal inner covering thickness

mm 1.0 1.2 1.4 1.6 1.8

Inner covering dia. (approx.)

mm 10.1 11.2 13.4 14.8 16.2 18.6 20.4 22.7 26.6 30.1 34.6 37.8 42.0 47.3 52.9 59.0 66.0

Nominal of galvanized steel wire

mm 0.9 1.6 2.0 2.5 3.15 3.15

Nominal outer-sheath thickness

mm 1.8 1.9 2.1 2.2 2.4 2.5 2.7 2.9 3.1 3.3 3.6

Approx. overall dia. mm 15.5 16.5 19.0 20.0 21.5 25.5 27.0 29.5 34.5 38.5 44.5 47.5 52.5 58.0 64.0 72.0 79.5

Cable net weight (approx.)

kg/km 430 500 650 790 980 1,560 2,030 2,520 3,480 4,520 6,220 7,440 8,880 10,830 13,650 17,240 21,390

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Max. conductor resistance DC at 20°C

Ω /km 12.10 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Max. conductor resis-tance 50Hz at 70°C

Ω /km 14.48 8.87 5.52 3.69 2.19 1.38 0.870 0.627 0.463 0.321 0.232 0.184 0.150 0.121 0.0928 0.0751 0.0603

Reactance at 50Hz Ω /km 0.107 0.0994 0.0983 0.0928 0.0886 0.0834 0.0879 0.0847 0.0851 0.0812 0.0805 0.0786 0.0788 0.0789 0.0780 0.0778 0.0772

Current rating In air at 40°C

A 18 23 31 40 53 71 94 115 140 175 215 245 280 325 380 435 490

Current rating In the ground at 25°C

A 25 33 43 54 72 93 120 140 170 205 245 280 310 350 400 450 490

FEC Cables (M) Sdn. Bhd.

26

LOW VOLTAGE SPECIFICATION

Dimensional

Electrical Data Electrical Data

Copper Conductor, PVC Insulated, PVC Inner Covering, Zinc-Coated Steel Wire Armour, PVC Sheathed

4 Core

600/1000 V IEC 60502-1

PVC Inner Covering

Armouring

PVC Outer Sheath

CopperPVC Insulation

Filler

Binder Tape

Note : CC = Circular Compacted

Nominal cross sectional area(Phase) mm² 25 35 50 70 95 120 150 185 240 300 400

Shape of Conductor(Phase) Shaped Stranded

Nominal insulation thickness(Phase) mm 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 2.6

Nominal cross sectional area(RNC) mm² 16 16 25 35 50 70 70 95 120 150 185

Shape of Conductor(RNC) Circular Compacted

Nominal insulation thickness(RNC) mm 1.0 1.0 1.2 1.2 1.4 1.4 1.4 1.6 1.6 1.8 2.0

Nominal inner covering thickness mm 1.0 1.0 1.2 1.2 1.2 1.4 1.4 1.4 1.6 1.6 1.8

Inner covering dia. (approx) mm 20.1 22.3 26.1 29.6 34.0 37.1 41.2 46.1 51.9 57.9 64.8

Nominal of galvanized steel wire mm 1.6 1.6 2.0 2.0 2.0 2.5 2.5 2.5 2.5 2.5 3.15

Nominal outer-sheath thickness mm 1.8 1.9 2.0 2.1 2.3 2.5 2.6 2.7 2.9 3.1 3.4

Approx. overall dia. mm 27.0 29.5 34.0 37.5 42.5 47.0 51.5 56.5 62.5 69.0 77.5

Cable net weight (approx) kg/km 1,920 2,320 3,250 4,160 5,360 6,920 8,080 9,860 12,390 14,900 19,370

Nominal cross sectional area mm² 25 35 50 70 95 120 150 185 240 300 400

Max. conductor resistance DC at 20°C(Phase) Ω /km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Max. conductor resistance DC at 20°C(RNC) Ω /km 1.15 1.15 0.727 0.524 0.387 0.268 0.268 0.193 0.153 0.124 0.0991

LOW VOLTAGE CABLES

27

LOW VOLTAGE SPECIFICATION

Dimensional

Electrical Data

Copper Conductor, PVC Insulated, PVC Inner Covering, Zinc-Coated Steel Wire Armour, PVC Sheathed

3½ Core

600/1000 V IEC 60502-1

PVC Inner Covering

Armouring

PVC Outer Sheath

Copper (Phase)

PVC Insulation (Phase)

Filler

Binder Tape

Copper (RNC)PVC Insulation (RNC)

Note : RNC = Reduced Neutral Conductor

Nominal cross sectional area

mm² 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000

Shape of Conductor Cicular Compacted Circular Stranded

Conductor dia. (approx.) 3.7 4.7 5.9 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3 32.76 37.05 41.6

Nominal insulation thickness

mm 0.7 0.9 1.0 1.1 1.2 1.4 1.6 1.7 1.8 2.0 2.2 2.4 2.6 2.8

Nominal outer-sheath thickness

mm 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.2 2.3 2.4

Approx. overall dia. mm 8.5 9.5 11.0 12.5 13.5 15.5 17.5 19.0 21.0 23.0 26.0 28.5 32.0 35.5 43.0 48.0 53.0

Cable net. weight (approx.)

kg/km 150 210 310 410 540 750 1,020 1,270 1,560 1,930 2,510 3,120 3,970 4,980 6,510 8,260 10,350

Nominal cross sectional area

mm² 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000

Max. conductor resistance DC at 20°C

Ω /km 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221 0.0176

Max. conductor resis-tance 50Hz at 90°C

Ω /km 2.33 1.47 0.927 0.669 0.494 0.342 0.247 0.196 0.160 0.128 0.0988 0.0801 0.0643 0.0521 0.0428 0.0363 0.0317

Reactance at 50Hz Ω /km 0.110 0.102 0.0979 0.0934 0.0905 0.0870 0.0851 0.0837 0.0837 0.0826 0.0812 0.0801 0.0792 0.0785 0.0776 0.0759 0.0749

Current rating In air at 40°C

A 68 91 120 150 185 235 290 340 390 455 545 630 735 850 985 1150 1280

Current rating In the ground at 25°C

A 89 115 145 170 205 250 295 340 380 430 495 560 635 715 800 895 970

Short circuit current for 1 sec.

kA 1.52 2.41 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 72.1 90.8 115.2 143.9

FEC Cables (M) Sdn. Bhd.

28

LOW VOLTAGE SPECIFICATION

Dimensional

1 Core

Electrical Data Electrical Data

Copper Conductor, XLPE Insulated, PVC Sheathed

600/1000 V IEC 60502-1

Copper

XLPE Insulation

PVC Sheath

Core Identification : Neutral

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Shape of Conductor Circular Stranded CC Shaped Stranded

Conductor dia. (approx.) 1.59 2.01 2.55 3.12 3.7 4.7 4.5 5.2 6.1 7.4 8.7 9.7 10.7 12.0 13.8 15.4 17.2

Nominal insulation thickness

mm 0.7 0.9 1.0 1.1 1.2 1.4 1.6 1.7 1.8 2.0

Nominal sheath thickness mm 1.8 1.8 2.0 2.1 2.2 2.3 2.5 2.7 2.9

Approx. overall dia. mm 10.0 11.0 12.0 13.0 14.5 16.5 17.0 18.5 20.5 24.0 27.0 29.5 32.5 36.0 40.5 44.5 49.5

Cable net weight (approx.) kg/km 110 140 180 230 330 460 640 830 1,090 1,520 2,060 2,570 3,150 3,920 5,130 6,290 8,050

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Max. conductor resistance DC at 20°C

Ω /km 12.10 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Max. conductor resis-tance 50Hz at 90°C

Ω /km 15.43 9.45 5.88 3.93 2.33 1.47 0.927 0.669 0.494 0.342 0.247 0.196 0.160 0.128 0.0987 0.0798 0.0640

Reactance at 50Hz Ω /km 0.103 0.0961 0.0899 0.0853 0.0785 0.0771 0.0776 0.0752 0.0744 0.0731 0.0713 0.0713 0.0719 0.0720 0.0713 0.0707 0.0704

Current rating In air at 40°C

A 25 32 44 57 79 100 135 165 205 255 315 370 420 485 580 665 770

Current rating In the ground at 25°C

A 35 45 60 76 98 125 160 195 230 285 340 385 435 490 565 640 725

Short circuit current for 1 sec.

kA 0.255 0.409 0.636 0.935 1.52 2.41 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7

LOW VOLTAGE CABLES

29

LOW VOLTAGE SPECIFICATION

Dimensional

Electrical Data

Copper Conductor, XLPE Insulated, PVC Sheathed

2 Core

600/1000 V IEC 60502-1

PVC Sheath

XLPE Insulation

Copper

Filler

Binder Tape

Note : CC = Circular Compacted

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Shape of Conductor Circular Stranded CC Shaped Stranded

Conductor dia. (approx.) 1.59 2.01 2.55 3.12 3.7 4.7 5.2 6.2 7.2 8.7 10.4 11.4 12.4 14.1 16.2 18.0 20.3

Nominal insulation thickness

mm 0.7 0.9 1.0 1.1 1.2 1.4 1.6 1.7 1.8 2.0

Nominal outer-sheath thickness

mm 1.8 1.9 2.0 2.1 2.3 2.4 2.6 2.8 3.1

Approx. overall dia. mm 10.5 11.5 12.5 14.0 15.5 17.5 19.0 21.5 24.0 27.5 31.5 34.0 37.5 42.0 47.0 51.5 58.0

Cable net. weight (approx.)

kg/km 130 170 230 300 430 620 900 1,190 1,570 2,230 3,010 3,760 4,610 5,760 7,540 9,240 11,880

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Max. conductor resistance DC at 20°C

Ω /km 12.10 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Max. conductor resis-tance 50Hz at 90°C

Ω /km 15.43 9.45 5.88 3.93 2.33 1.47 0.927 0.669 0.494 0.343 0.248 0.197 0.160 0.129 0.0996 0.0809 0.0653

Reactance at 50Hz Ω /km 0.103 0.0961 0.0899 0.0853 0.0785 0.0771 0.0776 0.0752 0.0744 0.0731 0.0713 0.0713 0.0719 0.0720 0.0713 0.0707 0.0704

Current rating In air at 40°C

A 21 26 37 48 65 87 115 140 175 220 270 315 360 420 495 570 655

Current rating In the ground at 25°C

A 28 37 48 60 81 105 135 160 190 235 285 325 365 410 475 535 605

Short circuit current for 1 sec.

kA 0.255 0.409 0.636 0.935 1.52 2.41 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7

FEC Cables (M) Sdn. Bhd.

30

LOW VOLTAGE SPECIFICATION

Dimensional

Electrical Data Electrical Data

Copper Conductor, XLPE Insulated, PVC Sheathed

3 Core

600/1000 V IEC 60502-1

XLPE Insulation

PVC Sheath

Copper

Filler

Binder Tape

Note : CC = Circular Compacted

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Shape of Conductor Circular Stranded CC Shaped Stranded

Conductor dia. (approx.) 1.59 2.01 2.55 3.12 3.7 4.7 5.9 7.0 8.1 9.8 11.5 12.8 14.4 16.2 18.4 20.8 23.5

Nominal insulation thickness

mm 0.7 0.9 1.0 1.1 1.2 1.4 1.6 1.7 1.8 2.0

Nominal sheath thickness mm 1.8 1.8 1.9 2.0 2.1 2.3 2.4 2.6 2.8 3.0 3.3

Approx. overall dia. mm 11.5 12.5 13.5 15.0 17.0 19.5 21.0 23.5 26.5 30.5 34.5 38.0 42.5 47.5 53.0 59.0 66.5

Cable net. weight (approx.)

kg/km 160 210 280 380 550 800 1,160 1,550 2,060 2,910 3,940 4,970 6,090 7,620 9,980 12,250 15,740

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Max. conductor resistance DC at 20°C

Ω /km 12.10 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Max. conductor resis-tance 50Hz at 90°C

Ω /km 15.43 9.45 5.88 3.93 2.33 1.47 0.927 0.669 0.494 0.343 0.248 0.197 0.160 0.129 0.0996 0.0809 0.0653

Reactance at 50Hz Ω /km 0.103 0.0961 0.0899 0.0853 0.0785 0.0771 0.0776 0.0752 0.0744 0.0731 0.0713 0.0713 0.0719 0.0720 0.0713 0.0707 0.0704

Current rating In air at 40°C

A 21 26 37 48 65 87 115 140 175 220 270 315 360 420 495 570 655

Current rating In the ground at 25°C

A 28 37 48 60 81 105 135 160 190 235 285 325 365 410 475 535 605

Short circuit current for 1 sec.

kA 0.255 0.409 0.636 0.935 1.52 2.41 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7

LOW VOLTAGE CABLES

31

LOW VOLTAGE SPECIFICATION

Dimensional

Electrical Data

Copper Conductor, XLPE Insulated, PVC Sheathed

4 Core

600/1000 V IEC 60502-1

FillerPVC Sheath

Copper

XLPE Insulation

Binder Tape

Note : CC = Circular Compacted

Nominal cross sectional area(Phase)

mm² 25 35 50 70 95 120 150 185 240 300 400

Shape of Conductor(Phase) Shaped Stranded

Nominal insulation thickness(Phase)

mm 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0

Nominal cross sectional area(RNC)

mm² 16 16 25 35 50 70 70 95 120 150 185

Shape of Conductor(RNC) Circular Compacted

Nominal insulation thickness(RNC)

mm 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.1 1.2 1.4 1.6

Nominal sheath thickness mm 1.8 1.8 1.8 1.9 2.1 2.2 2.3 2.5 2.7 2.9 3.1

Approx. overall dia. mm 20.5 23.0 25.5 30.0 34.0 37.0 41.5 46.5 52.0 58.0 64.5

Cable net weight (approx) kg/km 1,080 1,380 1,850 2,600 3,530 4,500 5,380 6,810 8,870 10,890 13,910

Nominal cross sectional area mm² 25 35 50 70 95 120 150 185 240 300 400

Max. conductor resistance DC at 20°C(Phase)

Ω /km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Max. conductor resistance DC at 20°C(RNC)

Ω /km 1.15 1.15 0.727 0.524 0.387 0.268 0.268 0.193 0.153 0.124 0.0991

FEC Cables (M) Sdn. Bhd.

32

LOW VOLTAGE SPECIFICATION

Dimensional

Electrical Data

Copper Conductor, XLPE Insulated, PVC Sheathed

3½ Core

600/1000 V IEC 60502-1

PVC Sheath

Copper (Phase)

XLPE Insulation (Phase)

Filler

Binder Tape

Copper (RNC)

XLPE Insulation (RNC)

Note : RNC = Reduced Neutral Conductor

Nominal cross sectional area

mm² 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000

Shape of Conductor Circular Compacted Circular Stranded

Conductor dia. (approx.)

3.7 4.7 5.9 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3 32.76 37.05 41.6

Nominal insulation thickness

mm 0.7 0.7 0.9 1.0 1.1 1.2 1.4 1.6 1.7 1.8 2.0 2.2 2.4 2.6 2.8

Nominal inner cover-ing thickness

mm 1.0 1.2 1.4

Inner covering dia. (approx.)

mm 7.3 8.0 9.7 10.8 12.1 13.9 15.6 17.2 19.2 21.3 23.9 26.3 29.9 33.3 40.3 45.4 50.3

Nominal of hard-drawn Al wire

mm 1.0 1.6 2.0 2.5

Nominal outer-sheath thickness

mm 1.8 1.9 2.1 2.2 2.3 2.5 2.7

Approx. overall dia. mm 13.0 14.0 15.5 16.5 18.0 20.0 21.5 24.5 26.5 28.5 31.0 33.5 38.5 42.0 49.5 55.5 61.0

Cable net. weight (approx.)

kg/km 260 330 450 560 710 940 1,210 1,560 1,870 2,270 2,890 3,520 4,550 5,620 7,290 9,320 11,580

Nominal cross sectional area

mm² 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000

Max. conductor resistance DC at 20°C

Ω /km 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221 0.0176

Max. conductor resistance 50Hz at 90°C

Ω /km 2.33 1.47 0.927 0.668 0.494 0.342 0.247 0.196 0.159 0.128 0.0982 0.0793 0.0632 0.0509 0.0415 0.0347 0.0300

Reactance at 50Hz Ω /km 0.137 0.126 0.119 0.113 0.113 0.107 0.102 0.101 0.0999 0.0975 0.0946 0.0920 0.0923 0.0903 0.0878 0.0863 0.0847

Current rating In air at 40°C

A 77 100 135 165 200 255 310 365 415 480 570 650 760 870 995 1150 1250

Current rating In the ground at 25°C

A 90 115 150 170 205 250 300 340 385 435 500 565 635 715 800 890 940

Short circuit current for 1 sec.

kA 1.52 2.41 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 72.1 90.8 115.2 143.9

LOW VOLTAGE CABLES

33

LOW VOLTAGE SPECIFICATION

Dimensional

Electrical Data

Copper Conductor, XLPE Insulated, PVC Sheathed, PVC Bedded,Aluminium Wire Armour, PVC Sheathed

1 Core

600/1000 V IEC 60502-1

Armouring

Binder Tape

PVC Outer Sheath

XLPE Insulation

Copper

PVC Inner Covering

Core Identification : Neutral

Nominal cross sectional area mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Shape of Conductor Circular Stranded CC Shaped Stranded

Conductor dia. (approx.) 1.59 2.01 2.55 3.12 3.7 4.7 4.5 5.2 6.1 7.4 8.7 9.7 10.7 12.0 13.8 15.4 17.2

Nominal insulation thickness mm 0.7 0.9 1.0 1.1 1.2 1.4 1.6 1.7 1.8 2.0

Nominal inner covering thickness

mm 1.0 1.2 1.4 1.6

Inner covering dia. (approx.) mm 8.9 9.7 10.8 11.9 13.5 15.5 15.9 17.3 19.5 22.6 25.6 28.0 30.8 34.6 38.6 42.6 47.0

Nominal of galvanized steel wire

mm 0.9 1.25 1.6 2.0 2.5

Nominal outer-sheath thickness

mm 1.8 2.0 2.1 2.2 2.3 2.5 2.7 2.8 3.1

Approx. overall dia. mm 14.0 14.5 16.5 17.5 19.0 21.0 22.5 23.5 26.0 29.5 33.5 36.0 39.0 44.5 48.5 53.0 58.0

Cable net weight (approx.) kg/km 320 370 500 590 730 920 1,210 1,460 1,790 2,360 3,220 3,850 4,550 5,870 7,320 8,720 10,750

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Max. conductor resistance DC at 20°C

Ω /km 12.10 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Max. conductor resistance 50Hz at 90°C

Ω /km 15.43 9.45 5.88 3.93 2.33 1.47 0.927 0.669 0.494 0.342 0.247 0.196 0.160 0.128 0.0987 0.0798 0.0640

Reactance at 50Hz Ω /km 0.103 0.0961 0.0899 0.0853 0.0780 0.0767 0.0770 0.0746 0.0738 0.0726 0.0808 0.0709 0.0719 0.0720 0.0713 0.0707 0.0704

Current rating In air at 40°C A 29 38 45 58 79 105 140 170 210 260 320 370 425 485 575 650 745

Current rating In the ground at 25°C

A 33 45 59 75 98 125 160 195 230 280 335 380 425 480 555 620 695

Short circuit current for 1 sec.

kA 0.255 0.409 0.636 0.935 1.52 2.41 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7

FEC Cables (M) Sdn. Bhd.

3�

LOW VOLTAGE SPECIFICATION

Dimensional

Electrical Data

Copper Conductor, XLPE Insulated, PVC Sheathed, PVC Bedded,Zinc-Coated Steel Wire Armour, PVC Sheathed

2 Core

600/1000 V IEC 60502-1

PVC Inner Covering

Armouring

PVC Outer Sheath

CopperXLPE Insulation

FillerBinder Tape

Note : CC = Circular Compacted

Nominal cross sectional area mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Shape of Conductor Circular Stranded CC Shaped Stranded

Conductor dia. (approx.) 1.59 2.01 2.55 3.12 3.7 4.7 4.5 6.2 7.2 8.7 10.4 11.4 12.4 14.1 16.2 18.0 20.3

Nominal insulation thickness mm 0.7 0.9 1.0 1.1 1.2 1.4 1.6 1.7 1.8 2.0

Nominal inner covering thickness

mm 1.0 1.2 1.4 1.6

Inner covering dia. (approx.) mm 9.4 10.3 11.4 12.7 14.3 16.5 18.0 20.1 22.6 26.6 30.1 32.6 35.9 40.3 45.4 49.6 55.2

Nominal of galvanized steel wire

mm 0.9 1.25 1.6 2.0 2.5

Nominal outer-sheath thickness

mm 1.8 1.9 2.0 2.2 2.3 2.5 2.6 2.8 3.0 3.2

Approx. overall dia. mm 14.5 16.0 17.0 18.5 20.0 22.0 24.5 26.5 29.0 34.0 38.0 41.0 45.5 50.0 55.5 60.5 66.5

Cable net. weight (approx.) kg/km 360 480 570 680 860 1,110 1,550 1,920 2,400 3,420 4,390 5,230 6,640 8,020 10,140 12,080 15,020

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Max. conductor resistance DC at 20°C

Ω /km 12.10 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Max. conductor resis-tance 50Hz at 90°C

Ω /km 15.43 9.45 5.88 3.93 2.33 1.47 0.927 0.669 0.494 0.343 0.248 0.197 0.160 0.129 0.0996 0.0809 0.0653

Reactance at 50Hz Ω /km 0.103 0.0961 0.0899 0.0853 0.0780 0.0767 0.0770 0.0746 0.0738 0.0726 0.0808 0.0709 0.0719 0.0720 0.0713 0.0707 0.0704

Current rating In air at 40°C

A 21 27 38 49 65 89 120 145 175 225 275 315 365 420 490 555 635

Current rating In the ground at 25°C

A 28 37 48 60 81 105 135 160 190 235 280 320 355 405 465 515 580

Short circuit current for 1 sec.

kA 0.255 0.409 0.636 0.935 1.52 2.41 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7

LOW VOLTAGE CABLES

35

LOW VOLTAGE SPECIFICATION

Dimensional

Electrical Data

Copper Conductor, XLPE Insulated, PVC Bedded,Zinc-Coated Steel Wire Armour, PVC Sheathed

3 Core

600/1000 V IEC 60502-1

XLPE Insulation

PVC Inner Covering

Armouring

PVC Outer Sheath

Copper

FillerBinder Tape

Note : CC = Circular Compacted

Nominal cross sectional area mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Shape of Conductor Circular Stranded CC Shaped Stranded

Conductor dia. (approx.) 1.59 2.01 2.55 3.12 3.7 4.7 5.9 7.0 8.1 9.8 11.5 12.8 14.4 16.2 18.4 20.8 23.5

Nominal insulation thickness mm 0.7 0.9 1.0 1.1 1.2 1.4 1.6 1.7 1.8 2.0

Nominal inner covering thickness

mm 1.0 1.2 1.4 1.6 1.8

Inner covering dia. (approx.) mm 10.2 11.2 12.5 13.9 15.8 18.2 19.9 22.2 24.9 29.5 33.1 36.6 40.9 45.6 51.1 56.6 63.5

Nominal of galvanized steel wire

mm 0.9 1.25 1.6 2.0 2.5 3.15

Nominal outer-sheath thickness

mm 1.8 1.9 2.0 2.2 2.3 2.5 2.6 2.8 3.0 3.2 3.5

Approx. overall dia. mm 15 17.0 18.0 19.5 21.5 24.5 26.5 29.0 32.0 37.5 41.5 46.5 51.0 56.0 62.0 67.5 76.5

Cable net. weight (approx.) kg/km 400 540 660 790 1,010 1,460 1,890 2,360 2,970 4,270 5,450 7,010 8,400 10,180 12,900 15,470 20,230

Nominal cross sectional area

mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

Max. conductor resistance DC at 20°C

Ω /km 12.10 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Max. conductor resis-tance 50Hz at 90°C

Ω /km 15.43 9.45 5.88 3.93 2.33 1.47 0.927 0.669 0.494 0.343 0.248 0.197 0.160 0.129 0.0996 0.0809 0.0653

Reactance at 50Hz Ω /km 0.103 0.0961 0.0899 0.0853 0.0780 0.0767 0.0770 0.0746 0.0738 0.0726 0.0708 0.0709 0.0719 0.0720 0.0713 0.0707 0.0704

Current rating In air at 40°C

A 21 27 38 49 65 89 120 145 175 225 275 315 365 420 490 555 635

Current rating In the ground at 25°C

A 28 37 48 60 81 105 135 160 190 235 280 320 355 405 465 515 580

Short circuit current for 1 sec.

kA 0.255 0.409 0.636 0.935 1.52 2.41 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7

FEC Cables (M) Sdn. Bhd.

36

LOW VOLTAGE SPECIFICATION

Dimensional

Electrical Data

Copper Conductor, XLPE Insulated, PVC Bedded,Zinc-Coated Steel Wire Armour, PVC Sheathed

4 Core

600/1000 V IEC 60502-1

PVC Inner Covering

Armouring

PVC Outer Sheath

CopperXLPE Insulation

Filler

Binder Tape

Note : CC = Circular Compacted

Nominal cross sectional area(Phase) mm² 25 35 50 70 95 120 150 185 240 300 400

Shape of Conductor(Phase) Shaped Stranded

Nominal insulation thickness(Phase) mm 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0

Nominal cross sectional area(RNC) mm² 16 16 25 35 50 70 70 95 120 150 185

Shape of Conductor(RNC) Circular Compacted

Nominal insulation thickness(RNC) mm 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.1 1.2 1.4 1.6

Nominal inner covering thickness mm 1.0 1.0 1.0 1.2 1.2 1.2 1.4 1.4 1.6 1.6 1.6

Inner covering dia. (approx) mm 19.5 21.8 24.5 29.0 32.5 35.6 40.2 44.7 50.1 55.5 61.9

Nominal of galvanized steel wire mm 1.6 1.6 1.6 2.0 2.0 2.0 2.5 2.5 2.5 2.5 3.15

Nominal outer-sheath thickness mm 1.8 1.8 1.9 2.1 2.2 2.4 2.5 2.7 2.9 3.0 3.3

Approx. overall dia. mm 26.0 28.0 31.0 37.0 40.5 44.0 50.0 55.0 60.5 66.0 74.5

Cable net weight (approx) kg/km 1,810 2,190 2,770 3,970 5,030 6,170 7,720 9,390 11,800 14,080 18,290

Nominal cross sectional area mm² 25 35 50 70 95 120 150 185 240 300 400

Max. conductor resistance DC at 20°C(Phase)

Ω /km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Max. conductor resistance DC at 20°C(RNC)

Ω /km 1.15 1.15 0.727 0.524 0.387 0.268 0.268 0.193 0.153 0.124 0.0991

LOW VOLTAGE CABLES

37

LOW VOLTAGE SPECIFICATION

Dimensional

Electrical Data

Copper Conductor, XLPE Insulated, PVC Inner Covering,Zinc-Coated Steel Wire Armour, PVC Sheathed

3½ Core

600/1000 V IEC 60502-1

PVC Inner Covering

Armouring

PVC Outer Sheath

Copper (Phase)

XLPE Insulation (Phase)

Filler

Binder Tape

Copper (RNC)XLPE Insulation (RNC)

Note : RNC = Reduced Neutral Conductor

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 1.59

Nominal insulation thickness

mm 0.8

Nominal sheath thickness mm 1.8

Approx. overall dia. mm 11.0 11.5 12.5 13.5 14.5 15.5 16.5 18.0 18.5 19.5 20.0 21.0

Cable net weight (approx.)

kg/km 140 170 200 240 270 280 330 370 400 420 450 480 510 550 570 610 630

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 1.59

Nominal insulation thickness mm 0.8

Nominal sheath thickness mm 1.8 1.9

Approx. overall dia. mm 21.0 22.0 22.5 23.0 23.5 24.5 25.0 25.5 26.0 28.0 29.0 32.0

Cable net weight (approx.) kg/km 650 690 710 750 790 810 840 860 890 910 950 970 1,160 1,250 1,500 1,550

FEC Cables (M) Sdn. Bhd.

38

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, PVC Insulated, PVC Sheathed Control

1.5 mm²

600/1000 V IEC 60502-1

PVC Sheath

Copper

PVC Insulation

Filler (If Necessary)

Binder Tape

Max. conductor resistance DC at 20°C = 12.10 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.01

Nominal insulation thickness

mm 0.8

Nominal sheath thickness mm 1.8

Approx. overall dia. mm 12.0 12.5 13.5 14.5 15.5 17.0 18.0 19.5 20.0 20.5 21.0 21.5 22.0 23.0 23.5

Cable net weight (approx.) kg/km 170 210 250 300 350 370 430 490 520 560 600 640 680 730 760 810 850

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.)

2.01

Nominal insulation thickness

mm 0.8

Nominal sheath thickness

mm 1.8 1.9 1.9 2.0

Approx. overall dia. mm 23.5 24.0 24.5 25.0 25.5 27.0 27.5 28.0 28.5 31.5 32.5 36.0

Cable net weight (approx.)

kg/km 870 920 960 1,010 1,060 1,090 1,120 1,160 1,200 1,240 1,280 1,320 1,600 1,730 2,060 2,130

LOW VOLTAGE CABLES

39

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, PVC Insulated, PVC Sheathed Control

2.5 mm²

600/1000 V IEC 60502-1

PVC Sheath

Copper

PVC Insulation

Filler (If Necessary)

Binder Tape

Max. conductor resistance DC at 20°C = 7.41 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor Circular Stranded

Conductor dia. (approx.)

2.55

Nominal insulation thickness

mm 1.0

Nominal sheath thickness

mm 1.8

Approx. overall dia. mm 14.0 14.5 16.0 17.0 18.5 20.0 21.5 23.5 24.0 24.5 25.5 26.0 26.5 27.5 28.0

Cable net weight (approx.)

kg/km 230 290 360 440 510 540 630 720 770 830 890 950 1,010 1,090 1,140 1,220 1,270

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.)

2.55

Nominal insulation thickness

mm 1.0

Nominal sheath thickness

mm 1.8 1.9 2.0 2.1 2.3

Approx. overall dia. mm 28.0 29.0 29.5 30.5 31.5 33.0 34.0 34.5 35.5 38.0 39.5 44.0

Cable net weight (approx.)

kg/km 1,300 1,390 1,450 1,540 1,620 1,670 1,720 1,780 1,860 1,910 1,980 2,040 2,460 2,670 3,200 3,310

FEC Cables (M) Sdn. Bhd.

�0

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, PVC Insulated, PVC Sheathed Control

4 mm²

600/1000 V IEC 60502-1

PVC Sheath

Copper

PVC Insulation

Filler (If Necessary)

Binder Tape

Max. conductor resistance DC at 20°C = 4.61 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor Circular Stranded

Conductor dia. (approx.)

1.59

Nominal insulation thickness

mm 0.8

Nominal sheath thickness

mm 1.8

Approx. overall dia. mm 11.5 12.0 13.0 14.0 15.0 16.0 17.0 18.5 19.0 19.5 20.0 20.5 21.0 21.5

Cable net weight (approx.)

kg/km 170 200 230 270 310 330 370 420 450 480 510 540 570 610 630 680 700

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 1.59

Nominal insulation thickness

mm 0.8

Nominal sheath thickness

mm 1.8 1.9 2.0

Approx. overall dia. mm 21.5 22.5 23.5 24.0 25.0 25.5 26.0 26.5 29.0 30.0 33.0

Cable net weight (approx.)

kg/km 710 760 780 820 860 890 910 940 970 990 1,030 1,060 1,270 1,360 1,620 1,670

LOW VOLTAGE CABLES

�1

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, PVC Insulated, PVC Sheathed (Screened-CU Tape) Control

1.5 mm²

600/1000 V IEC 60502-1

PVC Sheath

Copper

PVC Insulation

Filler (If Necessary)

Binder Tape

Screening

Binder Tape

Max. conductor resistance DC at 20°C = 12.10 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor Circular Stranded

Conductor dia. (approx.)

2.01

Nominal insulation thickness

mm 0.8

Nominal sheath thickness

mm 1.8

Approx. overall dia. mm 12.5 13.0 14.0 15.0 16.0 17.5 18.5 20.0 20.5 21.0 21.5 22.0 22.5 23.5 24.0

Cable net weight (approx.)

kg/km 200 240 290 340 400 410 480 540 580 620 660 700 740 790 830 890 920

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.01

Nominal insulation thickness mm 0.8

Nominal sheath thickness mm 1.8 1.9 2.0 2.1 2.2

Approx. overall dia. mm 24.0 24.5 25.0 25.5 26.0 27.5 28.5 29.0 29.5 32.0 33.0 36.5

Cable net weight (approx.) kg/km 940 1,000 1,030 1,090 1,140 1,170 1,210 1,250 1,310 1,340 1,390 1,430 1,710 1,840 2,190 2,280

FEC Cables (M) Sdn. Bhd.

�2

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, PVC Insulated, PVC Sheathed (Screened-CU Tape) Control

2.5 mm²

600/1000 V IEC 60502-1

PVC Sheath

Copper

PVC Insulation

Filler (If Necessary)

Binder Tape

Screening

Binder Tape

Max. conductor resistance DC at 20°C = 7.41 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor Circular Stranded

Conductor dia. (approx.)

2.55

Nominal insulation thickness

mm 1.0

Nominal sheath thickness

mm 1.8 1.9

Approx. overall dia. mm 14.0 15.0 16.0 17.5 19.0 20.5 22.0 23.5 24.5 25.0 25.5 26.5 27.0 28.0 29.0

Cable net weight (approx.)

kg/km 270 330 410 490 570 600 690 790 840 900 960 1,030 1,090 1,170 1,230 1,330 1,380

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.55

Nominal insulation thickness

mm 1.0

Nominal sheath thickness

mm 1.9 2.0 2.1 2.2 2.3 2.4

Approx. overall dia. mm 29.0 29.5 30.0 31.5 32.0 33.5 34.5 35.0 36.0 39.0 40.5 45.0

Cable net weight (approx.)

kg/km 1,410 1,500 1,560 1,660 1,730 1,790 1,840 1,900 1,980 2,040 2,110 2,170 2,600 2,830 3,370 3,480

LOW VOLTAGE CABLES

�3

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, PVC Insulated, PVC Sheathed (Screened-CU Tape) Control

4 mm²

600/1000 V IEC 60502-1

PVC Sheath

Copper

PVC Insulation

Filler (If Necessary)

Binder Tape

Screening

Binder Tape

Max. conductor resistance DC at 20°C = 4.61 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 1.59

Nominal insulation thickness

mm 0.8

Nominal inner covering thickness

mm 1.0

Inner covering dia. (approx.)

mm 8.7 9.3 10.1 11.1 12.1 13.2 14.2 15.5 16.0 16.3 16.9 17.4 17.9 18.4 18.9

Nominal of galvanized steel wire

mm 0.9 1.6

Nominal outer-sheath thickness

mm 1.8

Approx. overall dia. mm 14.0 14.5 15.5 16.5 17.5 18.5 19.5 21.0 21.5 22.5 23.0 25.0 25.5

Cable net weight (approx.)

kg/km 340 370 430 480 540 550 610 680 730 760 800 830 870 920 950 1,270 1,310

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 1.59

Nominal insulation thickness mm 0.8

Nominal inner covering thickness mm 1.0

Inner covering dia. (approx.) mm 18.9 19.5 19.9 20.6 21.0 22.3 22.8 23.1 23.7 25.7 26.7 29.6

Nominal of galvanized steel wire mm 1.6 2.0

Nominal outer-sheath thickness mm 1.8 1.9 2.0

Approx. overall dia. mm 25.5 26.5 27.5 29.0 29.5 30.0 30.5 32.5 33.5 37.5

Cable net weight (approx.) kg/km 1,320 1,380 1,430 1,480 1,530 1,590 1,620 1,640 1,690 1,720 1,760 1,810 2,080 2,210 2,790 2,840

FEC Cables (M) Sdn. Bhd.

��

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, PVC Insulated, PVC Inner Covering, Zinc-Coated Steel Wire Armour, PVC Sheathed Control

1.5 mm²

600/1000 V IEC 60502-1

PVC Outer Sheath

PVC Inner Covering

Armouring

Copper

PVC Insulation

Filler (If Necessary)

Binder Tape

Max. conductor resistance DC at 20°C = 12.10 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.01

Nominal insulation thickness mm 0.8

Nominal inner covering thickness

mm 1.0

Inner covering dia. (approx.) mm 9.6 10.2 11.2 12.2 13.4 13.4 14.5 15.7 17.2 17.8 18.1 18.8 19.3 19.9 20.5 21.0

Nominal of galvanized steel wire

mm 0.9 1.6

Nominal outer-sheath thickness

mm 1.8

Approx. overall dia. mm 15.0 15.5 16.5 17.5 18.5 20.0 21.0 22.5 23.0 25.0 25.5 26.0 26.5 27.0 27.5

Cable net weight (approx.) kg/km 380 430 500 570 640 660 740 830 890 920 980 1,280 1,360 1,420 1,470 1,550 1,590

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.01

Nominal insulation thickness mm 0.8

Nominal inner covering thickness

mm 1.0

Inner covering dia. (approx.) mm 21.0 21.7 22.2 22.9 23.3 24.8 25.4 25.7 26.4 28.6 29.8 33.4

Nominal of galvanized steel wire

mm 1.6 2.0

Nominal outer-sheath thickness

mm 1.8 1.9 2.0 2.1 2.2

Approx. overall dia. mm 27.5 28.5 29.0 29.5 30.0 32.0 32.5 33.5 36.0 37.5 41.5 42.0

Cable net weight (approx.) kg/km 1,610 1,690 1,740 1,810 1,870 1,970 2,010 2,050 2,100 2,140 2,200 2,250 2,600 3,010 3,540 3,630

LOW VOLTAGE CABLES

�5

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, PVC Insulated, PVC Inner Covering, Zinc-Coated Steel Wire Armour, PVC Sheathed Control

2.5 mm²

600/1000 V IEC 60502-1

PVC Outer Sheath

PVC Inner Covering

Armouring

Copper

PVC Insulation

Filler (If Necessary)

Binder Tape

Max. conductor resistance DC at 20°C = 7.41 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.55

Nominal insulation thickness mm 1.0

Nominal inner covering thickness mm 1.0

Inner covering dia. (approx.) mm 11.5 12.2 13.4 14.8 16.2 17.6 19.1 21.0 21.7 22.1 22.9 23.6 24.3 25.1 25.7

Nominal of galvanized steel wire mm 0.9 1.6

Nominal outer-sheath thickness mm 1.8 1.9

Approx. overall dia. mm 17.0 17.5 19.0 20.0 21.5 24.5 26.0 27.5 28.5 29.0 29.5 30.5 31.0 32.0 32.5

Cable net weight (approx.) kg/km 490 560 650 760 860 890 1,270 1,400 1,520 1,570 1,650 1,740 1,810 1,920 1,990 2,110 2,190

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.55

Nominal insulation thickness mm 1.0

Nominal inner covering thickness

mm 1.0 1.2 1.4

Inner covering dia. (approx.) mm 25.7 26.5 27.1 28.1 28.6 30.9 31.6 32.0 32.8 35.6 37.0 41.5

Nominal of galvanized steel wire mm 1.6 2.0 2.5

Nominal outer-sheath thickness mm 1.9 2.0 2.1 2.2 2.3 2.4

Approx. overall dia. mm 32.5 33.5 34.0 36.0 36.5 39.0 39.5 40.0 41.0 44.0 45.5 51.0

Cable net weight (approx.) kg/km 2,220 2,330 2,400 2,780 2,850 3,050 3,110 3,170 3,260 3,310 3,380 3,490 4,030 4,310 5,460 5,580

FEC Cables (M) Sdn. Bhd.

�6

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, PVC Insulated, PVC Inner Covering, Zinc-Coated Steel Wire Armour, PVC Sheathed Control

4 mm²

600/1000 V IEC 60502-1

PVC Outer Sheath

PVC Inner Covering

Armouring

Copper

PVC Insulation

Filler (If Necessary)

Binder Tape

Max. conductor resistance DC at 20°C = 4.61 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 1.59

Nominal insulation thickness mm 0.8

Nominal inner covering thickness mm 1.0

Inner covering dia. (approx.) mm 9.2 9.7 10.6 11.5 12.6 12.6 13.6 14.6 16.0 16.0 16.5 16.8 17.4 17.8 18.3 18.9 19.3

Nominal of galvanized steel wire mm 0.9 1.6

Nominal outer-sheath thickness mm 1.8

Approx. overall dia. mm 14.5 15.0 16.0 17.0 18.0 19.0 20.0 21.5 23.0 23.5 24.0 24.5 25.0 25.5 26.0

Cable net weight (approx.) kg/km 370 420 470 530 590 600 670 740 800 820 1,100 1,150 1,190 1,250 1,290 1,350 1,390

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 1.59

Nominal insulation thickness mm 0.8

Nominal inner covering thickness mm 1.0 1.2

Inner covering dia. (approx.) mm 19.3 20.0 20.4 21.0 21.4 22.7 22.7 22.7 23.3 23.3 23.6 24.1 26.1 27.6 30.4

Nominal of galvanized steel wire mm 1.6 2.0

Nominal outer-sheath thickness mm 1.8 1.9 2.0 2.1 2.2

Approx. overall dia. mm 26.0 26.5 27.0 28.0 29.5 30.0 30.5 31.0 34.0 35.5 39.0

Cable net weight (approx.) kg/km 1,410 1,470 1,510 1,570 1,620 1,700 1,730 1,750 1,800 1,820 1,870 1,920 2,420 2,610 2,980 3,030

LOW VOLTAGE CABLES

�7

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, PVC Insulated, PVC Inner Covering, Zinc-Coated Steel Wire Armour, PVC Sheathed (Screened-CU Tape) Control

1.5 mm²

600/1000 V IEC 60502-1

PVC Outer Sheath

Copper

PVC Insulation

Filler (If Necessary)

Binder Tape

PVC Inner Covering

Binder Tape

Amouring

Screening

Max. conductor resistance DC at 20°C = 12.10 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.01

Nominal insulation thickness mm 0.8

Nominal inner covering thickness

mm 1.0

Inner covering dia. (approx.) mm 10.0 10.6 11.6 12.7 13.8 15.0 16.2 17.6 18.2 18.5 19.2 19.7 20.3 20.9 21.4

Nominal of galvanized steel wire

mm 0.9 1.6

Nominal outer-sheath thickness mm 1.8

Approx. overall dia. mm 15.5 16.0 17.0 18.0 19.0 20.5 23.0 24.5 25.0 25.5 26.0 26.5 27.0 27.5 28.0

Cable net weight (approx.) kg/km 430 480 550 620 700 720 800 1,130 1,220 1,260 1,320 1,360 1,440 1,510 1,560 1,630 1,680

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.01

Nominal insulation thickness mm 0.8

Nominal inner covering thickness

mm 1.0 1.2

Inner covering dia. (approx.) mm 21.4 22.1 22.6 23.3 23.8 25.3 25.8 26.1 26.8 29.5 30.6 33.9

Nominal of galvanized steel wire mm 1.6 2.0

Nominal outer-sheath thickness mm 1.8 1.9 1.9 2.0 2.1 2.2 2.3

Approx. overall dia. mm 28.0 29.0 29.5 30.5 32.5 33.0 34.0 35.0 37.5 39.0 42.5

Cable net weight (approx.) kg/km 1,700 1,790 1,850 1,920 1,990 2,090 2,130 2,160 2,220 2,470 2,540 2,600 3,030 3,210 3,690 3,760

FEC Cables (M) Sdn. Bhd.

�8

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, PVC Insulated, PVC Inner Covering, Zinc-Coated Steel Wire Armour, PVC Sheathed (Screened-CU Tape) Control

2.5 mm²

600/1000 V IEC 60502-1

PVC Outer Sheath

Copper

PVC Insulation

Filler (If Necessary)

Binder Tape

PVC Inner Covering

Binder Tape

Amouring

Screening

Max. conductor resistance DC at 20°C = 7.41 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.55

Nominal insulation thickness mm 1.0

Nominal inner covering thickness mm 1.0

Inner covering dia. (approx.) mm 11.9 12.6 13.9 15.2 16.6 18.1 19.6 21.4 22.1 22.5 23.4 24.0 24.7 25.5 26.1

Nominal of galvanized steel wire mm 0.9 1.6

Nominal outer-sheath thickness mm 1.8 1.9 2.0

Approx. overall dia. mm 17.0 18.0 19.0 20.5 23.5 25.0 26.5 28.0 29.0 29.5 30.5 31.0 31.5 32.5 33.5

Cable net weight (approx.) kg/km 530 610 710 810 1,170 1,200 1,330 1,480 1,610 1,660 1,740 1,840 1,920 2,020 2,110 2,230 2,310

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.55

Nominal insulation thickness

mm 1.0

Nominal inner covering thickness

mm 1.0 1.2 1.4

Inner covering dia. (approx.)

mm 26.1 27.4 28.0 28.9 29.5 31.3 32.0 32.0 32.4 33.3 36.0 37.9 41.9

Nominal of galvanized steel wire

mm 1.6 2.0 2.5 2.5

Nominal outer-sheath thickness

mm 2.0 2.1 2.2 2.3 2.4 2.6

Approx. overall dia. mm 33.5 35.5 36.0 37.0 37.5 39.5 40.5 41.0 41.5 44.5 47.5 52.0

Cable net weight (approx.)

kg/km 2,340 2,750 2,810 2,950 3,050 3,180 3,240 3,290 3,410 3,470 3,540 3,630 4,200 4,920 5,680 5,800

LOW VOLTAGE CABLES

�9

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, PVC Insulated, PVC Inner Covering, Zinc-Coated Steel Wire Armour, PVC Sheathed (Screened-CU Tape) Control

4 mm²

600/1000 V IEC 60502-1

PVC Outer Sheath

Copper

PVC Insulation

Filler (If Necessary)

Binder Tape

PVC Inner Covering

Binder Tape

Amouring

Screening

Max. conductor resistance DC at 20°C = 4.61 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 1.59

Nominal insulation thickness mm 0.7

Nominal sheath thickness mm 1.8

Approx. overall dia. mm 10.5 11.0 12.0 13.0 14.0 15.0 16.0 17.0 17.5 18.0 18.5 19.0 19.5 20.0 20.5

Cable net weight (approx.) kg/km 130 150 180 210 240 250 280 320 340 360 390 410 430 460 490 520 540

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 1.59

Nominal insulation thickness mm 0.7

Nominal sheath thickness mm 1.8

Approx. overall dia. mm 20.5 21.0 21.5 22.0 22.5 23.5 24.0 24.5 25.0 26.5 27.5 30.5

Cable net weight (approx.) kg/km 540 580 600 630 660 680 700 720 750 770 790 820 960 1,040 1,230 1,270

FEC Cables (M) Sdn. Bhd.

50

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, XLPE Insulated, PVC Sheathed Control

1.5 mm²

600/1000 V IEC 60502-1

PVC Sheath

Copper

XLPE Insulation

Filler (If Necessary)

Binder Tape

Max. conductor resistance DC at 20°C = 12.10 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.01

Nominal insulation thickness

mm 0.7

Nominal sheath thickness mm 1.8

Approx. overall dia. mm 11.5 12.0 13.0 14.0 15.0 16.5 17.5 19.0 19.5 20.0 20.5 21.0 21.5 22.0 22.5

Cable net weight (approx.) kg/km 160 190 230 270 310 330 370 420 460 490 520 560 590 630 660 700 730

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.01

Nominal insulation thickness

mm 0.7

Nominal sheath thickness mm 1.8 1.9

Approx. overall dia. mm 22.5 23.0 23.5 24.0 24.5 26.0 26.5 27.0 27.5 30.0 31.0 34.0

Cable net weight (approx.) kg/km 750 790 820 860 900 940 970 1,000 1,030 1,060 1,090 1,130 1,350 1,450 1,740 1,800

LOW VOLTAGE CABLES

51

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, XLPE Insulated, PVC Sheathed Control

2.5 mm²

600/1000 V IEC 60502-1

PVC Sheath

Copper

XLPE Insulation

Filler (If Necessary)

Binder Tape

Max. conductor resistance DC at 20°C = 7.41 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.55

Nominal insulation thickness

mm 0.7

Nominal sheath thickness

mm 1.8

Approx. overall dia. mm 12.5 13.0 14.0 15.5 16.5 18.0 19.0 21.0 21.5 22.0 22.5 23.0 23.5 24.5 25.0

Cable net weight (approx.)

kg/km 200 250 300 360 420 450 510 580 630 680 720 780 830 880 930 990 1,040

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.)

2.55

Nominal insulation thickness

mm 0.7

Nominal sheath thickness

mm 1.8 1.8 1.8 1.8 1.8 1.9 2.1

Approx. overall dia. mm 25.0 25.5 26.0 27.0 27.5 29.0 30.0 31.0 33.5 35.0 38.5

Cable net weight (approx.)

kg/km 1,060 1,120 1,170 1,230 1,280 1,340 1,380 1,430 1,470 1,520 1,570 1,620 1,960 2,120 2,550 2,640

FEC Cables (M) Sdn. Bhd.

52

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, XLPE Insulated, PVC Sheathed Control

4 mm²

600/1000 V IEC 60502-1

PVC Sheath

Copper

XLPE Insulation

Filler (If Necessary)

Binder Tape

Max. conductor resistance DC at 20°C = 4.61 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 1.59

Nominal insulation thickness

mm 0.7

Nominal sheath thickness

mm 1.8

Approx. overall dia. mm 10.5 11.0 12.0 13.0 14.0 15.0 16.0 17.0 17.5 18.5 19.0 19.5 20.0 20.5

Cable net weight (approx.)

kg/km 150 170 200 240 270 280 320 360 390 410 430 460 480 510 540 570 590

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 1.59

Nominal insulation thickness

mm 0.7

Nominal sheath thickness

mm 1.8

Approx. overall dia. mm 20.5 21.0 22.0 23.5 24.0 25.0 26.5 27.5 30.5

Cable net weight (approx.)

kg/km 600 630 660 690 720 750 770 790 810 830 860 880 1,040 1,120 1,310 1,350

LOW VOLTAGE CABLES

53

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, XLPE Insulated, PVC Sheathed (Screened-CU Tape) Control

1.5 mm²

600/1000 V IEC 60502-1

PVC Sheath

Copper

XLPE Insulation

Filler (If Necessary)

Binder Tape

Screening

Binder Tape

Max. conductor resistance DC at 20°C = 12.10 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor Circular Stranded

Conductor dia. (approx.)

2.01

Nominal insulation thickness

mm 0.7

Nominal sheath thickness

mm 1.8

Approx. overall dia. mm 11.5 12.0 13.0 14.0 15.0 16.5 17.5 19.0 19.5 20.5 20.5 21.5 22.0 22.5

Cable net weight (approx.)

kg/km 180 210 260 300 350 360 410 470 510 540 570 610 640 680 720 760 790

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.01

Nominal insulation thickness

mm 0.7

Nominal sheath thickness

mm 1.8 1.9

Approx. overall dia. mm 22.5 23.0 23.5 24.0 24.5 26.0 26.5 27.0 27.5 29.5 30.5 34.0

Cable net weight (approx.)

kg/km 810 850 890 930 970 1,010 1,040 1,070 1,100 1,130 1,170 1,200 1,430 1,540 1,840 1,890

FEC Cables (M) Sdn. Bhd.

5�

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, XLPE Insulated, PVC Sheathed (Screened-CU Tape) Control

2.5 mm²

600/1000 V IEC 60502-1

PVC Sheath

Binder Tape

Screening

Binder Tape

Copper

XLPE Insulation

Filler (If Necessary)

Max. conductor resistance DC at 20°C = 7.41 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor Circular Stranded

Conductor dia. (approx.)

2.55

Nominal insulation thickness

mm 0.7

Nominal sheath thickness

mm 1.8

Approx. overall dia. mm 12.5 13.0 14.5 15.5 16.5 18.0 19.5 21.0 21.5 22.0 22.5 23.0 24.0 24.5 25.0

Cable net weight (approx.)

kg/km 230 280 340 400 470 490 560 630 690 740 790 840 890 950 1,000 1,060 1,110

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.55

Nominal insulation thickness

mm 0.7

Nominal sheath thickness

mm 1.8 1.9 2.0 2.1

Approx. overall dia. mm 25.0 26.0 26.5 27.0 27.5 29.0 30.0 30.5 31.0 33.5 35.0 39.0

Cable net weight (approx.)

kg/km 1,130 1,200 1,250 1,310 1,370 1,420 1,470 1,510 1,560 1,620 1,680 1,730 2,060 2,240 2,670 2,760

LOW VOLTAGE CABLES

55

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, XLPE Insulated, PVC Sheathed (Screened-CU Tape) Control

4 mm²

600/1000 V IEC 60502-1

PVC Sheath

Binder Tape

Screening

Binder Tape

Copper

Filler (If Necessary)

XLPE Insulation

Max. conductor resistance DC at 20°C = 4.61 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 1.59

Nominal insulation thickness mm 0.7

Nominal inner covering thickness mm 1.0

Inner covering dia. (approx.) mm 9.0 9.5 10.3 11.2 12.2 13.1 14.1 15.3 15.8 16.1 16.7 17.1 17.6 18.1 18.5

Nominal of galvanized steel wire mm 0.9 1.25

Nominal outer-sheath thickness mm 1.8

Approx. overall dia. mm 14.0 14.5 15.5 16.0 17.0 19.0 20.0 21.0 21.5 22.0 22.5 23.0 23.5 24.0 24.5

Cable net weight (approx.) kg/km 350 380 420 470 520 530 680 750 800 820 860 890 920 960 1,000 1,050 1,080

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 1.59

Nominal insulation thickness mm 0.7

Nominal inner covering thickness

mm 1.0

Inner covering dia. (approx.) mm 18.5 19.1 19.5 20.1 20.5 21.7 22.2 22.5 23.0 24.9 25.9 28.6

Nominal of galvanized steel wire mm 1.25 1.6

Nominal outer-sheath thickness mm 1.8 1.9

Approx. overall dia. mm 24.5 25.5 26.0 26.5 27.0 28.0 28.5 29.0 29.5 31.5 32.5 35.5

Cable net weight (approx.) kg/km 1,090 1,270 1,310 1,360 1,400 1,460 1,490 1,500 1,550 1,570 1,590 1,630 1,840 1,960 2,240 2,280

FEC Cables (M) Sdn. Bhd.

56

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, XLPE Insulated, PVC Inner Covering, Zinc-Coated Steel Wire Armour, PVC Sheated Control

1.5 mm²

600/1000 V IEC 60502-1

PVC Outer Sheath

PVC Inner Covering

Armouring

Copper

XLPE Insulation

Filler (If Necessary)

Binder Tape

Max. conductor resistance DC at 20°C = 12.10 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.01

Nominal insulation thickness mm 0.7

Nominal inner covering thickness mm 1.0

Inner covering dia. (approx.) mm 9.8 10.4 11.3 12.3 13.4 14.5 15.6 17.0 17.6 17.9 18.5 19.0 19.6 20.1 20.6

Nominal of galvanized steel wire mm 0.9 1.25 1.6

Nominal outer-sheath thickness mm 1.8

Approx. overall dia. mm 15.0 15.5 16.5 17.5 19.0 20.5 21.5 23.0 23.5 24.0 25.5 26.0 26.5 27.0

Cable net weight (approx.) kg/km 390 430 490 560 720 730 810 880 960 980 1,040 1,080 1,130 1,320 1,370 1,430 1,480

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.01

Nominal insulation thickness mm 0.7

Nominal inner covering thickness mm 1.0 1.2

Inner covering dia. (approx.) mm 20.6 21.3 21.7 22.4 22.8 24.2 24.8 25.1 25.7 27.9 29.0 32.4

Nominal of galvanized steel wire mm 1.6 2.0

Nominal outer-sheath thickness mm 1.8 1.9 2.0 2.1

Approx. overall dia. mm 27.0 27.5 28.5 29.0 29.5 31.0 31.5 32.0 32.5 34.5 36.0 40.5

Cable net weight (approx.) kg/km 1,490 1,550 1,600 1,660 1,720 1,790 1,820 1,850 1,900 1,950 2,000 2,050 2,340 2,500 3,190 3,250

LOW VOLTAGE CABLES

57

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, XLPE Insulated, PVC Inner Covering, Zinc-Coated Steel Wire Armour, PVC Sheated Control

2.5 mm²

600/1000 V IEC 60502-1

PVC Outer Sheath

PVC Inner Covering

Armouring

Copper

XLPE Insulation

Filler (If Necessary)

Binder Tape

Max. conductor resistance DC at 20°C = 7.41 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.01

Nominal insulation thickness mm 0.7

Nominal inner covering thickness mm 1.0

Inner covering dia. (approx.) mm 10.8 11.4 12.5 13.7 15.0 16.2 17.5 19.1 19.7 20.1 20.8 21.4 22.0 22.7 23.3

Nominal of galvanized steel wire mm 0.9 1.25 1.6

Nominal outer-sheath thickness mm 1.8

Approx. overall dia. mm 16.0 16.5 17.5 19.5 20.5 22.0 23.0 25.5 26.0 26.5 27.0 28.0 28.5 29.0 29.5

Cable net weight (approx.) kg/km 460 520 590 780 870 900 990 1,090 1,320 1,370 1,440 1,500 1,570 1,650 1,710 1,790 1,860

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.01

Nominal insulation thickness mm 0.7

Nominal inner covering thickness mm 1.0 1.2

Inner covering dia. (approx.) mm 23.3 24.0 24.5 25.3 25.8 27.4 28.0 28.4 29.1 32.0 33.2 36.7

Nominal of galvanized steel wire mm 1.6 2.0

Nominal outer-sheath thickness mm 1.8 1.9 2.0 2.1 2.2

Approx. overall dia. mm 29.5 30.5 31.0 32.0 32.5 34.0 34.5 35.0 36.0 40.0 41.0 45.0

Cable net weight (approx.) kg/km 1,880 1,980 2,040 2,140 2,210 2,310 2,360 2,400 2,470 2,530 2,600 2,670 3,410 3,600 4,160 4,250

FEC Cables (M) Sdn. Bhd.

58

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, XLPE Insulated, PVC Inner Covering, Zinc-Coated Steel Wire Armour, PVC Sheated Control

4 mm²

600/1000 V IEC 60502-1

PVC Outer Sheath

PVC Inner Covering

Armouring

Copper

XLPE Insulation

Filler (If Necessary)

Binder Tape

Max. conductor resistance DC at 20°C = 4.61 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 1.59

Nominal insulation thickness mm 0.7

Nominal inner covering thickness mm 1.0

Inner covering dia. (approx.) mm 8.9 9.4 10.2 11.1 12.1 13.0 14.0 15.3 15.8 16.0 16.6 17.0 17.5 18.0 18.5

Nominal of galvanized steel wire mm 0.9 1.25

Nominal outer-sheath thickness mm 1.8

Approx. overall dia. mm 14.0 14.5 15.5 16.0 17.0 19.0 20.0 21.0 21.5 22.0 22.5 23.0 23.5 24.0 24.5

Cable net weight (approx.) kg/km 360 400 450 500 550 560 710 770 840 860 900 930 970 1,010 1,050 1,100 1,130

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 1.59

Nominal insulation thickness mm 0.7

Nominal inner covering thickness mm 1.0

Inner covering dia. (approx.) mm 18.5 19.0 19.4 20.0 20.4 21.6 22.1 22.4 23.0 24.8 25.8 28.5

Nominal of galvanized steel wire mm 1.25 1.6

Nominal outer-sheath thickness mm 1.8 1.9

Approx. overall dia. mm 24.5 25.5 26.0 26.5 27.0 28.0 28.5 29.0 29.5 31.5 32.5 35.5

Cable net weight (approx.) kg/km 1,140 1,330 1,370 1,420 1,450 1,530 1,550 1,570 1,600 1,620 1,660 1,700 1,910 2,040 2,330 2,370

LOW VOLTAGE CABLES

59

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, XLPE Insulated, PVC Inner Covering, Zinc-Coated Steel Wire Armour, PVC Sheated (Screened-CU Tape) Control

1.5 mm²

600/1000 V IEC 60502-1

PVC Outer Sheath

Copper

XLPE Insulation

Filler (If Necessary)

Binder Tape

PVC Inner Covering

Binder Tape

Amouring

Screening

Max. conductor resistance DC at 20°C = 12.10 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.01

Nominal insulation thickness mm 0.7

Nominal inner covering thickness mm 1.0

Inner covering dia. (approx.) mm 9.7 10.3 11.2 12.3 13.3 14.4 15.5 16.9 17.5 17.8 18.4 18.9 19.5 20.1 20.6

Nominal of galvanized steel wire mm 0.9 1.25 1.6

Nominal outer-sheath thickness mm 1.8

Approx. overall dia. mm 15.0 15.5 16.5 17.5 19.0 20.5 21.5 23.0 23.5 24.5 25.5 26.0 26.5 27.0

Cable net weight (approx.) kg/km 420 460 520 580 750 770 840 930 1,000 1,030 1,080 1,130 1,180 1,380 1,430 1,490 1,540

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.01

Nominal insulation thickness mm 0.7

Nominal inner covering thickness mm 1.0 1.2

Inner covering dia. (approx.) mm 20.6 21.2 21.7 22.3 22.8 24.2 24.7 25.0 25.7 27.8 28.9 32.3

Nominal of galvanized steel wire mm 1.6 2.0

Nominal outer-sheath thickness mm 1.8 1.9 2.0 2.1

Approx. overall dia. mm 27.0 27.5 28.0 29.0 29.5 30.5 31.0 31.5 32.0 32.5 34.5 36.0 40.5

Cable net weight (approx.) kg/km 1,560 1,620 1,670 1,730 1,790 1,870 1,900 1,930 1,980 2,020 2,080 2,130 2,410 2,580 3,290 3,350

FEC Cables (M) Sdn. Bhd.

60

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, XLPE Insulated, PVC Inner Covering, Zinc-Coated Steel Wire Armour, PVC Sheated (Screened-CU Tape) Control

2.5 mm²

600/1000 V IEC 60502-1

Amouring

PVC Outer Sheath

Copper

XLPE Insulation

Filler (If Necessary)

Binder Tape

PVC Inner Covering

Binder TapeScreening

Max. conductor resistance DC at 20°C = 7.41 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

No. of cores 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.55

Nominal insulation thickness mm 0.7

Nominal inner covering thickness mm 1.0

Inner covering dia. (approx.) mm 10.9 11.5 12.6 13.8 15.0 16.3 17.6 19.2 19.8 20.2 20.9 21.5 22.1 22.8 23.3

Nominal of galvanized steel wire mm 0.9 1.25 1.6

Nominal outer-sheath thickness mm 1.8

Approx. overall dia. mm 16.0 16.5 18.5 19.5 20.5 22.0 24.0 25.5 26.0 26.5 27.5 28.0 28.5 29.0 29.5

Cable net weight (approx.) kg/km 490 550 720 820 920 940 1,050 1,270 1,380 1,430 1,500 1,570 1,640 1,720 1,780 1,880 1,950

No. of cores 19 20 21 22 23 24 25 26 27 28 29 30 37 40 48 50

Shape of Conductor Circular Stranded

Conductor dia. (approx.) 2.55

Nominal insulation thickness mm 0.7

Nominal inner covering thickness mm 1.0 1.2

Inner covering dia. (approx.) mm 23.3 24.1 24.6 25.4 25.9 27.5 28.1 28.5 29.2 32.0 33.3 36.8

Nominal of galvanized steel wire mm 1.6 2.0

Nominal outer-sheath thickness mm 1.8 1.9 2.0 2.1 2.2

Approx. overall dia. mm 29.5 30.5 31.0 32.0 32.5 34.0 35.0 36.0 37.0 40.0 41.0 45.0

Cable net weight (approx.) kg/km 1,970 2,070 2,140 2,220 2,290 2,400 2,450 2,500 2,580 2,860 2,940 3,020 3,520 3,710 4,280 4,370

LOW VOLTAGE CABLES

61

LOW VOLTAGE SPECIFICATION

Dimensional

Copper Conductor, XLPE Insulated, PVC Inner Covering, Zinc-Coated Steel Wire Armour, PVC Sheated (Screened-CU Tape) Control

4 mm²

600/1000 V IEC 60502-1

PVC Outer Sheath

Copper

XLPE Insulation

Filler (If Necessary)

Binder Tape

PVC Inner Covering

Binder Tape

Amouring

Screening

Max. conductor resistance DC at 20°C = 4.61 Ω /kmCore Identification : Black numbers on white cores(for 2 cores up to 48 cores)For 50 cores, White insulation with number 1 - 28 and Red insulation with number 1 - 22

FEC Cables (M) Sdn. Bhd.

62

The thermally permissible short circuit current for a conductor of specified size may be calculated from the equations below (based on IEC 609�9). For purposes of calculation, the standard short circuit duration period is up to 5 sec.

1. Copper Conductor :

2. Aluminium Conductor :

where s : conductor size in mm²

t : short circuit period in seconds

Short Circuit Current

Calculation Base for Electrical Characteristics

Installation

In air (Ambient temperature : 40 °C) In the ground (Ambient temperature : 25 °C)

Multi-core cable Single-core cable

Correction Factors For Continuous Current Rating

Ambient Temperature (°C)

Instalation15 20 25 30 35 �0 �5 50 55

In Air 1.22 1.18 1.1� 1.10 1.05 1.0 0.95 0.89 0.8�

In Ground 1.07 1.0� 1.0 0.96 0.92 0.88 0.83 0.78 0.73

I =1�3 • S

t1 + 0.�1 + 0.12t

sts (A)

I =9� • S

t1 + 0.57 + 0.16t

sts (A)

Multi-core cable Single-core cable

GroundLevel

700

mm

700

mm

Thermal Resistivity :120° C. cm/W

Factory 1Persiaran Raja Muda, �0000 Shah Alam, Selangor Darul Ehsan, Malaysia.(P.O. Box 7006, �0700 Shah Alam)Tel : 6 03 - 5519 1110 (Hotline) Fax : 6 03 - 5519 1296

Factory 2No. 16, Jalan Keluli 2, Bukit Raja Industrial Area, �1050 Klang, Selangor Darul Ehsan, Malaysia. Tel : 6 03 - 33�3 5837 (Hotline) Fax : 6 03 - 33�3 58�3

Sales OfficePersiaran Raja Muda, �0000 Shah Alam, Selangor Darul Ehsan, MalaysiaTel : 6 03 - 5519 1110 (Hotline) Fax : 6 03 - 5519 1296 / 5513 8688Email : [email protected]

www.fec.com.my

FEC Cables (M) Sdn. Bhd.(7293-W)

Des

ign

by

Tel :

03

- 772

2 48

18

FEC Cables (M) Sdn. Bhd.

Instrumentation Cables300/500V

CORPORATEHISTORY

INTRODUCTION OF

COMPANYWhen there is talk of high quality electric wires and cables, the one company that comes to mind is FEC Cables (Malaysia) Sdn. Bhd. FEC is a subsidiary of Permodalan Nasional Berhad and was formerly known as Furukawa Electric Cables (M) Sdn. Bhd. Having established its Shah Alam plant in 1967 on a 7-acre site at the Shah Alam Industrial Estate, Furukawa has come a long way.

The technical collaboration with our Japanese counterpart, Furukawa Japan, has brought about an amazing success for us. In terms of quality, we have climbed the ladders of product manufacturing, steadily and successfully, pushing FEC towards the pinnacle of excellence. Putting our customers’ demands and needs as our number one priority, we opened our second plant in 1995, on a 27-acre freehold land site in Bukit Raja Industrial area, Klang. In our quest for excellence, we equip the plant with the latest technological aids for the manufacture of a wide range of low and medium voltage cables.

The certification of the ISO 9001 for both plants only proves that we do not compromise on quality and customer satisfaction. Our dedicated and hard-working employees are the backbone of our success. This was greatly helped by the state-of-the-art technology equipment which has led us towards excellence.

Moving towards a new century, we pledge to continually strive towards progressive and dynamic growth as FEC Cables continues its efforts in contributing to the development Malaysia.

FEC Cables (M) Sdn. Bhd. was first established in 1967 and was previously known as Furukawa Electric Cables (M) Sdn. Bhd. In all the years until 2003, the company had been under the management and control of Furukawa Electric Co. Ltd. of Japan.

In 2003, the company was renamed FEC Cables (M) Sdn. Bhd. following the acquisition of its major equity stake by Permodalan Nasional Berhad, Malaysia’s government-owned premier multi-billion dollar investment institution.

The Company had started a technical collaboration from world renowned cable manufacturer, The Furukawa Electric Co. Ltd Japan (Furukawa Japan).

FEC Cables has benefited enormously from the technical collaboration and the subsequent technology transfer with Furukawa Japan. FEC Cables inherited from Furukawa Japan not only its advanced technology and technical know-how but also the disciplines of producing quality products using material conforming to the international standards of manufacturing cables.

Today FEC Cables plays a prominent role as a forerunner in the cable industry.

FEC Cables has been actively involved in serving various industrial sectors, namely the power, telecommunications, construction as well as the oil and gas sectors.

Instrumentation Cables

Table Of Contents

PE insulated and PVC sheathedBS 5308 Part 1 Type 1 & FEC (M) Standard

PE insulated, PE bedded, Steel wire armoured and PVC oversheathedBS 5308 Part 1 Type 2 & FEC (M) Standard

Multipair, Collective screen PE/PVC-SLA

PE/PE/SWA/PVC-SLA

Multipair, Individual pair screen PE/PVC-PSLA PE/PE/SWA/PVC-PSLA

Multitriple, collective screen PE/PVC-SLA PE/PE/SWA/PVC-SLA

Multitriple, individual triple screen PE/PVC-TSLA PE/PE/SWA/PVC-TSLA

PVC insulated and PVC SheathedBS 5308 Part 2 Type 1 & FEC (M) Standard

PVC insulated, PVC bedded, Steel wire armoured and PVC oversheathedBS 5308 Part 2 Type 2 & FEC (M) Standard

Multipair, Collective screen PVC/PVC-SLA PVC/PVC/SWA/PVC-SLA

Multipair, Individual pair screen PVC/PVC-PSLA PVC/PVC/SWA/PVC-PSLA

Multitriple, Collective screen PVC/PVC-SLA PVC/PVC/SWA/PVC-SLA

Multitriple, Individual triple screen PVC/PVC-TSLA PVC/PVC/SWA/PVC-TSLA

Instrumentation Cables

5

Multipair Cable

Applicable Standards

BS 5308 Part 1 (Type 1 & Type 2)BS 6746 / BS 7655BS 6234BS 6360 (IEC 60228)BS 4066 Part 1 (IEC 60332-1) & IEC 60332-3 (if required)

Construction

Conductor : Plain annealed copper wires according to BS 6360 (IEC 60228)

Insulation : Polyethylene type 03 according to BS 6234 or equivalent compound

Colour code : Refer to theTable 3

Pairing : Cores twisted to pairs (two pairs cable can be manufactured as a quad for collective screen cables)

Binder : Non-hygroscopic Polyester tape

Drain wire : Tinned annealed copper wire 0.5mm2 (1/0.80mm)

Screen : Aluminium/Polyester tape approx. 0.022mm thick over Drain ware

Bedding (Inner sheath) : Polyethylene type 03 Black colour according to BS 6234 or equivalent compound

Armour : Galvanized steel wires

Sheath/Oversheath : PVC compound type TM1 Black colour according to BS 6746 / BS 7655, Flame retardant to BS 4066 Part 1 (IEC 60332-1) or Low smoke, Non-halogen and Flame retardant thermoplastic compound (LSNHFR) to BS 4066 Part 1 & 3 (IEC 60332-1 & 3) if required.

Cable Identification : Manufacturer’s name and voltage

Temperature Rating

Applicable Standards

For transmission of analogue and digital signals in and around process plants in dry and damp industrial areas.(Non-armoured cables : not recommended for underground burial)

Non-armoured cable - During operation : 6 X Overall diameter - During installation : 8 X Overall diameterArmoured cable - During operation : 8 X Overall diameter - During installation : 10 X Overall diameter

During operation : -30°C up to +70°CDuring installation : -10°C up to +50°C

- PE : Polyethylene - SLA : Aluminium/Polyester tape collective screen-SWA : Steel wire armour - PSLA : Aluminium/Polyester tape pair screen- PVC : Polyvinyl Chloride

Application

Abbreviations

Minimum Bending Radius

FEC Cables (M) Sdn. Bhd.

6

Multipair Cable

Applicable StandardsTable 1 Collective Screen

Conductorsize

No.of

pair

Insulationthickness

Nom.(mm)

PE/PVC-SLA(Non-armoured cable)

PE/PE/SWA/PVC-SLA(Armoured cable)

Sheaththickness

Nom.(mm)

OveralldiameterApprox.(mm)

WeightApprox.(kg/km)

Beddingthickness

Nom.(mm)

Diameterover

beddingApprox.(mm)

Armourwire

diameterNom.(mm)

Sheaththickness

Nom.(mm)

OveralldiameterApprox.(mm)

WeightApprox.(kg/km)

0.50mm2

(1/0.80mm)

1

2

3

5

10

15

20

24

30

0.5

0.8

0.8

0.9

1.1

1.2

1.2

1.3

1.3

1.3

5.5

6

8.5

10.5

14

17

19.5

21

23

37

53

77

120

210

295

385

445

540

0.8

0.8

0.9

1.1

1.2

1.2

1.3

1.3

1.3

5.4

6.1

8.4

10.6

14.2

16.9

19.3

20.8

23.0

0.9

0.9

0.9

0.9

1.25

1.25

1.6

1.6

1.6

1.3

1.3

1.4

1.4

1.6

1.6

1.7

1.7

1.8

10

10.5

13

15

20

22.5

26

27.5

30

185

215

295

395

690

855

1180

1310

1495

0.50mm2

(7/0.30mm)

1

2

3

5

10

15

20

24

30

0.6

0.8

0.8

0.9

1.1

1.2

1.3

1.3

1.3

1.5

6

7

9.5

12

16

19.5

22

24

26.5

42

60

87

135

240

340

435

505

640

0.8

0.8

0.9

1.1

1.2

1.3

1.3

1.3

1.5

6

6.8

9.4

12

16.2

19.4

22

23.9

26.7

0.9

0.9

0.9

0.9

1.25

1.6

1.6

1.6

1.6

1.3

1.3

1.4

1.5

1.6

1.7

1.8

1.8

1.9

10.5

11

14

17

22

26

29

30.5

33.5

200

235

335

450

790

1145

1360

1510

1770

0.75mm2

(1/0.96mm)

1

2

3

5

10

15

20

24

30

0.6

0.8

0.8

0.9

1.1

1.2

1.3

1.3

1.5

1.5

6

7

9.5

12.5

16.5

20

22.5

25

27.5

47

69

100

155

280

405

515

625

760

0.8

0.8

0.9

1.1

1.2

1.3

1.3

1.5

1.5

6.1

7

9.6

12.3

16.6

19.9

22.6

24.9

27.4

0.9

0.9

0.9

0.9

1.25

1.6

1.6

1.6

1.6

1.3

1.3

1.4

1.5

1.6

1.7

1.8

1.8

1.9

10.5

11.5

14

17

22.5

26.5

29.5

31.5

34.5

210

250

350

480

840

1225

1465

1660

1910

0.75mm2

(7/0.37mm)

1

2

3

5

10

15

20

24

30

0.6

0.8

0.8

1.1

1.2

1.3

1.3

1.5

1.5

1.7

6.5

7.5

10.5

13

17.5

21

24

26.5

29

50

74

115

175

315

440

580

680

825

0.8

0.8

1.1

1.2

1.3

1.3

1.5

1.5

1.7

6.4

7.3

10.6

13.2

17.7

21.1

23.9

26.4

29.1

0.9

0.9

0.9

1.25

1.25

1.6

1.6

1.6

1.6

1.3

1.4

1.4

1.5

1.6

1.7

1.8

1.9

1.9

11

12

15

18.5

23

27.5

30.5

33.5

36

220

265

385

615

900

1320

1600

1790

2060

Instrumentation Cables

7

Multipair Cable

Conductorsize

No.of

pair

Insulationthickness

Nom.(mm)

PE/PVC-SLA(Non-armoured cable)

PE/PE/SWA/PVC-SLA(Armoured cable)

Sheaththickness

Nom.(mm)

OveralldiameterApprox.(mm)

WeightApprox.(kg/km)

Beddingthickness

Nom.(mm)

Diameterover

beddingApprox.(mm)

Armourwire

diameterNom.(mm)

Sheaththickness

Nom.(mm)

OveralldiameterApprox.(mm)

WeightApprox.(kg/km)

1.0mm2

(1/1.13mm)

1

2

3

5

10

15

20

24

30

0.6

0.8

0.8

1.1

1.2

1.2

1.3

1.5

1.5

1.5

6.5

7.5

10.5

13

17.5

21.5

24.5

26.5

29.5

55

83

125

195

345

500

665

775

945

0.8

0.8

1.1

1.2

1.2

1.3

1.5

1.5

1.5

6.4

7.4

10.6

13.2

17.7

21.3

24.5

26.6

29.3

0.9

0.9

0.9

1.25

1.25

1.6

1.6

1.6

1.6

1.3

1.4

1.4

1.5

1.7

1.8

1.8

1.9

2.0

11

12

15

18.5

23.5

28

31.5

33.5

36.5

225

275

405

635

945

1380

1675

1900

2210

1.0mm2

(7/0.43mm)

1

2

3

5

10

15

20

24

30

0.6

0.8

0.8

1.1

1.2

1.3

1.3

1.5

1.5

1.7

6.5

8

11

14

19

22.5

26

28

31.5

58

88

135

210

375

535

710

830

1040

0.8

0.8

1.1

1.2

1.3

1.3

1.5

1.5

1.7

6.7

7.8

11.2

14

18.9

22.5

26

28.2

31.5

0.9

0.9

0.9

1.25

1.6

1.6

1.6

1.6

2.0

1.3

1.4

1.5

1.5

1.7

1.8

1.9

1.9

2.0

11

12.5

16

19.5

25.5

29.5

33

35

39.5

235

290

435

675

1170

1485

1815

2035

2640

1.5mm2

(7/0.53mm)

1

2

3

5

10

15

20

24

30

0.6

0.8

0.9

1.2

1.2

1.3

1.5

1.5

1.7

1.7

7.5

8.5

12.5

15.5

21

25.5

28.5

31.5

35

73

115

180

270

500

735

950

1145

1400

0.8

0.9

1.2

1.2

1.3

1.5

1.5

1.7

1.7

7.3

8.7

12.5

15.4

20.9

25.3

28.7

31.6

34.9

0.9

0.9

1.25

1.25

1.6

1.6

2.0

2.0

2.0

1.4

1.4

1.5

1.6

1.8

1.9

2.0

2.0

2.1

12

13.5

18

21

27.5

32.5

36.5

39.5

43

265

335

595

790

1380

1815

2200

2780

3215

Table 1 (Cont’d) Collective Screen

FEC Cables (M) Sdn. Bhd.

8

Multipair Cable

Conductorsize

No.of

pair

Insulationthickness

Nom.(mm)

PE/PVC-PSLA(Non-armoured cable)

PE/PE/SWA/PVC-PSLA(Armoured cable)

Sheaththickness

Nom.(mm)

OveralldiameterApprox.(mm)

WeightApprox.(kg/km)

Beddingthickness

Nom.(mm)

Diameterover

beddingApprox.(mm)

Armourwire

diameterNom.(mm)

Sheaththickness

Nom.(mm)

OveralldiameterApprox.(mm)

WeightApprox.(kg/km)

0.50mm2

(1/0.80mm)

2

3

5

10

15

20

24

30

0.5

0.9

1.1

1.2

1.2

1.3

1.3

1.5

1.5

9.5

10.5

12.5

17.5

19.5

22

25.5

27

81

105

155

280

375

470

600

700

0.9

1.1

1.2

1.2

1.3

1.3

1.5

1.5

9.4

10.4

12.6

17.5

19.7

22.1

25.6

27.1

0.9

0.9

1.25

1.25

1.6

1.6

1.6

1.6

1.4

1.4

1.5

1.7

1.7

1.8

1.9

1.9

14

15

18

23.5

26.5

29

32.5

34

320

355

560

825

1135

1320

1580

1735

0.50mm2

(7/0.30mm)

2

3

5

10

15

20

24

30

0.6

1.1

1.1

1.2

1.3

1.5

1.5

1.5

1.7

11

11.5

14

20

23

25.5

29

31.5

100

120

175

330

450

565

700

835

1.1

1.1

1.2

1.3

1.5

1.5

1.5

1.7

10.9

11.6

14.2

20.0

22.8

25.5

29.1

31.3

0.9

0.9

1.25

1.6

1.6

1.6

1.6

2.0

1.5

1.5

1.6

1.8

1.8

1.9

1.9

2.1

15.5

16.5

20

27

29.5

32.5

36

39.5

380

410

625

1105

1320

1540

1795

2290

0.75mm2

(1/0.96mm)

2

3

5

10

15

20

24

30

0.6

1.1

1.1

1.2

1.3

1.3

1.5

1.5

1.7

11

12

14.5

20.5

23

26

30

32

110

135

200

380

495

655

805

970

1.1

1.1

1.2

1.3

1.3

1.5

1.5

1.7

11.2

11.9

14.5

20.5

22.9

26.1

29.8

32.0

0.9

0.9

1.25

1.6

1.6

1.6

1.6

2.0

1.5

1.5

1.6

1.7

1.8

1.9

1.9

2.0

16

16.5

20

27

29.5

33

37

40

390

425

660

1160

1370

1650

1920

2435

0.75mm2

(7/0.37mm)

2

3

5

10

15

20

24

30

0.6

1.1

1.2

1.2

1.3

1.5

1.5

1.7

1.7

12

12.5

15.5

21.5

24.5

27.5

32

34

120

150

215

410

560

710

905

1050

1.1

1.2

1.2

1.3

1.5

1.5

1.7

1.7

11.8

12.7

15.3

21.6

24.6

27.6

31.9

33.9

0.9

1.25

1.25

1.6

1.6

1.6

2.0

2.0

1.5

1.5

1.6

1.7

1.8

1.9

2.0

2.1

16.5

18

21

28

31.5

34.5

40

42

410

555

700

1230

1485

1765

2370

2625

Table 2 Individual Pair Screen

Instrumentation Cables

9

Multipair Cable

Conductorsize

No.of

pair

Insulationthickness

Nom.(mm)

PE/PVC-PSLA(Non-armoured cable)

PE/PE/SWA/PVC-PSLA(Armoured cable)

Sheaththickness

Nom.(mm)

OveralldiameterApprox.(mm)

WeightApprox.(kg/km)

Beddingthickness

Nom.(mm)

Diameterover

beddingApprox.(mm)

Armourwire

diameterNom.(mm)

Sheaththickness

Nom.(mm)

OveralldiameterApprox.(mm)

WeightApprox.(kg/km)

1.0mm2

(1/1.13mm)

2

3

5

10

15

20

24

30

0.6

1.1

1.2

1.2

1.3

1.5

1.7

1.7

2.0

12

13

15.5

22

25

28

32

34.5

130

160

235

455

625

815

1005

1220

1.1

1.2

1.2

1.3

1.5

1.7

1.7

2.0

11.8

12.8

15.4

21.8

24.8

28.2

32.1

34.7

0.9

1.25

1.25

1.6

1.6

2.0

2.0

2.0

1.5

1.5

1.6

1.8

1.9

2.0

2.0

2.2

16.5

18.5

21

28.5

32

36

40

43

410

570

725

1285

1580

2135

2475

2830

1.0mm2

(7/0.43mm)

2

3

5

10

15

20

24

30

0.6

1.2

1.2

1.2

1.3

1.5

1.5

1.7

2.0

12.5

13.5

16

23

26

29.5

34

36.5

145

175

255

485

670

850

1080

1310

1.2

1.2

1.2

1.3

1.5

1.5

1.7

2.0

12.7

13.4

16.2

23.0

26.2

29.4

34.0

36.7

1.25

1.25

1.25

1.6

1.6

1.6

2.0

2.0

1.5

1.5

1.6

1.8

1.9

2.0

2.1

2.2

18

19

22

30

33

36.5

42

45

550

600

765

1375

1665

1980

2650

3005

1.5mm2

(7/0.53mm)

2

3

5

10

15

20

24

30

0.6

1.2

1.2

1.3

1.5

1.7

1.7

2.0

2.0

14

14.5

18

26

29.5

33

38

40.5

180

220

335

650

900

1145

1460

1715

1.2

1.2

1.3

1.5

1.7

1.7

2.0

2.0

13.8

14.7

18.0

25.8

29.3

32.8

38.1

40.4

1.25

1.25

1.6

1.6

2.0

2.0

2.0

2.5

1.6

1.6

1.7

1.9

2.0

2.1

2.2

2.5

19.5

20.5

24.5

33

37.5

41

46.5

50.5

615

680

1035

1630

2250

2660

3220

4020

Table 2 (cont’d) Individual Pair Screen

FEC Cables (M) Sdn. Bhd.

10

Multipair Cable

Pair No. a-wire b-wire

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

Black

Black

Blue

Black

Blue

Green

Black

Blue

Green

Brown

Black

Blue

Green

Brown

White

Blue

Green

Green

Brown

Brown

Brown

White

White

White

White

Red

Red

Red

Red

Red

Pair No. a-wire b-wire

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

Black

Blue

Green

Brown

White

Red

Black

Blue

Green

Brown

White

Red

Orange

Black

Blue

Orange

Orange

Orange

Orange

Orange

Orange

Yellow

Yellow

Yellow

Yellow

Yellow

Yellow

Yellow

Grey

Grey

Note:Colour code for Two-pair cable(one quad) : Black, Blue, Green, Brown (colour coded in clockwise order of rotation)

Conductor sizeElectrical requirements

mm2

(no./mm)0.5

(1/0.80)0.5

(7/0.30)0.75

(1/0.96)0.75

(7/0.37)1.0

(1/1.13)1.0

(7/0.43)1.5

(7/0.53)

Conductor resistance at 20°C (Ω/km) Max. 36.8 36.7 25.0 25.0 18.4 18.5 12.3

Insulation resistance at 20°C (MΩ.km) Min. 5000

Mutual capacitance at 1 kHz (nF/km)

- Collective screen : one-pair & two-pair cable

: all other cable

- Individual screenMax.

115 75

115

12085

120

Capacitance unbalance at 1kHz (pF/250m) Max. 250

Inductance/Resistance ratio, L/R (µH/Ω) Max. 25 40

Voltage test for1 minute

core to core (kV) 1

1core to screen (kV)

Table 3 Colour code (Pair identification)

Table 4 Electrial characteristics

Instrumentation Cables

11

Conductor

Insulation

Binder

Drain wire

Screen

Sheath

Multipair Cable : Cross-Sectional Of Cable

PE/PVC-PSLA INDIVIDUAL PAIR SCREEN (NON-ARMOURED CABLE)

PE/PE/SWA/PVC-PSLA INDIVIDUAL PAIR SCREEN (ARMOURED CABLE)

PE/PE/SWA/PVC-SLA COLLECTIVE SCREEN (ARMOURED CABLE)

Binder

Conductor

Insulation

Binder

Drain wire

Screen

Sheath

Conductor

Insulation

Binder

Drain wire

Screen

Bedding

Armour

Oversheath

Conductor

Insulation

Binder

Binder

Drain wire

Screen

Bedding

Armour

Oversheath

PE/PVC-SLA COLLECTIVE SCREEN (NON-ARMOURED CABLE)

FEC Cables (M) Sdn. Bhd.

12

BS 5308 Part 1 (Type 1 & Type 2)BS 6746/ BS 7655BS 6234BS 6360 (IEC 60228)BS 4066 Part 1 (IEC 60332-1) & IEC 60332-3 (if required)

Construction

Conductor : Plain annealed copper wires according to BS 6360 (IEC 60228)Insulation : Polyethylene type 03 according to BS 6234 or equivalent compoundColour code : Refer to the Table 7Tripling : Cores twisted to triplesBinder : Non-hygroscopic Polyester tapeDrain wire : Tinned annealed copper wire 0.5mm2 (1/0.80mm)Screen : Aluminium/Polyester tape approx. 0.022mm thick over Drain wireBedding (Inner sheath) : Polyethylene type 03 Black colour according to BS 6234 or equivalent compoundArmour : Galvanized steel wiresSheath/Oversheath : PVC compound type TM 1 Black colour according to BS 6746 / BS 7655, Flame retardant to BS 4066 Part 1 (IEC 60332-1) or Low smoke, Non-halogen and Flame retardant thermoplastic compound (LSNHFR) to BS 4066 Part 1&3 (IEC 60332-1&3) if required.Cable Identification : Manufacturer’s name and voltage

Application

Abbreviations

Temperature Rating

Minimum Bending Radius

For transmission of analogue and digital signals in and around process plants in dry and damp industrial areas.(Non-armoured cables : not recommended for underground burial)

Non-armoured - During operation : 6 X Overall diameter - During Installation : 8 X Overall diameterArmoured cable - During operation : 8 X Overall diameter - During Installation : 10 X Overall diameter

During operation : -30°C up to +70°CDuring Installation : -10°C up to +50°C

- PE : Polyethylene- SLA : Aluminium/Polyester tape collective screen- SWA : Steel wire armour- PSLA : Aluminium/Polyester tape pair screen- PVC : Polyvinyl chloride

Applicable Standards

Multitriple Cable

Instrumentation Cables

13

Conductorsize

No.of

pair

Insulationthickness

Nom.(mm)

PE/PVC-SLA(Non-armoured cable)

PE/PE/SWA/PVC-SLA(Armoured cable)

Sheaththickness

Nom.(mm)

OveralldiameterApprox.(mm)

WeightApprox.(kg/km)

Beddingthickness

Nom.(mm)

Diameterover

beddingApprox.(mm)

Armourwire

diameterNom.(mm)

Sheaththickness

Nom.(mm)

OveralldiameterApprox.(mm)

WeightApprox.(kg/km)

0.50mm2

(1/0.80mm)

1235

101520

0.5

0.81.11.11.21.31.31.5

5.59.5

10.512.517.519.522.5

44100115175325435570

0.81.11.11.21.31.31.5

5.69.7

10.312.517.519.522.3

0.90.90.9

1.251.61.61.6

1.31.41.41.51.71.81.9

1014.5151824

26.529.5

195340375570

101011901430

0.50mm2

(7/0.30mm)

1235

101520

0.6

0.81.11.11.21.31.51.7

6.511

11.51420

22.526

51110135200380520680

0.81.11.11.21.31.51.7

6.311

11.614.220

22.725.8

0.90.90.9

1.251.61.62.0

1.31.51.51.61.71.81.9

10.516

16.520

26.529.533.5

220390425650

114013801860

0.75mm2

(1/0.96mm)

1235

101520

0.6

0.81.11.11.21.31.51.7

6.51112

14.520.523.526.5

57125155235445615810

0.81.11.11.21.31.51.7

6.411.211.914.520.523.326.5

0.90.90.9

1.251.61.62.0

1.31.51.51.61.81.81.9

1116

16.520

27.530

34.5

225405450695

123514952015

0.75mm2

(7/0.37mm)

1235

101520

0.6

0.81.11.21.21.31.51.7

6.51213

15.521.524.528

61135175255485670880

0.81.11.21.21.31.51.7

6.711.812.815.321.724.728.1

0.90.9

1.251.251.61.62.0

1.31.51.51.61.81.92.0

1116.518.521

28.531.536

235430575735

131016002160

1.0mm2

(1/1.13mm)

1235

101520

0.6

0.81.11.21.21.31.51.7

71213

15.52225

28.5

68150190285545765

1000

0.81.11.21.21.31.51.7

6.811.912.815.421.824.928.3

0.90.9

1.251.251.61.62.0

1.31.51.51.61.81.92.0

1116.518.521

28.532

36.5

245445595770

137517102305

1.0mm2

(7/0.43mm)

1235

101520

0.6

0.81.21.21.21.51.51.7

713

13.516.523.526.530

72165205305605815

1070

0.81.21.21.21.51.51.7

7.112.813.616.323.626.430.0

0.91.251.251.251.61.62.0

1.31.51.61.61.91.92.0

11.518.519.522

30.533.538

255570640815

150518152450

1.5mm2

(7/0.53mm)

1235

101520

0.6

0.81.21.21.31.51.71.9

814151826

29.533.5

92210265410805

11251475

0.81.21.21.31.51.71.9

7.814

14.918.226

29.533.5

0.91.251.251.61.62.02.0

1.41.61.61.71.92.02.1

12.519.520.52533

37.541.5

290660735

1110179524902995

Table 5 Collective Screen

Multitriple Cable

FEC Cables (M) Sdn. Bhd.

1�

Conductorsize

No.of

pair

Insulationthickness

Nom.(mm)

PE/PVC-TSLA(Non-armoured cable)

PE/PE/SWA/PVC-TSLA(Armoured cable)

Sheaththickness

Nom.(mm)

OveralldiameterApprox.(mm)

WeightApprox.(kg/km)

Beddingthickness

Nom.(mm)

Diameterover

beddingApprox.(mm)

Armourwire

diameterNom.(mm)

Sheaththickness

Nom.(mm)

OveralldiameterApprox.(mm)

WeightApprox.(kg/km)

0.50mm2

(1/0.80mm)

2

3

5

10

15

20

0.5

1.1

1.1

1.2

1.3

1.3

1.5

10.5

11

13.5

19.5

21.5

24.5

110

130

200

375

500

655

1.1

1.1

1.2

1.3

1.3

1.5

10.6

11.2

13.7

19.3

21.5

24.5

0.9

0.9

1.25

1.6

1.6

1.6

1.4

1.5

1.5

1.7

1.8

1.9

15

16

19

26

28.5

31.5

365

415

630

1120

1330

1595

0.50mm2

(7/0.30mm)

2

3

5

10

15

20

0.6

1.1

1.1

1.2

1.3

1.5

1.7

12

12.5

15.5

22

25

28.5

125

150

230

435

600

785

1.1

1.1

1.2

1.3

1.5

1.7

11.9

12.6

15.4

21.8

24.9

28.3

0.9

0.9

1.25

1.6

1.6

2.0

1.5

1.5

1.6

1.8

1.8

1.9

16.5

17.5

21

28.5

31.5

36

425

465

715

1285

1540

2085

0.75mm2

(1/0.96mm)

2

3

5

10

15

20

0.6

1.1

1.2

1.2

1.3

1.5

1.7

12

13

16

22.5

25.5

29

140

180

265

505

695

915

1.1

1.2

1.2

1.3

1.5

1.7

12.1

13.1

15.8

22.4

25.5

29.0

0.9

1.25

1.25

1.6

1.6

2.0

1.5

1.5

1.6

1.8

1.9

2.0

17

18.5

21.5

29

32.5

37

445

595

760

1355

1675

2260

0.75mm2

(7/0.37mm)

2

3

5

10

15

20

0.6

1.2

1.2

1.2

1.5

1.5

1.7

13

14

16.5

24

27

30.5

160

195

285

570

755

990

1.2

1.2

1.2

1.5

1.5

1.7

13

13.8

16.6

24.1

26.9

30.6

1.25

1.25

1.25

1.6

1.6

2.0

1.5

1.5

1.6

1.8

1.9

2.0

18.5

19.5

22.5

31

34

38.5

565

620

805

1475

1775

2400

1.0mm2

(1/1.13mm)

2

3

5

10

15

20

0.6

1.2

1.2

1.2

1.5

1.5

1.7

13

14

17

24

27

31

170

210

315

630

850

1115

1.2

1.2

1.2

1.5

1.5

1.7

13.1

13.9

16.8

24.2

27.1

30.9

1.25

1.25

1.25

1.6

1.6

2.0

1.5

1.5

1.6

1.8

1.9

2.0

18.5

19.5

22.5

31

34

39

585

650

840

1555

1885

2525

1.0mm2

(7/0.43mm)

2

3

5

10

15

20

0.6

1.2

1.2

1.2

1.5

1.5

1.7

13.5

14.5

17.5

25.5

28.5

32.5

185

225

340

675

910

1195

1.2

1.2

1.2

1.5

1.5

1.7

13.7

14.6

17.7

25.6

28.7

32.6

1.25

1.25

1.25

1.6

1.6

2.0

1.5

1.6

1.6

1.9

2.0

2.1

19

20.5

23.5

32.5

36

41

610

690

885

1655

2020

2710

1.5mm2

(7/0.53mm)

2

3

5

10

15

20

0.6

1.2

1.2

1.3

1.5

1.7

1.9

15

16

19.5

28

32

36.5

230

290

450

885

1235

1620

1.2

1.2

1.3

1.5

1.7

1.9

15

16

19.6

28.2

32

36.4

1.25

1.25

1.6

1.6

2.0

2.0

1.6

1.6

1.7

1.9

2.1

2.3

20.5

21.5

26

35

40

45

705

790

1210

1960

2725

3315

Multitriple Cable

Table 6 Individual Triple Screen

Instrumentation Cables

15

Type of triple a-wire b-wire c-wire

1

2

3

4

5

6

Black

Black

Black

Black

Black

Black

White

White

White

White

White

White

Red

Green

Yellow

Brown

Blue

Orange

No. of tripleTypr of triple

center 1st layer 2nd layer

1

2

3

5

10

15

20

1

-

-

-

-

-

1

-

1, 2

1~3

1~5

1, 2

1~4

1~6

-

-

-

-

1~6, 2, 3

1~6, 2~6

1~6, 2~6, 3, 4

Multitriple Cable

Table 8 Electrical characteristics

Conductor sizeElectrical requirements

mm2

(no./mm)0.5

(1/0.80)0.5

(7/0.30)0.75

(1/0.96)0.75

(7/0.37)1.0

(1/1.13)1.0

(7/0.43)1.5

(7/0.53)

Conductor resistance at 20°C (Ω/km) Max. 36.8 36.7 25.0 25.0 18.4 18.5 12.3

Insulation resistance at 20°C (MΩ.km) Min. 5000

Mutual capacitance at 1 kHz (nF/km)

- Collective screen : one-triple cable

: all other cables

- Individual screenMax.

115 75

115

12085

120

Inductance/Resistance ratio, L/R (µH/Ω) Max. 25 40

Voltage test for1 minute

core to core (kV) 1

1core to screen (kV)

Table 7 Colour code (Triple identification)

FEC Cables (M) Sdn. Bhd.

16

Conductor

Insulation

Binder

Drain wire

Screen

Sheath

Multitriple Cable : Cross-Sectional Of Cable

PE/PVC-TSLA INDIVIDUAL TRIPLE SCREEN (NON-ARMOURED CABLE)

Binder

Conductor

Insulation

Binder

Drain wire

Screen

Sheath

PE/PE/SWA/PVC-SLA COLLECTIVE SCREEN (ARMOURED CABLE)

Conductor

Insulation

Binder

Drain wire

Screen

Bending

Armour

Oversheath

PE/PE/SWA/PVC-TSLA INDIVIDUAL TRIPLE SCREEN (ARMOURED CABLE)

Conductor

Insulation

Binder

Binder

Drain wire

Screen

Bedding

Armour

Oversheath

PE/PVC-SLA COLLECTIVE SCREEN (NON-ARMOURED CABLE)

Instrumentation Cables

17

Multipair Cable

BS 5308 Part 2 (Type 1 & Type 2)BS 67�6/ BS 7655BS 6360 (IEC 60228)BS �066 Part 1 (IEC 60332-1) & IEC 60332-3 (if required)

Construction

Conductor : Plain annealed copper wires according to BS 6360 (IEC 60228)Insulation : PVC compound type TI1 according to BS 67�6/ BS 7655Colour code : White and Black (numbering on White core)Pairing : Cores twisted to pairs (two pair cable can be manufactured as a quad for collective screen cables)Binder : Non-hygroscopic Polyester tapeDrain wire : Tinned annealed copper wire 0.5mm2 (1/0.80mm)Screen : Aluminium/Polyester tape approx. 0.022mm thick over Drain wireBedding (Inner sheath) : PVC compaund type TM1 Black colour according to BS 67�6/ BS 7655, Flame retardant to BS �066

Part 1 (IEC 60332-1) or Low smoke, Non-halogen and Flame retardant thermoplastic compound (LSNHFR) to BS �066 Part 1&3 (IEC 60332-1&3) if required.

Armour : Galvanized steel wiresSheath/Oversheath : PVC compound type TM 1 Black colour according to BS 67�6 / BS 7655, Flame retardant to BS �066

Part 1 (IEC 60332-1) or Low smoke, Non-halogen and Flame retardant thermoplastic compound (LSNHFR) to BS �066 Part 1&3 (IEC 60332-1&3) if required.

Cable Identification : Manufacturer’s name and voltage

Application

Abbreviations

Temperature Rating

Minimum Bending Radius

For transmission of analogue and digital signals in and around process plants in dry and damp industrial areas.(Non-armoured cables : not recommended for underground burial)

Non-armoured - During operation : 6 X Overall diameter - During Installation : 8 X Overall diameterArmoured cable - During operation : 8 X Overall diameter - During Installation : 10 X Overall diameter

During operation : -30°C up to +70°CDuring Installation : -10°C up to +50°C

- PVC : Polyvinyl choloride- SLA : Aluminium/Polyester tape collective screen- SWA : Steel wire armour- PSLA : Aluminium/Polyester tape pair screen

Applicable Standards

FEC Cables (M) Sdn. Bhd.

18

Multipair Cable

Conductorsize

No.of

pair

Insulationthickness

Nom.(mm)

PVC/PVC-SLA(Non-armoured cable)

PVC/PVC/SWA/PVC-SLA(Armoured cable)

Sheaththickness

Nom.(mm)

OveralldiameterApprox.(mm)

WeightApprox.(kg/km)

Beddingthickness

Nom.(mm)

Diameterover

beddingApprox.(mm)

Armourwire

diameterNom.(mm)

Sheaththickness

Nom.(mm)

OveralldiameterApprox.(mm)

WeightApprox.(kg/km)

0.50mm2

(1/0.80mm)

1

2

3

5

10

15

20

24

30

0.5

0.8

0.8

0.9

1.1

1.2

1.2

1.3

1.3

1.3

5.5

6

8.5

10.5

14

17

19.5

21

23

39

57

83

130

230

325

425

495

600

0.8

0.8

0.9

1.1

1.2

1.2

1.3

1.3

1.3

5.4

6.1

8.4

10.6

14.2

16.9

19.3

20.8

23.0

0.9

0.9

0.9

0.9

1.25

1.25

1.6

1.6

1.6

1.3

1.3

1.4

1.4

1.6

1.6

1.7

1.7

1.8

10

10.5

13

15

20

22.5

26

27.5

30

195

225

315

420

730

915

1255

1395

1595

0.50mm2

(7/0.30mm)

1

2

3

5

10

15

20

24

30

0.6

0.8

0.8

0.9

1.1

1.2

1.3

1.3

1.3

1.5

6

7

9.5

12

16

19.5

22

24

26.5

45

66

96

150

270

385

495

580

725

0.8

0.8

0.9

1.1

1.2

1.3

1.3

1.3

1.5

6

6.8

9.4

12

16.2

19.4

22

23.9

26.7

0.9

0.9

0.9

0.9

1.25

1.6

1.6

1.6

1.6

1.3

1.3

1.4

1.5

1.6

1.7

1.8

1.8

1.9

10.5

11

14

17

22

26

29

30.5

33.5

205

250

355

485

845

1220

1460

1625

1915

0.75mm2

(1/0.96mm)

1

2

3

5

10

15

20

24

30

0.6

0.8

0.8

0.9

1.1

1.2

1.3

1.3

1.5

1.5

6

7

9.5

12.5

16.5

20

22.5

25

27.5

50

75

105

170

310

450

575

695

850

0.8

0.8

0.9

1.1

1.2

1.3

1.3

1.5

1.5

6.1

7

9.6

12.3

16.6

19.9

22.6

24.9

27.4

0.9

0.9

0.9

0.9

1.25

1.6

1.6

1.6

1.6

1.3

1.3

1.4

1.5

1.6

1.7

1.8

1.8

1.9

10.5

11.5

14

17

22.5

26.5

29.5

31.5

34.5

220

265

370

510

895

1305

1565

1780

2055

0.75mm2

(7/0.37mm)

1

2

3

5

10

15

20

24

30

0.6

0.8

0.8

1.1

1.2

1.3

1.3

1.5

1.5

1.7

6.5

7.5

10.5

13

17.5

21

24.5

26.5

29.5

54

81

125

190

345

490

650

765

955

0.8

0.8

1.1

1.2

1.3

1.3

1.5

1.5

1.7

6.4

7.3

10.6

13.2

17.7

21.1

23.9

26.4

29.1

0.9

0.9

0.9

1.25

1.6

1.6

1.6

1.6

2.0

1.3

1.4

1.4

1.5

1.7

1.8

1.8

1.9

2.0

11

12

15

18.5

24.5

28

31

33.5

37.5

230

280

410

655

1125

1410

1720

1925

2540

Table 9 Collective Screen

Instrumentation Cables

19

Multipair Cable

Conductorsize

No.of

pair

Insulationthickness

Nom.(mm)

PVC/PVC-SLA(Non-armoured cable)

PVC/PVC /SWA/PVC-SLA(Armoured cable)

Sheaththickness

Nom.(mm)

OveralldiameterApprox.(mm)

WeightApprox.(kg/km)

Beddingthickness

Nom.(mm)

Diameterover

beddingApprox.(mm)

Armourwire

diameterNom.(mm)

Sheaththickness

Nom.(mm)

OveralldiameterApprox.(mm)

WeightApprox.(kg/km)

1.0mm2

(1/1.13mm)

1

2

3

5

10

15

20

24

30

0.6

0.8

0.8

1.1

1.2

1.2

1.3

1.5

1.5

1.5

6.5

7.5

10.5

13

17.5

21.5

24.5

26.5

29.5

58

89

135

210

375

545

725

855

1045

0.8

0.8

1.1

1.2

1.2

1.3

1.5

1.5

1.5

6.4

7.4

10.6

13.2

17.7

21.3

24.5

26.6

29.3

0.9

0.9

0.9

1.25

1.25

1.6

1.6

1.6

1.6

1.3

1.4

1.4

1.5

1.7

1.8

1.8

1.9

2.0

11

12

15

18.5

23.5

28

31.5

33.5

36.5

235

290

430

670

1010

1465

1790

2030

2365

1.0mm2

(7/0.43mm)

1

2

3

5

10

15

20

24

30

0.6

0.8

0.8

1.1

1.2

1.3

1.3

1.5

1.5

1.7

6.5

8

11

14

19

22.5

26

28

31.5

62

95

145

225

415

590

785

925

1155

0.8

0.8

1.1

1.2

1.3

1.3

1.5

1.5

1.7

6.7

7.8

11.2

14

18.9

22.5

26

28.2

31.5

0.9

0.9

0.9

1.25

1.6

1.6

1.6

1.6

2.0

1.3

1.4

1.5

1.5

1.7

1.8

1.9

1.9

2.0

11

12.5

16

19.5

25.5

29.5

33

35

39.5

245

305

465

715

1245

1585

1945

2185

2830

1.5mm2

(7/0.53mm)

1

2

3

5

10

15

20

24

30

0.6

0.8

0.9

1.2

1.2

1.3

1.5

1.5

1.7

1.7

7.5

8.5

12.5

15.5

21

25.5

28.5

31.5

35

77

125

195

295

545

805

1040

1255

1540

0.8

0.9

1.2

1.2

1.3

1.5

1.5

1.7

1.7

7.3

8.7

12.5

15.4

20.9

25.3

28.7

31.6

34.9

0.9

0.9

1.25

1.25

1.6

1.6

1.6

2.0

2.0

1.4

1.4

1.5

1.6

1.8

1.9

2.0

2.0

2.1

12

13.5

18

21

27.5

32.5

36

39.5

43

280

355

630

840

1465

1940

2350

2965

3435

Table 9 (Cont’d) Collective Screen

FEC Cables (M) Sdn. Bhd.

20

Multipair Cable

Conductorsize

No.of

pair

Insulationthickness

Nom.(mm)

PVC/PVC-PSLA(Non-armoured cable)

PVC/PVC/SWA/PVC-PSLA(Armoured cable)

Sheaththickness

Nom.(mm)

OveralldiameterApprox.(mm)

WeightApprox.(kg/km)

Beddingthickness

Nom.(mm)

Diameterover

beddingApprox.(mm)

Armourwire

diameterNom.(mm)

Sheaththickness

Nom.(mm)

OveralldiameterApprox.(mm)

WeightApprox.(kg/km)

0.50mm2

(1/0.80mm)

2

3

5

10

15

20

24

30

0.5

0.9

1.1

1.2

1.2

1.3

1.3

1.5

1.5

9.5

10.5

12.5

17.5

19.5

22

25.5

27

85

110

165

300

405

510

650

760

0.9

1.1

1.2

1.2

1.3

1.3

1.5

1.5

9.4

10.4

12.6

17.5

19.7

22.1

25.6

27.1

0.9

0.9

1.25

1.25

1.6

1.6

1.6

1.6

1.4

1.4

1.5

1.7

1.7

1.8

1.9

1.9

14

15

18

23.5

26.5

29

32.5

34

335

375

590

875

1200

1400

1680

1850

0.50mm2

(7/0.30mm)

2

3

5

10

15

20

24

30

0.6

1.1

1.1

1.2

1.3

1.5

1.5

1.5

1.7

11

11.5

14

20

23

25.5

29

31.5

105

130

190

360

495

625

770

925

1.1

1.1

1.2

1.3

1.5

1.5

1.5

1.7

10.9

11.6

14.2

20.0

22.8

25.5

29.1

31.3

0.9

0.9

1.25

1.6

1.6

1.6

1.6

2.0

1.5

1.5

1.6

1.8

1.8

1.9

1.9

2.1

15.5

16.5

20

27

29.5

32.5

36

39.5

400

435

665

1175

1410

1655

1925

2455

0.75mm2

(1/0.96mm)

2

3

5

10

15

20

24

30

0.6

1.1

1.1

1.2

1.3

1.3

1.5

1.5

1.7

11

12

14.5

20.5

23

26

30

32

115

140

215

405

540

710

875

1055

1.1

1.1

1.2

1.3

1.3

1.5

1.5

1.7

11.2

11.9

14.5

20.5

22.9

26.1

29.8

32.0

0.9

0.9

1.25

1.6

1.6

1.6

1.6

2.0

1.5

1.5

1.6

1.7

1.8

1.9

1.9

2.0

16

16.5

20

27

29.5

33

37

40

410

450

700

1225

1470

1760

2055

2600

0.75mm2

(7/0.37mm)

2

3

5

10

15

20

24

30

0.6

1.1

1.2

1.2

1.3

1.5

1.7

1.7

2.0

12

12.5

15.5

21.5

24.5

28

32

34.5

125

160

235

445

615

800

985

1200

1.1

1.2

1.2

1.3

1.5

1.7

1.7

2.0

11.8

12.7

15.3

21.6

24.6

28.0

31.9

34.5

0.9

1.25

1.25

1.6

1.6

2.0

2.0

2.0

1.5

1.5

1.6

1.8

1.9

2.0

2.0

2.2

16.5

18

21

28.5

31.5

36

40

43

435

585

745

1315

1605

2160

2530

2905

Table 10 Individual Pair Screen

Instrumentation Cables

21

Multipair Cable

Conductorsize

No.of

pair

Insulationthickness

Nom.(mm)

PVC/PVC-PSLA(Non-armoured cable)

PVC/PVC/SWA/PVC-PSLA(Armoured cable)

Sheaththickness

Nom.(mm)

OveralldiameterApprox.(mm)

WeightApprox.(kg/km)

Beddingthickness

Nom.(mm)

Diameterover

beddingApprox.(mm)

Armourwire

diameterNom.(mm)

Sheaththickness

Nom.(mm)

OveralldiameterApprox.(mm)

WeightApprox.(kg/km)

1.0mm2

(1/1.13mm)

2

3

5

10

15

20

24

30

0.6

1.1

1.2

1.2

1.3

1.5

1.7

1.7

2.0

12

13

15.5

22

25

28

32

34.5

135

170

255

485

670

880

1080

1320

1.1

1.2

1.2

1.3

1.5

1.7

1.7

2.0

11.8

12.8

15.4

21.8

24.8

28.2

32.1

34.7

0.9

1.25

1.25

1.6

1.6

2.0

2.0

2.0

1.5

1.5

1.6

1.8

1.9

2.0

2.0

2.2

16.5

18.5

21

28.5

32

36

40

43

435

600

765

1360

1680

2265

2625

3025

1.0mm2

(7/0.43mm)

2

3

5

10

15

20

24

30

0.6

1.2

1.2

1.2

1.3

1.5

1.5

1.7

2.0

12.5

13.5

16

23

26

29.5

34

36.5

155

185

275

525

725

925

1170

1425

1.2

1.2

1.2

1.3

1.5

1.5

1.7

2.0

12.7

13.4

16.2

23.0

26.2

29.4

34.0

36.7

1.25

1.25

1.25

1.6

1.6

1.6

2.0

2.0

1.5

1.5

1.6

1.8

1.9

2.0

2.1

2.2

18

19

22

30

33

36.5

42

45

575

635

810

1455

1780

2115

2825

3225

1.5mm2

(7/0.53mm)

2

3

5

10

15

20

24

30

0.6

1.2

1.2

1.3

1.5

1.7

1.7

2.0

2.0

14

14.5

18

26

29.5

33

38

40.5

185

235

355

700

965

1235

1570

1850

1.2

1.2

1.3

1.5

1.7

1.7

2.0

2.0

13.8

14.7

18.0

25.8

29.3

32.8

38.1

40.4

1.25

1.25

1.6

1.6

2.0

2.0

2.0

2.5

1.6

1.6

1.7

1.9

2.0

2.1

2.2

2.4

19.5

20.5

24.5

33

37.5

41

46.5

50

650

720

1090

1730

2385

2830

3435

4245

Table 10 (Cont’d) Individual Pair Screen

Conductor sizeElectrical requirements

mm2

(no./mm)0.5

(1/0.80)0.5

(7/0.30)0.75

(1/0.96)0.75

(7/0.37)1.0

(1/1.13)1.0

(7/0.43)1.5

(7/0.53)

Conductor resistance at 20°C (Ω/km) Max. 36.8 36.7 25.0 25.0 18.4 18.5 12.3

Insulation resistance at 20°C (MΩ.km) Min. 25

Mutual capacitance at 1kHz (nF/km) Max. 250

Capacitance between any coreor screen at 1kHz (nF/km)

Max. 450

Inductance/Resistance ratio, L/R (µH/Ω) Max. 25 40

Test voltage for1 minute

core to core (kV) 1

1core to screen (kV)

Table 11 Electrical characteristic

FEC Cables (M) Sdn. Bhd.

22

Multipair Cable

Conductor

Insulation

Binder

Drain wire

Screen

Sheath

Multipair CableCross : Sectional Of Cable

PVC/PVC-PSLA INDIVIDUAL PAIR SCREEN (NON-ARMOURED CABLE)

Binder

Conductor

Insulation

Binder

Drain wire

Screen

Sheath

PVC/PVC/SWA/PVC-SLA COLLECTIVE SCREEN (ARMOURED CABLE)

Conductor

Insulation

Binder

Drain wire

Screen

Bedding

Armour

Oversheath

PVC/PVC/SWA/PVC-PSLA INDIVIDUAL PAIR SCREEN (ARMOURED CABLE)

Conductor

Insulation

Binder

Binder

Drain wire

Screen

Bedding

Armour

Oversheath

PVC/PVC-SLA COLLECTIVE SCREEN (NON-ARMOURED CABLE)

Instrumentation Cables

23

Applicable Standards

Multitriple Cable

BS 5308 Part 2 (Type 1 & Type 2)BS 6746 / BS 7655BS 6360 (IEC 60228)BS 4066 Part 1 (IEC60332-1) & IEC 60332-3 (if required)

Construction

Application

Temperature Rating

Abbreviations

Minimum Bending Radius

For transmission of analogue and digital signals in and around process plants in dry and damp industrial areas.(Non-armoured cables : not recommended for underground burial)

Non-armoured cable : During operation : 6 X Overall diameter : During installation : 8 X Overall diameterArmoured cable : During operation : 8 X Overall diameter : During installation : 10 X Overall diameter

During operation : -30°C up to +70°CDuring installation : -10°C up to +50°C

- PVC : Polyvinyl choloride- SLA : Aluminium/Polyester tape collective screen- SWA : Steel wire armour- TSLA : Aluminium/Polyester tape triple screen

Conductor : Plain annealed copper wires according to BS 6360 (IEC 60228)Insulation : PVC compound type TI1 according to BS 67�6/ BS 7655Colour code : White, Black and Red (numbering White core)Tripling : Cores twisted to triples Binder : Non-hygroscopic Polyester tapeDrain wire : Tinned annealed copper wire 0.5mm2 (1/0.80mm)Screen : Aluminium/Polyester tape approx. 0.022mm thick over Drain wireBedding (Inner sheath) : PVC compound type TM1 Black colour according to BS 67�6/ BS 7655, Flame retardant to BS �066

Part 1 (IEC 60332-1) or Low smoke, Non-halogen and Flame retardant thermoplastic compound (LSNHFR) to BS �066 Part 1&3 (IEC 60332-1&3) if required.

Armour : Galvanized Steel wiresSheath/Oversheath : PVC compoun type TM1 Black colour according to BS 67�6/BS 7655, Flame retardant to BS �066 Part

1 (IEC 60332-1) or Low smoke, Non-halogen and Flame retardant thermoplastic Compoun (LSNHFR) to BS �066 Part 1&3 (IEC 60332-1&3 if required.

Cable identification : Manufacturer’s name and voltage

Applicable Standards

FEC Cables (M) Sdn. Bhd.

2�

Conductorsize

No.of

pair

Insulationthickness

Nom.(mm)

PVC/PVC-SLA(Non-armoured cable)

PVC/PVC/SWA/PVC-SLA(Armoured cable)

Sheaththickness

Nom.(mm)

OveralldiameterApprox.(mm)

WeightApprox.(kg/km)

Beddingthickness

Nom.(mm)

Diameterover

beddingApprox.(mm)

Armourwire

diameterNom.(mm)

Sheaththickness

Nom.(mm)

OveralldiameterApprox.(mm)

WeightApprox.(kg/km)

0.50mm2

(1/0.80mm)

1235

101520

0.5

0.81.11.11.21.31.31.5

5.59.5

10.512.517.519.522.5

47105125190360480630

0.81.11.11.21.31.31.5

5.69.7

10.312.517.519.522.3

0.90.90.9

1.251.61.61.6

1.31.41.41.51.71.81.9

1014.5151824

26.529.5

205360395605

107012701535

0.50mm2

(7/0.30mm)

1235

101520

0.6

0.81.11.11.21.31.51.7

6.511

11.51420

22.526

55120150225425590770

0.81.11.11.21.31.51.7

6.311

11.614.220

22.725.8

0.90.90.9

1.251.61.62.0

1.31.51.51.61.71.81.9

10.516

16.520

26.529.533.5

230415455695

122014952010

0.75mm2

(1/0.96mm)

1235

101520

0.6

0.81.11.11.21.31.51.7

6.51112

14.520.523.526.5

61135170255490680895

0.81.11.11.21.31.51.7

6.411.211.914.520.523.326.5

0.90.90.9

1.251.61.62.0

1.31.51.51.61.81.81.9

1116

16.520

27.530

34.5

235430480740

131516102165

0.75mm2

(7/0.37mm)

1235

101520

0.6

0.81.11.21.21.31.51.7

6.51213

15.521.524.528

66145190280535750980

0.81.11.21.21.31.51.7

6.711.812.815.321.724.728.1

0.90.9

1.251.251.61.62.0

1.31.51.51.61.81.92.0

1116.518.521

28.531.536

250460610790

140517302330

1.0mm2

(1/1.13mm)

1235

101520

0.6

0.81.11.21.21.31.51.7

71213

15.52225

28.5

72160205310595835

1100

0.81.11.21.21.31.51.7

6.811.912.815.421.824.928.3

0.90.9

1.251.251.61.62.0

1.31.51.51.61.81.92.0

1116.518.521

28.532

36.5

255470630820

146018352470

1.0mm2

(7/0.43mm)

1235

101520

0.6

0.81.21.21.21.51.51.7

713

13.516.523.526.530

78180225335665905

1190

0.81.21.21.21.51.51.7

7.112.813.616.323.626.430

0.91.251.251.251.61.62.0

1.31.51.61.61.91.92.0

11.518.519.522

30.533.538

265600680870

161519552635

1.5mm2

(7/0.53mm)

1235

101520

0.6

0.81.21.21.31.51.71.9

814151826

29.533.5

100225290445875

12301615

0.81.21.21.31.51.71.9

7.814

14.918.226

29.533.5

0.91.251.251.61.62.02.0

1.41.61.61.71.92.02.1

12.519.520.52533

37.541.5

305695780

1180191526603220

Multitriple Cable

Table 12 Collective Screen

Instrumentation Cables

25

Conductorsize

No.of

pair

Insulationthickness

Nom.(mm)

PVC/PVC-TSLA(Non-armoured cable)

PVC/PVC/SWA/PVC-TSLA(Armoured cable)

Sheaththickness

Nom.(mm)

OveralldiameterApprox.(mm)

WeightApprox.(kg/km)

Beddingthickness

Nom.(mm)

Diameterover

beddingApprox.(mm)

Armourwire

diameterNom.(mm)

Sheaththickness

Nom.(mm)

OveralldiameterApprox.(mm)

WeightApprox.(kg/km)

0.50mm2

(1/0.80mm)

2

3

5

10

15

20

0.5

1.1

1.1

1.2

1.3

1.3

1.5

10.5

11

13.5

19.5

21.5

24.5

105

140

215

405

545

715

1.1

1.1

1.2

1.3

1.3

1.5

10.6

11.2

13.7

19.3

21.5

24.5

0.9

0.9

1.25

1.6

1.6

1.6

1.4

1.5

1.5

1.7

1.8

1.9

15

16

19

26

28.5

31.5

390

440

665

1180

1415

1705

0.50mm2

(7/0.30mm)

2

3

5

10

15

20

0.6

1.1

1.1

1.2

1.3

1.5

1.7

12

12.5

15.5

22

25

28.5

135

165

250

480

665

875

1.1

1.1

1.2

1.3

1.5

1.7

11.9

12.6

15.4

21.8

24.9

28.3

0.9

0.9

1.25

1.6

1.6

2.0

1.5

1.5

1.6

1.8

1.8

1.9

16.5

17.5

21

28.5

31.5

36

450

495

765

1370

1660

2240

0.75mm2

(1/0.96mm)

2

3

5

10

15

20

0.6

1.1

1.2

1.2

1.3

1.5

1.7

12

13

16

22.5

25.5

29

150

190

285

545

760

1000

1.1

1.2

1.2

1.3

1.5

1.7

12.1

13.1

15.8

22.4

25.5

29.0

0.9

1.25

1.25

1.6

1.6

2.0

1.5

1.5

1.6

1.8

1.9

2.0

17

18.5

21.5

29

32.5

37

470

630

810

1440

1790

2415

0.75mm2

(7/0.37mm)

2

3

5

10

15

20

0.6

1.2

1.2

1.2

1.5

1.5

1.7

13

14

16.5

24

27

30.5

170

210

310

620

835

1095

1.2

1.2

1.2

1.5

1.5

1.7

13

13.8

16.6

24.1

26.9

30.6

1.25

1.25

1.25

1.6

1.6

2.0

1.5

1.5

1.6

1.8

1.9

2.0

18.5

19.5

22.5

31

34

38.5

595

660

860

1575

1910

2575

1.0mm2

(1/1.13mm)

2

3

5

10

15

20

0.6

1.2

1.2

1.2

1.5

1.5

1.7

13

14

17

24

27

31

180

225

340

680

925

1215

1.2

1.2

1.2

1.5

1.5

1.7

13.1

13.9

16.8

24.2

27.1

30.9

1.25

1.25

1.25

1.6

1.6

2.0

1.5

1.5

1.6

1.8

1.9

2.0

18.5

19.5

22.5

31

34

39

615

690

890

1650

2015

2695

1.0mm2

(7/0.43mm)

2

3

5

10

15

20

0.6

1.2

1.2

1.2

1.5

1.5

1.7

13.5

14.5

17.5

25.5

28.5

32.5

195

245

370

735

1000

1310

1.2

1.2

1.2

1.5

1.5

1.7

13.7

14.6

17.7

25.6

28.7

32.6

1.25

1.25

1.25

1.6

1.6

2.0

1.5

1.6

1.6

1.9

2.0

2.1

19

20.5

23.5

32.5

36

41

645

730

945

1765

2165

2905

1.5mm2

(7/0.53mm)

2

3

5

10

15

20

0.6

1.2

1.2

1.3

1.5

1.7

1.9

15

16

19.5

28

32

36.5

245

310

485

955

1340

1760

1.2

1.2

1.3

1.5

1.7

1.9

15

16

19.6

28.2

32

36.4

1.25

1.25

1.6

1.6

2.0

2.0

1.6

1.6

1.7

1.9

2.1

2.3

20.5

21.5

26

35

40

45

755

835

1280

2090

2900

3550

Table 13 Individual Triple Screen

Multitriple Cable

FEC Cables (M) Sdn. Bhd.

26

Conductor sizeElectrical requirements

mm2

(no./mm)0.5

(1/0.80)0.5

(7/0.30)0.75

(1/0.96)0.75

(7/0.37)1.0

(1/1.13)1.0

(7/0.43)1.5

(7/0.53)

Conductor resistance at 20°C (Ω/km) Max. 36.8 36.7 25.0 25.0 18.4 18.5 12.3

Insulation resistance at 20°C (MΩ.km) Min. 25

Mutual capacitance at 1kHz (nF/km) Max. 250

Inductance/Resistance ratio, L/R (µH/Ω) Max. 25 40

Test voltage for1 minute

core to core (kV) 1

1core to screen (kV)

Multitriple Cable

Table 14 Electarical characteristics

Conductor

Insulation

Binder

Drain wire

Screen

Sheath Binder

Conductor

Insulation

Binder

Drain wire

Screen

Sheath

PVC/PVC/SWA/PVC-SLA COLLECTIVE SCREEN (ARMOURED CABLE)

Conductor

Insulation

Binder

Drain wire

Screen

Bending

Armour

Oversheath

PVC/PVC/SWA/PVC-TSLA INDIVIDUAL TRIPLE SCREEN (ARMOURED CABLE)

Conductor

Insulation

Binder

Binder

Drain wire

Screen

Bedding

Armour

Oversheath

Multitriple Cable - Cross-Sectional Of Cable

PVC/PVC-SLA COLLECTIVE SCREEN (NON-ARMOURED CABLE) PVC/PVC-TSLA INDIVIDUAL TRIPLE SCREEN (NON-ARMOURED CABLE)

27

Accreditations

FEC Cables (M) Sdn. Bhd.

Factory 1 : Persiaran Raja Muda, �0000 Shah Alam, Selangor Darul Ehsan, Malaysia.(P.O. Box 7006, �0700 Shah Alam) Tel : 603-5519 1110/3/�, 5519 1258, 5519 581�/5/7Fax : 603-5519 1296

Factory 2 : No. 16, Jalan Keluli 2, Bukit Raja Industrial Area, �0150 Klang, Selangor Darul Ehsan, Malaysia.Tel : 603-33�3 5837/9/�0, 33�3 7727Fax : 603-33�3 58�3, 33�3 9262

Sales Office :Persiaran Raja Muda, �0000 Shah Alam, Selangor Darul Ehsan, Malaysia.(P.O. Box 7006, �0700 Shah Alam) Tel : 603-5519 1110 (Hotline)Fax : 603-5519 1296, 5513 8688Website : www.furukawa.com.mye-mail : [email protected]

www.fec.com.my

(7293-W)

FEC Cables (M) Sdn. Bhd.

Fire Resistant Cables

CORPORATEHISTORY

INTRODUCTION OF

COMPANYWhen there is talk of high quality electric wires and cables, the one company that comes to mind is FEC Cables (Malaysia) Sdn. Bhd. FEC is a subsidiary of Permodalan Nasional Berhad and was formerly known as Furukawa Electric Cables (M) Sdn. Bhd. Having established its Shah Alam plant in 1967 on a 7-acre site at the Shah Alam Industrial Estate, Furukawa has come a long way.

The technical collaboration with our Japanese counterpart, Furukawa Japan, has brought about an amazing success for us. In terms of quality, we have climbed the ladders of product manufacturing, steadily and successfully, pushing FEC towards the pinnacle of excellence. Putting our customers’ demands and needs as our number one priority, we opened our second plant in 1995, on a 27-acre freehold land site in Bukit Raja Industrial area, Klang. In our quest for excellence, we equip the plant with the latest technological aids for the manufacture of a wide range of low and medium voltage cables.

The certification of the ISO 9001 for both plants only proves that we do not compromise on quality and customer satisfaction. Our dedicated and hard-working employees are the backbone of our success. This was greatly helped by the state-of-the-art technology equipment which has led us towards excellence.

Moving towards a new century, we pledge to continually strive towards progressive and dynamic growth as FEC Cables continues its efforts in contributing to the development Malaysia.

FEC Cables (M) Sdn. Bhd. was first established in 1967 and was previously known as Furukawa Electric Cables (M) Sdn. Bhd. In all the years until 2003, the company had been under the management and control of Furukawa Electric Co. Ltd. of Japan.

In 2003, the company was renamed FEC Cables (M) Sdn. Bhd. following the acquisition of its major equity stake by Permodalan Nasional Berhad, Malaysia’s government-owned premier multi-billion dollar investment institution.

The Company had started a technical collaboration from world renowned cable manufacturer, The Furukawa Electric Co. Ltd Japan (Furukawa Japan).

FEC Cables has benefited enormously from the technical collaboration and the subsequent technology transfer with Furukawa Japan. FEC Cables inherited from Furukawa Japan not only its advanced technology and technical know-how but also the disciplines of producing quality products using material conforming to the international standards of manufacturing cables.

Today FEC Cables plays a prominent role as a forerunner in the cable industry.

FEC Cables has been actively involved in serving various industrial sectors, namely the power, telecommunications, construction as well as the oil and gas sectors.

Fire Resistant Cables

Table Of Contents

INTRODUCTION 5FIRE TEST PHOTO 5APPLICATIONS 6APPLICABLE STANDARDS - SPECIFICATIONS 7KPA FIRE RESISTANT CABLE 9-15 KPA-1 & KPA 2 - NON-ARMOURED CABLES 600/1000 V KPA-1 & KPA 2 - ARMOURED CABLES 600/1000 V

KPA-3 - NON-ARMOURED CABLES 300/500 V FT-8 FIRE RESISTANT CABLE 16-21 FT-8 - NON-ARMOURED CABLES 600/1000 V FT-8 - ARMOURED CABLES 600/1000 V FT-8 - NON-ARMOURED CABLES 300/500 VMIFR FIRE RESISTANT CABLE 22-27 MIFR - NON-ARMOURED CABLES 600/1000 V MIFR - ARMOURED CABLES 600/1000 V MIFR - NON-ARMOURED CABLES �50/750 VTECHNICAL DATA 28

FIRE RESISTANT CABLES

5

INTRODUCTION

ApplicationsThe FEC’s Fire Resistant Cables are specially designed to maintain circuit integrity in a fire, conforming with BS 6387 categories C,W and Z. It’s widely use for the installation of safety systems, including lift, smoke exhaust, smoke and fire shutter, fire alarms, emergency lighting, PA systems, hydrants and emergency power supply which used in wide variety of public access building and industrial complexes. For example project using FEC fire resistant cables are Putrajaya and Petronas Twin Tower.

Quality FEC fire resistant cables are manufactured under an ISO 9001 quality system certified by BVQI. We also obtained approval from other accreditation bodies such as BOMBA, SIRIM, JKR, PETRONAS and PSB of Singapore. This proves that we do not compromise on quality and customer satisfaction. Our policy is to meet the requirements of customers by continually :• Upgrading the skills and productivity of our human resources• Maintaining the equipment and factory in peak form and performance• Sourcing cost effective materials• Improving and effectively implementing our quality management system in accordance to ISO 9001:2000 standard• Maintaining a harmonious workforce which is dedicated and committed to production of quality cables.

We believe in giving the best ! There is no compromise !

Fire Resistant Cable – Keeps a Safety of Human Life…Fire in high rise in urban area are recently becoming a big social problem throughout the world. Major accidents as occurred in the past which have resulted in the deaths of many people would have been avoided if there had been effective fire preventive feature designed and installed to minimize such injuries and damages and to save and protect human life and properties.

FIRE TEST PHOTO

Fire Test Category CWZ (BS6387) And Flame Propagation Test (IEC 60332-3 Cat. A,B,C)

FIRE TEST CATEGORY C FIRE AND WATER TEST CATEGORY W

FIRE AND IMPACT TEST CATEGORY Z

CABLES DURING IEC 60332PART 3 TEST

HistorySince 1985, FEC Cables were the first cable manufacturer to manufacture fire resistant cables in Malaysia. With 20 years of knowledge and experience in designing and manufacturing of Fire Resistant Cables, now we provide complete product range complying with industry standard and applications, including instrumentation, control and low voltage power cables. For safeguarding the human life and as well as protecting the equipment, FEC’s FireResistant Cables when burnt during a fire, produce very low quantities of smoke and acidic gases.

FEC Cables (M) Sdn. Bhd.

6

Lift

Smoke Exhaust Fire Exhaust Equipment

Smoke and Fire Shutter

Emergency Announcing Equipment

Emergency Guide Lamp

Emergency Plug Socket

Hydrant Equipment

Emergency Power Supply

APPLICATIONS

FIRE RESISTANT CABLES

7

APPLICABLE STANDARDS - SPECIFICATIONS

Fire Resistant Test

BS 6387, SS 299 Pt. 1, IEC 60331Specification for performance requirements for cables required to maintain circuit integrity under fire conditions.

Resistant to fire alone (BS 6387, SS 299)Category A - Cables are subjected to fire at 650°C for 3 hoursCategory B - Cables are subjected to fire at 750°C for 3 hoursCategory C - Cables are subjected to fire at 950°C for 3 hours

Note : For IEC 60331, cables are subjected to fire at 750°C for 3 hours. In not less than 12 hours after the test, the cable shall again be energized, and there shall not be any breakdown.

Resistant to fire with waterCategory W - Cables are subjected to fire at 650°C for 15 minutes, then water spray and falme for further 15 minutes.

Resistant to fire with mechanical shock (BS 6387, SS 299)Category X - Cables are subjected to fire at 650°C with mechanical shock for 15 mins.Category Y - Cables are subjected to fire at 750°C with mechanical shock for 15 mins.Category Z - Cables are subjected to fire at 950°C with mechanical shock for 15 mins.

During the test, the flame and test voltage shall be applied continuosly for a period of 3hours and no 3A fuse shall ruptured.

IEC 60332-1Tests on a single vertical insulated wire or cable.

IEC 60332-3Tests for vertical flame spread of vertically mounted bunched wires and cables.

Category A - 7 litres of combustible material per meter shall be bunched on a ladder exposed to flame for �0 minutes.Category B - 3.5 litres of combustible material per meter shall be bunched on a ladder exposed to flame for �0 minutes.Category C - 1.5 litres of combustible material per meter shall be bunched on a ladder exposed to flame for 20 minutes.

The cables specimens are placed vertically next to each other and than exposed to flame for a specific period of time. After the burning has ceased, the charred portion should not exceed a height of 2.5 meters.

Flame Retardant Test

Fire Resistanttested to

IEC 60331/SS 299/

BS 6387 CWZ

Flame Retardanttested to

IEC 60332 - 1&3 Cat. ABC

Zero Halogentested to

IEC 6075� - 1&2

Low SmokeEmissiontested toIEC 6103�

100˚C

50˚C

0˚C

110˚C

TemperatureRange

-25 ~ + 90°C

Acid GasEmission

Anti Termite& Rodent

FEC Cables (M) Sdn. Bhd.

8

APPLICABLE STANDARDS - SPECIFICATION

Smoke Emission Test

Acid Gas Emission Test

IEC 61034Measurement of smoke density of electric cables burning under defined conditions.

A one meter length of sample cable is placed in a 3m smoke chamber. Sample of cable are subjected to the flame of burning alcohol. A smoke is then produced within the chamber is measured by a photocell. The minimum light transmittance is recorded and the minimum value is 60% is acceptable.

General Standards

IEC 60754-1 Determination of the amount of halogen acid gas evolved during combustion of material from cables.

IEC 60754-2Determination of degree of acidity of gases evolved during combustion of materials taken from electric cables by measuring pH and conductivity.

This standard requires the weighted pH value should not be less than �.3 when related to 1 litre of water and the weighted value of conductivity should not exceed 10µS/mm.

IEC 60502-1Power cable with extruded insulation and their accessories for rated voltages from 1 kV up to 30 kV.

BS 6004PVC insulated cables for electrical power and lighting.

Fire Resistanttested to

IEC 60331/SS 299/

BS 6387 CWZ

Flame Retardanttested to

IEC 60332 - 1&3 Cat. ABC

Zero Halogentested to

IEC 6075� - 1&2

Low SmokeEmissiontested toIEC 6103�

100˚C

50˚C

0˚C

110˚C

TemperatureRange

-25 ~ + 90°C

Acid GasEmission

Anti Termite& Rodent

FIRE RESISTANT CABLES

9

FIRE RESISTANT CABLES

9

KPA FIRE RESISTANT CABLE

Cable Construction for KPA-1 & KPA-2

Core Identification

(1) PE Insulated, PVC FR Sheathed - 600/1000V (KPA-1) (2) PE Insulated, LSNHFR Sheathed - 600/1000V (KPA-2)

1. Conductor : Plain Annealed Copper Wires, circular non-compacted or compacted stranded.2. Fire Proof Layer : Mica Tape.3. Insulation : Extruded Polyethylene (PE) �. Filler : Non-hygroscopic fillers ( If necessary).5. Binder Tape : Non-hygroscopic tape.6. Sheath : Extruded Flame Retardant PVC or Low Smoke Non-halogen Flame Retardant (Inner Sheath) Thermoplastic.7. Armouring : Multi-core - Galvanized Steel Wire Single-core - Hard Drawn Aluminium Wire 8. Outer Sheath : Extruded Flame Retardant PVC or Low Smoke Non-halogen Flame Retardant Thermoplastic.

Single-core : Natural or Black2 – core : Red , Black3 – core : Red , Yellow , Blue� – core : Red , Yellow , Blue , Black5 – core and above : Black , White ( Numbering – black printing on white core)

Note : Other colour combination as per requirements. LSNHFR – Low Smoke Non-halogen Flame Retardant KPA-1(750°C) are fully complies to IEC 60331, IEC 60332-1 KPA-1(950°C) are fully complies to IEC 60331, IEC 60332-1, BS 6387, SS 299-1 KPA-2(750°C) are fully complies to IEC 60331, IEC 60332-1, IEC 6103�, IEC 6075� KPA-2(950°C) are fully complies to IEC 60331, IEC 60332-1, BS 6387, SS 299-1, IEC 6103�, IEC 6075�

1

2

3

4

5

67

8

FEC Cables (M) Sdn. Bhd.

10

KPA FIRE RESISTANT CABLE

(3) PE Insulated, PVC FR Sheathed - 300/500V (KPA-3)

Cable Construction for KPA-3

1. Conductor : Plain Annealed Copper Wires, circular non-compacted.2. Fire Proof Layer : Mica Tape.3. Insulation : Extruded Polyethylene (PE).�. Sheath : Extruded Flame Retardant PVC.5. Protective Earth 5.1. Conductor : Plain Annealed Copper Wires, circular non compacted. 5.2. Insulation : Extruded Polyethylene (PE)

Core Indentication

Single-core : Natural or Black 2 – core : Red , Black3 – core : Red , Yellow , Blue� – core : Red , Yellow , Blue , Black5 – core and above : Black , White ( Numbering – black printing on white core)Protective Earth : Green

Note : Other colour combination as per requirements. KPA-3 are fully complies to IEC 60331, IEC 60332-1

123

4

5

FIRE RESISTANT CABLES

11

KPA -1 & KPA-2: NON-ARMOURED CABLES 600/1000V

Table 1 : Single - Core (1C)

Conductor Size(mm²)

Insulation Nom. Thickness (mm)

Insulation Nom. Thickness (mm)

Approx. Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1.5 0.8 1.4 7 60

2.5 0.8 1.4 7.5 75

4 1.0 1.4 8.5 100

6 1.0 1.4 9 120

10 1.0 1.4 9.5 160

16 1.0 1.4 10.5 230

25 1.2 1.4 12 330

35 1.2 1.4 13.5 430

50 1.4 1.4 15 570

70 1.4 1.4 16.5 780

95 1.6 1.5 19 1050

120 1.6 1.5 20.5 1300

150 1.8 1.6 22.5 1550

185 2.0 1.7 24.5 1950

240 2.2 1.8 28 2500

300 2.4 1.9 30.5 3100

400 2.6 2.0 34 4050

500 2.8 2.1 38 5050

630 2.8 2.2 42 6450

800 2.8 2.3 48.5 8100

1000 3.0 2.5 54 10200

Table 2 : Two - Core (2C)

Conductor Size(mm²)

Insulation Nom. Thickness

(mm)

Outer Sheath Nom. Thickness

(mm)

Approx. Overall Diameter

(mm)

Approx. Overall Diameter

(mm)

1.5 0.8 1.8 11.5 130

2.5 0.8 1.8 12.5 160

� 1.0 1.8 1�.5 220

6 1.0 1.8 15.5 280

10 1.0 1.8 17 380

16 1.0 1.8 18.5 520

25 1.2 1.8 22 750

35 1.2 1.8 2� 980

50 1.� 1.8 27 1,250

70 1.� 1.9 30.5 1,700

95 1.6 2.0 35.5 2,350

120 1.6 2.1 38.5 2,900

150 1.8 2.2 �3 3,600

185 2.0 2.� �7 �,�00

2�0 2.2 2.5 53 5,600

300 2.� 2.7 58.5 7,000

FEC Cables (M) Sdn. Bhd.

12

Table 3 : Three-Core (3C)

KPA-1 & KPA-2: NON-ARMOURED CABLES 600/1000V

Conductor Size(mm²)

Insulation Nom. Thickness (mm)

Outer Sheath Nom. Thickness (mm)

Approx. Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1.5 0.8 1.8 12.5 160

2.5 0.8 1.8 13 200

4 1.0 1.8 15.5 280

6 1.0 1.8 16.5 360

10 1.0 1.8 18 500

16 1.0 1.8 20 690

25 1.2 1.8 23.5 1,000

35 1.2 1.8 25.5 1,300

50 1.4 1.8 29 1,700

70 1.4 1.9 32.5 2,400

95 1.6 2.1 38 3,300

120 1.6 2.2 41 4,100

150 1.8 2.3 46 5,000

185 2.0 2.5 50.5 6,300

240 2.2 2.7 57 8,000

300 2.4 2.8 62.5 9,900

Table 4 : Four - Core (4C)

Conductor Size(mm²)

Insulation Nom. Thickness (mm)

Outer Sheath Nom. Thickness (mm)

Approx. Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1.5 0.8 1.8 13.5 200

2.5 0.8 1.8 14.5 250

4 1.0 1.8 16.5 350

6 1.0 1.8 18 450

10 1.0 1.8 19.5 630

16 1.0 1.8 22 890

25 1.2 1.8 25.5 1,300

35 1.2 1.8 28.5 1,700

50 1.4 1.9 32 2,300

70 1.4 2.0 36.5 3,150

95 1.6 2.2 42 4,300

120 1.6 2.3 46 5,400

150 1.8 2.5 51.5 6,600

185 2.0 2.6 56 8,200

240 2.2 2.9 63.5 10,400

300 2.4 3.1 70 13,100

FIRE RESISTANT CABLES

13

KPA-1 & KPA-2: ARMOURED CABLES 600/1000V

Table 5 : Single - Core (1C)

Conductor Size(mm²)

Insulation Nom. Thickness (mm)

Inner Sheath Nom. Thickness (mm)

Approx. Diameter Over Inner Sheath(mm)

Armour Wire Nom. Diameter (mm)

Outer Sheath Nom. Thickness (mm)

Approx. Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1.5 0.8 1.0 6 0.90 1.8 11.5 150

2.5 0.8 1.0 6.5 0.90 1.8 12 170

4 1.0 1.0 7.5 0.90 1.8 13 210

6 1.0 1.0 8 0.90 1.8 13.5 240

10 1.0 1.0 8.5 0.90 1.8 14 290

16 1.0 1.0 9.5 0.90 1.8 15 360

25 1.2 1.0 11 0.90 1.8 16.5 480

35 1.2 1.0 12 1.25 1.8 18.5 630

50 1.4 1.0 13.5 1.25 1.8 20 790

70 1.4 1.0 15.5 1.25 1.8 21.5 1,000

95 1.6 1.0 17.5 1.60 1.8 24.5 1,350

120 1.6 1.0 19 1.60 1.8 26 1,550

150 1.8 1.0 21 1.60 1.8 28 1,900

185 2.0 1.0 23 1.60 1.9 30 2,300

240 2.2 1.0 26 1.60 1.9 33 2,850

300 2.4 1.0 28.5 2.00 2.1 36.5 3,600

400 2.6 1.2 32 2.00 2.2 40.5 4,600

500 2.8 1.2 36 2.00 2.3 44.5 5,650

630 2.8 1.2 39.5 2.50 2.4 49.5 7,250

800 2.8 1.4 46.5 2.50 2.6 57 9,200

1000 3.0 1.4 51.5 2.50 2.7 62 11,400

Table 6 : Two - Core (2C)

Conductor Size(mm²)

Insulation Nom. Thickness (mm)

Inner Sheath Nom. Thickness (mm)

Approx. Diameter Over Inner Sheath

(mm)

Armour Wire Nom. Diameter (mm)

Outer Sheath Nom. Thickness (mm)

Approx. Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1.5 0.8 1.0 10.5 0.90 1.8 15.5 400

2.5 0.8 1.0 11.5 0.90 1.8 16.5 450

4 1.0 1.0 13 0.90 1.8 18 550

6 1.0 1.0 14.5 1.25 1.8 20 730

10 1.0 1.0 15.5 1.25 1.8 21.5 870

16 1.0 1.0 17.5 1.25 1.8 23.5 1,050

25 1.2 1.0 20.5 1.60 1.8 27 1,500

35 1.2 1.0 23 1.60 1.8 29.5 1,800

50 1.4 1.0 26 1.60 1.9 32.5 2,200

70 1.4 1.0 29 2.00 2.0 36.5 3,000

95 1.6 1.2 34 2.00 2.2 42 3,900

120 1.6 1.2 37 2.00 2.3 45 4,600

150 1.8 1.2 41 2.50 2.4 50.5 5,800

185 2.0 1.4 45 2.50 2.6 55 7,000

240 2.2 1.4 51 2.50 2.8 61 8,500

300 2.4 1.6 56.5 2.50 2.9 67 10,200

FEC Cables (M) Sdn. Bhd.

1�

KPA-1 & KPA-2: ARMOURED CABLES 600/1000V

Table 7 : Three-Core (3C)

Conductor Size(mm²)

Insulation Nom. Thickness (mm)

Inner Sheath Nom. Thickness (mm)

Approx. Diameter Over Inner Sheath(mm)

Armour Wire Nom. Diameter (mm)

Outer Sheath Nom. Thickness (mm)

Approx. Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1.5 0.8 1.0 11 0.90 1.8 16 440

2.5 0.8 1.0 12 0.90 1.8 17 500

4 1.0 1.0 14 1.25 1.8 19.5 720

6 1.0 1.0 15 1.25 1.8 21 830

10 1.0 1.0 16.5 1.25 1.8 22.5 1,000

16 1.0 1.0 19 1.25 1.8 24.5 1,200

25 1.2 1.0 22 1.60 1.8 28.5 1,800

35 1.2 1.0 24.5 1.60 1.8 31 2,200

50 1.4 1.0 27.5 1.60 2.0 34.5 2,800

70 1.4 1.2 31.5 2.00 2.1 39.5 3,900

95 1.6 1.2 36.5 2.00 2.2 44.5 5,000

120 1.6 1.2 39.5 2.00 2.3 48 5,900

150 1.8 1.4 44.5 2.50 2.5 54 7,500

185 2.0 1.4 48.5 2.50 2.7 58.5 9,000

240 2.2 1.6 55 2.50 2.9 65.5 11,100

300 2.4 1.6 60.5 2.50 3.1 71.5 13,300

Table 8 : Four - Core (4C)

Conductor Size(mm²)

Insulation Nom. Thickness (mm)

Inner Sheath Nom. Thickness (mm)

Approx. Diameter Over Inner Sheath(mm)

Armour Wire Nom. Diameter (mm)

Outer Sheath Nom. Thickness (mm)

Approx. Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1.5 0.8 1.0 12 0.90 1.8 17 500

2.5 0.8 1.0 13 0.90 1.8 18 570

4 1.0 1.0 15.5 1.25 1.8 21 840

6 1.0 1.0 16.5 1.25 1.8 22.5 970

10 1.0 1.0 18.5 1.25 1.8 24 1,200

16 1.0 1.0 21 1.60 1.8 27 1,600

25 1.2 1.0 24.5 1.60 1.8 31 2,200

35 1.2 1.0 27 1.60 1.9 33.5 2,700

50 1.4 1.2 31 2.00 2.1 39 3,700

70 1.4 1.2 35 2.00 2.2 43 4,800

95 1.6 1.2 40.5 2.50 2.4 50 6,600

120 1.6 1.4 44.5 2.50 2.5 54 7,900

150 1.8 1.4 49.5 2.50 2.7 59.5 9,400

185 2.0 1.6 54.5 2.50 2.8 64.5 11,200

240 2.2 1.6 61 2.50 3.1 72 13,900

300 2.4 1.6 67.5 3.15 3.3 80 17,700

FIRE RESISTANT CABLES

15

KPA -3: NON-ARMOURED CABLES 300/500V

Table 9

No of CoreConductor Size

(mm²) Insulation Nom. Thickness

(mm)Outer Sheath Nom. Thickness

(mm)Approx. Overall Diameter

(mm)Approx. Overall Weight

(kg/km)

1C1.52.54

0.55 0.54

4.55.5

254055

2C1.52.54

0.55 0.578

9.5

70100140

3C1.52.54

0.55 0.57.59

10

90130180

4C1.52.54

0.55 0.58.59.511

110160230

2C + P.E1.52.54

0.55 0.57.59

10

90130190

3C + P.E1.52.54

0.55 0.58.59.511

110160240

4C + P.E1.52.54

0.55 0.59.5

10.512

130200290

P.E : Protective Earth core

FEC Cables (M) Sdn. Bhd.

16

FT-8 FIRE RESISTANT CABLE

Cable Construction for FT-8

1. Conductor : Plain Annealed Copper Wires, circular non-compacted or compacted stranded.2. Fire Proof Layer : Mica Tape.3. Insulation : Extruded Cross-linked Polyethylene (XLPE).�. Filler : Non-hygroscopic fillers ( If necessary).5. Binder Tape : Non-hygroscopic tape.6. Sheath : Extruded Low Smoke Non-halogen Flame Retardant Thermoplastic (Inner Sheath) 7. Armouring : Multi-core - Galvanized Steel Wire Single-core - Hard Drawn Aluminium Wire 8. Outer Sheath : Extruded Low Smoke Non-halogen Flame Retardant Thermoplastic

Core Identification

Single-core : Natural or Black2 – core : Red , Black3 – core : Red , Yellow , Blue� – core : Red , Yellow , Blue , Black5 – core and above : Black , White ( Numbering – black printing on white core)

Note : Other colour combination as per requirements. FT-8 Cables are fully complies to BS 6387, SS 299-1, IEC 60331, IEC 60332-1, IEC 6103�, IEC 6075�

1

3

4

5

6

7

8

2

XLPE Insulated, LSNHFR Sheathed – 600/1000V

FIRE RESISTANT CABLES

17

FT-8: NON-ARMOURED CABLES 600/1000V

Conductor Size(mm²)

Insulation Nom. Thickness (mm)

Outer Sheath Nom. Thickness (mm)

Approx. Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1.52.546

10162535507095

120150185240300400500630800

1000

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.02.22.42.62.8

1.41.41.41.41.41.41.41.41.41.41.51.51.61.61.71.81.92.02.22.32.4

77.58

8.59

1011.512.51416

17.519.521.523.526.529

32.536.541

48.553.5

607090

110160220320420550760

1,0001,2501,5501,9002,4503,0503,9504,9506,4008,100

10,150

Table 10 : Single - Core (1C)

Table 11 : Two - Core (2C)

Conductor Size(mm²)

Insulation Nom. Thickness (mm)

Outer Sheath Nom. Thickness (mm)

Approx. Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1.52.546

10162535507095

120150185240300

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

1.81.81.81.81.81.81.81.81.81.81.92.02.22.32.52.6

11.512.513.515

16.518.521.524

26.530

33.537

41.546

51.556.5

140170210260370510740960

1,2001,7002,2502,8503,5004,3505,5506,900

FEC Cables (M) Sdn. Bhd.

18

FT-8: NON-ARMOURED CABLES 600/1000V

Table 12 : Three - Core (3C)

Table 13 : Four - Core (4C)

Conductor Size(mm²)

Insulation Nom. Thickness (mm)

Outer Sheath Nom. Thickness (mm)

Approx. Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1.52.546

10162535507095

120150185240300

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

1.81.81.81.81.81.81.81.81.81.92.02.12.32.42.62.7

12.513.514.515.517.519.523

25.5283236

39.544.549.555.561

160200260340480680

1,0001,3001,7002,4003,2004,0004,9506,1507,8509,750

Conductor Size(mm²)

Insulation Nom. Thickness (mm)

Outer Sheath Nom. Thickness (mm)

Approx. Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1.52.546

10162535507095

120150185240300

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

1.81.81.81.81.81.81.81.81.82.02.12.32.42.62.83.0

13.514.515.51719

21.525.528313640

44.549.5556268

200250330420610870

1,2501,7002,2003,1004,2005,3006,5008,100

10,30012,850

FIRE RESISTANT CABLES

19

FT-8: ARMOURED CABLES 600/1000V

Table 14 : Single - Core (1C)

Conductor Size(mm²)

Insulation Nom. Thickness (mm)

Inner Sheath Nom. Thickness (mm)

Approx. Diameter Over Inner Sheath(mm)

Armour Wire Nom. Diameter (mm)

Outer Sheath Nom. Thickness (mm)

Approx. Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1.52.546

10162535507095

120150185240300400500630800

1000

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.02.22.42.62.8

1.01.01.01.01.01.01.01.01.01.01.01.01.01.01.01.01.21.21.21.41.4

5.56

6.57.589

10.511.513

14.516.51820222527

30.534.538.54651

0.900.900.900.900.900.900.900.901.251.251.251.601.601.601.601.602.002.002.002.502.50

1.81.81.81.81.81.81.81.81.81.81.81.81.81.81.91.92.12.22.32.52.7

1111.512.513

13.514.516171921

22.525272932

34.53943

47.556

61.5

150170200230280350470580760

1,0001,2501,5501,8502,3002,8503,4504,5505,6507,1009,150

11,400

Table 15 : Two - Core (2C)

Conductor Size

(mm²)

Insulation Nom. Thickness (mm)

Inner Sheath Nom. Thickness (mm)

Approx. Diameter Over Inner Sheath

(mm)

Armour Wire Nom. Diameter (mm)

Outer Sheath Nom. Thickness (mm)

Approx. Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1.52.546

10162535507095

120150185240300

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

1.01.01.01.01.01.01.01.01.01.01.21.21.21.41.41.6

10.511.512.513.515.517.520.522.525

28.532.535.540

44.549.555

0.900.900.900.901.251.251.601.601.601.602.002.002.002.502.502.50

1.81.81.81.81.81.81.81.81.82.02.12.22.32.52.72.8

15.516.517.518.521232729

31.535.540.54448546065

400450520600840

1,0001,4501,7502,1502,7503,7504,5005,3006,8508,300

10,000

FEC Cables (M) Sdn. Bhd.

20

FT-8: ARMOURED CABLES 600/1000V

Table 16 : Three - Core (3C)

Conductor Size(mm²)

Insulation Nom. Thickness (mm)

Inner Sheath Nom. Thickness (mm)

Approx. Diameter Over Inner Sheath

(mm)

Armour Wire Nom. Diameter (mm)

Outer Sheath Nom. Thickness (mm)

Approx. Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1.52.546

10162535507095

120150185240300

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

1.01.01.01.01.01.01.01.01.01.01.21.21.41.41.61.6

111213

14.516.518.521.52427

30.5353843

47.553.559

0.900.900.901.251.251.251.601.601.602.002.002.002.502.502.502.50

1.81.81.81.81.81.81.81.81.92.02.22.32.52.62.83.0

16171820222428

30.533.538.543

46.553

57.564

69.5

440500590790990

1,2001,8002,2002,7003,7504,8005,7507,4008,850

10,90013,100

Table 17 : Four - Core (4C)

Conductor Size(mm²)

Insulation Nom. Thickness (mm)

Inner Sheath Nom. Thickness (mm)

Approx. Diameter Over Inner Sheath

(mm)

Armour Wire Nom. Diameter (mm)

Outer Sheath Nom. Thickness (mm)

Approx. Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1.52.546

10162535507095

120150185240300

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

1.01.01.01.01.01.01.01.01.01.21.21.41.41.41.61.6

1213

14.51618

20.524

26.530

34.538.5434853

59.565.5

0.900.901.251.251.251.601.601.601.602.002.002.502.502.502.502.50

1.81.81.81.81.81.81.81.92.02.22.32.52.62.83.03.2

171820

21.523.527

30.533.536.542.547

52.558

63.570.576.5

500570780920

1,1501,6002,1502,7003,3004,7006,0007,7009,150

11,10013,65016,550

FIRE RESISTANT CABLES

21

FT-8: NON-ARMOURED CABLES 300/500V

Table 18

P.E : Protective Earth core

No of Core Conductor Size (mm²)

Insulation Nom. Thickness (mm)

Outer Sheath Nom. Thickness (mm)

Approx.Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1C1.52.54

0.55 0.54.55

5.5

354560

2C1.52.54

0.55 0.59

1011

85100140

3C1.52.54

0.55 0.59.5

10.512

100140190

4C1.52.54

0.55 0.510.511.513

130170250

2C + P.E1.52.54

0.55 0.59.5

10.512

100130190

3C + P.E1.52.54

0.55 0.510.511.513

130170240

4C + P.E1.52.54

0.55 0.511.513

14.5

160210300

FEC Cables (M) Sdn. Bhd.

22

MIFR FIRE RESISTANT CABLE

Cable Construction for MIFR

1. Conductor : Plain Annealed Copper Wires, circular non-compacted or compacted stranded.2. Fire Proof Layer : Mica Tape.3. Insulation : Extruded Flame Retardant Cross-linked Polyethylene (XLPEFR).�. Filler : Non-hygroscopic fillers (If necessary).5. Binder Tape : Non-hygroscopic tape.6. Sheath : Extruded Low Smoke Non-halogen Flame Retardant Mineral Filled compound. (Inner Sheath) 7. Armouring : Multi-core - Galvanized Steel Wire Single-core - Hard Drawn Aluminium Wire 8. Outer Sheath : Extruded Low Smoke Non-halogen Flame Retardant Mineral Filled compound.

Core Identification

Single-core : Natural or Black2 – core : Red , Black3 – core : Red , Yellow , Blue� – core : Red , Yellow , Blue , Black5 – core and above : Black , White ( Numbering – black printing on white core)

Note : Other colour combination as per requirements. MIFR Cables are fully complies to BS 6387, SS 299-1, IEC 60331, IEC 60332-3(A,B,C), IEC 60332-1, IEC 6103�, IEC 6075� For �50/750V Cables, the insulation colour as per requirements.

1

3

4

5

6

7

8

2

XLPEFR Insulated, LSNHFR Sheathed – 600/1000VXLPEFR Insulated, Non-Sheathed Cables – 450/750V

FIRE RESISTANT CABLES

23

MIFR: NON-ARMOURED CABLES 600/1000V

Table 19 : Single - Core (1C)

Conductor Size(mm²)

Insulation Nom. Thickness (mm)

Outer Sheath Nom. Thickness (mm)

Approx. Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1.52.546

10162535507095

120150185240300400500630800

1000

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.02.22.42.62.8

1.41.41.41.41.41.41.41.41.41.41.51.51.61.61.71.81.92.02.22.32.4

7.58

8.59

9.510.51213

14.516.51820222427

29.53337

41.54954

7585

100130180240350450590810

1,0501,3001,6002,0002,5503,2004,1005,1506,6008,350

10,500

Table 20 : Two - Core (2C)

Conductor Size(mm²)

Insulation Nom. Thickness (mm)

Outer Sheath Nom. Thickness (mm)

Approx. Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1.52.546

10162535507095

120150185240300

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

1.81.81.81.81.81.81.81.81.81.81.92.02.22.32.52.6

1212.513.515161821

23.526

29.533

36.541

45.551

56.5

160190230290390540780

1,0001,2501,7502,3502,9003,6004,5005,7507,100

FEC Cables (M) Sdn. Bhd.

2�

MIFR: NON-ARMOURED CABLES 600/1000V

Table 21 : Three - Core (3C)

Conductor Size(mm²)

Insulation Nom. Thickness (mm)

Outer Sheath Nom. Thickness (mm)

Approx. Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1.52.546

10162535507095

120150185240300

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

1.81.81.81.81.81.81.81.81.81.92.02.12.32.42.62.7

12.513.514.515.517

19.522.525

27.532

35.539.544.54955

60.5

190230300370510720

1,0501,3501,7502,4503,3004,1505,1006,4008,100

10,050

Table 22 : Four - Core (4C)

Conductor Size(mm²)

Insulation Nom. Thickness (mm)

Outer Sheath Nom. Thickness (mm)

Approx. Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1.52.546

10162535507095

120150185240300

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

1.81.81.81.81.81.81.81.81.82.02.12.32.42.62.83.0

13.514.515.517192125

27.530.535.539.54449

54.561.567.5

230280370470650920

1,3501,7502,3003,2504,3505,4506,7008,400

10,65013,250

FIRE RESISTANT CABLES

25

MIFR: ARMOURED CABLES 600/1000V

Table 23 : Single - Core (1C)

Conductor Size(mm²)

Insulation Nom. Thickness (mm)

Insulation Nom. Thickness (mm)

Approx. Diameter Over Inner Sheath

(mm)

Armour Wire Nom. Diameter (mm)

Outer Sheath Nom. Thickness (mm)

Approx. Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1.52.546

10162535507095

120150185240300400500630800

1000

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.02.22.42.62.8

1.01.01.01.01.01.01.01.01.01.01.01.01.01.01.01.01.21.21.21.41.4

5.56

6.57.589

10.511.513

14.516.51820222527

30.534.538.54651

0.900.900.900.900.900.900.900.901.251.251.251.601.601.601.601.602.002.002.002.502.50

1.81.81.81.81.81.81.81.81.81.81.81.81.81.81.91.92.12.22.32.52.7

1111.512.513

13.514.516171921

22.525272932

34.53943

47.556

61.5

160180210240290370490610790

1,0001,3001,6001,9502,3502,9503,5504,7005,8007,3009,450

11,700

Table 24 : Two - Core (2C)

Conductor Size

(mm²)

Insulation Nom. Thickness (mm)

Insulation Nom. Thickness (mm)

Approx. Diameter Over Inner Sheath

(mm)

Armour Wire Nom. Diameter

(mm)

Outer Sheath Nom. Thickness (mm)

Approx. Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1.52.546

10162535507095

120150185240300

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

1.01.01.01.01.01.01.01.01.01.01.21.21.21.41.41.6

10.511.512.513.515172022

24.528.532

35.539.544

49.554.5

0.900.900.900.901.251.251.601.601.601.602.002.002.002.502.502.50

1.81.81.81.81.81.81.81.81.82.02.12.22.32.52.72.8

15.516.517.518.520.522.526.528.5313540

43.54854

59.565

430480550630870

1,0501,5001,8002,2002,8003,8504,5505,4007,0508,550

10,200

FEC Cables (M) Sdn. Bhd.

26

MIFR: ARMOURED CABLES 600/1000V

Table 25 : Three - Core (3C)

Conductor Size(mm²)

Insulation Nom. Thickness (mm)

Inner Sheath Nom. Thickness (mm)

Approx. Diameter Over Inner Sheath

(mm)

Armour Wire Nom. Diameter (mm)

Outer Sheath Nom. Thickness (mm)

Approx. Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1.52.546

10162535507095

120150185240300

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

1.01.01.01.01.01.01.01.01.01.01.21.21.41.41.61.6

111213

14.51618

21.523.526.530.534.53843

47.553.558.5

0.900.900.901.251.251.251.601.601.602.002.002.002.502.502.502.50

1.81.81.81.81.81.81.81.81.92.02.22.32.52.62.83.0

1617

18.520

21.524

27.5303338

42.546

52.557

63.569

470540630830

1,0001,2501,8502,2502,7503,8504,9005,9007,5509,050

11,15013,400

Table 26 : Four - Core (4C)

Conductor Size(mm²)

Insulation Nom. Thickness (mm)

Inner Sheath Nom. Thickness (mm

Approx. Diameter Over Inner Sheath(mm)

Armour Wire Nom. Diameter (mm)

Outer Sheath Nom. Thickness (mm)

Approx. Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1.52.546

10162535507095

120150185240300

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

1.01.01.01.01.01.01.01.01.01.21.21.41.41.41.61.6

1213

14.516

17.520

23.526

29.53438

42.547.552.55965

0.900.901.251.251.251.601.601.601.602.002.002.502.502.502.502.50

1.81.81.81.81.81.81.81.92.02.22.32.52.62.83.03.2

171820

21.523.526.530333642

46.552

57.5637076

530610820970

1,1501,6502,2002,7503,4004,8506,1007,8509,400

11,35014,05016,950

FIRE RESISTANT CABLES

27

MIFR: NON-SHEATHED CABLES 450/750V

Table 27

Conductor Size(mm²)

Insulation Nom. Thickness (mm)

Approx. Overall Diameter (mm)

Approx. Overall Weight (kg/km)

1.52.546

10162535507095

120150185240300400500630

0.70.80.80.81.01.01.21.21.41.41.61.61.82.02.22.42.62.82.8

44.55.05.56.57.59

1011.513.515.51719

20.524

26.529.53337

25405575

120180280380510710980

1,2001,4501,8502,4003,0003,8504,8506,200

FEC Cables (M) Sdn. Bhd.

28

TECHNICAL DATA

Electrical Characteristics For Single Core Cable

Cond. Size(mm²)

Conductor Resistance (ohm/km) Reactance at 50 Hz (ohm/km) Current Rating in Air at 40 °C (A) Short-circuit Current (kA)

D.C at 20 °C A.C at 90°c Flat TrefoilFlat

Trefoil 1 sec. 2 sec.2 cables 3 cables

1.5 12.1 15.4 0.169 0.154 27 23 20 0.20 0.15

2.5 7.41 9.45 0.158 0.142 38 32 30 0.35 0.25

4 4.61 5.88 0.147 0.133 52 44 43 0.57 0.40

6 3.08 3.93 0.139 0.124 65 56 55 0.85 0.61

10 1.83 2.33 0.132 0.117 88 77 75 1.43 1.01

16 1.15 1.47 0.123 0.109 115 100 99 2.28 1.62

25 0.727 0.927 0.118 0.104 155 135 130 3.57 2.53

35 0.524 0.669 0.113 0.0989 190 170 165 5.00 3.54

50 0.387 0.494 0.109 0.0948 230 205 200 7.15 5.06

70 0.268 0.342 0.106 0.0916 290 265 255 10.0 7.08

95 0.193 0.247 0.102 0.0877 360 325 315 13.5 9.61

120 0.153 0.196 0.103 0.0887 415 380 370 17.1 12.1

150 0.124 0.160 0.102 0.0879 480 440 430 21.4 15.2

185 0.0991 0.128 0.101 0.0864 555 510 495 26.4 18.7

240 0.0754 0.0988 0.0993 0.0848 660 615 595 34.3 24.3

300 0.0601 0.0801 0.0979 0.0834 760 710 690 42.9 30.3

400 0.0470 0.0643 0.0976 0.0830 940 830 805 57.2 40.5

500 0.0366 0.0521 0.0968 0.0823 1010 960 930 71.5 50.6

630 0.0283 0.0428 0.0952 0.0807 1170 1110 1080 90.0 63.7

800 0.0221 0.0363 0.0932 0.0787 1360 1300 1260 114 81

1000 0.0176 0.0317 0.0920 0.0775 1510 1450 1400 143 101

Voltage Drop Per Ampere Per Meter For Single Core Cable

Cond. Size (mm²) Two cables Three cables, three phase A.C Four cables, three phase A.C

D.C (mV) Single phase A.C (mV) Flat (mV) Trefoil (mV) Flat (mV) Trefoil (mV)

1.5 30.0 30.0 26.0 26.7 15.0 26.7

2.5 18.0 18.0 16.0 16.3 9.4 16.3

4 11.7 11.7 10.1 10.1 5.9 10.1

6 7.83 7.84 6.8 6.8 3.92 6.8

10 6.06 4.66 4.03 4.04 2.32 4.04

16 2.93 2.94 2.54 2.54 1.47 2.54

25 1.84 1.86 1.61 1.61 0.933 1.61

35 1.34 1.35 1.18 1.16 0.678 1.16

50 0.986 1.01 0.875 0.860 0.505 0.860

70 0.682 0.716 0.620 0.599 0.357 0.599

95 0.491 0.533 0.463 0.435 0.266 0.435

120 0.390 0.443 0.383 0.349 0.220 0.349

150 0.316 0.378 0.329 0.287 0.190 0.287

185 0.253 0.326 0.282 0.235 0.163 0.234

240 0.192 0.280 0.243 0.186 0.140 0.186

300 0.153 0.253 0.219 0.157 0.126 0.156

400 0.120 0.234 0.202 0.132 0.117 0.130

500 0.0933 0.220 0.190 0.114 0.110 0.113

630 0.0722 0.209 0.181 0.102 0.104 0.0996

800 0.0563 0.200 0.173 0.0931 0.100 0.0903

1000 0.0449 0.195 0.169 0.0879 0.0973 0.0847

FIRE RESISTANT CABLES

29

TECHNICAL DATA

Electrical Characteristics For Multi Core Cable

Cond.Size

(mm²)

Conductor Resistance(ohm/km) Reactance at 50 Hz

(ohm/km)

Current Rating in air at40 °C (A)

Short circuit Current (kA)

D.C at 20 °C A.C at 90 °C

2 core 3,4 core 2 core 3,4 core 1 sec. 2 sec.

1.5 12.1 15.4 15.4 0.120 28 24 0.21 0.15

2.5 7.41 9.45 9.45 0.111 37 31 0.36 0.25

4 4.61 5.88 5.88 0.103 49 41 0.57 0.40

6 3.08 3.93 3.93 0.0967 62 52 0.86 0.61

10 1.83 2.33 2.33 0.0920 84 71 1.43 1.01

16 1.15 1.47 1.47 0.0865 110 95 2.29 1.62

25 0.727 0.927 0.927 0.0851 150 125 3.58 2.53

35 0.524 0.669 0.669 0.0818 180 155 5.01 3.54

50 0.387 0.494 0.494 0.0807 220 190 7.15 5.06

70 0.268 0.342 0.343 0.0785 280 240 10.01 7.08

95 0.193 0.247 0.248 0.0760 345 295 13.59 9.61

120 0.153 0.196 0.197 0.0769 405 345 17.16 12.13

150 0.124 0.160 0.160 0.0766 460 395 21.45 15.17

185 0.0991 0.128 0.129 0.0762 535 460 26.46 18.71

240 0.0754 0.0987 0.0996 0.0750 635 545 34.32 24.27

300 0.0601 0.0798 0.0809 0.0739 725 625 42.9 30.33

Voltage Drop Per Ampere Per Meter For Multi Core Cable

Cond. Size(mm²)

2 core cable3 core cable, three phase A.C. (mV) 4 core cable, three phase A.C. (mV)

D.C. (mV) Single phase A.C (mV)

1.5 30.0 30.0 26.0 26.0

2.5 18.0 18.0 16.0 16.0

4 11.7 11.7 10.1 10.1

6 7.83 7.84 6.8 6.8

10 4.66 4.66 4.03 4.03

16 2.93 2.94 2.54 2.54

25 1.84 1.86 1.61 1.61

35 1.34 1.35 1.17 1.17

50 0.986 1.01 0.867 0.867

70 0.682 0.704 0.609 0.609

95 0.491 0.517 0.449 0.449

120 0.390 0.421 0.366 0.366

150 0.316 0.354 0.307 0.307

185 0.253 0.298 0.259 0.259

240 0.192 0.248 0.216 0.216

300 0.153 0.218 0.190 0.190

FEC Cables (M) Sdn. Bhd.

30

Applicable Conditions For Continuous And Short-Circuit Current Rating

1. Maximum rated conductor temperature Normal operation : 90 °C Short circuit : 250 °C

2. Correction factor for continuous current rating

Ambient Temp.(°C) 15 20 25 30 35 �0 �5 50 55Rating Factor 1.22 1.18 1.1� 1.10 1.05 1.00 0.95 0.89 0.8�

3. Correction factor for continuous current rating of grouped cables

3.1 Single core cables on tray, flat formation and no spacing between cables

No. of cables � 6 9 12 Above 12Rating Factor 0.82 0.76 0.70 0.70 0.65Applied value As per 2 cables of Technical data for single core

3.2 Multi core cables on tray, flat formation and no spacing between cables

No. of cables 2 3 � 6 9Rating Factor 0.85 0.78 0.75 0.72 0.70

where, S : Conductor size in mm² t : Short-circuit duration in second (s)

Note : Where the spacing between grouped cables exceeds twice the overall diameter, reduction factor need not be applied.

�. Short-circuit current for copper conductor

The following formula is applied for a duration of up to 5 seconds.

0.1�3 × SIS = (kA) t

TECHNICAL DATA

Accreditations

FEC Cables (M) Sdn. Bhd.

Factory 1 : Persiaran Raja Muda, �0000 Shah Alam, Selangor Darul Ehsan, Malaysia.(P.O. Box 7006, �0700 Shah Alam) Tel : 603-5519 1110/3/�, 5519 1258, 5519 581�/5/7Fax : 603-5519 1296

Factory 2 : No. 16, Jalan Keluli 2, Bukit Raja Industrial Area, �0150 Klang, Selangor Darul Ehsan, Malaysia.Tel : 603-33�3 5837/9/�0, 33�3 7727Fax : 603-33�3 58�3, 33�3 9262

Sales Office :Persiaran Raja Muda, �0000 Shah Alam, Selangor Darul Ehsan, Malaysia.(P.O. Box 7006, �0700 Shah Alam) Tel : 603-5519 1110 (Hotline)Fax : 603-5519 1296, 5513 8688Website : www.furukawa.com.mye-mail : [email protected]

www.fec.com.my

(7293-W)

FEC Cables (M) Sdn. Bhd.

Bare Aluminium Conductors, ACSR and ABC Cables

CORPORATEHISTORY

INTRODUCTION OF

COMPANYWhen there is talk of high quality electric wires and cables, the one company that comes to mind is FEC Cables (Malaysia) Sdn. Bhd. FEC is a subsidiary of Permodalan Nasional Berhad and was formerly known as Furukawa Electric Cables (M) Sdn. Bhd. Having established its Shah Alam plant in 1967 on a 7-acre site at the Shah Alam Industrial Estate, Furukawa has come a long way.

The technical collaboration with our Japanese counterpart, Furukawa Japan, has brought about an amazing success for us. In terms of quality, we have climbed the ladders of product manufacturing, steadily and successfully, pushing FEC towards the pinnacle of excellence. Putting our customers’ demands and needs as our number one priority, we opened our second plant in 1995, on a 27-acre freehold land site in Bukit Raja Industrial area, Klang. In our quest for excellence, we equip the plant with the latest technological aids for the manufacture of a wide range of low and medium voltage cables.

The certification of the ISO 9001 for both plants only proves that we do not compromise on quality and customer satisfaction. Our dedicated and hard-working employees are the backbone of our success. This was greatly helped by the state-of-the-art technology equipment which has led us towards excellence.

Moving towards a new century, we pledge to continually strive towards progressive and dynamic growth as FEC Cables continues its efforts in contributing to the development of Malaysia.

FEC Cables (M) Sdn. Bhd. was first established in 1967 and was previously known as Furukawa Electric Cables (M) Sdn. Bhd. In all the years until 2003, the company had been under the management and control of Furukawa Electric Co. Ltd. of Japan.

In 2003, the company was renamed FEC Cables (M) Sdn. Bhd. following the acquisition of its major equity stake by Permodalan Nasional Berhad, Malaysia’s government-owned premier multi-billion dollar investment institution.

The Company had started a technical collaboration from world renowned cable manufacturer, The Furukawa Electric Co. Ltd Japan (Furukawa Japan).

FEC Cables has benefited enormously from the technical collaboration and the subsequent technology transfer with Furukawa Japan. FEC Cables inherited from Furukawa Japan not only its advanced technology and technical know-how but also the disciplines of producing quality products using material conforming to the international standards of manufacturing cables.

Today FEC Cables plays a prominent role as a forerunner in the cable industry.

FEC Cables has been actively involved in serving various industrial sectors, namely the power, telecommunications, construction as well as the oil and gas sectors.

Bare Aluminium Conductors, ACSR and ABC Cables

1) STRANDED HARD-DRAWN ALL ALUMINIUM CONDUCTOR(AAC)

Construction

a) BS 215 : Part 1

b) BS EN 50182

c) ASTM B 231

2) BARE STRANDED ALL ALUMINIUM ALLOY CONDUCTOR(AAAC)

Construction

a) BS EN 50182

b) ASTM B 399

3) ALUMINIUM CONDUCTOR STEEL REINFORCED(ACSR)

Construction

a) BS 215 : Part 2

b) BS EN 50182

c) ASTM B 232

�) LOW VOLTAGE AERIAL CABLE 600/1000 V

TNBD & IEC 60502-1

5) MEDIUM VOLTAGE AERIAL CABLE 11 kV

TNBD & IEC 60502-2

6) MEDIUM VOLTAGE AERIAL CABLE 33 kV

TNBD & IEC 60502-2

5

6

7

8-9

10

11

12

13

1�

15

16-18

19

20

21

Table Of Contents

BARE ALUMINIUM CONDUCTORS, ACSR AND ABC CABLES

5

7(1+6)

61(1+6+12+18+24) 91(1+6+12+18+24+30) 127(1+6+12+18+24+30+36)

19(1+6+12) 37(1+6+12+18)

Stranded Hard-Drawn All Aluminium Conductor (AAC)

FEC Cables (M) Sdn. Bhd.

SPECIFICATION

6

AAC BS 215 Part 1

Stranded Hard-Drawn All Aluminium Conductor

Code NameNominal Area

ConstructionNo. /Wire Diameter

Calculated AreaApprox. Overall

DiameterApprox. Weight

Calculated Min. Breaking Load

DC Resistance at 20°C

mm2 No. /mm mm2 mm kg/km kN ohm/km

Midge 22 7/2.06 23.33 6.18 64 3.99 1.227

Ant 50 7/3.10 52.83 9.30 145 8.28 0.5419

Fly 60 7/3.40 63.55 10.20 174 9.90 0.4505

Wasp 100 7/4.39 106.0 13.17 290 16.00 0.2702

Hornet 150 19/3.25 157.6 16.25 434 24.70 0.1825

Chafer 200 19/3.78 213.2 18.90 587 32.40 0.1349

Cockroach 250 19/4.22 265.7 21.10 731 40.40 0.1083

Butterfly 300 19/4.65 322.7 23.25 888 48.75 0.08916

Centipede 400 37/3.78 415.20 26.46 1145 63.10 0.06944

BARE ALUMINIUM CONDUCTORS, ACSR AND ABC CABLES

Stranded Hard-Drawn All Aluminium Conductor

SPECIFICATION

7

Code nameNominal

areaConstruction

No./Wire diameterCalculated area

Approx. overalldiameter

Approx. weightCalculated

min. breakingload

DCresistance

at 20ºC

mm² No./mm mm² mm kg/km kN ohm/km

Gnat - 7/2.21 26.90 6.63 73 4.83 1.0643

Mosquito - 7/2.59 36.90 7.77 101 6.27 0.7749

Ladybird - 7/2.79 42.80 8.37 117 7.28 0.6678

Bluebottle ;- 7/3.66 73.60 10.98 201 11.78 0.3880

Earwig - 7/3.78 78.60 11.34 215 12.57 0.3638

Grasshopper - 7/3.91 84.10 11.73 230 13.46 0.3400

Clegg - 7/4.17 95.60 12.51 261 15.30 0.2989

Beetle - 19/2.67 106.4 13.35 292 18.08 0.2701

Bee - 7/4.90 132.0 14.70 361 21.12 0.2165

Caterpillar - 19/3.53 185.9 17.65 511 29.75 0.1546

Spider - 19/3.99 237.6 19.95 653 38.01 0.1210

Moth ;- 19/5.00 373.1 25.00 1025 59.69 0.0770

Drone - 37/3.58 372.4 25.06 1027 59.59 0.0774

Maybug - 37/4.09 486.1 28.63 1340 77.78 0.593

Scorpion - 37/4.27 529.8 29.89 1461 84.77 0.0544

Cicada - 37/4.65 628.3 32.55 1732 100.54 0.0459

BS EN 50182AAC

FEC Cables (M) Sdn. Bhd.

SPECIFICATION

Stranded Hard-Drawn All Aluminium Conductor

8

AAC ASTM B 231

Code nameTotal area

ConstructionNo./Wire diameter

Approx.overall diameter

Approx. weightCalculated

min. breakingload

DCresistance

at 20ºC

AWG or MCM mm² No./mm mm kg/km kN ohm/km

Peachbell 6.0 13.30 7/1.56 4.68 37 2.53 2.169

Rose 4.0 21.10 7/1.96 5.88 58 3.91 1.362

Iris 2.0 33.60 7/2.47 7.41 93 5.99 0.8574

Pansy 1.0 42.40 7/2.78 8.34 117 7.30 0.6801

Poppy 1/0.0 53.50 7/3.12 9.36 147 8.84 0.5390

Aster 2/0.0 67.40 7/3.50 10.50 186 11.10 0.4276

Phlox 3/0.0 85.00 7/3.93 11.79 234 13.50 0.3390

Oxlip 4/0.0 107.2 7/4.42 13.26 295 17.00 0.2688

Valerian 250.0 126.7 19/2.91 14.55 349 20.70 0.2275

Sneezewort 250.0 126.7 7/4.80 14.40 349 20.10 0.2275

Laurel 266.8 135.2 19/3.01 15.05 372 22.10 0.2133

Daisy 266.8 135.2 7/4.96 14.88 372 21.40 0.2133

Peony 300.0 152.0 19/3.19 15.95 418 24.30 0.1896

Tulip 336.4 170.5 19/3.38 16.90 470 27.30 0.1695

Daffodil 350.0 177.3 19/3.45 17.25 488 28.40 0.1625

Canna 397.5 201.4 19/3.67 18.35 555 31.60 0.1432

Goldentuft 450.0 228.0 19/3.91 19.55 628 35.00 0.1264

Syringa 477.0 242.0 37/2.88 20.16 665 38.60 0.1193

Cosmos 477.0 242.0 19/4.02 20.10 665 37.00 0.1193

Hyacinth 500.0 253.3 37/2.95 20.65 697 40.50 0.1137

Zinna 500.0 253.3 19/4.12 20.60 697 38.90 0.1137

Dahlia 556.5 282.0 19/4.35 21.75 776 43.30 0.1023

Mistletoe 556.5 282.0 37/3.12 21.84 776 44.30 0.1023

Meadowsweet 600.0 304.0 37/3.23 22.61 836 47.50 0.0948

Orchid 636.0 323.3 37/3.33 23.31 887 50.40 0.0893

Heuchera 650.0 329.4 37/3.37 23.59 907 51.70 0.0875

BARE ALUMINIUM CONDUCTORS, ACSR AND ABC CABLES

Stranded Hard-Drawn All Aluminium Conductor

SPECIFICATION

9

AAC ASTM B 231

Code nameTotal area

ConstructionNo./Wire diameter

Approx.overall diameter

Approx. weightCalculated

min. breakingload

DCresistance

at 20ºC

AWG or MCM mm² No./mm mm kg/km kN ohm/km

Flag 700.0 354.7 61/2.72 24.48 976 57.10 0.0813

Verbena 700.0 354.7 37/3.49 24.43 976 55.40 0.0813

Nasturtium 715.5 362.60 61/2.75 24.75 999 58.40 0.0795

Violet 715.5 362.60 37/3.53 24.71 999 56.70 0.0795

Cattail 750.0 380.0 61/2.82 25.38 1046 60.30 0.0759

Petunia 750.0 380.0 37/3.62 25.34 1046 58.60 0.0759

Lilac 795.0 402.8 61/2.90 26.10 1110 63.80 0.0715

Arbutus 795.0 402.8 37/3.72 26.04 1109 61.80 0.0715

Snapdragon 900.0 456.0 61/3.09 27.81 1256 70.80 0.0632

Coskscomb 900.0 456.0 37/3.96 27.72 1256 68.40 0.0632

Goldenrod 954.0 483.4 61/3.18 28.62 1331 75.00 0.0596

Magnolia 954.0 483.4 37/4.08 28.56 1331 72.60 0.0596

Camellia 1000.0 506.7 61/3.25 29.25 1394 78.30 0.0569

Hawkweed 1000.0 506.7 37/4.18 29.26 1395 76.20 0.0569

Larkspur 1033.5 523.7 61/3.31 29.79 1442 81.30 0.0550

Bluebell 1033.5 523.7 37/4.25 29.75 1441 78.80 0.0550

Marigold 1113.0 564.0 61/3.43 30.87 1553 87.30 0.0511

Hawthorn 1192.5 604.2 61/3.55 31.95 1662 93.50 0.0447

Narcissus 1272.0 644.5 61/3.67 33.03 1774 98.10 0.0447

Columbine 1351.0 694.8 61/3.78 34.02 1884 104.00 0.0421

Carnation 1431.0 725.1 61/3.89 35.01 1997 108.00 0.0398

Gladiolus 1510.5 765.4 61/4.00 36.00 2108 114.00 0.0376

Coreopsis 1590.0 805.7 61/4.10 36.90 2216 120.00 0.0358

Jessamine 1750.0 886.7 61/4.30 38.70 2442 132.00 0.0325

Cowslip 2000.0 1013.0 91/3.77 41.47 2787 153.00 0.0284

Lupine 2500.0 1267.0 91/4.21 46.31 3519 186.00 0.0230

Trillium 3000.0 1520.0 127/3.90 50.70 4226 223.00 0.0191

Bluebonnet 3500.0 1773.0 127/4.22 54.86 4977 261.00 0.0166

FEC Cables (M) Sdn. Bhd.

10

Bare Stranded All Aluminium Alloy Conductors (AAAC)

7(1+6)

61(1+6+12+18+24)

19(1+6+12)

37(1+6+12+18)

BARE ALUMINIUM CONDUCTORS, ACSR AND ABC CABLES

SPECIFICATION

11

AAAC BS EN 50182

Bare Stranded All Aluminium Alloy Conductor

Code nameConstruction

No./Wire diameter Calculated

area

Approx.overall

diameter

Approx.weight

Calculated min. breaking

load

DCresistance

at 20ºC

No./mm mm² mm kg/km kN ohm/km

Box 7/1.85 18.8 5.55 51 5.55 1.7480

Acacia 7/2.08 23.9 6.24 65 7.02 1.3828

Almond 7/2.34 30.1 7.02 82 8.88 1.0926

Cedar 7/2.54 35.5 7.62 97 10.46 0.9273

Deodar 7/2.77 42.2 8.31 115 12.44 0.7797

Fir 7/2.95 47.8 8.85 131 14.11 0.6875

Hazel 7/3.30 59.9 9.90 163 17.66 0.5494

Pine 7/3.61 71.60 10.80 196 21.14 0.4591

Holly 7/3.91 84.1 11.70 230 24.79 0.3913

Willow 7/4.04 89.7 12.10 245 26.47 0.3665

Oak 7/4.65 118.9 13.95 325 35.07 0.2767

Mulbery 19/3.18 150.9 15.90 414 44.52 0.2192

Ash 19/3.48 180.7 17.40 496 53.31 0.1830

Elm 19/3.76 211.0 18.80 579 62.24 0.1568

Poplar 37/2.87 239.4 20.10 659 70.61 0.1387

Sycamore 37/3.23 303.2 22.60 835 89.40 0.1095

Upas 37/3.53 362.1 24.70 998 106.82 0.0917

Yew 37/4.06 479.0 28.40 1320 141.31 0.0693

Totara 37/4.14 498.1 29.42 1372 146.93 0.0666

Rubus 61/3.50 586.9 31.50 1622 173.13 0.0567

Sorbus 61/3.71 659.4 33.40 1823 194.53 0.0505

Araucaria 61/4.14 821.1 37.30 2270 242.24 0.0406

FEC Cables (M) Sdn. Bhd.

SPECIFICATION

12

AAAC ASTM B 399

Total areConstruction

No./Wire diameterApprox.

overall diameterApprox. weight

Calculated min. breaking

load

DCresistance

at 20ºC

AWG or MCM* mm² No./mm mm kg/km kN ohm/km

6 13.3 7/1.55 4.65 36 4.22 2.519

4 21.1 7/1.96 5.88 58 6.72 1.584

2 33.6 7/2.47 7.41 92 10.70 0.9958

0 53.5 7/3.12 9.36 147 17.00 0.6261

2/0 67.4 7/3.50 10.50 185 20.50 0.4968

3/0 85.0 7/3.93 11.79 233 25.90 0.3939

4/0 107.2 7/4.42 13.26 299 32.70 0.3124

250 126.70 19/2.91 14.55 347 39.00 0.2643

300 152.0 19/3.19 15.95 417 46.80 0.2204

350 177.3 19/3.45 17.25 486 52.30 0.1889

400 202.7 19/3.69 18.45 555 59.80 0.1655

450 228.0 19/3.91 19.55 624.4 67.30 0.1469

500 253.4 19/4.12 20.60 697 74.70 0.1322

550 278.7 37/3.10 21.70 763 83.90 0.1202

600 304.0 37/3.23 22.61 832 91.50 0.1101

650 329.4 37/3.37 23.59 901.3 95.00 0.1017

700 354.7 37/3.49 24.43 971 102.00 0.09439

750 380.0 37/3.62 25.34 1041 110.00 0.08816

800 405.4 37/3.73 26.11 1109 117.00 0.0826

900 456.0 37/3.96 27.72 1249 132.00 0.07341

1000 506.7 37/4.18 29.26 1388 146.00 0.06609

* Circular mils x 1000

Bare Stranded All Aluminium Conductor

BARE ALUMINIUM CONDUCTORS, ACSR AND ABC CABLES

13

Aluminium Conductor Steel Reinforced (ACSR)

6+1

18(6+12)+1 24(9+15)+7(1+6) 26(10+16)+7(1+6) 30(12+18)+7(1+6)

6+7(1+6) 12 + 7(1+6) 14 + 7(1+6) 14 + 19(1+6+12)

54(12+18+24)+19(1+6+12)

45(9+15+21)+7(1+6) 48(10+16+22)+7(1+6) 54(12+18+24)+7(1+6) 30(12+18)+19(1+6+12)

FEC Cables (M) Sdn. Bhd.

SPECIFICATION

1�

ACSR BS 215 : PART 2

Aluminium Conductor Steel Reinforced

Code name

Nominalaluminium

areamm²

ConstructionNo./Wire diameter

Cross-sectional area Approx.overall

diameter

Approx.weight

Calculated breaking

load

DCresistance

at 20ºCAluminium Steel Aluminium Steel Total

No./mm No./mm mm² mm² mm² mm kg/km kN ohm/km

Gopher 25 6/2.36 1/2.36 26.24 4.38 30.62 7.08 106 9.61 1.093

Weasel 30 6/2.59 1/2.59 31.61 5.27 36.88 7.77 128 11.45 0.9077

Ferret 40 6/3.00 1/3.00 42.41 7.07 49.48 9.00 172 15.20 0.6776

Rabbit 50 6/3.35 1/3.35 52.88 8.81 61.70 10.05 214 18.35 0.5426

Horse 70 12/2.79 7/2.79 73.37 42.80 116.2 13.95 538 61.20 0.3936

Dog 100 6/4.72 7/1.57 105.0 13.50 118.5 14.15 394 32.70 0.2733

Wolf 150 30/2.59 7/2.59 158.1 36.80 194.9 18.13 726 69.20 0.1828

Dingo 150 18/3.35 1/3.35 158.7 8.80 167.5 16.75 506 35.70 0.1815

Lynx 175 30/2.79 7/2.79 183.4 42.80 226.2 19.53 842 79.80 0.1576

Caracal 175 18/3.61 1/3.61 184.3 10.20 194.5 18.05 587 41.10 0.1563

Panther 200 30/3.00 7/3.00 212.1 49.20 261.5 21.00 974 92.25 0.1363

Jaguar 200 18/3.86 1/3.86 210.6 11.70 222.3 19.30 671 46.55 0.1367

Batang* 300 18/4.78 7/1.68 323.0 15.50 338.5 24.16 1010 69.67 0.08914

Zebra 400 54/3.18 7/3.18 428.9 55.60 484.5 28.62 1621 131.9 0.06740

* Not in BS 215 : Part 2 but in accordance to TNB’s spec.

BARE ALUMINIUM CONDUCTORS, ACSR AND ABC CABLES

SPECIFICATION

15

Code name

ConstructionNo./Wire diameter

Cross-sectional area Approx.overall

diameter

Approx.weight

Calculated breaking

load

DCresistance

at 20ºCAluminium Steel Aluminium Steel Total

No./mm No./mm mm² mm² mm² mm kg/km kN ohm/km

Mole 6/1.50 1/1.50 10.60 1.77 12.40 4.50 43 4.14 2.7027

Squirrel 6/2.11 1/2.11 21.00 3.50 24.50 6.33 85 7.87 1.3659

Fox 6/2.79 1/2.79 36.70 6.11 42.80 8.37 148 13.21 0.7812

Mink 6/3.66 1/3.66 63.10 10.50 73.60 11.00 255 21.67 0.4540

Skunk 12/2.59 7/2.59 63.20 36.90 100.1 13.00 463 52.79 0.4568

Beaver 6/3.99 1/3.99 75.00 12.50 87.50 12.00 303 25.76 0.3820

Racoon 6/4.10 1/4.10 79.20 13.20 92.40 12.30 318 27.06 0.3635

Otter 6/4.22 1/4.22 83.90 14.00 97.90 12.70 339 28.81 0.3415

Cat 6/4.50 1/4.50 95.40 15.90 111.3 13.50 385 32.76 0.3003

Hare 6/4.72 1/4.72 105.0 17.50 122.5 14.20 424 36.04 0.2730

Coyote 26/2.54 7/1.91 131.7 20.10 151.8 15.90 521 45.86 0.2192

Cougar 18/3.05 1/3.05 131.5 7.31 138.8 15.30 419 29.74 0.2188

Tiger 30/2.36 7/2.36 131.2 30.60 161.8 16.50 602 57.87 0.2202

Lion 30/3.18 7/3.18 238.3 55.60 293.9 22.30 1093 100.47 0.1213

Bear 30/3.35 7/3.35 264.4 61.70 326.1 23.50 1213 111.50 0.1093

Goat 30/3.71 7/3.71 324.3 75.70 400.0 26.00 1488 135.13 0.0891

Sheep 30/3.99 7/3.99 375.1 87.50 462.6 27.90 1721 156.30 0.0771

Antelope 54/2.97 7/2.97 374.1 48.50 422.6 26.70 1414 118.88 0.0773

Bison 54/3.00 7/3.00 381.7 49.50 431.2 27.00 1443 121.30 0.0758

Deer 30/4.27 7/4.27 429.6 100.2 529.8 29.90 1971 179.00 0.0673

Elk 30/4.50 7/4.50 477.1 111.3 588.4 31.50 2190 198.80 0.0606

Camel 54/3.35 7/3.35 476.0 61.70 537.7 30.20 1799 146.40 0.0608

Moose 54/3.53 7/3.53 528.5 68.50 597.0 31.80 1997 159.92 0.0547

ACSR BS EN 50182

Aluminium Conductor Steel Reinforced

FEC Cables (M) Sdn. Bhd.

SPECIFICATION

16

ACSR ASTM B 232

Aluminium Conductor Steel Reinforced

Code name

ConstructionNo./Wire diameter

Cross-sectional area Approx.overall

diameter

Approx.weight

Calculated breaking

load

DCresistance

at 20ºCAluminium Steel Aluminium Steel Total

No./mm No./mm mm² mm² mm² mm kg/km kN ohm/km

Turkey 6/1.68 1/1.68 13.29 2.21 15.50 5.04 54 5.20 2.157

Swan 6/2.12 1/2.12 21.18 3.53 24.71 6.36 85 8.30 1.356

Swanate 7/1.96 1/2.61 21.12 5.35 26.47 6.53 100 10.50 1.356

Sparrow 6/2.67 1/2.67 33.59 5.60 39.19 8.01 136 12.70 0.8530

Sparate 7/2.47 1/3.30 33.54 8.55 42.09 8.24 159 16.10 0.8530

Robin 6/3.00 1/3.00 42.41 7.07 49.48 9.00 171 15.80 0.6765

Raven 6/3.37 1/3.37 53.52 8.92 62.44 10.11 216 19.40 0.5364

Quail 6/3.78 1/3.78 67.33 11.22 78.55 11.34 272 23.60 0.4255

Pigeon 6/4.25 1/4.25 85.12 14.19 99.30 12.75 343 29.50 0.3373

Penguin 6/4.77 1/4.77 107.2 17.87 125.1 14.31 433 37.10 0.2676

Waxwing 18/3.09 1/3.09 135.0 7.50 142.5 15.45 430 30.60 0.2133

Partridge 26/2.57 7/2.00 134.9 22.00 156.9 16.28 546 50.30 0.2142

Ostrich 26/2.73 7/2.12 152.2 24.71 176.9 17.28 613 56.50 0.1906

Linnet 26/2.89 7/2.25 170.6 27.83 198.4 18.31 688 62.70 0.1699

Oriole 30/2.69 7/2.69 170.5 39.80 210.3 18.83 783 77.00 0.1704

Chickdee 18/3.77 1/3.77 200.9 11.16 212.1 18.85 641 44.20 0.1432

Brant 24/3.27 7/2.18 201.6 26.13 227.7 19.61 761 64.90 0.1438

Iblis 26/3.14 7/2.44 201.3 32.73 234.1 19.88 812 72.50 0.1438

Lark 30/2.92 7/2.92 200.9 46.88 247.8 20.44 925 90.30 0.1442

Pelican 18/4.14 1/4.14 242.3 13.46 255.8 20.70 770 52.50 0.1193

Flicker 24/3.58 7/2.39 241.6 31.4 273.0 21.49 914 76.10 0.1199

Hawk 26/3.44 7/2.68 241.7 39.49 281.1 21.80 975 86.70 0.1199

Hen 30/3.20 7/3.20 241.3 56.30 297.6 22.40 1110 105.9 0.1202

Osprey 18/4.47 1/4.47 282.5 15.69 298.2 22.35 898 60.9 0.1022

Parakeet 24/3.87 7/2.58 282.3 36.60 318.9 23.22 1066 88.1 0.1028

Dove 26/3.72 7/2.89 282.6 45.92 328.5 23.55 1139 100.5 0.1028

Eagle 30/3.46 7/3.46 282.0 65.82 347.9 24.21 1296 123.7 0.1030

Peacock 24/4.03 7/2.69 306.1 39.78 345.9 24.20 1159 95.6 0.09449

Squab 26/3.87 7/3.01 305.8 49.81 355.6 24.51 1237 106.8 0.09449

BARE ALUMINIUM CONDUCTORS, ACSR AND ABC CABLES

SPECIFICATION

17

Aluminium Conductor Steel Reinforced

ACSR ASTM B 232

Code name

ConstructionNo./Wire diameter

Cross-sectional area Approx.overall

diameter

Approx.weight

Calculated breaking

load

DCresistance

at 20ºCAluminium Steel Aluminium Steel Total

No./mm No./mm mm² mm² mm² mm kg/km kN ohm/km

Wood Duc 30/3.61 7/3.61 307.1 71.65 378.7 25.25 1408 128.5 0.09473

Teal 30/3.61 19/2.16 307.1 69.62 376.7 25.24 1397 133.4 0.09475

Kingbird 18/4.78 1/4.78 323.0 17.95 341.0 23.88 1027 69.4 0.8942

Rook 24/4.14 7/2.76 323.1 41.88 365.0 24.84 1218 101.0 0.08989

Grosbeak 26/3.97 7/3.09 321.8 52.49 374.3 25.15 1301 112.1 0.08989

Scoter 30/3.70 7/3.70 322.6 75.26 397.8 25.88 1481 134.8 0.09011

Egret 30/3.70 19/2.22 322.6 73.50 396.1 25.90 1469 140.1 0.09012

Flamingo 24/4.23 7/2.82 337.3 43.72 381.0 25.40 1277 105.4 0.08576

Gannet 26/4.07 7/3.16 338.3 54.90 393.2 28.30 1363 117.4 0.08576

Stilt 24/4.39 7/2.92 363.3 46.88 410.2 26.31 1370 113.4 0.07989

Starling 26/4.21 7/3.28 361.9 59.15 421.1 26.68 1464 126.3 0.07992

Redwing 30/3.92 19/2.35 362.1 82.41 444.5 27.43 1651 153.9 0.08009

Tern 45/3.38 7/2.25 403.8 27.83 431.6 27.03 1332 98.3 0.07192

Condor 54/3.08 7/3.08 402.3 52.15 454.5 27.72 1521 125.4 0.07192

Cuckoo 24/4.62 7/3.08 402.3 52.15 454.5 27.74 1522 124.1 0.07190

Drake 26/4.44 7/3.45 402.6 65.44 468.0 28.11 1626 140.1 0.07192

Mallard 30/4.14 19/2.48 403.8 91.78 495.6 28.96 1836 170.8 0.07208

Ruddy 45/3.59 7/2.40 455.5 31.67 487.2 28.73 1507 108.3 0.06356

Canary 54/3.28 7/3.28 456.3 59.15 515.4 29.52 1723 141.9 0.06352

Rail 45/3.70 7/2.47 483.8 33.54 517.4 29.61 1598 115.2 0.05994

Cardinal 54/3.38 7/3.38 484.5 62.81 547.3 30.42 1826 150.3 0.05994

Ortolan 45/3.85 7/2.57 523.9 36.31 560.2 30.81 1731 123.2 0.05531

Curlew 54/3.52 7/3.52 525.5 68.12 593.6 31.68 1978 162.8 0.05531

Bluejay 45/4.00 7/2.66 565.5 38.90 604.4 31.98 1866 132.6 0.05161

Finch 54/3.65 19/2.19 565.0 71.57 636.6 32.85 2128 173.9 0.05161

Bunting 45/4.14 7/2.76 605.8 41.88 647.6 33.12 1997 141.9 0.04820

Grackle 54/3.77 19/2.27 602.8 76.89 679.7 33.97 2278 185.9 0.04820

Bittern 45/4.27 7/2.85 644.4 44.66 689.1 34.17 2131 151.7 0.04518

FEC Cables (M) Sdn. Bhd.

SPECIFICATION

18

Aluminium Conductor Steel Reinforced

ASTM B 232ACSR

Code name

ConstructionNo./Wire diameter

Cross-sectional area Approx.overall

diameter

Approx.weight

Calculated breaking

load

DCresistance

at 20ºCAluminium Steel Aluminium Steel Total

No./mm No./mm mm² mm² mm² mm kg/km kN ohm/km

Pheasant 54/3.90 19/2.34 645.1 81.71 726.8 35.10 2431 193.9 0.04518

Dipper 45/4.40 7/2.92 684.2 46.88 731.1 35.16 2263 161.0 0.04259

Martin 54/4.02 19/2.41 685.4 86.67 772.1 36.17 2582 205.9 0.04259

Bobolink 45/4.53 7/3.02 725.3 50.14 775.4 36.24 2397 170.8 0.04016

Plover 54/4.14 19/2.48 726.90 91.78 818.70 37.24 2735 218.0 0.04016

Nuthatch 45/4.65 7/3.10 764.2 52.83 817.0 37.20 2530 178.4 0.03802

Parrot 54/4.25 19/2.55 766.1 97.0 863.1 38.25 2884 230.4 0.03802

Lapwing 45/4.77 7/3.18 804.2 55.60 859.8 38.16 2664 187.3 0.03612

Falcon 54/4.36 19/2.62 806.2 102.4 908.7 39.26 3039 242.9 0.03612

BARE ALUMINIUM CONDUCTORS, ACSR AND ABC CABLES

19

ABC

Low Voltage Aerial Cable

Cable Size1 x 16

+ 1 x 253 x 16

+ 1 x 253 x 95

+ 1 x 70+ 1 x 16

3 x 185+ 1 x 120+ 1 x 16

Phase Conductor

Conductor

Cross-sectional area mm² 16 16 95 185

Number of wires 7 7 19 37

Number of cores 1 3 3 3

Nom. insulation thickness mm 1.00 1.00 1.60 2.00

Approx. diameter of insulated core mm 6.9 6.9 15.0 20.4

Max. DC resistance of conductor at 20ºC Ω/km 1.91 1.91 0.320 0.164

Messenger/Neutral Conductor

Conductor

Cross-sectional area mm² 25 25 70 120

Number of wires 7 7 19 19

Number of cores 1 1 1 1

Nom. insulation thickness mm 1.20 1.20 1.40 1.60

Approx. diameter of insulated core mm 8.6 8.6 13.0 16.6

Max. DC resistance of conductor at 20ºC Ω/km 1.312 1.312 0.469 0.273

Calculated Breaking Load kN 7.5 7.5 36.0 36.0

Lighting Conductor

Conductor

Cross-sectional area mm² * * 16 16

Number of wires * * 7 7

Number of cores * * 1 1

Nom. insulation thickness mm * * 1.0 1.0

Approx. diameter of insulated core mm * * 6.9 6.9

Max. DC resistance of conductor at 20ºC Ω/km * * 1.91 1.91

Approx. overall diameter of cable mm 15.5 19.2 40.5 49.3

Approx. overall weight of the cable kg/km 160 290 1300 2360

Cable length per drum m 1000 1000 500 500

Phase Conductor

Insulation

Neutral Conductor (Messenger)

Street Lighting

FEC Cables (M) Sdn. Bhd.

20

Medium Voltage Aerial Cable

Cable Size3 x 70

+ 1 x 503 x 150

+ 1 x 503 x 240

+ 1 x 50

Phase Conductor

Conductor

Cross-sectional area mm² 70 120 240

Number of wires 19 37 37

Number of cores 3 3 3

Min. thickness of conductor screen mm 0.50 0.50 0.50

Nom. insulation thickness mm 3.40 3.40 3.40

Min. thickness of insulation screen mm 0.50 0.50 0.50

Nominal thickness of metallic screen mm 0.105 0.105 0.105

Min. thickness of outer sheath mm 2.30 2.30 2.30

Approx. overall diameter of cable mm 25.9 30.7 34.6

Messenger/Neutral Conductor

Cross-sectional area mm² 50 50 50

Number of wires 7 7 7

Number of cores 1 1 1

Calculated Breaking Load kN 63.0 63.0 63.0

Standard Cable

Approx. overall diameter of stranded cable mm 60.6 70.9 79.3

Approx. net weight kg/km 3000 4170 5320

Max. DC resistance of conductor at 20ºC Ω/km 0.443 0.206 0.125

Cable length per drum m 500 500 500

Conductor

Conductor Screen

Insulation

Insulation Screen

Metallic Screen

Binder Tape

Outer Sheath

Messenger

ABC TNBD & IEC 60502-211 kV SPECIFICATION

BARE ALUMINIUM CONDUCTORS, ACSR AND ABC CABLES

21

TNBD & IEC 60502-233 kV SPECIFICATION

Cable Size3 x 70

+ 1 x 503 x 150

+ 1 x 50

Phase Conductor

Conductor

Cross-sectional area mm² 70 150

Number of wires 19 37

Number of cores 3 3

Min. thickness of conductor screen mm 0.50 0.50

Nom. insulation thickness mm 8.00 8.00

Min. thickness of insulation screen mm 0.50 0.50

Nominal thickness of metallic screen mm 0.105 0.105

Min. thickness of outer sheath mm 2.30 2.30

Approx. overall diameter of cable mm 35.1 39.9

Messenger/Neutral Conductor

Cross-sectional area mm² 50 50

Number of wires 7 7

Number of cores 1 1

Calculated Breaking Load kN 63.0 63.0

Standard Cable

Approx. overall diameter of stranded cable mm 80.4 90.8

Approx. net weight kg/km 4530 5880

Max. DC resistance of conductor at 20ºC Ω/km 0.443 0.206

Cable length per drum m 500 500

Conductor

Conductor Screen

Insulation

Insulation Screen

Metallic Screen

Binder Tape

Outer Sheath

Messenger

ABC

Medium Voltage Aerial Cable

FEC Cables (M) Sdn. Bhd.

22

Factory 1Persiaran Raja Muda, �0000 Shah Alam, Selangor Darul Ehsan, Malaysia.(P.O. Box 7006, �0700 Shah Alam)Tel : 6 03 - 5519 1110 (Hotline) Fax : 6 03 - 5519 1296

Factory 2No. 16, Jalan Keluli 2, Bukit Raja Industrial Area, �1050 Klang, Selangor Darul Ehsan, Malaysia. Tel : 6 03 - 33�3 5837 (Hotline) Fax : 6 03 - 33�3 58�3

Sales OfficePersiaran Raja Muda, �0000 Shah Alam, Selangor Darul Ehsan, MalaysiaTel : 6 03 - 5519 1110 (Hotline) Fax : 6 03 - 5519 1296 / 5513 8688Email : [email protected]

www.fec.com.my

FEC Cables (M) Sdn. Bhd.(7293-W)

Des

ign

by

Tel :

03

- 772

2 48

18