49
Chillers Data Centers Hospitals Water Efficiency and You

Introducing nereus for cooling 09112014 gn (2)

Embed Size (px)

Citation preview

Page 1: Introducing nereus for cooling 09112014 gn (2)

Chillers

Data Centers

Hospitals

Water Efficiency

and You

Page 2: Introducing nereus for cooling 09112014 gn (2)

Executive SummaryWater Misalignment• Current Water Practices are

unsustainable

• We face

– Epic Drought

– Pressure like never before on water

• Current WT industries method of

delivery sets incorrect incentives

– Maximize

• the sale of high margin “Specialty “

product

– Minimize

• “Service “ Time

– Almost Ignore

• Water and energy use

In the end, the current services delivery

method simply ignores the key issues and

costs customers more to operate chiller

system than should be the case

Resources Wasted• Water

– Excessive Water

• Make up

• Bleed

– Excessive & Dangerous Chemical

• Antiscale

• Biocide

• Acids

– Excessive Utility Use

• Electrical Use

– Chiller inefficient Kw / Tn

• Process management

– Staff assigned no / low value activities

• Daily water testing

– Important information not communicated

• H/E

– Approach, Heat Flux, Etc

• Tower efficiency

• Atmospheric conditions

– Wet bulb, dew point, humidity

– Out of spec conditions not reported until

damage is done vs with in seconds

Page 3: Introducing nereus for cooling 09112014 gn (2)

Getting Started• No Cost to Client

– Water Samples provided to SWS LLC

• City & Tower

– System Information

• Cost

– Water, Sewer, Power, Descaling

– Tns total system design

– % Load On Line

» Fall, Winter, Spring, Summer

» Days in each season

• Output with in 2 weeks

– Savings available, Cap Ex, Op Ex

• Pilot is available

• Process guarantee

– $ savings will be delivered

– Water will be saved

– System will operate with less scale than is currently the case

– System will operate with less corrosion than is currently the case

– System will operate with less energy than is currently the case

Page 4: Introducing nereus for cooling 09112014 gn (2)

Preface - Drought

Houston – We Have A Problem

Page 5: Introducing nereus for cooling 09112014 gn (2)

Preface - Inefficiency

Page 6: Introducing nereus for cooling 09112014 gn (2)

No Water

From Water Project

Reservoirs are Drying Up

Preface – Surface Water

Page 7: Introducing nereus for cooling 09112014 gn (2)

Preface – Ground Water

Page 8: Introducing nereus for cooling 09112014 gn (2)

Preface - Food Prices

Page 9: Introducing nereus for cooling 09112014 gn (2)

Preface

People, Food, Energy – All Need H2O

Page 10: Introducing nereus for cooling 09112014 gn (2)

Preface – Energy Cost Up

Page 11: Introducing nereus for cooling 09112014 gn (2)

Executive Summary

Too Many Big Straws in The Milkshake

Page 12: Introducing nereus for cooling 09112014 gn (2)

Help Do Your Part to Help Us Help You

Save 1,000,000,000 GPY

Page 13: Introducing nereus for cooling 09112014 gn (2)

The Data on Water

• As data centers get larger, they are getting

thirstier as well. The enormous volume of

water required to cool high-density cloud

computing server farms is making water

management a growing priority for data

center operators. A 15-megawatt data center

can use up to 360,000 gallons of water a

day, according to James Hamilton, a data

center designer and researcher at

Amazon.com.

Page 14: Introducing nereus for cooling 09112014 gn (2)

The Data on Water

• Hospitals on average use 136,000

gallons of water / year / bed for cooling

Page 15: Introducing nereus for cooling 09112014 gn (2)

Get the Water Chemistry Right

Proper Water Chemistry Allows Higher Cycles

-

2,000,000

4,000,000

6,000,000

8,000,000

10,000,000

12,000,000

14,000,000

2 4 6 8

Annual Water Use 500 Tn Chiller

Page 16: Introducing nereus for cooling 09112014 gn (2)

Carbonate Based Scales• 6/18 of common scales in cooling applications

are associated with Carbonate / BiCarbonate

– Calcite

– Aragonite

– Witherite

– Strontianite

– Calcium Oxalate

– Stederite

• Eliminate this with H+

CO3-2 + 2H+= CO2 + H200 0

0

Condensafe II

In the past Today

danger

Page 17: Introducing nereus for cooling 09112014 gn (2)

Carbonate Based Scales• 4/18 of common scales in

cooling applications are

associated with Sulfate

– Anhydrite

– Gypsum

– Barite

– Celestite

• Eliminate this by not feeding

H2SO4

CO3-2 + 2H+= CO2 + H200 0

0

Condensafe II

In the past Today

danger

Page 18: Introducing nereus for cooling 09112014 gn (2)

Condensafe II

• Synthetic

• Functional replacement for H2SO4

• On June 18, 2008

– Dr. Robert Scheuplein, Toxicologist and Veteran Director of the Office of

Toxicology Sciences at FDA’s Center for Food Safety and Applied Nutrition.

• Dr. Scheuplein has assessed that the active ingreadient in Condensafe II is “Generally Recognized as Safe

(GRAS) in accordance with FDA assessment guidelines.

• Condensafe product formulations

– carry a triple zero Hazardous Materials Information System Score

– An A rating with regards to required PPE

– Are 100% biodegradable in 30 days or less per EPA, Design for the Environment,

– OECD and Hach Reactor method guidelines and meet or exceed stringent Direct Release Guidelines for 10 day

bio-degradation.

– The entire family of SAFE products

• are non-regulated by the

– US D.O.T.,

– CANADIAN TDG, IMO and IATA.

• are classified as non-voc, non-corrosive, non-mutagenic, and non-toxic.

• show no potential for the generation of carbon dioxide under NIOSH 7903, OSHA & ACGIH testing protocols.

Page 19: Introducing nereus for cooling 09112014 gn (2)

All Good Cooling Inhibitors Contain Common

Building Blocks – BZT

• BZT is a corrosion inhibitor and/or yellow metal deactivator based on 1,2,3-

benzotrizole.

– BZT prevents corrosion of yellow metals such as copper, copper alloys, bronze, and other

metals.

– BZT inhibits the corrosion of steel, cast iron, cadmium and nickel alloys under certain

conditions.

– BZT reduces the corrosive influence of copper ions on various metals.

– HEDP

• HEDP is an organophosphoric acid corrosion / scale inhibitor.

– HEDP can chelate with Fe, Cu, and Zn ions to form stable chelating compounds.

– HEDP shows excellent scale and corrosion inhibition effects under temperature 250℃.

– HEDP has good chemical stability under high pH value, hard to be hydrolyzed, and hard to be

decomposed under ordinary light and heat conditions.

– HEDP acid/alkali and chlorine oxidation tolerance are better than that of other

organophosphoric acids (salt).

– HEDP can react with metal ions in water systems to form hexa-element chelating complex,

with calcium ion in particular.

– PBTC

• PBTC acts as a crystal modifying agent and threshold inhibitor for calcium and other

metal salts.

– PBTC is widely used in industry as a sequestering agent and calcium carbonate scale inhibitor.

– In systems that utilize oxidizing microbiocides, such as bromine, PBTC exhibits superior

stability under oxidizing conditions compared to other organophosphonate compounds.

– Silica Control Polymer

• ACUMER 5000 is a proprietary multifunctional polymer with a molecular weight of

5000 that provides outstanding silica and magnesium silicate scale inhibition.

– ACUMER 5000 prevents silica-based scale formation by dispersing colloidal silica and by

preventing magnesium silicate scale formation at heat transfer surfaces

Page 20: Introducing nereus for cooling 09112014 gn (2)

Alternatives

• Do Nothing

• Dolphin and or Magnets

– Relies on Low Cycles

• Wastes Water

• Deposits

• Corrosion

• Softeners

– Improper water chemistry results in corrosion

• Other Water Treatment Companies

– Low degree of monitoring

– Disincentive to provide service

Page 21: Introducing nereus for cooling 09112014 gn (2)

Traditional Water Treatment

• Monitored

– Conductivity

– pH

• Controlled

– pH

– Conductivity

– Antiscale pump on and off

Page 22: Introducing nereus for cooling 09112014 gn (2)

Dolphin

• Controls nothing

• Tower is bled to keep – Cycles Low

– Water Use High• Essentially once through cooling

Page 23: Introducing nereus for cooling 09112014 gn (2)

Softeners

Softeners are not recommended for galvanized towers

• Historically, maximum service life was obtained by maintaining the chemistry of

the circulating water at an essentially neutral state (pH of 6.5 to 9.0) and

allowing the natural formation of a protective, light crystalline film on the zinc

surface which retarded the formation of white rust.

• While there is still some disagreement on the actual cause of the recent increase

in reported cases of "white rust", various water treatment experts are concluding

that some of the newer, higher alkaline, treatment chemistries actually inhibit the

formation of protective films on the galvanized surface and thus allow the

development of white rust.

• There are also indications that soft water (less than 30 ppm total hardness),

when combined with these high pH conditions, can exacerbate the problem.

Page 24: Introducing nereus for cooling 09112014 gn (2)

We Use Water More Effectively

Page 25: Introducing nereus for cooling 09112014 gn (2)
Page 26: Introducing nereus for cooling 09112014 gn (2)

Nereus On Line Chemistry

• Conductivity

– Controls cycles of concentration

• pH

– Controls alkalinity / LSI / Scale

• ORP

– Controls biocide feed

– Biological control

• Antiscalant

– Controls scale

• Ca

• Si

• Fe

Page 27: Introducing nereus for cooling 09112014 gn (2)

Nereus On Line Meters

• Make Up– Water Use and cost

• Bleed– Sewer discharge and cost

• Recirculation– Supply to Heat Exchangers

• Temperature– Air Dry

– Air Wet bulb

– Heat exchanger supply water

– Heat exchanger return water

– Refrigerant condensing temperature

• Chemical inventory levels

• Chemical feed rate

Page 28: Introducing nereus for cooling 09112014 gn (2)

Nereus Auxilary

• Corrosion coupons– System metallurgy

• Biological Testing– Total Aerobic Count

– Sulfate Reducing Bacteria

– Mold

– Fungus

Page 29: Introducing nereus for cooling 09112014 gn (2)

Nereus Calculations

• Tower– Efficiency and efficiency vs design

– Approach and approach vs design

– Delta T and delta T vs design

• Heat Exchanger– Approach and approach vs design

– Heat Flux in BTU / Sq. Ft. / Hr. and Heat flux vs

design

– $ lost due to fouling

• Today / this Month / YTD

• Yr over Yr

• Water– $ / Day, Month, Yr

– $ vs budget Day / Month / Yr

– Yr over Yr

• Sewer– $ / Day, Month, Yr

– $ vs budget Day / Month / Yr

– Yr over Yr

• Chemical– % Tank level

– $ / Day, Month, Yr

– $ vs budget Day / Month / Yr

– Yr over Yr

Page 30: Introducing nereus for cooling 09112014 gn (2)

Nereus Calculations

• Refrigeration tns on line

• Refrigeration as a % of design max

• Cost / Tn of refrigeration for – Water actual / actual vs budget / Yr vs Yr

– Sewer actual / actual vs budget / Yr vs Yr

– Chemical actual / actual vs budget / Yr vs Yr

– Power actual / actual vs budget / Yr vs Yr

• Refrigeration Efficiency– Kw / Tn refrigeration actual / actual vs budget / Yr vs Yr

Page 31: Introducing nereus for cooling 09112014 gn (2)

Nereus vs Old School

Page 32: Introducing nereus for cooling 09112014 gn (2)

We Use Water More Effectively

Page 33: Introducing nereus for cooling 09112014 gn (2)

Getting Started• No Cost to Client

– Water Samples provided to SWS LLC

• City & Tower

– System Information

• Cost

– Water, Sewer, Power, Descaling

– Tns total system design

– % Load On Line

» Fall, Winter, Spring, Summer

» Days in each season

• Output with in 2 weeks

– Savings available, Cap Ex, Op Ex

• Process guarantee

– $ savings will be delivered

– System will operate with less scale than is currently the case

– System will operate with less corrosion than is currently the case

– System will operate with less energy than is currently the case

Page 34: Introducing nereus for cooling 09112014 gn (2)

Appendix

• Chiller Facts

• Measuring

• Definitions

• Chillers

• Fouling

• Chiller Efficiency

• Improving Chiller Efficiency

• Typical Water Treatment Problems

• Pitting

Page 35: Introducing nereus for cooling 09112014 gn (2)

Chiller FactsThis article has been published in Maintenance Technology and Hotel Engineer Magazines.

• Chillers are the single largest energy-using component in most facilities, and can

typically consume over 50% of the electrical usage.

• Chillers use approximately 20% of the total electrical power generated in North America

• U.S. Department of Energy estimates that chillers expend up to 30% in additional

energy through inefficiency.

• With over 100,000 chillers in the United States alone, inefficiency costs industry billions

of dollars in energy annually.

• Chillers running inefficiently also result in decreased equipment reliability, increased

maintenance intervals and shortened lifespan. The slightest decrease in chiller

performance can have a major impact on efficiency.

• For instance, every 1°F increase in condenser water temperature above full load

design can decrease chiller efficiency by 1% to 2%.

• A failing or neglected water treatment program can reduce efficiency 10% to 35% or

more in extreme cases.

Page 36: Introducing nereus for cooling 09112014 gn (2)

Measuring

• The metric for water usage in the data center is defined at a

high level as Water Usage Effectiveness or WUE

Annual Water Usage

IT Equipment Energy

• The units of WUE are liters/kilowatt-hour (L/kWh).

• IT Equipment Energy. This includes the load associated with all

of the IT equipment, including computer, storage, and network

equipment, along with supplemental equipment such as KVM

switches, monitors, and workstations/laptops used to monitor

or otherwise control the data center

• “We think that 0.22 L/kWh is a great result, but it should be

noted that the WUE concept is fairly new and, to our

knowledge, no one else has publicly reported WUE yet,” writes

Facebook’s Daniel Lee. “

Page 37: Introducing nereus for cooling 09112014 gn (2)

Definitions

• 1 ppm

– 1 Lb. of something / 1,000,000 Lbs. of something

– Ex 1 pounds antiscale / 1,000,000 Lbs water

– 10 pounds antiscale / 1,000,000 Lbs water

– Our Dose of antiscale

• 100 – 200 pounds antiscale / 1,000,000 Lbs water

• 10 – 20 / 100,000

• 1 - 2/ 10,000

• 2 – 4 / 20,000 Find 2 guys at an average a’s game

• Q or Heat Flux = BTU / Sq. Ft. / Hr

• 1 Tn Refrigeration = 12,000 BTU / Hr rejected

• Cycles = How many times a feed water is concentrated up

• Bleed = water removed from the system to control cycles

Page 38: Introducing nereus for cooling 09112014 gn (2)

Definitions

• Heat exchangers were initially developed to use plain (or

smooth) heat transfer surfaces.

– An Enhanced heat transfer surface has a special surface geometry

that provides a higher thermal performance, per unit base surface

area than a plain surface.

Internal Enhancement External Enhancement

Page 39: Introducing nereus for cooling 09112014 gn (2)

Chillers

• What is a Chiller?

– A chiller is a water-cooled air conditioning system that cools inside air, creating a

more comfortable and productive environment.

– Chillers are also used in the manufacturing environment to provide "process"

cooling to equipment in an effort to maximize productivity.

• With large facilities, such as commercial buildings, hospitals, universities,

government facilities and theme parks, the cost of energy to generate

cooling in excess of 50 tons is cost prohibitive with air-cooled units.

• Water-cooled chillers produce higher tonnage at lower costs per ton,

creating greater energy efficiency.

• Typical Home

– has 3-5 tons of cooling capacity.

• Typical Data Center

– has 300 – 1000 + tns cooling

– Older = smaller

– Newer = larger

• Typical Hospital

– has 2 – 5 tns / bed

Page 40: Introducing nereus for cooling 09112014 gn (2)

Chillers

• How a Complete Chiller System

Works

– Chillers circulate chilled water to

air-handlers in order to transfer

heat from air to water.

– This water then returns to the

evaporator side of the chiller

where the heat is passed from the

water to a liquid refrigerant (freon).

– The refrigerant leaves the

evaporator as a cold vapor and

enters the compressor where it is

compressed into a hot vapor.

– Upon leaving the compressor, the

vapor enters the condenser side of

the chiller where heat is

transferred from the refrigerant to

the water side of the condenser

where it is circulated to an open

cooling tower for the final removal

of heat via evaporation in the

cooling tower.

Closed Chilled Water Loop Open Tower Water Loop

Potential Fouling Points

On Water Side

Page 41: Introducing nereus for cooling 09112014 gn (2)

Fouling• 240 ton chiller

– Greg Bush Regional Services Lead for Americas

• SAP GFM Data Center Services

• Regional Energy Manager for Americas

– In the case of SAP at $0.15 kWH

– $5,600.00 a year in wasted electricity per degree approach

fowling. This is a meter verified number.

• Chiller in study has efficiency of .65 Kw per ton annualized.

EPA statement said a 1000 ton chiller at

$0.11 per kWH is $10,000.00 a year of

wasted energy per degree fouling

Page 42: Introducing nereus for cooling 09112014 gn (2)

Chiller Efficiency

• Chiller efficiency is the amount of energy (electricity) it takes to produce a "ton" of

cooling. It is expressed as kw/ton.

– All chillers have a designed kw/ton efficiency that was established when the chiller was

commissioned.

– Plant design, water treatment, maintenance practices, chiller age, cooling tower design,

cooling load and plant operations dramatically effect chiller operating efficiency and

operating costs.

• A chiller "operator" is known by several titles, including Stationary Engineer, HVAC

Engineer and Service Technician.

– Operation and maintenance includes collecting and logging data from various gauges,

controls and meters located on or near the chiller.

• There are essentially three types of maintenance performed on chillers;

– Water chemistry is maintained to keep proper balance and minimize the effects of scale,

corrosion and micro-biological / debris fouling.

– Mechanical maintenance includes proper lubrication, adequate liquid refrigerant, oil levels

and pump curve tests.

– Operational procedures include eddy-current tests, oil analysis, calibration of gauges and

meters and other various tests.

Page 43: Introducing nereus for cooling 09112014 gn (2)

Improving Chiller Efficiency

• The best way to provide precise data, obtain concrete results and minimize problems

is to verify flow rates to the chiller for tonnage measurements and other

calculations to determine efficiency.

Four methods for determining flow are

inline flow meter, external flow meter, delta pressure and delta temperature.

• The use of delta temperature along with a flow meter or delta pressure gauge creates a powerful

diagnostic tool that can detect problems affecting efficiency in the chiller system.

• Increase the Chill Water Temperature and Lower the Entering Condenser Water Temperature For

constant speed chillers, every 1°F increase in chill water temperature can increase chiller energy

efficiency 1 to 2%. For variable speed chillers, every 1°F increase in chill water temperature can result in

a 2 to 4% efficiency increase.

• Take advantage of wet bulb conditions in the cooling tower system to lower the chiller's entering

condenser water temperature. This can result in a 1 to 1.5% efficiency improvement for every 1°F below

the chiller full load design.

Page 44: Introducing nereus for cooling 09112014 gn (2)

Improving Chiller Efficiency

• A good water treatment program is a necessity for efficiency. Maintaining the proper

water treatment will prevent costly problems.

– If a problem(s) already exists, take the necessary steps to correct it immediately.

• Biocide and Scale/Corrosion Protection

– A water treatment program provides a biocide program that minimizes microbiological

growth along with excellent scale/corrosion protection.

– Microbes, if not properly controlled, can cause numerous problems, such as forming sticky

slime deposits in the tube bundle of a chiller, possibly reducing heat transfer efficiency 15%

or more.

– The situation can be compounded by the formation of permanent scale or iron deposits on

the sticky site. If this occurs, an additional 10 to 20% loss in heat transfer efficiency may

result.

Page 45: Introducing nereus for cooling 09112014 gn (2)

Typical Problems Encountered

• Tower Basin

– Calcium deposits

– Corrosion Tubercle

• Tubercle removed

• Under Deposit Corrosion

• Corrosion Perforation– Under Deposit Corrosion

Page 46: Introducing nereus for cooling 09112014 gn (2)

Pitting

• All forms of corrosion, with the exception of some types of high-

temperature corrosion, occur through the action of the electrochemical

cell.

• The elements that are common to all corrosion cells are:

– An anode where oxidation and metal loss occur,

– A cathode where reduction and protective effects occur,

– Metallic and electrolytic ( system water ) paths between the anode and

cathode through which electronic and ionic current flows,

– A potential difference that drives the cell.

• The driving potential may be the result of differences between the characteristics of

dissimilar metals, surface conditions, and the environment, including chemical

concentrations.

Page 47: Introducing nereus for cooling 09112014 gn (2)

Pitting

• Pitting corrosion is a localized form of corrosion by which cavities or

"holes" are produced in the material.

• Pitting is considered to be more dangerous than uniform corrosion

damage because it is more difficult to detect, predict and design against.

• Corrosion products often cover the pits.– A small, narrow pit with minimal overall metal loss can lead to the failure of an entire

engineering system.

– Pitting corrosion, which, for example, is almost a common denominator of all types of

localized corrosion attack, may assume different shapes.

• Pitting is initiated by:– Localized chemical or mechanical damage to the protective oxide film; water chemistry

factors which can cause breakdown of a passive film are acidity, low dissolved oxygen

concentrations (which tend to render a protective oxide film less stable) and high

concentrations of chloride (as in seawater)

– Localized damage to, or poor application of, a protective coating

– The presence of non-uniformities in the metal structure of the component, e.g. nonmetallic

inclusions.

• Theoretically, a local cell that leads to the initiation of a pit can be caused

by – an abnormal anodic site ( under a deposit ) surrounded by normal surface which acts as a

cathode,

– or by the presence of an abnormal cathodic site surrounded by a normal surface in which a

pit will have disappeared due to corrosion.

Page 48: Introducing nereus for cooling 09112014 gn (2)

Theory

• Water Chemistry– Lack of proper water treatment chemistry allows deposits to occur

– Ca, Mg, Fe

– Deposits cause corrosion

– Corrosion products cause more deposits / corrosion with out proper treatment

Page 49: Introducing nereus for cooling 09112014 gn (2)

Observations

• Corrosion

• Corrosion Products

• Corrosion products covered with

scale

• Scale is chips off and anode is

formed

• Small anode

• Combined with large cathode

• Pitting is expected