01-24-2012
EXHIBIT D
TRANSPORTATION AND EXCHANGE
INTERCONNECT PROJECT
PROCEDURE
for
DESIGN, INSTALLATION, RECORDS
AND GAS QUALITY REQUIREMENTS
Revision 13
TABLE OF CONTENTS
Design, Installation, Records, and Gas Quality Requirements
CODE REQUIREMENT 1
1. METER TUBE REQUIREMENTS 1
2. OVERPRESSURE PROTECTION AND FLOW CONTROL REQUIREMENTS 3
3. ELECTRONIC GAS MEASUREMENT REQUIREMENTS 3
4. DATA COMMUNICATIONS EQUIPMENT 4
5. GAS SAMPLING 5
6. GAS QUALITY 5
7. MATERIALS FOR GAS PIPING 6
8. CATHODIC PROTECTION 9
9. CONTRACTORS/MANUFACTURERS 9
10. FABRICATION 9
11. DRAWINGS AND RECORDS 9
12. EXISTING EQUIPMENT & EXISTING METER STATION EXPANSION/ UPGRADE 10
13. INSTALLATION REQUIREMENTS 10
14. INSPECTION 12
15. HYDROSTATIC/PNEUMATIC TESTING 12
16. WELDING 12
17. RADIOGRAPHY 14
18. CLEANING AND PAINTING 15
19. FACILITIES COMMISSIONING GENERAL OVERVIEW 15
20. MAINTENANCE AND SECURITY 18
ATTACHMENTS
ATTACHMENT A - Company and US DOT Documentation Requirements 19
ATTACHMENT B - Typical Interconnect and Meter Standard Drawings 20
ATTACHMENT C - Approved Manufactures 24
ATTACHMENT D - Approved Meter Fabricators 43
- 1 -
DESIGN, INSTALLATION, RECORDS,
AND GAS QUALITY REQUIREMENTS
CODE REQUIREMENT
The Connecting Party’s meter station and associated piping will comply with all requirements
for materials, design, fabrication, welding, testing and installation, as stated in Part 192, Title
49 of the U. S. Department of Transportation (DOT) Code of Federal Regulations,
“Transportation of Natural and Other Gas by Pipelines: Minimum Federal Safety Standards”
and ANSI/ASME Code for Pressure Containing Piping, B31.8 (latest edition) Gas
Transmission and Distribution Piping Systems.
I. METER TUBE REQUIREMENTS
1.1 Meter Tube – The meter tube will meet or exceed Spectra Energy and/or its
subsidiaries (“Company”) specifications and will be designed in accordance
with the latest edition of AGA/ANSI B109 specifications per type of meter
station constructed. The meter station will additionally be designed per
Company specifications DS-MR1.6 and ES-PQ1.1. Company will determine the
type and design of the measurement facility required. Meter tubes will be
furnished by the meter fitting vendor or will be fabricated by a shop approved by
both the fitting vendor and Company. If fabricated by an approved shop, the
welding procedure and welder test report will be provided to Company for
Company’s approval prior to fabrication. The meter tube must be inspected by
a Company representative at the meter tube fabricator’s shop location.
1.2. Meter Fittings - Meter fittings will comply with AGA reports in conjunction
with the corresponding ANSI 2530-92 / API 14.3 / GPA 8185-92 reports.
A. Orifice Meter: AGA Report #3 (current edition) and Company Standard
Drawing SP-5000
B. Turbine Meter: AGA Report #7 (current edition)
C. Displacement Meter: ANSI B109 (current edition)
D. Ultrasonic Meter: AGA Report #9 (current edition) and Company Standard
Drawing SP-5011
1.3 Inspection – A Company representative must verify the meter tube
measurements prior to installation on meter skid. Connecting Party will notify
Company fifteen (15) business days prior to meter micing, ultrasonic meter
calibration, testing or inspection. Company must inspect the measurement
facilities, including witnessing the “micing” of the meter tube, at the vendor’s
fabrication yard, prior to shipment. If the inspection is performed after the
measurement facilities have been shipped to the meter site, the Connecting Party
will provide all necessary manpower and equipment to disassemble the tube for
- 2 -
inspection by Company. If meter tube(s) fail to meet the AGA or ANSI B109
requirements, Connecting Party is responsible for correcting the discrepancies
including shipment to repair facilities and return to the meter site.
1.4 Ultrasonic Meter Calibration – Prior to shipment for calibration, the meter tube
will inspected by a Company representative. Each ultrasonic meter will be
calibrated per Company standards, and such calibration will be witnessed by a
Company representative. The entire assembly, per Company Standard Drawing
SP-5011 including all spool pieces, inspection tees and any other piping that
constitutes the “meter tube,” will be calibrated together as one unit. The tube
will not be taken apart once the calibration has been completed. All thermo
wells and test wells will be installed prior to calibration.
1.5 Orifice Meter Runs - Single meter runs will be equipped with dual chamber
(senior type) orifice fittings. The orifice meter fitting will be a Daniel Senior or
a TMCO Sure Shot/Dual Chamber – three (3) piece assembly per Company
Standard Drawing SP-5000.
1.6 Flow Conditioner – A Daniel Profiler or CPA-50E 304 stainless steel flow
conditioner will be installed on all meter tubes as specified by Company.
1.7 Pipe Couplings - Couplings are not permitted.
1.8 Name Plate - Manufacturer’s nameplate will be securely attached to the meter
tube. Nameplate data will include design pressure, test pressure, purchaser’s
drawing number, manufacturer’s name, and date of purchase.
1.9 Pipe - Seamless steel pipe and ERW pipe are acceptable.
1.10 Taps - A total of six taps will be installed on the meter run – two taps upstream
and four taps downstream. Reference Company Standard Drawing SP-5000 for
orifice meters or SP-5011 for ultrasonic meters for size, location, placement and
orientation of the taps. Additional taps may be required for gas sampling, flow
control or pressure control based upon proposed gas volumes or operating
conditions as determined by Company and specified on Company’s Standard
drawings.
1.11 Closures - Yale head end closures will be installed to provide a means for open-
ended inspection of the meter tube without disassembly.
1.12 Transmitters - All electronic transmitters for gas measurement will be installed
as close to the meter as possible and at an elevation to avoid interference from
liquids per AGA-3 / ANSI – API 2530.
1.13 Bypass - No bypass is allowed around the meter run.
- 3 -
II. OVERPRESSURE PROTECTION & FLOW CONTROL REQUIREMENTS
2.1 Over pressure protection (OPP) and flow control requirements are based on
approved maximum gas flows at the meter station. Any increase in maximum
flow will require Company’s review and approval and may require upgraded or
additional equipment, as specified by Company.
2.2 All Meter Stations – An OPP device - relief valve, pressure monitor control
valve, etc. – is required at all meter stations. The type of OPP device will be
determined by Company.
2.3 Relief Valve Requirements - The manufacturer, type and size of the relief valve
to be installed will be approved by the Company. The relief valve will be
installed on the upstream side of the meter station. The capacity of the relief
valve will ensure the gas pressure will not exceed the meter station maximum
allowable operating pressure (MAOP) or Company’s pipeline MAOP or
Deferred Maximum Operating Pressure (DMOP), as applicable, plus four
percent (MAOP * 104% or DMOP * 104%). The diameter of the relief valve
riser piping will be a minimum of one inch larger than the size of the relief
valve. Reference Attachment C - Drawing HT-SC-1001.
2.4 Connecting Party Relief Valve – If approved by Company, Connecting Party’s
existing relief valve or monitor regulator may be used as overpressure protection
if the Connecting Party’s facilities have an MAOP that is less than or equal to
Company’s pipeline MAOP.
2.5 Positive Shut-in Valve – A solenoid operated On/Off Valve will be installed if
the approved maximum gas flow allowed is greater than or equal to 5.0 million
standard cubic feet per day (MMscf/d) and less than 25.0 MMscf/d.
2.6 Control Valve - A flow control (throttling) valve will be installed if the
maximum gas flow allowed is greater than or equal to 25 MMscf/d or as
otherwise determined by Company based upon gas quality or operating
conditions. Control valves will include a 3-valve manifold with bypass.
2.7 Multiple Control Valves (Worker & Pressure Monitor) – Two control valves
may be installed in series instead of an atmospheric relief valve dependent upon
gas flow parameters and Company approval. Standard drawings of the Meter
Station facilities are included in Attachment C of this Guideline for reference.
III ELECTRONIC GAS MEASUREMENT REQUIREMENTS
3.1 Electronic Gas Measurement (EGM) equipment and facilities are required for all
meter stations. Company will install EGM facilities at the meter station.
- 4 -
3.2 The EGM facilities at all new or upgraded meter stations will include a
Company approved remote terminal unit (RTU). Company will determine the
type of RTU based upon specific meter station requirements.
3.3 EGM Equipment - The following EGM Equipment will be ordered by Company:
A. EGM building(s), consisting of
i) RTU
ii) Battery charger or solar panels as determined by Company
iii) Battery box
iv) Communication equipment
v) Junction box, if required
vi) Gas sampling and quality monitoring equipment, as specified by
Company
B. All transmitter equipment for Company use will be specified by Company.
i) Transmitters used for custody transfer measurement will be multivariable
transmitters.
ii) Transmitters used for process control may be single variable transmitters.
3.4 EGM Equipment Placement - Company operations field representative or
Company’s on-site inspector will coordinate the placement of the EGM
equipment with Connecting Party.
3.5 Electronic Data Communications - Company will determine the type of EGM
communication media required for the meter station. Equipment type will be
based on the location, elevation and RTU required at the meter station site.
Radio communications are preferred and may require a radio tower at the meter
station. Alternate communication methods include satellite, cellular, TELCO
dial up telephone and leased circuit.
IV. DATA COMMUNICATIONS EQUIPMENT
4.1 Radio Communications - Approved radio communications equipment will be
installed by Company or Company-approved contractor including installation of
the foundation and any required radio towers.
4.2 Satellite Communications – Satellite equipment will be installed by Company or
Company-approved contractor.
- 5 -
4.3 TELCO Data Circuit (Lease Line) - Connecting Party will install utilities
required to provide telephone service to the meter station if required.
V. GAS SAMPLING
A gas analysis is required for all receipt connections to verify that the gas complies with
Company’s FERC gas tariff. Requirements for gas sampling equipment are determined
by Company and based on gas quality and approved maximum gas flows through the
meter station. Any change in gas flow may require additional or upgraded equipment,
as determined by Company. Gas sampling and equipment requirements are based upon
the following flow rates:
5.1 Initial Gas Sample -- Prior to first flow through the meter station, Connecting
Party must demonstrate the ability to comply with Company gas quality
standards.
5.2 Spot Sampler - Spot gas samples will be manually collected if the approved
maximum gas flow is less than or equal to 5 MMscf/d, unless otherwise
specified by Company.
5.3 Continuous Sampler - A continuous gas sampler is required if the approved
maximum gas flow is greater than or equal to 5 MMscf/d and less than 15
MMscf/d or if the gas source is from multiple wells, unless otherwise specified
by Company.
5.4 Gas Chromatograph - A gas chromatograph is required if the approved
maximum gas flow is greater than or equal to 15 MMscf/d. (Exception: All
receipt interconnects on the ETNG system will require chromatograph sampling
regardless of volumes).
VI. GAS QUALITY
6.1 Gas quality monitoring equipment requirements will be determined by Company
and are based upon actual gas quality and approved maximum gas flow through
the meter station. Any change in proposed gas flow or quality may require
additional or upgraded equipment, as specified by Company.
A. Moisture Analyzer – The need for a moisture analyzer is to be determined by
Company on a case by case basis. Additional water vapor content-
monitoring equipment may be required based on the results of the gas
quality sample and actual quality and quantity of gas received.
B. Additional Analyzers – Any additional requirements to maintain gas quality
will be determined on a case by case basis by Company.
6.2 Meter Station Shut-In - Company will shut in the meter station if the gas quality
fails to meet Company’s gas quality standards.
- 6 -
VII. MATERIALS FOR GAS PIPING
7.1 Valves
A. All valves will be of forged steel construction and meet API 6D
requirements. Malleable iron or cast iron valves are not acceptable.
B. Ball valves will be of ¼-turn valve design.
C. Meter tube isolation valves must be full-open ball or gate valves.
D. The minimum valve design rating is ANSI 600.
E. All valves will meet ANSI Specification ANSI B16.5 for steel pipe flanges,
flanged valves and fittings.
F. All ¼-inch, ½-inch, ¾-inch and 1-inch valves will be rated for a minimum
3,000 psig working pressure.
G. Screwed-body valves are not acceptable.
7.2 Control Valves (if applicable) - The capacity of control valves will be verified
and approved by Company prior to Connecting Party’s procurement of the
valve.
7.3 Instrumentation Gas Supply System (if applicable) - A Company approved
instrument gas supply (IGS) system is required for each flow-controlled or
pressure-controlled device. A Welker DA-1 IGS is acceptable and should
include the following features:
A. Parallel Fisher 1301F regulators with spring range of 50-150 psig
(Primary regulator set at 105 psig; secondary regulator set at 100 psig
B. Pressure gauge, 0-300 psig operating range
C. Relief valve set at 125 psig
D. Two (2) Welker-style F-5 filter dryers
7.4 Fittings
A. All fittings will be of forged steel construction. Malleable iron or cast iron
fittings are not acceptable.
B. All fittings will meet the following guidelines:
- 7 -
i) ANSI B16.9 – Manufacturing Standard for Grade B fittings. Factory-
made, wrought-steel, butt-welded fittings, design and dimensional
requirements for all fittings.
ii) MSS-SP-75 – Manufacturing Standard for High Yield fittings.
Dimensional requirements for fittings < 16” use ASME B16.9.
iii) ANSI B16.11 – Manufacturing Standard for forged-steel, socket-welded
and threaded fittings.
iv) ASTM A234 – Material Standard for Grade B fittings.
v) ASTM A694 – Material Standard for High Yield fittings.
C. The design pressure rating, wall thickness, and design factor for fittings will
be equal to or greater than that of the pipe.
D. All fittings 2-inch diameter or greater will be butt-welded; all fittings below
2-inch diameter will be socket-welded if installed underground or threaded if
installed aboveground.
7.5 Flanges
A. All flanges shall meet the following standards:
i) ASME B16.5 – Manufacturing Standard for Grade B flanges ≤ 24”
(except 22”).
ii) MSS-SP-44 – Manufacturing Standard for High Yield flanges and
flanges 22” and > 24”. MSS-SP-44 and ASME Section VIII, Appendix
II. Flanges may be proof tested to ASME Section VIII, UG-101 as an
alternate.
iii) ASTM A105 – Material Standard for Grade B flanges.
iv) ASTM A694 – Material Standard for High Yield flanges.
v) ANSI rating of flanges shall meet MAOP requirements.
B. The minimum flange design rating is ANSI 600.
C. All flanges will meet ANSI B16.5 for Pipe Flanges and Flanged fittings.
7.6 Piping
A. All gas piping less than 3-inch nominal pipe diameter will be Schedule 80;
all gas piping 3-inch and greater nominal pipe diameter must be Schedule 40
- 8 -
or better. All gas piping will be either API-5L or seamless, ASTM A106,
Grade B steel pipe.
B. All steel gas piping for meter stations; regulator stations; compressor
stations; or platforms located offshore or in in-land navigable waters,
including pipe riser, will meet a design factor of 0.50. All other pipe will be
designed in accordance with DOT Subpart C – Pipe Design.
C. The inner diameter of pipe utilized as meter tube spool pieces will be within
+/- 1% of the meter inner diameter for orifice and ultrasonic meters.
7.7 Nuts and Bolts
A. All flange bolts will be alloy steel, grade B7, meet ASTM A193 or ANSI
B16.5, IMF-3W coated.
B. All nuts will meet ASTM A194 or ANSI B16.5, grade 2-H, IMF-3W coated.
C. At least three threads will protrude beyond each nut after completion of the
assembly process.
D. All washers (1 per bolt) will be made of hardened steel, meet ASTM-A325,
and IMF-3W coated.
7.8 Gaskets
A. Gaskets will be spiral wound; ANSI 600; 1/8-inch thick; style CGI; inner
ring material: 304 SS; filler material: non-asbestos; outer ring material: CS.
Gaskets cannot protrude into the gas flow.
B. Connecting Party will electrically isolate the Connecting Party’s meter
station piping from the Company’s mainline system. Company will
determine the applicable electrical isolation equipment required.
C. An insulated flange kit will be provided by the Company for flange or
flanges at the change of ownership. Installation will be coordinated by
Company field operations representative or Company’s on-site inspector.
D. Solid-state polarization cell replacement (PCR) must be installed across the
insulating flange and will be 3.7 kA fault current; hazardous rating: Class-1,
Division-2; 304 SS weld tabs; and corrosion inhibitor: Dairyland Model No.
PCR-3.7 KA-WTM, purchased from Dairyland Electrical Industries (P.O.
Box, Stoughton, WI 53589).
- 9 -
VIII. CATHODIC PROTECTION
8.1 Company must approve the applicable cathodic protection measures to be
installed for corrosion control of the meter station underground piping.
8.2 Packaged Zinc Grounding Anode: 1.4-inch x 1.4-inch x 5-feet with 10-feet
minimum of #2 AWG stranded copper HMWPE wire silver soldered to anode,
C/W prepared backfill consisting of 50% Bentonite clay and 50% Gypsum in a
cloth sack. The packaged anode will be purchased from Corrpro Companies,
Inc. (7000B Hollister, Houston TX. 77040).
IX. CONTRACTORS/MANUFACTURERS
The Connecting Party is responsible for selecting the contractor and manufacturer for its
facilities, unless otherwise specified by the Company. Attachment D to this Guideline is
a listing of Company-approved manufacturers for Connecting Party’s use in ordering
materials.
X. FABRICATION
10.1 Piping
A. The gas piping will be fabricated in accordance with the ANSI/ASME Code
for Pressure Containing Piping: B31.8 (latest edition).
B. Piping 2-inch diameter and larger will be butt-welded or flanged.
C. Piping and headers will be constructed so no residual stresses are introduced
by jacking on piping or mechanically forcing piping into alignment for
bolting of flanges or welding. Heating of pipe while under restraint to
achieve alignment or reduce residual stresses is not permitted.
10.2 Weld-o-lets & Thread-o-lets
A. Couplings are not allowed. Only weld-o-lets and/or thread-o-lets will be
utilized.
B. Threads on thread-o-lets will be chased after installation, and threaded plugs
will be installed.
XI. DRAWINGS AND RECORDS
11.1 Reference Drawings- Connecting Party will use the isometric drawings provided
in Attachment C as an example to design and construct proposed meter station.
- 10 -
11.2 Review of Connecting Party Drawings - Prior to the start of fabrication or
construction of the meter station, the Connecting Party will submit all drawings
of the measurement facilities including plot plan, all bill-of-materials, and piping
and instrumentation diagrams (P&ID’s) to Company for approval. The
drawings will indicate the pressure ratings of the facilities and illustrate all
major piping, EGM, measurement equipment and instrumentation. The
approved drawings and bill-of-materials may not be changed without
Company’s prior written approval; Company may withhold such approval at its
sole discretion.
11.3 Equipment Layout - The Connecting Party’s measurement facility equipment
will be laid out according to the Company-approved drawings. Connecting
Party will “build to fit” its connecting piping from the meter station to
Company’s aboveground flanged connection after the Company facilities have
been installed.
11.4 As-Built Drawings - Within sixty (60) days of completion, the Connecting Party
will furnish to Company three (3) sets of all “as-built” drawings, including bill-
of-material, for the meter station. All drawings, including the bill-of-material
and mill test reports, must be sent to the Company Engineering Coordinator.
11.5 Records - DOT Maintenance Records will be provided as specified in the
Reimbursement, Construction, Ownership and Operation Agreement for the
meter station.
XII. EXISTING EQUIPMENT & EXISTING METER STATION EXPANSION/
UPGRADE
Should the Connecting Party utilize equipment or facilities already existing or
previously in gas service, the Connecting Party agrees that any such facilities not
conforming to the standards set forth in this guideline will be upgraded or replaced, as
necessary, and approved by Company prior to flow of gas through the subject facilities.
XIII. INSTALLATION REQUIREMENTS
13.1 Hot Tap Assembly – Company will fabricate and install the hot tap(s) and
associated piping terminating at a flange at the edge of Company ROW.
13.2 Meter Station Site Preparation – Connecting Party is responsible for obtaining
all property rights with ingress and egress assignment to Company for the meter
station site. Connecting Party must provide all-weather access as well as power
service and phone service if required. Connecting Party must prepare the meter
station site for the proposed facilities.
13.3 Meter Building - Connecting Party is responsible for installation of the meter
building or canopy, if required, as determined by Company. The building or
- 11 -
canopy type must be appropriate for the region’s weather conditions and
maintenance requirements, as determined by Company.
13.4 EGM
A. Building – Company will fabricate, outfit and install the EGM building. The
EGM building will house the RTU and electrical equipment of the Company
only. The Connecting Party will be responsible for providing a separate
EGM building for its RTU and associated equipment.
B. Site Preparation – Connecting Party will be responsible for site preparation
and installation of the EGM building foundation, unless specified otherwise
by Company.
C. Transportation – Company is responsible for the transportation of the EGM
building to the meter station site.
D. Conduit - Connecting Party will be responsible for the installation of all
conduits for power, communications and EGM equipment unless specified
otherwise by Company. All below ground conduits shall be PVC – coated
rigid metallic and a minimum of 1” diameter in size. Conduit and fitting
sizes of 1¼” diameter are not permitted. Installations will comply with NEC.
E. Electrical Wiring - Connecting Party will be responsible for the installation
of all wiring for power, communications, and EGM equipment and
grounding system unless specified otherwise by Company. The primary
power grounding system maximum resistance in the USA is three (3) ohms
to true earth ground when measured according to IEEE 81, unless specified
otherwise by Company. Instrument grounding system resistance will not
exceed one (1) ohm to the main ground system, unless specified otherwise
by Company. Installation will comply with NEC. Company operations field
representative will terminate all final connections to Company’s EGM
equipment.
13.5 Isolation Valve - A stand alone and separate isolation valve must be installed,
owned and operated by the Customer for the purpose of purging the Customers
gas system. The isolation valve must be located within 25’ feet of the meter
facility. The meter run isolation valves cannot be used for the purging of the
Customers gas system.
13.6 Separator - Company pipelines operating under an alternative design/waiver at
stress levels above 72% SMYS will require a filter separator to be installed at all
receipt M&R Stations to prevent liquids or contaminates from entering the
pipeline. A Company approved filter separator with a minimum removal
efficiency of 99.5% of liquid and solid particles 1 micron or larger is required.
Prior to specifying which type of separator is required, each location will be
evaluated as to gas quality and contaminates. The Company evaluation will
- 12 -
dictate if a filter/liquid separator is required along with a CO2 analyzer, Moisture
analyzer and or an H2S analyzer.
XIV. INSPECTION
14.1 Company reserves the right to inspect all facilities during installation,
fabrication and/or testing. Prior to start of construction, Company requires two
(2) weeks prior notice to arrange for inspection of the Connecting Party’s
facilities.
14.2 The inspection notifications will be directed to the Company Engineering
Coordinator unless specified otherwise by Company Project Manager.
XV. HYDROSTATIC/PNEUMATIC TESTING
15.1 Pipe Test Section - The gas piping, from the point of interconnection to the
Company facilities, including all piping 40-feet upstream (receipt) or
downstream (delivery) of the measurement facilities, shall be hydrostatically
tested to the lesser of 100% SMYS, 2 x MAOP or 1.5 x ACWP. If the MAOP is
less than 1110 psig, the 2 x MAOP will control. If the MAOP is greater than
1110 psig, the 1.5 x ACWP (for ANSI 600 valves and flanges) will control at
2220 psig. Pneumatic testing shall be 1.5 x MAOP. Pressure testing shall be in
accordance with Company Specification DP-CT1. The maximum design
pressure (-0, +50 psig) of the piping shall be held continuously for eight (8)
hours with no unaccounted for pressure loss for two (2) continuous hours during
the duration of the test. Quarter hour (15 minute) recordings will be made of the
test pressure and ambient and pipe temperatures for the first two hours of the test
and every 30 minutes for the remainder of the test. Dead weights will be used
and dead weight pressures recorded. Dead weights and pressure and
temperature recorders will be certified and calibrated by an AL2A certified
laboratory within six months prior to the date the test is performed.
15.2 Test Records - A copy of the test report log, including copies of the dead weight
and recorder’s calibration certificates, must be sent to the Company Engineering
Coordinator prior to first flow through the interconnect.
XVI. WELDING
16.1 Procedures - All welding of pipe will be performed in accordance with the
established written procedures for the materials being welded. The procedures
for welding of pipe will be qualified under API Std.1104, 20th Edition, October
2005, with Errata\Addendum, July 2007 or ASME BPVC Section IX, 2004
Edition, including addenda through July 1, 2005.
16.2 Welder Qualifications - All welding of pipe will be in accordance with API
Std.1104, 20th Edition, October 2005, with Errata\Addendum, July 2007 (“API
- 13 -
1104”) or ASME BPVC, Section IX, 2004 Edition, including addenda through
July 1, 2005 (“ASME BPVC”).
A. Welding will be performed by welders who were qualified according to a
Company-provided welding procedure or a Company-approved,
Contractor-provided procedure.
B. Welders working on compressor station, meter station or pipeline
components will be qualified by destructive testing. Welder qualification
destructive testing will be in accordance with API 1104.
B. Qualifications of welders for manual welding processes shall be in
accordance with Section 6 of API 1104 or in accordance with ASME
BPVC.
C. Mechanized welding processes shall be in accordance with Section 12 of
API 1104, or as directed by Company Engineer. ASME welder
qualifications shall be in accordance with the requirements of ASME
BPVC Section IX, or as directed by Company Engineer.
D. Qualified welders must maintain copies of the qualified welding
procedures, welder qualification reports, and Operator Qualification
Certifications in their possession for the duration of the project.
E. Qualification records for each welder who has welded on the pipe will be
current within one (1) year for the appropriate scope of work.
16.3 Repairs - All repair-welding will be performed in accordance with an
established written procedure per the latest DOT approved edition of API 1104.
16.4 Replacement - One attempt at repair is permitted on piping after which the
defective weld will be cut out as a cylinder.
16.5 Pipe Preheating - Preheating will be employed to 250°F minimum on all repairs
by welding.
16.6 Inspection - Welding will reflect a workmanlike appearance. It will be visually
inspected for such things as: undercutting; craters; high-low, inadequate or
excessive weld metal in cap; arc burns; cracks; and, when possible, incomplete
fusion or penetration. Arc burns will not be repaired and will be cut out as a
cylinder. Other defects will be repaired or cut out as needed to make the defect
area acceptable to Company’s on-site inspector. All cracked welds will be cut
out as a cylinder.
16.7 Clean Up - After welding of the orifice fitting, all welds inside of the meter tube
piping are to be ground smooth and flush with the wall of the pipe.
- 14 -
XVII. RADIOGRAPHY
17.1 Pipe Test Section - All gas piping welds from 40-feet upstream (receipt) or
downstream (delivery) of the measurement facilities to the connection with
Company will be 100% radiographically examined in the manner prescribed by
the API Std.1104, 20th Edition, October 2005, with Errata\Addendum, July
2007 (“API 1104”).
17.2 Radiographic Examination - Radiographic examination of piping will be
performed in accordance with a qualified written procedure. The procedure will
comply with the referenced standard and will be furnished upon request to the
Company Engineering Coordinator prior to first flow through the meter station.
All radiographs will be made available to the Company on-site inspector or
Company Engineering Coordinator, as determined by Company, for
examination prior to first flow through the meter station.
A. Any X-ray not meeting the referenced standard will be retaken at the
Connecting Party’s expense.
B. Any weld that is repaired or replaced will be re-examined by radiograph in
accordance with the same procedure used to examine the weld initially. Any
repair costs will be the sole responsibility of the Connecting Party.
C. For each rejected weld radiograph, the weld or x-ray number will be written
at the end of each radiograph in white paint stick/pen for easy referencing
and review.
D. All films will be clearly identified by the weld ID number, job number and
number of belts so that the proper weld and any discontinuities in it can be
quickly and accurately located. When radiographing a repaired weld, use
the original weld number and add the letter “R” at the end of the number.
E. When radiographing a cutout weld, add the letter “N” to the original weld
number. If the weld requires replacement again, add “NN” to the original
number. If a replacement weld requires repair, add “NR”.
F. The Connecting Party will provide a cross-reference number sketch showing
assigned numbers to specific welds on the assembly to Company’s
Engineering Coordinator prior to first flow through the interconnect.
G. All nondestructive test personnel examining pipe will be qualified in
accordance with the requirements of SNT-TC-1A for the procedure/method
being used.
- 15 -
H. A copy of the x-ray report, including the qualification records of the
nondestructive test personnel, must be sent to the Company Engineering
Coordinator prior to first flow through the interconnect.
XVIII. CLEANING AND PAINTING
18.1 Sandblasting - All sandblasting will be performed in accordance with NACE /
SPC-6. All surfaces must be sandblasted to a “commercial” finish to remove
corrosion products and loose mill scale. Any residue including oil, grease, wax
and soil, will be washed off, and the surface will be allowed to thoroughly dry.
18.2 Painting - All painting will be performed in accordance with NACE / SPC-6.
The prime coat of paint will be applied to a thickness of two to three (2-3) mils
immediately after sandblasting per the paint manufacturer’s specifications. Two
(2) coats of finish paint will be applied to a thickness of two to four (2-4) mils
per coat and in accordance with the paint manufacturer’s specifications.
XIX. FACILITIES COMMISSIONING GENERAL OVERVIEW
19.1 The Commissioning Procedure for each facility requires a complete repetition of
the Factory Acceptance Testing as well as additional procedures to verify the
proper operation of every device installed within the facility. This includes, but
is not limited to, physically verifying that the equipment is installed on-site
according to the design drawings and identified with proper tagging; physical
damage inspection of all structures and equipment; calibration checks and re-
calibration, if necessary, of all instrumentation; startup of analyzers and systems
required for operating and monitoring the facility; testing of AC and DC power
systems; startup and testing of local and wide-area communications; and
operational verification of all manual and automated valves.
19.2 General Building Inspection and Testing
A. Visually inspect building for any physical damage
B. Verify that all building penetrations are weather tight
C. Connect AC Power to EGM building electrical panel
D. Energize all AC circuit breakers
E. Test all electrical outlets using a multi-meter
F. Verify all building lighting is in working order
G. Verify operation of air conditioning unit
- 16 -
H. Verify operation of heating unit
I. Verify that all required components are installed within building according
to Company specifications and drawings
J. Verify that door locks, and keys operate as required
19.3 EGM Building I/O - All I/O physically located in the EGM building(s) and
connected to the RTU will be tested in conjunction with the RTU. The data will
be manipulated and verified within the RTU. This requires that all power
supplies, backup devices and local building I/O is properly installed and
operational.
19.4 Piping Skid I/O - All I/O relating to the piping skids will be tested back to the
RTU. This will include stroking valves using nitrogen for power gas, setting
pilot regulators, confirming limit switch operation, testing transmitter operation,
setting communications network addresses, testing communications to multi-
variable transmitters and ultrasonic meters, and testing meter data valid and
frequency signals.
19.5 Gas Chromatograph - When applicable, a factory-trained technician will be on-
site to provide initial startup, commissioning and initial calibration of the gas
chromatograph. Prior to energizing the device, the carrier gas and calibration
gas cylinders will be installed and connected to the gas chromatograph. A
thorough inspection will be conducted which will include leak checks of all
fittings and tubing connected to the gas chromatograph, verification that the
proper electrical and communications connections have been made, and
verification that the controller is configured properly for communication to both
the gas chromatograph and the RTU. The trained technician will then follow
standard startup and commissioning procedures as applicable to the gas
chromatograph installed at the site. Prior approval will be required before any
configuration changes and/or adjustments are made to the configuration of the
gas chromatograph. Upon completion of the commissioning of the gas
chromatograph, a copy of the configuration as it exists within the gas
chromatograph and controller will be turned over to the commissioning team.
19.6 Moisture, Hydrogen Sulfide & Total Sulfur Analyzer - When applicable, a
factory trained technician will be on-site to provide initial startup,
commissioning and initial calibration of the moisture and/or H2S analyzer and/or
total sulfer analyzer. Prior to energizing the device(s), a thorough inspection
will be conducted which will include leak checks of all fittings and tubing
connected to the analyzers, verification that the proper I/O connections have
been made, and verification that the analyzers are configured properly for the
application. The trained technician will then follow standard startup and
commissioning procedures as applicable to the analyzers installed at the site.
- 17 -
Prior approval will be required before any configuration changes and/or
adjustments are made to the configuration of the analyzer(s).
19.7 Valve Position Controllers & Operators - When applicable, a factory-trained
technician will be on-site to provide initial startup and commissioning of the
valve position controllers and operators. Prior to energizing the valve position
controllers and operators, a thorough inspection will be conducted which will
include leak checks of all fittings and tubing connected to the valve position
controllers and operators, verification that the proper I/O connections have been
made, and verification that the valve position controllers and operators are
configured properly for the application. The trained technician will then follow
standard startup and commissioning procedures as applicable for the valve
position controllers and operators installed at the site. Prior approval from
Company’s Project Manager will be required before any configuration changes
and/or adjustments are made to the configuration of the valve position
controllers and operators.
19.8 Manually Operated Valves - There may be a variety of types and sizes of
manually operated valves in use at the facility. Proper operation of each of these
valves must be verified prior to placing the facility in service.
19.9 Quarter-Turn Ball Valves - Using the P&ID and valve tagging, verify that all
required quarter-turn ball valves are installed in the proper location and are
configured properly. Each valve should be manually manipulated to the fully
open and fully closed position and verification made that the locking device is
installed and functional on each valve.
19.10 Instrumentation Plug Valves - Using the P&ID and valve tagging, verify that all
required instrumentation plug valves are installed in the proper location and are
configured properly. Each valve should be manually manipulated to the fully
open and fully closed.
19.11 Pipeline Isolation Valves - Using the P&ID and valve tagging, verify that all
required pipeline isolation valves are installed in the proper location and are
configured properly. Each valve should be manually manipulated to the fully
open and fully closed position.
19.12 Grounding Test - The grounding system will comply with the ohms
requirements in section 13.4, paragraph E of this guideline.
19.13 Communication System Checklist
A. Antenna dish is installed on the antenna mast, if applicable
B. Outdoor unit electronics are installed
C. Indoor unit electronics are installed
- 18 -
D. Antenna is positioned to optimize the signal, if applicable
E. Verify communications between the facility and host facility
F. For sites that have alternate means of communications, primary
communications will be disconnected and communications verified with the
backup.
XX. MAINTENANCE AND SECURITY
20.1 Tap Assembly - Company will be responsible for the maintenance and security
of the tap valves and check valves installed within Company pipeline right-of-
way. The tap assembly will be fenced and all gates locked.
20.2 Meter Station - Connecting Party will be responsible for the maintenance and
security at the meter station. The meter station site will be fenced and all gates
locked.
- 19 -
ATTACHMENT A
Company and US DOT Documentation Requirements
I. Documentation – At least five (5) days prior to commencement of gas flow,
Connecting Party will furnish to Company Engineering Coordinator: All
documentation required by Company to ensure compliance with the U.S. DOT
regarding the installation of the meter station equipment and everything within forty
(40) feet of the meter station. Such documentation will include but not limited to the
following:
1.1 Orifice meter tube micrometer reports, filled out by or witnessed by a Company
representative, or ultrasonic meter tube calibration reports, witnessed by a
Company representative
1.2 Hydrostatic/pneumatic testing equipment certification documents; inspection
reports, including test logs; temperature and pressure recorder charts;
deadweight and recorder certifications (current within 6 months); and leaks/
failures noted and their disposition
1.3 Radiographic inspection reports for 100% of the welds made including the
number of girth welds made, the number rejected and the disposition of the
rejects, with a sketch identifying the weld locations; radiographer qualification
records; and radiographic examination procedure qualifications
1.4 Each welding procedure used and results of specific welder qualifying tests
1.5 All drawings, including bill of material, mill test reports for the pipe material,
and P&IDs
1.6 Purchase orders for all materials
1.7 Relief valve sizing and capacity calculation as applicable
1.8 Cathodic protection measures installed
FIRST FLOW WILL NOT OCCUR UNTIL COMPANY HAS RECEIVED,
REVIEWED AND APPROVED, IN WRITING, THE ABOVE DOCUMENTATION.
II. As-Built Drawing - Connecting Party, within sixty (60) days after completion of all of
its activities as herein contemplated, will furnish to Company Engineering Coordinator
as-built information along with daily construction logs and completion reports,
including three (3) sets of all "As-Built" drawings for the M&R.
- 20 -
ATTACHMENT B
Typical Interconnect and Meter Standard Drawings
The attached drawings are provided for reference.
C
8" 8"
OR APPROVED EQUAL
DETAIL 2
ORIFICE
FITTING
DETAIL 1
SP-5000
6"
�" SPACER
FEMALE FLANGE
MALE FLANGE
�" RAISED FACE
�" RECESS
FLOW
THIS DRAWING
THIS DRAWING
SEE DETAIL 18"8"
FLOW
7 5
3
1
1
224
4
6 6
J
11
12
2
8
11
12
2
CONSTANTS
2
3
4
6
8
10
12 114"
38"
57"
76"
95"
9
36"
36"
CLOSURE
UL1 UL2
L
DANIEL DUAL CHAMBER FITTING
1
CLOSURE
A B C
K
WN+RF
3.125"
4.250"
6.375"
6.250"
4.875"
16"
19"
27"
36"
54"
45"
K K6"
A B C
18"
UL1 UL2
FULL SIZE TEE
SIZE
(INCH)
5.250"
9.125"
8.625"
13
SAMPLE
PROBE
PIPE SIZE
2",3",4"
6"
10"
12"
8"
THREADOLET
WELD
THERMOWELL
DIM "U"
2.5"
FULL SIZE
TEE
THERMOWELLS
DIM."U"
J (DANIEL) J (TMCO)L
316"
34" T.O.L.
3.500"
5.500"
L ORIFICE PLATE
CORIFICE PLATE L TO FLG.
34" T.O.L.
DETAIL 2
SEE
CONFIRM ORIENTATION FOR
FABRICATION OR FIELD INSTALL
GAS SAMPLE
PROBE W/FULL
PORTED VALVE
PAINTED YELLOW
AND TAGGED
DETAIL 3
THIS DRAWING
DETAIL 3
SEE
9.5 X D 8.0 x D 4.5 X D
6.938"
6.563"
7.938"
8.813"
5.250"
8.000"
8.625"
6.938"
6.563"
7.938"
8.813"
2
3
3
FLOW
TEMPERATURE TEST
WELL W/ CAP AND
CHAIN
(TEMPERATURE TRANSMITTER CONNECTION
HEAD/RTD/THERMOWELL)
MINIMUM REQUIRED SPOOL LENGTHS
SELECTED AGA VALUESFOR FABRICATION
16"
24"
32"
48"
64"
80"
96"
52"
52"
55"
76"
94"
113"
132"
22"
31"
39"
57"
90"
105"
73"
44"
45"
47"
55"
63"
74"
82"
119.8125"
129.8125"
142.8125"
231.8125"
321.8125"
279.8125"
189.8125"
**
**
**
* * *
316"1
58"(SIZES 2"-8")
258"(SIZES 10"-12")
TEMPERATURE WELL
(CUSTODY TRANSFER)
TEMPERATURE WELL
(CHECK MEASUREMENT)
1" T.O.L.6
1.5"
2.0"
3.0"
4.0"
SP
50
00.
DG
N
DESIGN NOTES:
5. ALL METER TUBES SHALL BE HYDROSTATICALLY TESTED TO 2220 PSIG
(-0,+25 PSIG) FOR 8 CONTINUOUS HOURS.
*
DL
PLAN VIEW
DL
CONFIRM ORIENTATION
FOR FABRICATION OR
FIELD INSTALL
1. METER TUBE SHALL CONFORM TO ALL PROVISIONS OF API 14.3/AGA 3,
AND SHALL BE IN ACCORDANCE WITH THIS STANDARD DRAWING.
2. METER TUBE SHALL BE PURCHASED AS ASSEMBLY, COMPLETE WITH A
HONED TUBE UPSTREAM AND DOWNSTREAM AND A FLOW-CONDITIONING
PLATE UPSTREAM OF THE ORIFICE.
3. METER TUBE SHALL BE FURNISHED WITH CPA50E OR DANIEL PROFILER
FLOW CONDITIONER AS REQUIRED UPSTREAM OF THE ORIFICE.
4. UNLESS OTHERWISE SPECIFIED IN DESIGN INFORMATION SHEET, TWO (2)
PAIRS OF 12" N.P.T. DIFFERENTIAL PRESSURE TAPS SHALL BE
REQUIRED ON THE SENIOR ORIFICE FITTING. ONE (1) PAIR EACH AT THE
3 O’CLOCK AND THE 9 O’CLOCK POSITIONS.
6. INTERNAL PIPE ROUGHNESS OF SPOOLS AND METER TO BE HONED TO 250
MICRO-INCHES OR LESS. THE FLANGE I.D. SHALL BE THE SAME I.D. AS
THAT OF THE PIPE. SPOOL AND METER ID MUST BE WITHIN 1%.
MATERIAL SPECIFICATIONS
5 FLOW CONDITIONER: PLATE-TYPE, 304 S.S., ANSI 600
2 FLANGES: ANSI 600, WNRF, BTM PIPE ID, ANSI B16.5, ASTM A-105
DESCRIPTIONMK#
3 GASKETS: ANSI 600, 18" SPIRAL WOUND, FLEXITALIC & NON-INTRUSIVE INTO
THE FLOW PATH.
4 BOLTS: STUD, ASTM A193, GR. B-7, EACH W/2 HEX. NUTS, ONE WASHER, ASTM
A194, GR.2H. BOLTS SHALL BE IMF-3W (XYLAN) COATED.
8 ORIFICE FITTING:DANIEL DUAL-CHAMBER, ORIFICE FITTING-SENIOR C-STYLE
ANSI 600, WExFE, OR APPROVED EQUAL.
11 TEE: FULL SIZE, ANSI B16.9. MINIMUM GRADE SHALL BE SPECIFIED IN
DESIGN INFORMATION SHEET.
12 CLOSURE: HORIZONTAL, ANSI 600, BTM PIPE ID, YALE FIG. 500 W/HINGE
OR APPROVED EQUAL.
13 SPACER PLATE 12" INCH ASTM A-516-70, CARBON STEEL, SERRATE BOTH FACES
TO MATCH ANSI 600 FLANGE FACINGS. O.D. OF SPACER TO FIT INSIDE FLANGE
BOLTS. I.D. OF SPACER = I.D. OF PIPE.
7 SPACER PLATE: 1" FOR SIZES 2"-8", 2" FOR SIZES 10" AND 12". ASTM A-516-70,
CARBON STEEL, SERRATE BOTH FACES TO MATCH ANSI 600 FLANGE FACINGS. O.D.
OF SPACER TO FIT INSIDE FLANGE BOLTS. I.D. OF SPACER = I.D. OF PIPE.
SPACER PLATE SHALL BE 118" if 2" CPA 50E FLOW CONDITIONER IS USED.
1 PIPE: UNLESS OTHERWISE SPECIFIED IN DESIGN INFORMATION SHEET, USE API-5L
OR ASTM A-106 GR.B. MINIMUM GRADE SHALL BE SPECIFIED IN DESIGN
INFORMATION SHEET.
9 ORIFICE PLATES: 304 S.S., PER API 14.3/AGA 3. PLATE SIZES FROM 0.2 TO 0.6
BETA IN 14" INCREMENTS FOR 2" THROUGH 6" RUNS AND
12" INCREMENTS FOR 8"
THROUGH 12" RUNS.
10 ORIFICE PLATE SEAL: 2" THROUGH 8", REMOVABLE DUAL SEAL; 10" & 12", DUAL
VULCANIZED SEAL.
14
15
16
17 GASKET: ANSI 600, 18" SPIRAL WOUND, NON-INTRUSIVE INTO FLOW PATH.
17
34" T.O.L.
6 14 15 16
6 THREDOLETS: 3000#, ASTM A-105.
18
18
PIPE NIPPLE 34", EH, GR. B, 3" LONG, TBE (SHIP LOOSE).
VALVE 34", BALL, 3000#, THREADED, BOLTED OR WELDED BODY (SHIP LOOSE).
PIPE PLUG 34", 3000#, FS, HEX HEAD, THREADED (SHIP LOOSE).
ID IS GREATER THAN NOMINAL DIA. FOR 6" NOM. STD W.T. PIPING
THEREFORE 1" HAS BEEN ADDED TO CALCULATED SPOOL LENGTH.
FLANGE: ANSI 600, WN FEMALE FACED, BTM PIPE ID, ANSI B16.5, ASTM A-105
ORIFICE METER TUBE
ASSEMBLY - ANSI 600
04-07-10AKL
IG.#
REV.DWG.
STANDARDS
INITIALS DATE
E:\
XM\
Workspace\standards\
Approved
Stds\
SP5000.d
gn
4/9/2010
Dra
wing:
Model:
Default
Ti
me:
twar
was
Userna
me:
DESIGN MANAGER
PRESSURE REGULATING SKID LIMITS
PSIGD
E
SET@150
PSIG
P
SET@125
P
SET@120
PSIG
PSIGA
B
SET@150
PSIG
P
SET@125
P
SET@120
PSIG
S1
INSTRUMENT GAS (S1)
INSTRUMENT GAS (S2)
HEATER
S2
HEATER
C
F
PI
0-1500 PSIG
1"
PI
0-1500 PSIG
1" 1"
V
1"
PI
0-1500 PSIG
34"
34"
34"
34"
PI
0-1500 PSIG
1"
PI
0-1500 PSIG
1" 1"
V
PI
0-1500 PSIG
34"
34"
34"
34"
RUN #1
PM
122BOPP
FCV
122B
PM
122AOPP
FCV
122A
DI
ZSC
122B
DI
ZSO
122B
AO
122B
AI
122B
DI
ZSC
122A
DI
ZSO
122A
AO
AI
1"
PIT
122
0-1500 PSIG
AI
PT
122
INSULATING
FLANGE
INSULATING
FLANGE
VENTVENTVENTVENT
VENTVENT VENTV
UH
34"
V
UH
34"
34"
34"
FR
OM
ME
TE
R
SKI
DS
ZT
122A
FY
122A
ZT FY
S1 S2
B
CE
F
INSULATING
FLANGE
INSULATING
FLANGE
FC
W/PO
W/PO
FC
2D PUP
2D PUP
SSD/PCR
SSD/PCR
SSD/PCR
SSD/PCR
FIL
TE
R
DR
YE
R
DR
YE
R
FIL
TE
R
FIL
TE
R
DR
YE
R
DR
YE
R
FIL
TE
R
PIPING & INSTRUMENTATION DIAGRAM
FOR REGULATOR RUNS
RUN #2
SWI
TC
HI
NG
SKI
D
TO
VA
LV
E
COMPANY/CUSTOMER
DEMARCATION
POINT*
OR
CU
ST
OM
ER
*ONLY IF STATION DOES NOT INCLUDE VALVE SWITCHING SKID.
V
V
IG.# REV.DWG.
INITIALS DATE
$$$$$$$$$$$$$$$$$$$$$$$$$$$
DG
NS
PE
C$$$$$$$$$$$$$$$$
$$$$$
SY
TI
ME$$$$$$
Dra
wing:
Model:
$M
OD
EL
NA
ME$
Ti
me:
$$$$$
US
ER
NA
ME$$$$
Userna
me:
DESIGN MANAGER
5400 Westheimer Ct. Houston, TX 77056-5310 713 / 627-5400
TYPICAL
VENT
VENT
VENT
TO REGULATOR RUNS
FROM FILTER/
SEPARATOR
RUN #3
2D PUP
2D PUP
SSD/PCR
SSD/PCR
SSD/PCRSSD/PCR
SSD/PCR
SSD/PCR
PSIGH
SET@150
PSIG
P
SET@125
P
SET@120
PSIG
S4
INSTRUMENT GAS (S4)
TW
MB
UT
MB
UT
120B
TE
FR
120B
120B 120B
A+ GENIE
PROBE
AW
12"SET @ XX PSIG
(0-60 PSIG)
1"
120B
UT
120C
MB
UT
120C
TE
120C
TW
A+ GENIE
PROBE
AW
12"
120C
1"
SET @ XX PSIG(0-60 PSIG)
E
T
ET
SPACER PLATE
SPACER PLATE
TW
TW
TW
TW
H
H
H 34"
V
UH
S4
UNCORRECTED
FLOW PULSE
DATA VALID
ALARM
DI
PI
FA
FT
120B
120B
A+ GENIE
PROBE
PD
3"
TW
TW
AW
12"
FT
120A
FE
120A
5-VALVE
UT
120A
SET @ XX PSIG(0-60 PSIG)1"
120A
14"
TW
TE
120A
PI
FT
120A
MB
UT
120B
S
STRAINER
PDS
120
PDI
120
5-VALVE
ST
120
DI
XY
120A
RS485 ULTRASONIC
METER FEED
MB
FR
120C
UNCORRECTED
FLOW PULSE
DATA VALID
ALARM
DI
PI
FA
FT
120C
120C
RS485 ULTRASONIC
METER FEED
FIL
TE
R
DR
YE
R
DR
YE
R
FIL
TE
R
FLOW
CONDITIONER
FLOW
CONDITIONER
RSV
120A
RSV
120C
RSV
120B
V
310
V
311
V
312
SPACER PLATE
INSPECTION
PORT
INSULATING
FLANGE
INSULATING
FLANGE
INSULATING
FLANGE
SPACER PLATE
INSPECTION
PORT
INSPECTION
PORT
INSPECTION
PORT
RUN #2
RUN #1
INSULATINGFLANGE
INSULATINGFLANGE
INSULATINGFLANGE
PIPING & INSTRUMENTATION DIAGRAM
FOR METER RUNS
1D PUP
(6" MINIMUM)
1D PUP
(6" MINIMUM)
HE
AT
TR
AC
ED
HE
AT
TR
AC
ED
V
301
2"
1"
2"
SI
PH
ON/
DR
AI
N
AS
SY
RESTRICTING ORIFICE PLATE /
FLOW LIMITING NOZZLE
DI
ZSO
120A
DI
ZSC
120A
DO
120A
DO
120A
EYOEYC
DI
ZSO
DI
ZSC
DO
DO
120B 120B 120B 120B
EYOEYC
DI
ZSO
DI
ZSC
DO
DO
120C 120C 120C 120C
EYOEYC
12"
12"
ETH
ET
120B
ETHERNET ULTRASONIC
METER FEED (TECH)
ETH
ET
120C
ETHERNET ULTRASONIC
METER FEED (TECH)
BYPASS
INDICATOR
E
T
HE
AT
TR
AC
ED
IG.# REV.DWG.
INITIALS DATE
$$$$$$$$$$$$$$$$$$$$$$$$$$$
DG
NS
PE
C$$$$$$$$$$$$$$$$
$$$$$
SY
TI
ME$$$$$$
Dra
wing:
Model:
$M
OD
EL
NA
ME$
Ti
me:
$$$$$
US
ER
NA
ME$$$$
Userna
me:
DESIGN MANAGER
5400 Westheimer Ct. Houston, TX 77056-5310 713 / 627-5400
TYPICAL
PSIGH
SET@150
PSIG
P
SET@125
P
SET@120
PSIG
S4
INSTRUMENT GAS (S4)
FIL
TE
R
DR
YE
R
DR
YE
R
FIL
TE
RDI
ZSO
DI
ZSC
DO
DO
VENT
DI
ZSO
DI
ZSC
DO
DO
VENT
120A 120A 120A 120A
120B 120B 120B 120B
FROM FILTER/
SEPARATOR
EYOEYC
EYOEYC
SSD/PCR
SSD/PCRSSD/PCR
SSD/PCR
TW
UT
MB
UT
120A
TE
120A 120A
A+ GENIE
PROBE
AW
12"SET @ XX PSIG
(0-60 PSIG)
1"
120A
E
T
SPACER PLATE
TW
TW
H
H
FLOW
CONDITIONER
ORIFICE METER
FE-120A
TW
UT
MB
UT
120B
TE
120B 120B
A+ GENIE
PROBE
AW
12"SET @ XX PSIG
(0-60 PSIG)
1"
120B
E
T
TW
TW
FLOW
CONDITIONER
ORIFICE METER
FE-120B
SPACER PLATE
34"
V
UH
S4TO REGULATOR RUNS
RSV
120A
RSV
120B
SPACER PLATE
SPACER PLATE
V
310
V
311
INSULATINGFLANGE
INSULATINGFLANGE
INSULATING
FLANGE
INSULATING
FLANGE
INSPECTION
PORT
INSPECTION
PORT
INSPECTION
PORT
INSPECTION
PORT
RUN #1
RUN #2
PIPING & INSTRUMENTATION DIAGRAM
FOR ORIFICE METER RUNS
IG.# REV.DWG.
INITIALS DATE
$$$$$$$$$$$$$$$$$$$$$$$$$$$
DG
NS
PE
C$$$$$$$$$$$$$$$$
$$$$$
SY
TI
ME$$$$$$
Dra
wing:
Model:
$M
OD
EL
NA
ME$
Ti
me:
$$$$$
US
ER
NA
ME$$$$
Userna
me:
DESIGN MANAGER
5400 Westheimer Ct. Houston, TX 77056-5310 713 / 627-5400
TYPICAL
V
205
V
202
2" 1"
2" 2"
V
201
INSPECTION
TAP
2"
12"
2"
2"
V
206
V
204
INSULATING
FLANGE
24"
12"
DIELECTRIC
FTG
2"x1"
12"
2"x 12
"
N5C
N3B
N2
N5D
N7BN7A
F/S
302
N4C
N4D
N14
N11B
2"x1"
N13A
LG
N5A
N3AN5B N11A
2"x1"
LCV
001A
N12
LCV
002A
2"x1"
2"x1"
INSULATING
FLANGE
DIELECTRIC
FTGV
304
N13BLG
RESTRICTING
ORIFICE
INSULATING
FLANGE
N1N8N10
SET @
1,248 PSIG
RV
N6D
N6C
N6B
N6A
12"
2"x1"
N4A
N4B
LC
001A
2"
12"
LC
001B
S
F
DO
FISHER-ROSEMOUNT
TYPE 1367
HP INSTRUMENT SUPPLY SYSTEM
SET @ 30 PSIG
N2
N7BN7A
F/S
301
N14
N12
S
INSULATING
FLANGE
DIELECTRIC
FTG
V
303
N1N8N10
SET @
1,248 PSIG
RV
12"
2"x1"
F
2"
12"
N5C
N3B N5D
N4C
N4DN11B
2"x1"
N13ALG
N5A
N3AN5B N11A
2"x1"
LCV
001A
LCV
002A
2"x1"
2"x1"
N13BLG
RESTRICTING
ORIFICE
INSULATING
FLANGE
N6D
N6C
N6B
N6A N4A
N4B
LC
001A
LC
001B
FISHER-ROSEMOUNT
TYPE 1367
HP INSTRUMENT SUPPLY SYSTEM
SET @ 30 PSIG
INSULATING
FLANGE
12"
DIELECTRIC
FTG
2"x1"
V
203
TO CONDENSTATE TANK
AI
PDT
302
PDT
302
LSH302A
DI
302A
LSH
LSH
302A
DI
302B
LSH
DO
AI
PDT
301
PDT
301
LSH301A
DI
301A
LSH
LSH301B
DI
301B
LSH
EV0
302
EV0
301
SIPHON/
DRAIN ASSY
FROM SWITCHING SKID TO METER RUNS
SSD/PCR
SSD/PCR
SSD/PCR
SSD/PCR
PIPING & INSTRUMENTATION DIAGRAM
FOR FILTER SEPARATORS
IG.# REV.DWG.
INITIALS DATE
$$$$$$$$$$$$$$$$$$$$$$$$$$$
DG
NS
PE
C$$$$$$$$$$$$$$$$
$$$$$
SY
TI
ME$$$$$$
Dra
wing:
Model:
$M
OD
EL
NA
ME$
Ti
me:
$$$$$
US
ER
NA
ME$$$$
Userna
me:
DESIGN MANAGER
5400 Westheimer Ct. Houston, TX 77056-5310 713 / 627-5400
TYPICAL
- 24 -
ATTACHMENT C
Approved Manufacturers
The attached listing is provided for reference.
Thursday, July 28, 2011
1:57:40 PMSpectra Commodities Lis
Table of ContentsACTUATORS........................................................... 2
BUILDINGS............................................................. 3
CATALYTIC CONVERTS........................................... 5
CHROMATOGRAPHS............................................. 6
CLOSURES.............................................................. 7
COATING APPLICATORS........................................ 8
COMPRESSORS...................................................... 12
CRANES.................................................................. 14
ENGINE GENERATOR SETS.................................... 15
FABRICATIONS....................................................... 16
FITTINGS................................................................ 21
FLANGES................................................................ 26
GASKETS................................................................ 28
GRAVITOMETERS.................................................. 29
HEAT EXCHANGERS............................................... 30
HEATERS................................................................ 31
INDUCTIONBEND.................................................. 32
INSTRUMENTATION.............................................. 33
INSULATING KITS................................................... 34
MAGNETIC PIG SIGS.............................................. 35
METERING............................................................. 36
MOTOR CONTROL CENTERS................................. 38
MOTORS................................................................ 39
PIPE........................................................................ 40
RTU........................................................................ 43
SWITCHGEAR......................................................... 44
TANKS.................................................................... 45
TRANSFORMERS.................................................... 46
TRANSFORMET...................................................... 47
TRANSMITTERS..................................................... 48
VALVES.................................................................. 49
VARIABLE SPEED DRIVES....................................... 57
VESSELS................................................................. 58
ACTUATORS........................................................... 3
BUILDINGS............................................................. 4
CATALYTIC CONVERTS........................................... 5
CHROMATOGRAPHS............................................. 6
CLOSURES.............................................................. 7
COATING APPLICATORS........................................ 8
COMPRESSORS...................................................... 12
CRANES.................................................................. 14
ENGINE GENERATOR SETS.................................... 15
FABRICATIONS....................................................... 16
FITTINGS................................................................ 21
FLANGES................................................................ 26
GASKETS................................................................ 28
GRAVITOMETERS.................................................. 29
HEAT EXCHANGERS............................................... 30
HEATERS................................................................ 31
INDUCTIONBEND.................................................. 32
INSTRUMENTATION.............................................. 33
INSULATING KITS................................................... 34
MAGNETIC PIG SIGS.............................................. 35
METERING............................................................. 36
MOTOR CONTROL CENTERS................................. 38
MOTORS................................................................ 39
PIPE........................................................................ 40
RTU........................................................................ 43
SWITCHGEAR......................................................... 44
TANKS.................................................................... 45
TRANSFORMERS.................................................... 46
TRANSFORMET...................................................... 47
TRANSMITTERS..................................................... 48
VALVES.................................................................. 49
VARIABLE SPEED DRIVES....................................... 57
VESSELS................................................................. 58
Thursday, July 28, 2011
1:57:43 PMSpectra Commodities Lis
ACTUATORSDirect Gas Actuators
Ph (419) 529‐4311 (419) 529‐3688
Mansfield OH 44906
Limitations: ‐
Shafer Valve Operating Systems Fx:
DS:108‐2
Ph (847) 437‐5940 (847) 437‐2549
Elk Grove Village IL 60007
Limitations: ‐
Dresser Flow Solutions ‐ Becker Operations Fx:
DS:011‐1
Ph 713‐983‐8880 713‐983‐8788
Houston TX 77041
Limitations: ‐
Gevalco, Inc. Fx:
DS:285‐1
Ph (281) 499‐1561 (281) 499‐8445
Missouri City TX 77489
Limitations: ‐
EIM Controls Fx:
DS:019‐1
Ph (281) 727‐5300 (281) 727‐5353
18703 G H Circle, Waller TX
Limitations: ‐
Bettis Corporation Fx:
DS:018‐1
Electric Motor Drive Actuators
Ph (434) 528‐4400 (434) 845‐9736
5114 Woodall Rd., Lynchburg VA 24502
Limitations: ‐
Limitorque Corporation Fx:
DS:058‐1
Ph (281) 499‐1561 (281) 499‐8445
Missouri City TX 77489
Limitations: ‐
EIM Controls Fx:
DS:019‐1
Gas Hydraulic Actuators
Ph (419) 529‐4311 (419) 529‐3688
Mansfield OH 44906
Limitations: ‐
Shafer Valve Operating Systems Fx:
DS:108‐1
Page 3 of 61
Thursday, July 28, 2011
1:57:43 PMSpectra Commodities Lis
BUILDINGSAuxillary Buildings
Ph 281‐219‐1877 832‐553‐7906
14350 Chrisman, Houston Tx 77039
Limitations: ‐
Volta LLC Fx:
DS:290‐1
Ph (281) 496‐1300 (281) 496‐1314
Houston TX 77079
Limitations: ‐
United Steel Structures Fx:
DS:076‐2
Compressor Buildings
Ph (281) 531‐2800 (281) 531‐2888
Houston TX 77082
Limitations: ‐
Standard Industrial Structures Corporation Fx:
DS:075‐1
Ph (281) 496‐1300 (281) 496‐1314
Houston TX 77079
Limitations: ‐
United Steel Structures Fx:
DS:076‐1
Fabricated Buildings
James Stone Ph 713‐723‐9950
PO Box 35636, Houston TX 77235
Limitations: ‐
Parkline Texas, Inc. Fx:
DS:298.0001
Prefabricated Buildings
Ph (281) 445‐2600 (281) 445‐0598
Houston TX 77037
Limitations: ‐
Cleveland Manufacturing, Inc. Fx:
DS:172‐1
Ph (409) 935‐5743 (409) 938‐4189
Texas City TX 77568
Limitations: ‐
Bebco Industries, Inc. Fx:
DS:171‐1
James Stone Ph 713‐723‐9950
PO Box 35636, Houston TX 77235
Limitations: ‐
Parkline Texas, Inc. Fx:
DS:298.0001
Ph (603) 216‐0607 (603) 4378668
15 Independence Dr., Londonderry NH 03053
Limitations: Precast Concrete
Concrete System, Inc. / Shelter Technologies Fx:
DS:279‐1
Ph (281) 444‐6022 (281) 444‐1290
Houston TX 77066
Limitations: ‐
Tesla Power and Automation, Inc. Fx:
DS:191‐1
Ph (281) 590‐8185 (281) 590‐5947
Houston TX 77039
Limitations: ‐
Russell Manufacturing and Fabricating, Inc. Fx:
DS:187‐1
Page 4 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
CATALYTIC CONVERTSCatalytic Converter
Ph (281) 255‐6955 (281) 351‐8502
Cypress TX 77429
Limitations: Not Approved by TETCO
McGuffy Industries Fx:
DS:093‐1
Page 5 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
CHROMATOGRAPHSGas Chromatographs
Ph (281) 491‐5252 (281) 491‐8440
Stafford TX 77477
Limitations: ‐
Instromet, Inc. Fx:
DS:249‐1
Ph (918) 338‐4888 (918) 338‐4605
Bartlesville OK 74006
Limitations: ‐
ABB, Inc. ‐ Totalflow Products Fx:
DS:266‐1
Ph 631‐345‐3434 631‐924‐7337
Yaphank NY 11980
Limitations: ‐
COSA Instrument Corp. Fx:
DS:276‐1
Ph (713) 467‐6000 (713) 827‐3880
111000 Brittmore Park, Houston TX 77041
Limitations: 2"" and larger"
Daniel Measurement & Control, Division of Emerson Fx:
DS:045‐1
Ph (713) 849‐1600 (713) 849‐1645
Houston TX 77040
Limitations: ‐
Cutler Hammer Div., Eaton Corp. Fx:
DS:173‐1
Page 6 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
CLOSURESClosures
Ph 281‐807‐2818 281‐894‐1332
Houston TX 77065
Limitations: ‐
GD Closure Systems Fx:
DS:221‐1
Ph (936) 539‐9222 (936) 539‐1450
1011 Beach Airport Rd., Conroe TX 77305
Limitations: ‐
Modco Industries, Inc. Fx:
DS:039‐1
Ph (940) 325‐2575 (940) 325‐4622
118 Washington Ave., Mineral Wells TX 76068
Limitations: ‐
PECO ‐ Perry Corp. Fx:
DS:099‐1
Ph (281) 351‐2222 (281) 351‐6557
Tomball TX 77375‐8934
Limitations: ‐
R&M Energy Systems Fx:
DS:141‐1
Ph (918) 447‐5100 (918) 446‐6327
Tulsa OK 74131
Limitations: ‐
TD Williamson, Inc. Fx:
DS:265‐1
Page 7 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
COATING APPLICATORSAbrasion Coating Applicators
Ph (219) 322‐4564 (219) 322‐2761
925 Kennedy Ave., Schereville IN 46375
Limitations: ‐
Midwest Pipe Coating, Inc. Fx:
DS:065‐1
Bill Browman Ph 281‐204‐6020
Bay St. Louis Mississippi
Limitations: ‐
PSL North America, LLC Fx:
DS:299.0001
Nick Ehnot Ph 281‐457‐0200 281‐457‐5568
711 Shields St., Channelview TX 77520
Limitations: 6" thru 48" / 1.250"w
LaBarge Coating, LLC (Site 2) Fx:
DS:242‐2
Brian Roper Ph 713‐465‐1600
900 Paper Mill Rd., Mobile AL 36610
Limitations: ‐
Berg Spiral Pipe Corp Fx:
DS:300.000‐1
Ph (281) 425‐8321 (281) 485‐5638
4501 Knapp RD, Pearland TX 77581
Limitations: ‐
ShawCor Pipe Protection LLC Fx:
DS:021.002‐2
Diane Burger Ph 281‐752‐7300
Thisvi Greece
Limitations: ‐
Corinth Pipe Works Fx:
DS:254.000‐1
Nick Ehnot Ph (281) 445‐6191 (281) 445‐8681
400 S. Sheldon Road, Channelview TX 77530
Limitations: 2 3/8" thru 42" / .625"w
LaBarge Coating, LLC (Site 1) Fx:
DS:242‐1
Ph (306) 543‐2552 (306) 543‐6168
2501 Pasqua Street North, Regina Saskatchewan, CAN SPS3C2 (Canada)
Limitations: ‐
ShawCor Pipe Protection LLC Fx:
DS:230‐1
Ph (713) 676‐0085 (713) 676‐0085
Houston TX 77013
Limitations: Approved for applying Powercrete abrasion coating.
Power Lone Star Fx:
DS:217‐1
Ph (281) 590‐8491 (281) 590‐9528
Houston TX 77032
Limitations: ‐
Clock Spring Company, LP. Fx:
DS:248‐2
Concrete Coating Applicators
Ph (281) 886‐2350 (281) 886‐2351
Houston TX 77032
Limitations: 4 1/2"" to 42"""
ShawCor Pipe Protection LLC Fx:
DS:034‐1
Ph (337) 369‐3761 (337) 365‐9747
New Iberia LA 70560
Limitations: 12" to 48"
Bayou Pipe Coaters Fx:
DS:197.001‐1
Fusion Bond Epoxy Coating Applicators
Page 8 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
Fusion Bond Epoxy Coating Applicators
Jason Norris Ph (724) 327‐0280 (724) 327‐0113
2658 Puckety Drive, Export PA 15632
Limitations: ‐
Dura‐Bond Coating, Inc. Fx:
DS:144‐1
Jason Norris Ph (717) 986‐1100 (717) 986‐1104
Steelton PA 17113
Limitations: ‐
Dura‐Bond Coating, Inc. Fx:
DS:144‐2
Jason Norris Ph 724‐327‐0782 724‐387‐2720
3200 Youghiogheny River Road, McKeesport PA 15134
Limitations: ‐
Dura‐Bond Coating, Inc. Fx:
DS:144‐3
Ph (903) 656‐2581 (903) 639‐2421
Lone Star TX 75668
Limitations: Pre‐Award/Prepro
A & A Coating, Inc. Fx:
DS:145‐1
Gary Foerster Ph (205) 252‐3490 (205) 252‐4185
3135‐B Daniel Payne Dr., Birmingham AL 35214
Limitations: 6 5/8"" to 36"""
L. B. Foster Company Fx:
DS:194‐1
Ph (713) 465‐1600 713‐827‐7423
Panama City FL 32412
Limitations: ‐
EB Coaters ‐ Panama City, FL Fx:
DS:066‐1
Ph (225) 775‐3018 (225) 775‐6277
Baton Rouge LA 70807
Limitations: 10 3/4 "" to 36"""
Bayou Pipe Coaters Fx:
DS:197‐1
Ph (337) 369‐3761 (337) 365‐9747
New Iberia LA 70560
Limitations: 10" to 48"
Bayou Pipe Coaters Fx:
DS:197‐2
Nick Ehnot Ph (281) 445‐6191 (281) 445‐8681
400 S. Sheldon Road, Channelview TX 77530
Limitations: 2 3/8" ‐ 42" / .625" W
LaBarge Coating, LLC (Site 1) Fx:
DS:242‐1
Ph (909) 357‐9002 (909) 357‐9021
14000 San Bernardina Ave., SW Gate 6, Fontana CA 92335
Limitations: ‐
ShawCor Pipe Protection LLC Fx:
DS:021.001‐1
Ph (281) 425‐8321 (281) 485‐5638
4501 Knapp RD, Pearland TX 77581
Limitations: ‐
ShawCor Pipe Protection LLC Fx:
DS:021.002‐2
Ph (801) 229‐2077 (801) 229‐2173
1750 N. Pioneer Lane, Vineyard UT 84058
Limitations: ‐
ShawCor Pipe Protection LLC Fx:
DS:226‐1
Ph (281) 886‐2350 (281) 886‐2351
Houston TX 77032
Limitations: 3/4"" to 4"", 3"" to 36"", 4"" to 30"", 6"" to 42
ShawCor Pipe Protection LLC Fx:
DS:034‐1
Page 9 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
Fusion Bond Epoxy Coating Applicators
Ph (417) 865‐2844 (417) 865‐2467
522 Fremont, Springfield MO 65802
Limitations: ‐
AFI International Fx:
DS:003‐1
Ph (306) 543‐2552 (306) 543‐6168
2501 Pasqua Street North, Regina Saskatchewan, CAN SPS3C2 (Canada)
Limitations: ‐
ShawCor Pipe Protection LLC Fx:
DS:230‐1
Ph (219) 322‐4564 (219) 322‐2761
925 Kennedy Ave., Schereville IN 46375
Limitations: 3/4"" to 48"" ‐ Schereville, IN"
Midwest Pipe Coating, Inc. Fx:
DS:065‐1
Bill Browman Ph 281‐204‐6020
Bay St. Louis Mississippi
Limitations: ‐
PSL North America, LLC Fx:
DS:299.0001
Kevin Trow Ph 713‐585‐3027
Hickman AR 72310
Limitations: ‐
Tenaris/Hickman Fx:
DS:251‐3
Brian Roper Ph 713‐465‐1600
900 Paper Mill Rd., Mobile AL 36610
Limitations: ‐
Berg Spiral Pipe Corp Fx:
DS:300.000‐1
Diane Burger Ph 281‐752‐7300
Thisvi Greece
Limitations: Up to 48"
Corinth Pipe Works Fx:
DS:254.000‐1
Nick Ehnot Ph 281‐457‐0200 281‐457‐5568
711 Shields St., Channelview TX 77520
Limitations: 6" thru 48" / 1.250"w
LaBarge Coating, LLC (Site 2) Fx:
DS:242‐2
Internal Coating Applicators
Ph (225) 775‐3018 (225) 775‐6277
Baton Rouge LA 70807
Limitations: ‐
Bayou Pipe Coaters Fx:
DS:197‐1
Nick Ehnot Ph 281‐457‐0200 281‐457‐5568
711 Shields St., Channelview TX 77520
Limitations: ‐
LaBarge Coating, LLC (Site 2) Fx:
DS:242‐2
Ph (713) 465‐1600 713‐827‐7423
Panama City FL 32412
Limitations: ‐
EB Coaters ‐ Panama City, FL Fx:
DS:066‐1
Diane Burger Ph 281‐752‐7300
Thisvi Greece
Limitations: ‐
Corinth Pipe Works Fx:
DS:254.000‐1
Ph (306) 543‐2552 (306) 543‐6168
2501 Pasqua Street North, Regina Saskatchewan, CAN SPS3C2 (Canada)
Limitations: ‐
ShawCor Pipe Protection LLC Fx:
DS:230‐1
Page 10 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
Internal Coating Applicators
Jason Norris Ph (717) 986‐1100 (717) 986‐1104
Steelton PA 17113
Limitations: ‐
Dura‐Bond Coating, Inc. Fx:
DS:144‐2
Brian Roper Ph 713‐465‐1600
900 Paper Mill Rd., Mobile AL 36610
Limitations: ‐
Berg Spiral Pipe Corp Fx:
DS:300.000‐1
Ph (281) 886‐2350 (281) 886‐2351
Houston TX 77032
Limitations: ‐
ShawCor Pipe Protection LLC Fx:
DS:034‐1
Somastic Coating Applicators
Ph (281) 886‐2350 (281) 886‐2351
Houston TX 77032
Limitations: ‐
ShawCor Pipe Protection LLC Fx:
DS:034‐1
Page 11 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
COMPRESSORSElectric Motor Driver Compressors
Ph (713) 672‐3500 (713) 672‐3644
Houston TX 77029‐1398
Limitations: ‐
G.E. Oil & Gas Company Fx:
DS:043‐1
Briz Garcia Ph 713‐895‐4286 713‐895‐4270
2200 Pacific Highway, San Diego CA
Limitations: ‐
Solar Turbines, Inc. Fx:
DS:115‐1
Gas Turbine Driver Compressors
Briz Garcia Ph 713‐895‐4286 713‐895‐4270
2200 Pacific Highway, San Diego CA
Limitations: ‐
Solar Turbines, Inc. Fx:
DS:115‐1
Ph (713) 672‐3500 (713) 672‐3644
Houston TX 77029‐1398
Limitations: ‐
G.E. Oil & Gas Company Fx:
DS:043‐1
High Speed Unit Packager Compressors/Recip
Ph (713) 467‐2221 (713) 935‐3490
1200 W. Sam Houston Parkway North, Houston TX 77043
Limitations: ‐
Dresser Rand Company Fx:
DS:028‐1
Ph (979) 732‐2327 (979) 732‐0056
Alleyton TX 78935
Limitations: ‐
Exterran (Hanover Smith) Fx:
DS:208‐1
Centrifugal Assembly Natural Gas Compressors
Briz Garcia Ph 713‐895‐4286 713‐895‐4270
2200 Pacific Highway, San Diego CA
Limitations: ‐
Solar Turbines, Inc. Fx:
DS:115‐1
Ph (713) 672‐3500 (713) 672‐3644
Houston TX 77029‐1398
Limitations: ‐
G.E. Oil & Gas Company Fx:
DS:043‐1
Ph (609) 890‐5000 (609) 895‐9180
Trenton NJ 08650
Limitations: ‐
Siemens Demag Delaval Turbomachinery Corp. Fx:
DS:054‐1
Ph (713) 467‐2221 (713) 935‐3490
1200 W. Sam Houston Parkway North, Houston TX 77043
Limitations: ‐
Dresser Rand Company Fx:
DS:028‐1
Ph (713) 354‐1900 (713) 354‐1923
Houston TX 77092
Limitations: ‐
Cameron Compression Fx:
DS:023‐1
Low Speed Integral Compressor Natural Gas/Recip
Page 12 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
Low Speed Integral Compressor Natural Gas/Recip
Ph (713) 467‐2221 (713) 935‐3490
1200 W. Sam Houston Parkway North, Houston TX 77043
Limitations: ‐
Dresser Rand Company Fx:
DS:028‐1
Ph (713) 354‐1900 (713) 354‐1923
Houston TX 77092
Limitations: ‐
Cameron Compression Fx:
DS:023‐1
Reconditioned Recip Integral Natural Gas Comp
Ph (713) 467‐2221 (713) 935‐3490
1200 W. Sam Houston Parkway North, Houston TX 77043
Limitations: ‐
Dresser Rand Company Fx:
DS:028‐1
Ph (713) 354‐1900 (713) 354‐1923
Houston TX 77092
Limitations: ‐
Cameron Compression Fx:
DS:023‐1
Ph (281) 579‐7850 (281) 579‐4545
Houston TX 77084
Limitations: ‐
Baker/MO Services, Inc. (Baker Energy Services) Fx:
DS:007‐1
Recip Valve Pocket Natural Gas Compressors
Ph (713) 354‐1900 (713) 354‐1923
Houston TX 77092
Limitations: ‐
Cameron Compression Fx:
DS:023‐1
Ph (918) 583‐5711 (918) 388‐3202
Tulsa OK 74110
Limitations: ‐
Arrow Engine (Dressor Rand) Fx:
DS:008‐1
Ph (713) 467‐2221 (713) 935‐3490
1200 W. Sam Houston Parkway North, Houston TX 77043
Limitations: ‐
Dresser Rand Company Fx:
DS:028‐1
Ph (713) 664‐7333 (713) 663‐1858
Houston TX 77081
Limitations: ‐
Compressor Engineering Corp. ‐ CECO Fx:
DS:111‐1
Page 13 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
CRANESBridge Cranes
Ph (918) 836‐6827 (918) 835‐1008
Claremore OK 74019
Limitations: ‐
Gaffey, Inc. of Tulsa Fx:
DS:163‐1
Jib Cranes
Ph (918) 836‐6827 (918) 835‐1008
Claremore OK 74019
Limitations: ‐
Gaffey, Inc. of Tulsa Fx:
DS:163‐1
Page 14 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
ENGINE GENERATOR SETSEngine Generator Sets
Ph (713) 723‐1050 (713) 551‐0799
Houston TX 77035
Limitations: ‐
Waukesha Pearce Industries Fx:
DS:192‐1
Ph (504) 367‐2401 (504) 367‐4044
2550 Belle Chasse Highway, Gretna LA 70054
Limitations: ‐
Reagan Equipment Company, Inc. Fx:
DS:203‐1
Ph (281) 452‐3610 (281) 452‐7550
Houston TX 77015
Limitations: ‐
S & S Energy, a Division of GE, Gas Turbine Produ Fx:
DS:118‐1
Ph (713) 460‐2000 (713) 460‐3582
12800 Northwest Freeway, Houston TX 77251
Limitations: ‐
Mustang CAT Power Systems Fx:
DS:078‐1
Page 15 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
FABRICATIONSAir Compressor Skid Fabrications
Ph (713) 335‐7000 (713) 335‐7771
Houston TX 77041
Limitations: ‐
Universal Compression Fx:
DS:219‐1
Anchoring System Fabrications
Ph (713) 354‐1900 (713) 354‐1923
Houston TX 77092
Limitations: ‐
Cameron Compression Fx:
DS:023‐1
Dehydration Unit Fabrications
Ph (281) 371‐7500 (281) 371‐0132
35610 Clay Road, Houston TX 77492
Limitations: ‐
Optimized Process Designs, Inc. Fx:
DS:205‐1
Ph (405) 258‐2314 (405) 258‐2110
1510 East 15th Street, Chandler OK 74834
Limitations: ‐
Barnhart's Technical Service, Inc. Fx:
DS:198‐1
Jim Wall Ph 918‐492‐0508 918‐488‐9042
5555 E. 71st ST, Tulsa Oklahoma 74136
Limitations: ‐
E.T.I. Fx:
DS:308.01
Lilac Khosrowyar Ph 918‐663‐8383 918‐663‐8460
1007 E.Admiral Blvd., Tulsa Ok. 74120
Limitations: ‐
Gas Tech Eng. Fx:
DS:309.01
Gas Process Skid Fabrications
Ph (281) 452‐7202 (281) 860‐6713
Channelview TX 77530
Limitations: ‐
Turbofab ‐ Solar Fx:
DS:164‐1
Ph 281‐351‐6315 281‐351‐2382
18115 Telge Road, Cypress TX 77429
Limitations: ‐
Professional Projects, Inc. Fx:
DS:289‐1
Ph (740) 685‐2542 (740) 685‐5516
Derwent OH 43733
Limitations: ‐
Bicon Services, Inc. Fx:
DS:112‐2
Ph (409) 938‐ 6602 (409) 935‐9361
La Marque TX 77568
Limitations: ‐
Paragon Fabricators, Inc. Fx:
DS:204‐1
Ph (432) 337‐3571 (432) 337‐2624
Odessa TX 77429
Limitations: ‐
Sivalls, Inc. Fx:
DS:094‐1
Lilac Khosrowyar Ph 918‐663‐8383 918‐663‐8460
1007 E.Admiral Blvd., Tulsa Ok. 74120
Limitations: ‐
Gas Tech Eng. Fx:
DS:309.01
Page 16 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
Gas Process Skid Fabrications
Jim Wall Ph 918‐492‐0508 918‐488‐9042
5555 E. 71st ST, Tulsa Oklahoma 74136
Limitations: ‐
E.T.I. Fx:
DS:308.01
Ph (281) 371‐7500 (281) 371‐0132
35610 Clay Road, Houston TX 77492
Limitations: ‐
Optimized Process Designs, Inc. Fx:
DS:205‐1
Ph (713) 225‐4913 (713) 224‐7937
3905 Jensen Drive, Houston TX 77026
Limitations: ‐
EN‐FAB, Inc. Fx:
DS:038‐1
Ph (918) 437‐2272 (918) 438‐6418
Tulsa OK 74116
Limitations: ‐
Red Man Measurement Fx:
DS:229‐2
Launcher & Receiver Fabrications
Ph (918) 227‐4600 (918) 224‐8452
Sapulpa OK 74066
Limitations: ‐
Sagebrush Pipeline Equipment Company Fx:
DS:235‐1
John Kennedy Ph (913) 294‐5331 (913) 294‐5337
Paola KS 66071
Limitations: ‐
Taylor Forge Engineered Systems Fx:
DS:127‐2
Ph 918‐224‐4144 918‐224‐4455
Tulsa OK 74131
Limitations: ‐
Pipeline Equipment, Inc. Fx:
DS:283‐1
Ph (740) 685‐2542 (740) 685‐5516
Derwent OH 43733
Limitations: ‐
Bicon Services, Inc. Fx:
DS:112‐1
Machining Fabrications
Ph (432) 563‐5010 (432) 563‐4013
4307 South County Rd. 1300, Odessa TX 79765
Limitations: ‐
Texas Welding & Crankshaft Repair Fx:
DS:114‐1
Ronnie Maybre Ph (713) 691‐3781 (713) 691‐6938
8923 Manus, Houston TX 77093
Limitations: ‐
Natco Machine & Welding Co., Inc. Fx:
DS:105‐1
Ph (785) 825‐4683 (785) 826‐4425
Salina KS 67402‐1487
Limitations: ‐
Exline, Inc. Fx:
DS:104‐1
Ph (903) 892‐8145 (903) 892‐6395
Sherman TX 75090
Limitations: Able to do crankshaft machining.
Washington Iron Works Fx:
DS:103‐1
Page 17 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
Machining Fabrications
Ph (717) 653‐8111 (717) 653‐2013
Mount Joy PA 17752
Limitations: ‐
Griener Industries, Inc. Fx:
DS:132‐1
Mole Sieve Unit Fabrications
Ph (281) 371‐7500 (281) 371‐0132
35610 Clay Road, Houston TX 77492
Limitations: ‐
Optimized Process Designs, Inc. Fx:
DS:205‐1
Pipe Support, Clamp & Strap Fabrications
Ronnie Maybre Ph (713) 691‐3781 (713) 691‐6938
8923 Manus, Houston TX 77093
Limitations: ‐
Natco Machine & Welding Co., Inc. Fx:
DS:105‐1
Ph (713) 731‐0030 (713) 731‐8640
3701 Holmes Road, Houston TX 77051
Limitations: ‐
Sweco‐Fab Fx:
DS:153‐1
Repair Sleeve Fabrications
Ph (918) 447‐5100 (918) 446‐6327
Tulsa OK 74131
Limitations: ‐
TD Williamson, Inc. Fx:
DS:265‐1
Ronnie Maybre Ph (713) 691‐3781 (713) 691‐6938
8923 Manus, Houston TX 77093
Limitations: ‐
Natco Machine & Welding Co., Inc. Fx:
DS:105‐1
Tracey Provenzano Ph (814) 362‐9200 (814) 362‐9353
Bradford PA 16701
Limitations: ‐
Dresser Piping Specialties Fx:
DS:267‐1
Structural Fabrications
Ronnie Maybre Ph (713) 691‐3781 (713) 691‐6938
8923 Manus, Houston TX 77093
Limitations: ‐
Natco Machine & Welding Co., Inc. Fx:
DS:105‐1
Ph (281) 371‐7500 (281) 371‐0132
35610 Clay Road, Houston TX 77492
Limitations: ‐
Optimized Process Designs, Inc. Fx:
DS:205‐1
Ph (918) 583‐7184 (918) 583‐8423
2505 South 33rd West Avenue, Tulsa OK 74107
Limitations: ‐
Allen Edwards, Inc. Fx:
DS:002‐1
Eric Verzwyvelt Ph 985‐868‐7854
250 N0. American Ct, Houma LA 70363
Limitations: ‐
Performance Energy Fx:
DS:303‐1
Ph (281) 496‐1300 (281) 496‐1314
Houston TX 77079
Limitations: ‐
United Steel Structures Fx:
DS:076‐1
Page 18 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
Structural Fabrications
Ph (217) 253‐3371 (217) 253‐2834
980 North CR 610 E, Tuscola IL 61953
Limitations: ‐
J. L. Allen Company Fx:
DS:071‐1
General Non‐Asme Vessel Fabrications
Ph 519‐451‐5480 519‐451‐9922
London ON N5V 2C1
Limitations: ‐
Sleegers Engineering, Inc. Fx:
DS:286‐1
Ph 918‐224‐4144 918‐224‐4455
Tulsa OK 74131
Limitations: ‐
Pipeline Equipment, Inc. Fx:
DS:283‐1
Ph (281) 371‐7500 (281) 371‐0132
35610 Clay Road, Houston TX 77492
Limitations: ‐
Optimized Process Designs, Inc. Fx:
DS:205‐1
Ph (225) 381‐9422 (225) 381‐9746
1700 West Port Drive, Port Allen LA 70767
Limitations: ‐
Turner Industries Group, LLC Fx:
DS:055‐1
Ph (918) 227‐4600 (918) 224‐8452
Sapulpa OK 74066
Limitations: Including Meter Skids
Sagebrush Pipeline Equipment Company Fx:
DS:235‐1
Ph (740) 685‐2542 (740) 685‐5516
Derwent OH 43733
Limitations: ‐
Bicon Services, Inc. Fx:
DS:112‐1
Tracey Provenzano Ph (814) 362‐9200 (814) 362‐9353
Bradford PA 16701
Limitations: ‐
Dresser Piping Specialties Fx:
DS:267‐1
Ph (409) 938‐ 6602 (409) 935‐9361
La Marque TX 77568
Limitations: ‐
Paragon Fabricators, Inc. Fx:
DS:204‐1
Ph (361) 289‐5892 (361) 289‐0124
Corpus Christi TX 78409
Limitations: ‐
Pickett Measurement Fx:
DS:238‐1
Ph 713‐466‐6252 713‐466‐6217
6417 Cunningham Rd., Houston TX 77041
Limitations: ‐
R & N Manufacturing Fx:
DS:297.000‐1
John Kennedy Ph (913) 294‐5331 (913) 294‐5337
Paola KS 66071
Limitations: ‐
Taylor Forge Engineered Systems Fx:
DS:127‐2
Ph (432) 337‐3571 (432) 337‐2624
Odessa TX 77429
Limitations: ‐
Sivalls, Inc. Fx:
DS:094‐1
Page 19 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
General Non‐Asme Vessel Fabrications
Ph (918) 342‐3222 (918) 341‐9430
2405 South Hwy 66, Claremore OK 74017
Limitations: ‐
Process Pipe Fabricators, Inc. Fx:
DS:161‐1
Ph 281‐351‐6315 281‐351‐2382
18115 Telge Road, Cypress TX 77429
Limitations: ‐
Professional Projects, Inc. Fx:
DS:289‐1
Ph
Limitations: ‐
Valtronics Fx:
DS:301.000‐1
Ph (713) 683‐9292 (713) 683‐6768
Houston TX 77092
Limitations: ‐
NATCO Fx:
DS:096‐1
Ronnie Maybre Ph (713) 691‐3781 (713) 691‐6938
8923 Manus, Houston TX 77093
Limitations: ‐
Natco Machine & Welding Co., Inc. Fx:
DS:105‐1
Ph (217) 253‐3371 (217) 253‐2834
980 North CR 610 E, Tuscola IL 61953
Limitations: ‐
J. L. Allen Company Fx:
DS:071‐1
Ph (903) 757‐7341 (903) 759‐6986
White Oak TX 75693
Limitations: ‐
Winston F2S Corporation Fx:
DS:239‐1
Page 20 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
FITTINGSAnchor Forging Fittings
Ph (713) 868‐4200 (713) 868‐4160
Houston TX 77015
Limitations: 2"" to 48"""
Coffer Corporation, An Ameri‐Forge Group Company Fx:
DS:020‐1
Ph (713) 688‐2515 (713) 688‐0205
Houston TX 77091
Limitations: 2"" to 48"""
National Flange & Fitting Company Inc Fx:
DS:073‐1
Ph (214) 589‐8177 (214) 589‐8892
Dallas TX 75356
Limitations: 1/2"" to 48"""
Ladish Fittings ‐ Trinity Fx:
DS:057‐1
Extrusion Fittings
Ph (713) 460‐3700 (713) 939‐1808
Houston TX 77092‐4495
Limitations: 2"" through 36"" ‐ Due to shop size, orders shoul
Weldfit Corporation Fx:
DS:223‐1
John Kennedy Ph (913) 294‐5331 (913) 294‐5337
Paola KS 66071
Limitations: ‐
Taylor Forge Engineered Systems Fx:
DS:127‐1
Ph (318) 222‐3295 (318) 222‐6185
1810 Barton Drive, Shreveport LA 71107
Limitations: 12"" to 48"""
Steel Forgings, Inc. Fx:
DS:116‐1
Ph 918‐224‐4144 918‐224‐4455
Tulsa OK 74131
Limitations: ‐
Pipeline Equipment, Inc.(Extrusion) Fx:
DS:284‐1
Flexiforge End Connector Fittings
Al Cooper Ph 713‐326‐4500 713‐329‐4951
11911 FM 529, Houston TX 77041
Limitations: ‐
Oceaneering Fx:
DS:302‐1
Ph (713) 510‐2200 (713) 668‐9166
Houston TX 77040
Limitations: ‐
Oil States Industries, Inc. Fx:
DS:236‐1
Forged Steel Fittings ‐ 2in and less
Ph (214) 589‐8177 (214) 589‐8892
708 S. Elmira, Russellville AR 72801
Limitations: 2"" and less ‐ Caps 1/2"" to 2"""
Hackney Fittings, Div of Trinity Fitting Group In Fx:
DS:048‐1
Ph (214) 589‐8177 (214) 589‐8892
Dallas TX 75356
Limitations: 1/2"" to 2"""
Ladish Fittings ‐ Trinity Fx:
DS:057‐1
Ph 610‐266‐0530
Catasauqua PA 18032
Limitations: ‐
Phoenix Forging Company Fx:
DS:263‐1
Page 21 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
Forged Steel Fittings ‐ 2in and less
Ph (603) 422‐8000 (603) 422‐8033
110 Corporate Dr., Suite 10, Portsmouth NH 03802‐3180
Limitations: 2"" and less ‐ Longview, TX"
Anvil International Inc Fx:
DS:044‐1
Ph (918) 241‐3595
Tulsa OK 74101
Limitations: 1 1/2"" to 2"""
Flo‐Bend ‐ Trinity Fx:
DS:042‐1
Ph (817) 542‐9977
US Route 522 South, Mount Union PA 17066‐0330
Limitations: 2"" and less"
Bonney Forge Fx:
DS:015‐1
Ph (323) 321‐6520 (310) 32‐0476
Gardena CA 90248
Limitations: ‐
Mills Iron Works Fx:
DS:067‐1
Grade B Fittings
Ph (214) 589‐8177 (214) 589‐8892
400 E. Willow, Enid OK 73701
Limitations: Caps 2"" to 28"""
Hackney Fittings ‐ Trinity Fx:
DS:048.001‐1
Ph (918) 241‐3595
Tulsa OK 74101
Limitations: 2"" to 24""; Elbows ‐ thru 30""; Caps ‐ thru 36""
Flo‐Bend ‐ Trinity Fx:
DS:042‐1
John Kennedy Ph (913) 294‐5331 (913) 294‐5337
Paola KS 66071
Limitations: caps 10"" to 42""; reducers 12"" X 8"" to 48"" X4
Taylor Forge Engineered Systems Fx:
DS:127‐1
Ph (318) 222‐3295 (318) 222‐6185
1810 Barton Drive, Shreveport LA 71107
Limitations: caps 10"" t0 48""; reducers 2"" to 28""; tees 10"
Steel Forgings, Inc. Fx:
DS:116‐1
Ph (503) 241‐0716 (503) 274‐7196
Portland OR 97210
Limitations: Tees 2""‐ 30""_Ells 2""‐30""_Reducers 2""‐ 24""_C
Tube Forgings of America, Inc. Fx:
DS:234‐1
Ph (214) 589‐8177 (214) 589‐8892
Dallas TX 75356
Limitations: 2"" to 48"""
Ladish Fittings ‐ Trinity Fx:
DS:057‐1
Ph (323) 321‐6520 (310) 32‐0476
Gardena CA 90248
Limitations: 2"" to 24"""
Mills Iron Works Fx:
DS:067‐2
Ph (214) 589‐8177 (214) 589‐8892
708 S. Elmira, Russellville AR 72801
Limitations: Caps 2"" to 28"""
Hackney Fittings, Div of Trinity Fitting Group In Fx:
DS:048‐1
Ph (450) 375‐3575 (450) 375‐3772
Granby Quebec, CAN J2J 1J6
Limitations: 4"" and Larger"
EZEFlow, Inc. Fx:
DS:233‐1
Page 22 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
Grade B Fittings
Ph (713) 460‐3700 (713) 939‐1808
Houston TX 77092‐4495
Limitations: 2"" through 36"""
Weldfit Corporation Fx:
DS:223‐1
Ph (908) 638‐6200 (908) 638‐0015
High Bridge NJ 08829
Limitations: 2"" thru 42"""
Custom Alloy Corporation Fx:
DS:228‐1
High Yield Fittings
Ph (450) 375‐3575 (450) 375‐3772
Granby Quebec, CAN J2J 1J6
Limitations: ‐
EZEFlow, Inc. Fx:
DS:233‐1
Ph (214) 589‐8177 (214) 589‐8892
Dallas TX 75356
Limitations: 2"" to 48"""
Ladish Fittings ‐ Trinity Fx:
DS:057‐2
Harald Irowez Ph 281‐363‐2686 281‐367‐2488
Houston TX (Austria)
Limitations: ‐
ERNE Fittings Fx:
DS:307.01
Ph (318) 222‐3295 (318) 222‐6185
1810 Barton Drive, Shreveport LA 71107
Limitations: caps 10"" t0 48""; reducers 2"" to 28""; tees 10"
Steel Forgings, Inc. Fx:
DS:116‐1
Massimo Maimi Ph 390523889811
Castelsangiovanni Piacenza Italy 29027
Limitations: No Flanges
Tecnoforge Fx:
DS:292‐1
John Kennedy Ph (913) 294‐5331 (913) 294‐5337
Paola KS 66071
Limitations: caps 10"" to 42""; reducers 12"" X 8"" to 48"" X4
Taylor Forge Engineered Systems Fx:
DS:127‐1
Ph (713) 460‐3700 (713) 939‐1808
Houston TX 77092‐4495
Limitations: 2"" through 36"""
Weldfit Corporation Fx:
DS:223‐1
Ph (908) 638‐6200 (908) 638‐0015
High Bridge NJ 08829
Limitations: 2"" thru 42"", Through Y‐70"
Custom Alloy Corporation Fx:
DS:228‐1
Ph (503) 241‐0716 (503) 274‐7196
Portland OR 97210
Limitations: Tees 2""‐30"", Y‐70_Ells 2""‐30"", Y‐70_Reducers
Tube Forgings of America, Inc. Fx:
DS:234‐2
Ph 39 0523 555311 39 0523 559621
via Roma 150, Podenzano Piacenza Italy 29027
Limitations: Up to NPS 48""_Supplies ""non‐field"" segmentable
TecTubi Raccordi S.p.A Fx:
DS:291‐1
Ph 39 0523 555311 39 0523 559621
Via Ancona, 27, Calendasco (Piacenza) Italy 29027
Limitations: Up to NPS 48""_Supplies ""non‐field"" segmentable
TecTubi Raccordi S.p.A. Fx:
DS:291.02‐1
Page 23 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
High Yield Fittings
Ph (918) 241‐3595
Tulsa OK 74101
Limitations: 2"" to 24""; Elbows ‐ thru 30""; Caps ‐ thru 36""
Flo‐Bend ‐ Trinity Fx:
DS:042‐1
Mechanical End Connectors
Ph (713) 510‐2200 (713) 668‐9166
Houston TX 77040
Limitations: ‐
Oil States Industries, Inc. Fx:
DS:236‐1
Al Cooper Ph 713‐326‐4500 713‐329‐4951
11911 FM 529, Houston TX 77041
Limitations: ‐
Oceaneering Fx:
DS:302‐1
Ph 713‐526‐7274 713‐529‐3773
Houston TX 77040
Limitations: ‐
Quality Connector Systems, LLC Fx:
DS:288‐1
Mechanical Hot Taps
Ph (713) 510‐2200 (713) 668‐9166
Houston TX 77040
Limitations: ‐
Oil States Industries, Inc. Fx:
DS:236‐1
Al Cooper Ph 713‐326‐4500 713‐329‐4951
11911 FM 529, Houston TX 77041
Limitations: ‐
Oceaneering Fx:
DS:302‐1
Ph 713‐526‐7274 713‐529‐3773
Houston TX 77040
Limitations: ‐
Quality Connector Systems, LLC Fx:
DS:288‐1
Piggable Y Fitting
Ph 713‐526‐7274 713‐529‐3773
Houston TX 77040
Limitations: ‐
Quality Connector Systems, LLC Fx:
DS:288‐1
Pipe Insulating Joints
Al Cooper Ph 713‐326‐4500 713‐329‐4951
11911 FM 529, Houston TX 77041
Limitations: ‐
Oceaneering Fx:
DS:302‐1
Ph 39‐059‐578611 39‐059‐570633
Formigine Italy 41043
Limitations: ‐
Nuova Giungas SRL Fx:
DS:262‐1
Ph (713) 510‐2200 (713) 668‐9166
Houston TX 77040
Limitations: ‐
Oil States Industries, Inc. Fx:
DS:236‐1
Repair Clamps
Page 24 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
Repair Clamps
Al Cooper Ph 713‐326‐4500 713‐329‐4951
11911 FM 529, Houston TX 77041
Limitations: ‐
Oceaneering Fx:
DS:302‐1
Ph (713) 510‐2200 (713) 668‐9166
Houston TX 77040
Limitations: ‐
Oil States Industries, Inc. Fx:
DS:236‐2
Ph 713‐526‐7274 713‐529‐3773
Houston TX 77040
Limitations: ‐
Quality Connector Systems, LLC Fx:
DS:288‐1
Ph (440) 871‐5700 (440) 871‐9577
Cleveland OH 44145
Limitations: ‐
Plidco International, Inc. Fx:
DS:250‐1
Split Tees / Weld Saddles
Ph 918‐224‐4144 918‐224‐4455
Tulsa OK 74131
Limitations: ‐
Pipeline Equipment, Inc. Fx:
DS:283‐1
Tracey Provenzano Ph (814) 362‐9200 (814) 362‐9353
Bradford PA 16701
Limitations: ‐
Dresser Piping Specialties Fx:
DS:267‐1
Ph (318) 222‐3295 (318) 222‐6185
1810 Barton Drive, Shreveport LA 71107
Limitations: ‐
Steel Forgings, Inc. Fx:
DS:116‐1
Stopples
Tracey Provenzano Ph (814) 362‐9200 (814) 362‐9353
Bradford PA 16701
Limitations: ‐
Dresser Piping Specialties Fx:
DS:267‐1
Ph (918) 447‐5100 (918) 446‐6327
Tulsa OK 74131
Limitations: ‐
TD Williamson, Inc. Fx:
DS:265‐1
Tubing Fittings
Ph (440) 656‐3700
Hudson OH 44236
Limitations: ‐
Swagelok Quick‐Connect Company Fx:
DS:190‐1
Ph (614) 279‐7070 (614) 279‐7685
Columbus OH 43228
Limitations: ‐
Parker Hannifin Corporation, Tube Fittings Divisi Fx:
DS:200‐2
Page 25 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
FLANGESFuturetap Flanges
Ph 713‐526‐7274 713‐529‐3773
Houston TX 77040
Limitations: ‐
Quality Connector Systems, LLC Fx:
DS:288‐1
Al Cooper Ph 713‐326‐4500 713‐329‐4951
11911 FM 529, Houston TX 77041
Limitations: ‐
Oceaneering Fx:
DS:302‐1
Ph (713) 510‐2200 (713) 668‐9166
Houston TX 77040
Limitations: ‐
Oil States Industries, Inc. Fx:
DS:236‐1
Misalignment Flanges
Ph (713) 510‐2200 (713) 668‐9166
Houston TX 77040
Limitations: ‐
Oil States Industries, Inc. Fx:
DS:236‐1
Al Cooper Ph 713‐326‐4500 713‐329‐4951
11911 FM 529, Houston TX 77041
Limitations: ‐
Oceaneering Fx:
DS:302‐1
Ph 713‐526‐7274 713‐529‐3773
Houston TX 77040
Limitations: ‐
Quality Connector Systems, LLC Fx:
DS:288‐1
Swivel Ring Flanges
Al Cooper Ph 713‐326‐4500 713‐329‐4951
11911 FM 529, Houston TX 77041
Limitations: ‐
Oceaneering Fx:
DS:302‐1
Ph 713‐526‐7274 713‐529‐3773
Houston TX 77040
Limitations: ‐
Quality Connector Systems, LLC Fx:
DS:288‐1
Ph (713) 510‐2200 (713) 668‐9166
Houston TX 77040
Limitations: ‐
Oil States Industries, Inc. Fx:
DS:236‐1
Weld Neck Flanges
Ph (214) 589‐8177 (214) 589‐8892
708 S. Elmira, Russellville AR 72801
Limitations: 1/2"" to 24"""
Hackney Fittings, Div of Trinity Fitting Group In Fx:
DS:048‐1
Ph (713) 675‐9433 (713) 258‐2110
Houston TX 77013
Limitations: ‐
Boltex, Inc. Fx:
DS:202‐1
Ph (713) 868‐4200 (713) 868‐4160
Houston TX 77015
Limitations: 1/2"" to 60"""
Coffer Corporation, An Ameri‐Forge Group Company Fx:
DS:020‐1
Page 26 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
Weld Neck Flanges
Ph (713) 433‐0700 (713) 433‐5580
Houston TX 77047
Limitations: 2"" ‐ 42"" ‐ ANSI 150 ‐ 1500, ASME B16.5 & MSS SP
Galperti, Inc. Fx:
DS:232‐1
Karan Guzman Ph 832‐397‐4290 713‐635‐4784
7785 East Little York, Houston Texas 77016 (USA)
Limitations: ‐
DL Flange Fx:
DS:311.01
Ph (713) 688‐2515 (713) 688‐0205
Houston TX 77091
Limitations: 1/2"" to 48"""
National Flange & Fitting Company Inc Fx:
DS:073‐1
Ph (214) 589‐8177 (214) 589‐8892
Dallas TX 75356
Limitations: 1/2"" to 60"""
Ladish Fittings ‐ Trinity Fx:
DS:057‐1
Page 27 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
GASKETSSpiral Wound Gaskets
Ph (281) 459‐7202 (281) 459‐7243
Houston TX 77049
Limitations: ‐
Garlock Sealing Technologies Fx:
DS:155‐1
Ph (281) 604‐2400 (281) 604‐2415
Deer Park TX 77563
Limitations: ‐
Flexitallic LP Fx:
DS:156‐1
Page 28 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
GRAVITOMETERSGravitometers
Ph (814) 371‐8000 (814) 375‐8460
Dubois PA 15801
Limitations: Not approved by TETCO
Sensus Metering Systems, Inc. Fx:
DS:245‐1
Ph (918) 250‐7200 (918) 459‐0165
Broken Arrow OK 74012
Limitations: ‐
Amatek Fx:
DS:176‐1
Page 29 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
HEAT EXCHANGERSGas Cooler Heat Exchangers
Ph (918) 251‐2571 (918) 251‐2574
12585 East 61st Street, Broken Arrow OK 74012
Limitations: Need to required AWS D1.1 structural welders for o
R & R Engineering Company, Inc. Fx:
DS:207‐1
Ph (918) 251‐7477 (918) 251‐7482
Broken Arrow OK 74012
Limitations: Need to order without slits in the tube fins ‐ spe
Air Cooled Exchangers, Inc. Fx:
DS:206‐1
Ph (918) 747‐7447 (918) 749‐5080
1219 East 33rd, Tulsa OK 74105
Limitations: Tek‐ Fins fabricates tube fins and assembles aeria
Tek‐Fins, Inc. Fx:
DS:220‐1
Ph (918) 619‐8000 (918) 384‐5000
5215 Arkansas Rd, Catoosa OK 74015
Limitations: ‐
Air X‐Changers, A Harsco Company Fx:
DS:001‐1
Ph (918) 446‐4406 (918) 445‐2857
6312 S. 39th W. Ave., Tulsa Ok 74132
Limitations: ‐
Smithco Engineering Fx:
DS:095‐1
Regenerator Heat Exchangers
Ph (303) 987‐0123
Lakewood CO 80228
Limitations: ‐
GEA Power Cooling, Inc. Fx:
DS:159‐1
Shell and Tube Heat Exchangers
Ph 716‐684‐6700 716‐684‐2129
Buffalo NY 14225
Limitations: ‐
API Basco Fx:
DS:278‐1
Ph (716) 897‐2800 (716) 897‐1777
Buffalo NY 14227
Limitations: ‐
ITT Standard Fx:
DS:069‐1
Ph (281) 471‐4140 (281) 471‐5612
12415 LaPorte Road ‐ Hwy. 225, LaPorte TX 77571
Limitations: ‐
Ohmstede, LTD Fx:
DS:195‐1
Turbocharger Aftercooler Heat Exchangers
Ph (713) 467‐2221 (713) 935‐3490
1200 W. Sam Houston Parkway North, Houston TX 77043
Limitations: ‐
Dresser Rand Company Fx:
DS:028‐1
Ph (713) 354‐1900 (713) 354‐1923
Houston TX 77092
Limitations: ‐
Cameron Compression Fx:
DS:023‐1
Page 30 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
HEATERSDirect Fired Heaters
Ph (713) 683‐9292 (713) 683‐6768
Houston TX 77092
Limitations: ‐
NATCO Fx:
DS:096‐1
Ph (432) 337‐3571 (432) 337‐2624
Odessa TX 77429
Limitations: ‐
Sivalls, Inc. Fx:
DS:094‐1
Indirect Fired Heaters
Ph (979) 732‐2327 (979) 732‐0056
Alleyton TX 78935
Limitations: Inspect critical points indentified on the ITP.
Exterran (Hanover Smith) Fx:
DS:208‐1
Ph (713) 683‐9292 (713) 683‐6768
Houston TX 77092
Limitations: ‐
NATCO Fx:
DS:096‐1
Ph (432) 337‐3571 (432) 337‐2624
Odessa TX 77429
Limitations: ‐
Sivalls, Inc. Fx:
DS:094‐1
Lilac Khosrowyar Ph 918‐663‐8383 918‐663‐8460
1007 E.Admiral Blvd., Tulsa Ok. 74120
Limitations: ‐
Gas Tech Eng. Fx:
DS:309.01
Ph 519‐451‐5480 519‐451‐9922
London ON N5V 2C1
Limitations: ‐
Sleegers Engineering, Inc. Fx:
DS:286‐1
Page 31 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
INDUCTIONBENDInduction Bends
Ph (225) 667‐1000 (225) 667‐1019
Walker LA 70785
Limitations: Pre‐Pro
Sunland Fabricators, Inc. Fx:
DS:216‐1
Ph (403) 279‐2222 (403) 236‐1522
S.E. Calgary Alberta, CAN T2C2V8
Limitations: 2"" to 36"""
Indutech Canada Fx:
DS:146‐1
Ph (801) 773‐2575 (801) 773‐2950
210 E 700 South, Clearfield UT 84015
Limitations: 2"" to 66"""
Shaw Naptech, Inc. Fx:
DS:147‐1
Ph (218) 722‐0205 (218) 722‐6598
366 Garfield Ave, Duluth MN 55802
Limitations: ‐
Bendtec, Inc. Fx:
DS:157‐1
Ph 918‐749‐2463 918‐834‐5910
3207 Dawson Road, Tulsa OK 74110
Limitations: 2" thru 42"
American Pipe Bending Co. Fx:
DS:304‐1
Ph (281) 449‐8241 (281) 449‐3707
14500 E. Hardy, Houston TX 77039
Limitations: 2"" to 36"""
Houston Pipe Benders Fx:
DS:051‐1
Ph (225) 381‐9422 (225) 381‐9746
1700 West Port Drive, Port Allen LA 70767
Limitations: 2"" TO 32"""
Turner Industries Group, LLC Fx:
DS:055‐1
Page 32 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
INSTRUMENTATIONPneumatic Interface Panels
Ph (713) 937‐8111 (713) 937‐0486
Houston TX 77040‐3191
Limitations: ‐
Tex‐A‐Draulics, Inc. Fx:
DS:210‐1
Page 33 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
INSULATING KITSInsulating Kits
Ph (281) 556‐1661 (281) 556‐1683
Houston TX 77082
Limitations: ‐
Pipeline Seal & Insulator, Inc. Fx:
DS:237‐1
Page 34 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
MAGNETIC PIG SIGSMagnetic Pig Sigs
Ph (918) 447‐5100 (918) 446‐6327
Tulsa OK 74131
Limitations: ‐
TD Williamson, Inc. Fx:
DS:265‐1
Page 35 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
METERINGAnnubars
Ph (952) 906‐8811
8200 Market Blvd., Chanhassen MN 55317
Limitations: ‐
Dieterich Standard, Subsidiary of Rosemount Fx:
DS:030‐1
Flow Conditioner
Mike Sanders Ph 281‐235‐0052
10653 46 St. S.E., Calgary Alberta T2C 5C2 (Canada)
Limitations: ‐
MPS Systems LLC Fx:
DS:300.01
Ph (713) 467‐6000 (713) 827‐3880
111000 Brittmore Park, Houston TX 77041
Limitations: ‐
Daniel Measurement & Control, Division of Emerson Fx:
DS:045‐1
Orifice Fittings
Clyde Shugart Ph 432‐381‐5153 432‐381‐3537
725 N. Ave., Odessa TX 79763
Limitations: Includes:Orifice Plates, Seal Rings, Replace Parts
Precision Flow Inc. Fx:
DS:305‐2
Orifice Meters
Ph 713‐465‐3255 713‐465‐3237
Houston TX 77043
Limitations: ‐
TMCO ‐ The Measurement Company, Inc. Fx:
DS:275‐2
Clyde Shugart Ph 432‐381‐5153 432‐381‐3537
725 N. Ave., Odessa TX 79763
Limitations: ‐
Precision Flow Inc. Fx:
DS:305‐1
Ph (713) 467‐6000 (713) 827‐3880
111000 Brittmore Park, Houston TX 77041
Limitations: ‐
Daniel Measurement & Control, Division of Emerson Fx:
DS:045‐1
Rotary Meters
Charlene Bragg Ph 832‐590‐2542
16240 Port N.W. Dr. ST.100, Houston TX
Limitations: ‐
Dresser Roots Meters Fx:
DS:294‐1
Ph (281) 491‐5252 (281) 491‐8440
Stafford TX 77477
Limitations: ‐
Instromet, Inc. Fx:
DS:249‐1
Meter Tube Pipe
Ph 281‐391‐4340
1501 FM 1489 So., Brookshire TX
Limitations: ‐
Scot Industries Fx:
DS:313.01
Meter Tubes
Page 36 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
Meter Tubes
Ph (713) 467‐6000 (713) 827‐3880
111000 Brittmore Park, Houston TX 77041
Limitations: ‐
Daniel Measurement & Control, Division of Emerson Fx:
DS:045‐1
Clyde Shugart Ph 432‐381‐5153 432‐381‐3537
725 N. Ave., Odessa TX 79763
Limitations: ‐
Precision Flow Inc. Fx:
DS:305‐1
Turbine Meters
Ph (814) 371‐8000 (814) 375‐8460
Dubois PA 15801
Limitations: ‐
Sensus Metering Systems, Inc. Fx:
DS:245‐1
Ultrasonic Meters
Ph (713) 467‐6000 (713) 827‐3880
111000 Brittmore Park, Houston TX 77041
Limitations: ‐
Daniel Measurement & Control, Division of Emerson Fx:
DS:045‐1
Ph 631‐231‐3600 631‐231‐3334
Hauppauge NY 11788
Limitations: Portable Clamp‐on Ultrasonic Flowmeters for check
Controlotron Fx:
DS:243‐2
Darryl Kahanek Ph 281‐436‐5100
15415 International Plaza Dr. St 100, Houston Texas 77032
Limitations: ‐
SICK MEASUREMENT Fx:
DS:296.000‐1
Ph 814‐898‐5000 814‐899‐8927
Erie PA 16510
Limitations: ‐
FMC Measurement Solutions Fx:
DS:268‐1
Page 37 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
MOTOR CONTROL CENTERSMotor Control Centers
Ph (713) 672‐3500 (713) 672‐3644
Houston TX 77029‐1398
Limitations: ‐
G.E. Oil & Gas Company Fx:
DS:043‐2
Ph (847) 397‐2600
Palatine IL 60067
Limitations: ‐
Square D / Schneider Electric Fx:
DS:189‐1
Ph (770) 740‐3000
Alpharetta GA 30005
Limitations: ‐
Siemens Energy & Automation, Inc. ‐ Corp. Headqua Fx:
DS:188‐1
Page 38 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
MOTORSElectric Motors
Ph (864) 297‐4800 (864) 281‐2433
Greenville SC 29615
Limitations: ‐
Reliance Electric Fx:
DS:184‐1
Ph (770) 740‐3000
Alpharetta GA 30005
Limitations: ‐
Siemens Energy & Automation, Inc. ‐ Corp. Headqua Fx:
DS:188‐2
Page 39 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
PIPEDouble Submerged Arc Weld Pipe
Ph 55‐12‐3644‐9122 55‐12‐3644‐9027
Av. Gastao Vidigal Neto, 475, Cidade Nova, Pindamonhangaba Sao Paula Brazil
Limitations: 24" to 60"
Tenaris / Confab Fx:
DS:251‐1
Ph 44(0)1536‐402121 44(0)1536‐404004
Brenda Rd, Hartlepool Clevland UK TS252EF
Limitations: 16" to 42"
Corus Tubes Fx:
DS:252‐1
Ph (713) 653‐8400 (713) 658‐9246
Houston TX 77024
Limitations: ‐
Sumitomo Corporation of America Fx:
DS:256.001‐1
Ph (713) 465‐1600 (713) 827‐7423
5315 W 19th Street, Panama City FL 32401
Limitations: 30"" to 72"""
Berg Steel Pipe Corp. Fx:
DS:012‐1
Ph (713) 532‐0052 (713) 532‐0062
Houston TX 77042
Limitations: 20" to 64"
JFE / Kawasaki Fx:
DS:257.001‐1
Ph (713) 465‐1600 (713) 827‐7423
Houston TX 77042
Limitations: ‐
Europipe Fx:
DS:255‐1
Ph (713) 532‐0052 (713) 532‐0062
Houston TX 77042
Limitations: ‐
JFE / Nippon Fx:
DS:258.001‐1
April Schatte Ph (713) 961‐5858 (713) 961‐4433
Taranto Italy
Limitations: 18" to 56"
Ilva America, Inc. Fx:
DS:253‐1
Ph
Limitations: ‐
Evraz Camrose Fx:
DS:306‐2
Electric Resistance Weld Pipe
Diane Burger Ph (281) 752‐7300 (281) 752‐7303
., Thisvi Greece
Limitations: 8" to 26"
Corinth Pipeworks Fx:
DS:254‐000‐2
Ph (972) 386‐3981 (972) 770‐6409
6866 Hwy 259 South, Lone Star TX 75668‐1000
Limitations: Diameters 8 5/8"" through 16"" for grades X‐60 an
U.S. Steel (Lone Star Steel) Fx:
DS:224‐1
Ph 909‐350‐5978 (909) 350‐6210
Fontana CA 92335
Limitations: Diameters 4 1/2"" through 16"" for all grades"
California Steel Industries Fx:
DS:225‐1
Page 40 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
Electric Resistance Weld Pipe
April Schatte Ph (713) 961‐5858 (713) 961‐4433
Taranto Italy
Limitations: 6" to 20"
Ilva America, Inc. Fx:
DS:253‐1
Mark Tinne Ph 281‐671‐3800281‐671‐3800
10343 Sam Houston Park Drive, McKeesport PA
Limitations: 8 5/8" thru 16" x‐52
U.S. Steel Fx:
DS:131.000‐2
Ph (225) 775‐8800 (225) 775‐7610
12555 Ronaldson Road, Baton Rouge LA 70807
Limitations: 10 3/4"" to 24"""
Stupp Corporation Fx:
DS:119‐1
Kevis Trow Ph 713‐585‐3027
Hickman Arkansas 72310
Limitations: Up thru 16" (X‐60)
Tenaris/Hickman Fx:
DS:251‐2
Ph 55‐12‐3644‐9122 55‐12‐3644‐9027
Av. Gastao Vidigal Neto, 475, Cidade Nova, Pindamonhangaba Sao Paula Brazil
Limitations: ‐
Tenaris / Confab Fx:
DS:251.000‐1
Ph (306) 924‐7700 (306) 924‐7500
Reginia Canada
Limitations: 14"" thr 24"" diameter with yield strength up
Evraz IPSCO Regina. Fx:
DS:212‐1
Ph
Limitations: ‐
Evraz Camrose Fx:
DS:306‐1
Ph (713) 532‐0052 (713) 532‐0062
Houston TX 77042
Limitations: 8" to 24"
JFE / Nippon Fx:
DS:258.001‐1
Ph (713) 532‐0052 (713) 532‐0062
Houston TX 77042
Limitations: ‐
JFE / Kawasaki Fx:
DS:257‐2
Ph (713) 465‐1600 (713) 827‐7423
Houston TX 77042
Limitations: ‐
Europipe Fx:
DS:255‐1
Ph (713) 653‐8400 (713) 658‐9246
Houston TX 77024
Limitations: ‐
Sumitomo Corporation of America Fx:
DS:256.000‐2
Ph 44(0)1536‐402121 44(0)1536‐404004
Brenda Rd, Hartlepool Clevland UK TS252EF
Limitations: ‐
Corus Tubes Fx:
DS:252‐1
Ph (713) 686‐4351 (713) 685‐2222
Houston TX 77055
Limitations: ‐
TEX Tube, Inc Fx:
DS:128.000‐1
Page 41 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
Electric Resistance Weld Pipe
Ph (205) 325‐7742 (205) 325‐8194
1501 31st Ave North, Birmingham AL 35201
Limitations: 10 3/4"" to 24"""
American Steel Pipe, Division, American Cast Iron Fx:
DS:004‐1
Seamless Pipe
Ph (705) 946‐8130 (705) 946‐8154
Sault Ste Marie ON P6C 1L9
Limitations: ‐
Tenaris / Algoma Tubes Fx:
DS:251.001‐1
Ph (713) 532‐0052 (713) 532‐0062
Houston TX 77042
Limitations: 2" to 16"
JFE / Nippon Fx:
DS:258.000‐1
Ph (81) 44‐328‐3400 (81) 44‐328‐3456
Kawasaki City Japan 210‐0855
Limitations: ‐
Tenaris / NKK Tubes Fx:
DS:251.002‐1
Mark Tinne Ph
Fairfield AL
Limitations: Seamless
U.S. Steel Fx:
DS:131.000‐3
Karen Leone Ph 281‐456‐6018 281‐456‐7247
Youngstown Ohio 44510
Limitations: Seamless Pipe sizes 6"" to 10"""
V&M Star Steel, Inc.(North Star) Fx:
DS:199.000‐1
Mark Tinne Ph 281‐671‐3800
Lorain Ohio
Limitations: Seamless
U.S. Steel Fx:
DS:131.000‐1
Spiral Pipe
Bill Browman Ph 281‐204‐6020
Bay St. Louis Mississippi
Limitations: ‐
PSL North America, LLC Fx:
DS:299.0001
Ph (225) 775‐8800 (225) 775‐7610
12555 Ronaldson Road, Baton Rouge LA 70807
Limitations: ‐
Stupp Corporation Fx:
DS:119‐1
Ph
Reginia Canada (Canada)
Limitations: ‐
Evraz IPSCO Regina Fx:
DS:212‐2
Diane Burger Ph 281‐752‐7300
Thisvi Greece
Limitations: 24" to 48"
Corinth Pipe Works Fx:
DS:254.000‐1
Brian Roper Ph 713‐465‐1600
900 Paper Mill Rd., Mobile AL 36610
Limitations: ‐
Berg Spiral Pipe Corp Fx:
DS:300.000‐1
Page 42 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
RTURemote Terminal Units (RTU)
Ph (713) 272‐2294 (713) 272‐5338
Houston TX 77099
Limitations: ‐
Thermo Electron Corporation Fx:
DS:244.000‐1
Page 43 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
SWITCHGEARSwitchgear
Ph (770) 740‐3000
Alpharetta GA 30005
Limitations: ‐
Siemens Energy & Automation, Inc. ‐ Corp. Headqua Fx:
DS:188.000‐1
Ph (713) 672‐3500 (713) 672‐3644
Houston TX 77029‐1398
Limitations: ‐
G.E. Oil & Gas Company Fx:
DS:043.000‐2
Page 44 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
TANKSAtmospheric Storage Tanks
Ronnie Maybre Ph (713) 691‐3781 (713) 691‐6938
8923 Manus, Houston TX 77093
Limitations: ‐
Natco Machine & Welding Co., Inc. Fx:
DS:105.000‐1
Ph (903) 859‐2111 (903) 859‐4191
100 Hwy 64 West, Arp TX 75750
Limitations: ‐
Baker Tank Company Fx:
DS:083.000‐1
Ph (580) 338‐5496 (580) 338‐0885
Guymon OK 73942
Limitations: ‐
Cimarron, Inc. Fx:
DS:084.000‐1
Page 45 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
TRANSFORMERSTransformers
Ph (713) 672‐3500 (713) 672‐3644
Houston TX 77029‐1398
Limitations: ‐
G.E. Oil & Gas Company Fx:
DS:043.000‐1
Ph (434) 846‐3553
Lynchburg VA 24501
Limitations: ‐
Delta Star, Inc. Fx:
DS:175.000‐1
Ph (414) 209‐1620 (414) 209‐1621
Franklin WI 53132‐8847
Limitations: ‐
Jefferson Electric Fx:
DS:214.000‐1
Ph (606) 813‐2236
Versailles KY 40383
Limitations: ‐
Kuhlman Electric Fx:
DS:180.000‐1
Page 46 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
TRANSFORMETTransformet
Ph (919) 734‐8900 (919) 580‐3244
Goldsboro NC 27530
Limitations: ‐
Waukeshau Electric Fx:
DS:178.000‐1
Page 47 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
TRANSMITTERSTransmitters
Ph (952) 906‐8811
Chanhassen MN 55317‐9687
Limitations: ‐
Rosemount Division Emerson Process Management Fx:
DS:185.000‐1
Ph (713) 780‐6500 (713) 780‐6676
Houston TX 77063
Limitations: ‐
Honeywell, Inc. Fx:
DS:179.000‐1
Page 48 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
VALVESBall Valve ‐ 2inch and larger
Bill Richardson Ph 281‐261‐3698 (281) 261‐3589
Weifang City China
Limitations: 2" thru 24" All valves must be tested in US
Cameron Valves Fx:
DS:016.000‐2
Ph (780) 463‐4888
3707 97th Street, Edmonton Alberta T6E 6J2
Limitations: ‐
Grove Valve, Valgro Fx:
DS:046.001‐1
Bill Richardson Ph 281‐261‐3698 (281) 261‐3589
Ville Platte LA 70586
Limitations: 2"" to 16"", Removed Small Valves with threaded d
Cameron Valves WKM Fx:
DS:016.001‐1
Franco Perfetti Ph 8651285160128
Wujiang China
Limitations: All valves must be tested in U.S.
Valvitalia (Delta)(China) Fx:
DS:277.000‐2
Ph 281‐261‐3698 (281) 261‐3589
Houston TX 77042
Limitations: As of 02/27/2002, Cameron's Type 40, bolted‐body
Cameron Valves/Ville Platte Fx:
DS:016.000‐1
Ph (405) 631‐1533 (405) 631‐5034
Oklahoma City OK 73143
Limitations: 2"" to 4"""
KF Industries, Inc. Fx:
DS:151.000‐1
Max Ruggeri Ph 39.0382.94.59.11 39.0383.916.31
Rivanazzano (PV) Italy 27055
Limitations: Valves to be tested in U.S.
Delta Valve / Valvitalia Fx:
DS:277.000‐1
Ph 800‐643‐9390 501‐570‐5700
Little Rock AR 72209
Limitations: ‐
Orbit Valve ‐ Cooper Cameron Fx:
DS:086.000‐1
Bill Richardson Ph 281‐261‐3698 281‐261‐3589
Houston TX 77041
Limitations: 2"" & larger ‐ 2"" to 48"""
Grove Valve, (Cameron Ville Platte) Fx:
DS:046.000‐1
Ph (281) 340‐5400 (281) 340‐5499
Stafford TX 77477
Limitations: 2"" thru 24"", ANSI 150 thru 1500, 2"" thru 12"",
PBV‐USA, Inc. Fx:
DS:222.000‐2
Ph (905) 791‐5777 (905) 791‐5756
Brampton ON, CAN L6T 4L3
Limitations: Approved for 20"" ‐ 60"""
GVS, Ltd. ‐ Guide Valve (Nuovo Pignone Design) Fx:
DS:240.000‐1
Josh Smith Ph 281‐482‐4728 281‐482‐9728
3521 FM 646 Rd. North, Santa Fe Texas 77510
Limitations: Up thru 24"
Southern California Valve Fx:
DS:312.02
Ball Valve ‐ less than 2in
Page 49 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
Ball Valve ‐ less than 2in
Ph (704) 841‐6000 (704) 841‐6020
Matthews NC 28106
Limitations: Now make up 12" FExFE ‐ Bronze, Carbon, Stainles
Apollo Ball Valve Division, Conbraco Fx:
DS:005.000‐1
Josh Smith Ph 281‐482‐4728 281‐482‐9728
3521 FM 646 Rd. North, Santa Fe Texas 77510
Limitations: ‐
Southern California Valve Fx:
DS:312.02
Ph 603‐895‐4761 603‐865‐6785
Raymond NH 03077
Limitations: ‐
Gemini Valve Fx:
DS:272.000‐1
Ph (508) 481‐4800 (508) 481‐4454
Marlborough MA 01752
Limitations: Less than 2"" ‐ 1/8"" to 2"" bolt‐thru body desig
Worcester Controls Corp. Fx:
DS:138.000‐1
Ph 508‐852‐0200 508‐852‐8172
44 Bowditch Dr., Shrewsbury MA 01545
Limitations: Bolt‐thru body design only
Neles‐Jamesbury Valve, Div of Metso Automation Fx:
DS:074.000‐1
Ph (440) 473‐1050 (440) 473‐0402
Highland Heights OH 44143
Limitations: 1/8"" to 2"" bolt‐thru body design only ‐ AGT doe
Swagelok ‐ Whitey Fx:
DS:137.000‐1
Ph (931) 432‐4021 (931) 432‐5518
Cookeville TN 38501
Limitations: Less than 2"" ‐ 1/4"" to 1"" ‐ Screwed Body Const
McCanna / Marpac Valves Div of Flowserve Fx:
DS:062.000‐1
Butterfly Valves (Non Gas Service)
Ph (931) 432‐4021 (931) 432‐5518
Cookeville TN 38501
Limitations: 3"" to 36"""
McCanna / Marpac Valves Div of Flowserve Fx:
DS:062.000‐1
Ph 641‐754‐3011 641‐754‐2830
Marshalltown IA 50158
Limitations: ‐
Posi‐Seal, Division of Fisher Controls Fx:
DS:152.000‐1
Check Valves ‐ 2in and larger
John Brown Ph 832‐912‐1022 832‐912‐1151
Edmonton Canada
Limitations: 1" thru 42"
Stream‐Flo Industries Fx:
DS:295.1
Daniele Balzarotti Ph 3904447491168 390444401498
Vicenza Italy
Limitations: Valves must be tested in U.S.
Valvitalia (Vitas) Fx:
DS:293.01
Ph (281) 599‐3777 (281) 599‐3888
Nijverheidsstraat 67, Gouda The Netherlands
Limitations: 2"" & larger ‐ 2"" to 48"" ‐ Disapproved by AGT"
Mokveld Valves, Inc. Fx:
DS:068.000‐1
Page 50 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
Check Valves ‐ 2in and larger
Ph (281) 469‐0550 (281) 894‐1332
19191 Hempstead Hwy., Houston TX 77065
Limitations: 2"" thru 16"""
M & J Valve, An SPX Process Equipment Operation Fx:
DS:027.000‐2
Ph (832) 590‐2300 (832) 590‐2529
Houston TX 77041
Limitations: 2"" & larger ‐ 2"" to 48"""(US Only)
Tom Wheatley Valve Fx:
DS:130.000‐1
Ph (918) 446‐4551 (918) 582‐5013
6750 S. 57th West Ave., Tulsa OK 74131‐2233
Limitations: 2 & larger ‐ 2"" to 48"
National Oilwell Varco Fx:
DS:136.000‐1
Josh Smith Ph 281‐482‐4728 281‐482‐9728
3521 FM 646 Rd. North, Santa Fe Texas 77510
Limitations: Up thru 24"
Southern California Valve Fx:
DS:312.01
Check Valves ‐ less than 2"
Ph (814) 542‐9977
Mount Union PA 77040
Limitations: Less than 2"" ‐ 1/4"" to 2"""
RP & C, Division of Bonney Forge Fx:
DS:102.000‐1
Ph (903) 885‐3151 (903) 439‐3411
1511 Jefferson St., Sulphur Springs TX 75482
Limitations: Less than 2"" ‐ 1/4"" to 2"" ‐ Not Approved by AG
Vogt Valve, Div. of Flowserve Fx:
DS:135.000‐1
Josh Smith Ph 281‐482‐4728 281‐482‐9728
3521 FM 646 Rd. North, Santa Fe Texas 77510
Limitations: ‐
Southern California Valve Fx:
DS:312.02
Ph (918) 446‐4551 (918) 582‐5013
6750 S. 57th West Ave., Tulsa OK 74131‐2233
Limitations: Less than 2"" ‐ 1/2"" to 2"""
National Oilwell Varco Fx:
DS:136.000‐1
Ph (203) 363‐7300
Stamford CT 06902
Limitations: 1/4"" to 2"" ‐ Disapproved by AGT"
Crane Company Fx:
DS:025.000‐1
Ph (832) 590‐2300 (832) 590‐2529
Houston TX 77041
Limitations: Less than 2"" ‐ 1/2"" to 2"""(US Only)
Tom Wheatley Valve Fx:
DS:130.000‐1
Ph (713) 590‐1312 (713) 590‐1319
Houston TX 77040
Limitations: Less than 2"" ‐ 1/4"" to 2"" ‐ Disapproved by AGT
Smith Valve, Division of Newdell Industries Fx:
DS:109.000‐1
John Brown Ph 832‐912‐1022 832‐912‐1151
Edmonton Canada
Limitations: ‐
Stream‐Flo Industries Fx:
DS:295.1
Control Valves
Page 51 of 61
Thursday, July 28, 2011
1:57:44 PMSpectra Commodities Lis
Control Valves
Ph (832) 590‐2300 (832) 590‐2529
Houston TX 77041
Limitations: ‐
Masoneilan Valve Division, Dresser Flow Solutions Fx:
DS:061.000‐1
Ph (952) 906‐8811
Chanhassen MN 55317
Limitations: Ball 4"" to 24"", Globe 1"" to 12"""
Fisher, Division of Emerson Process Management Fx:
DS:041.000‐1
Ph (801) 489‐8611 (801) 489‐3719
Springville UT 84663‐0903
Limitations: Ball 2"" ‐ 12""; Globe 1/2"" to 42"""
Flow Serv Fx:
DS:134.000‐1
Ph (985) 851‐3160 (985) 851‐7062
Houma LA 70360
Limitations: ‐
CorVal, L. P. Fx:
DS:241.000‐1
Ph 508‐852‐0200 508‐852‐8172
44 Bowditch Dr., Shrewsbury MA 01545
Limitations: Ball 4"" ‐ 36"", Globe 1/2"" ‐ 16"""
Neles‐Jamesbury Valve, Div of Metso Automation Fx:
DS:074.000‐1
Gate Valves ‐ 2in and larger
Ph (780) 463‐4888
3707 97th Street, Edmonton Alberta T6E 6J2
Limitations: ‐
Grove Valve, Valgro Fx:
DS:046.001‐1
Bill Richardson Ph 281‐261‐3698 (281) 261‐3589
Ville Platte LA 70586
Limitations: 2"" to 36"""
Cameron Valves WKM Fx:
DS:016.001‐1
Bill Richardson Ph 281‐261‐3698 281‐261‐3589
Houston TX 77041
Limitations: 2"" & larger ‐ 2"" to 48"""
Grove Valve, (Cameron Ville Platte) Fx:
DS:046.000‐1
Ph (281) 469‐0550 (281) 894‐1332
19191 Hempstead Hwy., Houston TX 77065
Limitations: 2"" to 87"""
M & J Valve, An SPX Process Equipment Operation Fx:
DS:027.000‐2
Josh Smith Ph 281‐482‐4728 281‐482‐9728
3521 FM 646 Rd. North, Santa Fe Texas 77510
Limitations: Up thru 24"
Southern California Valve Fx:
DS:312.01
Ph (203) 363‐7300
Stamford CT 06902
Limitations: ‐
Crane Company Fx:
DS:025.000‐1
Ph 281‐261‐3698 (281) 261‐3589
Houston TX 77042
Limitations: ‐
Cameron Valves/Ville Platte Fx:
DS:016.000‐1
Gate Valves ‐ less than 2in
Page 52 of 61
Thursday, July 28, 2011
1:57:45 PMSpectra Commodities Lis
Gate Valves ‐ less than 2in
Ph (814) 542‐9977
Mount Union PA 77040
Limitations: Less than 2"" ‐ 1/2"" to 2"" ‐ Disapproved by AGT
RP & C, Division of Bonney Forge Fx:
DS:102.000‐1
Ph (713) 590‐1312 (713) 590‐1319
Houston TX 77040
Limitations: Less than 2"" ‐ 1/4"" to 2"" ‐ Disapproved by AGT
Smith Valve, Division of Newdell Industries Fx:
DS:109.000‐1
Ph (203) 363‐7300
Stamford CT 06902
Limitations: 1/2"" to 2"""
Crane Company Fx:
DS:025.000‐1
Josh Smith Ph 281‐482‐4728 281‐482‐9728
3521 FM 646 Rd. North, Santa Fe Texas 77510
Limitations: ‐
Southern California Valve Fx:
DS:312.02
Ph (903) 885‐3151 (903) 439‐3411
1511 Jefferson St., Sulphur Springs TX 75482
Limitations: Less than 2"" ‐ 1/2"" to 2"""
Vogt Valve, Div. of Flowserve Fx:
DS:135.000‐1
Globe Valves ‐ less than 2in
Ph (713) 590‐1312 (713) 590‐1319
Houston TX 77040
Limitations: Less than 2"" ‐ 1/4"" to 2"""
Smith Valve, Division of Newdell Industries Fx:
DS:109.000‐1
Ph (814) 542‐9977
Mount Union PA 77040
Limitations: Less than 2"" ‐ 1/4"" to 2"" ‐ Disapproved by AGT
RP & C, Division of Bonney Forge Fx:
DS:102.000‐1
Ph (903) 885‐3151 (903) 439‐3411
1511 Jefferson St., Sulphur Springs TX 75482
Limitations: Less than 2"" ‐ 1/2"" to 2"""
Vogt Valve, Div. of Flowserve Fx:
DS:135.000‐1
Ph (203) 363‐7300
Stamford CT 06902
Limitations: 1/4"" to 2"""
Crane Company Fx:
DS:025.000‐1
Manifold Valves
Ph (832) 261‐2400 (281) 291‐8801
Pasadena TX 77507
Limitations: ‐
Anderson Greenwood, Div of TYCO Valves & Controls Fx:
DS:106.000‐1
Ph (713) 466‐0056 (800) 568‐9228
Houston TX 77041
Limitations: ‐
PGI International Fx:
DS:100.000‐1
Ph (440) 473‐1050 (440) 473‐0402
Highland Heights OH 44143
Limitations: ‐
Swagelok ‐ Whitey Fx:
DS:137.000‐1
Needle Valves
Page 53 of 61
Thursday, July 28, 2011
1:57:45 PMSpectra Commodities Lis
Needle Valves
Ph (864) 574‐7966 (864) 587‐5608
405 Centura Court, Spartanburg SC 29303
Limitations: ‐
Hoke, Inc. Fx:
DS:120.000‐1
Ph (440) 951‐7100 (440) 951‐4872
Willouby OH 44084
Limitations: ‐
Swagelok ‐ Nupro Fx:
DS:082.000‐1
Ph (440) 473‐1050 (440) 473‐0402
Highland Heights OH 44143
Limitations: ‐
Swagelok ‐ Whitey Fx:
DS:137.000‐1
Ph 304‐387‐1200 304‐387‐1212
Newell WV 26050
Limitations: ‐
Marsh ‐ Bellofram Fx:
DS:060.000‐1
Ph (832) 261‐2400 (281) 291‐8801
Pasadena TX 77507
Limitations: ‐
Anderson Greenwood, Div of TYCO Valves & Controls Fx:
DS:106.000‐1
Ph (713) 466‐0056 (800) 568‐9228
Houston TX 77041
Limitations: ‐
PGI International Fx:
DS:100.000‐1
Piston Check Valves ‐ 2in and larger
Ph (281) 599‐3777 (281) 599‐3888
Nijverheidsstraat 67, Gouda The Netherlands
Limitations: 2"" & larger"
Mokveld Valves, Inc. Fx:
DS:068.000‐1
Ph (832) 590‐2300 (832) 590‐2529
Houston TX 77041
Limitations: Waiver Req. 2"" to 20""_VERTICAL PISTON"
Tom Wheatley Valve Fx:
DS:130.000‐1
Ph (713) 590‐1312 (713) 590‐1319
Houston TX 77040
Limitations: 2"" and larger"
Smith Valve, Division of Newdell Industries Fx:
DS:109.000‐1
John Brown Ph 832‐912‐1022 832‐912‐1151
Edmonton Canada
Limitations: 2" thru 42"(Valves to be tested in No. Am.)
StreamFlo (Europa Va) Fx:
DS:295‐2
Plug Valves ‐ 2in and larger
Veron Jones Ph 281‐890‐2739 281‐469‐2827
1511 Jefferson Street, Sulphur Springs TX 75482
Limitations: 2"" and larger ‐ 8"" to 42"""
Nordstrom Valves Division of Flowserve Fx:
DS:079.000‐1
Franco Perfetti Ph 8651285160128
Wujiang China
Limitations: ‐
Valvitalia (Delta)(China) Fx:
DS:277.000‐2
Page 54 of 61
Thursday, July 28, 2011
1:57:45 PMSpectra Commodities Lis
Plug Valves ‐ 2in and larger
Josh Smith Ph 281‐482‐4728 281‐482‐9728
3521 FM 646 Rd. North, Santa Fe Texas 77510
Limitations: Up thru 24"
Southern California Valve Fx:
DS:312.02
Ph (713) 692‐9921 (713) 692‐1802
Houston TX 77022
Limitations: 2"" and larger‐ 2"" to 24"""
Serck Audco Valves, Division of Flowserve Fx:
DS:107.000‐2
Max Ruggeri Ph 39.0382.94.59.11 39.0383.916.31
Rivanazzano (PV) Italy 27055
Limitations: ‐
Delta Valve / Valvitalia Fx:
DS:277.000‐1
Ph 39.02.96.799.632 39.02.96.799.699
Milano Italy 20020
Limitations: ‐
Galli‐Cassina Fx:
DS:280.000‐1
Plug Valves ‐ less than 2in
Ph (440) 951‐7100 (440) 951‐4872
Willouby OH 44084
Limitations: 2"" ‐ 1/8"" to 1/2"""
Swagelok ‐ Nupro Fx:
DS:082.000‐1
Ph (713) 692‐9921 (713) 692‐1802
Houston TX 77022
Limitations: Less than 2"" ‐ 1/2"" to 2"""
Serck Audco Valves, Division of Flowserve Fx:
DS:107.000‐1
Veron Jones Ph 281‐890‐2739 281‐469‐2827
1511 Jefferson Street, Sulphur Springs TX 75482
Limitations: less than 2"" ‐ 1/4"" to 2"""
Nordstrom Valves Division of Flowserve Fx:
DS:079.000‐1
Regulators
Ph (780) 463‐4888
3707 97th Street, Edmonton Alberta T6E 6J2
Limitations: ‐
Grove Valve, Valgro Fx:
DS:046.001‐1
Ph (801) 487‐2225 (801) 487‐2587
Salt Lake City UT 84115
Limitations: ‐
Mooney Controls ‐ Division of Dresser Fx:
DS:070.000‐1
Ph (952) 906‐8811
Chanhassen MN 55317
Limitations: ‐
Fisher, Division of Emerson Process Management Fx:
DS:041.000‐1
Bill Richardson Ph 281‐261‐3698 281‐261‐3589
Houston TX 77041
Limitations: ‐
Grove Valve, (Cameron Ville Platte) Fx:
DS:046.000‐1
Ph (281) 491‐2331 (281) 491‐8344
13839 West Bellfort, Sugarland TX 77478
Limitations: ‐
Welker Engineering Fx:
DS:053.000‐1
Relief Valves
Page 55 of 61
Thursday, July 28, 2011
1:57:45 PMSpectra Commodities Lis
Relief Valves
Ph (281) 491‐2331 (281) 491‐8344
13839 West Bellfort, Sugarland TX 77478
Limitations: ‐
Welker Engineering Fx:
DS:053.000‐1
Ph (801) 487‐2225 (801) 487‐2587
Salt Lake City UT 84115
Limitations: ‐
Mooney Controls ‐ Division of Dresser Fx:
DS:070.000‐1
Ph (832) 261‐2400 (281) 291‐8801
Pasadena TX 77507
Limitations: ‐
Anderson Greenwood, Div of TYCO Valves & Controls Fx:
DS:106.000‐1
Ph (780) 463‐4888
3707 97th Street, Edmonton Alberta T6E 6J2
Limitations: ‐
Grove Valve, Valgro Fx:
DS:046.001‐1
Perry Blythe (The Blythe Co)
Ph 704‐843‐1960 704‐843‐1990
6012 Waxhaw Highway, Mineral Springs North Carolina 28108 (USA)
Limitations: 1/2" inlet to 8" inlet
Mercer Valve Co. Fx:
DS:310.01
Bill Richardson Ph 281‐261‐3698 281‐261‐3589
Houston TX 77041
Limitations: ‐
Grove Valve, (Cameron Ville Platte) Fx:
DS:046.000‐1
Ph 716‐662‐2585 716‐662‐2580
Orchard Park NY 14127
Limitations: ‐
Flow Safe Supply Fx:
DS:282.000‐1
Page 56 of 61
Thursday, July 28, 2011
1:57:45 PMSpectra Commodities Lis
VARIABLE SPEED DRIVESElectric Variable Speed Drives
Ph (713) 467‐9888 (713) 827‐8460
Houston TX 77043
Limitations: ‐
National Oil Well Fx:
DS:186.000‐1
Ph (770) 740‐3000
Alpharetta GA 30005
Limitations: ‐
Siemens Energy & Automation, Inc. ‐ Corp. Headqua Fx:
DS:188.000‐1
Ph (713) 672‐3500 (713) 672‐3644
Houston TX 77029‐1398
Limitations: ‐
G.E. Oil & Gas Company Fx:
DS:043.000‐1
Page 57 of 61
Thursday, July 28, 2011
1:57:45 PMSpectra Commodities Lis
VESSELSBlowdown Tanks/Silencers
Ph (716) 662‐6540 (716) 662‐6548
401 US Hwy 281, Wichita Falls TX 76310
Limitations: ‐
Burgess‐Manning, Inc. Fx:
DS:092.000‐1
Ph (713) 465‐0995 (713) 465‐0997
7607 Wright Road, Houston TX 77041
Limitations: ‐
Mueller Environmental Designs, Inc. Fx:
DS:201.000‐1
Ph (716) 662‐6540 (716) 662‐6548
105 E. 10th Street, Sisco TX 76437
Limitations: ‐
Burgess‐Manning, Inc. Fx:
DS:092.001‐1
Ph (318) 671‐5400 (318) 671‐5583
Shreveport LA 71106‐7198
Limitations: ‐
Beaird Company, LTD Fx:
DS:010.000‐1
Ph (281) 255‐6955 (281) 351‐8502
Cypress TX 77429
Limitations: ‐
McGuffy Industries Fx:
DS:093.000‐1
Engine Air Intake Filters
Ph (952) 887‐3131 (952) 887‐3155
9250 West Bloomington, Minneapolis MN 55431
Limitations: ‐
Donaldson Company, Torit Products Fx:
DS:113.000‐1
Ph (281) 255‐6955 (281) 351‐8502
Cypress TX 77429
Limitations: ‐
McGuffy Industries Fx:
DS:093.000‐1
Engine Air Intake Silencers
Ph (608) 873‐4242 (608) 873‐4298
1925 Hwy 51 W, Stoughton WI 53589
Limitations: ‐
Universal Silencers Fx:
DS:085.000‐1
Ph (716) 662‐6540 (716) 662‐6548
105 E. 10th Street, Sisco TX 76437
Limitations: ‐
Burgess‐Manning, Inc. Fx:
DS:092.000‐2
Ph (318) 671‐5400 (318) 671‐5583
Shreveport LA 71106‐7198
Limitations: ‐
Beaird Company, LTD Fx:
DS:010.000‐1
Ph (713) 465‐0995 (713) 465‐0997
7607 Wright Road, Houston TX 77041
Limitations: ‐
Mueller Environmental Designs, Inc. Fx:
DS:201.000‐1
Ph (716) 662‐6540 (716) 662‐6548
401 US Hwy 281, Wichita Falls TX 76310
Limitations: ‐
Burgess‐Manning, Inc. Fx:
DS:092.000‐1
Engine Lube Oil Filters
Page 58 of 61
Thursday, July 28, 2011
1:57:45 PMSpectra Commodities Lis
Engine Lube Oil Filters
Ph (940) 325‐2575 (940) 325‐4622
118 Washington Ave., Mineral Wells TX 76068
Limitations: ‐
PECO ‐ Perry Corp. Fx:
DS:099.000‐1
Ph (847) 674‐7782 (847) 674‐0379
3440 Cleveland Ave., Skokie IL 60076
Limitations: ‐
William W. Nugent & Co., Inc. Fx:
DS:081.000‐1
Ph (607) 733‐7121 (617) 737‐1108
Elmira NY 14902‐7121
Limitations: ‐
Hilco Div. / Hilliard Corp. Fx:
DS:050.000‐2
Exhaust Silencers
Ph (716) 662‐6540 (716) 662‐6548
105 E. 10th Street, Sisco TX 76437
Limitations: ‐
Burgess‐Manning, Inc. Fx:
DS:092.001‐1
Ph (318) 671‐5400 (318) 671‐5583
Shreveport LA 71106‐7198
Limitations: ‐
Beaird Company, LTD Fx:
DS:010.000‐1
Ph (713) 465‐0995 (713) 465‐0997
7607 Wright Road, Houston TX 77041
Limitations: ‐
Mueller Environmental Designs, Inc. Fx:
DS:201.000‐1
Ph (716) 662‐6540 (716) 662‐6548
401 US Hwy 281, Wichita Falls TX 76310
Limitations: ‐
Burgess‐Manning, Inc. Fx:
DS:092.000‐1
Ph (281) 255‐6955 (281) 351‐8502
Cypress TX 77429
Limitations: ‐
McGuffy Industries Fx:
DS:093.000‐1
Gas Separators
Ph (713) 225‐4913 (713) 224‐7937
3905 Jensen Drive, Houston TX 77026
Limitations: ‐
EN‐FAB, Inc. Fx:
DS:038.000‐1
Ph 905‐696‐9292 905‐696‐8046
Mississauga Ontario L4W 2V6
Limitations: ‐
ESS Corp. Fx:
DS:270.000‐1
John Kennedy Ph (913) 294‐5331 (913) 294‐5337
Paola KS 66071
Limitations: ‐
Taylor Forge Engineered Systems Fx:
DS:127.000‐1
Lilac Khosrowyar Ph 918‐663‐8383 918‐663‐8460
1007 E.Admiral Blvd., Tulsa Ok. 74120
Limitations: ‐
Gas Tech Eng. Fx:
DS:309.01
Page 59 of 61
Thursday, July 28, 2011
1:57:45 PMSpectra Commodities Lis
Gas Separators
Ph 713‐466‐6252 713‐466‐6217
6417 Cunningham Rd., Houston TX 77041
Limitations: ‐
R & N Manufacturing Fx:
DS:297.000‐1
Ph (903) 757‐7341 (903) 759‐6986
White Oak TX 75693
Limitations: ‐
Winston F2S Corporation Fx:
DS:239‐1
Ph (940) 325‐2575 (940) 325‐4622
118 Washington Ave., Mineral Wells TX 76068
Limitations: ‐
PECO ‐ Perry Corp. Fx:
DS:099.000‐1
Ph (214) 357‐6181 (214) 351‐0194
ABILINE TX 75229
Limitations: ‐
Peerless Manufacturing Fx:
DS:098.000‐1
Ph (716) 662‐6540 (716) 662‐6548
401 US Hwy 281, Wichita Falls TX 76310
Limitations: ‐
Burgess‐Manning, Inc. Fx:
DS:092.000‐1
Ph (903) 759‐4478 (903) 759‐6781
208 South Ave. A, Longview TX 75604
Limitations: ‐
King Tool Company Fx:
DS:091.000‐1
Inline Silencers
Ph (608) 873‐4242 (608) 873‐4298
1925 Hwy 51 W, Stoughton WI 53589
Limitations: ‐
Universal Silencers Fx:
DS:085.000‐1
Pulsation Bottles
Ph (740) 685‐2542 (740) 685‐5516
Derwent OH 43733
Limitations: ‐
Bicon Services, Inc. Fx:
DS:112.000‐1
Ph (716) 662‐6540 (716) 662‐6548
401 US Hwy 281, Wichita Falls TX 76310
Limitations: ‐
Burgess‐Manning, Inc. Fx:
DS:092.000‐1
Ph (214) 357‐6181 (214) 351‐0194
ABILINE TX 75229
Limitations: ‐
Peerless Manufacturing Fx:
DS:098.000‐1
John Kennedy Ph (913) 294‐5331 (913) 294‐5337
Paola KS 66071
Limitations: ‐
Taylor Forge Engineered Systems Fx:
DS:127.000‐1
Strainers, 6" and Larger"
Ph (940) 325‐2575 (940) 325‐4622
118 Washington Ave., Mineral Wells TX 76068
Limitations: Larger than 6"""
PECO ‐ Perry Corp. Fx:
DS:099.000‐1
Page 60 of 61
Thursday, July 28, 2011
1:57:45 PMSpectra Commodities Lis
Strainers, 6" and Larger"
Ph (214) 357‐6181 (214) 351‐0194
ABILINE TX 75229
Limitations: Larger than 6"""
Peerless Manufacturing Fx:
DS:098.000‐1
Ph (716) 662‐6540 (716) 662‐6548
401 US Hwy 281, Wichita Falls TX 76310
Limitations: larger than 6"""
Burgess‐Manning, Inc. Fx:
DS:092.000‐1
John Kennedy Ph (913) 294‐5331 (913) 294‐5337
Paola KS 66071
Limitations: ‐
Taylor Forge Engineered Systems Fx:
DS:127.000‐1
Strainers, Less than 6""
Ph (704) 841‐6000 (704) 841‐6020
Matthews NC 28106
Limitations: ‐
Apollo Ball Valve Division, Conbraco Fx:
DS:005.001‐1
Ph (903) 885‐3151 (903) 439‐3411
1511 Jefferson St., Sulphur Springs TX 75482
Limitations: Less than 6"""
Vogt Valve, Div. of Flowserve Fx:
DS:135.000‐1
Ph (610) 825‐2100 (610) 825‐1235
480 Norristown Rd., Blue Bell PA 19422
Limitations: Less than 6"""
Yarway Corp Fx:
DS:139.000‐1
Ph (713) 6692‐3340 (713) 699‐5186
4920 Airline Drive, Houston TX 77022
Limitations: Less than 6"""
Aitken, Inc. Fx:
DS:149.000‐1
Ph (903) 757‐7341 (903) 759‐6986
White Oak TX 75693
Limitations: less than 6"""
Winston F2S Corporation Fx:
DS:239.000‐2
Ph (910) 865‐8241 (910) 865‐3179
St. Pauls NC 28384
Limitations: less than 6"""
Mueller Steam Specialties Fx:
DS:089.000‐1
Ph (908) 351‐5400 (908) 351‐7893
900 Fairmont Ave., Elizabeth NJ 07207
Limitations: less than 6"""
Hayward Industrial Products Fx:
DS:049.000‐1
Ph (918) 445‐1140 (918) 445‐4617
Sapulpa OK 74066
Limitations: less than 6"""
Weamco, Inc. Fx:
DS:088.000‐1
Page 61 of 61
- 43 -
ATTACHMENT D
Approved Meter Fabricators
The attached listing is provided for reference.
Spectra» Energy
Manufacturer
Daniel Measurement
Northstar Industries
Pickett Measurement
Pipeline Equipment, Inc.
Sagebrush
SICK Maihak, Inc.
* Valtronics, Inc.
*Dresser
*Gas Tech
Page 10f2
Revision: 3 Date: 03-09-2011
Approved Manufacturers Commodity: Fabrication - Meter and Regulator Skids / Meter Tubes
Contact / E-Mail
Bill Buckley [email protected]
Tom Quine [email protected]
Mike Quick [email protected]
Tom Gates [email protected]
Richard Gray [email protected]
Darryl Kahanek [email protected]
Ken Thompson [email protected]
Patty German [email protected]
Paul Hall [email protected]
Phone
713.827.5150
978.975.5500
281.825.0512 877 .602.6868 (Toll)
832.698.1690 877.914.4144 (Toll)
281. 723.8585
281.436.5100 877.356.9742 (Toll)
304.273.5356
814.362.9230
281.825.1845 800.685.6579 (Toll)
Approved Location (ONLY specified Shop below)
Houston,
Methuen, MA
Corpus Christi, TX
Tulsa, OK
Tulsa, OK
Houston, TX
Ravenswood, W. VA
Bradford, PA
Tulsa, Ok
Spect~ Energy
Manufacturer
Bi-Con
*Accurate Measurement
*Star Measurement
Approved Manufacturers Commodity: Fabrication - Meter and Regulator Skids / Meter Tubes
Contact / E-Mail
Steve Warner [email protected]
Mike Arceneaux ma [email protected]
Danny Guilliot [email protected]
Phone
740.68S.2S42-Ext. 262
337-369-9222
337.233.1211
Approved Location (ONLY specified Shop below)
Derwent,OH
Broussard, LA
Lafayette, LA
*Tentatively approved pending final review.
Page 2 of 2