InteliCompact NT 1.1 Operator Guide(2)

Embed Size (px)

Citation preview

  • 8/13/2019 InteliCompact NT 1.1 Operator Guide(2)

    1/13

    InteliCompactNT

    Paralelling gen-set control ler

    SW version 1.1, March 2009

    OPERATOR GUIDE

    Copyright 2008,2009 ComAp s.r.o.

    ComAp, spol. s r.o.Kundratka 17, 180 00 Praha 8, Czech RepublicTel: +420 246 012 111, Fax: +420 266 316 647

    E-mail: [email protected], www.comap.cz

    mailto:[email protected]://www.comap.cz/http://www.comap.cz/mailto:[email protected]
  • 8/13/2019 InteliCompact NT 1.1 Operator Guide(2)

    2/13

    InteliCompact-NT, SW version 1.1, ComAp March 2009 2InteliCompact-NT-1.1 Operator guide.pdf

    Table of contents

    Table of contents ..................................................................................................................................... 2Document information ............................................................................................................................. 3

    Clarification of notation........................................................................................................................ 3Conformity Declaration........................................................................................................................ 3

    Operator guide......................................................................................................................................... 4Front panel elements .......................................................................................................................... 4User interface modes .......................................................................................................................... 6Display screens and pages structure.................................................................................................. 6View measured values ........................................................................................................................ 8Setpoints - view and change ............................................................................................................... 8Browsing the history log ...................................................................................................................... 9Browsing alarms................................................................................................................................ 10Entering the password ...................................................................................................................... 11Controller information screen............................................................................................................ 11Controller language selection............................................................................................................ 12User interface mode selection........................................................................................................... 13Display contrast adjustment .............................................................................................................. 13

  • 8/13/2019 InteliCompact NT 1.1 Operator Guide(2)

    3/13

    InteliCompact-NT, SW version 1.1, ComAp March 2009 3InteliCompact-NT-1.1 Operator guide.pdf

    Document information

    INTELICOMPACT-NT-OPERATOR GUIDE

    WRITTEN BY:JAN TOMANDL2008COMAP LTD.KUNDRATKA 17,PRAHA 8,CZECH REPUBLICPHONE:+420246012111,FAX:+420266316647WEB:HTTP://WWW.COMAP.CZ,E-MAIL:[email protected]

    DOCUMENT HISTORY

    REVISION NUMBER RELATED SW.VERSION DATE

    1 1.0 30.05.2008

    2 1.1 28.02.2009

    Clarification of notation

    NOTE:This type of paragraph calls readers attention to a notice or related theme.

    CAUTION!This type of paragraph highlights a procedure, adjustment etc., which can cause a damage orunproper function of the equipment if not performed correctly and may not be clear at first sight.

    WARNING!This type of paragraph indicates things, procedures, adjustments etc. which need high level of

    attention, otherwise can cause personal injury or death.

    Conformity Declaration

    The following described machine complies with the appropriate basic safety andhealth requirement of the EC Low Voltage Directive No: 73/23 / EEC and ECElectromagnetic Compatibility Directive 89/336 / EEC based on its design and type,as brought into circulation by us.

    http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/
  • 8/13/2019 InteliCompact NT 1.1 Operator Guide(2)

    4/13

  • 8/13/2019 InteliCompact NT 1.1 Operator Guide(2)

    5/13

    InteliCompact-NT, SW version 1.1, ComAp March 2009 5InteliCompact-NT-1.1 Operator guide.pdf

    6

    MODE RIGHTbutton. Use this button to change the mode. The button worksonly if the main screen with the indicator of currently selected mode isdisplayed.NOTE:This button will not work if the controller mode is forced by one of binaryinputs listed in the Reference Guide - Operating modes chapter.

    7

    GCBbutton. Works in MAN and TEST modes only. Press this button to openor close the GCB or start synchronizing manually. Note that certainconditions must be valid otherwise GCB closing resp. starting ofsynchronization is blocked. See the Reference Guide - Connecting to theload chapter for details.

    8

    MCBbutton. Works in MAN and TEST modes only. Press this button to openor close the MCB or start reverse synchronizing manually.CAUTION!You can disconnect the load from the mains supply with this button! Be sureyou know well what you are about to do!

    GEN-SET OPERATION INDICATORS

    POSITION DESCRIPTION

    9General alarm. This red indicator lits if at least one alarm is present in the alarm list. Itblinks if a new alarm has appeared and is still not acknowledged.

    10

    Gen-set vo ltage OK. This green indicator lits if the generator voltage and frequency isin limits.NOTE:The limits for the generator voltage and frequency are given by setpoints in the GenerProtect group.

    11GCB position. This green indicator blinks if the forward sychronizing is currently inprogress, otherwise it shows current status of the generator circuit breaker accordingto the feedback input.

    12 Bus under voltage. This green indicator shows if the bus is under voltage or not.

    13MCB posit ion. This green indicator blinks if the reverse sychronizing is currently inprogress, otherwise it shows current status of the mains circuit breaker according tothe feedback input.

    14Mains voltage OK. This green indicator lits if the mains is evaluated as healthy. Seethe Reference guide - AMF function chapter for details about mains evaluation.

    15Mains failure. This red indicator starts blinking when the mains failure is detected andafter the gen-set has started and is about to take the load it lights permanently until themains failure disappears.

    DISPLAY AND DISPLAY CONTROL BUTTONS

    POSITION DESCRIPTION

    16 Graphic B/W display, 128x64 pixels

    17PAGEbutton. Use this button to switch over display pages. See next chapterfor details about display pages and screens structure

  • 8/13/2019 InteliCompact NT 1.1 Operator Guide(2)

    6/13

    InteliCompact-NT, SW version 1.1, ComAp March 2009 6InteliCompact-NT-1.1 Operator guide.pdf

    18 UPbutton. Use this button to move up or increase value.

    19 DOWNbutton. Use this button to move down or decrease value.

    20ENTERbutton. Use this button to finish editing a setpoint or moving right inthe history page.

    User interface modes

    There are two modes of the user interface:

    User modeallows the user to go through all screens with measurements and alarms. The

    button does not work, i.e. setpoints and history pages are not accesible.

    Engineer modegives the qualified person full access to all pages and screens.

    See the chapter User interface mode selection to learn how to switch the user interface mode.

    Display screens and pages structure

    The displayed information is structured into "pages" and "screens". Use PAGE button to switch overthe pages.

    1. The page Measurementconsists of screens which display measured values like voltages,current, oil pressure etc., computed values like i.e. gen-set power, statistic data and the alarmlist on the last screen.

    2. The page Setpointscontains all setpoints organized to groups and also a special group forentering password.

    3. The page History logshows the history log in the order that the last record is displayed first.

    NOTE:The picture below shows the structure of displayed data. The contents of each particular screen may

    be slightly different according to the firmware branch and version.

  • 8/13/2019 InteliCompact NT 1.1 Operator Guide(2)

    7/13

    InteliCompact-NT, SW version 1.1, ComAp March 2009 7InteliCompact-NT-1.1 Operator guide.pdf

    STRUCTURE OF THE DISPLAYED DATA

  • 8/13/2019 InteliCompact NT 1.1 Operator Guide(2)

    8/13

    InteliCompact-NT, SW version 1.1, ComAp March 2009 8InteliCompact-NT-1.1 Operator guide.pdf

    View measured values

    Press button repeatedly until you see the main screen with the kW meter and mode selector.

    Then press or to select requested screen within the measurement page.

    THE MAIN SCREEN

    Setpoints - view and change

    1. Press button repeatedly until you see a screen with a list of setpoint groups. Then

    select desired group by pressing the or buttons and finally pressbutton to continue into the selected group.

    2. Now you will see the list of setpoints which belong to the selected group together with their

    current setting. Use the or buttons again to select the setpoint you want to

    modify and press .3. The current value of the setpoint will appear in the right part under the setpoint name and you

    can change it by pressing or buttons. The rate of changing the value willaccelerate when the button is held down

    4. Press button to confirm the change or to discard it and return to the list ofsetpoints of the selected group.

    5. Continue with change of another setpoint or press to return to the list of groups.

    LIST OF GROUPS OF SETPOINTS

  • 8/13/2019 InteliCompact NT 1.1 Operator Guide(2)

    9/13

    InteliCompact-NT, SW version 1.1, ComAp March 2009 9InteliCompact-NT-1.1 Operator guide.pdf

    LIST OF SETPOINTS WITHIN SELECTED GROUP

    EDITING A SETPOINT

    Browsing the history log

    1. Press button repeatedly until you see the main history log screen with the reasoncolumn and the latest record.

    NOTE:

    The records are numbered in reverse order, i.e. the latest (newest) record is "0" and olderrecords have "-1", "-2" etc.

    2. Use the button to move over columns within the selected record. Pressing itrepeatedly will move cyclically through the columns, i.e. after last column the first one will bedisplayed.

    3. Use buttons and to move over the records.

    4. Press button to select another display page.

  • 8/13/2019 InteliCompact NT 1.1 Operator Guide(2)

    10/13

    InteliCompact-NT, SW version 1.1, ComAp March 2009 10InteliCompact-NT-1.1 Operator guide.pdf

    MAIN HISTORY LOG SCREEN

    NOTE:The first history record after the controller is switched on, programmed or watchdog reset occurscontains diagnostic values instead of operational. Some fields in these records seem to havenonsense values. Do not take these values into account.

    Browsing alarms

    The Alarmlist and ECU Alarmlist are displayed on the last two screens in the measurement page. Ifthe main screen is displayed then the Alarmlist screen will appear automatically always when a newalarm occurs. It can be also displayed manually as described in the chapter View measured values.

    Use the to move over the alarms in the ECU Alarmlist. Details of the selected alarmare displayed in the bottom line.

    Press button to reset alarms.

    Active alarmsare displayed as white text on black background. It means the alarm is stilactive, i.e. the appropriate alarm conditions are still present.

    Inactive alarmsare displayed as black text on white background. It means the alarm is nomore active, i.e. the appropriate alarm conditions are gone.

    Not confirmed alarmsare displayed with an asterisk. It means the alarm is still notacknowledged (confirmed).

    ALARMLIST

    ECUALARMLIST

  • 8/13/2019 InteliCompact NT 1.1 Operator Guide(2)

    11/13

    InteliCompact-NT, SW version 1.1, ComAp March 2009 11InteliCompact-NT-1.1 Operator guide.pdf

    NOTE:The ECU AlarmList is visible only if an ECU is configured.

    Entering the password

    The password must be entered prior adjusting setpoints, that are password-protected. Password islocated in the first group of setpoints and the way how to enter or change password is similar tochange of setpoints as described in the setpoints chapter.

    NOTE:It is possible to change only passwords of the same or lower level than actually entered password!

    NOTE:Lost password?Display the information screen containing the serial number a password decodenumber as described in the chapter below. Write down both numbers and send a request to retrievethe passord to your local distributor containing these two numbers. You can also save and send anarchive instead.

    Controller information screen

    1. Press the button repeatedly until you will see the main controller screen with themode selector and kW analog meter.

    2. Hold down the button and simultaneously press the button to see thecontroller information screen.

    3. The information screen will disappear automatically after 5 secs

    4. Press the button again within 5s to switch to language selection screen.

    5. Press the button again to switch to the user interface mode selection screen. Thisscreen also contains serial number and password decode number.

    6. Next pressing of the button switches back to the information screen.

    7. Press the button to get back to the controller main screen.

  • 8/13/2019 InteliCompact NT 1.1 Operator Guide(2)

    12/13

    InteliCompact-NT, SW version 1.1, ComAp March 2009 12InteliCompact-NT-1.1 Operator guide.pdf

    The information screen contains following information:

    Controller Name Firmware identification string

    Serial number of the controller

    Firmware version, application version

    Application type

    Branch name

    Control ler language selection

    There are two languages available in the controller. Default languages are English and Chinese. Thelanguages can be changed or modified during the configuration in LiteEdit. Please see the LiteEditdocumentation for details.

    To switch the controller language:

    1. Display the information screen as described above.

    2. While the information screen is still displayed, press the button.

    3. Language menu will appear, use or buttons to select the desired language.

    4. Press to confirm the selection.

  • 8/13/2019 InteliCompact NT 1.1 Operator Guide(2)

    13/13

    InteliCompact-NT, SW version 1.1, ComAp March 2009 13InteliCompact-NT-1.1 Operator guide.pdf

    User interface mode selection

    To switch the User interface mode, follow instructions below:

    1. Display the information screen as described above.

    2. While the information screen is still displayed, press the button twice.

    3. User interface mode menu will appear, use or buttons to select the desiredmode.

    4. Press to confirm the selection.

    Display contrast adjustment

    1. Press the button repeatedly until you will see the main controller screen with themode selector and kW analog meter.

    2. Hold down the button and simultaneously press button or repeatedly

    to increase or decrease the contrast