Integrating Siemens Drive into Rockwell Automations Studio 5000 by using Speed Control Telegrams

Application Manual Studio 5000 Telegrams 1, 2, 3, 4, 20, 350, 352 Speed Control

https://support.industry.siemens.com/cs/ww/en/view/82843076

Siemens Industry Online Support

Page 2: Integrating Siemens Drive into Rockwell Automations Studio

Legal information

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 2

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Legal information Use of application examples

Application examples illustrate the solution of automation tasks through an interaction of several components in the form of text, graphics and/or software modules. The application examples are a free service by Siemens AG and/or a subsidiary of Siemens AG (“Siemens”). They are non-binding and make no claim to completeness or functionality regarding configuration and equipment. The application examples merely offer help with typical tasks; they do not constitute customer-specific solutions. You yourself are responsible for the proper and safe operation of the products in accordance with applicable regulations and must also check the function of the respective application example and customize it for your system. Siemens grants you the non-exclusive, non-sublicensable and non-transferable right to have the application examples used by technically trained personnel. Any change to the application examples is your responsibility. Sharing the application examples with third parties or copying the application examples or excerpts thereof is permitted only in combination with your own products. The application examples are not required to undergo the customary tests and quality inspections of a chargeable product; they may have functional and performance defects as well as errors. It is your responsibility to use them in such a manner that any malfunctions that may occur do not result in property damage or injury to persons.

Disclaimer of liability Siemens shall not assume any liability, for any legal reason whatsoever, including, without limitation, liability for the usability, availability, completeness and freedom from defects of the application examples as well as for related information, configuration and performance data and any damage caused thereby. This shall not apply in cases of mandatory liability, for example under the German Product Liability Act, or in cases of intent, gross negligence, or culpable loss of life, bodily injury or damage to health, non-compliance with a guarantee, fraudulent non-disclosure of a defect, or culpable breach of material contractual obligations. Claims for damages arising from a breach of material contractual obligations shall however be limited to the foreseeable damage typical of the type of agreement, unless liability arises from intent or gross negligence or is based on loss of life, bodily injury or damage to health. The foregoing provisions do not imply any change in the burden of proof to your detriment. You shall indemnify Siemens against existing or future claims of third parties in this connection except where Siemens is mandatorily liable. By using the application examples you acknowledge that Siemens cannot be held liable for any damage beyond the liability provisions described.

Other information Siemens reserves the right to make changes to the application examples at any time without notice. In case of discrepancies between the suggestions in the application examples and other Siemens publications such as catalogs, the content of the other documentation shall have precedence. The Siemens terms of use (https://support.industry.siemens.com) shall also apply.

Security information Siemens provides products and solutions with industrial security functions that support the secure operation of plants, systems, machines and networks. In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens’ products and solutions constitute one element of such a concept. Customers are responsible for preventing unauthorized access to their plants, systems, machines and networks. Such systems, machines and components should only be connected to an enterprise network or the Internet if and to the extent such a connection is necessary and only when appropriate security measures (e.g. firewalls and/or network segmentation) are in place. For additional information on industrial security measures that may be implemented, please visit https://www.siemens.com/industrialsecurity. Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber threats. To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed at: https://www.siemens.com/industrialsecurity.

Page 3: Integrating Siemens Drive into Rockwell Automations Studio

List of contents

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 3

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

List of contents Legal information ......................................................................................................... 2

1 Overview ............................................................................................................. 4

2 Telegrams ........................................................................................................... 5

3 Reference Scaling Parameters ....................................................................... 17

4 Startdrive Configuration ................................................................................. 18

5 Download to the drive ..................................................................................... 33

6 Motor Identification ......................................................................................... 35

7 Create New Project with Rockwell Software Studio 5000 ........................... 41

8 Rockwell Automation EDS Wizard ................................................................. 46

9 Add a Siemens Drive to the Ethernet Network ............................................. 54

10 Import Add-On Instruction .............................................................................. 58

11 Configure IP Address for a Rockwell Controller .......................................... 60

12 Configure RSLinx Communications for a Rockwell Controller .................. 66

13 Insert a Rung for the Add-On Instruction ...................................................... 70

14 Controlling the Siemens Drive ....................................................................... 75

15 Download Project to the Rockwell Controller .............................................. 78

16 Create a Rockwell’s FactoryTalk View Application ...................................... 80

17 Establish Communications Between the Rockwell Controller and the Rockwell PanelView Plus Terminal ................................................................ 81

18 Import Siemens Global Objects ..................................................................... 84

19 Import Siemens Display .................................................................................. 89

20 Add GOTO Button to a Display ...................................................................... 94

21 Alarms and Warnings ...................................................................................... 99

22 Edit Tags for Alarm Setup............................................................................. 103

23 Test Application ............................................................................................. 105

24 Transfer Utility ............................................................................................... 113

25 Firmware Upgrade Wizard ............................................................................ 117

26 Appendix ........................................................................................................ 122

26.1 Application Support .......................................................................... 122 26.2 Links and Literature .......................................................................... 122 26.3 History .............................................................................................. 122

Page 4: Integrating Siemens Drive into Rockwell Automations Studio

1 Overview

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 4

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

1 Overview

Scope:

This document will explain how to integrate Siemens drives into Rockwell Automations Studio 5000 software. This document will illustrate how to add Electronic Data Sheet (EDS) file, add a Siemens drive to the Ethernet/IP network, import Add-On Instructions, and create a routine for the Add-On instruction to an existing Studio 5000 PLC program. This document will illustrate how to import global objects, displays, alarms, and warnings into a FactoryTalk View Machine Edition HMI application.

This document includes commonly used Siemens telegrams along with additional speed control telegrams for unique applications.

Components Used:

Hardware:

Rockwell Automations CompactLogix 5370 Controller 1769-L16ER-BB1B

Siemens G120 CU250S-2 PN V4.7 SP10

Software:

Rockwell Automations Studio 5000 V30 and FactoryTalk View Studio Machine Edition V10.0

Startdrive V16.1

BootP DHCP Ethernet/IP Commissioning Tool V3.02.00

RSLinx V4.00.00 CPR 9 SR 10.0

Page 5: Integrating Siemens Drive into Rockwell Automations Studio

2 Telegrams

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 5

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

2 Telegrams

What is a Telegram? Telegrams are universal blocks of data that organize parameters and functions into a uniform consistent format that all Siemens drives can use to pass data to the PLC. They are organized into 16-bit process words (abbreviated as PZD) that contain relevant information such as control words, status words, and setpoints. Most telegrams have a control word, status word, speed setpoint, and speed feedback word in common.

A telegram is easily selected within the programming platform by loading the correct electronic data sheet (EDS) file.

Commonly Used Siemens Telegrams for Speed Control:

Telegrams 1 and 352 are the most commonly used telegrams for speed control applications. Siemens recommends that you choose one of these telegrams for speed control applications.

Telegram 1 for Basic Speed Setpoint (16-bit):

This telegram is a standard PROFIdrive telegram of 2 words in length. It will control the state of the drive by selecting the appropriate bits in the control word and set the running speed in the speed setpoint word (16-bit).

Table 2-1 From Drive to PLC

PLC Tagname

Description Data Type

Drive Parameter

DriveStatus0 Status Word 1 (ZSW1) Integer r52

DriveStatus1 Smoothed Actual Speed (NIST_A_GLATT) Integer r63[1]

Page 6: Integrating Siemens Drive into Rockwell Automations Studio

2 Telegrams

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 6

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Table 2-2 From PLC to Drive

PLC Tagname

Description Data Type

Drive Parameter

DriveControl0 Control Word 1 (STW1) Integer r54

DriveControl1 Speed Setpoint (NSOLL_A) Integer p1070[0]

Telegram 352 for Vector Speed Control, Speed Setpoint, and Diagnostics:

Telegram 352 is a standard Siemens telegram of 6 words in length for speed control with VECTOR Drive Objects. This telegram cannot be used with SERVO Drive Objects. This telegram offers four optional User Defined Control Setpoints, and four added status words returning to the PLC for Current, Torque, Warnings, and Faults.

Table 2-3 From Drive to PLC

PLC Tagname

Description Data Type

Drive Parameter

DriveStatus0 Status Word 1 (ZSW1) Integer r52

DriveStatus1 Smoothed Actual Speed (NIST_A_GLATT) Integer r63[1]

DriveStatus2 Smoothed Actual Current (IAIST_GLATT) Integer r68[1]

DriveStatus3 Smoothed Actual Torque (MIST_GLATT) Integer r80[1]

DriveStatus4 Alarm Code - The most recent alarm code is displayed. 0 = No alarm present. (WARN_CODE)

Integer p2132

DriveStatus5 Fault Code - The oldest fault code is displayed. 0 = No fault present. (ALARM_CODE)

Integer p2131

Table 2-4 From PLC to Drive

PLC Tagname Description Data Type

Drive Parameter

DriveControl0 Control Word 1 (STW1) Integer r54

DriveControl1 Speed Setpoint (NSOLL_A) Integer p1070[0]

DriveControl2 User Defined Integer

DriveControl3 User Defined Integer

DriveControl4 User Defined Integer

DriveControl5 User Defined Integer

Additional Siemens Telegrams for Speed Control:

This section has additional telegrams that can be used for speed control applications. If telegrams 1 and 352 are not suitable for your application, the telegrams in this section can be used.

Telegram 2 for Basic Speed Setpoint (32-bit):

This telegram is a standard Siemens telegram of four words in length. It will control the state of the drive by selecting the appropriate bits in the control word and set the running speed in the speed setpoint word (32-bit). This telegram contains a second control and status word.

Table 2-5 From Drive to PLC

PLC Tagname

Description Data Type

Drive Parameter

DriveStatus0 Status Word 1 (ZSW1) Integer r52

Page 7: Integrating Siemens Drive into Rockwell Automations Studio

2 Telegrams

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 7

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

DriveStatus1 Actual Speed (NIST_B) Integer r63[0]

DriveStatus2 Actual Speed (NIST_B) Integer r63[0]

DriveStatus3 Status Word 2 (ZSW2) Integer p2081

Table 2-6 From PLC to Drive

PLC Tagname

Description Data Type

Drive Parameter

DriveControl0 Control Word 1 (STW1) Integer r54

DriveControl1 Speed Setpoint (NSOLL_B) Integer p1070[0]

DriveControl2 Speed Setpoint (NSOLL_B) Integer p1070[0]

DriveControl3 Control Word 2 (STW2) Integer r2093

Telegram 3 for Speed Setpoint (32-bit) with Position Encoder:

This telegram is a Siemens telegram of 9 words in length. It will control the state of the drive by selecting the appropriate bits in the two control words and set the running speed in the speed setpoint word. The control word, status word, and position feedback of the encoder is also included. Telegram 3 is not suitable for sensorless vector control.

Table 2-7 From Drive to PLC

PLC Tagname

Description Data Type

Drive Parameter

DriveStatus0 Status Word 1 (ZSW1) Integer r2089[0]

DriveStatus1 Actual Speed Value (NIST_B) Integer r63[0]

DriveStatus2 Actual Speed Value (NIST_B) Integer r63[0]

DriveStatus3 Status Word 2 (ZSW2) Integer r2089[1]

DriveStatus4 Encoder Status Word (G1_ZSW) Integer r481[0]

DriveStatus5 Encoder 1 Actual Position 1 (G1_XIST1) Integer r482[0]

DriveStatus6 Encoder 1 Actual Position 1 (G1_XIST1) Integer r482[0]

DriveStatus7 Encoder 1 Actual Position 2 (G1_XIST2) Integer r483[0]

DriveStatus8 Encoder 1 Actual Position 2 (G1_XIST2) Integer r483[0]

Table 2-8 From PLC to Drive

PLC Tagname

Description Data Type

Drive Parameter

DriveControl0 Control Word 1 (STW1) Integer r54

DriveControl0 Main Setpoint (NSOLL_B) Integer p1070[0]

DriveControl2 Main Setpoint (NSOLL_B) Integer p1070[0]

DriveControl3 Control Word 2 (STW2) Integer p2045

DriveControl4 Encoder 1 Control Word (G1_STW) Integer p480[0]

Telegram 4 for Speed Setpoint (32-bit) with Two Position Encoders:

This telegram is a standard Siemens telegram of 14 words in length. It will control the state of the drive by selecting the appropriate bits in the two control words and set the running speed in the speed setpoint word. The control words, status words, and position feedback of two encoders are also included. Telegram 4 is not suitable for sensorless vector control.

Page 8: Integrating Siemens Drive into Rockwell Automations Studio

2 Telegrams

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 8

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Table 2-9 From Drive to PLC

PLC Tagname Description Data Type

Drive Parameter

DriveStatus0 Status Word 1 (ZSW1) Integer r2089[0]

DriveStatus1 Actual Speed Value (NIST_B) Integer r63[0]

DriveStatus2 Actual Speed Value (NIST_B) Integer r63[0]

DriveStatus3 Status Word 2 (ZSW2) Integer r2089[1]

DriveStatus4 Encoder Status Word (G1_ZSW) Integer r481[0]

DriveStatus5 Encoder 1 Actual Position 1 (G1_XIST1) Integer r482[0]

DriveStatus6 Encoder 1 Actual Position 1 (G1_XIST1) Integer r482[0]

DriveStatus7 Encoder 1 Actual Position 2 (G1_XIST2) Integer r483[0]

DriveStatus8 Encoder 1 Actual Position 2 (G1_XIST2) Integer r483[0]

DriveStatus9 Encoder 2 Status Word (G2_ZSW) Integer r481[1]

DriveStatus10 Encoder 2 Actual Position 1 (G2_XIST1) Integer r482[1]

DriveStatus11 Encoder 2 Actual Position 1 (G2_XIST1) Integer r482[1]

DriveStatus12 Encoder 2 Actual Position 2 (G2_XIST2) Integer r483[1]

DriveStatus13 Encoder 2 Actual Position 2 (G2_XIST2) Integer r483[1]

Table 2-10 From PLC to Drive

PLC Tagname

Description Data Type

Drive Parameter

DriveControl0 Control Word 1 (STW1) Integer

DriveControl1 Main Setpoint (NSOLL_B) Integer p1070[0]

DriveControl2 Main Setpoint (NSOLL_B) Integer p1070[0]

DriveControl3 Control Word 2 (STW2) Integer p2045

DriveControl4 Encoder 1 Control Word (G1_STW) Integer p480[0]

DriveControl5 Encoder 2 Control Word (G2_STW) Integer p480[1]

Telegram 20 for Speed Setpoint (16-bit) for VIK-NAMUR:

This telegram is a standard PROFIdrive telegram of 6 words in length. It will control the state of the drive by selecting the appropriate bits in the control word and set the running speed in the speed setpoint word. Additionally, this telegram can send current, torque, and power feedback.

Table 2-11 From Drive to PLC

PLC Tagname

Description Data Type

Drive Parameter

DriveStatus0 Status Word 1 (ZSW1) Integer r52

DriveStatus1 Smoothed Actual Speed (NIST_A_GLATT) Integer r63[1]

DriveStatus2 Smoothed Actual Current (IAIST_GLATT) Integer r68[1]

DriveStatus3 Smoothed Actual Torque (MIST_GLATT) Integer r80[1]

DriveStatus4 Smoothed Actual Power (PIST_GLATT) Integer r82[1]

DriveStatus5 MELD_NAMUR Namur Message Bit Bar Integer p3113

Page 9: Integrating Siemens Drive into Rockwell Automations Studio

2 Telegrams

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 9

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Table 2-12 From PLC to Drive

PLC Tagname

Description Data Type

Drive Parameter

DriveControl0 Control Word 1 (STW1) Integer r54

DriveControl1 Speed Setpoint (NSOLL_A) Integer p1070[0]

Telegram 350 for Speed Setpoint (16-bit), Speed Feedback, Current Feedback, and Torque Limit:

This telegram is a standard Siemens telegram of 4 words in length. The drive is controlled through two control words and a speed setpoint. In the output image, speed and current feedback are available. Scaling of the upper torque limit to limit the speed controller output can be controlled in the input image.

Table 2-13 From Drive to PLC

PLC Tagname

Description Data Type

Drive Parameter

DriveStatus0 Status Word 1 (ZSW1) Integer r2089[0]

DriveStatus1 Actual Speed Value (FIST_GLATT) Integer r63[1]

DriveStatus2 Absolute Current Actual Value (IAIST_GLATT) Integer r68[1]

DriveStatus3 Status Word 2 (ZSW3) Integer r53

Table 2-14 From PLC to Drive

PLC Tagname Description Data Type

Drive Parameter

DriveControl0 Control Word 1 (STW1) Integer

DriveControl1 Main Setpoint (FSOLL) Integer p1070[0]

DriveControl2 Torque Limit Upper Scaling Without Offset (M_LIM) Integer p1552[0]

DriveControl3 Control Word 3 (STW3) Integer

Data from the Drive to the PLC – Drive Status Word Individual Bits:

Table 2-15 Status Word 1 (ZSW1)

Bit Name Functionality Data Type

Drive Parameter

0

Ready to Power On

1 = Drive ready

0 = Drive not ready

Bool r0899.0

1

Ready to Run

1 = Ready to run

0 = Not ready to run

Bool r0899.1

2

Drive Running

1 = Motor enabled

0 = Motor not enabled

Bool r0899.2

3

Fault Present

1 = Converter fault

0 = No fault active

Bool r2139.3

4

Coast Stop

0 = Coast down (OFF2) inactive

1 = Coast down active

Bool r0899.4

5

Quick Stop

0 = Quick stop (OFF3) inactive

1 = Quick stop active

Bool r0899.5

Page 10: Integrating Siemens Drive into Rockwell Automations Studio

2 Telegrams

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 10

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

6

Switch On Inhibited

1 = Motor inhibited from switching on

0 = Motor can be switched on

Bool r0899.6

7

Warning Present

1 = Warning present

0 = No warning present

Bool r2139.7

8

Motor at Acceptable Speed

1 = Speed deviation within tolerance

0 = Speed deviation outside tolerance

Bool r2197.7

9

PLC Has Control

1 = Master control requested

0 = No action

Bool r0899.9

10

Speed Comparison Reached

1 = Speed greater than or equal to max speed

0 = Speed less than max speed

Bool r2199.1

11

Torque Limit Reached

1 = Torque limit reached

0 = Torque limit not reached

Bool r0052.11

12

Holding Brake Open

1 = Holding brake open

0 = Holding brake closed

Bool r0899.12

13

Motor Overload

0 = No overtemperature alarm

1 = Overtemperature alarm present

Bool r2135.14

14

Reverse Direction

1 = Motor rotates clockwise

0 = Motor rotates counterclockwise

Bool r2197.3

15

Drive Overload

0 = No converter thermal overload alarm

1 = Thermal overload alarm present

Bool r2135.15

Table 2-16 Status Word 2 (ZSW2)

Bit Name Functionality Data Type

Drive Parameter

0 Drive data set selection (DDS) Bit 0

Bits 0-4 display the selected drive data set.

Bool

Bool

r0051.0

1 Drive data set selection (DDS) Bit 1 r0051.1

2 Drive data set selection (DDS) Bit 2

3 Drive data set selection (DDS) Bit 3

4 Drive data set selection (DDS) Bit 4

5

Alarm Class Bit 0

Bits 5-6 are used for the classification of internal alarm classes and are intended for diagnostic purposes only.

Bool r2139.11

6 Alarm Class Bit 1 1 = On; 0 = Off Bool r2139.12

7

Parking Axis Function Status

1 = Parking axis function active

0 = Parking axis function inactive

Bool

8

Travel to Fixed Stop Status

1 = Travel to fixed end stop function active

0 = Travel to fixed end stop inactive

Bool

r1406.8

9 Reserved

10 Pulse Status 1 = Pulses enabled; 0 = Pulses inhibited Bool r0899.11

11

Motor Data Set Changeover Status

1 = Motor data set changeover active

0 = Motor data set changeover inactive

Bool

r0835.0

12 Slave sign-of-life Bit 0 Bool

13 Slave sign-of-life Bit 1 Bool

14 Slave sign-of-life Bit 2 Bool

15 Slave sign-of-life Bit 3 Bool

Page 11: Integrating Siemens Drive into Rockwell Automations Studio

2 Telegrams

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 11

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Table 2-17 Status Word 3 (ZSW3)

Bit Name Functionality Data Type

Drive Parameter

0

DC Brake Status

1 = DC braking active

0 = DC braking inactive

Bool

r0053.0

1

Speed Above Stationary Speed

1 = Absolute speed is greater than "stationary" speed (p1226)

0 = Speed less than stationary speed

Bool

r0053.1

2

Speed Above Minimum Speed

1 = Absolute speed is greater than minimum speed (p1080)

0 = Speed less than minimum speed

Bool

r0053.2

3

Current Above Threshold Value

1 = Current greater than or equal to threshold value (p2170)

0 = Current less than threshold value

Bool

r0053.4

4

Speed Above Threshold 2

1 = Absolute speed greater than speed threshold value 2 (p2155)

0 = Speed less than threshold 2

Bool

r0053.4

5

Speed Below Threshold 2

1 = Absolute speed less than or equal to speed threshold value 2

0 = Speed greater than threshold 2

Bool

r0053.5

6

Speed Setpoint Reached

1 = Absolute speed greater than or equal to setpoint (r1119)

0 = Speed less than setpoint

Bool

r0053.6

7

DC Link Voltage Below Threshold

1 = DC link voltage at or below threshold value (p2172)

0 = DC link voltage below threshold value

Bool

r0053.7

8

DC Link Voltage Above Threshold

1 = DC link voltage above threshold value

0 = DC link voltage below threshold value

Bool

r0053.8

9

Ramp Function Generator Status

1 = Ramp up or ramp down completed (RFG inactive)

0 = Ramp up or ramp down incomplete

Bool

r0053.9

10

Technology Controller Lower Limit

1 = Tech controller output at or below lower limit (p2292)

0 = Output above lower limit

Bool

r0053.10

11

Technology Controller Upper Limit

1 = Tech controller output above upper limit (p2291)

0 = Output below or at upper limit

Bool

r0053.11

12 Reserved

13 Reserved

14 Reserved

15 Reserved

Table 2-18 Encoder 1 Status Word (G1_ZSW)

Bit Name Functionality Data Type

Drive Parameter

Encoder

Control Word

Bit 7 = 0

Encoder

Control Word

Bit 7 = 1

0

Function 1 Status Search for reference cam 1 active

Flying referencing to rising edge of reference cam 1 active

Bool

r2051[4]

1 Function 2 Status

Search for reference cam 1 active

Flying referencing to falling edge of

Bool r2051[4]

Page 12: Integrating Siemens Drive into Rockwell Automations Studio

2 Telegrams

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 12

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Bit Name Functionality Data Type

Drive Parameter

reference cam 1 active

2

Function 3 Status Search for reference cam 2 active

Flying referencing to rising edge of reference cam 2 active

Bool

r2051[4]

3

Function 4 Status Search for reference cam 2 active

Flying referencing to falling edge of reference cam 2 active

Bool

r2051[4]

4

Status Value 1

Actual position at reference cam 1

Flying referencing to rising edge of reference cam 1 complete

Bool

r2051[4]

5

Status Value 2

Actual position at reference cam 1

Flying referencing to falling edge of reference cam 1 complete

Bool

r2051[4]

6

Status Value 3

Actual position at reference cam 2

Flying referencing to rising edge of reference cam 2 complete

Bool

r2051[4]

7

Status Value 4

Actual position at reference cam 2

Flying referencing to falling edge of reference cam 2 complete

Bool

r2051[4]

8 Measuring Probe 1 Deflection Status

1 = Measuring probe 1 deflected

0 = Measuring probe 1 not deflected

Bool

r2051[4]

9 Measuring Probe 2 Deflection Status

1 = Measuring probe 2 deflected

0 = Measuring probe 2 not deflected

Bool

r2051[4]

10

Encoder 1 Status

1 = Encoder 1 on

0 = Encoder 1 off

Bool

r2051[4]

11 Acknowledge 1 = Acknowledge encoder fault is active Bool r2051[4]

12

Encoder 1 Status

1 = Encoder 1 on

0 = Encoder 1 off

Bool

r2051[4]

13

Cyclic Absolute Value Status

1 = Actual position displayed in r0483

0 = No value displayed

r0483[0] displays the encoder position value

r0483[1] displays the encoder fault number if a fault is present.

Bool

r2051[4]

14

Parking Status

1 = Encoder is parked

0 = Encoder is not parked

Bool

r2051[4]

15

Fault Status

1 = Encoder indicates its fault type in r0483

0 = No fault

Bool

r2051[4]

Table 2-19 Encoder 2 Status Word (G2_ZSW)

Bit Name Functionality Data Type

Drive Parameter

Encoder

Control Word

Bit 7 = 0

Encoder

Control Word

Bit 7 = 1

0

Function 1 Status Search for reference cam 1 active

Flying referencing to rising edge of reference cam 1 active

Bool

r2051[4]

Page 13: Integrating Siemens Drive into Rockwell Automations Studio

2 Telegrams

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 13

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Bit Name Functionality Data Type

Drive Parameter

1

Function 2 Status Search for reference cam 1 active

Flying referencing to falling edge of reference cam 1 active

Bool

r2051[4]

2

Function 3 Status Search for reference cam 2 active

Flying referencing to rising edge of reference cam 2 active

Bool

r2051[4]

3

Function 4 Status Search for reference cam 2 active

Flying referencing to falling edge of reference cam 2 active

Bool

r2051[4]

4

Status Value 1

Actual position at reference cam 1

Flying referencing to rising edge of reference cam 1 complete

Bool

r2051[4]

5

Status Value 2

Actual position at reference cam 1

Flying referencing to falling edge of reference cam 1 complete

Bool

r2051[4]

6

Status Value 3

Actual position at reference cam 2

Flying referencing to rising edge of reference cam 2 complete

Bool

r2051[4]

7

Status Value 4

Actual position at reference cam 2

Flying referencing to falling edge of reference cam 2 complete

Bool

r2051[4]

8 Measuring Probe 1 Deflection Status

1 = Measuring probe 1 deflected

0 = Measuring probe 1 not deflected

Bool

r2051[4]

9 Measuring Probe 2 Deflection Status

1 = Measuring probe 2 deflected

0 = Measuring probe 2 not deflected

Bool

r2051[4]

10

Encoder 1 Status

1 = Encoder 1 on

0 = Encoder 1 off

Bool

r2051[4]

11 Acknowledge 1 = Acknowledge encoder fault is active Bool r2051[4]

12

Encoder 1 Status

1 = Encoder 1 on

0 = Encoder 1 off

Bool

r2051[4]

13

Cyclic Absolute Value Status

1 = Actual position displayed in r0483

0 = No value displayed

r0483[0] displays the encoder position value

r0483[1] displays the encoder fault number if a fault is present.

Bool

r2051[4]

14

Parking Status

1 = Encoder is parked

0 = Encoder is not parked

Bool

r2051[4]

15

Fault Status

1 = Encoder indicates its fault type in r0483

0 = No fault

Bool

r2051[4]

Data from the PLC to the Drive – Drive Control Word Individual Bits:

Page 14: Integrating Siemens Drive into Rockwell Automations Studio

2 Telegrams

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 14

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Table 2-20 Control Word 1 (STW1)

Bit Name Functionality Data Type

Drive Parameter

0

Run Command

1 = Enable drive

0 = Ramp down and disable drive

Bool p0840[0]

1

Coast Stop

0 = No stop command issued

1 = Immediate disable and coast to stop

Bool p0844[0]

2

Quick Stop

0 = No stop command issued

1 = Immediate disable and quick stop

Bool p0848[0]

3

Enable Operation

1 = Enable drive (pulses enabled)

0 = Inverter prohibited from generating pulses

Bool p0852[0]

4

RFG Enable

1 = Ramp function generator output enabled

0 = Ramp function generator output set to 0

Bool p1140[0]

5

RFG Freeze

1 = Ramp function generator follows setpoint input

0 = Ramp function generator freezes at current value

Bool p1141[0]

6

Setpoint Enable

1 = Ramp function generator setpoint input enabled

0 = Ramp function generator input set to 0

Bool p1142[0]

7 Fault Acknowledge 1 = Acknowledge faults (on rising edge) Bool p2103[0]

8 Reserved

9 Reserved

10

PLC Control

1 = Control is by PLC

0 = No control by PLC

Bool p0854[0]

11

Reverse Direction

1 = Reverse Rotation

0 = Forward Rotation

Bool p1113[0]

12 Reserved

13

MOP Raise Setpoint

1 = Raise Motorized potentiometer setpoint

0 = No action

Bool p1035[0]

14

MOP Lower Setpoint

1 = Lower Motorized potentiometer setpoint

0 = No action

Bool p1036[0]

15 Reserved

Table 2-21 Control Word 2 (STW2)

Bit Name Functionality Data Type

Drive Parameter

0 Drive data set selection (DDS) Bit 0 1 = On; 0 = Off Bool p0820[0]

1 Drive data set selection (DDS) Bit 1 1 = On; 0 = Off Bool p0821[0]

2 Drive data set selection (DDS) Bit 2

3 Drive data set selection (DDS) Bit 3

4 Drive data set selection (DDS) Bit 4

5 Reserved

6 Reserved

7

Parking Axis Selection

1 = Parking axis function active

0 = Parking axis function inactive

Bool p0897

8

Traverse to Fixed End Stop

1 = Travel to fixed end stop function active

0 = Travel to fixed end stop inactive

This bit is only available for the S120 and is not available for vector U/f control

Bool p1545[0]

9 Reserved

10 Reserved

Page 15: Integrating Siemens Drive into Rockwell Automations Studio

2 Telegrams

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 15

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

11 Motor Changeover Feedback Signal

12 Master sign-of-life Bit 0

13 Master sign-of-life Bit 1

14 Master sign-of-life Bit 2

15 Master sign-of-life Bit 3

Table 2-22 Control Word 3 (STW3)

Bit Name Functionality Data Type

Drive Parameter

0 Fixed Setpoint Selector Bit 0 Bits 0-3 are used to select between 16 different fixed setpoints.

Bool p1020[0]

1 Fixed Setpoint Selector Bit 1 Bool p1021[0]

2 Fixed Setpoint Selector Bit 2 Bool p1022[0]

3 Fixed Setpoint Selector Bit 3 Bool p1023[0]

4 Drive data set selection (DDS) Bit 0 Bits 4-5 are used to select a drive data set.

Bool p0820

5 Drive data set selection (DDS) Bit 1 Bool p0821

6 Reserved

7 Reserved

8

Technology Controller Enable

1 = Technology Controller Enabled

0 = Technology Controller Disable

Bool

p2200[0]

9

DC Braking Enable

1 = Enable DC braking

0 = DC braking disabled

Bool

p1230[0]

10 Reserved

11

Droop Feedback Enable

1 = Speed controller droop enable

0 = Speed controller droop disable

Bool

p1492[0]

12

Vector Control Mode

1 = Torque control active

0 = Speed control active

Bool

p1501[0]

13

External Fault Status

1 = No external fault

0 = External fault present

Bool

p2106[0]

14 Reserved

15 Command Data Set Selection Bit 0 Bool p0811[0]

Table 2-23 Encoder 1 Control Word (G1_STW)

Bit Name Functionality Data Type

Drive Parameter

If bit 7 = 0 If bit 7 = 1

0

Request Function 1

Search for reference cam 1 with positive start direction

Request flying referencing to the rising edge of reference cam 1

Bool

r2050[4]

1

Request Function 2

Search for reference cam 1 with negative start direction

Request flying referencing to the falling edge of reference cam 1

Bool

r2050[4]

2

Request Function 3

Search for reference cam 2 with positive start direction

Request flying referencing to the rising edge of reference cam 2

Bool

r2050[4]

3

Request Function 4

Search for reference cam 2 with negative start direction

Request flying referencing to the falling edge of reference cam 2

Bool

r2050[4]

4 Request Command Bit 0 1 = Activate the function requested using bits 0…3 Bool r2050[4]

5 Request Command Bit 1 1 = Read the value requested using bits 0…3 Bool r2050[4]

Page 16: Integrating Siemens Drive into Rockwell Automations Studio

2 Telegrams

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 16

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Bit Name Functionality Data Type

Drive Parameter

6 Request Command Bit 2 Reserved Bool r2050[4]

7

Function Mode Selection

1 = Flying measurement function set

0 = Reference cam search function set

Bool

r2050[4]

8 Reserved

9 Reserved

10 Reserved

11 Reserved

12 Reserved

13 Request Absolute Value Cyclic

1 = Request for cyclic transfer of actual position value of encoder 1

Bool r2050[4]

14 Request Parking Encoder 1 = Request to park the encoder Bool r2050[4]

15 Request Acknowledge Encoder Fault 1 = Acknowledge encoder fault (on rising edge)

Bool r2050[4]

Table 2-24 Encoder 2 Control Word (G2_STW)

Bit Name Functionality Data Type

Drive Parameter

If bit 7 = 0 If bit 7 = 1

0

Request Function 1

Search for reference cam 1 with positive start direction

Request flying referencing to the rising edge of reference cam 1

Bool

r2050[4]

1

Request Function 2

Search for reference cam 1 with negative start direction

Request flying referencing to the falling edge of reference cam 1

Bool

r2050[4]

2

Request Function 3

Search for reference cam 2 with positive start direction

Request flying referencing to the rising edge of reference cam 2

Bool

r2050[4]

3

Request Function 4

Search for reference cam 2 with negative start direction

Request flying referencing to the falling edge of reference cam 2

Bool

r2050[4]

4 Request Command Bit 0 1 = Activate the function requested using bits 0…3 Bool r2050[4]

5 Request Command Bit 1 1 = Read the value requested using bits 0…3 Bool r2050[4]

6 Request Command Bit 2 Reserved Bool r2050[4]

7

Function Mode Selection

1 = Flying measurement function set

0 = Reference cam search function set

Bool

r2050[4]

8 Reserved

9 Reserved

10 Reserved

11 Reserved

12 Reserved

13 Request Absolute Value Cyclic

1 = Request for cyclic transfer of actual position value of encoder 1

Bool r2050[4]

14 Request Parking Encoder 1 = Request to park the encoder Bool r2050[4]

15 Request Acknowledge Encoder Fault 1 = Acknowledge encoder fault (on rising edge)

Bool r2050[4]

Page 17: Integrating Siemens Drive into Rockwell Automations Studio

3 Reference Scaling Parameters

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 17

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

3 Reference Scaling Parameters

Certain data words are normalized internally by the drive using the following parameters. Commanded values use the scale that is set by these parameters. For example, if the desired 100% command to motor speed is 2000 rpm, then p2000 should be set to 2000. A command of 1500 rpm would be treated as 75%.

Table 3-1 Reference Scaling Parameters

Parameter Name [Data Type] Functionality

p2000 Reference Speed, Velocity, or Frequency [FloatingPoint32]

The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of speed, velocity, or frequency. Factory default values: 120.00 m/min (velocity), 3000.00 rpm (speed), 50.00 Hz (frequency)

p2001 Reference Voltage [FloatingPoint32]

The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of voltage. Factory default value: 1000 V

p2002 Reference Current or Pressure [FloatingPoint32]

The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of current or pressure. Factory default values: 100.00 Arms (current), 100.00 bar (pressure)

p2003 Reference Force or Torque [FloatingPoint32]

The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of force or torque. Factory default values: 100.00 N (force), 1.00 Nm (torque)

p2004 Reference Power [FloatingPoint32]

The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of power. Its factory default is calculated from p2003 * p2000 (torque * speed) or p2003 * p2000 (force * linear speed).

p2005 Reference Angle [FloatingPoint32]

The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of ref. angle. Factory default values: 90.00 degrees

p2006 Reference Temperature [FloatingPoint32]

The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of temperature. Factory default values: 100.00 degrees C

p2007 Reference Acceleration [FloatingPoint32]

The value of this parameter corresponds to 100% or 4000 hex (16b) or 4000000 hex (32b) of rotational acceleration. Factory default values: 0.01 revolutions/sec^2

Page 18: Integrating Siemens Drive into Rockwell Automations Studio

4 Startdrive Configuration

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 18

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

4 Startdrive Configuration

Create a New Project: Launch TIA Portal or Startdrive. For this example, TIA Portal is being used. Create New Project. Assign Project Name. Select Path. Click Create.

Click Open the project view.

Online Access: Click the Accessible devices from the toolbar.

Type of the PG/PC interface: Select the appropriate interface for your application from the pulldown. For this example, PN/IE will be used.

PG/PC interface: Select the appropriate interface for the application from the pulldown. For this example, Intel® I210 Gigabit Network Connection will be used.

Select the appropriate drive. Click Start search. Click Show.

Page 19: Integrating Siemens Drive into Rockwell Automations Studio

4 Startdrive Configuration

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 19

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

The result will be displayed.

Assign IP address: Double click Online & Diagnostics. Expand Functions. Click Assign IP address. Enter IP address. Enter Subnet mask. Click Assign IP address.

Page 20: Integrating Siemens Drive into Rockwell Automations Studio

4 Startdrive Configuration

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 20

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Upload device as new station: Right click the desired drive. Click Upload device as new station.

An image of the result is below.

Page 21: Integrating Siemens Drive into Rockwell Automations Studio

4 Startdrive Configuration

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 21

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Commission the Drive: Expand the desired drive from the Project tree. Double click Commissioning. Click Commissioning Wizard.

Application class:

You can set the application class in the wizard function in the configuration. Select one of the following classes:

Standard Drive Control: The same performance such as U/f with FCC and slip compensation / speed accuracy is only restricted. There is therefore no speed controller and no torque

Page 22: Integrating Siemens Drive into Rockwell Automations Studio

4 Startdrive Configuration

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 22

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

accuracy. Two rating plate parameters are required for the motor commissioning: Rated current and rated speed. The synchronous rated speed is accepted. The motor data identification is preset. A short measurement is performed once (only stator resistance, dead time compensation) to improve the start-up. This is followed by a direct switchover to operation. The optimization of the speed controller is not relevant. Dynamic Drive Control: Compared to Standard Drive Control, the performance such as sensorless vector control / speed accuracy is significantly improved. The robustness is improved with higher model change limits but takes effect at slow reversing. Three rating plate parameters are required for the motor commissioning: Rated current, rated power and rated speed. The motor data identification is preset and serves to simplify and shorten the measurement compared with the existing standstill measurement. This is followed by a direct switchover to operation. In the speed controller optimization, there is a shorter measurement of the moment of inertia / magnetizing current with direct transition to operation and the setpoint speed defined by the user. Expert: The Expert functions include the Standard Drive Control and Dynamic Drive Control functions. Select the appropriate application class for the drive from the pulldown. For this example, [1] Standard Drive Control (SDC) is selected. Click Next.

Page 23: Integrating Siemens Drive into Rockwell Automations Studio

4 Startdrive Configuration

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 23

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Setpoint specification: Selection if the drive is connected to a PLC and where the setpoint is to be created.

Select the appropriate controller connection and the setpoint specification. For this example, data exchange from the PLC to the drive (Ramp function in the drive) will be used. Click Next.

Further functions: Select the appropriate function modules for the drive. For this example; Telegram 352 will be used. Click Next.

Page 24: Integrating Siemens Drive into Rockwell Automations Studio

4 Startdrive Configuration

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 24

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Defaults of the setpoints/command sources: Selection of a predefined interconnection of the inputs/outputs and, if required, the fieldbus telegram. Can be changed later user-specifically.

Select the appropriate IO configuration from the pulldown. For this example, [4] Conveyor technology with fieldbus will be selected. Select the appropriate Telegram configuration from the pulldown. For this example, [352] SIEMENS telegram 352, PZD-6/6 will be selected to control a Siemens drive with a Rockwell processor. PZD-6/6 represents the number of Integers that will be received from the drive and sent to the drive. Click Next.

Page 25: Integrating Siemens Drive into Rockwell Automations Studio

4 Startdrive Configuration

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 25

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Drive setting: Selection of motor standard and load cycle.

Select appropriate setting from the pull down. Enter Drive unit line supply voltage. For this example, the motor being used is [0] IEC-Motor (50 Hz, SI unitts) at 230V line supply voltage. Click Next.

Page 26: Integrating Siemens Drive into Rockwell Automations Studio

4 Startdrive Configuration

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 26

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Drive options: Configuration of optional braking resistor and drive filter.

If applicable, select Braking resistor. Select Drive filter type motor side from pull down. For this example, braking resistor will be deselected with [0] No filter. Click Next.

Page 27: Integrating Siemens Drive into Rockwell Automations Studio

4 Startdrive Configuration

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 27

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Motor: Specification of motor type and motor data. Select appropriate motor configuration from the pull down. For this example, Enter motor data is selected. Select motor type from the pulldown. For this example, [1] Induction motor is selected. Select the connection type for the motor from the pulldown. For this example, Star is selected. Enter the rated motor current, rated motor power, rated motor speed, rated motor voltage, and rated motor frequency from the motor nameplate. Select motor cooling type from the pulldown. For this example, [0] Natural ventilization is selected. Select Temperature sensor from the pulldown. For this example, [0] No sensor is selected. Click Next.

Page 28: Integrating Siemens Drive into Rockwell Automations Studio

4 Startdrive Configuration

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 28

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Motor holding brake: Select Motor holding brake configuration from pull down. For this example, [0] No motor holding brake available. Click Next.

Page 29: Integrating Siemens Drive into Rockwell Automations Studio

4 Startdrive Configuration

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 29

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Important parameters: Specification of the most important dynamic response data.

Synchronization of the speed of the drive with the speed of the PLC:

Enter Reference speed: p2000. Sets reference quantity for speed and frequency.

Enter Maximum speed: p1082[0]. Sets the highest possible speed.

Configuration of ramp up and ramp down time:

Enter Ramp up time: p1120[0]. The ramp-function generator ramps-up the speed setpoint from standstill (setpoint = 0) up to the maximum speed (p1082) in this time.

Enter OFF1 ramp down time: p1121[0]. The ramp-function generator ramps-down the speed setpoint from the maximum speed (p1082) down to standstill (setpoint = 0) in this time.

Enter OFF3 (quick stop) ramp down time: Sets the ramp-down time from the maximum speed down to zero speed for the OFF3 command.

Configuration of the current limit:

Enter current limit: p640[0]. Sets the current limit.

Click Next.

Page 30: Integrating Siemens Drive into Rockwell Automations Studio

4 Startdrive Configuration

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 30

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Drive functions: Specification of the method to measure the motor data.

Select technological application (Standard Drive Control) from the pulldown. For this example, [0] Constant load (linear characteristic) is selected. Select motor identification from the pulldown. For this example, [2] Identifying motor data (at standstill) is selected. Click Next.

Page 31: Integrating Siemens Drive into Rockwell Automations Studio

4 Startdrive Configuration

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 31

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Summary: Click Finish.

Page 32: Integrating Siemens Drive into Rockwell Automations Studio

4 Startdrive Configuration

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 32

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Page 33: Integrating Siemens Drive into Rockwell Automations Studio

5 Download to the drive

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 33

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

5 Download to the drive

Expand the desired drive from the Project tree. Select the appropriate drive. Click download from the toolbar.

Click Load.

Page 34: Integrating Siemens Drive into Rockwell Automations Studio

5 Download to the drive

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 34

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Page 35: Integrating Siemens Drive into Rockwell Automations Studio

6 Motor Identification

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 35

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

6 Motor Identification

Expand the desired drive from the Project tree. Select the appropriate drive. Double click Commissioning. Click Control panel.

Click Go online from the toolbar.

Notice the motor measurement drive status is visible. Click Activate.

Page 36: Integrating Siemens Drive into Rockwell Automations Studio

6 Motor Identification

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 36

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click Accept.

If required, set Drive enables. Click Forward. Repeat until motor measurement drive status is invisible.

Notice the motor measurement drive status is invisible. Click Deactivate.

Page 37: Integrating Siemens Drive into Rockwell Automations Studio

6 Motor Identification

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 37

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click Accept.

Field bus interface protocol selection:

Double click Parameter.

Page 38: Integrating Siemens Drive into Rockwell Automations Studio

6 Motor Identification

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 38

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click Parameter View. Scroll down to p2030. Select [10] Ethernet/IP from the pulldown.

User Defined Parameter List: Click create new user defined parameter list.

Type the following parameters: 922, 2030, 8980, 2000, 2001, 2002, 2003, 2004, 1820. These are a few useful parameters. Click Save.

Page 39: Integrating Siemens Drive into Rockwell Automations Studio

6 Motor Identification

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 39

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click Yes.

Assign a file name and location. Click Save.

Save RAM to ROM:

Double click Commissioning. Click Backup/Restore. Save RAM data to EEPROM: Click Save.

Page 40: Integrating Siemens Drive into Rockwell Automations Studio

6 Motor Identification

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 40

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Save project: Click Save project.

Click Go offline:

Reboot drive.

Page 41: Integrating Siemens Drive into Rockwell Automations Studio

7 Create New Project with Rockwell Software Studio 5000

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 41

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

7 Create New Project with Rockwell Software Studio 5000

Under Create, Click New Project.

Expand appropriate controller. Select controller. Assign name. Click Browse.

Page 42: Integrating Siemens Drive into Rockwell Automations Studio

7 Create New Project with Rockwell Software Studio 5000

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 42

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Select appropriate folder. Click OK.

Page 43: Integrating Siemens Drive into Rockwell Automations Studio

7 Create New Project with Rockwell Software Studio 5000

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 43

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click Next.

Page 44: Integrating Siemens Drive into Rockwell Automations Studio

7 Create New Project with Rockwell Software Studio 5000

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 44

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Select revision from pulldown. If applicable, select expansion IO from pulldown. Click Finish.

Page 45: Integrating Siemens Drive into Rockwell Automations Studio

7 Create New Project with Rockwell Software Studio 5000

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 45

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Page 46: Integrating Siemens Drive into Rockwell Automations Studio

8 Rockwell Automation EDS Wizard

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 46

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

8 Rockwell Automation EDS Wizard

A Siemens drive is not firmware dependent to operate. These EDS files were created without a specific firmware version. From the Toolbar, Click Tools. Click EDS Hardware Installation Tool.

Welcome to Rockwell Automation’s EDS Wizard. To continue, Click Next.

Page 47: Integrating Siemens Drive into Rockwell Automations Studio

8 Rockwell Automation EDS Wizard

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 47

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Options - What task do you want to complete? Select Register an EDS file(s). This option will add a device(s) to our database. To continue, Click Next.

Registration – Electronic Data Sheet file(s) will be added to your system for use in Rockwell Automation applications. Select Register a directory of EDS files and check Look in subfolders. Click Browse.

Page 48: Integrating Siemens Drive into Rockwell Automations Studio

8 Rockwell Automation EDS Wizard

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 48

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Browse to the folder where the EDS files are located. Select All EDS Files (this is the folder where all EDS files for a Siemens G drive resides) folder. Click OK.

Page 49: Integrating Siemens Drive into Rockwell Automations Studio

8 Rockwell Automation EDS Wizard

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 49

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click Next.

Page 50: Integrating Siemens Drive into Rockwell Automations Studio

8 Rockwell Automation EDS Wizard

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 50

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

EDS File Installation Test Results – This test evaluates each EDS file for errors in the EDS file. This test does not guarantee EDS file validity. If the installation test results have a green check mark, click Next.

Page 51: Integrating Siemens Drive into Rockwell Automations Studio

8 Rockwell Automation EDS Wizard

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 51

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Change Graphic Image – You can change the graphic image that is associated with a device. To continue, click Next.

Page 52: Integrating Siemens Drive into Rockwell Automations Studio

8 Rockwell Automation EDS Wizard

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 52

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Final Task Summary – This is a review of the task you want to complete. You would like to register the following device. To continue, click Next.

You have successfully completed the EDS Wizard. To continue, click Finish.

Page 53: Integrating Siemens Drive into Rockwell Automations Studio

8 Rockwell Automation EDS Wizard

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 53

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Page 54: Integrating Siemens Drive into Rockwell Automations Studio

9 Add a Siemens Drive to the Ethernet Network

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 54

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

9 Add a Siemens Drive to the Ethernet Network

As an example, the following information will be using Telegram 352. In the Controller Organizer, expand I/O Configuration, right click on Ethernet and click New Module.

In the “Select Module Type” window, type T352 into the search bar. The results should show Siemens G Drive – T352. Another option would be to deselect Module Type Vendor Filters and scroll down to Siemens AG, select Siemens AG. Select Siemens G Drive – T352. Select Close on Create. To continue, click Create.

Page 55: Integrating Siemens Drive into Rockwell Automations Studio

9 Add a Siemens Drive to the Ethernet Network

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 55

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Assign a Name for the New Module. Assign the IP Address. Click Change.

Select Disable Keying in the Electronic Keying Dropdown. Select the connections size data type as INT. Click OK.

Page 56: Integrating Siemens Drive into Rockwell Automations Studio

9 Add a Siemens Drive to the Ethernet Network

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 56

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Change module definition? Click Yes.

Click OK.

Page 57: Integrating Siemens Drive into Rockwell Automations Studio

9 Add a Siemens Drive to the Ethernet Network

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 57

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

You have completed adding an Ethernet module to control a Siemens drive by using Telegram 352.

Page 58: Integrating Siemens Drive into Rockwell Automations Studio

10 Import Add-On Instruction

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 58

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

10 Import Add-On Instruction

As an example, the following information will be using Telegram 352 to manually control a Siemens drive with a PanelView Plus terminal. Right click on Add-On Instruction and click Import Add-On Instruction.

Browse to the folder where the Add-On Instruction resides. Select AOI_Telegram_352_HMI.L5X for use with an HMI. Click Open.

Click OK.

Page 59: Integrating Siemens Drive into Rockwell Automations Studio

10 Import Add-On Instruction

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 59

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

You have completed importing the Add-On Instruction.

Page 60: Integrating Siemens Drive into Rockwell Automations Studio

11 Configure IP Address for a Rockwell Controller

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 60

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

11 Configure IP Address for a Rockwell Controller

Connect the Ethernet cable directly to the controller. If the process is not connected to the plant Ethernet communications, connect the PC and the controller Ethernet cable to an ethernet switch.

Record the MAC address of the controller.

Launch BootP DHCP Tool.

Select the proper Ethernet adapter through which the PC is connected to the PLC. Click OK.

Page 61: Integrating Siemens Drive into Rockwell Automations Studio

11 Configure IP Address for a Rockwell Controller

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 61

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click OK.

Click OK.

Page 62: Integrating Siemens Drive into Rockwell Automations Studio

11 Configure IP Address for a Rockwell Controller

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 62

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click Add Relation.

The software will begin pinging the controller.

Page 63: Integrating Siemens Drive into Rockwell Automations Studio

11 Configure IP Address for a Rockwell Controller

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 63

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Double click the MAC address. Assign the Client IP Address. Click OK.

Select the device. Click Enable BOOTP/DHCP.

Page 64: Integrating Siemens Drive into Rockwell Automations Studio

11 Configure IP Address for a Rockwell Controller

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 64

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

The device appears in the upper section.

Select the device in the lower section. Click Disable BOOTP/DHCP. The IP address has been successfully assigned to the controller. Close software.

Page 65: Integrating Siemens Drive into Rockwell Automations Studio

11 Configure IP Address for a Rockwell Controller

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 65

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Page 66: Integrating Siemens Drive into Rockwell Automations Studio

12 Configure RSLinx Communications for a Rockwell Controller

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 66

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

12 Configure RSLinx Communications for a Rockwell Controller

Launch RSLinx Classic.

Click Communications. Click Configure Drivers.

Select Ethernet/IP Driver from the pulldown. Click Add New.

Page 67: Integrating Siemens Drive into Rockwell Automations Studio

12 Configure RSLinx Communications for a Rockwell Controller

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 67

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Assign a name for the driver.

Select the appropriate IP address. Click Apply. Click OK.

Page 68: Integrating Siemens Drive into Rockwell Automations Studio

12 Configure RSLinx Communications for a Rockwell Controller

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 68

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click Close.

Click Communications. Click RSWho.

Page 69: Integrating Siemens Drive into Rockwell Automations Studio

12 Configure RSLinx Communications for a Rockwell Controller

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 69

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Expand the newly created driver. The PC is communicating with the processor.

Page 70: Integrating Siemens Drive into Rockwell Automations Studio

13 Insert a Rung for the Add-On Instruction

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 70

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

13 Insert a Rung for the Add-On Instruction

As an example, the following information will be using Telegram 352. Click Add-On. Click AOI_Telegram_352_HMI.

Right click AOI_ Telegram_352_HMI.

Click New Tag.

Page 71: Integrating Siemens Drive into Rockwell Automations Studio

13 Insert a Rung for the Add-On Instruction

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 71

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Assign Name. Click Create.

Page 72: Integrating Siemens Drive into Rockwell Automations Studio

13 Insert a Rung for the Add-On Instruction

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 72

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Double click DriveStatus (data from the drive to the PLC). Click pulldown. Expand Drive_01:I (Drive_01 was the name assigned to the drive when it was added to the IO Configuration). Double click Drive_01:I.Data. Press Enter.

Page 73: Integrating Siemens Drive into Rockwell Automations Studio

13 Insert a Rung for the Add-On Instruction

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 73

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click pulldown for DriveControl (data from the PLC to the drive). Expand Drive_01:O (Drive_01 was the name assigned to the drive when it was added to the IO Configuration). Double click Drive_01:O.Data. Press Enter.

The next fields in the AOI can be assigned with an Integer value.

Reference_Speed_P2000 = p2000 (Reference speed reference frequency)

Reference_Current_P2002 = p2002 (Reference current)

Reference_Torque_P2003 = p2003 (Reference torque)

The units for actual speed is RPM. A conversion would be required to display the actual speed in a different unit.

Page 74: Integrating Siemens Drive into Rockwell Automations Studio

13 Insert a Rung for the Add-On Instruction

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 74

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Page 75: Integrating Siemens Drive into Rockwell Automations Studio

14 Controlling the Siemens Drive

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 75

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

14 Controlling the Siemens Drive

As an example, a Siemens drive will be replacing a Rockwell’s PowerFlex 525 drive.

Output structure for Rockwell’s PowerFlex 525 drive.

Output structure for a Siemens drive using Telegram 352.

To Run or Jog the Drive in the Forward direction:

DriveControl1_MainSetpoint (RPM): Enter a value from (–) Maximum speed to (+) Maximum speed

DriveControl0_DriveEnable = 1

DriveControl0_ReverseDirection = 0

DriveControl0_RunCommand = 1

Page 76: Integrating Siemens Drive into Rockwell Automations Studio

14 Controlling the Siemens Drive

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 76

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

To Run or Jog the Drive in the Reverse Direction:

DriveControl1_MainSetpoint (RPM): Enter a value from (–) Maximum speed to (+) Maximum speed

DriveControl0_DriveEnable = 1

DriveControl0_ReverseDirection = 1

DriveControl0_ RunCommand = 1

To perform a Coast to Stop:

DriveControl0_CoastStop = 1

To perform a Quick Stop:

DriveControl0_QuickStop = 1

Acknowledge Fault:

DriveControl0_FaultAcknowledge = 1

Page 77: Integrating Siemens Drive into Rockwell Automations Studio

14 Controlling the Siemens Drive

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 77

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Page 78: Integrating Siemens Drive into Rockwell Automations Studio

15 Download Project to the Rockwell Controller

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 78

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

15 Download Project to the Rockwell Controller

Click Communications. Click Who Active.

Click Set Project Path. Click Download.

Follow instructions before downloading. Click download.

Page 79: Integrating Siemens Drive into Rockwell Automations Studio

15 Download Project to the Rockwell Controller

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 79

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click Yes.

Page 80: Integrating Siemens Drive into Rockwell Automations Studio

16 Create a Rockwell’s FactoryTalk View Application

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 80

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

16 Create a Rockwell’s FactoryTalk View Application

Click New. Assign Application name. Select Language from the pulldown. Select Resolution from the pulldown. Click Create.

Page 81: Integrating Siemens Drive into Rockwell Automations Studio

17 Establish Communications Between the Rockwell Controller and the Rockwell PanelView Plus Terminal

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 81

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

17 Establish Communications Between the Rockwell Controller and the Rockwell PanelView Plus Terminal

Expand FactoryTalk Linx. Double click Communication Setup.

FactoryTalk Linx Runtime Configuration Wizard: Select an operation about runtime configuration. Select create a new configuration. Click Finish.

Click Add. Assign shortcut name. Press Enter. Select the appropriate controller. Click Apply.

Page 82: Integrating Siemens Drive into Rockwell Automations Studio

17 Establish Communications Between the Rockwell Controller and the Rockwell PanelView Plus Terminal

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 82

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click Yes.

Click Copy from Design to Runtime.

Page 83: Integrating Siemens Drive into Rockwell Automations Studio

17 Establish Communications Between the Rockwell Controller and the Rockwell PanelView Plus Terminal

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 83

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click Yes.

Click OK.

Page 84: Integrating Siemens Drive into Rockwell Automations Studio

18 Import Siemens Global Objects

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 84

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

18 Import Siemens Global Objects

These steps only apply to Telegram 1, 20, and 352. Expand Graphics. Right click on Global Objects. Click Import and Export.

Select Import graphic information into displays. Click Next.

Page 85: Integrating Siemens Drive into Rockwell Automations Studio

18 Import Siemens Global Objects

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 85

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Select No. Click Next.

Select Multiple displays batch import file. Click Next.

Page 86: Integrating Siemens Drive into Rockwell Automations Studio

18 Import Siemens Global Objects

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 86

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Browse to the folder where the global object resides.

Select BatchImport_Global_Telegram 352. Click Open.

Page 87: Integrating Siemens Drive into Rockwell Automations Studio

18 Import Siemens Global Objects

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 87

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click Finish.

Exit Notepad.

Page 88: Integrating Siemens Drive into Rockwell Automations Studio

18 Import Siemens Global Objects

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 88

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Page 89: Integrating Siemens Drive into Rockwell Automations Studio

19 Import Siemens Display

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 89

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

19 Import Siemens Display

These steps only apply to Telegram 1, 20, and 352. Expand Graphics. Right click on Displays. Click Import and Export.

Select Import graphic information into displays. Click Next.

Page 90: Integrating Siemens Drive into Rockwell Automations Studio

19 Import Siemens Display

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 90

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Select No. Click Next.

Select Multiple displays batch import file. Click Next.

Page 91: Integrating Siemens Drive into Rockwell Automations Studio

19 Import Siemens Display

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 91

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Browse to the folder where the display resides.

Select BatchImport_Display_Telegram 352. Click Open.

Page 92: Integrating Siemens Drive into Rockwell Automations Studio

19 Import Siemens Display

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 92

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click Finish.

Exit Notepad.

Page 93: Integrating Siemens Drive into Rockwell Automations Studio

19 Import Siemens Display

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 93

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Page 94: Integrating Siemens Drive into Rockwell Automations Studio

20 Add GOTO Button to a Display

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 94

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

20 Add GOTO Button to a Display

When the operator presses the Goto Display button at run time, the graphic display assigned to the button opens. Expand Graphics. Expand Global Objects. Double click Telegram 352.

Right click on the motor icon. Click Copy.

Page 95: Integrating Siemens Drive into Rockwell Automations Studio

20 Add GOTO Button to a Display

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 95

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Expand Graphics. Expand Displays. Select desired display. Right click on the display. Click Paste.

Right click on the icon. Click Global Object Parameter Values.

Page 96: Integrating Siemens Drive into Rockwell Automations Studio

20 Add GOTO Button to a Display

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 96

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click Tag.

Page 97: Integrating Siemens Drive into Rockwell Automations Studio

20 Add GOTO Button to a Display

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 97

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Select Refresh All Folders. Expand device shortcut. Expand Online. Select the appropriate controller tag. Click OK.

Click OK.

Page 98: Integrating Siemens Drive into Rockwell Automations Studio

20 Add GOTO Button to a Display

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 98

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

You have completed adding a GOTO button for Siemens Telegram 352.

Page 99: Integrating Siemens Drive into Rockwell Automations Studio

21 Alarms and Warnings

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 99

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

21 Alarms and Warnings

Expand Alarms. Right click on Alarm Setup. Click Import and Export.

Select Import alarm configuration into application. Click Next.

Page 100: Integrating Siemens Drive into Rockwell Automations Studio

21 Alarms and Warnings

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 100

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Select No. Click Next.

Click Browse.

Page 101: Integrating Siemens Drive into Rockwell Automations Studio

21 Alarms and Warnings

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 101

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Browse to the appropriate folder. Select Alarm Setup. Click Open.

Page 102: Integrating Siemens Drive into Rockwell Automations Studio

21 Alarms and Warnings

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 102

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click Finish.

Exit Notepad.

Page 103: Integrating Siemens Drive into Rockwell Automations Studio

22 Edit Tags for Alarm Setup

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 103

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

22 Edit Tags for Alarm Setup

Double click Alarm Setup

Based on the controller tag name for the Add-On instruction, the triggers for the alarms may need to be Edited. Select the appropriate tag. Click Edit.

Click Tag.

Page 104: Integrating Siemens Drive into Rockwell Automations Studio

22 Edit Tags for Alarm Setup

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 104

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Select the appropriate tag. Click OK.

Click OK.

Repeat these steps for WarnCode.

Page 105: Integrating Siemens Drive into Rockwell Automations Studio

23 Test Application

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 105

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

23 Test Application

Click Application. Click Test Application.

Click Motor.

If DriveControl0_DriveEnable is energized from the external code, the Drive Enable Override button will be invisible. Click Manual.

Enter Speed Setpoint (RPM). Click Start.

Page 106: Integrating Siemens Drive into Rockwell Automations Studio

23 Test Application

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 106

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

The motor ramps to 250 RPM’s in the Forward direction based on the Acceleration rate.

Click Forward. The motor ramps to -250 RPM’s in the Reverse direction based on the Deceleration rate.

Page 107: Integrating Siemens Drive into Rockwell Automations Studio

23 Test Application

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 107

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click Stop. The drive performs a Stop based on the Deceleration rate.

Click Reverse. Click Start. The motor ramps to 250 RPM’s in the Forward direction based on the Acceleration rate.

Page 108: Integrating Siemens Drive into Rockwell Automations Studio

23 Test Application

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 108

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click Auto. The drive performs a Stop based on the Deceleration rate.

Click Manual. Click Start. The motor ramps to 250 RPM’s in the Forward direction based on the Acceleration rate.

Page 109: Integrating Siemens Drive into Rockwell Automations Studio

23 Test Application

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 109

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click Close. The drive performs a Stop based on the Deceleration rate. The display closes and goes to the display where the motor is located.

Click motor. Click Manual. Click Start. The motor ramps to 250 RPM’s in the Forward direction based on the Acceleration rate.

Page 110: Integrating Siemens Drive into Rockwell Automations Studio

23 Test Application

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 110

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Remove the Ethernet cable from the PanelView Plus terminal. The drive performs a Stop based on the Deceleration rate.

Page 111: Integrating Siemens Drive into Rockwell Automations Studio

23 Test Application

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 111

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click Status. Status Word: Data from the drive to the PLC. Control Word: Data from the PLC to the drive.

Click Faults. Click Acknowledge Faults to reset all active alarms. A warning is cleared when the drives Run Command is activated. If active, a Fault Code or Warning Code with appropriate description will be displayed.

Page 112: Integrating Siemens Drive into Rockwell Automations Studio

23 Test Application

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 112

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Page 113: Integrating Siemens Drive into Rockwell Automations Studio

24 Transfer Utility

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 113

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

24 Transfer Utility

Click Application. Click Create Runtime Application.

Create Runtime Application: Save the file to the desired folder. Enter file name. Select type from the pulldown. Click Always Allow Conversion. Click Save.

Page 114: Integrating Siemens Drive into Rockwell Automations Studio

24 Transfer Utility

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 114

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click Tools. Click Transfer Utility.

Page 115: Integrating Siemens Drive into Rockwell Automations Studio

24 Transfer Utility

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 115

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click Download. Browse to select source file. Select destination storage from the pulldown. Select Run Application at Startup. Select Replace Communications and Delete Log files when application runs. Select the appropriate PanelView terminal. Click Download.

Click OK.

Page 116: Integrating Siemens Drive into Rockwell Automations Studio

24 Transfer Utility

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 116

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click Exit.

Page 117: Integrating Siemens Drive into Rockwell Automations Studio

25 Firmware Upgrade Wizard

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 117

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

25 Firmware Upgrade Wizard

Click Tools. Click Firmware Upgrade Wizard.

Select the type of firmware upgrade to perform: Click Upgrade firmware on terminal. Click Next.

Page 118: Integrating Siemens Drive into Rockwell Automations Studio

25 Firmware Upgrade Wizard

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 118

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click Yes.

Select the type of connection to the terminal: Click Network connection. Click Next.

Page 119: Integrating Siemens Drive into Rockwell Automations Studio

25 Firmware Upgrade Wizard

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 119

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Select the appropriate PanelView Plus terminal. Click Next.

Page 120: Integrating Siemens Drive into Rockwell Automations Studio

25 Firmware Upgrade Wizard

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 120

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Firmware source folder: Leave as default. Upgrade firmware version: Select the appropriate version from the pulldown. Click Next.

Select all the KEPServer drivers to be included in the firmware. Click Next.

Page 121: Integrating Siemens Drive into Rockwell Automations Studio

25 Firmware Upgrade Wizard

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 121

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

Click Finish.

Page 122: Integrating Siemens Drive into Rockwell Automations Studio

26 Appendix

Integrating Siemens Drive into Rockwell Automations Studio 5000 Speed Control Telegrams Entry ID: 82843076, V2.0.1, 10/2020 122

© S

iem

en

s A

G 2

02

0 A

ll ri

gh

ts r

ese

rve

d

26 Appendix

26.1 Application Support

Siemens AG Digital Industries Factory Automation Production Machines DI FA PMA APC Frauenauracher Str. 80 D-91056 Erlangen, Germany

mailto: [email protected]

26.2 Links and Literature

Table 26-1

No. Topic

\1\ Siemens Industry Online Support

https://support.industry.siemens.com

\2\ Link to this entry page of this application example

https://support.industry.siemens.com/cs/ww/en/109477746

\3\ Startdrive for commissioning G120

https://support.industry.siemens.com/cs/ww/en/view/109771710

\4\ Starter software for commissioning G120

https://support.industry.siemens.com/cs/ww/en/view/26233208

26.3 History

Table 26-2

Version Date Modification

V1.0 03/2020 First Version

V2.0 09/2020 Second Version

V2.0.1 10/2020 Manual optimized, no functional adaptions