show the entry list INSYS Modem 336 for Teleservice with SIMATIC S7-200 QUESTION: Which entries are required for STEP 7 Micro/WIN 32 V3.1 to use the INSYS Modem 336? ANSWER: Proceed as follows to configure the industry modem INSYS Modem 336: 1. In STEP 7 Micr o/WI N open the communicat ions wi ndow vi a the menu bar"View > Communication" . 2. Double-click the icon of the interface card. A window opens for s etting the PG/PC int erfa ce. 3. In the wi ndow "Interface Parameter Assignment Use:" select the setting "PC/PPI cable (PPI)". 4. The n press the "Properties..." button. In this window you select the transmission rate of 19.2 kbps and "Local Modem" as the modem connection. Then close the w indow for interface settings. 5. Now two modems appear in t he Communicat ions Setup window, whi ch you sti ll have t o configure. Page 1 of 5 Siemens - Industry Automation and Drive Technologies - Service& Support - Automation... 10.09.2010 http://support.automation.siemens.com/WW/llisapi.dll/5267250?func=ll&objId=5267250 ...

INSYS Modem 336 for Teleservice With SIMATIC S7-200 Www.otomasyonegitimi.com

Embed Size (px)

Citation preview

Page 1: INSYS Modem 336 for Teleservice With SIMATIC S7-200 Www.otomasyonegitimi.com

8/2/2019 INSYS Modem 336 for Teleservice With SIMATIC S7-200 Www.otomasyonegitimi.com

http://slidepdf.com/reader/full/insys-modem-336-for-teleservice-with-simatic-s7-200-wwwotomasyonegitimicom 1/5

show the entry listINSYS Modem 336 for Teleservice with SIMATIC S7-200

QUESTION:Which entries are required for STEP 7 Micro/WIN 32 V3.1 to use the INSYS Modem 336?

ANSWER: 

Proceed as follows to configure the industry modem INSYS Modem 336:

1. In STEP 7 Micro/WIN open the communications window via the menu bar "View >Communication".

2. Double-click the icon of the interface card. A window opens for setting the PG/PC interface.

3. In the window "Interface Parameter Assignment Use:" select the setting "PC/PPI cable(PPI)".

4. Then press the "Properties..." button. In this window you select the transmission rate of 19.2kbps and "Local Modem" as the modem connection. Then close the window for interface

settings.5. Now two modems appear in the Communications Setup window, which you still have toconfigure.

Page 1 of 5Siemens - Industry Automation and Drive Technologies - Service& Support - Automation...

10.09.2010http://support.automation.siemens.com/WW/llisapi.dll/5267250?func=ll&objId=5267250 ...

Page 2: INSYS Modem 336 for Teleservice With SIMATIC S7-200 Www.otomasyonegitimi.com

8/2/2019 INSYS Modem 336 for Teleservice With SIMATIC S7-200 Www.otomasyonegitimi.com

http://slidepdf.com/reader/full/insys-modem-336-for-teleservice-with-simatic-s7-200-wwwotomasyonegitimicom 2/5

 

6. Entry for STEP 7 Micro/WIN32 for the local modem:Open the "Modem Setup" window by double-clicking the icon for the local modem.

Page 2 of 5Siemens - Industry Automation and Drive Technologies - Service& Support - Automation...

10.09.2010http://support.automation.siemens.com/WW/llisapi.dll/5267250?func=ll&objId=5267250 ...

Page 3: INSYS Modem 336 for Teleservice With SIMATIC S7-200 Www.otomasyonegitimi.com

8/2/2019 INSYS Modem 336 for Teleservice With SIMATIC S7-200 Www.otomasyonegitimi.com

http://slidepdf.com/reader/full/insys-modem-336-for-teleservice-with-simatic-s7-200-wwwotomasyonegitimicom 3/5

7. Now you must reinsert the INSYS modem.Click the "Add..." button and enter the name of the modem. A window then opens in which youmust specify the following entries:

Initialization string:AT&F%C0&D0E0\G0&K0\N0X3Communications string: S23 = 12

8. Description of the AT command:

9. Click the "Program/Test" button. The text "Successful" must appear in the "Status" field.10. Entry for STEP 7 Micro/WIN 32 for the remote modem:

Open the "Modem Setup" window by double-clicking the icon for the remote modem.Now select the newly added modem and click the "Configure..." button. Now re-enter thecharacter string given below:

AT &F Reset to factory setting

%C0 Do not permit data compression

&D0 Ignore DTR

E0 Switch off echo from modem

 \G0 Switch off the modem-modem data flow control

&K0 No data flow control

 \N0 Switch off error clearance

X3 No ringback identification

S0=1 Pick-up after first call signal (remote modem only)

S23=12 Set the protocol 19200, 8, E, 1

&W0 Save the initialization in the Profile 0 (remote modem only)

Page 3 of 5Siemens - Industry Automation and Drive Technologies - Service& Support - Automation...

10.09.2010http://support.automation.siemens.com/WW/llisapi.dll/5267250?func=ll&objId=5267250 ...

Page 4: INSYS Modem 336 for Teleservice With SIMATIC S7-200 Www.otomasyonegitimi.com

8/2/2019 INSYS Modem 336 for Teleservice With SIMATIC S7-200 Www.otomasyonegitimi.com

http://slidepdf.com/reader/full/insys-modem-336-for-teleservice-with-simatic-s7-200-wwwotomasyonegitimicom 4/5

 

Initialization string: AT&F%CO&D0E0\G0&K0\N0X3S0=1S0=1Communications string: S23 = 12Suffix: &W0^M

11. Complete the entries by pressing the "OK" button.

This complete configuration of the modem. The settings are retained even after power off.

Note:The functionality of the communications connection was tested with the modem firmware versionV2.200-V34_ACF_DS1. Please check the version of your modem firmware using the command ATI3.If a different firmware is loaded in the modem and no connection is set up, then please get in touchwith the manufacturer of the modem.

For data exchange later you must set the transmission rate of the PPI interface in the S7-200 CPUalso to 19.2 kbps.

You must make the following settings of the PC/PPI cable:

Note:When using the PC/PPI cable (MLFB 6ES7 901-3BF00-0XA0) the "DTE" setting cannot be activated.This is why it is necessary to have an additional zero modem adapter between the remote modemand the PC/PPI cable.More information on data communications via modem is available in the S7-200 System Manual,section 7.4 "Communicating with Modems".

Baud rate 19.2 kbps

Switch 4 OFF (11 Bit)Switch 5 ON (DTE)

Page 4 of 5Siemens - Industry Automation and Drive Technologies - Service& Support - Automation...

10.09.2010http://support.automation.siemens.com/WW/llisapi.dll/5267250?func=ll&objId=5267250 ...

Page 5: INSYS Modem 336 for Teleservice With SIMATIC S7-200 Www.otomasyonegitimi.com

8/2/2019 INSYS Modem 336 for Teleservice With SIMATIC S7-200 Www.otomasyonegitimi.com

http://slidepdf.com/reader/full/insys-modem-336-for-teleservice-with-simatic-s7-200-wwwotomasyonegitimicom 5/5

Keywords:Remote maintenance, Remote interfacing

Entry ID:5267250 Date:2001-10-01

I regard this article.... as helpful as not helpful  

Copy link Suggestion for the entry Send to a friend

Print 

 © Siemens AG 2010 - Corporate Information - Privacy Policy - Terms of Use

Page 5 of 5Siemens - Industry Automation and Drive Technologies - Service& Support - Automation...

10.09.2010http://support.automation.siemens.com/WW/llisapi.dll/5267250?func=ll&objId=5267250 ...