Instrument TransformerReference

Meter and Relay Applications for theElectrical Industry

Page 2: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

Note: For Current and Voltage Transformer Pricing Information refer to: 600 V -PL 42-8005 kV-36 kV -PL 42-900

The transformers listed in this guide represent those mostcommonly built for the electric utility industry but are a smallsample of what we actually offer. For special designs or unitsnot listed please contact your local ABB representative.

VT Voltage Designations

14400/24940YThis unit is rated for 14400 operating Volts. It can be connected at14400 Volts line-ground on a 24940 Volt system (line to line Volts are24940 V) OR it can be connected line to line on a system with 14400V line to line. This unit is not suitable for operation at 24940 Volts.The "Y" indicates it has two fully insulated bushings, suitable for lineto line connection.

14400/24940GYThis unit is rated for 14400 operating Volts. It can be connected at14400 Volts line-ground on a 24940 Volt system (line to line Volts are24940 V). It CANNOT be connected line to line. The "GY" indicates itonly has one fully insulated bushing, making it suitable for line toground connection only.

14400/14400YThis unit is rated for 14400 operating Volts. It can be connected at14400 Volts line to line.

14400/14400GYThis unit is rated for 14400 operating Volts. However, it can only beconnected line to ground on a 14400 V system. Therefore the actualoperating voltage of the unit would be 14400/1.73. The accuracy andthermal ratings of this unit are based on 14400 V. This is typicalwhere there is a relay connected to the unit which should operatewhen there is a single line to ground fault. In this condition, the line toground voltage becomes equal to the line to line voltage. This unit isnot suitable for line to line connection as indicated by the "GY".

CT Rating Factors: Rating factors given in this brochure are standard at 30ºC. See thethermal loading guide on page 70-71 for derating for higher averageambient temperatures.

Transformers in this booklet conform to the following standards where applicable:

1) IEEE Standard Requirements for Instrument Transformers,C57.13–1993.

2) ANSI Standard for Instrument Transformers for MeteringPurposes, 15 kV and less, C12.11–1987.

Page 3: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

1

GGEENNEERRAALL IINNDDEEXX GGUUIIDDEE

600 VOLT CURRENT TRANSFORMERSPrimary Current Type Product Page

Bulletin No.

50 thru 1000 IMC 42-810 2-3100 thru 800 CBT/1 42-811 2-3100 thru 800 CBT-H 42-811 4-5200 thru 600 CSF 42-813 4-5200 thru 800 CSH 42-814 6-7200 thru 300 CMS 42-815 6-7100 thru 1200 CMF 42-818 8-9200 thru 4000 CMV 42-820 10-11200 thru 5000 CMV-HT 42-820HT 12-13600 thru 4000 CLC 42-824 14-171000 thru 6000 CLE 42-826 18-19600 thru 4000 RLC 42-828 20-21Multi-Ratio AUXILIARY 42-850 22-23Multi-Ratio A-AUTO 42-852 22-23600 thru 3000 OBCT 42-858 24-25

600 VOLT VOLTAGE TRANSFORMERSPrimary Voltage Type Product Page

Bulletin No.

240 thru 600 PPW 42-871 26-27120 thru 600 PPM 42-873 26-2760 thru 480 PPX 26-27

5 kV-36 kV CURRENT TRANSFORMERSClass Type Product Page

Bulletin No.

5, 8.7 kV Indoor KIR-60,75 42-914 28-2915 kV Indoor KIR-11 42-914 30-315, 8.7 kV Outdoor KOR-60,75 42-920 32-3315 kV Outdoor KOR-11 42-922 34-3515 kV Outdoor KON-11 42-924 36-3725 kV Outdoor KOR-15C 42-927 38-3936 kV Outdoor KOR-20 42-928A 40-415-25 kV Outdoor KOT 42-930 42-4515-36 kV Outdoor KOTD 42-940 46-49

5 kV-36 kV VOLTAGE TRANSFORMERSClass Type Product Page

Bulletin No.

5 kV Indoor VIY-60 42-951 50-518.7, 15 kV Indoor VIZ-75, 11 42-955 52-5325 kV Indoor VIZZ-15, 15G 42-959 54-555 kV Outdoor VOY-60 42-961 56-578.7, 15 kV Outdoor VOZ-75, 11 42-963A 56-5715 kV Outdoor VOZ-11M 42-963 58-5915 kV Outdoor VOY-11 42-964 58-5915 kV Outdoor VOG-11 42-965 58-5925 kV Outdoor VOY-12 42-966 60-6125 kV Outdoor VOG-12 42-967 60-6125 kV Outdoor VOY-15, 15G 42-970 62-6325 kV Outdoor VOZ-15 42-971 62-6336 kV Outdoor VOHD-200, 200G 42-977 64-6525 kV Outdoor VOZZ-15, 15G 42-978 64-6536 kV Outdoor VOZZ-20, 20G 42-979 66-6736 kV Outdoor VOY-20, 20G 42-974 66-67

Application Data 68-71Accuracy Standards 72-73IT Type Designations 74-75Cross-Reference 74-75

Page 4: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

2

600 V CURRENT TRANSFORMERS

TYPE IIMMCC PB 42-810

Window Dia.2.50 In.

ULRecognizedComponent

600 VoltsIndoor, 10 kV BIL25 Through 400Hertz

Primary Style IEEE Meter AccuracyAmps Number B0.1 B0.2 B0.5

TYPE IMC

50 7524A98G11 2.4100 7524A98G01 1.2150 7524A98G02 1.2 1.2200 7524A98G03 0.6 1.2 2.4250 7524A98G04 0.6 1.2 2.4300 7524A98G05 0.6 0.6 0.6400 7524A98G06 0.6 0.6 0.6500 7524A98G07 0.3 0.3 0.6600 7524A98G08 0.3 0.3 0.6800 7524A98G09 0.3 0.3 0.31000 7524A98G10 0.3 0.3 0.3Optional Accessory Mtg. Feet Style 9628A05G01

TYPE CBT/1

100 7882A77G01 0.3200 7882A77G04 0.3 0.3300 7882A77G07 0.3 0.3400 7882A77G10 0.3 0.3500 7882A77G13 0.3 0.3600 7882A77G16 0.3 0.3800 7882A77G19 0.3 0.3

100 7882A77G02 0.3200 7882A77G05 0.3 0.3300 7882A77G08 0.3 0.3400 7882A77G11 0.3 0.3500 7882A77G14 0.3 0.3600 7882A77G17 0.3 0.3800 7882A77G20 0.3 0.3

100 7882A77G03 0.3200 7882A77G06 0.3 .0.3300 7882A77G09 0.3 .0.3400 7882A77G12 0.3 .0.3500 7882A77G15 0.3 .0.3600 7882A77G18 0.3 .0.3800 7882A77G21 0.3 .0.3

No Base

Flat Base

High Base

Page 5: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

3

TYPE CCBBTT//11 PB 42-811

RatingFactor Height Width Length Weight

2.00 5.47 4.72 2.0 3.52.00 5.47 4.72 2.0 3.52.00 5.47 4.72 2.0 3.52.00 5.47 4.72 2.0 3.52.00 5.47 4.72 2.0 3.52.00 5.47 4.72 2.0 3.52.00 5.47 4.72 2.0 3.52.00 5.47 4.72 2.0 3.51.50 5.47 4.72 2.0 3.51.33 5.47 4.72 2.0 3.51.00 5.47 4.72 2.0 3.5

4.0 4.51 3.31 11.87 2.82.0 4.51 3.31 11.87 2.82.0 4.51 3.31 11.87 3.12.0 4.51 3.31 11.87 3.12.0 4.51 3.31 12.12 3.82.0 4.51 3.31 12.12 4.01.5 4.51 3.31 12.12 4.0

4.0 4.60 3.37 11.87 2.82.0 4.60 3.37 11.87 2.82.0 4.60 3.37 11.87 3.12.0 4.60 3.37 11.87 3.12.0 4.60 3.37 12.12 3.82.0 4.60 3.37 12.12 4.01.5 4.60 3.37 12.12 4.0

4.0 6.50 3.37 11.87 3.02.0 6.50 5.25 11.87 3.02.0 6.50 5.25 11.87 3.32.0 6.50 5.25 11.87 3.32.0 6.50 5.25 12.12 4.02.0 6.50 5.25 12.12 4.21.5 6.50 5.25 12.12 4.2

600 VoltsIndoor/Outdoor10 kV BIL60 Hertz

Page 6: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

4

600 V CURRENT TRANSFORMERS

TYPE CCBBTT--HH PB 42-812

Primary Style IEEE Meter AccuracyAmps Number B0.1 B0.2 B0.5

TYPE CBT-H

200 7882A78G04 0.3 0.3 0.3300 7882A78G07 0.3 0.3 0.3400 7882A78G10 0.3 0.3 0.3500 7882A78G13 0.3 0.3 0.3600 7882A78G16 0.3 0.3 0.3800 7882A78G19 0.3 0.3 0.3

200 7882A78G05 0.3 0.3 0.3300 7882A78G08 0.3 0.3 0.3400 7882A78G11 0.3 0.3 0.3500 7882A78G14 0.3 0.3 0.3600 7882A78G17 0.3 0.3 0.3800 7882A78G20 0.3 0.3 0.3

200 7882A78G06 0.3 0.3 0.3300 7882A78G09 0.3 0.3 0.3400 7882A78G12 0.3 0.3 0.3500 7882A78G15 0.3 0.3 0.3600 7882A78G18 0.3 0.3 0.3800 7882A78G21 0.3 0.3 0.3

Primary Style IEEE Meter AccuracyAmps Number B0.1 B0.2 B0.5

TYPE CSF ①

200 7524A85G01 0.3 0.3300 7524A85G02 0.3 0.3400 7524A83G02 0.3 0.3600 7524A83G03 0.3 0.3

200 7524A85G03 0.3 0.3300 7524A85G04 0.3 0.3400 7524A83G05 0.3 0.3600 7524A83G06 0.3 0.3

200 7524A85G05 0.3 0.3300 7524A85G06 0.3 0.3400 7524A83G08 0.3 0.3600 7524A83G09 0.3 0.3

① Optional Accessory: Primary Bars 1.500" D Style 9628A05G09

No Base

Flat Base

High Base

No Base

Flat Base

High Base

600 VoltsIndoor/Outdoor10 kV BIL60 Hertz

*Accuracy 20% less at 50 Hertz.

Page 7: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

5

TYPE CCSSFF PB 42-813

RatingFactor Height Width Length Weight

2.0 4.62 3.37 11.87 4.22.0 4.62 3.37 11.87 3.42.0 4.62 3.37 11.87 3.42.0 4.62 3.37 12.12 4.32.0 4.62 3.37 12.12 4.41.5 4.62 3.37 12.12 4.4

2.0 4.62 3.37 11.87 4.22.0 4.62 3.37 11.87 3.42.0 4.62 3.37 11.87 3.42.0 4.62 3.37 12.12 4.32.0 4.62 3.37 12.12 4.41.5 4.62 3.37 12.12 4.4

2.0 6.63 5.25 11.87 4.32.0 6.63 5.25 11.87 3.52.0 6.63 5.25 11.87 3.52.0 6.63 5.25 12.12 4.42.0 6.63 5.25 12.12 4.51.5 6.63 5.25 12.12 4.5

Rating WindowFactor Dia. Height Width Length Weight

3.0 1.50 4.85 3.47 3.32 3.752.0 1.50 4.85 3.47 3.32 3.752.0 2.00 4.85 3.47 3.32 2.251.5 2.00 4.85 3.47 3.32 2.25

3.0 1.50 4.94 3.47 5.25 4.002.0 1.50 4.94 3.47 5.25 4.002.0 2.00 4.94 3.47 5.25 2.501.5 2.00 4.94 3.47 5.25 2.50

3.0 1.50 6.54 5.25 4.50 4.002.0 1.50 6.54 5.25 4.50 4.002.0 2.00 6.54 5.25 4.50 2.501.5 2.00 6.54 5.25 4.50 2.50

2.000" D Style 9628A05G10

600 VoltsIndoor/Outdoor10 kV BIL50/60 Hertz*

Page 8: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

6

600 V CURRENT TRANSFORMERS

TYPE CCSSHH PB 42-814

Primary Style IEEE Meter AccuracyAmps Number B0.1 B0.2 B0.5

TYPE CSH

200 7526A90G01 0.3 0.3 0.3300 7526A90G02 0.3 0.3 0.3400 7526A90G03 0.3 0.3 0.3500 7526A90G04 0.3 0.3 0.3600 7526A90G05 0.3 0.3 0.3800 7526A90G06 0.3 0.3 0.3

200 7526A90G11 0.3 0.3 0.3300 7526A90G12 0.3 0.3 0.3400 7526A90G13 0.3 0.3 0.3500 7526A90G14 0.3 0.3 0.3600 7526A90G15 0.3 0.3 0.3800 7526A90G16 0.3 0.3 0.3

200 7526A90G21 0.3 0.3 0.3300 7526A90G22 0.3 0.3 0.3400 7526A90G23 0.3 0.3 0.3500 7526A90G24 0.3 0.3 0.3600 7526A90G25 0.3 0.3 0.3800 7526A90G26 0.3 0.3 0.3

TYPE CMS

200 7524A79G01 0.3 0.3300 7524A79G02 0.3 0.3 0.3

200 7524A79G03 0.3 0.3300 7524A79G04 0.3 0.3 0.3

200 7524A79G05 0.3 0.3300 7524A79G06 0.3 0.3 0.3

*Accuracy 20% less at 50 Hertz.

600 VoltsIndoor/Outdoor10 kV BIL50/60 Hertz

Window Dia. 1.50 In. 200 & 300 Amps2.00 In. all other ratings

No Base

Flat Base

High Base

No Base

Flat Base

High Base

Page 9: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

7

TYPE CCMMSS PB 42-815

600 VoltsIndoor/Outdoor10 kV BIL50/60 Hertz

Relay* RatingAccuracy Factor Height Width Length Weight

C10 3.0 5.41 4.00 3.87 7.25C10 2.0 5.41 4.00 3.87 7.25C10 2.0 5.41 4.00 3.87 6.00C10 2.0 5.41 4.00 3.87 5.50C10 2.0 5.41 4.00 3.87 5.20C10 1.5 5.41 4.00 3.87 5.00

C10 3.0 5.50 5.62 3.87 7.50C10 2.0 5.50 5.62 3.87 7.50C10 2.0 5.50 5.62 3.87 6.25C10 2.0 5.50 5.62 3.87 5.75C10 2.0 5.50 5.62 3.87 5.45C10 1.5 5.50 5.62 3.87 5.25

C10 3,0 7.09 5.25 4.50 7.50C10 2.0 7.09 5.25 4.50 7.50C10 2.0 7.09 5.25 4.50 6.25C10 2.0 7.09 5.25 4.50 5.75C10 2.0 7.09 5.25 4.50 5.45C10 1.5 7.09 5.25 4.50 5.25

C10 3.0 5.41 4.00 3.87 5.50C10 2.0 5.41 4.00 3.87 5.50

C10 3.0 5.50 4.00 5.25 5.75C10 2.0 5.50 4.00 5.25 5.75

C10 3.0 7.09 5.25 4.50 5.75C10 2.0 7.09 5.25 4.50 5.75

Window Dia. 2.00 In.

Page 10: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

Primary Style IEEE Meter AccuracyAmps Number B0.1 B0.2 B0.5 B1.8

50 4460A30G25 1.2100 4460A30G23 0.3200 4460A30G01 0.3 0.3 0.3400 4460A30G03 0.3 0.3 0.3500 4460A30G05 0.3 0.3 0.3600 4460A30G07 0.3 0.3 0.3800 4460A30G09 0.3 0.3 0.31000 4460A30G21 0.3 0.3 0.31200 4460A30G19 0.3 0.3 0.3 0.3200/400 4460A30G11 0.3/0.3 0.3/0.3 0.3/0.3300/600 4460A30G13 0.3/0.3 0.3/0.3 0.3/0.3400/800 4460A30G15 0.3/0.3 0.3/0.3 0.3/0.3

50 4460A30G26 1.2100 4460A30G24 0.3200 4460A30G02 0.3 0.3 0.3400 4460A30G04 0.3 0.3 0.3500 4460A30G06 0.3 0.3 0.3600 4460A30G08 0.3 0.3 0.3800 4460A30G10 0.3 0.3 0.31000 4460A30G22 0.3 0.3 0.31200 4460A30G20 0.3 0.3 0.3 0.3200/400 4460A30G12 0.3/0.3 0.3/0.3 0.3/0.3300/600 4460A30G14 0.3/0.3 0.3/0.3 0.3/0.3400/800 4460A30G16 0.3/0.3 0.3/0.3 0.3/0.3

100 7525A01G25 0.3200 7525A01G01 0.3 0.3 0.3400 7525A01G03 0.3 0.3 0.3500 7525A01G05 0.3 0.3 0.3600 7525A01G07 0.3 0.3 0.3800 7525A01G09 0.3 0.3 0.31000 7525A01G23 0.3 0.3 0.31200 7525A01G19 0.3 0.3 0.3 0.3200/400 7525A01G11 0.3/0.3 0.3/0.3 0.3/0.3300/600 7525A01G13 0.3/0.3 0.3/0.3 0.3/0.3400/800 7525A01G15 0.3/0.3 0.3/0.3 0.3/0.3

100 7525A01G26 0.3200 7525A01G02 0.3 0.3 0.3400 7525A01G04 0.3 0.3 0.3500 7525A01G06 0.3 0.3 0.3600 7525A01G08 0.3 0.3 0.3800 7525A01G10 0.3 0.3 0.31000 7525A01G24 0.3 0.3 0.31200 7525A01G20 0.3 0.3 0.3 0.3200/400 7525A01G12 0.3/0.3 0.3/0.3 0.3/0.3300/600 7525A01G14 0.3/0.3 0.3/0.3 0.3/0.3400/800 7525A01G16 0.3/0.3 0.3/0.3 0.3/0.3

8

600 V CURRENT TRANSFORMERS

TYPE CCMMFF

*Accuracy 20% less at 50 Hertz.

Window Dia.2.50 In. 100, 200 & 200/400Amps3.06 In. all other ratings

With Windowand Flat Base

With Windowand High Base

With Primary Barand Flat Base

With Primary Barand High Base

600 Volts, Indoor/Outdoor, 10 kV BIL50/60 Hertz*

Page 11: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

Relay* RatingAccuracy Factor Height Width Length Weight

––– 4.0 7.12 5.62 4.50 12.3C20 4.0 7.12 5.62 4.50 12.3C30 4.0 7.12 5.62 4.50 12.3C30 4.0 7.12 5.62 4.50 8.5C30 3.0 7.12 5.62 4.50 8.5C30 2.0 7.12 5.62 4.50 8.5C20 2.0 7.12 5.62 4.50 8.3C30 2.0 7.12 5.62 4.50 8.3C30 1.5 7.12 5.62 4.50 8.3C30/C50 4/2 7.12 5.62 4.50 12.4C20/C30 2/2 7.12 5.62 4.50 9.7C20/C50 2/2 7.12 5.62 4.50 8.7

4.0 7.91 5.25 4.50 12.3C20 4.0 7.91 5.25 4.50 12.3C30 4.0 7.91 5.25 4.50 12.3C30 4.0 7.91 5.25 4.50 8.5C30 3.0 7.91 5.25 4.50 8.5C30 2.0 7.91 5.25 4.50 8.5C20 2.0 7.91 5.25 4.50 8.3C30 2.0 7.91 5.25 4.50 8.3C30 1.5 7.91 5.25 4.50 8.3C30/C50 4/2 7.91 5.25 4.50 12.4C20/C30 2/2 7.91 5.25 4.50 9.7C20/C50 2/2 7.91 5.25 4.50 8.7

C20 4.0 7.12 5.62 11.81 14.3C30 4.0 7.12 5.62 11.81 14.3C30 4.0 7.12 5.62 11.81 12.5C30 3.0 7.12 5.62 11.81 12.5C30 2.0 7.12 5.62 11.81 12.5C20 2.0 7.12 5.62 11.81 12.3C30 2.0 7.12 5.62 11.81 12.3C30 1.5 7.12 5.62 11.81 12.3C30/C50 4/2 7.12 5.62 11.81 14.4C20/C30 2/2 7.12 5.62 11.81 13.7C20/C50 2/2 7.12 5.62 11.81 12.7

C20 4.0 7.91 5.25 11.81 14.3C30 4.0 7.91 5.25 11.81 14.3C30 4.0 7.91 5.25 11.81 12.5C30 3.0 7.91 5.25 11.81 12.5C30 2.0 7.91 5.25 11.81 12.5C20 2.0 7.91 5.25 11.81 12.3C30 2.0 7.91 5.25 11.81 12.3C30 1.5 7.91 5.25 11.81 12.3C30/C50 4/2 7.91 5.25 11.81 14.4C20/C30 2/2 7.91 5.25 11.81 13.7C20/C50 2/2 7.91 5.25 11.81 12.7

9

PB 42-818

Page 12: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

Primary Style IEEE Meter Accuracy

Amps Number B0.1 B0.2 B0.5 B0.9 B1.8

CMV

200 7524A75G01 0.3300 7524A75G02 0.3 0.3400 7524A75G03 0.3 0.3500 7524A75G12 0.3 0.3600 7524A75G04 0.3 0.3 0.3800 7524A75G05 0.3 0.3 0.31000 7524A75G06 0.3 0.3 0.3

1200 7524A75G07 0.3 0.3 0.3 0.31500 7524A75G08 0.3 0.3 0.3 0.32000 7524A75G09 0.3 0.3 0.3 0.3 0.33000 7524A75G10 0.3 0.3 0.3 0.3 0.34000 7524A75G11 0.3 0.3 0.3 0.3 0.3

200 200 7524A73G01 0.3300 7524A73G02 0.3 0.3400 7524A73G03 0.3 0.3500 7524A73G12 0.3 0.3600 7524A73G04 0.3 0.3 0.3800 7524A73G05 0.3 0.3 0.31000 7524A73G06 0.3 0.3 0.3

1200 7524A73G07 0.3 0.3 0.3 0.31500 7524A73G08 0.3 0.3 0.3 0.32000 7524A73G09 0.3 0.3 0.3 0.3 0.33000 7524A73G10 0.3 0.3 0.3 0.3 0.34000 7524A73G11 0.3 0.3 0.3 0.3 0.3

Optional AccessoriesMounting Feet—4 pcs. w hdwr., Style #9628A05G15One Piece Base w hdwr., Style #9628A05G16

10

600 V CURRENT TRANSFORMERS

TYPE CCMMVV

① Accuracy 20% less at 50 Hertz.

Window Opening3.50 x 4.50 In.

Tapered Bottom

Wide Bottom

Page 13: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

Relay① Rating

Accuracy Factor Height Width Length Weight

C20 4.00 8.80 6.00 2.19 6.0C20 4.00 8.80 6.00 2.19 6.0C20 4.00 8.80 6.00 2.19 6.0C20 3.00 8.80 6.00 2.19 6.0C20 3.00 8.80 6.00 2.19 6.0C20 3.00 8.80 6.00 2.19 6.0C30 2.00 8.80 6.00 2.19 6.0

C20 1.50 8.80 6.00 2.19 6.0C50 2.00 8.80 6.00 2.19 6.0C50 1.50 8.80 6.00 2.19 6.0C30 1.33 8.80 6.00 2.19 6.0C20 1.00 8.80 6.00 2.19 6.0

C20 4.00 8.68 6.00 2.19 6.5C20 4.00 8.68 6.00 2.19 6.5C20 4.00 8.68 6.00 2.19 6.5C20 3.00 8.68 6.00 2.19 6.5C20 3.00 8.68 6.00 2.19 6.5C20 3.00 8.68 6.00 2.19 6.5C30 2.00 8.68 6.00 2.19 6.5

C20 1.50 8.68 6.00 2.19 6.5C50 2.00 8.68 6.00 2.19 6.5C50 1.50 8.68 6.00 2.19 6.5C30 1.33 8.68 6.00 2.19 6.5C20 1.00 8.68 6.00 2.19 6.5

11

PB 42-820

600 Volts, Indoor/Outdoor10 kV BIL50/60 Hertz*

Accessory: Bus Bar AdapterStyle #9628A05G17 (2 pcs.)Supplied with Style #7524A75GXXTo order without use Style # 7524A76GXX

fits the following bus bar sizes:

¼ " ⅜ "* ½"**with modification

Page 14: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

12

Primary Style IEEE Meter AccuracyAmps Number B0.1 B0.2 B0.5 B0.9 B1.8

200 923A231G01 0.3300 923A231G02 0.3 0.3400 923A231G03 0.3 0.3600 923A231G04 0.3 0.3 0.3800 923A231G05 0.3 0.3 0.31000 923A231G06 0.3 0.3 0.31200 923A231G07 0.3 0.3 0.3 0.31500 923A231G08 0.3 0.3 0.3 0.32000 923A231G09 0.3 0.3 0.3 0.3 0.33000 923A231G10 0.3 0.3 0.3 0.3 0.34000 923A231G11 0.3 0.3 0.3 0.3 0.3

600 V CURRENT TRANSFORMERS

TYPE CCMMVV--HHTT

Window Opening3.5 x 4.5 In.

600 VoltsIndoor/Outdoor10 kV BIL25-60 Hertz

* Accuracy 20% less at 50 Hertz.

“HT” refers to CTsdesigned for hightemperatureenvironments. Referto Product Bulletinfor details.

Page 15: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

13

Relay* RatingAccuracy Factor Height Width Length Weight

C20 4.00 8.80 6.00 2.19 6.00C20 4.00 8.80 6.00 2.19 6.00C20 4.00 8.80 6.00 2.19 6.00C20 3.00 8.80 6.00 2.19 6.00C20 3.00 8.80 6.00 2.19 6.00C30 2.00 8.80 6.00 2.19 6.00C20 1.50 8.80 6.00 2.19 6.00C50 2.00 8.80 6.00 2.19 6.00C50 1.50 8.80 6.00 2.19 6.00C30 1.33 8.80 6.00 2.19 6.00C20 1.00 8.80 6.00 2.19 6.00

PB 42-820HT

Page 16: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

14

Primary Style IEEE Meter AccuracyAmps Number B0.1 B0.2 B0.5 B0.9 B1.8

600 7524A58G16 0.3 0.3 0.3800 7524A58G01 0.3 0.3 0.31000 7524A58G02 0.3 0.3 0.31200 7524A58G03 0.3 0.3 0.3 0.31500 7524A58G04 0.3 0.3 0.3 0.32000 7524A58G05 0.3 0.3 0.3 0.3 0.33000 7524A58G06 0.3 0.3 0.3 0.3 0.34000 7524A58G07 0.3 0.3 0.3 0.3 0.3

600/1200 7524A58G080.3 0.30.3 0.3 0.3 0.3 ➁

800/1600 7524A58G090.3 0.30.3 0.3 0.3 0.3 0.3 ➁

1000/2000 7524A58G100.3 0.3 0.30.3 0.3 0.3 0.3 0.3 ➁

1500/3000 7524A58G110.3 0.3 0.3 0.30.3 0.3 0.3 0.3 0.3 ➁

2000/4000 7524A58G120.3 0.3 0.3 0.3 0.30.3 0.3 0.3 0.3 0.3 ➁

600 7524A59G16 0.3 0.3 0.3800 7524A59G01 0.3 0.3 0.31000 7524A59G02 0.3 0.3 0.31200 7524A59G03 0.3 0.3 0.3 0.31500 7524A59G04 0.3 0.3 0.3 0.32000 7524A59G05 0.3 0.3 0.3 0.3 0.33000 7524A59G06 0.3 0.3 0.3 0.3 0.34000 7524A59G07 0.3 0.3 0.3 0.3 0.3

600/1200 7524A59G080.3 0.30.3 0.3 0.3 0.3 ➁

800/1600 7524A59G090.3 0.30.3 0.3 0.3 0.3 0.3 ➁

1000/2000 7524A59G100.3 0.3 0.30.3 0.3 0.3 0.3 0.3 ➁

1500/3000 7524A59G110.3 0.3 0.3 0.30.3 0.3 0.3 0.3 0.3 ➁

2000/4000 7524A59G120.3 0.3 0.3 0.3 0.30.3 0.3 0.3 0.3 0.3 ➁

600 V CURRENT TRANSFORMERS

TYPE CCLLCC

➁ Tap Connection X2-X3*Accuracy 20% less at 50 Hertz.

Window Dia.5.50 In.

WithoutMounting Feet

With Mounting Feet 4-Piece

Page 17: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

15

PB 42-824

600 Volts, Indoor/Outdoor, 10 kV BIL50/60 Hertz*

Optional Accessories:Mounting Feet-Set of 4 with Hardware 9628A05G20One Piece Base 9628A05G21Window Plate-One required 9628A05G22Primary Bar Assemblies800-1500 Amps-1 Bar 9628A05G232000 Amps-2 Bars 9628A05G243000 Amps-3 Bars 9628A05G254000 Amps-4 Bars 9628A05G26

Relay* RatingAccuracy Factor Height Width Length Weight

C30 3.00 9.75 8.25 2.62 11.0C30 2.00 9.75 8.25 2.62 11.0C50 2.00 9.75 8.25 2.62 11.0C30 2.00 9.75 8.25 2.62 11.0C30 3.00 9.75 8.25 2.62 11.0C50 2.00 9.75 8.25 2.62 11.0C10 1.50 9.75 8.25 2.62 11.0––– 1.33 9.75 8.25 2.62 11.0

C10 3.009.75 8.25 2.62 11.0C30 2.00

C20 3.009.75 8.25 2.62 11.0C30 2.00

C30 3.009.75 8.25 2.62 11.0C50 2.00

––– 2.009.75 8.25 2.62 11.0C10 1.33

___ 2.00 9.75 8.25 2.62 11.0___ 1.33

C30 3.00 9.75 8.25 6.37 11.5C30 2.00 9.75 8.25 6.37 11.5C50 2.00 9.75 8.25 6.37 11.5C30 2.00 9.75 8.25 6.37 11.5C30 3.00 9.75 8.25 6.37 11.5C50 2.00 9.75 8.25 6.37 11.5C10 1.50 9.75 8.25 6.37 11.5––– 1.33 9.75 8.25 6.37 11.5

C10 3.009.75 8.25 6.37 11.5C30 2.00

C20 3.009.75 8.25 6.37 11.5C30 2.00

C30 3.009.75 8.25 6.37 11.5C50 2.00

––– 2.009.75 8.25 6.37 11.5C10 1.33

___ 2.009.75 8.25 6.37 11.5––– 1.33

continued on next page

Page 18: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

Primary Style IEEE Meter AccuracyAmps Number B0.1 B0.2 B0.5 B0.9 B1.8

600 7524A60G16 0.3 0.3 0.3800 7524A60G01 0.3 0.3 0.31000 7524A60G02 0.3 0.3 0.31200 7524A60G03 0.3 0.3 0.3 0.31500 7524A60G04 0.3 0.3 0.3 0.32000 7524A60G05 0.3 0.3 0.3 0.3 0.33000 7524A60G06 0.3 0.3 0.3 0.3 0.34000 7524A60G07 0.3 0.3 0.3 0.3 0.3

600/1200 7524A60G080.3 0.30.3 0.3 0.3 0.3 ➁

800/1600 7524A60G090.3 0.30.3 0.3 0.3 0.3 0.3 ➁

1000/2000 7524A60G100.3 0.3 0.30.3 0.3 0.3 0.3 0.3 ➁

1500/3000 7524A60G110.3 0.3 0.3 0.30.3 0.3 0.3 0.3 0.3 ➁

2000/4000 7524A60G120.3 0.3 0.3 0.3 0.30.3 0.3 0.3 0.3 0.3 ➁

600 7524A61G16 0.3 0.3 0.3800 7524A61G01 0.3 0.3 0.31000 7524A61G02 0.3 0.3 0.31200 7524A61G03 0.3 0.3 0.3 0.31500 7524A61G04 0.3 0.3 0.3 0.32000 7524A61G05 0.3 0.3 0.3 0.3 0.33000 7524A61G06 0.3 0.3 0.3 0.3 0.34000 7524A61G07 0.3 0.3 0.3 0.3 0.3

600/1200 7524A61G080.3 0.30.3 0.3 0.3 0.3 ➁

800/1600 7524A61G090.3 0.30.3 0.3 0.3 0.3 0.3 ➁

1000/2000 7524A61G100.3 0.3 0.30.3 0.3 0.3 0.3 0.3 ➁

1500/3000 7524A61G110.3 0.3 0.3 0.30.3 0.3 0.3 0.3 0.3 ➁

2000/4000 7524A61G120.3 0.3 0.3 0.3 0.30.3 0.3 0.3 0.3 0.3 ➁

16

600 V CURRENT TRANSFORMERS

TYPE CCLLCC CONT’D.

➁ Tap Connection X2-X3*Accuracy 20% less at 50 Hertz.

With OnePiece Base

With WindowPlate

Page 19: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

Relay* RatingAccuracy Factor Height Width Length Weight

C30 3.00 9.75 8.25 2.62 11.0C30 2.00 9.75 8.25 2.62 11.0C50 2.00 9.75 8.25 2.62 11.0C30 2.00 9.75 8.25 2.62 11.0C30 3.00 9.75 8.25 2.62 11.0C50 2.00 9.75 8.25 2.62 11.0C10 1.50 9.75 8.25 2.62 11.0––– 1.33 9.75 8.25 2.62 11.0

C10 3.009.75 8.25 2.62 11.0C30 2.00

C20 3.009.75 8.25 2.62 11.0C30 2.00

C30 3.009.75 8.25 2.62 11.0C50 2.00

––– 2.009.75 8.25 2.62 11.0C10 1.33

––– 2.009.75 8.25 2.62 11.0––– 1.33

C30 3.00 9.75 8.25 6.37 11.5C30 2.00 9.75 8.25 6.37 11.5C50 2.00 9.75 8.25 6.37 11.5C30 2.00 9.75 8.25 6.37 11.5C30 3.00 9.75 8.25 6.37 11.5C50 2.00 9.75 8.25 6.37 11.5C10 1.50 9.75 8.25 6.37 11.5––– 1.33 9.75 8.25 6.37 11.5

C10 3.009.75 8.25 6.37 11.5C30 2.00

C20 3.009.75 8.25 6.37 11.5C30 2.00

C30 3.009.75 8.25 6.37 11.5C50 2.00

––– 2.009.75 8.25 6.37 11.5C10 1.33

––– 2.009.75 8.25 6.37 11.5––– 1.33

17

PB 42-824

Page 20: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

Primary Style IEEE Meter AccuracyAmps Number B0.1 B0.2 B0.5 B0.9 B1.8

2000 7524A63G01 0.3 0.3 0.3 0.33000 7524A63G02 0.3 0.3 0.3 0.3 0.34000 7524A63G03 0.3 0.3 0.3 0.3 0.35000 7524A63G04 0.3 0.3 0.3 0.3 0.36000 7524A63G05 0.3 0.3 0.3 0,3 0.3

1000/2000 7524A63G060.3 0.3 0.3 ②

0.3 0.3 0.3 0.3

1500/3000 7524A63G070.3 0.3 0.3 ②

0.3 0.3 0.3 0.3 0.3

2000/4000 7524A63G080.3 0.3 0.3 0.3 ②

0.3 0.3 0.3 0.3 0.3

2500/5000 7524A63G090.3 0.3 0.3 0.3 0.3 ②

0.3 0.3 0.3 0.3 0.3

3000/6000 7524A63G100.3 0.3 0.3 0.3 0.3 ②

0.3 0.3 0.3 0.3 0.3

2000 7524A64G01 0.3 0.3 0.3 0.33000 7524A64G02 0.3 0.3 0.3 0.3 0.34000 7524A64G03 0.3 0.3 0.3 0.3 0.35000 7524A64G04 0.3 0.3 0.3 0.3 0.36000 7524A64G05 0.3 0.3 0.3 0.3 0.3

1000/2000 7524A64G060.3 0.3 0.3 ②

0.3 0.3 0.3 0.3

1500/3000 7524A64G070.3 0.3 0.3 ②

0.3 0.3 0.3 0.3 0.3

2000/4000 7524A64G080.3 0.3 0.3 0.3 ②

0.3 0.3 0.3 0.3 0.3

2500/5000 7524A64G090.3 0.3 0.3 0.3 0.3 ②

0.3 0.3 0.3 0.3 0.3

3000/6000 7524A64G100.3 0.3 0.3 0.3 0.3 ②

0.3 0.3 0.3 0.3 0.3

18

600 V CURRENT TRANSFORMERS

TYPE CCLLEE

➁ Tap Connection X2-X3*Accuracy 20% less at 50 Hertz.

Without Mounting Feet

With Mounting Feet2-Piece

Window Dia.8.25 In.

Page 21: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

Relay* RatingAccuracy Factor Height Width Length Weight

C50 2.00 12.87 11.37 2.62 16.0C100 2.00 12.87 11.37 2.62 16.0C100 1.50 12.87 11.37 2.62 16.0C100 1.33 12.87 11.37 2.62 16.0––– 1.00 12.87 11.37 2.62 16.0

C30 3.0012.87 11.37 2.62 16.0C50 2.00

C50 3.0012.87 11.37 2.62 16.0C100 2.00

C50 2.0012.87 11.37 2.62 16.0C100 1.50

C100 2.0012.87 11.37 2.62 16.0C200 1.33

––– 1.3312.87 11.37 2.62 16.0––– 1.00

C50 2.00 12.87 11.37 6.37 17.0C100 2.00 12.87 11.37 6.37 17.0C100 1.50 12.87 11.37 6.37 17.0C100 1.33 12.87 11.37 6.37 17.0––– 1.00 12.87 11.37 6.37 17.0

C30 3.0012.87 11.37 6.37 17.0C50 2.00

C30 3.0012.87 11.37 6.37 17.0C50 2.00

C30 2.0012.87 11.37 6.37 17.0C50 1.50

C100 2.00 12.87 11.37 6.37 17.0C200 1.33 12.87 11.37 6.37 17.0

––– 1.33 12.87 11.37 6.37 17.0––– 1.00 12.87 11.37 6.37 17.0

19

PB 42-826

600 Volts, Indoor/Outdoor, 10 kV BIL50/60 Hertz

Optional AccessoriesMounting Feet-Set of 2 w/hdwr. 9628A05G27Window Plates-Set of 2 w/hdwr. 9628A05G28

Page 22: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

Primary Style IEEE Meter AccuracyAmps Number B0.1 B0.2 B0.5 B0.9 B1.8

750 7524A52G01 0.3 0.3 0.3 0.6800 7524A52G02 0.3 0.3 0.3 0.3 0.6900 7524A52G03 0.3 0.3 0.3 0.3 0.61000 7524A52G04 0.3 0.3 0.3 0.3 0.31200 7524A52G05 0.3 0.3 0.3 0.3 0.31500 7524A52G06 0.3 0.3 0.3 0.3 0.32000 7524A52G07 0.3 0.3 0.3 0.3 0.33000 7524A52G08 0.3 0.3 0.3 0.3 0.34000 7524A52G09 0.3 0.3 0.3 0.3 0.3

600/1200 7524A52G10 0.3 0.3 0.3 0.6 1.2 ②

0.3 0.3 0.3 0.3 0.3

800/1600 7524A52G11 0.3 0.3 0.3 0.6 1.2 ②

0.3 0.3 0.3 0.3 0.3

1000/2000 7524A52G12 0.3 0.3 0.3 0.3 0.6 ②

0.3 0.3 0.3 0.3 0.3

1500/3000 7524A52G13 0.3 0.3 0.3 0.3 0.3 ②

0.3 0.3 0.3 0.3 0.3

2000/4000 7524A52G14 0.3 0.3 0.3 0.3 0.3 ②

0.3 0.3 0.3 0.3 0.3

1000 9625A21G01 0.3 0.3 0.3 0.32000 9625A21G02 0.3 0.3 0.3 0.3 0.33000 9625A21G03 0.3 0.3 0.3 0.3 0.34000 9625A21G04 0.3 0.3 0.3 0.3 0.3

1000/2000 9625A21G05 0.3 0.3 0.3 0.3 ②

0.3 0.3 0.3 0.3 0.3

1500/3000 9625A21G06 0.3 0.3 0.3 0.3 0.3 ②

0.3 0.3 0.3 0.3 0.3

2000/4000 9625A21G07 0.3 0.3 0.3 0.3 0.3 ②

0.3 0.3 0.3 0.3 0.3

20

600 V CURRENT TRANSFORMERS

TYPE RRLLCC

② Tap Connection X2-X3*Accuracy 20% less at 50 Hertz.

Standard

Hi RelayAccuracy

Window Dia.5.50 In.

600 VoltsIndoor/Outdoor10 kV BIL50/60 Hertz

Page 23: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

Relay* RatingAccuracy Factor Height Width Length Weight

C100 2.00 11.25 10.50 4.12 21.0C100 2.00 11.25 10.50 4.12 21.0C100 2.00 11.25 10.50 4.12 21.0C100 2.00 11.25 10.50 4.12 21.0C200 2.00 11.25 10.50 4.12 21.0C200 2.00 11.25 10.50 4.12 21.0C200 1.50 11.25 10.50 4.12 21.0C200 1.33 11.25 10.50 4.12 21.0C200 1.33 11.25 10.50 4.12 21.0

C100 2.00 11.25 10.50 4.12 21.0C200 2.00

C100 2.00 11.25 10.50 4.12 21.0C200 1.50

C100 2.00 11.25 10.50 4.12 21.0C200 1.50

C100 1.50 11.25 10.50 4.12 21.0C200 1.33

C100 1.50 11.25 10.50 4.12 21.0C200 1.33

C200 2.00 11.25 10.50 4.12 29.0C400 1.50 11.25 10.50 4.12 29.0C400 1.50 11.25 10.50 4.12 29.0C400 1.50 11.25 10.50 4.12 29.0

C200 2.00 11.25 10.50 4.12 29.0C400 1.50 11.25 10.50 4.12 29.0

C200 1.50 11.25 10.50 4.12 29.0C400 1.33 11.25 10.50 4.12 29.0

C200 1.50 11.25 10.50 4.12 29.0C400 1.33 11.25 10.50 4.12 29.0

21

PB 42-828

Page 24: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

Style Winding Turns Winding TurnsRatio Number 1-2 2-3 3-4 5-6 7-8

Multi 7881A02G01 160 40 67 800 800Multi 7881A02G02 160 40 67 200 200Multi 7881A02G03 80 20 33 80 80Multi 7881A02G04 80 20 33 800 800Multi 7881A02G05 80 20 33 400 400Multi 7881A02G06 80 20 33 100 100Multi 7881A02G07 195 7 32 117 117Multi 7881A03G01 125 25 50 25 25Multi 7881A03G02 160 40 67 40 40Multi 7881A03G03 160 40 67 80 80Multi 7881A03G04 160 40 67 400 400

5:5 7881A01G01 140 14010:5 7881A01G02 70 14015:5 7881A01G03 47 141

22

1 2 3 4

5 6 7 8

IndoorTest Voltage: 2500 Volts25 Through 60 Hertz

Multi-Ratio Winding Developmenttapped wdg.

2 part wdg.

TYPE A CCUURRRREENNTT BBAALLAANNCCIINNGG AAUUTTOOIndoor Test Voltage: 2500 Volts25 Through 60 Hertz Type A transformers provide alarge number of fine ratioadjustment taps for establishingan exact current ratio balancebetween the CT's on the inputand output sides of powertransformers.

Volt-Ampere Style Ratio Adjustment RangeRating Number

50 7881A17G01 from 10.8:5 to 5:5 Amps.

100 7881A17G02 from 10.8:5 to 5:5 Amps.

600 V CURRENT TRANSFORMERS

AAUUXXIILLIIAARRYY

Page 25: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

23

PB 42-850

Typical Accuracy Values at 800 Ampere turns are:Relay MeterMulti-Ratio: T50 0.3 thru B0.5, 0.6 thru B1.8Single Ratio: T50 Same

Dimensions & WeightsMulti-Ratio Single-Ratio

Height 7.00 6.37Width 5.50 5.75Length 8.50 7.75Weight 23.00 23.00

Auxiliary CT's offer a wide selection of turns ratios for use inchanging the overall ratio of main CT's. Available ratios canbe determined from the wdg. turns tabulation. The max.continuous current rating of multi-ratio transformers can becalculated as follows:

Single ratio auxiliary CTs have a nominal output of 5 amperesand a continuous current rating factor of 1.33.

PB 42-852

Page 26: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

24

Primary Style IEEE Meter Accuracy ①

Amps Number B0.1 B0.2 B0.5 B1.8

600 7881A86G01 0.3 0.3 0.3 1.2600 7881A86G02 0.6 0.6 0.6 1.2600 7881A86G03 0.6 0.6 0.6 1.2600 7881A86G04 0.6 0.6 1.2

1200 7881A86G05 0.3 0.3 0.3 0.31200 7881A86G06 0.3 0.3 0.3 0.61200 7881A86G07 0.3 0.3 0.3 0.61200 7881A86G08 0.3 0.3 0.6 0.6

2000 7881A86G09 0.3 0.3 0.3 0.32000 7881A86G10 0.3 0.3 0.3 0.32000 7881A86G11 0.3 0.3 0.3 0.32000 7881A86G12 0.3 0.3 0.3 0.6

3000 7881A86G51 0.3 0.3 0.3 0.33000 7881A86G52 0.3 0.3 0.3 0.33000 7881A86G53 0.3 0.3 0.3 0.33000 7881A86G54 0.3 0.3 0.3 0.3

600 V CURRENT TRANSFORMERS

TYPE OOBBCCTT

① Applies to Normal Ratio Only (Full Winding)

Note: When stacking two bushing current transformers on a common bushing,

20 10 50 40Turns Turns Turns Turns

40 20 100 80Turns Turns Turns Turns

80 160 60 100Turns Turns Turns Turns

200 240 60 100Turns Turns Turns Turns

Mounting Brackets, includes mounting hardware

Inside ANSI Bushing Flange CharacteristicsDiameter Bolt Circle Diameter and Number of Bolts and Bolt Size

12 589B864G01 589B864G01 589B864G0218 .................... .................... 589B864G0422 .................... .................... ....................32 .................... .................... ....................

Page 27: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

25

Relay ① Case CaseAccuracy ID OD Height Weight

C400 12 24.1 6.37 240C400 18 30.4 6.37 330C400 22 34.5 6.37 400C400 32 44.6 6.37 550

C800 12 24.1 6.37 240C800 18 30.4 6.37 330C800 22 34.5 6.37 400C800 32 44.6 6.37 550

C800 12 23.5 4.94 155C800 18 29.7 4.94 210C800 22 33.7 4.94 245C800 32 43.8 4.94 340

C800 12 22.6 4.75 125C800 18 28.4 4.56 160C800 22 32.6 4.56 190C800 32 42.7 4.56 260

PB 42-858

bracket 589B864G07 should also be ordered

Multi-Ratio, Externally Mounted Test Voltage: 2500 Volts 25-60 Hertz

.................... .................... .................... ....................

.................... .................... .................... ....................589B864G03 589B864G04 589B864G05 ........................................ .................... .................... 589B864G06

Page 28: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

26

Primary Style Voltage Ratio Number

TYPE PPW

240/416Y 2:1 7526A04G01288/500Y 2.4:1 7526A04G02300/520Y 2.5:1 7526A04G03480/480Y 4:1 7526A04G04600/600Y 5:1 7526A04G05

TYPE PPM

240/416Y 2:1 7526A10G01288/500Y 2.4:1 7526A10G02300/520Y 2.5:1 7526A10G03480/480Y 4:1 7526A10G04600/600Y 5:1 7526A10G05120/120Y 1:1 7526A10G06480/480Y 2:1 9628A88G07*

TYPE PPX

120/208Y 1:1 7525A16G01①

69.4/120Y .578:1 7525A16G03400/400Y 3.33:1 7525A16G04①

120 to 70 1.714:1 7525A16G05①

207.8/360Y 1.732:1 7525A16G0960/104Y .500:1 7525A16G10①

600 V VOLTAGE TRANSFORMERS

TYPE PPPPWW PB 42-871

① 50 /60 Hertz* 240 V Secondary

600 Volts, Indoor and Outdoor10 kV BIL, 60 Hertz

PPW Thermal Rating:150 Va at 30º C ambient100 Va at 55º C ambient

Page 29: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

27

IEEE MeterAccuracy Height Width Length Weight

0.3 Class 4.62 4.50 5.00 9for W 4.62 4.50 5.00 90.6 Class 4.62 4.50 5.00 9for X 4.62 4.50 5.00 9Burdens 4.62 4.50 5.00 9

0.3 Class 5.87 5.87 6.12 19for 5.87 5.87 6.12 19W, X, M & Y 5.87 5.87 6.12 19Burdens 5.87 5.87 6.12 19

5.87 5.87 6.12 195.87 5.87 6.12 195.87 5.87 6.12 19

0.6W-Y 5.87 5.87 6.12 190.3W, 0.6X-Y 5.87 5.87 6.12 190.3W, 0.6X-Y 5.87 5.87 6.12 190.3W, 0.6X-Y 5.87 5.87 6.12 190.3W-Y 5.87 5.87 6.12 190.6W-Y 5.87 5.87 6.12 19

TYPE PPPPMM aanndd PPPPXX PB 42-873

600 Volts, Indoor and Outdoor10 kV BIL, 60 Hertz

PPM Thermal Rating:500 Va at 30º C ambient350 Va at 55º C ambientPPX Thermal Rating:500 Va at 30º C ambient

Page 30: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

28

Primary Style IEEE MeterAmps Number Accuracy

5 7524A01G0110 7524A01G0215 7524A01G0320 7524A01G0425 7524A01G0530 7524A01G0640 7524A01G07 0.3 B0.150 7524A01G08 through75 7524A01G09 B1.8100 7524A01G10 All Ratings150 7524A01G11200 7524A01G12300 7524A01G13400 7524A01G14600 7524A01G15800 7524A01G161200 7524A01G201000 7524A01G21

5 7524A02G0110 7524A02G0215 7524A02G0320 7524A02G0425 7524A02G0530 7524A02G06 0.3 B0.140 7524A02G07 through50 7524A02G08 B1.875 7524A02G09 All Ratings100 7524A02G10150 7524A02G11200 7524A02G12300 7524A02G13400 7524A02G14600 7524A02G15800 7524A02G16

5 kV-8.7 kV CURRENT TRANSFORMERS

TYPE KKIIRR--6600 AANNDD KKIIRR--7755

*Accuracy 20% less at 50 Hertz.

Mechanical Rating:5 thru 600 Amps, 150 x normal

800 Amps, 110 x normalThermal Rating:

5 thru 600 Amps, 100 x normal for 1 second800 Amps, 75 x normal for 1 second

Indoor 60,75 kV BIL50/60 Hertz*

NSV 5.0 kV 60 kV BIL

NSV 8.7 kV 75 kV BIL

Page 31: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

29

IEEE Relay* RatingAccuracy Factor Height Width Length Weight

T100 1.50 8.06 6.12 15.0 35T100 1.50 8.06 6.12 15.0 35T100 1.50 8.06 6.12 15.0 35T100 1.50 8.06 6.12 15.0 35T100 1.50 8.06 6.12 15.0 35T100 1.50 8.06 6.12 15.0 35T100 1.50 8.06 6.12 15.0 35T100 1.50 8.06 6.12 15.0 35T100 1.50 8.06 6.12 15.0 35T100 1.50 8.06 6.12 15.0 35T100 1.50 8.06 6.12 15.0 35T100 1.50 8.06 6.12 15.0 35T100 1.50 8.06 6.12 15.0 38T100 1.50 8.06 6.12 15.0 38T100 1.50 8.06 6.12 15.0 38T100 1.33 8.06 6.12 15.0 38T100 1.00 8.06 6.12 15.0 39T100 1.33 8.06 6.12 15.0 38

T100 1.50 10.3 6.12 16.0 36T100 1.50 10.3 6.12 16.0 36T100 1.50 10.3 6.12 16.0 36T100 1.50 10.3 6.12 16.0 36T100 1.50 10.3 6.12 16.0 36T100 1.50 10.3 6.12 16.0 36T100 1.50 10.3 6.12 16.0 36T100 1.50 10.3 6.12 16.0 36T100 1.50 10.3 6.12 16.0 36T100 1.50 10.3 6.12 16.0 36T100 1.50 10.3 6.12 16.0 36T100 1.50 10.3 6.12 16.0 36T100 1.50 10.3 6.12 16.0 39T100 1.50 10.3 6.12 16.0 39T100 1.50 10.3 6.12 16.0 39T100 1.33 10.3 6.12 16.0 39

PB 42-914

Page 32: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

Primary Style IEEE MeterAmps Number Accuracy

5 7524A03G0110 7524A03G0215 7524A03G0320 7524A03G0425 7524A03G0530 7524A03G0640 7524A03G07 0.3 B0.150 7524A03G08 through75 7524A03G09 B1.8100 7524A03G10 All Ratings150 7524A03G11200 7524A03G12300 7524A03G13400 7524A03G14600 7524A03G16800 7524A03G171200 7524A03G181000 7524A03G21

5/10 7524A04G0110/20 7524A04G0220/40 7524A04G0325/50 7524A04G04 0.350/100 7524A04G05 B0.175/150 7524A04G06 through100/200 7524A04G07 B1.8 Full150/300 7524A04G08 B0.9 Tap200/400 7524A04G09 All Ratings300/600 7524A04G10400/800 7524A04G11600/1200 7524A04G14

30

15 kV CURRENT TRANSFORMERS

TYPE KKIIRR--1111

*Accuracy 20% less at 50 Hertz.

Mechanical Rating:5 thru 600 Amps, 150 x normal

800 Amps, 110 x normal Thermal Rating:

5 thru 600 Amps, 100 x normal for 1 second800 Amps, 75 x normal for 1 second

Indoor 110 kV BIL50/60 Hertz*

NSV 15.0 kV 110 kV BILSingle Ratio

NSV 15.0 kV 110 kV BILDouble Ratio

Page 33: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

IEEE Relay* RatingAccuracy Factor Height Width Length Weight

T200 1.50 9.87 6.75 23 56T200 1.50 9.87 6.75 23 56T200 1.50 9.87 6.75 23 56T200 1.50 9.87 6.75 23 56T200 1.50 9.87 6.75 23 56T200 1.50 9.87 6.75 23 56T200 1.50 9.87 6.75 23 56T200 1.50 9.87 6.75 23 56T200 1.50 9.87 6.75 23 56T200 1.50 9.87 6.75 23 56T200 1.50 9.87 6.75 23 56T200 1.50 9.87 6.75 23 56T200 1.50 9.87 6.75 23 61T200 1.50 9.87 6.75 23 61T200 1.50 9.87 6.75 23 61T200 1.33 9.87 6.75 23 61T200 1.00 9.87 6.75 23 62T200 1.33 9.87 6.75 23 61

T90/T200 2.0/1.5 9.87 6.75 23 56T90/T200 2.0/1.5 9.87 6.75 23 56T90/T200 2.0/1.5 9.87 6.75 23 56T90/T200 2.0/1.5 9.87 6.75 23 56T90/T200 2.0/1.5 9.87 6.75 23 56T90/T200 2.0/1.5 9.87 6.75 23 56T90/T200 2.0/1.5 9.87 6.75 23 56T90/T200 2.0/1.5 9.87 6.75 23 61T90/T200 2.0/1.5 9.87 6.75 23 61T90/T200 2.0/1.5 9.87 6.75 23 61T100/T200 2.0/1.33 9.87 6.75 23 61T90/T200 2.0/1.0 9.87 6.75 23 62

31

PB 42-914

Page 34: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

Primary Style IEEE MeterAmps Number Accuracy

5 7524A10G0110 7524A10G0215 7524A10G0320 7524A10G0425 7524A10G0530 7524A10G06 0.3 B0.140 7524A10G07 through50 7524A10G08 B1.875 7524A10G09 All Ratings100 7524A10G10150 7524A10G11200 7524A10G12300 7524A10G13400 7524A10G14600 7524A10G15800 7524A10G161000 7524A10G17

5 7524A11G0110 7524A11G0215 7524A11G0320 7524A11G0425 7524A11G0530 7524A11G06 0.3 B0.140 7524A11G07 through50 7524A11G08 B1.875 7524A11G09 All Ratings100 7524A11G10150 7524A11G11200 7524A11G12300 7524A11G13400 7524A11G14600 7524A11G15800 7524A11G161000 7524A11G17

32

5 kV-8.7 kV CURRENT TRANSFORMERS

TYPE KKOORR--6600 aanndd KKOORR--7755

*Accuracy 20% less at 50 Hertz.

Outdoor60 kV and 75 kV BIL50/60 Hertz

Mechanical Rating:5 thru 400 Amp;

150 x normal600-1000 Amp;

110 x normal Thermal Rating:

5 thru 600 Amp;100 x normal for 1 second

800 Amp;75 x normal for 1 second

1000 Amp;50 x normal for 1 second

NSV 5.0 kV 60 kV BIL

NSV 8.7 kV 75 kV BIL

Page 35: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

IEEE Relay* RatingAccuracy Factor Height Width Length Weight

T100 1.50 12.3 9.37 11.00 41T100 1.50 12.3 9.37 11.00 41T100 1.50 12.3 9.37 11.00 41T100 1.50 12.3 9.37 11.00 41T100 1.50 12.3 9.37 11.00 41T100 1.50 12.3 9.37 11.00 41T100 1.50 12.3 9.37 11.00 41T100 1.50 12.3 9.37 11.00 41T100 1.50 12.3 9.37 11.00 41T100 1.50 12.3 9.37 11.00 41T100 1.50 12.3 9.37 11.00 41T100 1.50 12.3 9.37 11.00 45T100 1.50 12.3 9.37 11.00 45T100 1.50 12.3 9.37 11.00 45T100 1.50 12.3 9.37 11.00 45T100 1.33 12.3 9.37 11.00 45T70 1.33 12.3 9.37 11.00 45

T100 1.50 12.3 9.37 11.00 41T100 1.50 12.3 9.37 11.00 41T100 1.50 12.3 9.37 11.00 41T100 1.50 12.3 9.37 11.00 41T100 1.50 12.3 9.37 11.00 41T100 1.50 12.3 9.37 11.00 41T100 1.50 12.3 9.37 11.00 41T100 1.50 12.3 9.37 11.00 41T100 1.50 12.3 9.37 11.00 41T100 1.50 12.3 9.37 11.00 41T100 1.50 12.3 9.37 11.00 41T100 1.50 12.3 9.37 11.00 45T100 1.50 12.3 9.37 11.00 45T100 1.50 12.3 9.37 11.00 45T100 1.50 12.3 9.37 11.00 45T100 1.33 12.3 9.37 11.00 45T70 1.33 12.3 9.37 11.00 45

33

PB 42-920

Page 36: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

Primary Style IEEE MeterAmps Number Accuracy

5 7524A12G0110 7524A12G0215 7524A12G0320 7524A12G0425 7524A12G0530 7524A12G06 0.3 B0.140 7524A12G07 through50 7524A12G08 B1.875 7524A12G09 All Ratings100 7524A12G10150 7524A12G11200 7524A12G12300 7524A12G13400 7524A12G14600 7524A12G15800 7524A12G161000 7524A12G181200 7524A12G17

5/10 7524A13G0110/20 7524A13G0220/40 7524A13G0325/50 7524A13G04 0.3 B0.150/100 7524A13G05 through75/150 7524A13G06 B1.8 Full100/200 7524A13G07 B0.9 Tap150/300 7524A13G08 All Ratings200/400 7524A13G09300/600 7524A13G10400/800 7524A13G11600/1200 7524A13G12

34

15 kV CURRENT TRANSFORMERS

TYPE KKOORR--1111

*Accuracy 20% less at 50 Hertz.

Outdoor110 kV BIL50/60 Hertz

Mechanical Rating:5 thru 600 Amp;

150 x normal800 Amp.

110 x normal

Thermal Rating:5 thru 600 Amp;

100 x normal for 1 second800 Amp.

75 x normal for 1 second

Page 37: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

IEEE Relay* RatingAccuracy Factor Height Width Length Weight

T200 1.50 15.7 10.8 12.5 70T200 1.50 15.7 10.8 12.5 70T200 1.50 15.7 10.8 12.5 70T200 1.50 15.7 10.8 12.5 70T200 1.50 15.7 10.8 12.5 70T200 1.50 15.7 10.8 12.5 70T200 1.50 15.7 10.8 12.5 70T200 1.50 15.7 10.8 12.5 70T200 1.50 15.7 10.8 12.5 70T200 1.50 15.7 10.8 12.5 70T200 1.50 15.7 10.8 12.5 70T200 1.50 15.7 10.8 12.5 73T200 1.50 15.7 10.8 12.5 73T200 1.50 15.7 10.8 12.5 73T200 1.50 15.7 10.8 12.5 73T200 1.33 15.7 10.8 12.5 73T150 1.50 15.7 10.8 12.5 73T200 1.50 15.7 10.8 12.5 73

T90/T200 2.0/1.5 15.7 10.8 12.5 70T90/T200 2.0/1.5 15.7 10.8 12.5 70T90/T200 2.0/1.5 15.7 10.8 12.5 70T90/T200 2.0/1.5 15.7 10.8 12.5 70T90/T200 2.0/1.5 15.7 10.8 12.5 70T90/T200 2.0/1.5 15.7 10.8 12.5 70T90/T200 2.0/1.5 15.7 10.8 12.5 73T90/T200 2.0/1.5 15.7 10.8 12.5 73T90/T200 2.0/1.5 15.7 10.8 12.5 73T90/T200 2.0/1.5 15.7 10.8 12.5 73T100/T200 2.0/1.33 15.7 10.8 12.5 73T90/T200 2.0/1.5 15.7 10.8 12.5 73

35

PB 42-922

Page 38: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

36

15 kV CURRENT TRANSFORMERS

TYPE KKOONN--1111

*Accuracy 20% less at 50 Hertz.

Outdoor110 kV BIL50/60 Hertz

Mechanical Rating:All Ratings 270 x normal

Thermal Rating:All Ratings 190 x normal,

1 second

Primary Style IEEE MeterAmps Number Accuracy

5 7524A25G16

10 7524A25G01

15 7524A25G02

20 7524A25G03

25 7524A25G04

30 7524A25G05

40 7524A25G06

50 7524A25G07 0.3 B0.1,

75 7524A25G08 B0.2, B0.5

100 7524A25G09 All Ratings

150 7524A25G10

200 7524A25G11

300 7524A25G12

400 7524A25G13

600 7524A25G14

800 7524A25G15

1000 7524A25G18

1200 7524A25G19

Page 39: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

37

PB 42-924

IEEE Relay* RatingAccuracy Factor Height Width Length Weight

C40 3.0 13.5 10.8 12.4 37

C40 3.0 13.5 10.8 12.4 37

C40 3.0 13.5 10.8 12.4 37

C40 3.0 13.5 10.8 12.4 37

C40 3.0 13.5 10.8 12.4 37

C40 3.0 13.5 10.8 12.4 37

C40 3.0 13.5 10.8 12.4 37

C40 3.0 13.5 10.8 12.4 37

C40 3.0 13.5 10.8 12.4 37

C40 3.0 13.5 10.8 12.4 37

C40 3.0 13.5 10.8 12.4 41

C40 3.0 13.5 10.8 12.4 41

C40 3.0 13.5 10.8 12.4 41

C40 3.0 13.5 10.8 12.4 41

C40 2.0 13.5 10.8 12.4 41

C40 1.5 13.5 10.8 12.4 41

C40 1.2 13.5 10.8 12.4 41

C40 1.0 13.5 10.8 12.4 41

Page 40: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

Primary Style IEEE MeterAmps Number Accuracy

5 923A185G0110 923A185G0215 923A185G0320 923A185G0425 923A185G05 0.3 B0.1,30 923A185G06 through40 923A185G07 B0.950 923A185G08 All Ratings75 923A185G09100 923A185G10150 923A185G11200 923A185G12300 923A185G13400 923A185G14500 923A185G15600 923A185G16800 923A185G171200 923A185G18

5/10 923A186G0110/20 923A186G0220/40 923A186G03 0.3 B0.1 through25/50 923A186G04 B0.9 Tap50/100 923A186G05 B1.8 Full75/150 923A186G06 All Ratings100/200 923A186G07150/300 923A186G08200/400 923A186G09300/600 923A186G10400/800 923A186G11600/1200 923A186G12

38 *Accuracy 20% less at 50 Hertz.

Single Ratio

Double Ratio

Mechanical Rating:All styles single ratio290 x normal All styles double ratio290 TAP145 FULL

Thermal Rating:All styles 100 x normal,

1 second

25 kV CURRENT TRANSFORMERS

TYPE KKOORR--1155CC (THIS REPLACES KOR-15AND KOR-15B)

Page 41: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

39

Outdoor150 kV BIL50/60 Hertz

IEEE Relay* RatingAccuracy Factor Height Width Length Weight

3.0 17.9 10.9 13.9 903.0 17.9 10.9 13.9 903.0 17.9 10.9 13.9 903.0 17.9 10.9 13.9 90

C100 3.0 17.9 10.9 13.9 90All Ratings 3.0 17.9 10.9 13.9 90

3.0 17.9 10.9 13.9 903.0 17.9 10.9 13.9 903.0 17.9 10.9 13.9 903.0 17.9 10.9 13.9 903.0 17.9 10.9 13.9 903.0 17.9 10.9 13.9 953.0 17.9 10.9 13.9 953.0 17.9 10.9 13.9 952.0 17.9 10.9 13.9 952.0 17.9 10.9 13.9 951.5 17.9 10.9 13.9 951.0 17.9 10.9 13.9 95

3.0/1.5 17.9 10.9 13.9 903.0/1.5 17.9 10.9 13.9 90

C100 Tap 3.0/1.5 17.9 10.9 13.9 90C200 Full 3.0/1.5 17.9 10.9 13.9 90All Ratings 3.0/1.5 17.9 10.9 13.9 90

3.0/1.5 17.9 10.9 13.9 903.0/1.5 17.9 10.9 13.9 953.0/1.5 17.9 10.9 13.9 953.0/1.5 17.9 10.9 13.9 953.0/1.5 17.9 10.9 13.9 953.0/1.5 17.9 10.9 13.9 952.0/1.0 17.9 10.9 13.9 95

PB 42-927

Page 42: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

Primary Style IEEE MeterAmps Number Accuracy

10 7524A22G0115 7524A22G0220 7524A22G0325 7524A22G0430 7524A22G0540 7524A22G06 0.3 B0.1,50 7524A22G07 B0.2, B0.5,75 7524A22G08 B0.9100 7524A22G09 All Ratings150 7524A22G10200 7524A22G11300 7524A22G12400 7524A22G13500 7524A22G14600 7524A22G15800 7524A22G161200 7524A22G17

5/10 7524A21G0110/20 7524A21G0220/40 7524A21G03 0.3 B0.1 through25/50 7524A21G04 B0.9 Tap50/100 7524A21G05 B1.8 Full75/150 7524A21G06 All Ratings100/200 7524A21G07150/300 7524A21G08200/400 7524A21G09300/600 7524A21G10400/800 7524A21G11600/1200 7524A21G12

40 *Accuracy 20% less at 50 Hertz.

36 kV CURRENT TRANSFORMERS

TYPE KKOORR--2200

NSV 36 kV 200 kV BILSingle Ratio

NSV 36 kV 200 kV BILDouble Ratio

Page 43: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

IEEE Relay* RatingAccuracy Factor Height Width Length Weight

3.0 20.9 11.2 13.9 1123.0 20.9 11.2 13.9 1123.0 20.9 11.2 13.9 1123.0 20.9 11.2 13.9 1123.0 20.9 11.2 13.9 112

C100 3.0 20.9 11.2 13.9 112All Ratings 3.0 20.9 11.2 13.9 112

3.0 20.9 11.2 13.9 1123.0 20.9 11.2 13.9 1123.0 20.9 11.2 13.9 1123.0 20.9 11.2 13.9 1203.0 20.9 11.2 13.9 1203.0 20.9 11.2 13.9 1202.0 20.9 11.2 13.9 1202.0 20.9 11.2 13.9 1201.5 20.9 11.2 13.9 1201.0 20.9 11.2 13.9 120

3.0 Tap 20.9 11.2 13.9 1121.5 Full 20.9 11.2 13.9 112

C100 Tap 20.9 11.2 13.9 112C200 Full 20.9 11.2 13.9 112All Ratings 20.9 11.2 13.9 112

20.9 11.2 13.9 11220.9 11.2 13.9 12020.9 11.2 13.9 12020.9 11.2 13.9 12020.9 11.2 13.9 12020.9 11.2 13.9 120

2.0/1.0 20.9 11.2 13.9 120

41

PB 42-928A

Outdoor200 kV BIL50/60 Hertz

Page 44: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

42 *Accuracy 20% less at 50 Hertz.

Primary Style IEEE MeterAmps Number Accuracy

800 7524A32G01 0.3B0.91200 7524A32G02 0.3B1.81500 7524A32G03 0.3B1.82000 7524A32G04 0.3B1.83000 7524A32G05 0.3B1.84000 7524A32G06 0.3B1.8600/1200 7524A32G07 0.3B0.5 Tap

B1.8 Full1000/2000 7524A32G08 0.3B0.9 Tap

B1.8 Full2000/4000 7524A32G09 0.3B1.8 Tap

B1.8 Full

800 7524A33G01 0.3B0.91200 7524A33G02 0.3B1.81500 7524A33G03 0.3B1.82000 7524A33G04 0.3B1.83000 7524A33G05 0.3B1.84000 7524A33G06 0.3B1.8600/1200 7524A33G07 0.3B0.5 Tap

B1.8 Full1000/2000 7524A33G08 0.3B0.9 Tap

B1.8 Full2000/4000 7524A33G09 0.3B1.8 Tap

B1.8 Full

800 7524A34G01 0.3B0.91200 7524A34G02 0.3B1.81500 7524A34G03 0.3B1.82000 7524A34G04 0.3B1.83000 7524A34G05 0.3B1.84000 7524A34G06 0.3B1.8600/1200 7524A34G07 0.3B0.5 Tap

B1.8 Full1000/2000 7524A34G08 0.3B0.9 Tap

B1.8 Full2000/4000 7524A34G09 0.3B1.8 Tap

B1.8 Full

800 7524A35G01 0.3B0.91200 7524A35G02 0.3B1.81500 7524A35G03 0.3B1.82000 7524A35G04 0.3B1.83000 7524A35G05 0.3B1.84000 7524A35G06 0.3B1.8600/1200 7524A35G07 0.3B0.5 Tap

B1.8 Full1000/2000 7524A35G08 0.3B0.9 Tap

B1.8 Full2000/4000 7524A35G09 0.3B1.8 Tap

B1.8 Full

5 kV-25 kV CURRENT TRANSFORMERS

TYPE KKOOTT

Outdoor60, 75, 110, 150 kV BIL50/60 Hertz

Tube Type3.25 in. ID

KOT-60Tube Type

NSV 5.0 kV 60 kV BIL

KOT-75Tube Type

NSV 8.7 kV 75 kV BIL

KOT-11Tube Type

NSV 15.0 kV 110 kV BIL

KOT-15Tube Type

NSV 25 kV 150 kV BIL

Page 45: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

43Continued on Next Page

IEEE Relay* RatingAccuracy Factor Height Width Length Weight

C100 2.0 17.25 10.50 10.25 40C200 2.0 17.25 10.50 10.25 40C200 2.0 17.25 10.50 10.25 40C200 2.0 17.25 10.50 10.25 40C200 1.5 17.25 10.50 10.25 40C200 1.5 17.25 10.50 10.25 40C100/C200 3.0/2.0 17.25 10.50 10.25 40

C100/C200 3.0/2.0 17.25 10.50 10.25 40

C100/C200 2.0/1.5 17.25 10.50 10.25 40

C100 2.0 17.25 10.50 13.25 43C200 2.0 17.25 10.50 13.25 43C200 2.0 17.25 10.50 13.25 43C200 2.0 17.25 10.50 13.25 43C200 1.5 17.25 10.50 13.25 43C200 1.5 17.25 10.50 13.25 43C100/C200 3.0/2.0 17.25 10.50 13.25 43

C100/C200 3.0/2.0 17.25 10.50 13.25 43

C100/C200 2.0/1.5 17.25 10.50 13.25 43

C100 2.0 17.25 10.50 17.75 47C200 2.0 17.25 10.50 17.75 47C200 2.0 17.25 10.50 17.75 47C200 2.0 17.25 10.50 17.75 47C200 1.5 17.25 10.50 17.75 47C200 1.5 17.25 10.50 17.75 47C100/C200 3.0/2.0 17.25 10.50 17.75 47

C100/C200 3.0/2.0 17.25 10.50 17.75 47

C100/C200 2.0/1.5 17.25 10.50 17.75 47

C100 2.0 17.25 10.50 26.75 52C200 2.0 17.25 10.50 26.75 52C200 2.0 17.25 10.50 26.75 52C200 2.0 17.25 10.50 26.75 52C200 1.5 17.25 10.50 26.75 52C200 1.5 17.25 10.50 26.75 52C100/C200 3.0/2.0 17.25 10.50 26.75 52

C100/C200 3.0/2.0 17.25 10.50 26.75 52

C100/C200 2.0/1.5 17.25 10.50 26.75 52

PB 42-930

Mechanical Rating:All units: effectively unlimited Thermal Rating:

800 and 1200 Amp 80 x normal, 1 second

1500 Amp and above 100 x normal, 1 second

Page 46: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

44 *Accuracy 20% less at 50 Hertz.

Primary Style IEEE MeterAmps Number Accuracy

800 7524A36G01 0.3B0.91200 7524A36G02 0.3B1.81500 7524A36G03 0.3B1.82000 7524A36G04 0.3B1.83000 7524A36G05 0.3B1.84000 7524A36G06 0.3B1.8600/1200 7524A36G07 0.3B0.5 Tap

B1.8 Full1000/2000 7524A36G08 0.3B0.9 Tap

B1.8 Full2000/4000 7524A36G09 0.3B1.8 Tap

B1.8 Full

800 7524A37G01 0.3B0.91200 7524A37G02 0.3B1.81500 7524A37G03 0.3B1.82000 7524A37G04 0.3B1.83000 7524A37G05 0.3B1.84000 7524A37G06 0.3B1.8600/1200 7524A37G07 0.3B0.5 Tap

B1.8 Full1000/2000 7524A37G08 0.3B0.9 Tap

B1.8 Full2000/4000 7524A37G09 0.3B1.8 Tap

B1.8 Full

800 7524A38G01 0.3B0.91200 7524A38G02 0.3B1.81500 7524A38G03 0.3B1.82000 7524A38G04 0.3B1.83000 7524A38G05 0.3B1.84000 7524A38G06 0.3B1.8600/1200 7524A38G07 0.3B0.5 Tap

B1.8 Full1000/2000 7524A38G08 0.3B0.9 Tap

B1.8 Full2000/4000 7524A38G09 0.3B1.8 Tap

B1.8 Full

800 7524A39G01 0.3B0.91200 7524A39G02 0.3B1.81500 7524A39G03 0.3B1.82000 7524A39G04 0.3B1.83000 7524A39G05 0.3B1.84000 7524A39G06 0.3B1.8600/1200 7524A39G07 0.3B0.5 Tap

B1.8 Full1000/2000 7524A39G08 0.3B0.9 Tap

B1.8 Full2000/4000 7524A39G09 0.3B1.8 Tap

B1.8 Full

5 kV-25 kV CURRENT TRANSFORMERS

TYPE KKOOTT CON’T

Outdoor60, 75, 110, 150 kV BIL50/60 Hertz

base details on detailsprevious page

Bar Type

KOT-60Bar Type

NSV 5.0 kV 60 kV BIL

KOT-75Bar Type

NSV 8.7 kV 75 kV BIL

KOT-11Bar Type

NSV 15.0 kV 110 kV BIL

KOT-15Bar Type

NSV 25 kV 150 kV BIL

Page 47: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

45

IEEE Relay* RatingAccuracy Factor Height Width Length Weight

C100 2.00 17.25 10.50 19.62 62C200 2.00 17.25 10.50 19.62 62C200 2.00 17.25 10.50 19.62 62C200 1.50 17.25 10.50 19.62 62C200 1.33 17.25 10.50 19.62 73C200 1.00 17.25 10.50 19.62 73C100/C200 3.0/2.0 17.25 10.50 19.62 62

C100/C200 2.0/1.5 17.25 10.50 19.62 62

C100/C200 1.5/1.0 17.25 10.50 19.62 73

C100 2.00 17.25 10.50 22.62 67C200 2.00 17.25 10.50 22.62 67C200 2.00 17.25 10.50 22.62 67C200 1.50 17.25 10.50 22.62 67C200 1.33 17.25 10.50 22.62 79C200 1.00 17.25 10.50 22.62 79C100/C200 3.0/2.0 17.25 10.50 22.62 67

C100/C200 2.0/1.5 17.25 10.50 22.62 67

C100/C200 1.5/1.0 17.25 10.50 22.62 79

C100 2.00 17.25 10.50 27.12 75C200 2.00 17.25 10.50 27.12 75C200 2.00 17.25 10.50 27.12 75C200 1.50 17.25 10.50 27.12 75C200 1.33 17.25 10.50 27.12 89C200 1.00 17.25 10.50 27.12 89C100/C200 3.0/2.0 17.25 10.50 27.12 75

C100/C200 2.0/1.5 17.25 10.50 27.12 75

C100/C200 1.5/1.0 17.25 10.50 27.12 89

C100 2.00 17.25 10.50 36.12 90C200 2.00 17.25 10.50 36.12 90C200 2.00 17.25 10.50 36.12 90C200 1.50 17.25 10.50 36.12 90C200 1.33 17.25 10.50 36.12 107C200 1.00 17.25 10.50 36.12 107C100/C200 3.0/2.0 17.25 10.50 36.12 90

C100/C200 2.0/1.5 17.25 10.50 36.12 90

C100/C200 1.5/1.0 17.25 10.50 36.12 107

PB 42-930

Page 48: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

46 *Accuracy 20% less at 50 Hertz.

Primary Style IEEE MeterAmps Number Accuracy

200/400 923A142G01 0.3B0.5300/600 923A142G02 0.3B0.9400/800 923A142G03 0.3B1.8500/1000 923A142G04 0.3B1.8600/1200 923A142G05 0.3B1.8800/1600 923A142G06 0.3B1.81000/2000 923A142G07 0.3B1.81500/3000 923A142G08 0.3B1.82000/4000 923A142G09 0.3B1.82500/5000 923A142G10 0.3B1.8

200/400 923A156G01 0.3B0.5300/600 923A156G02 0.3B0.9400/800 923A156G03 0.3B1.8500/1000 923A156G04 0.3B1.8600/1200 923A156G05 0.3B1.8800/1600 923A156G06 0.3B1.81000/2000 923A156G07 0.3B1.81500/3000 923A156G08 0.3B1.82000/4000 923A156G09 0.3B1.82500/5000 923A156G10 0.3B1.8

200/400 923A170G01 0.3B0.5300/600 923A170G02 0.3B0.9400/800 923A170G03 0.3B1.8500/1000 923A170G04 0.3B1.8600/1200 923A170G05 0.3B1.8800/1600 923A170G06 0.3B1.81000/2000 923A170G07 0.3B1.81500/3000 923A170G08 0.3B1.82000/4000 923A170G09 0.3B1.82500/5000 923A170G10 0.3B1.8

5 kV-36 kV CURRENT TRANSFORMERS

TYPE KKOOTTDD

Outdoor110, 150, 200 kV BIL50/60 Hertz

Tube Type5 Inch ID

KOTD-110Tube Type

NSV 15 kV, 110 kV BIL

KOTD-150Tube Type

NSV 25 kV 150 kV BIL

KOTD-200Tube Type

NSV 36 kV, 200 kV BIL

Page 49: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

47Continued on Next Page

IEEE Relay* RatingAccuracy Factor Height Width Length Weight

C100/200 2.0/2.0 20.0 14.7 17.0 220C100/200 2.0/2.0 20.0 14.7 17.0 220C200/400 2.0/2.0 20.0 14.7 17.0 220C200/400 2.0/2.0 20.0 14.7 17.0 220C200/400 2.0/2.0 20.0 14.7 17.0 220C200/400 2.0/2.0 20.0 14.7 17.0 220C400/800 2.0/2.0 20.0 14.7 17.0 220C400/800 2.0/1.5 20.0 14.7 17.0 220C400/800 2.0/1.25 20.0 14.7 17.0 220C400/800 2.0/1.0 20.0 14.7 17.0 220

C100/200 2.0/2.0 22.5 14.7 17.0 245C100/200 2.0/2.0 22.5 14.7 17.0 245C200/400 2.0/2.0 22.5 14.7 17.0 245C200/400 2.0/2.0 22.5 14.7 17.0 245C200/400 2.0/2.0 22.5 14.7 17.0 245C200/400 2.0/2.0 22.5 14.7 17.0 245C400/800 2.0/2.0 22.5 14.7 17.0 245C400/800 2.0/1.5 22.5 14.7 17.0 245C400/800 2.0/1.25 22.5 14.7 17.0 245C400/800 2.0/1.0 22.5 14.7 17.0 245

C100/200 2.0/2.0 25.0 14.7 17.0 260C100/200 2.0/2.0 25.0 14.7 17.0 260C200/400 2.0/2.0 25.0 14.7 17.0 260C200/400 2.0/2.0 25.0 14.7 17.0 260C200/400 2.0/2.0 25.0 14.7 17.0 260C200/400 2.0/2.0 25.0 14.7 17.0 260C400/800 2.0/2.0 25.0 14.7 17.0 260C400/800 2.0/1.5 25.0 14.7 17.0 260C400/800 2.0/1.25 25.0 14.7 17.0 260C400/800 2.0/1.0 25.0 14.7 17.0 260

PB 42-940

BASEDETAILS

15.00

13.50

.75

.75

7.50

9.00

.56 DIA. HOLE4 TOTAL

FR

ON

T

PRIMARYPOLARITYMARKER

NAMEPLATE

Page 50: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

48

15 kV-36 kV CURRENT TRANSFORMERS

TYPE KKOOTTDD CON’T

Outdoor110, 150, 200 kV BIL50/60 Hertz

Bar Type

base detail on previous page

Primary Style IEEE MeterAmps Number Accuracy*

200/400 923A148G01 0.3B0.5300/600 923A148G02 0.3B0.9400/800 923A148G03 0.3B1.8500/1000 923A148G04 0.3B1.8600/1200 923A148G05 0.3B1.8800/1600 923A148G06 0.3B1.81000/2000 923A148G07 0.3B1.81500/3000 923A148G08 0.3B1.82000/4000 923A148G09 0.3B1.82500/5000 923A148G10 0.3B1.8

200/400 923A162G01 0.3B0.5300/600 923A162G02 0.3B0.9400/800 923A162G03 0.3B1.8500/1000 923A162G04 0.3B1.8600/1200 923A162G05 0.3B1.8800/1600 923A162G06 0.3B1.81000/2000 923A162G07 0.3B1.81500/3000 923A162G08 0.3B1.82000/4000 923A162G09 0.3B1.82500/5000 923A162G10 0.3B1.8

200/400 923A176G01 0.3B0.5300/600 923A176G02 0.3B0.9400/800 923A176G03 0.3B1.8500/1000 923A176G04 0.3B1.8600/1200 923A176G05 0.3B1.8800/1600 923A176G06 0.3B1.81000/2000 923A176G07 0.3B1.81500/3000 923A176G08 0.3B1.82000/4000 923A176G09 0.3B1.82500/5000 923A176G10 0.3B1.8

KOTD-110Bar Type

NSV 15 kV, 110 kV BIL

KOTD-150Bar Type

NSV 25 kV, 150 kV BIL

KOTD-200Bar Type

NSV 36 kV 200 kV BIL

*Accuracy 20% less at 50 Hertz.

Page 51: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

49

PB 42-940

IEEE Relay RatingAccuracy Factor Height Width Length Weight

C100/200 2.0/2.0 20.0 14.7 25.0 235C100/200 2.0/2.0 20.0 14.7 25.0 235C200/400 2.0/2.0 20.0 14.7 25.0 235C200/400 2.0/2.0 20.0 14.7 25.0 235C200/400 2.0/2.0 20.0 14.7 25.0 235C200/400 2.0/2.0 20.0 14.7 25.0 235C400/800 2.0/2.0 20.0 14.7 25.0 235C400/800 2.0/1.5 20.0 14.7 25.0 235C400/800 2.0/1.25 20.0 14.7 25.0 235C400/800 2.0/1.0 20.0 14.7 25.0 235

C100/200 2.0/2.0 22.5 14.7 25.0 260C100/200 2.0/2.0 22.5 14.7 25.0 260C200/400 2.0/2.0 22.5 14.7 25.0 260C200/400 2.0/2.0 22.5 14.7 25.0 260C200/400 2.0/2.0 22.5 14.7 25.0 260C200/400 2.0/2.0 22.5 14.7 25.0 260C400/800 2.0/2.0 22.5 14.7 25.0 260C400/800 2.0/1.5 22.5 14.7 25.0 260C400/800 2.0/1.25 22.5 14.7 25.0 260C400/800 2.0/1.0 22.5 14.7 25.0 260

C100/200 2.0/2.0 25.0 14.7 25.0 275C100/200 2.0/2.0 25.0 14.7 25.0 275C200/400 2.0/2.0 25.0 14.7 25.0 275C200/400 2.0/2.0 25.0 14.7 25.0 275C200/400 2.0/2.0 25.0 14.7 25.0 275C200/400 2.0/2.0 25.0 14.7 25.0 275C400/800 2.0/2.0 25.0 14.7 25.0 275C400/800 2.0/1.5 25.0 14.7 25.0 275C400/800 2.0/1.25 25.0 14.7 25.0 275C400/800 2.0/1.0 25.0 14.7 25.0 275

Page 52: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

50 ① Thermal and Accuracy ratings are at 120 V secondary voltage.

5 kV VOLTAGE TRANSFORMERS

TYPE VVIIYY--6600

Indoor60 kV BIL60 Hertz

Primary StyleVoltage Ratio Number

2400/4160Y 20:1 7525A50G014200/4200Y 35:1 7525A50G024800/4800Y 40:1 7525A50G03

2400/4160Y 20:1 7525A51G014200/4200Y 35:1 7525A51G024800/4800Y 40:1 7525A51G03

2400/4160GY 20:1 7525A52G014200/4200GY② 35:1 7525A52G024800/4800GY② 40:1 7525A52G03

Unfused

2 Fuses

1 Fuse

Thermal Rating①

1000 VA at 30ºC700 VA at 55ºC

Page 53: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

51② Fluxed for line-to-line Voltage; when connected line-to-ground,

normal secondary Voltage is 69.3 Volts.

PB 42-951

IEEE MeterAccuracy① Height Width Length Weight

0.3W, X, M, Y 6.90 6.37 9.31 320.3W, X, M, Y 6.90 6.37 9.31 320.3W, X, M, Y 6.90 6.37 9.31 32

0.3W, X, M, Y 8.25 6.75 10.00 360.3W, X, M, Y 8.25 6.75 10.00 360.3W, X, M, Y 8.25 6.75 10.00 36

0.3W, X, M, Y 8.56 6.37 10.00 340.3W, X, M, Y 8.56 6.37 10.00 340.3W, X, M, Y 8.56 6.37 10.00 34

Page 54: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

52

8.7 kV and 15 kVVOLTAGE TRANSFORMERS

TYPE VVIIZZ--7755 AANNDD VVIIZZ--1111

Indoor75 kV and 110 kV BIL60 Hertz

Primary StyleVoltage Ratio Number

2400/4160Y 20:1 7525A66G014200/7280Y 35:1 7525A66G024800/8320Y 40:1 7525A66G037200/7200Y 60:1 7525A66G04

7200/12470Y 60:1 7525A66G058400/14560Y 70:1 7525A66G0712000/12000Y 100:1 7525A66G0814400/14400Y 120:1 7525A66G10

2400/4160Y 20:1 7525A67G014200/7280Y 35:1 7525A67G024800/8320Y 40:1 7525A67G037200/7200Y 60:1 7525A67G04

7200/12470Y 60:1 7525A67G058400/14560Y 70:1 7525A67G0712000/12000Y 100:1 7525A67G0814400/14400Y 120:1 7525A67G10

2400/4160GY 20:1 7525A68G014200/7280GY 35:1 7525A68G024800/8320GY 40:1 7525A68G037200/7200GY② 60:1 7525A68G04

7200/12470GY 60:1 7525A68G058400/14560GY 70:1 7525A68G0712000/12000GY② 100:1 7525A68G0814400/14400GY② 120:1 7525A68G10

VIZ-7575 kV BILUnfused

VIZ-11110 kV BILUnfused

VIZ-7575 kV BIL2 Fuses

VIZ-11110 kV BIL

2 Fuses

VIZ-7575 kV BIL

1 Fuse

VIZ-11110 kV BIL

1 Fuse

Thermal Ratings:①

1500 VA at 30ºC1000 VA at 50ºC

① Thermal and Accuracy ratings are at 120 V secondary voltage.② Fluxed for line-to-line voltage; when connected line-to-ground,

normal secondary voltage is 69.3 Volts.

Page 55: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

53

PB 42-955

IEEE MeterAccuracy① Height Width Length Weight

0.3W, X, M, Y, Z 9.00 9.25 13.12 690.3W, X, M, Y, Z 9.00 9.25 13.12 690.3W, X, M, Y, Z 9.00 9.25 13.12 690.3W, X, M, Y, Z 9.00 9.25 13.12 69

0.3W, X, M, Y, Z 9.00 9.25 13.12 690.3W, X, M, Y, Z 9.00 9.25 13.12 690.3W, X, M, Y, Z 9.00 9.25 13.12 690.3W, X, M, Y, Z 9.00 9.25 13.12 69

0.3W, X, M, Y, Z 11.25 9.25 15.50 730.3W, X, M, Y, Z 11.25 9.25 15.50 730.3W, X, M, Y, Z 11.25 9.25 15.50 73

0.3W, X, M, Y, Z 11.25 9.25 15.50 730.3W, X, M, Y, Z 11.25 9.25 15.50 730.3W, X, M, Y, Z 11.25 9.25 15.50 730.3W, X, M, Y, Z 11.25 9.25 15.50 73

0.3W, X, M, Y, Z 12.18 9.25 15.50 710.3W, X, M, Y, Z 12.18 9.25 15.50 710.3W, X, M, Y, Z 12.18 9.25 15.50 71

0.3W, X, M, Y, Z 12.18 9.25 15.50 710.3W, X, M, Y, Z 12.18 9.25 15.50 710.3W, X, M, Y, Z 12.18 9.25 15.50 710.3W, X, M, Y, Z 12.18 9.25 15.50 71

Page 56: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

54

25 kV VOLTAGE TRANSFORMERS

TYPE VVIIZZZZ--1155 AANNDD VVIIZZZZ--1155GG

Indoor150 kV BIL60 Hertz

Available at other ratiosand single tappedsecondary or doublesecondary.

Thermal Ratings:3000 VA at 30ºC Ambient

Primary StyleVoltage Ratio Number

12000/20800Y 100:1 7525A82G0114400/24940Y 120:1 7525A82G0218000/18000Y 150:1 7525A82G0324000/24000Y 200:1 7525A82G04

12000/20800GY 100:1 7524A84G0114400/24940GY 120:1 7524A84G0220000/20000GY 166.67:1 7524A84G0324000/24000GY 200:1 7524A84G0418000/18000GY 150:1 7524A84G05

VIZZ-15150 kV BIL

*VIZZ-15G 150 kV BIL

*Single bushing

① Style with Clamp Type Primary Terminal. Stud Type available.

Page 57: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

55

PB 42-959

IEEE MeterAccuracy Height Width Length Weight

0.3W, X, M, Y, Z, ZZ 22.3 16.0 18.6 2050.3W, X, M, Y, Z, ZZ 22.3 16.0 18.6 2050.3W, X, M, Y, Z, ZZ 22.3 16.0 18.6 2050.3W, X, M, Y, Z, ZZ 22.3 16.0 18.6 205

0.3W, X, M, Y, Z, ZZ 22.3 15.6 18.6 2050.3W, X, M, Y, Z, ZZ 22.3 15.6 18.6 2050.3W, X, M, Y, Z, ZZ 22.3 15.6 18.6 2050.3W, X, M, Y, Z, ZZ 22.3 15.6 18.6 2050.3W, X, M, Y, Z, ZZ 22.3 15.6 18.6 205

Page 58: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

56

5 kV, 8.7 kV and 15 kVVOLTAGE TRANSFORMERS

TYPE VVOOYY--6600

TYPE VVOOZZ--7755 aanndd VVOOZZ--1111

Outdoor60 kV BIL60 Hertz

Thermal Rating:1000 VA at 30ºC ambient

Outdoor75 kV and 110 kV BIL60 Hertz

Thermal Rating:1500 VA at 30ºC ambient

Primary StyleVoltage Ratio Number

2400/4160Y 20:1 7525A85G014200/4200Y 35:1 7525A85G024800/4800Y 40:1 7525A85G03

2400/4160Y 20:1 7525A89G014200/7280Y 35:1 7525A89G024800/8320Y 40:1 7525A89G037200/7200Y 60:1 7525A89G04

7200/12470Y 60:1 7525A89G057620/13200Y 63.5:1 7525A89G068400/14560Y 70:1 7525A89G0712000/12000Y 100:1 7525A89G0813200/13200Y 110:1 7525A89G0914400/14400Y 120:1 7525A89G10

Page 59: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

57

PB 42-961A

PB 42-963

IEEE MeterAccuracy Height Width Length Weight

0.3W, X, M, Y 11.69 9.62 10.75 420.3W, X, M, Y 11.69 9.62 10.75 420.3W, X, M, Y 11.69 9.62 10.75 42

0.3W, X, M, Y, Z 15.81 11.67 13.94 740.3W, X, M, Y, Z 15.81 11.67 13.94 740.3W, X, M, Y, Z 15.81 11.67 13.94 740.3W, X, M, Y, Z 15.81 11.67 13.94 74

0.3W, X, M, Y, Z 15.81 11.67 13.94 740.3W, X, M, Y, Z 15.81 11.67 13.94 740.3W, X, M, Y, Z 15.81 11.67 13.94 740.3W, X, M, Y, Z 15.81 11.67 13.94 740.3W, X, M, Y, Z 15.81 11.67 13.94 740.3W, X, M, Y, Z 15.81 11.67 13.94 74

Page 60: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

58

15 kV VOLTAGE TRANSFORMERS

TYPE VVOOZZ--1111MM

TYPE VVOOYY--1111

Outdoor110 kV BIL60 Hertz

Thermal Rating:1500 VA at 30ºC ambient

Outdoor110 kV BIL60 Hertz

Thermal Rating:1500 VA at 30ºC ambient

Primary StyleVoltage Ratio Number

7200/12470GY 60:1 7525A91G057620/13200GY 63.5:1 7525A91G068400/14560GY 70:1 7525A91G07

Primary StyleVoltage Ratio Number

7200/12470Y 60:1 7525A23G057620/13200Y 63.5:1 7525A23G068400/14560Y 70:1 7525A23G0712000/12000Y 100:1 7525A23G0813200/13200Y 110:1 7525A23G0914400/14400Y 120:1 7525A23G10

TYPE VVOOGG--1111

Outdoor110 kV BIL60 Hertz

Thermal Rating:1000 VA at 30ºC ambient

Primary StyleVoltage Ratio Number

7200/12470GY 60:1 7525A95G017620/13200GY 63.5:1 7525A95G028400/14560GY 70:1 7525A95G03

VOZ-11M110 kV BIL

Page 61: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

59

PB 42-963A

PB 42-964

IEEE MeterAccuracy Height Width Length Weight

0.3W, X, M, Y, Z 15.81 12.13 13.94 740.3W, X, M, Y, Z 15.81 12.13 13.94 740.3W, X, M, Y, Z 15.81 12.13 13.94 74

IEEE MeterAccuracy Height Width Length Weight

0.3W, X, M, Y 15.81 12.13 13.94 740.3W, X, M, Y 15.81 12.13 13.94 740.3W, X, M, Y 15.81 12.13 13.94 740.3W, X, M, Y 15.81 12.13 13.94 740.3W, X, M, Y 15.81 12.13 13.94 740.3W, X, M, Y 15.81 12.13 13.94 74

PB 42-965

IEEE MeterAccuracy Height Width Length Weight

0.3W, X, M, Y 15.81 12.13 13.94 460.3W, X, M, Y 15.81 12.13 13.94 460.3W, X, M, Y 15.81 12.13 13.94 46

Page 62: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

60

25 kV VOLTAGE TRANSFORMERS

TYPE VVOOYY--1122

TYPE VVOOGG--1122

Outdoor125 kV BIL60 Hertz

Thermal Ratings:1000 VA at 30ºC ambient

Primary StyleVoltage Ratio Number

12000/20780Y 100:1 7525A87G0114400/24940Y 120:1 7525A87G0218000/18000Y 150:1 7525A87G0324000/24000Y 200:1 7525A87G04

Primary StyleVoltage Ratio Number

12000/20780GY 100:1 7525A97G0114400/24940GY 120:1 7525A97G02

VOY-12125 kV BIL

Thermal Ratings:750 VA at 30ºC ambient

Page 63: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

61

PB 42-966

PB 42-967

IEEE MeterAccuracy Height Width Length Weight

0.3W, X, M, Y 15.81 12.13 13.94 740.3W, X, M, Y 15.81 12.13 13.94 740.3W, X, M, Y 15.81 12.13 13.94 740.3W, X, M, Y 15.81 12.13 13.94 74

IEEE MeterAccuracy Height Width Length Weight

0.3W, X, M, Y 15.81 12.13 13.94 460.3W, X, M, Y 15.81 12.13 13.94 46

The mounting base isthe same as VOG-11

Page 64: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

62

25 kV VOLTAGE TRANSFORMERS

TYPE VVOOYY--1155 aanndd VVOOYY--1155GG

TYPE VVOOZZ--1155

Outdoor150 kV BIL60 Hertz

Primary StyleVoltage Ratio Number

12000/20780Y 100:1 7526A62G0114400/24940Y 120:1 7526A62G0218000/18000Y 150:1 7526A62G0320000/20000Y 166.7:1 7526A62G0424000/24000Y 200:1 7526A62G05

12000/20780GY 100:1 7526A63G0114400/24940GY 120:1 7526A63G02

Primary StyleVoltage Ratio Number

12000/20780Y 100:1 7525A90G0114400/24940Y 120:1 7525A90G0218000/18000Y 150:1 7525A90G0324000/24000Y 200:1 7525A90G04

Thermal Ratings:1000 VA at 30ºC ambient

Outdoor150 kV BIL60 Hertz

Thermal Ratings:2000 VA at 30ºC ambient

Page 65: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

63

PB 42-970

PB 42-971

IEEE MeterAccuracy Height Width Length Weight

0.3W, X, M, Y 19.00 15.87 16.94 1480.3W, X, M, Y 19.00 15.87 16.94 1480.3W, X, M, Y 19.00 15.87 16.94 1480.3W, X, M, Y 19.00 15.87 16.94 1480.3W, X, M, Y 19.00 15.87 16.94 148

0.3W, X, M, Y 19.00 13.81 16.94 1420.3W, X, M, Y 19.00 13.81 16.94 142

IEEE MeterAccuracy Height Width Length Weight

0.3W, X, M, Y, Z 19.00 15.87 16.94 1480.3W, X, M, Y, Z 19.00 15.87 16.94 1480.3W, X, M, Y, Z 19.00 15.87 16.94 1480.3W, X, M, Y, Z 19.00 15.87 16.94 148

Page 66: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

64

25 kV AND 36 kVVOLTAGE TRANSFORMERS

TYPE VVOOHHDD--220000 AANNDD VVOOHHDD--220000GG

Outdoor200 kV BIL60 Hertz

Primary StyleVoltage Ratio Number*

20125/34500Y 175/300:1 7882A31G01

27600/27600Y 240/400:1 7882A31G02

34500/34500Y 300/500:1 7882A31G03

20125/34500GY 175/300:1 9629A95G01

Thermal Ratings:1000 VA at 30ºC Ambient

TYPE VVOOZZZZ--1155 aanndd VVOOZZZZ--1155GG

Outdoor150 kV BIL60 Hertz

Primary StyleVoltage Ratio Number*

12000/20800Y 100:1 7525A93G01

14400/24940Y 120:1 7525A93G02

18000/18000Y 150:1 7525A93G03

24000/24000Y 200:1 7525A93G04

12000/20800GY 100:1 7525A98G0114400/24940GY 120:1 7525A98G02

Thermal Ratings:3000 VA at 30ºC Ambient

VOZZ-15150 kV BIL

VOZZ-15G 150 kV BIL

Single Bushing

Available with double secondaries andtapped double secondaries.

*Available in stud type terminals.

Page 67: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

65

PB 42-977

IEEE MeterAccuracy Height Width Length Weight

0.3W, X, M, Y 22.6 18.9 20.0 255Full and Tap0.3W, X, M, Y 22.6 18.9 20.0 255Full and Tap0.3W, X, M, Y 22.6 18.9 20.0 255Full and Tap

0.3W, X, M, Y 23.3 16.1 20.0 245Full and Tap

PB 42-978

IEEE MeterAccuracy Height Width Length Weight

0.3W, X, M, Y, Z, 23 16.1 17.6 205ZZ

0.3W, X, M, Y, Z, 23 16.1 17.6 205ZZ

0.3W, X, M, Y, Z, 23 16.1 17.6 205ZZ

0.3W, X, M, Y, Z, 23 16.1 17.6 205ZZ

0.3W, X, M, Y, Z, ZZ 23 15.6 17.6 2020.3W, X, M, Y, Z, ZZ 23 15.6 17.6 202

Page 68: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

Primary StyleVoltage Ratio Number①

27600/27600Y 240 & 240:1 9629A96G02

34500/34500Y 300 & 300:1 9629A96G01

20125/34500GY 175/300:1 9629A97G01& 175/300:1

20125/34500GY . 175/300:1 7882A42G01

Tapped and Single Secondaries Available.

TYPE VVOOYY--2200 aanndd VVOOYY--2200GG

Primary StyleVoltage Ratio Number

27600/27600Y 240:1 7881A82G0334500/34500Y 275:1 7881A82G04

20125/34500GY 175/300:1 7526A55G01

66

36 kV VOLTAGE TRANSFORMERS

TYPE VVOOZZZZ--2200 aanndd VVOOZZZZ--2200GG

Outdoor200 kV BIL60 Hertz

Thermal Ratings:3000 VA at 30ºC Ambient

Outdoor200 kV BIL60 Hertz

Thermal Ratings:1000 VA at 30ºC Ambient

① Style includes clamp type primary terminals.

Stud type available for spade terminal.

VOY-20200 kV BIL

VOY-20G200 kV BIL

Page 69: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

IEEE MeterAccuracy Height Width Length Weight

0.3W, X, M, Y, 26.0 18.1 24.3 380Z, ZZ

0.3W, X, M, Y, 26.0 18.1 24.3 380Z, ZZ

0.3W, X, M, Y, 26.7 17.0 24.3 380Z, ZZ

0.3W, X, M, Y, 26.7 17.0 24.3 380Z, ZZ

PB 42-974

IEEE MeterAccuracy Height Width Length Weight

0.3W, X, M, and Y 19.00 15.87 16.94 1480.3W, X, M, and Y 19.00 15.87 16.94 148

0.3W, X, M, and Y 19.00 13.81 16.94 142

67

PB 42-979

Page 70: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

68

AAPPPPLLIICCAATTIIOONN DDAATTAA

Po

lari

ty:

Des

igna

tion

of t

he r

elat

ive

inst

anta

neou

sdi

rect

ions

of

the

curr

ents

ent

erin

g th

e pr

imar

y le

ads

and

leav

ing

the

seco

ndar

y le

ads.

Whe

n cu

rren

t is

flow

ing

tow

ard

the

mar

ked

prim

ary

lead

, it

is f

low

ing

away

fro

mth

e tr

ansf

orm

er in

the

mar

ked

seco

ndar

yle

ad.

Page 71: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

69Continued on Next Page

INS

TR

UM

EN

TT

RA

NS

FO

RM

ER

S

insu

late

met

ers

or o

ther

ins

trum

ents

fro

m h

igh

volta

ges

and

curr

ents

and

tran

sfor

m th

em (i

.e.,

step

-dow

n)to

va

lues

w

here

th

ey

can

be

mea

sure

d by

stan

dard

met

ers.

All

inst

rum

ent

tran

sfor

mer

s ar

e cl

assi

fied

ase

ithe

r cu

rre

nt

tra

nsf

orm

ers

o

r vo

ltag

etr

an

sfo

rme

rs.

Th

ey

are

u

sed

fo

r re

ven

ue

met

erin

g an

d al

so

with

re

lays

an

d in

dica

ting

inst

rum

ents

.

Cu

rren

t Tr

ansf

orm

ers

(CT

)T

he p

rimar

y w

indi

ngs

of c

urre

nt tr

ansf

orm

ers

are

conn

ecte

d in

se

ries

w

ith

the

line

and

thei

rse

cond

arie

s co

nnec

ted

to

the

curr

ent

coils

or

elem

ents

of

met

ers,

rel

ays

or i

nstr

umen

ts.

All

stan

dard

cur

rent

tra

nsfo

rmer

s ha

ve a

5 A

mpe

rera

ted

seco

ndar

y re

gard

less

of

th

eir

prim

ary

curr

ent.

Eac

h cu

rren

t tr

ansf

orm

er

has

spec

ifica

tions

base

d on

con

tinuo

us c

urre

nt,

shor

t tim

e cu

rren

t,an

d m

echa

nica

l st

ress

. T

here

are

tw

o ac

cura

cy

clas

sific

atio

ns:

one

for

met

erin

g an

d on

e fo

rre

layi

ng.

The

m

eter

ing

accu

racy

cl

assi

ficat

ion

tells

wha

t err

or in

tran

sfor

mat

ion

can

be e

xpec

ted

at

no

rma

l cu

rre

nts

. T

he

re

layi

ng

a

ccu

racy

clas

sific

atio

n te

lls w

hat

perc

ent

accu

racy

can

be

expe

cted

whe

n th

e se

cond

ary

is c

alle

d up

on t

oin

duce

a c

erta

in v

olta

ge.

The

sec

onda

ry o

f th

e cu

rren

t tr

ansf

orm

er s

houl

dal

way

s be

con

nect

ed t

o a

load

(bu

rden

) or

sho

rtci

rcui

ted.

If

the

seco

ndar

y is

ope

n ci

rcui

ted,

the

tran

sfor

mer

m

ay

deve

lop

a da

nger

ousl

y hi

ghse

cond

ary

volta

ge.

Rat

ing

Fac

tor:

The

fact

or b

y w

hich

the

nam

epla

tepr

imar

y cu

rren

t of

a C

Tis

mul

tiplie

d to

obt

ain

max

imum

pr

imar

y cu

rren

t th

at

can

be

carr

ied

con

tinu

ou

sly

with

ou

t e

xce

ed

ing

th

e

limiti

ng

tem

pera

ture

ris

e. T

he a

ccur

acy

clas

s at

the

ratin

gfa

ctor

poi

nt s

houl

d be

the

sam

e as

at

nam

epla

tera

ting.

Volt

age

Tran

sfo

rmer

s (V

T)

The

prim

ary

win

ding

s of

vol

tage

tran

sfor

mer

s ar

e

conn

ecte

d ac

ross

the

lin

e. T

hey

step

dow

n th

elin

e vo

ltage

to

a

valu

e su

itabl

e fo

r st

anda

rdm

eter

s, n

orm

ally

115

Vol

ts o

r 12

0 V

olts

.

In b

asic

con

stru

ctio

n, v

olta

ge t

rans

form

ers

are

muc

h lik

e di

strib

utio

n tr

ansf

orm

ers

exce

pt t

hat

the

curr

ent

and

the

kva

capa

city

are

ver

y lo

w.

The

y ar

e de

sign

ed t

o gi

ve a

n ac

cura

te v

olta

getr

ansf

orm

atio

n.

Sel

ecti

on

Anu

mbe

r of

co

nsid

erat

ions

ar

e in

volv

ed

inse

lect

ing

p

rop

er

inst

rum

en

t tr

an

sfo

rme

rsin

clud

ing:

sy

stem

vo

ltage

, B

IL,

load

cu

rren

t,ra

ting

fact

or

and

accu

racy

cl

ass

at

spec

ified

burd

ens.

Phy

sica

l req

uire

men

ts s

uch

as in

door

or

outd

oor

inst

alla

tion,

win

dow

or

bar

type

(fo

r 60

0V

CTs

), a

nd w

indo

w d

iam

eter

are

als

o im

port

ant.

Man

y of

th

e tr

ansf

orm

er

type

s lis

ted

in

this

cata

log

h

ave

so

me

ch

ara

cte

rist

ics

tha

t a

redu

plic

ated

in o

ther

type

s lis

ted,

but

eac

h ty

pe h

asits

ow

n un

ique

com

bina

tion

of f

eatu

res

that

bes

tm

eet

the

appl

icat

ion

for

whi

ch it

was

des

igne

d.

Page 72: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

70

AAPPPPLLIICCAATTIIOONN DDAATTAA

AMPERE CAPACITYOF INSULATED CONDUCTORS

Single Conductor In Free Air At 30°C (86° F)

Types RUW Types RHSize T RHWAWG Approximate TW RUH

or Diameter THWMCM (inches) Cu AI Cu AI

6 .397 80 60 95 754 .452 105 80 125 1003 .481 120 95 145 1152 .513 140 110 170 1351 .588 165 130 195 155

0 .629 195 150 230 18000 .675 225 175 265 210

000 .727 260 200 310 2400000 .785 300 230 360 280

250 .868 340 265 405 315300 .933 375 290 445 350350 .985 420 330 505 395400 1.032 455 355 545 425500 1.119 515 405 620 485

600 1.233 575 455 690 545700 1.304 630 500 755 595750 1.339 655 515 785 620800 1.372 680 535 815 645900 1.435 700 580 870 700

1000 1.494 780 625 935 7501250 1.676 890 710 1065 8551500 1.801 980 795 1175 9501750 1.916 1070 875 1280 10502000 2.021 1155 960 1385 1150

CALCULATION OF LINE AMPERESON POLYPHASE CIRCUITS

Amps = Load KVA X 1000

1.732 X Line To Line Voltage

Applicable to both 3 phase 3 wire delta and3 phase 4 wire wye.

REQUIRED DIAMETER OF CT WINDOWFOR MULTIPLE CONDUCTOR

Number ofPrimary MinimumConductors Window Diameter

2 2.00 X Conductor O.D.3 2.16 X Conductor O.D.4 2.42 X Conductor O.D.5 2.70 X Conductor O.D.

Page 73: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

Typical burden value (per stator) ABB Type D5

Polyphase MetersClass 20 Transformer

Rated

Potential coil at 120 Volts: 6.8 VA at 14 percent power

factor.

Current coil at 2.5 Amps: 1. 2 VA at 22 percent power

factor.(2½ Amp meter)

Resistance of coppersecondary wire in ohms

per 1000 feet at 68°F(20°C).

Wire Size Ohms

14 2.525012 1.588010 0.99898 0.6282

71

COMMON ELECTRICAL TERMS

Ampere (I) = Unit of current or rate of flow of electricityVolt (E) = Unit of electromotive forceOhm (R) = Unit of resistanceOhm's Law E = IRVolt Amperes (VA) = Unit of apparent power

= El (single phase)= E x I x 1.73 ( 3 phase)

Kilovolt Amperes (kVA) = 1000 Volt-AmperesWatt W = Unit of true power

= VA x p-f= .00134 hp

Kilowatt (kW) = 1000 wattsPower Factor (p-f) = ratio of true to apparent power

W kW= orVAkVA

Watthour (WHR) = unit of electrical work= one watt for one hour= 3.413 Btu= 2.655 ft. lbs.

Kilowatthour (kWHR) = 1000 watthoursHorsepower (hp) = Measure of time rate of doing work

= Equivalent of raising 33,000 lbs. one ft.in one minute

= 746 wattsDemand Factor = Ratio of maximum demand to the total

connected loadDiversity Factor = Ratio of the sum of individual maximum

demands of the various subdivisions ofa system to the maximum demand of thewhole system

Load Factor = Ratio of the average load over adesignated period of time to the peak loadoccuring in that period

Page 74: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

72

AACCCCUURRAACCYY SSTTAANNDDAARRDDSS

Current TransformersThe accuracy classification of current transformers for metering service includes a

correlation between ratio correction factor and phase angle so as to show the overall effecton watthour meter registration. The classification is based on the requirement that thetransformer correction factor (the correction for overall error due to both ratio error andphase angle) be within the limits specified. For any particular accuracy class the ratiocorrection factor and phase angle must fall within the parallelograms for 100% and 10%current respectively.

For example, the overall correction will never exceed .3% at 100% rated current fora transformer in the 0.3 accuracy class. If the ratio correction factor is 1.003 the maximumallowable phase angle is +15.6 minutes. The transformer correction factor is:

The corresponding ratio correction factor and phase angle for any point inside the 0.3 classparallelogram for 100% rated current will always give a transformer correction factorbetween .997 and 1.003.

Standard Burden Characteristics 60 Hz and 5 Ampere secondary

Burden Resistance Inductance Impedance Volt- PowerDesignation Ohms Millihenrys Ohms Amperes Factor

Metering Burdens

B-0.1 0.09 0.116 0.1 2.5 0.9B-0.2 0.18 0.232 0.2 5.0 0.9B-0.5 0.45 0.580 0.5 12.5 0.9B-0.9 0.81 1.040 0.9 22.5 0.9B-1.8 1.62 2.080 1.8 45.0 0.9

Relaying Burdens

B-1 0.5 2.3 1.0 25 0.5B-2 1.0 4.6 2.0 50 0.5B-4 2.0 9.2 4.0 100 0.5B-8 4.0 18.5 8.0 200 0.5

*Based on .6 Power Factor (lagging) of metered load.

Page 75: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

73

Standard Burdens

Burden Designation Secondary Volt-Amperes Burden Power Factor

W 12.5 0.10X 25.0 0.70M 35.0 0.20Y 75.0 O.85Z 200.0 O.85ZZ 400.0 0.85

Limits of Transformer Correction Factor (TCF)

Limits of PowerAccuracy Minimum Maximum Factor of Metered

Class Load-Lagging

minimum maximum

1.2 0.988 1.012 0.6 1.00.6 0.994 1.006 0.6 1.00.3 0.997 1.003 0.6 1.0

Voltage TransformersThe accuracy classification of voltage transformers for metering service includes a

correlation between ratio correction factor and phase angle so as to show the overall effecton watthour meter registration. The classification is based on the requirement that thetransformer correction factor (the correction for overall error due to both ratio error andphase angle) be within the limits specified. For any particular accuracy class the ratiocorrection factor and phase angle must fall within the parallelogram. These limits apply overthe voltage range of ± 10% of the rated voltage at rated frequency.

For example, the overall correction will never exceed .3% for a transformer in the 0.3accuracy class. If the ratio correction factor is 1.003 the maximum allowable phase angle is- 15.6 minutes. The transformer correction factor is:

The corresponding ratio correction factor and phase angle for any point inside the 0.3 classparallelogram will always give a transformer correction factor between .997 and 1.003.

Page 76: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

74

IITT TTYYPPEE DDEESSIIGGNNAATTIIOONNSSKEY TO TYPE DESIGNATIONS

600 V IMC ECI C = CT, 600 V, meteringCTS CBT-1 RTM accuracy

CBH None I - CT, 600 V, IndicatingCMV CRA R = CT, 600 V, RelayingCMF CTR (burden capabilityCSF CSB exceeds normalCSH None metering requirements.)CMS CSB (Lg.)CLC CLA (5½ ")CLE CLA (8¼ ")RLC EMC

600 V PPW PPI/EMP P=VT, 600 VVTS PPM PXA (+)

5 kV-25 kV

> 600 V KIR 60-11 CTM 5-15CTS KIT 60-11 UP 5-15

KOR 60-11 CTOM 5-15KON 11 CTOM 110KOR 15 CCO 150KOT 60-11 EMC 5-15

> 600 V VIY 60 PC 60 V=VT, > 600 VVTS VOY 60 PCO 60

VIZ 75, 11 PTM 75, 100VOZ 75, 11 PTOM 75, 110VOG 11 NoneVOZ 15 PTOM 150VIZZ 15 PT 25

GECABB Type Durham G.E.Type SchlumbergerIMC - JCH-0 -CBT/1 TCB JGT-0 R6BACBT-H TAB JCM-0 R6B

600 V CSF TCW JCR-0 R6SACurrent CSH TFW JCW-0 R6STransformers CMF AB JAK-0 R6M

CMV AP JAB-0 R6PCLC AD JAD-0 R6LCLE ACL JCD-0 -RLC AD JCP-O -

600 V PPW DF None T5RVoltage PPM DA JVA-0 (0.3M only) T6RTransformers PPX - None -

CCRROOSSSS RREEFFEERREENNCCEE of Most Commonly Used Types

Page 77: Instrument Transformer Reference - ABB Group · Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry. ... The transformers listed in this guide

75

2nd Position 3rd Position

Window Size Letters SCALE give a closer approximationof window diameter in inches.S C A L E

S = Small 1"-2" 1 1¼ 1½ 1¾ 2

M=Medium 2"-5" 2 2½ 3¼ 4 5

L= Large 5"-8¼" 5 5½ 6½ 7½ 8¼

G= Gt. > 8¼" F = Family of window sizes i.e., CMF withB=Bar 2½" & 3 1/16" windows

V = OvalT = Thru typeH = 0.5 (Half) Ohm Burden

P = Performance I = IndicatingM = .3 accuracy@ 35 VA

4th & 5th Position

I = Indoor N = 0.3B0.5 Perf. 60 = 60 kV BIL0 = Outdoor P = 0.3B0.9 Perf. 75 = 75 kV BIL

R = 0.3B1.8 Perf. 11 = 110 kV BILT = Thru Type 15 = 150 kV BIL

I = Indoor Y = .3 accuracy Same as above0 = Outdoor @ 75 VA

Z = .3 accuracy@ 200 VAG = Single bushingfor line to groundconnection

AssociatedABB Type G.E. Type Type

KIR-60,75, 11 JKM-3, 4, 5KOR-60,75, 11 JKW-3, 4, 5 BB-15-829

5-36 kV KON-11 JCK-5 BB-15-8218Current KON-12Transformer KOR-12

KOR-15 JKW-6 BB-25-8210/19KOT-60,75, 11 JCD-3, 4, 5 TID 532/LG-15KOR-20 JKW-7 BB-34.5KOTD-150,200 JKW-150, 200 LG 25/34.5

VIY-60 JVM-3VIZ-75, 11 JVM-4, 5VOY-60 JVW-3VOY-11 JVW-110 PTT-110-881VOZ-75, 11 JVW-4, 5 PTT-110-8212

5-36 kV VOG-11 JVW-110Voltage VOZ-11M JVW-5 (1 bushing)Transformers VOY, VOG-12 JVW-6

VOY-15, 15G JVW-7 (2 bushings) PTT-150-806VOZ-15VOHD 200, 200G JVW-7 (11 bushing)VOZZ-15, 20 JVT 150, 200VOZZ-15G, 20G JVS 150, 200