Instrument compartments in Experimental halls 1, 2 & 3

1

Page 2: Instrument compartments in Experimental halls 1, 2 & 3 1

Shielding materialsBoron-loaded paraffin and boron-loaded polyethylene

Page 3: Instrument compartments in Experimental halls 1, 2 & 3 1

Agenda boron-loaded paraffin

Building element with boron-loaded paraffin Fire properties of boron-loaded paraffin Issues regarding boron-loaded paraffin Fire load and design fires Safety distances and fire protection cladding

3

Page 4: Instrument compartments in Experimental halls 1, 2 & 3 1

Building element4

Page 5: Instrument compartments in Experimental halls 1, 2 & 3 1

Vertical flame spread test, boron-loaded paraffin5

Page 6: Instrument compartments in Experimental halls 1, 2 & 3 1

Cone calorimeter test, boron-loaded paraffin6

Page 7: Instrument compartments in Experimental halls 1, 2 & 3 1

Boron-loaded paraffin, B(OH)3

• Consists of paraffin and 30% boric acid• Boric acid theoretically consists of 56% boron oxide and 44 % water• Melting point 65 - 75 ˚C• Heat of combustion of 21 MJ/kg• Heat release of 300 kW/m2

7

Page 8: Instrument compartments in Experimental halls 1, 2 & 3 1

Fire load and design fire at ESS

Fire load can be installed or variable and can contribute to a design basis fire All excess fire load should be considered as protected fire load, not to contribute

to a fire Protected fire load shall be verified by literature or experiments Validation of protected fire load by test at SP Technical Research Institute of

Sweden 30MW design fire corresponds to 100m2 pool fire of boron-loaded paraffin or the

interior floor area of an instrument compartment of 10 x 10 m that is being rebuilt.

8

Page 9: Instrument compartments in Experimental halls 1, 2 & 3 1

Safety distances - Instrument compartments during construction

9

Page 10: Instrument compartments in Experimental halls 1, 2 & 3 1

Fire and heat protection of building elements10

Page 11: Instrument compartments in Experimental halls 1, 2 & 3 1

Conclusion paraffin-filled building elements

Design value will be the maximum design fire of 30MW, This corresponds to a burning truck or a burning pool fire,100 m2, of boron-loaded paraffin. This pool fire may consist of 1 m3 boron-loaded paraffin distributed as melted material with a height of 1 cm over 100 m2

Conclusion: the instrument compartments can only be built or rebuilt one at a time If a sprinkler system is installed, the fire analysis present that the 30 MW fire in an

instrument compartment will not reach it’s value. The fire growth will be stopped at 6 MW Conclusion: several instruments compartments can be built or rebuilt at the same time but with safety distances

Safety distances to prevent fire spread between instrument compartments

Fire protection cladding to prevent fire spread between instrument compartments

11

1 MW 2 meter

6 MW 5 meter

30 MW 10 meter