Upload
others
View
5
Download
0
Embed Size (px)
Citation preview
DOCUMENT 1274
REVISION B
October 5, 2016
Instruction Manual
PRO APF SERIES
IN-PAVEMENT
OMNI-DIRECTIONAL UTILITY LIGHT
Eaton Crouse-Hinds Series
Airport Lighting Products
1200 Kennedy Road
Windsor, CT 06095
Copyright © 2016 Cooper Technologies Company
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
ii
Table of Contents
1 Revisions ............................................................................................................................... iv
2 Product Warranty .................................................................................................................... v
3 Safety Notices ........................................................................................................................ vi
3.1 Keep Away from Live Circuits ....................................................................................... vi
3.2 RESUSCITATION ......................................................................................................... vi
4 Safety Symbols .................................................................................................................... vii
4.1 Danger ........................................................................................................................... vii
4.2 Warning ......................................................................................................................... vii
4.3 Caution .......................................................................................................................... vii
4.4 Warning: Notice ............................................................................................................ vii
4.5 Warning: Important ....................................................................................................... vii
5 Recommended Test Equipment and Tools ......................................................................... viii
6 General Information ............................................................................................................... 1
6.1 General Description – Taxiway Omni-Directional Light ................................................. 1
Table 1, Part number Explanation .................................................................................................. 3
Figure 1, Fixture Dimensions ......................................................................................................... 4
7 Installation .............................................................................................................................. 5
7.1 ANSI Installation Bolt Torque and Installation Method .................................................. 7
7.2 Heico-Lock Installation Guide (2014) ............................................................................. 8
Figure 2, 19999 Installation (Lifting) Tool ..................................................................................... 9
8 Maintenance .......................................................................................................................... 10
8.1 General ........................................................................................................................... 10
8.2 Recommended Spares .................................................................................................... 10
8.3 Cleaning Lens ................................................................................................................ 11
8.4 O-Ring Replacement ...................................................................................................... 11
8.5 Feed-thru Replacement .................................................................................................. 12
8.6 Outer Lens/Heater Replacement .................................................................................... 12
8.7 LED Replacement .......................................................................................................... 13
8.8 Power Supply Replacement (Series Circuit Powered Units) ......................................... 14
8.9 Power Supply Replacement (Voltage Powered Fixtures) .............................................. 15
8.10 8 Inch Fixture External Gasket Replacement ................................................................. 15
8.11 Pressure Test .................................................................................................................. 16
8.12 Cleanliness and Workmanship ....................................................................................... 16
8.13 Maintenance Program .................................................................................................... 16
9 Troubleshooting .................................................................................................................... 18
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
iii
9.1 Visual Inspection ............................................................................................................ 18
9.2 Electrical Inspection, Series Circuit Powered Fixtures .................................................. 18
Figure 3, Power Supply, Series Circuit Fixtures ........................................................................... 19
Wiring Diagrams, Series Circuit Powered Fixtures ...................................................................... 20
Jumper Diagram, Series Circuit Powered Fixture ........................................................................ 21
Figure 4, Part Identification ......................................................................................................... 22
10 Fixture Mounting Bolts & 2-Piece Washers ......................................................................... 30
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
iv
1 Revisions
Rev.
No.
Issue/Reissue
Number Letter Description Checked Approved
A A216-212 Initial release PG 6/1/16
B A216-365
Page 4, Fig 852UL-AP1-XXX-12X, Added base flange
diameter “Z”, Ø9.94 for -12A & -12C versions &
Ø9.19 for -12B & -12D versions.
IM 10/5/16
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
v
2 Product Warranty
Warranty Refer to Eaton’s Crouse-Hinds Airport Lighting Products Terms and Conditions for product
specific warranty information.
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
vi
3 Safety Notices
This equipment is normally used or connected to circuits that may employ voltages which
are dangerous and may be fatal if accidentally contacted by operating or maintenance
personnel. Extreme caution should be exercised when working with this equipment.
While practical safety precautions have been incorporated in this equipment, the
following rules must be strictly observed:
3.1 Keep Away from Live Circuits
Operating and maintenance personnel must at all times observe all safety regulations. Do
not perform maintenance on internal components or service with power ON.
DANGER:
DANGER DO NOT PERFORM MAINTENANCE ON INTERNAL
COMPONENTS OR SERVICE WITH POWER ON.
3.2 RESUSCITATION
Maintenance personnel should familiarize themselves with the technique for resuscitation
found in widely published manuals of first aid instruction.
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
vii
4 Safety Symbols
4.1 Danger
DANGER:
DANGER The hazard or unsafe practice will result in severe injury or death.
4.2 Warning
WARNING:
WARNING The hazard or unsafe practice could result in severe injury or death.
4.3 Caution
CAUTION:
CAUTION The hazard or unsafe practice could result in minor injury.
4.4 Warning: Notice
WARNING:
NOTICE Possibly dangerous situation, goods might be damaged.
4.5 Warning: Important
WARNING:
IMPORTANT Helpful information.
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
viii
5 Recommended Test Equipment and Tools
There is a wide variety of tools and equipment needed to safely and correctly perform airfield
lighting equipment installation and maintenance. In addition to the obvious tools (screwdrivers,
wrenches, etc.), there is a specialized equipment needed to do the job.
Multimeter
One of the most important pieces of test equipment is the Multimeter. It is used to measure
voltages, currents, and resistances. Almost every single maintenance task requires the use of a
multimeter at one point or another. A quality meter in good repair and calibration is a must
because airfield lighting power distribution equipment produces non-sinusoidal waveforms,
traditional average reading meters are inaccurate and have very limited use. Checking or
adjusting equipment based upon incorrect current reading may dramatically reduce lamp life and
adversely affect power equipment performance. A meter with TRUE RMS measuring capability
with a current clamp-on accessory is needed to accurately measure distorted or chopped
waveforms. All meter manufacturers offer TRUE RMS measuring meters. The following is a
short list of TRUE RMS Multimeters from Fluke:
Manufacturer Model Number
Fluke 287
Our recommended multimeter is the Fluke 287 with the Fluke I800 current clamp accessory.
Refer to the equipment manufacturer’s manuals for the proper use, maintenance and calibration
(if necessary) of all meters.
Thread Lubricant
Anti-seize (marine grade preferred, Henkel/Loctite P/N 34395 or 34026 or equal customer
supplied [ http://www.henkelna.com/adhesives/product-search-
1554.htm?nodeid=8797882515457]) with a K factor of 0.18 for fully coating the fixture
installation bolts.
Drive and Ratchet
A 3/8 inch square drive socket and ratchet (use ratchet for loosening bolts only and a torque
wrench to tighten), size 9/16 or 14 mm for the fixture 3/8-16 UNC hex installation (customer
supplied) bolts installed into a FAA L-867 or L-868 base.
Torque Wrench
A calibrated torque wrench (micrometer adjustable solid audible/tactile “click” impulse when
torque value attained with an accuracy of +/- 4%) to fit a 9/16 or 14 mm socket for drive size of
the socket to tighten the fixture hex bolts per Sections 7.1 and 7.2. Torque wrenches: Sturtevant
Richmont P/N 810748, range 100 to 600 in-lbs or equal, or Sturtevant Richmont P/N 810782,
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
ix
range 10 to 50 Nm or equal. Certificate of calibration included with suggested torque wrenches.
Note, never loosen bolts with a torque wrench.
Torque Screwdriver
A calibrated adjustable torque screwdriver to torque the smaller internal hardware and the
bottom cover external screws if the fixture is opened for maintenance. Sturtevant Richmont P/N
810568 (comes with bits [hex, slotted, Torx, Phillips, sq. recess, bit holder, socket adapter], case and
certificate of calibration), range 2 to 36 in-lbs/0.2 to 4 Nm or equal. Note, never loosen screws with a
torque screwdriver.
Pliers
Needle nose pliers for installing the extremely small header jumper onto a spare Power Supply
J203 header when required, or removing the flag type fast-on terminals from the power supply.
Xcelite P/N NN54-2 miniature pliers, fine needle nose, ESD-Safe or equal.
ESD Protection
A grounded ESD Wrist Strap when working on or handling fixture power supplies or LED/Heat
sink assemblies. ESD Wrist Straps, also known as anti-static Wrist Straps, are used to prevent
electrostatic discharge (ESD) by safely grounding a person working with electronic equipment or
at an electronic assembly facility. It consists of a band of fabric with fine conductive fibers
woven into it. The fibers are usually made of carbon-filled rubber, and the strap is bound with a
stainless steel clasp or plate. They a usually used in conjunction with an ESD table mat on the
workbench, or a special static-dissipating plastic laminate on the workbench. ESD Products
brand ( http://www.esdproduct.com/esd_wrist_straps.php ) or equal.
Fixture Installation/ Removal Tool
A Crouse-Hinds P/N 19999 installation tool to aid in the installation and removal of 12 inch
diameter fixtures (only available from Crouse-Hinds).
Most tools indicated above can be purchased from MSC Industrial Supply Co. (
http://www.mscdirect.com/ ), or McMaster-Carr ( http://www.mcmaster.com/ ).
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
1
6 General Information
6.1 General Description – Taxiway Omni-Directional Light
The Crouse-Hinds Utility Light part number 852UL-AP1-XXX-XXX is a Omni-directional Style
3 in-pavement fixture per FAA AC 150/5345-46 (latest revision). It is designed for installation
at the taxiway edge or any other location where visual guidance of moving aircraft or ground
vehicles is desirable. The fixture is designed to fit on a FAA L-868, size B (-12A) or FAA L-
867 size B (-12B) light base per FAA AC 150/5345-42 (latest version), and have a total height
above grade/ground level of .250 inch. Part Number 852-AP1-008 fits Crouse-Hinds Shallow
Bases 21431-X-X. The fixture is Omni-directional, projecting the beam of light 360° in the
horizontal direction. It is weatherproof and will endure roll over loads without damage. The
LED “AP1” series circuit power supply can be used with either a 3 (4.8, 5.5, 6.6A output) or 5
step (2.8, 3.4, 4.1, 5.2, 6.6A output) Constant Current Regulator (CCR), 50 or 60 Hz. The power
supply has a power factor of 0.99 in all steps, and an efficiency greater than 80% at 6.6A. The
series circuit power supply is compatible with all known CCR types, has a 3.5 crest factor to
ensure compatibility with series CCRs, has a 0.88 second switch-on time, a typical initial turn on
voltage of 1.5V, high frequency 400 Hz PWM to help eliminate flicker perception, and a
10k/5kA surge protection.
The LED(s) have a projected life of greater than L70 (L70 = elapsed operating time in hours
over which the LED light source maintains 70% of its initial output) @ 50,000 hours at 6.6A. If
an Arctic Kit is ordered (available on 6.6A units only) with the fixture, it will comply with the
requirements of FAA EB67 (latest), which will raise the light emitting surface temperature 15
degree C (59 degrees F) after 30 minutes of operation at the CCR high step of 6.6A. The arctic
kit heating filament is applied directly to the glass dome interior and does not obstruct the
photometric output. Units can be supplied with a parallel powered (voltage) LED supply for
12VDC, 24VDC and 100-277VAC. Parallel powered units are not available with Artic Kits. All
fixtures are factory illuminated.
The light fixture consists of a 1-piece aluminum optical assembly. The 12 inch diameter
aluminum optical assembly is mounted to a FAA size B light base with six bolts and six 2-piece
locking washers (order separately, see Section 10). The 8 inch diameter aluminum optical
housing assembly is mounted to a Crouse-Hinds shallow base, P/N 21431-X-X (order separately)
which is supplied with mounting hardware. All fixtures have aluminum housing and a die cast
bottom cover that is attached using 4 screws. A O-ring is used to provide a watertight seal
between the inner cover and the optical housing. An LED module is secured to the lens bracket,
which is fastened to the optical housing. The power supply is secured to the inner cover using a
bracket. Electrical connections are made at one feed-thru assembly in the inner cover. The feed-
thru is a 2 conductor molded cable and has an ITS verified L-823 plug for connecting to FAA L-
830/ L-831 isolation transformer. Parallel powered (voltage) units are also supplied with a
secondary receptacle with two leads for the customer to make waterproof butt splices to to
introduce their power. The outer lens is held into the aluminum housing with a bracket, gasket,
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
2
molded elastomeric boot and 12 screws. All hardware is type 18-8 stainless steel except for the
12 screws holding the outer lens bracket onto the aluminum housing, which are type 410 heat-
treated black oxide stainless steel. The complete 852UL-AP1-12A or 852UL-AP1-12B light unit
is 11.94 inches in diameter, 2.75 inches deep from grade, and weighs 10.5 lbs. The 8 inch unit is
the same depth as the 12 inch unit. The series powered (constant current) fixture requires a
minimum 6.6A/6.6A, 10/15 watt series isolation transformer without the arctic (heater) kit
(minimum 20/25 watt or 30/45 watt with the arctic kit).
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
3
Table 1, Part number Explanation
852UL - AP1 - - - -
FIXTURE TYPE:
SERIES VERSION:
FIXTURE DIAMETER:
In-Pavement Utility Light
AP1 = Pro APF1
008 = 8" Fixture with mounting bolt pattern per IEC specifications
12A = 12" Fixture with 11.25" mounting BC for FAA L-868 base can12B = 12" fixture with 10.25" mounting BC for FAA L-867 base can
OPTIONS:
1 = Artic Kit (6.6A Input Units Only)
COLOR:
B = Blue (Not Available For 6.6A Units, Use P/N 852T-AP1)G = GreenY = YellowR = RedW = White
INPUT POWER:
066 = 6.6A Constant Current012 = 12VDC Input (Not Available With Option 1)024 = 24VDC Input (Not Available With Option 1)120 = 100-277 VAC Input (Not Available With Option 1)
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
4
Figure 1, Fixture Dimensions
852UL-AP1-XXX-008
Note, there are two blind holes on the underside of the optical forging to accept the 21431
Shallow Base pins/studs.
852UL-AP1-XXX-12X
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
5
7 Installation
WARNING:
NOTICE
852UL-AP1 base can pavement specifications and design are the
responsibility of the installer and/or airport. Transformer housing,
series isolation transformers, primary connector kits, heat shrink
kits, series loop primary wire, counterpoise cable/wire, grounding
rods, ground wire and connectors, waterproof splices, fixture
mounting bolts and 2-piece washers are not included as part of the
852UL-AP1. Additionally, the electrical power originating from the
CCR and any electrical equipment required to bring utility power or
generator power to the CCR or fixture(s) is the responsibility of the
installer and/or airport. Underlined items may be ordered from
Crouse-Hinds Airport Lighting. See Section 10 for mounting bolts
and 2-piece washer part numbers.
a. Refer to your agency’s your airport construction plans for installation and fixture spacing
recommendations.
DANGER:
DANGER
Lock out electrical power at its source that will power the fixture at its
source before attempting any electrical connections/splices per your
safety procedures.
WARNING:
IMPORTANT
Check the fixture for shipping damage upon arrival and in all cases,
check for damage prior to installation.
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
6
CAUTION:
CAUTION
Never handle the light assembly by the leads as this can break the
waterproof seal.
b. A list of tools which can help during installation are referenced in Section 5, “Recommended
Test Equipment and Tools”.
c. Check the fixture part number before installation to be sure it will be installed at the correct
location.
d. Be sure the correct series isolation transformer size is installed for the fixture; minimum
10/15 watt, 6.6/6.6A secondary without an arctic (heater) kit, or a minimum 20/25 watt or
30/45 watt 6.6/6.6A secondary for fixtures with the arctic kit installed if the fixture is series
circuit (CCR) powered.
WARNING:
IMPORTANT
Crouse-Hinds P/N 19999 will ease in the installation and removal of 12
inch diameter fixtures (see Figure 2). The threaded eyebolts on the
lifting tool screw into threaded holes in the fixture.
e. Plug the fixture’s L-823 plug into the series isolation transformer secondary receptacle
located in the base can if series powered. Apply electrical tape to this connection to keep
this secondary connection from possible disconnection in the base due to freeze/thaw cycles
that may occur from water intrusion into the base can. Note, if you are using a Crouse-
Hinds type SIB-8 Shallow Base, the series isolation transformer will not be located in the
shallow base. A secondary extension cable (length dependent on installation) will be
required to make the connection between the fixture and series isolation transformer
secondary plug and receptacle.
f. Plug the fixture’s L-823 plug into the supplied L-823 receptacle after waterproof butt splices
have been made to voltage power on parallel powered units. Note, for DC powered units,
the small diameter plug/receptacle pin is the positive (+) side. Failure to connect power
polarity correctly will result in power supply/LED damage.
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
7
g. Verify that the mounting flange on the fixture base can is clean and the O-ring (optional on
deep cans) is coated with Dow Corning FS 1292 grease and is in place on the base can.
The 8 inch diameter fixture, P/N 852UL-AP1-XXX- 008 comes with a gasket on the bottom
cover exterior to seal it to a Crouse-Hinds Shallow Base having an inner bore diameter of
6.61 inches. This gasket should also be coated with the Dow Corning grease if using this
size fixture.
WARNING:
IMPORTANT
Failure to apply anti-seize to fixture mounting bolts at installation
may result in difficult removal of a mounting bolts and poor
clamping force. The correct “k” value anti-seize must be used in
addition to 2-piece locking washers as described in Section 7.1 to
maintain to correct boly clamping force.
h. Torque the fixture installation bolts per Section 7.1 instructions.
i. Return power to the circuit per your safety procedures.
7.1 ANSI Installation Bolt Torque and Installation Method
Use fully threaded, cold-worked 18-8 stainless steel 3/8-16 bolts. (P/N 21715 is
recommended).
Use Heico-Lock or Nord-Lock stainless steel lock-washers per FAA Advisory
Circular (AC)150/5345-30 (latest) and AC 150/5340-26 (latest) FAA Engineering
Brief (EB)83 (latest).
Mounting base holes must be degreased, cleaned, and dried prior to bolt
installation.
Base-to-fixture mating surfaces must be degreased, cleaned, and dried prior to
installation.
Apply marine grade anti-seize (K=.18) per manufacturer’s instructions to each
bolt.
Install the 3/8-16 bolts with lock-washers per lock-washer manufacturer’s
guidelines.
See section 7.2 for Heico-Lock installation guidelines (2014)
Achieve a full final torque of 225 in-lb (25.4 N-m) +10%, -0% with a calibrated
torque wrench.
Impact wrenches are not recommended as installation tools.
Check torque and re-torque all bolts within 2 weeks of initial installation.
Maintain all bolts by checking and re-torqueing per FAA AC 150/5345-26
(latest).
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
8
If any lubricants or thread locking compounds are used (not recommended),
torque must be recalculated based on K factor provided by lubricant or compound
manufacturer.
New bolts and lock-washers shall be used each time a light unit is removed from
its bas
7.2 Heico-Lock Installation Guide (2014)
Step 1: Hand tighten to ensure that 2-3 threads extend beyond the nut on through-bolt
applications.
Step 2: Tighten each bolt to one-third of the final required torque following the pattern as
shown below.
Step 3: Increase the torque to two-thirds following the pattern shown below.
Step 4: Increase the torque to full torque following the pattern shown below.
Step 5: Perform one final pass on each bolt working clockwise from bolt 1, at the full
final torque.
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
9
Figure 2, 19999 Installation (Lifting) Tool
(Note, fixture illustrated in not a Omni-Directional)
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
10
8 Maintenance
8.1 General
The preferred method of maintaining a light unit is to periodically replace the unit and return it to
the maintenance shop for renovation. As an alternative, the optical assembly can be serviced in
the field. Work on electrical circuits should only be performed by qualified electricians with a
working knowledge of airfield lighting circuits. However, it is recommended that field servicing
be limited to bolt torque checks per Section 7.1 and cleaning the lens as described in Section 8.3.
Users should also reference FAA AC 150/5340-26 (latest), “Maintenance of Airport Visual Aid
Facilities” for their recommended practices for runway and taxiway edge lighting systems. A
list of tools which can help during maintenance are referenced in Section 5, “Recommended Test
Equipment and Tools”. Figure 4 will aid in part identification and in replacement part numbers.
8.2 Recommended Spares
The number of recommended spare fixtures is 2% installed at the airfield. If the quantity for each
type is less than 50, then at least two fixtures. The number of individual spare parts should be at
least 3% of the total fixtures installed at the airfield. This number may vary greatly if aggressive
snow removal operations occur.
WARNING:
IMPORTANT Do not open any light fixture unless the warranty period has expired.
Opening a light fixture will void the warranty.
DANGER:
DANGER
Lock out electrical power to the series loop that will power the fixture
at its source before attempting servicing to the fixture.
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
11
DANGER:
DANGER
Do not remove the fixture from the base can while the fixture is
powered. Dangerous voltage may be present on the primary and
secondary sides of the isolation transformer.
WARNING:
WARNING
A buzzing or humming noise coming from the isolation transformer
may indicate a failed power supply or LED. It is also an indicator of
dangerous voltage on the primary and secondary sides of the isolation
transformer.
8.3 Cleaning Lens
Clean the outer surface of the glass lens with a detergent solution. If the lens is coated
with a substance impervious to the detergent, a suitable solvent should be sparingly
applied with a wad of cotton or a patch of cloth on the end of a wood splint. After the
solvent has acted the remaining solvent and softened coating should be removed with a
clean piece of cotton or cloth. Care should be taken to avoid excessive contact between
the solvent and the lens seal. Remove all remaining solvent from lens and seal. A gentle
air blast may be used.
8.4 O-Ring Replacement
Every time the fixture is opened, the O-ring must be replaced.
WARNING:
IMPORTANT
Every time a fixture is opened, its O-ring and fixture exterior gasket
(present on 8 inch fixtures only) is recommended to be replaced. O-
rings and gaskets will develop a permanent deformation over time. A
bad O-ring is the most common cause of in-pavement fixture leaks.
Failure to replace them when the fixture is opened may result in a
fixture leak. Apply Dow Corning FS 1292 grease to the fixture O-ring
and exterior gasket.
Remove and secure power to the fixture. Remove and discard the old O-ring from the
groove in the optical housing using a plastic, or comparably soft, tool. Carefully clean the
O-ring groove and flange mating surface on the inner cover. Take care not to damage the
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
12
mating surface or the new O-ring. Coat the new O-ring with a thin layer of Dow Corning
FS 1292 lubricating grease. Position the new O-ring concentric with the groove and press
it into place. Torque the inner cover screws to 30 in-lbs. Perform a pressure test as
described in paragraph 8.11. Connect the light unit lead(s) from the isolation transformer(s).
Clean the mounting flange area of the fixture and base. Install the fixture into the base per
Section 7.1.
8.5 Feed-thru Replacement
Remove and secure power to the fixture. Remove the two bolts and 2-piece locking
washers (8 inch fixture) or six bolts and 2-piece locking washers (12 inch fixture) securing
the fixture to the base. Disconnect the light unit lead(s) from the isolation transformer(s).
Turn the fixture upside down and remove the four screws holding the bottom cover to the
fixture housing. Disconnect the power supply leads /ferrite leads from the feed-thru
terminals. Remove the feed-thru by unscrewing its round retaining collar. Clean the
mounting surfaces with denatured alcohol and allow to dry. Apply a thin coat of Dow
Corning FS 1292 grease to the mounting flange of a new feed-thru. Apply a drop of
Loctite 243 to the feed-thru adapter threads. Screw the feed-thru retaining collar onto the
adapter. Torque the round retaining collar to 25-30 in-lbs. Reconnect the power supply leads/
ferrite leads to the feed-thru terminals. Replace the optical housing’s O-ring per section
8.4. Install the fixture into the base per Section 7.1.
8.6 Outer Lens/Heater Replacement
Outer Lens:
If the outer glass lens is broken, leaks, or is badly pitted or scarred, it must be replaced.
It is highly recommended that this task be performed in a clean shop environment. Outer
Lens Replacement Kit P/N 21332 contains all necessary parts to change a lens. Remove
and secure power to the fixture. Remove the two bolts and 2-piece locking washers (8
inch fixture) or six bolts and 2-piece locking washers (12 inch fixture) securing the fixture to
the base. Disconnect the light unit lead from the isolation transformer. Turn the fixture
upside down and remove the four screws holding the bottom cover to the fixture housing.
Remove the lens retaining bracket screws from the light housing. Remove the lens-retaining
bracket and discard the lens-retaining gasket. Firmly push the lens/boot assembly from the
outside of the light housing; discard the old lens and boot. Thoroughly clean the lens opening
with isopropyl alcohol and let dry. Inspect the lens opening for scratches or pits; a damaged
lens opening surface will not seal properly. Place a new lens boot (P/N 21256) over the
replacement outer lens (P/N 21254). Apply a thin coat of Dow Corning FS 1292 grease
over the entire outside surface of the lens boot. Align the lens/boot assembly in the lens
opening and press it into place. Verify that the lens boot is not pinched in the lens
opening. Using a new lens retaining gasket (P/N 21258), fasten the lens retaining bracket
(P/N 21297) to the light housing. Torque the mounting screws to 39-43 in-lb.
Inspect/replace the optical housing’s O-ring per Section 8.4. Assemble the bottom cover
onto the light housing. Torque the mounting screws to 30 in-lbs. Perform a pressure test
per Section 8.11. Clean the mounting flange area of the fixture and base. Install the
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
13
fixture onto the base and torque the mounting bolts with anti-seize applied along with 2-
piece locking washers for each bolt per Section 7.1.
Outer Lens with Heater (Series Circuit Powered Fixtures Only):
Outer Lens/Heater Replacement Kit P/N 21332 and Heater/Bracket
Assembly/Thermoswitch Kit P/N 21761 contain all necessary parts to change a
lens/heater assembly. Do as stated above; however, this fixture will not have a lens
retaining gasket since it is incorporated into the heater assembly and make sure that when
mounting the lens retaining bracket, the heater wires are aligned with the slot on the lens
retaining bracket so the wires are not pinched. The thermostat and its bracket is also part
of the replacement kit.
For Heater installation:
Clean the underside of the outer lens with alcohol and allow to dry.
Peal the adhesive strip (not the insulating foil side) from the heater (round disc
the leads attached) and adhere to the underside of the outer lens. Make sure when
adhering the heater to the outer lens that they remain concentric to each other so
light will not be blocked.
Clean the back side of the heater (insulation foil side) with alcohol and allow to
dry.
Peal the adhesive strip from the foam rubber pad (replaces flat circular hard outer
lens gasket) and adhere the heater to the foam rubber pad; making sure when
adhering the heater to the foam rubber pad that they remain concentric to each
other so light will not be blocked.
8.7 LED Replacement
WARNING:
NOTICE
A grounded ESD Wrist Strap should be worn by personal working on
or handling fixture LED assemblies. ESD Wrist Straps, also known as
anti-static wrist straps, are used to prevent electrostatic discharge
(ESD) by safely grounding a person working with electronic
equipment.
LED Replacement Kit P/N 21486-B1 contains all necessary parts to change the
LED module. Remove and secure power to the fixture. Remove the two bolts and 2-
piece locking washers (8 inch fixture) or six bolts and 2-piece locking washers (12 inch
fixture) securing the fixture to the base. Disconnect the light unit lead from the isolation
transformer. Turn the fixture upside down and remove the four screws holding the bottom
cover to the fixture housing. Disconnect the LED module leads from the power supply.
Remove the lens retaining bracket screws from the optical housing. Remove the lens-
retaining bracket and remove the LED heat sink from it unscrewing the screws. Install the
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
14
new LED module heat sink torque the screws in a star pattern to 30 in-lb; tightening the
lens retaining bracket screws to a torque greater than 35 in-lb may cause failures under
high loads. For the heater option fixture, make sure that the heater wires are aligned with
the slot on the lens retaining bracket so that they are not pinched at final assembly.
Replace the optical housing’s O-ring per Section 8.4. Install the fixture into the base per
Section 7.1
8.8 Power Supply Replacement (Series Circuit Powered Units)
CAUTION:
CAUTION Power supply is hot (temperature) when the fixture is energized and
remains hot for a short time after the fixture is turned off.
WARNING:
NOTICE
A grounded ESD Wrist Strap should be worn by personal working on
or handling fixture power supplies. ESD Wrist Straps, also known as
anti-static wrist straps, are used to prevent electrostatic discharge
(ESD) by safely grounding a person working with electronic
equipment.
WARNING:
IMPORTANT
The jumpers (on power supply J203) must be in the correct position(s)
for proper operation of the fixture to achieve outputs the fixture is
specified for.
WARNING:
NOTICE
Applying input current to the power supply without the arctic kit
heater or the heater jumper lead assembly installed on the power
supply will cause damage to the power supply.
WARNING:
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
15
IMPORTANT Applying a constant voltage greater than 50V (AC or DC) to the input
will cause damage to the power supply on series powered units.
Remove and secure power to the fixture. Remove the two bolts and 2-piece locking
washers (8 inch fixture) or six bolts and 2-piece locking washers (12 inch fixture) securing
the fixture to the base. Disconnect the light unit lead from the isolation transformer. Turn the
fixture upside down and remove the four screws holding the bottom cover to the fixture
housing. Remove the three power supply bracket screws. Disconnect internal cables to
power supply termination points. Remove the power supply bracket with attached power
supply. Remove the three power supply screws and discard the old power supply as an
electronics assembly. Configure the J203 jumper settings for the new power supply per
Jumper Diagrams in Section 9. Reconnect internal cables per the appropriate Wiring
Diagrams. Apply thermal grease to the mating surface of the new power supply and secure it
to the bracket using the three supplied screws. Torque the screws to 22-24 in-lb. Secure the
power supply bracket. Torque the bracket mounting screws to 25-30 in-lb. Replace O-ring
per Section 8.4. Install the fixture to the base per Section 7.1
8.9 Power Supply Replacement (Voltage Powered Fixtures)
Remove and secure power to the fixture. Remove the two bolts and 2-piece locking
washers (8 inch fixture) or six bolts and 2-piece locking washers (12 inch fixture) securing
the fixture to the base. Disconnect the fixture L-823 plug from the L-823 receptacle going to
voltage power. Turn the fixture upside down and remove the four screws holding the
bottom cover to the fixture housing. Remove the two power supply bracket screws.
Disconnect power supply cables at connection points. Install a new gap pad and power
supply using the existing bracket. Torque the bracket screws to 25-30 in-lb. Make
connections for the corresponding voltage power supply per Figure 4 power supply
illustration connection points indicated. Replace O-ring per Section 8.4. Install the fixture to
the base per Section 7.1
8.10 8 Inch Fixture External Gasket Replacement
Remove and secure power to the fixture. Remove the two bolts and 2-piece locking
washers (8 inch fixture) securing the fixture to the base. Disconnect the light unit lead
from the isolation transformer. Any gasket that is stretched, torn, has a permanent set or
some other defect, will allow water to enter the light base. Remove the old gasket from
the inner cover by carefully scraping with a plastic, or comparably soft, tool. Take care
not to damage the inner cover. Clean the sealing surface. Form a thin bead of high
temperature silicone adhesive, such as GE RTV 106, on the inner cover sealing surface.
Position the new gasket on the inner cover in the same location as the old gasket. Apply a
thin coat of Dow Corning FS 1292 grease over the entire outside surface of the gasket
before placing the optical assembly onto the base. Install the fixture onto the base per
Section 7.1.
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
16
8.11 Pressure Test
A light unit should be subjected to a 20-psig air pressure test to verify that it is
waterproof after it has been opened or components have been replaced. A tire valve
style pressure fitting is located on the bottom of the inner cover. Pressurize the unit to
20-psig then place it in a tub of water or use a soap solution to locate escaping air
bubbles. Carefully inspect the areas around the lens, inner cover seal, and feed-through
adapter for leaks. Relieve the internal air pressure before installing the light unit or
attempting to repair a leak.
8.12 Cleanliness and Workmanship
Service life depends upon the entire assembly being waterproof. All internal surfaces
must be clean, dry and free of all foreign matter if the light unit is to operate for extended
periods without requiring maintenance.
8.13 Maintenance Program
In order to ensure maximum light unit life, the installed units should be subject to a
maintenance program in accordance with the following:
A daily operation check should be made of the lighting units. The lights should be
energized and visually inspected. If any units are out, the location of the unit should be
recorded and replaced with a spare at a time when the circuit is de-energized.
Regular cleaning is necessary to ensure that in-pavement lighting units operate at
maximum efficiency. The lens should be cleaned periodically with a soft cloth and
solvent. The weather and the location of the units will dictate the regularity and type
of cleaning.
Snowplow operators should exercise extra care not to strike the light units with
snowplow blades. After snow removal operations, inspect all fixtures and replace if
any damaged fixtures. Passes over the light rows should be made with a power
broom only if practical. Whenever snowplows must traverse in-pavement light units,
they should be traveling at less than 5 mph or have the blades lifted clear of the units.
Recommended snow removal techniques are described in AC 150/5200-23.
The light is designed to exclude both ground and surface water from entering. If the
lights are not properly maintained (i.e., bolts tightened and seals in good condition)
water may enter the unit. To prevent this from occurring, it is recommended that each
unit be inspected for the presence of water at least once a month. More frequent
inspection is desirable during and following rainy seasons.
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
17
Fixture mounting bolts should be checked for proper torque per section 7.1 and
whenever a unit is serviced regardless of the season. Light units in and around the
touchdown zone area are especially prone to vibration and shock damage if the
mounting bolts are not properly torqued. The mounting surface of the light base
must be clean and free of foreign matter when checking mounting bolts.
If any light unit contains water, the water should be removed and the entire light unit
cleaned and dried. Perform a pressure test per Section 8.11 to locate the source of
the leak. Repair the leak and replace the fixture O-ring per Section 8.4.
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
18
9 Troubleshooting
If a light unit is under warranty, please contact Crouse-Hinds Airport Lighting for
assistance. DO NOT open a unit. If the unit is opened, the warranty is VOID. If the
warranty period has expired and troubleshooting is required, follow the steps below to
find the root cause. Replacement parts will be required for testing of the different
components of the light unit.
Review all DANGER, WARNING, IMPORTANT and NOTICE statements in Section
8. All still apply when troubleshooting.
9.1 Visual Inspection
Follow the steps in Section 8 to open the fixture. Verify all the wires are not pinched or
damaged and that the wire insulation is intact. Verify the input AC is connected to the
feed thru secondary plug. Verify the power supply connections. Verify the appropriate
J203 jumper settings per Wiring Diagrams, Jumper Diagrams and Figure 3 for series
circuit power fixtures. Replace any damaged or burned cables. Replace damaged LED
per Section 8.7. Replace damaged power supply per Section 8.8 or 8.9. Refer to Figure 4
part identification to determine the appropriate replacement part/kit for your fixture.
9.2 Electrical Inspection, Series Circuit Powered Fixtures
Follow the steps in Section 8 to open the fixture. The power supply continuously
monitors the status of the fixture LED. There is a green status LED (see Figure 3) that
may be visible through the potting. A blinking status LED indicates the power supply has
detected a fault condition.
Fault conditions include:
Disconnected or ‘Open’ LED module
o Replace cable if damaged or ‘open’.
Incorrect jumper setting or missing jumpers
o See Jumper Diagrams for proper jumper setting.
More than 25% of the driven LED ‘Shorted’
o Replace LED module per Section 8.7.
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
19
Figure 3, Power Supply, Series Circuit Fixtures
Connections
See Jumper Diagrams and Wiring Diagrams for connections for the Part Number
installed.
Status Indicator
When powered, if the status LED is not visible or not lit, replace the power supply per
Section 8.8 or contact Crouse-Hinds Airport Lighting Products for assistance.
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
20
Wiring Diagrams, Series Circuit Powered Fixtures
Without Heater, 6.6A Input
With Heater, 6.6A Input
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
21
Jumper Diagram, Series Circuit Powered Fixture
Power Supply J203 Jumper Positions for Part Numbers
852UL-AP1-066-XXX
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
22
Figure 4, Part Identification
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
23
Power Supply Shown For Series (CCR) Powered Fixtures
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
24
21486-_ & 21486- _1 LED/ Heat Sink Module Replacement Kits
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
25
21761 Heater, Thermostat, Thermostat Bracket and Power Cables Replacement Kit,
Option 1 Fixtures
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
26
21757-1 Bottom Cover
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
27
852UL-AP1-X-012-XXX (12 VDC) and 852UL-AP1-X-024-XXX (24 VDC)
Power Supply
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
28
852UL-AP1-X-120-XXX (100-277 VAC) Power Supply
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
29
Ferrite Placement Without Heater, 066 Input Power Fixtures
Ferrite Placement with Heater, 066 Input Power Fixtures with Option 1
DOCUMENT 1274
REV. B
Instruction Manual
PRO APF IN-PAVEMNT
OMNI-DIRECTIONAL UTILITY LIGHT
30
10 Fixture Mounting Bolts & 2-Piece Washers
P/N 21647-XXXX 2-Piece Washer Replacement Kit, customer specified quantity
P/N 21715-XX Bolt, Hex-Head, 3/8-16, cold worked 18-8 stainless steel, customer
specified length, quantity 1