94
READ THIS MANUAL CAREFULLY BEFORE CARRYING OUT ANY OPERATIONS ON THE DRYER. INSTRUCTION AND MAINTENANCE MANUAL Refrigerant Compressed Air Dryers QED 1250, QED 1600, QED 1800, QED 2100

INSTRUCTION AND MAINTENANCE MANUAL - Air Energy, Incairenergy.com/files/products/qed-210-operation-manual.pdfREAD THIS MANUAL CAREFULLY BEFORE CARRYING OUT ANY OPERATIONS ON THE DRYER

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

  • READ THIS MANUAL CAREFULLY BEFORE CARRYING OUT ANY OPERATIONS ON THE DRYER.

    INSTRUCTION AND MAINTENANCE MANUAL

    Refrigerant Compressed Air Dryers

    QED 1250, QED 1600, QED 1800, QED 2100

  • QUINCY

    QED 1250, QED 1600, QED 1800, QED 2100

    Instruction bookOriginal instructions

    Copyright NoticeAny unauthorized use or copying of the contents or any part thereof is prohibited.

    This applies in particular to trademarks, model denominations, part numbers and drawings.

    This instruction book is valid for CE as well as non-CE labelled machines. It meets therequirements for instructions specified by the applicable European directives as identifiedin the Declaration of Conformity.

    2012 - 09

    No. 2920 1822 00

    www.quincycompressor.com

  • Table of contents

    1 General description........................................................................................................4

    1.1 INTRODUCTION...................................................................................................................................4

    1.2 AIR SYSTEM......................................................................................................................................7

    1.3 REFRIGERATION SYSTEM......................................................................................................................9

    1.4 AUTOMATIC REGULATION SYSTEM........................................................................................................11

    1.5 CONDENSATE DRAIN SYSTEM..............................................................................................................12

    1.6 ELECTRICAL SYSTEM.........................................................................................................................15

    2 Air Logic controller........................................................................................................21

    2.1 AIR LOGIC controller ....................................................................................................................21

    2.2 CONTROL PANEL..............................................................................................................................22

    2.3 ICONS USED....................................................................................................................................23

    2.4 MAIN SCREEN..................................................................................................................................26

    2.5 CALLING UP MENUS..........................................................................................................................29

    2.6 INPUTS MENU...................................................................................................................................30

    2.7 OUTPUTS MENU...............................................................................................................................32

    2.8 COUNTERS......................................................................................................................................34

    2.9 EVENT HISTORY MENU.......................................................................................................................36

    2.10 MODIFYING SETTINGS........................................................................................................................37

    2.11 INFO MENU......................................................................................................................................44

    2.12 WEEK TIMER MENU...........................................................................................................................45

    2.13 TEST MENU.....................................................................................................................................53

    2.14 SERVICE MENU................................................................................................................................55

    2.15 PROTECTIONS MENU.........................................................................................................................59

    2.16 EXTRA MENU...................................................................................................................................60

    2.17 WEB SERVER..................................................................................................................................62

    2.18 PROGRAMMABLE SETTINGS ................................................................................................................67

    Instruction book

    2 2920 1822 00

  • 3 Installation.....................................................................................................................68

    3.1 DIMENSION DRAWINGS.......................................................................................................................68

    3.2 INSTALLATION PROPOSAL...................................................................................................................73

    3.3 INSTALLATION INSTRUCTIONS..............................................................................................................75

    3.4 ELECTRIC CABLE SIZE AND FUSES........................................................................................................76

    3.5 PICTOGRAPHS.................................................................................................................................77

    4 Operating instructions.................................................................................................79

    4.1 WARNINGS......................................................................................................................................79

    4.2 INITIAL START..................................................................................................................................79

    4.3 STARTING.......................................................................................................................................80

    4.4 DURING OPERATION..........................................................................................................................81

    4.5 STOPPING.......................................................................................................................................81

    5 Maintenance..................................................................................................................83

    5.1 MAINTENANCE INSTRUCTIONS.............................................................................................................83

    6 Problem solving............................................................................................................85

    6.1 PROBLEM SOLVING...........................................................................................................................85

    7 Technical data...............................................................................................................87

    7.1 REFERENCE CONDITIONS AND LIMITATIONS............................................................................................87

    7.2 AIR DRYER DATA..............................................................................................................................88

    8 Pressure equipment directives...................................................................................91

    Instruction book

    2920 1822 00 3

  • 1 General description

    1.1 Introduction

    Description

    The air dryer removes moisture from compressed air by cooling the air to near freezing point. This causeswater to condense. The condensate is automatically drained. The air is warmed up before leaving the dryer(approx. 5 ˚C (9 ˚F) below the incoming air temperature).

    The electronic controller keeps the pressure dew-point stable at no load by opening or closing the solenoid valve of the hot-gas by-pass.

    The condenser has a cooling fan controlled by a pressure sensor.

    General view

    QED dryer

    Instruction book

    4 2920 1822 00

  • Position of components

    dryer

    1 Heat exchanger2 Cooling fan(s)3 Condenser4 Cubicle5 Hot-gas by-pass valve6 Refrigerant compressor7 Liquid separator8 Sight-glass with moisture indicator9 Thermostatic expansion valve10 Refrigerant dryer/filter11 Non-return valve

    Instruction book

    2920 1822 00 5

  • Connections

    Rear view of dryer

    1 Compressed air outlet2 Compressed air inlet3 Cable gland, electrical connection4 Automatic drain hose

    Instruction book

    6 2920 1822 00

  • 1.2 Air system

    Air flow diagram

    Air and refrigerant flow diagram of QED 1250-2100 dryers

    Reference Name101a Air/air heat exchanger101b Air/refrigerant heat exchanger

    Instruction book

    2920 1822 00 7

  • Reference Name102 Condensate separator201 Non-return valve202 Air-cooled condenser (air-cooled version)203 Fan blower (air-cooled version)204 Thermostatic expansion valve205 Pressure shut-down switch206 Refrigerant dryer/filter207 Liquid separator208 Hot-gas by-pass valve209 Refrigerant compressor210 Solenoid valve211 Sight-glass212 Flow switch213 Temperature sensor214 Pressure sensor301 Cubicle401 Automatic drain(1) Air(2) Refrigerant(3) Drain(4) Water(5) Mechanical link(6) Electric power(7) Electric signal(8) Enclosure for several components assembled in one unit

    Description

    Compressed air enters heat exchanger (101a) and is cooled by the outgoing, cold, dried air. Water in theincoming air starts to condense. The air then flows through heat exchanger/evaporator (101b) where therefrigerant evaporates causing the air to be further cooled to close to the evaporating temperature of therefrigerant. More water in the air condenses. The cold air then flows through separator (102) where all thecondensate is separated from the air.

    The condensate collects in the Electronic Water Drain (EWD) (401) and is automatically drained. The cold,dried air flows through heat exchanger (101a), where it is warmed up by the incoming air to approx. 5 ˚C (9˚F) below the incoming air temperature.

    Condensation in the air net cannot occur unless the air is cooled to below the pressure dew-point indicatedon the control panel.

    Instruction book

    8 2920 1822 00

  • 1.3 Refrigeration system

    Refrigerant flow diagram

    Air and refrigerant flow diagram of QED 1250-2100 dryers

    Description

    Refrigerant compressor (209) delivers hot, high-pressure refrigerant gas, which flows through condenser(202), where most of the refrigerant condenses.

    Instruction book

    2920 1822 00 9

  • The liquid flows through refrigerant dryer/filter (206) to thermostatic expansion valve (204) via sight-glass(211). The refrigerant leaves the thermostatic expansion valve at evaporating pressure.

    The refrigerant enters evaporator (101b), where it withdraws heat from the compressed air by furtherevaporation at constant pressure. The heated refrigerant leaves the evaporator and is sucked in by refrigerantcompressor (209) via liquid separator (207).

    The dryers are provided with a sight-glass (211). The sight-glass allows the refrigerant flow in the line to bechecked. During normal operation, the liquid flow must be clear. In general, vapour bubbles indicate a shortageof refrigerant. Note that fluctuations in the load may cause bubbles to pass in the flow for a short time. Thecentre of the glass is provided with a moisture indicator which is green when the liquid refrigerant is free ofmoisture. It will turn yellow when the refrigerant contains moisture, indicating that the refrigerant dryer/filter(206) needs to be replaced.

    Instruction book

    10 2920 1822 00

  • 1.4 Automatic regulation system

    Air and refrigerant flow diagram

    Air and refrigerant flow diagram of QED 1250-2100 dryers

    Description

    The condenser pressure must be kept as constant as possible to obtain stable operation, therefore:

    Instruction book

    2920 1822 00 11

  • • The controller stops and starts the cooling fans

    When at partial or no load the dew-point pressure stays below the set-point, the controller opens solenoid valve (210) and hot, high-pressure gas is fed through hot-gas by-pass valve (208) to the evaporator circuit to prevent the evaporator temperature from dropping below 0 ˚C (32 ˚F).

    1.5 Condensate drain system

    Description

    Electronic water drain location on QED 1250

    Electronic water drain location on QED 1600-1800

    Instruction book

    12 2920 1822 00

  • Electronic water drain location on QED 2100

    Electronic water drain functioning

    Drain frequency during alarm condition

    1 Inlet

    Instruction book

    2920 1822 00 13

  • 2 Supply line3 Pilot valve4 Diaphragm5 Sensor6 Collector7 Valve seat8 Outlet

    The condensate enters the Electronic Water Drain (EWD) via inlet (1) and accumulates in collector (6). Acapacitive sensor (5) continuously measures the liquid level.

    The pilot valve (3) is activated as soon as the collector is filled up to a certain level. Diaphragm (4) opensoutlet (8), discharging the condensate.

    When the collector has been emptied, the outlet closes quickly without wasting compressed air.

    When the controller registers a malfunction, the red alarm LED on the control panel of the EWD starts flashing, a warning appears on the display of the controller and the electronic drain valve will automatically change to the alarm mode, opening and closing the valve according to a sequence as shown above. This condition continues until the fault is remedied. If the fault is not remedied automatically, maintenance is required.

    Testing the Electronic water drain

    Control panel, EWD

    Briefly press the TEST button and check that the valve opens for condensate discharge.

    Checking the alarm signal

    • Press and hold the test button for at least 1 minute.• Check that the alarm LED flashes.• Check that a warning is generated on the display of the controller.• Release the test button.

    Instruction book

    14 2920 1822 00

  • 1.6 Electrical system

    Electrical diagrams

    Electrical diagram, QED 1250 and QED 1600

    Instruction book

    2920 1822 00 15

  • Electrical diagram, QED 1800

    Instruction book

    16 2920 1822 00

  • Electrical diagram, QED 2100

    Instruction book

    2920 1822 00 17

  • Position of components

    Electric cubicle of QED 1250, QED 1600 and QED 1800

    Instruction book

    18 2920 1822 00

  • Electric cubicle QED 2100

    Ref. DescriptionA1 Alarm contact, warningA2 Alarm contact, shut-downED1 Electronic Water DrainE1 Electronic controllerF0 Main fuses (customer's installation)F10 Internal overload Fan 1F11 Internal overload Fan 2K1 Contactor, refrigerant compressorK5 Contactor, fan motor 1K25 Phase sequence relayM1 Refrigerant compressor

    Instruction book

    2920 1822 00 19

  • Ref. DescriptionM5 Fan motor 1PT20 Pressure sensor, condenser pressureQ1 Circuit breaker, refrigerant compressorQ3 Circuit breaker, transfoQ4 Circuit breaker, control voltageQ5 Circuit breaker, fan motorQ8 Circuit breaker, electronic controllerS0 Main switch (customer's installation)S1' Remote start-stop switchS2 High pressure switchS3 Flow switchT1 Transformer, control voltageTT89 Temperature sensor, refrigerant temperatureTT90 Temperature sensor, LAT in airflowTT91 Temperature sensor, ambientY1 Solenoid valve1X0 Terminal strip, supply1X3 Terminal strip, earthing1X5 Terminal strip, < or = 24 VAC1X6 Terminal strip, < or = 24 VDC1X7 Terminal strip, alarm contacts1X10 Electronic controller ethernet connection

    Dryer protection

    The unit is provided with a phase sequence relay (K25).

    The high-pressure shut-down switch (S1) stops the compressor motor when the pressure in the refrigerantcircuit reaches the upper set-point of the switch.

    After tripping:

    • The switch must be reset manually by pressing its reset knob and by pressing reset key (//) on the controller (electronic controller).

    The compressor motor has a built-in thermic protection. If the thermic protection trips, the compressor motorwill be stopped. The compressor will restart when the motor windings have cooled down, which may take upto 3 hours.

    Instruction book

    20 2920 1822 00

  • 2 Air Logic controller

    2.1 Air Logic controller

    Control panel

    General description

    The electronic controller automatically controls the dryer, i.e.:

    • keeps the pressure dew-point stable• stops the dryer whenever necessary• restarts the dryer when required

    In order to control the dryer and to read and modify programmable parameters, the controller has a control panel provided with:

    • LEDs indicating the status of the dryer• a display indicating the operating conditions or a fault• keys to control the dryer and to access the data collected by the controller• buttons to manually start and stop the dryer

    In general, the controller has following functions:

    • controlling the dryer• protecting the dryer• automatic restart after voltage failure (made inactive)

    Controlling the dryer

    The controller keeps the pressure dew-point stable at no load by opening or closing the solenoid valve of the hot-gas by-pass.

    In order to keep the condenser pressure constant:

    • The controller starts and stops the fan motor(s) as necessary.

    Instruction book

    2920 1822 00 21

  • Protecting the dryer

    Shut-down

    • In case the pressure in the refrigerant circuit is too high, the dryer will be stopped.• The dryer will also be stopped if there is an overload of a fan motor.

    Warning

    • A warning message appears if the EWD is malfunctioning.

    Automatic restart after voltage failure

    The controller has a built-in function to automatically restart the dryer if the voltage is restored after voltage failure. For dryers leaving the factory, this function is not activated. If desired, the function can be activated. Consult the Customer Centre.

    If activated and provided the controller was in the automatic operation mode, the dryer will automatically restart if the supply voltage to the module is restored within a programmed time period.The power recovery time (the period within which the voltage must be restored to have an automatic restart) can be set between 15 and 3600 seconds or to ‘Infinite’. If the power recovery time is set to ‘Infinite’, the dryer will always restart after a voltage failure, no matter how long it takes to restore the voltage. A restart delay can also be programmed, allowing for example the dryer and the compressors to be restarted one after the other.

    2.2 Control panel

    Air Logic controller

    Parts and functions

    Reference Designation Function1 Display Shows the dryer operating condition and a number of

    icons to navigate through the menu.2 Pictograph Automatic operation

    Instruction book

    22 2920 1822 00

  • Reference Designation Function3 Pictograph General alarm4 General alarm LED Flashes if a shut-down warning condition exists.5 Pictograph Service6 Service LED Lights up if service is needed7 Automatic operation LED Indicates that the controller is automatically controlling

    the dryer.8 Voltage on LED Indicates that the voltage is switched on.9 Pictograph Voltage on10 Enter key Key to select the parameter indicated by the horizontal

    arrow. Only the parameters followed by an arrowpointing to the right can be modified.

    11 Escape key To go to previous screen or to end the current action12 Scroll keys Keys to scroll through the menu.13 Stop button Button to stop the dryer. LED (7) goes out.14 Start button Button to start the dryer. LED (7) lights up indicating

    that the Air Logic controller is operative.

    2.3 Icons used

    Status icons

    Name Icon DescriptionStopped/Running When the dryer is stopped, the icon stands still.

    When the dryer is running, the icon is rotating.

    Machine control mode Local start/stop

    Remote start/stop

    Network control

    Automatic restart after voltagefailure

    Automatic restart after voltage failure is active

    Week timer Week timer is active

    Shutdown

    Instruction book

    2920 1822 00 23

  • Warning

    Service Service required

    Main screen Change main screen

    Main chart

    Input icons

    Icon DescriptionPressure

    Temperature

    Digital input

    Special protection

    System icons

    Icon DescriptionDryer

    Fan

    Frequency converter

    Drain

    Instruction book

    24 2920 1822 00

  • Filter

    Motor

    Failure expansion module

    Network problem

    General alarm

    Menu icons

    Icon DescriptionInputs

    Outputs

    Alarms (Warnings, shutdowns)

    Counters

    Test

    Settings

    Service

    Event history (saved data)

    Access key/User password

    Network

    Set point

    Instruction book

    2920 1822 00 25

  • Info

    Navigation arrows

    Icon DescriptionUp

    Down

    2.4 Main screen

    Control panel

    (1) Scroll keys(2) Enter key(3) Escape key

    Function

    The Main screen shows the status of the dryer operation and is the gateway to all functions implemented inthe controller.

    The Main screen is shown automatically when the voltage is switched on and one of the keys is pushed. It isswitched off automatically after a few minutes when no keys are pushed.

    Five different main screens can be chosen:

    1. Two value lines2. Four value lines3. Chart (High resolution)

    Instruction book

    26 2920 1822 00

  • 4. Chart (Medium resolution)5. Chart (Low resolution)

    Two and four value views

    Typical Main screen (Two value lines)

    Text on figures

    (1) Dryer PDP(2) Relative humidity(3) Starting(4) Menu

    • Section A shows information regarding the dryer operation (e.g. the Dryer PDP (1), the Relative Humidity(2)).

    • Section B shows Status icons. Following icon types are shown in this field:• Fixed icons

    These icons are always shown in the main screen and cannot be selected by the cursor (e.g. Dryerstopped or running, Dryer status).

    • Optional iconsThese icons are only shown if their corresponding function is activated (e.g. week timer, automaticrestart after voltage failure , etc.)

    • Pop up iconsThese icons pop up if an abnormal condition occurs (warnings, shutdowns, service,...)

    To call up more information about the icons shown, select the icon using the scroll keys and press theenter key.

    • Section C is called the Status barThis bar shows the text that corresponds to the selected icon.

    • Section D shows the Action buttons. These buttons are used:• to call-up or program settings• to reset a service message• to have access to all data collected by the controllerThe function of the buttons depends on the displayed menu. The most common functions are:

    Instruction book

    2920 1822 00 27

  • Designation FunctionMenu To go to the menuModify To modify programmable settingsReset To reset a timer or message

    To activate an action button, highlight the button by using the Scroll keys and press the Enter key.To go back to the previous menu, press the Escape key.

    Chart views

    When the Chart (High Resolution) is selected, a chart showing the pressure per minute is shown on the mainscreen. The pressure depends on the selection made in the input screen. Each point in the chart is 1 second.The screen shows 4 minutes.

    The switch button (icon) for selecting other screens is changed into a small Chart and is highlighted (active).

    When the Chart (Medium Resolution) is selected, a chart showing the pressure per hour is shown on the mainscreen. The pressure depends on the selection made in the input screen. Each point is the average of 1 minute.The screen shows 4 hours.

    The switch button (icon) for selecting other screens is changed into a small Chart and is highlighted (active).

    Instruction book

    28 2920 1822 00

  • When the Chart (Low Resolution) is selected, a chart showing the pressure per day is shown on the mainscreen. This pressure depends on the selection made in the input screen. Each point is the average of 1 hour.The screen shows 10 days.

    The switch button (icon) for selecting other screens is changed into a small Chart and is highlighted (active).

    2.5 Calling up menus

    Control panel

    (1) Scroll keys(2) Enter key(3) Escape key

    Description

    When the voltage is switched on, the main screen is shown automatically (see section Main screen):

    Instruction book

    2920 1822 00 29

  • • To go to the Menu screen, highlight the Menu button (4), using the Scroll keys.• Press the Enter key to select the menu. Following screen appears:

    • The screen shows a number of icons. Each icon indicates a menu item. By default, the Inputs icon isselected. The status bar shows the name of the menu that corresponds with the selected icon.

    • Use the Scroll keys to select an icon.• Press the Enter key (2) to open the menu or press the Escape key (3) to return to the Main screen.

    2.6 Inputs menu

    Control panel

    Instruction book

    30 2920 1822 00

  • (1) Scroll keys(2) Enter key(3) Escape key

    Menu icon, Inputs

    Function

    To call up information regarding the actually measured data and the status of some inputs such as theCondensing Pressure.

    Procedure

    Starting from the main screen (see Main screen),

    • Move the cursor to the action button Menu and press the Enter key. Following screen appears:

    • Press the Enter key. A screen similar to the one below appears:

    Text on figure

    Instruction book

    2920 1822 00 31

  • (1) Condensing pressure(2) Evaporating pressure(3) Dryer LAT 1(4) Refrigerant 1

    • The screen shows the first items of a list of all inputs with their corresponding icons and readings. Usethe scroll button the see the other items in the list.

    • If an input is in warning or shutdown, the original icon is replaced by the warning or shutdown iconrespectively.

    2.7 Outputs menu

    Control panel

    (1) Scroll keys(2) Enter key(3) Escape key

    Menu icon, Outputs

    Function

    To call up information regarding the actual status of some outputs such as the Solenoid valve, Dryer fan, etc.

    Procedure

    Starting from the Main screen (see Main screen),

    • Move the cursor to the action button Menu and press the Enter key. Following screen appears:

    Instruction book

    32 2920 1822 00

  • • Move the cursor to the Outputs icon using the Scroll keys.• Press the Enter key. A screen similar to the one below appears:

    (1) Outputs(2) Solenoid Valve 1 HGBP1(3) Run Enable Dryer Motor(4) Dryer Fan 1(5) Dryer Fan 2

    • The screen shows the first items of a list of all outputs with their corresponding icons and readings. Usethe scroll button the see the other items in the list.

    • If an input is in warning or shutdown, the original icon is replaced by the warning or shutdown iconrespectively.

    Instruction book

    2920 1822 00 33

  • 2.8 Counters

    Control panel

    (1) Scroll keys(2) Enter key(3) Escape key

    Menu icon, Counters

    Function

    To call up:

    • The running hours• The number of dryer starts• The number of hours that the controller has been powered

    Procedure

    Starting from the Main screen (see Main screen),

    • Move the cursor to the action button Menu and press the Enter key. Following screen appears:

    Instruction book

    34 2920 1822 00

  • • Using the Scroll keys, move the cursor to the Counters icon (see above, section Menu icon)• Press the Enter key. Following screen appears:

    Text on figure

    (1) Counters(2) Running hours dryer(3) Dryer starts(4) Module hours

    The screen shows a list of all counters with their actual readings.

    Instruction book

    2920 1822 00 35

  • 2.9 Event history menu

    Control panel

    (1) Scroll keys(2) Enter key(3) Escape key

    Menu icon, Event History

    Function

    To call up the last shut-down and last emergency stop data.

    Procedure

    Starting from the Main screen (see Main screen),

    • Move the cursor to the action button Menu and press the Enter key. Following screen appears:

    • Using the Scroll keys, move the cursor to the Event History icon (see above, section Menu icon)

    Instruction book

    36 2920 1822 00

  • • The list of last shut-down and emergency stop cases is shown.• Scroll through the items to select the desired shut-down or emergency stop event.• Press the Enter key to find the date, time and other data reflecting the status of the compressor when that

    shut-down or emergency stop occurred.

    2.10 Modifying settings

    Control panel

    (1) Scroll keys(2) Enter key(3) Escape key

    Menu icon, Settings

    Function

    To display and modify a number of settings (e.g. Network settings, General settings, ...)

    Procedure

    Starting from the Main screen (see Main screen),

    • Move the cursor to the action button Menu and press the Enter key. Following screen appears:

    Instruction book

    2920 1822 00 37

  • • Using the Scroll keys, move the cursor to the Settings icon (see above, section menu icon).• Press the Enter key. Following screen appears:

    • The screen shows a number of icons:

    Icon FunctionNetwork settings

    General settings

    Dryer

    Automatic restart after voltage failure settings

    Access key

    User password

    Instruction book

    38 2920 1822 00

  • Icon FunctionMain chart

    • Move the cursor to the icon of the function to be modified and press the Enter key.

    Modifying network settings

    • Select the network settings icon as described above and press the Enter button (2). Following screenappears:

    Text on figure

    (1) Network(2) Ethernet(3) CAN

    • A selection bar is covering the first item (CAN). Use the ↓ key of the Scroll keys to select the setting tobe modified and press the Enter key. Following screen appears:

    Screen for CAN settings

    Instruction book

    2920 1822 00 39

  • Screen for Ethernet settings

    .• Press the Enter button; a selection bar is covering the first item (Ethernet).• Using the Scroll keys, move the cursor to the setting to be modified (e.g. Ethernet) and press the Enter

    button (2).• A pop-up screen appears. Use the ↑ or ↓ key to select the required parameter and press the Enter key to

    confirm.

    General settings

    • Select the General settings icon as described above and press the Enter button (2). Following screenappears:

    Text on figure

    (1) General(2) Language in use(3) Time(4) Date(5) Date format

    • The screen shows the first items of a list of all settings. Use the scroll button the see the other items in thelist.

    • Press the Enter button (2); a selection bar is covering the first item (Language in use).

    Instruction book

    40 2920 1822 00

  • Use the ↓ key of the Scroll keys to select the setting to be modified and press the Enter key.• A pop-up screen appears. Use the ↑ or ↓ key to select the required parameter and press the Enter key to

    confirm.

    Dryer settings

    • Select the Dryer settings icon as described above and press the Enter button (2). Following screen appears:

    Text on figure

    (1) Regulation(2) Dryer operation mode(3) Flow switch mode(4) Dewpoint alarm mode(5) Variable dewpoint alarm offset

    • The screen shows the first items of a list of all settings. Use the scroll button to see the other items in thelist.

    • Press the Enter button (2); a selection bar is covering the first item (Dryer operation mode).Use the ↓ key of the Scroll keys to select the setting to be modified and press the Enter key.

    • A pop-up screen appears. Use the ↑ or ↓ key to select the required parameter and press the Enter key toconfirm.

    It is possible to program three operation modes:

    • ‘Economy’: the set-point for the pressure dew-point is ambient temperature minus 68 °F (20 ̊ C) (minimumset-point is 37 °F (3 ˚C)).

    • ‘Lowest Dewp.’: the set-point for the pressure dew-point is 37 °F (3 ˚C) regardless of the ambienttemperature.

    • ‘Max. Saving’: the set-point for the pressure dew-point is ambient temperature minus 59 °F (15 ˚C)(minimum set-point is 39 °F (4 ˚C)).

    Automatic restart

    • Select the Automatic restart settings icon as described above and press the Enter button (2). Followingscreen appears:

    Instruction book

    2920 1822 00 41

  • Text on figure

    (1) Automatic restart(2) Maximum power down time(3) Restart delay

    • The screen shows the list of all settings.• Press the Enter button (2); a selection bar is covering the first item (Automatic restart).

    Use the ↓ key of the Scroll keys to select the setting to be modified and press the Enter key.• A pop-up screen appears. Use the ↑ or ↓ key to select the required parameter and press the Enter key to

    confirm.

    Access key

    Different security levels are programmed in the controller (e.g. user, service technician, etc). This menu item is used to change the security level. Scroll to the correct icon using the scroll key. Press the enter button. Press the enter button again to modify the security level. Press the enter button again; a pop-up menu appears. Use the scroll keys to enter the password of the new security level. Press the enter key to confirm the change.

    User password

    If the password option is activated, it is impossible for not authorized persons to modify any setting.

    • Using the Scroll keys, move the cursor to the Password icon.• Press the Enter key.• Select the Modify button using the Scroll keys and press the Enter key. Next, modify the password as

    required.

    Main chart settings

    The main chart settings menu allows to adjust the scale and lines on the graph. To modify these settings,proceed as follows:

    • Select the Main chart settings icon as described above and press the Enter button (1). Following screenappears:

    Instruction book

    42 2920 1822 00

  • Text on figure

    (1) Main chart(2) Main chart signal(3) Chart range(4) Minimum(5) Maximum(6) Chart band(7) Low(8) High(9) Off

    The screen shows the main chart signal, the actual settings of the chart range and the chart band. To modifythese settings, proceed as follows:

    • Press the Enter key; the first item, chart range, becomes highlighted.• Press the Enter key to modify the chart range or press the arrow down key to modify the chart band.

    Modifying the chart range

    Select the chart range as described above and proceed as follows:

    • Press the enter key; the minimum setting becomes highlighted. Press the enter key to modify the minimumsetting or use the arrow down key to modify the maximum setting.

    • Press the enter key to accept the modification.

    Modifying the chart band

    Select the chart band as described above and proceed as follows:

    • Press the enter key; the low band setting becomes highlighted. Press the enter key to modify the on/offsetting or use the arrow down key to modify the low setting.

    • Press the enter key to accept the modification.• Proceed in the same way to modify the high band settings.

    Instruction book

    2920 1822 00 43

  • 2.11 Info menu

    Control panel

    (1) Scroll keys(2) Enter key(3) Escape key

    Menu icon, Info

    Function

    To show the internet address.

    Procedure

    Starting from the Main screen (see Main screen),

    • Move the cursor to the action button Menu and press the Enter key. Following screen appears:

    • Using the Scroll keys, move the cursor to the Info icon (see above, section Menu icon).

    Instruction book

    44 2920 1822 00

  • • Press the Enter key. The internet address appears on the screen.

    2.12 Week timer menu

    Control panel

    (1) Scroll keys(2) Enter key(3) Escape key

    Menu icon, Week timer

    Function

    • To program time-based start/stop commands for the dryer• Four different week schemes can be programmed.• A week cycle can be programmed (a week cycle is a sequence of 10 weeks). For each week in the cycle,

    one of the four programmed week schemes can be chosen.

    Procedure

    Starting from the Main screen (see Main screen),

    • Move the cursor to the action button Menu and press the Enter key. Use the Scroll buttons to select theTimer icon.

    • Press the Enter key on the controller. Following screen appears:

    Instruction book

    2920 1822 00 45

  • (1) Week Timer(2) Week Action Schemes(3) Week Cycle(4) Status(5) Week Timer Inactive(6) Remaining Running Time

    The first item in this list is highlighted. Select the item requested and press the Enter key on the controllerto modify.

    Programming week schemes

    • Select Week action schemes and press Enter. A new window opens. The first item in the list is highlighted.Press the Enter key on the controller to modify Week Action Scheme 1.

    (1) Week Action Schemes(2) Week Action Scheme 1(3) Week Action Scheme 2(4) Week Action Scheme 3(5) Week Action Scheme 4

    • A weekly list is shown. Monday is automatically selected and highlighted. Press the Enter key on thecontroller to set an action for this day.

    Instruction book

    46 2920 1822 00

  • (1) Week Action Scheme 1(2) Monday(3) Tuesday(4) Wednesday(5) Thursday(6) Friday(7) Saturday(8) Sunday

    • A new window opens. The Modify action button is selected. Press the enter button on the controller tocreate an action.

    (1) Monday(2) Modify

    • A new pop-up window opens. Select an action from this list by using the Scroll keys on the controller.When ready press the Enter key to confirm.

    • A new window opens. The action is now visible in the first day of the week.

    Instruction book

    2920 1822 00 47

  • (1) Monday(2) Start(3) Save(4) Modify

    • To adjust the time, use the Scroll keys on the controller and press the Enter key to confirm.

    (1) Monday(2) Start(3) Save(4) Modify

    • A pop-up window opens. Use the ↑ or ↓ Scroll keys to modify the values of the hours. Use the ← or →Scroll keys to modify the minutes.

    (1) Monday(2) Time(3) Save(4) Modify

    • Press the Escape key on the controller. The action button Modify is selected. Use the Scroll keys to selectthe action Save.

    Instruction book

    48 2920 1822 00

  • (1) Monday(2) Start(3) Save(4) Modify

    • A new pop-up window opens. Use the Scroll keys on the controller to select the correct actions. Press theEnter key to confirm.

    (1) Monday(3) Are you sure?(4) No(5) Yes(6) Save(7) Modify

    Press the Escape key to leave this window.• The action is shown below the day the action is planned.

    (1) Week Action Scheme 1

    Instruction book

    2920 1822 00 49

  • (2) Monday - Start(3) Tuesday(4) Wednesday(5) Thursday(6) Friday(7) Saturday(8) Sunday

    Press the Escape key on the controller to leave this screen.

    Programming the week cycle

    A week cycle is a sequence of 10 weeks. For each week in the cycle, one of the four programmed weekschemes can be chosen.

    • Select Week Cycle from the main Week Timer menu list.

    (1) Week Timer(2) Week Action Schemes(3) Week Cycle(4) Status(5) Week Timer Inactive(6) Remaining Running Time

    • A list of 10 weeks is shown.

    (1) Week Cycle(2) Week 1(3) Week 2

    Instruction book

    50 2920 1822 00

  • (4) Week 3(5) Week 4(6) Modify

    Press twice the Enter key on the controller to modify the first week.• A new window opens. Select the action, example: Week Action Scheme 1

    (1) Week Cycle(2) Week 1(3) Week Action Scheme 1(4) Week Action Scheme 2(5) Week Action Scheme 3(6) Modify

    • Check the status of the Week TimerUse the Escape key on the controller to go back to the main Week Timer menu. Select the status of theWeek Timer.

    (1) Week Timer(2) Week Action Schemes(3) Week Cycle(4) Status(5) Week Timer Inactive(6) Remaining Running Time

    • A new window opens. Select Week 1 to set the Week Timer active.

    Instruction book

    2920 1822 00 51

  • (1) Week Timer(2) Week(3) Week Timer Inactive(4) Week 1

    • Press the Escape key on the controller to leave this window. The status shows that week 1 is active.

    (1) Week Timer(2) Week Action Schemes(3) Week Cycle(4) Status(5) Remaining Running Time

    • Press the Escape key on the controller to go to the main Week Timer menu. Select Remaining RunningTime from the list and press the Enter key on the controller to Modify.

    Instruction book

    52 2920 1822 00

  • (1) Week Timer(2) Week Action Schemes(3) Week Cycle(4) Status(5) Remaining Running Time

    • This timer is used when the week timer is set and for certain reasons the compressor must continue working,for example, for 1 hour, this can be set in this screen. This timer is prior to the Week Timer action.

    (1) Week Timer(2) Week action schemes(3) Remaining Running Time

    2.13 Test menu

    Control panel

    Instruction book

    2920 1822 00 53

  • Menu icon, Test

    Function

    • To test the electronic water drain.

    Procedure

    Starting from the Main screen (see Main screen):

    • Move the cursor to the action button Menu and press the enter key (2); following screen appears:

    • Using the scroll keys (1), move the cursor to the test icon (see above, section Menu icon)• Press the enter key (2); following screen appears:

    • A selection bar is covering the item drain test; press the enter key. A screen is shown to start draining orto modify the manual drain time. Select the desired option and press the enter button (2).• In case the drain test was chosen, the automatic drain will be opened for the time specified in the manual

    drain time function.• In case the manual drain time was chosen, a pop-up window appears. Use the up and down buttons (1)

    to modify the value as required.

    Instruction book

    54 2920 1822 00

  • 2.14 Service menu

    Control panel

    (1) Scroll keys(2) Enter key(3) Escape key

    Menu icon, Service

    Function

    • To reset the service plans which are carried out.• To check when the next service plans are to be carried out.• To find out which service plans were carried out in the past.• To modify the programmed service intervals.

    Procedure

    Starting from the Main screen (see Main screen),

    • Move the cursor to the action button Menu and press the Enter key. Following screen appears:

    Instruction book

    2920 1822 00 55

  • • Using the Scroll keys, move the cursor to the Service icon (see above, section Menu icon).• Press the Enter key. Following screen appears:

    Text on figure

    (1) Service(2) Overview(3) Service plan(4) Next service(5) History

    • Scroll through the items to select the desired item and press the Enter key to see the details as explainedbelow.

    Instruction book

    56 2920 1822 00

  • Overview

    Text on figure

    (1) Overview(2) Running Hours (green)(3) Real Time hours (blue)

    Example for service level (A):

    The figures at the left are the programmed service intervals. For Service interval A, the programmed numberof running hours is 4000 hours (upper row, green) and the programmed number of real time hours is 4000hours, which corresponds to six months (second row, blue). This means that the controller will launch a servicewarning when either 4000 running hours or 4000 real hours are reached, whichever comes first. Note that thereal time hours counter keeps counting, also when the controller is not powered.

    The figures at the right are the number of hours to go till the next service intervention. In the example above,the compressor was just started up, which means it still has 4000 running hours or 3976 real time hours to gobefore the next Service intervention.

    Service plans

    A number of service operations are grouped (called Level A, Level B, etc...). Each level stands for a numberof service actions to be carried out at the time intervals programmed in the electronic controller.

    When a service plan interval is reached, a message will appear on the screen.

    After carrying out the service actions related to the indicated levels, the timers must be reset.

    From the Service menu above, select Service plan (3) and press Enter. Following screen appears:

    Instruction book

    2920 1822 00 57

  • Text on figure

    (1) Service plan(2) Level(3) Running hours(4) Real time hours

    Next Service

    Text on figure

    (1) Next service(2) Level(3) Running hours(4) Actual

    In the example above, the A Service level is programmed at 4000 running hours, of which 0 hours have passed.

    History

    The History screen shows a list of all service actions done in the past, sorted by date. The date at the top isthe most recent service action. To see the details of a completed service action (e.g. Service level, Runninghours or Real time hours), use the Scroll keys to select the desired action and press the Enter key.

    Instruction book

    58 2920 1822 00

  • 2.15 Protections menu

    Converter panel

    (1) Scroll keys(2) Enter key(3) Escape key

    Menu icon, Test

    Function

    • To call-up and to reset the protections.

    Before resetting a warning or shut down message, always remedy the problem. Frequentlyresetting these messages without remedying may damage the dryer.

    Procedure

    Starting from the Main screen (see Main screen):

    • Move the cursor to the action button Menu and press the enter key (2). Following screen appears:

    Instruction book

    2920 1822 00 59

  • • Using the scroll keys (1), move the cursor to the protections icon (see above, section Menu icon)• Press the enter key (2). Following screen appears:

    • The screen shows a list of all shut-down and shut-down warning settings and the actual reading. In caseof shut-down, the protection can be reset after remedying.

    2.16 Extra menu

    Control panel

    Instruction book

    60 2920 1822 00

  • (1) Scroll keys(2) Enter key(3) Escape key

    Menu icon, Test

    Function

    • To call-up the actual readings for the pressure dewpoint, the relative humidity and the LAT setpoint.

    Procedure

    Starting from the Main screen (see Main screen):

    • Move the cursor to the action button Menu and press the enter key (2). Following screen appears:

    • Using the scroll keys (1), move the cursor to the Extra icon (see above, section Menu icon)• Press the enter key (2). A screen showing the actual readings for the pressure dewpoint, the relative

    humidity and the LAT setpoint appears.

    Instruction book

    2920 1822 00 61

  • 2.17 Web serverThe controllers have a built-in web server that allows direct connection to a PC via a local area network (LAN).This allows to consult certain data and settings via the PC instead of via the display of the controller.

    Getting started

    Make sure you are logged in as administrator.

    • Use the internal network card from your computer or an USB to LAN adapter (see picture below).

    USB to LAN adapter

    • Use an UTP cable (CAT 5e) to connect to the controller (see picture below).

    Configuration of the network card

    • Go to My Network places (1).

    Instruction book

    62 2920 1822 00

  • • Click on View Network connections (1).

    • Select the Local Area connection (1), which is connected to the controller.

    • Click with the right button and select properties (1).

    Instruction book

    2920 1822 00 63

  • • Use the checkbox Internet Protocol (TCP/IP) (1) (see picture). To avoid conflicts, de-select other propertiesif they are selected. After selecting TCP/IP, click on the Properties button (2) to change the settings.

    • Use the following settings:• IP Address 192.168.100.200• Subnetmask 255.255.255.0Click OK and close network connections.

    Configuration of the web server

    Configure the web interface

    The internal web server is designed and tested for Microsoft® Internet Explorer 6, 7 and8. Other web browsers like Opera and Firefox do not support this internal web server.When using Opera or Firefox, a redirect page opens. Click on the hyperlink to connect tothe download server from Microsoft® to download the latest version of Internet Explorer,and install this software.

    • When using Internet Explorer:Open Internet Explorer and click on Tools - Internet options (2).

    Instruction book

    64 2920 1822 00

  • • Click on the Connections tab (1) and then click on the LAN settings button (2).

    • In the Proxy server Group box, click on the Advanced button (1).

    Instruction book

    2920 1822 00 65

  • • In the Exceptions Group box, enter the IP address of your controller. Multiple IP addresses can be givenbut they must be separated with semicolons (;).Example: Suppose that you already added two IP addresses (192.168.100.1 and 192.168.100.2). Now youadd 192.168.100.100 and separate the 3 IP addresses by putting semicolons between them (1) (see picture).Click OK (2) to close the window.

    Viewing the controller data

    • Open your browser and type the IP address of the controller you want to view in your browser (in thisexample http://192.168.100.100). The interface opens and shows the dryer data.

    Navigation and options

    • The banner shows the compressor type and the language selector. In this example, three languages areinstalled on the controller.

    Instruction book

    66 2920 1822 00

  • • On the left side of the interface the navigation menu can be found.If a license for ESi is foreseen, the menu contains 3 buttons.• Dryer: shows all dryer settings.• ES: shows the ESi status (if a license is provided).• Preferences: allows to change temperature and pressure unit.

    Dryer settings

    All settings can be hidden or shown. Put a mark for each setting. Only the machine status is fixed and can notbe removed from the main screen.

    • Analog inputs (the units of measure can be changed in the preference button from the navigation menu).• Counters: give an overview of all actual counters from controller and dryer.• Info status: the machine status is always shown on the web interface.• Digital inputs: gives an overview of all Digital inputs and their status.• Digital outputs: shows a list of all digital outputs and their status.• Special protections: give an overview of all special protections of the compressor.• Service plan: shows all levels of the service plan and status. This screen only shows the running hours. It

    is also possible to show the actual status of the service interval.• ES screen controller: if an ESi license is provided, the button ES is shown in the navigation menu. At the

    left all compressors in the ES and at the right the ES status is shown.

    2.18 Programmable settings

    Settings

    The regulating and safety devices are factory-adjusted to obtain optimum performance of the dryer. Noadjustments are required.

    Instruction book

    2920 1822 00 67

  • 3 Installation

    3.1 Dimension drawings

    Dimensions

    Dimension drawing of QED 1250

    Instruction book

    68 2920 1822 00

  • Dimension drawing of QED 1600

    Instruction book

    2920 1822 00 69

  • Dimension drawing of QED 1800

    Instruction book

    70 2920 1822 00

  • Dimension drawing of QED 2100

    Reference Description(1) Compressed air inlet(2) Compressed air outlet(3) Automatic drain, flexible drain pipe ø 8 mm (or ø 12 mm for units from production date

    07/16/2012) - length = 2000 mmAutomatic drain, Flexible drain pipe Ø 0.47", Length = 79"

    (4) Electrical connection, cable gland M32

    Instruction book

    2920 1822 00 71

  • Reference Description(5) Cooling air out(6) Cooling air in(7) Air-cooled dryer type(8) Ambient(9) Net mass, approx.(10) Flanges

    Instruction book

    72 2920 1822 00

  • 3.2 Installation proposal

    Example

    Installation proposal for QED 650-2100 (in inch)

    Instruction book

    2920 1822 00 73

  • Installation proposal, by-pass pipe and valve

    Reference Description1 The air dryer should be installed on a level floor suitable for taking its weight.2a A general-purpose filter which traps solid particles down to 1 micron with a max. oil carry-

    over of 0.1 mg/m3 (0.1 ppm) can be installed.2c A high-efficiency filter, may be installed downstream of the refrigerant dryer. This filter traps

    particles down to 0.01 micron with a max. oil carry-over of 0.01 mg/m3 (0.01 ppm).3 Air receiver with condensate drain.4 Pressure gauge5 Condensate drain6 Dryer outlet valve7 By-pass system8 By-pass valve9 Dryer inlet valve10 Electronic water drain (EWD)

    Instruction book

    74 2920 1822 00

  • 3.3 Installation instructions

    Procedure

    Item ActionDryer • The unit should be installed on a level floor capable of taking the weight of the dryer.

    • Distances between units and walls stated are minimum.Ventilation For air-cooled dryer:

    • Provide free space above the dryer.• The inlet grid(s) (1) and ventilation fan (2) (if provided) should be installed in such a

    way that any recirculation of cooling air to the dryer is avoided.• The required ventilation to limit the dryer room temperature is noted in the table below.• The air velocity to the grid(s) has to be limited to 5 m/s (16.405 ft/s).• Install the dryer where the ambient air is as clean as possible and where the

    temperature of the air will never exceed the limits: minimum air temperature at thedryer cooling opening of 0 ˚C (32 ˚F), maximum air temperature at the dryer coolingopening: 40 ˚C (104 ˚F).

    • Keep the ventilation gratings of the dryer free. If necessary, take action to avoidexternal influences (wind, draughts, etc.) through the ventilation gratings of the dryer,as they may disturb the cooling air flow.

    For the reference of components, see section Installation proposal.

    The required ventilation to limit the dryer room temperature

    Dryer m3/h (50Hz) m3/h (60Hz)QED 1250 5200 5700QED1600 6800 7800QED 1800 9000 9200QED 2100 11000 12000

    Instruction book

    2920 1822 00 75

  • Item ActionAir • Connect the compressed air lines to the marked inlet and outlet pipes of the dryer.

    • Provide an air inlet valve and outlet valve.• If a by-pass pipe and valve are installed, the dryer can be serviced while being by-

    passed.Drain pipes • Each drain pipe must be individually connected to the waste pipe.

    • Lay out the condensate drain pipes via a funnel towards the waste pipe to allow visualinspection. The pipes must slope downwards. For draining of pure condensate, installan oil/water separator; consult your customer centre.

    • If the condensate drain pipes have been fitted outside the compressor room wherethey may be exposed to freezing temperatures, they must be insulated.

    Electricalconnection

    • Check that the primary side connections of transformer (T1) correspond with thesupply voltage.

    • See the section Electric cable size and fuses for the recommended fuses and cablesize of the supply cables.

    • Check that the electrical installation corresponds to the local codes. The dryer mustbe earthed and protected against short circuits by fuses of the inert type in all phases.

    • An isolating switch must be installed near the dryer.• The unit is provided with a phase sequence relay. When the dryer does not start, switch

    off the voltage and reverse two incoming electric lines.

    • All pipes should be installed stress-free to the dryer unit.• All pipes should be installed so that there is no obstruction accessing the unit through the

    removable panels.

    3.4 Electric cable size and fuses

    Important

    Local regulations remain applicable if they are stricter than the values proposed.For 50 Hz dryers, the settings of the main fuses below are according to Directive 73/23/EEC(low-voltage directive) EN60204, 83/336/EC electromagnetic compatibility. The cable size isvalid for cable PVC 70 ˚C (158 ˚F) at an ambient temperature of 40 ˚C (104 ˚F).For 60 Hz dryers, the settings of the main fuses below are according to CSA standards C22.2Nos. 0; 0.4; 0.5; 0.12; 14; 68 and UL508. The cable size is valid for cable 90 ˚C (194 ˚F) atan ambient temperature of 40 ˚C (104 ˚F).

    CSA

    Dryer type/approval Network Fuses(A)

    Fuse type Cable sizeAWG

    Maximumcabletemperature(°C/°F)

    QED 1250 TT/TN 3x50 HRC Form II 10 90/194QED 1600 TT/TN 3x50 HRC Form II 10 90/194QED 1800 TT/TN 3x60 HRC Form II 8 90/194QED 2100 TT/TN 3x60 HRC Form II 8 90/194QED 1250 IT 3x25 HRC Form II 10 90/194

    Instruction book

    76 2920 1822 00

  • Dryer type/approval Network Fuses(A)

    Fuse type Cable sizeAWG

    Maximumcabletemperature(°C/°F)

    QED 1600 IT 3x25 HRC Form II 10 90/194QED 1800 IT 3x25 HRC Form II 10 90/194QED 2100 IT 3x25 HRC Form II 10 90/194

    UL

    Dryer type/approval Network Fuses(A)

    Fuse type Cable sizeAWG

    Maximumcabletemperature(°C/°F)

    QED 1250 TT/TN 3x50 HRC Form II 10 90/194QED 1600 TT/TN 3x50 HRC Form II 10 90/194QED 1800 TT/TN 3x60 HRC Form II 8 90/194QED 2100 TT/TN 3x60 HRC Form II 8 90/194QED 1250 IT 3x25 HRC Form II 10 90/194QED 1600 IT 3x25 HRC Form II 10 90/194QED 1800 IT 3x25 HRC Form II 10 90/194QED 2100 IT 3x25 HRC Form II 10 90/194

    3.5 Pictographs

    Explanation of pictographs

    Reference Name1 Disconnect from electrical supply before opening2 Warning, voltage3 Cooling water outlet

    (Only for water-cooled dryers)

    Instruction book

    2920 1822 00 77

  • Reference Name4 Cooling water inlet

    (Only for water-cooled dryers)5 Maximum air inlet temperature of 70 ˚C (158 ˚F)6 Switch off and depressurize the dryer before starting maintenance or repair7 Compressed air inlet8 Dry air outlet9 Automatic condensate drain

    Instruction book

    78 2920 1822 00

  • 4 Operating instructions

    4.1 Warnings

    Safety precautions

    The operator must apply all relevant safety precautions, including those mentioned in this manual.

    Altitude operation

    Consult your supplier if operating above 3000 m (9843 ft).

    4.2 Initial start

    Control panel

    Description

    Step Action1 At least 10 minutes before starting, the main supply to the dryer must be switched on to

    initialize the electronic controller and flow switch.2 Press start button (14).

    • Three-phase units are provided with a phase sequence relay. When the dryercompressor motor does not start, switch off the voltage and reverse two incomingelectric lines.

    For air-cooled versions: Check the rotation direction of the fan motor(s). The correctrotation direction is indicated by an arrow next to each fan. If incorrect, switch off thevoltage and reverse two of the three phase connections.Check the rotation direction of the fan motor(s). The correct rotation direction is indicatedby an arrow next to each fan. If incorrect, switch off the voltage and reverse two of thethree phase connections.

    Instruction book

    2920 1822 00 79

  • 4.3 Starting

    Control panel

    Description

    Step Action- At least 10 minutes before starting, the main supply to the dryer must be switched on to

    initialize the electronic controller and flow switch.- Close the dryer by-pass valve, if installed.- Press start button (14).- Open the dryer air inlet valve (customer's installation).- Approx. 5 minutes later, open the dryer air outlet valve (customer's installation).- Approx. 10 minutes later, the nominal dew-point will be reached.

    Instruction book

    80 2920 1822 00

  • 4.4 During operation

    Control panel

    Description

    Regularly check:

    • The pressure dew-point on the display of the control panel. The pressure dew-point will deviate fromnominal if the air inlet conditions or volume flow differ from nominal.

    • That condensate is discharged. The amount depends on the operating conditions.

    4.5 Stopping

    Control panel

    Instruction book

    2920 1822 00 81

  • Procedure

    Step Action1 Close dryer inlet and outlet valves (customer's installation).2 Press stop button (13). The dryer stops. Voltage on LED (8) remains lit. Leave the voltage

    on if the dryer has to remain on stand-by.

    Instruction book

    82 2920 1822 00

  • 5 Maintenance

    5.1 Maintenance instructions

    Important

    The dryers contain refrigerant HFC.When the automatic operation LED is lit, starting and stopping of the dryer are controlledautomatically.If the dryer start/stop timer is active, the dryer may start automatically, even if it was stoppedmanually.

    Safety precautions

    When handling refrigerant R410a, all applicable safety precautions must be observed. The followingpoints are stressed:

    • Contact of refrigerant with the skin will cause freezing. Special gloves must be worn and, if there is contactwith the skin, the skin should be rinsed with water. On no account may clothing be removed.

    • Fluid refrigerant will also cause freezing of the eyes; therefore, safety glasses must be worn.• Refrigerant R410a is poisonous. Do not inhale refrigerant vapors. Check that the working area is

    adequately ventilated.

    When removing the side panels of the dryer, be aware that internal elements such as the pipes can reach atemperature of 120 ˚C (248 ˚F). Therefore, wait until the dryer has cooled down before removing the sidepanels.

    Before starting any maintenance or repairs, switch off the voltage. Isolate the dryer from the air net anddepressurize by opening valve (5) on inlet collector (6).

    Valve on the inlet collector (air-cooled)

    Local legislation

    Local legislation may impose that:

    Instruction book

    2920 1822 00 83

  • • Work on the refrigerant circuit of the cooling dryer or on any equipment which influences its functionmust be carried out by an authorized control body.

    • The installation should be checked once a year by an authorized control body.

    Warranty and product liability

    Use only authorized genuine parts. Any damage or malfunction caused by the use of unauthorized parts is notcovered by Warranty or Product Liability.

    Service agreements

    Customer Centres have a range of service agreements to suit your needs:

    • An Inspection Plan.• A Preventive Maintenance Plan.• A Total Responsibility Plan.

    Contact your Customer Centre to arrange a tailor-made service agreement. This will ensure optimumoperational efficiency, minimize downtime and reduce the total life cycle costs.

    General

    The following remarks should be kept in mind:

    • Keep the dryer clean.• Brush or blow off the finned surface of the condenser regularly.• Inspect and clean the Electronic Water Drain (EWD) once a year .

    Instruction book

    84 2920 1822 00

  • 6 Problem solving

    6.1 Problem solving

    Valve on inlet collector

    Valve on the inlet collector (air-cooled)

    Attention

    Use only authorized parts. Any damage or malfunction caused by the use of unauthorizedparts is not covered by Warranty or Product Liability.Apply all relevant Safety precautions.Before carrying out any maintenance or repairs on the dryer, stop the dryer and switch offthe voltage.Open the isolating switch to prevent an accidental start.Isolate the dryer from the air net and depressurize by opening valve (5) on inlet collector(6).

    Faults and remedies (general)

    Condition Fault Remedy- Pressure dew-point too high Air inlet temperature too high Check and correct; if necessary,

    install a pre-coolerAmbient temperature too high Check and correct; if necessary, draw

    cooling air via a duct from a coolerplace or relocate dryer

    Air inlet pressure too low Increase inlet pressureDryer capacity exceeded Reduce air flowShortage of refrigerant Have circuit checked for leaks and

    rechargedRefrigerant compressor doesnot run

    See below

    Instruction book

    2920 1822 00 85

  • Condition Fault RemedyEvaporator pressure too high See belowCondenser pressure too high See belowAutomatic drain systemclogged

    Have the system cleaned

    - Condenser pressure too highor too low on air-cooled dryers

    Fan control switch out of order Replace

    Fan or fan motor out of order Check fan/fan motorAmbient temperature too high Check and correct; if necessary, draw

    cooling air via a duct from a coolerplace or relocate dryer

    Condenser externally clogged Clean condenser- Compressor stops or does not

    startElectric power supply tocompressor is interrupted

    Check and correct as necessary

    Motor overload protection ofrefrigerant compressor motorhas tripped

    Have motor checkedFor resetting: see the sectionElectrical system

    High-pressure switch tripped See above- Condensate drain remains

    inoperativeAutomatic drain systemclogged

    Flush the assembly by openingmanual drain valve.Have system inspected

    - Condensate trap continuouslydischarges air and water

    Automatic drain system out oforder

    Have system checked. If necessaryreplace automatic drain

    - Evaporator pressure is too highor too low at unload

    Hot-gas by-pass valveincorrectly set or out of order

    Have hot-gas by-pass valve adjusted

    Condenser pressure too highor too low

    See above

    Shortage of refrigerant Have circuit checked for leaks andrecharged

    Instruction book

    86 2920 1822 00

  • 7 Technical data

    7.1 Reference conditions and limitations

    Reference conditions

    UnitVolume Flow 1,2 l/s 610

    Volume Flow 1,2 cfm 1292.52

    Volume Flow 1,2 l/s 760

    Volume Flow 1,2 cfm 1610.35

    Volume Flow 1,2 l/s 870

    Volume Flow 1,2 cfm 1843.43

    Volume Flow 1,2 l/s 1010

    Volume Flow 1,2 cfm 2140.07

    Compressed air inlet pressure bar(e) 7Compressed air inlet pressure psig 101.53Compressed air inlet temperature See dryer dataAmbient temperature ˚C See dryer dataInlet relative humidity of compressed air % 100

    1 Referred to absolute pressure of 1 bar and temperature of 20°C and measured according to ISO 71832 At other working conditions, see AHB 2933187000 - Tab 17.

    Limits

    UnitMaximum compressed air inlet pressure bar(e) 14Maximum compressed air inlet pressure psig 203.05Minimum-maximum ambient air temperature ˚C 0-40Minimum-maximum ambient air temperature ˚F 32-104Maximum compressed air inlet temperature ˚C 50Maximum compressed air inlet temperature ˚F 122

    Instruction book

    2920 1822 00 87

  • 7.2 Air dryer data

    Important note

    The values below are valid at reference conditions, unless otherwise stated, the inletconditions are specified at the inlet grating. See the section Reference conditions.

    Air-cooled 60 Hz

    Performance data

    Unit QED1250

    QED1600

    QED1800

    QED2100

    Pressure dewpoint air outlet

    • Ambient air temperature 38 °CCompressed air inlet temperature 38 °C

    °C 3 4 4 4

    • Ambient air temperature 100 °FCompressed air inlet temperature 100 °F

    °F 37.4 39.2 39.2 39.2

    • Ambient air temperature 25 °CCompressed air inlet temperature 35 °C

    °C 3 3 3 3

    • Ambient air temperature 77 °FCompressed air inlet temperature 95 °F

    °F 37.4 37.4 37.4 37.4

    • Ambient air temperature 30 °CCompressed air inlet temperature 40 °C

    °C 3 5 5 5

    • Ambient air temperature 86 °FCompressed air inlet temperature 104 °F

    °F 37.4 41.0 41.0 41.0

    • Ambient air temperature 35 °CCompressed air inlet temperature 45 °C

    °C 10 10 10 10

    • Ambient air temperature 95 °FCompressed air inlet temperature 113 °F

    °F 50.0 50.0 50.0 50.0

    • Ambient air temperature 40 °CCompressed air inlet temperature 50 °C

    °C 17 18 17 17

    • Ambient air temperature 104 °FCompressed air inlet temperature 122 °F

    °F 62.6 64.4 62.6 62.6

    Total electrical power input

    • Ambient air temperature 38 °CCompressed air inlet temperature 38 °C

    kW 7.6 8.1 10.2 11.9

    • Ambient air temperature 100 °FCompressed air inlet temperature 100 °F

    hp 10.2 10.9 13.7 16.0

    • Ambient air temperature 25 °CCompressed air inlet temperature 35 °C

    kW 5.8 6.3 8.2 9.0

    • Ambient air temperature 77 °FCompressed air inlet temperature 95 °F

    hp 7.8 8.5 11.0 12.1

    • Ambient air temperature 30 °CCompressed air inlet temperature 40 °C

    kW 6.7 7.1 9.2 10.4

    • Ambient air temperature 86 °FCompressed air inlet temperature 104 °F

    hp 9.0 9.5 12.3 14.0

    Instruction book

    88 2920 1822 00

  • Unit QED1250

    QED1600

    QED1800

    QED2100

    • Ambient air temperature 35 °CCompressed air inlet temperature 45 °C

    kW 7.6 8.0 10.3 11.9

    • Ambient air temperature 95 °FCompressed air inlet temperature 113 °F

    hp 10.2 10.7 13.8 16.0

    • Ambient air temperature 40 °CCompressed air inlet temperature 50 °C

    kW 8.5 9.2 11.6 13.8

    • Ambient air temperature 104 °FCompressed air inlet temperature 122 °F

    hp 11.4 12.3 15.6 18.5

    Fan(s) electrical power input kW 0.71 1.11 1.48 1.42Fan(s) electrical power input hp 0.95 1.49 1.98 1.90Cooling air flow (approx.) l/s 1583 2167 2556 3333Cooling air flow (approx.) cfm 3354 4592 5416 7062Heat dissipated by cooling medium flow (approx.)

    • Ambient air temperature 38 °CCompressed air inlet temperature 38 °C

    kW 18 22 26 30

    • Ambient air temperature 100 °FCompressed air inlet temperature 100 °F

    hp 24.1 29.5 34.9 40.2

    • Ambient air temperature 25 °CCompressed air inlet temperature 35 °C

    kW 15 18 22 25

    • Ambient air temperature 77 °FCompressed air inlet temperature 95 °F

    hp 20.1 24.1 29.5 33.5

    • Ambient air temperature 30 °CCompressed air inlet temperature 40 °C

    kW 19 22 26 30

    • Ambient air temperature 86 °FCompressed air inlet temperature 104 °F

    hp 25.5 29.5 34.9 40.2

    • Ambient air temperature 35 °CCompressed air inlet temperature 45 °C

    kW 22 26 31 36

    • Ambient air temperature 95 °FCompressed air inlet temperature 113 °F

    hp 29.5 34.9 41.6 48.3

    • Ambient air temperature 40 °CCompressed air inlet temperature 50 °C

    kW 26 31 37 43

    • Ambient air temperature 104 °FCompressed air inlet temperature 122 °F

    hp 34.9 41.6 49.6 57.7

    Design data

    Unit QED1250

    QED1600

    QED1800

    QED2100

    Pressure drop over dryer 1 bar 0.17 0.17 0.15 0.17

    Pressure drop over dryer 1 psi 2.47 2.47 2.18 2.47

    Refrigerant type R410a R410a R410a R410aRefrigerant amount kg 2.9 3.9 4.5 5.5Refrigerant amount lb 6.39 8.6 9.92 12.13

    Mean sound pressure level 2 dB(A) 64 64 64 64

    Length mm 1040 1245 1245 1580

    Instruction book

    2920 1822 00 89

  • Unit QED1250

    QED1600

    QED1800

    QED2100

    Length in 40.95 49.02 49.02 62.21Width mm 1060 1060 1060 1060Width in 41.73 41.73 41.73 41.73Height mm 1430 1430 1430 1430Height in 5630 5630 5630 5630Net weight kg 320 380 400 460Net weight lb 705.5 837.8 881.9 1014

    1 At other working conditions, see AHB 2933187000 - Tab 17.2 A-weighted emission sound pressure level at the work station (LpWSAd). Measured according to ISO 2151:2004 using ISO 9614/2 (sound intensity method). A total correction factor for uncertainties of 3 dB has to beadded conform the test code. Possible noise from discharge line, accessories and/or anncillary equipment isnot included. For more information about noise levels, see printed matter 9780 0380 10, "Compressed AirManual 1998", Section 3.9.

    Instruction book

    90 2920 1822 00

  • 8 Pressure equipment directives

    Components subject to 97/23/EC Pressure Equipment Directive

    Components subject to 97/23/EC Pressure Equipment Directive greater than or equal to category II.

    Description PED ClassLiquid separator IIHigh-pressure switch IV

    Overall rating

    The dryers conform to PED category II.

    Instruction book

    2920 1822 00 91

  • Cod. 2920 1822 00 - Edition 09/2012 quincycompressor.com

    [email protected] | 217.222.7700

    mailto:[email protected]

    Table of contents1 General description1.1 IntroductionDescriptionGeneral viewPosition of componentsConnections

    1.2 Air systemAir flow diagramDescription

    1.3 Refrigeration systemRefrigerant flow diagramDescription

    1.4 Automatic regulation systemAir and refrigerant flow diagramDescription

    1.5 Condensate drain systemDescriptionTesting the Electronic water drain

    1.6 Electrical systemElectrical diagramsPosition of componentsDryer protection

    2 Air Logic regulator2.1 Air Logic regulatorControl panelGeneral descriptionControlling the dryerProtecting the dryerAutomatic restart after voltage failure

    2.2 Control panelAir Logic regulatorParts and functions

    2.3 Icons usedStatus iconsInput iconsSystem iconsMenu iconsNavigation arrows

    2.4 Main screenControl panelFunctionTwo and four value viewsChart views

    2.5 Calling up menusControl panelDescription

    2.6 Inputs menuControl panelMenu icon, InputsFunctionProcedure

    2.7 Outputs menuControl panelMenu icon, OutputsFunctionProcedure

    2.8 CountersControl panelMenu icon, CountersFunctionProcedure

    2.9 Event history menuControl panelMenu icon, Event HistoryFunctionProcedure

    2.10 Modifying settingsControl panelMenu icon, SettingsFunctionProcedureModifying network settingsGeneral settingsDryer settingsAutomatic restartAccess keyUser passwordMain chart settings

    2.11 Info menuControl panelMenu icon, InfoFunctionProcedure

    2.12 Week timer menuControl panelMenu icon, Week timerFunctionProcedureProgramming week schemesProgramming the week cycle

    2.13 Test menuControl panelMenu icon, TestFunctionProcedure

    2.14 Service menuControl panelMenu icon, ServiceFunctionProcedureOverviewService plansNext ServiceHistory

    2.15 Protections menuConverter panelMenu icon, TestFunctionProcedure

    2.16 Extra menuControl panelMenu icon, TestFunctionProcedure

    2.17 Web serverGetting startedConfiguration of the network cardConfiguration of the web serverDryer settings

    2.18 Programmable settingsSettings

    3 Installation3.1 Dimension drawingsDimensions

    3.2 Installation proposalExampleInstallation proposal, by-pass pipe and valve

    3.3 Installation instructionsProcedure

    3.4 Electric cable size and fusesImportantCSAUL

    3.5 PictographsExplanation of pictographs

    4 Operating instructions4.1 WarningsSafety precautionsAltitude operation

    4.2 Initial startControl panelDescription

    4.3 StartingControl panelDescription

    4.4 During operationControl panelDescription

    4.5 StoppingControl panelProcedure

    5 Maintenance5.1 Maintenance instructionsImportantSafety precautionsLocal legislationWarranty and product liabilityService agreementsGeneral

    6 Problem solving6.1 Problem solvingValve on inlet collectorAttentionFaults and remedies (general)

    7 Technical data7.1 Reference conditions and limitationsReference conditionsLimits

    7.2 Air dryer dataImportant noteAir-cooled 60 Hz

    8 Pressure equipment directivesComponents subject to 97/23/EC Pressure Equipment DirectiveOverall rating